Today Menu:
1. CDVR2. Introduction to Control Panels3. System Operation/Testing and
Adjusting• EMCP I (SENR3535 via SIS)
• EMCP I I+ (RENR1200 via SIS)
• EMCP I I I (RENR7902 via SIS)
4. TMI web
2
3
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Caterpillar Digital Voltage Regulator(CDVR)
Introduction and Specifications
Prepared by Service Traininghttps://psmktg.cat.com/srvtrng/
4
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Foreword
This presentation was prepared by Caterpillar Service Training to be a training overview of the CDVR for Caterpillar generator set service personnel. This presentation provides comparisons to the previous design, DVR, and includes information pertaining to the removal of a DVR and replacement with a new CDVR. As always, the proper service information for the regulators in SIS should be used for the latest specific details for operation, adjustments, programming and troubleshooting.
3
5
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Compatibility – Products Affected
The following product’s standard configuration or available options will be affected. The change will affect PMG generators that have the CDVR as standard or option. Generators that do not have an option for the DVR will not be affected.
6
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Compatibility – Products Affected Con’ t.The following product’s standard configuration or available options will be affected. The change will affect PMG generators that have the CDVR as standard or option. Generators that do not have an option for the DVR will not be affected.
4
7
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Other CDVR Production Information
• The CDVR will replace DVR for low and medium voltage generators and will also replace KCR 760 & KCR 65-12B for high voltage generators. A follow-up announcement will be sent that details product changeover on all affected products.
• The CDVR will be used in all EPG products currently available with a standard or optional CDVR and with high voltage applications where analog regulators are standard with current product.
• 3500 SE Generators will be shipped with a VR-6
• 3500 PM Generators will be shipped with a CDVR
8
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR started production January 2004
Digital Voltage Digital Voltage Regulator or “ DVR”Regulator or “ DVR”
Caterpillar Digital Voltage Caterpillar Digital Voltage Regulator or “ CDVR”Regulator or “ CDVR”
JanuaryJanuary20042004
TransitionTransition
5
9
EP Basic AP Service Learning
Service Excellence &Relentless Execution
DVR from 1994-2003
• Previous design pictured• Called the “DVR” or “Digital
Voltage Regulator”• Manufactured by Magnetek-
Century• Will be discontinued• Replaced with the new
“Caterpillar Digital Voltage Regulator” or “CDVR”
• Six part numbers were used to accommodate SE & PM, 120, 240, and 480 VAC sensing requirements
10
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Caterpillar Digital Voltage Regulator
• New design pictured
• Called the “Caterpillar Digital Voltage Regulator” or abbreviated “CDVR”
• Made by Basler Electric
• Will be used on Caterpillar generator sets and will replace the “DVR”
• January 2004 Production
• Only One Part Number is needed for all applications
• KVAR/PF control included
6
11
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR Publications
• Available on Service Information System (SIS)– RENR7941 Specifications System Operation
Testing & Adjusting Guide
– “CDVR PC Software” is available on SISweb in the download section or on the monthly SIS subscription Flash File CD ROM.
• Available on Electronic Media Center– LEHE3225 Specifications Sheet
– LEXE3226 November 2003 Product News
12
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Part Numbers
• Cat Digital Voltage Regulator (CDVR) - 235-5725
• Connector Part Numbers– P6 plug: 234-1856, P6 seal 246-7013.
– P9 plug: 234-1857, P9 seal 246-7014.
– P12 plug 234-1858, P12 seal 246-7015.
– P6, P9 and P12 Pins : 244-0452.
• Planned part number releases:– Crimping tool: 239-5260.
– Extraction tool: 246-8636.
7
13
EP Basic AP Service Learning
Service Excellence &Relentless Execution
A Brief Look…
• There is no touch pad or display for programming
• PC programming only
• PC software is on SIS
• RS-232 PC connection
• No screw terminals
• 3 Molex connectors
• Bolt pattern like the DVR
• Fault LED Indicator
14
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Why a new Caterpillar Regulator?
• DVR was designed in early 1990’s…– 1990’s technology has fewer features
– Internal components are becoming obsolete
– DVR designed for fewer applications
– Not cost effective to improve present design
• The CDVR has improved transient performance, added standard features such as VAR & PF control, and expanded flexibility for optimizing performance to individual customer applications.
8
15
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Features
• Microprocessor control of three standard modes – Automatic Voltage Regulation (AVR)
– Power Factor Regulation (PF)
– Reactive Power Regulation (VAR)
• Programmable stability settings
• Soft start control with an adjustable time setting in AVR control mode
• Dual Slope Under Frequency (volts/Hertz) regulation
16
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Features
• Three-phase or single-phase generator voltage (RMS) sensing/regulation in AVR mode
• Single-phase generator current sensing for regulation purposes
• Field current and field voltage sensing
• Five contact sensing inputs for system interface
• One common LED for visual indication of Alarm and Shutdown fault conditions
• Ten generator protective functions
9
17
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Features
• Fault Shutdown Driver and Alarm Output Driver for indication of Alarm and Shutdown fault conditions
• Generator paralleling with reactive droop compensation and reactive differential compensation
• Line drop compensation
• Remote communication interface via CAN 2.0B or RS-232
• UL 508 Recognized and CE certified
18
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Modes of Operation Defined
•Automatic Voltage Regulation (AVR)
•Reactive Power (VAR) Regulation
•Power Factor (PF) Regulation
10
19
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Automatic Voltage Regulation Mode
• AVR mode regulates the RMS generator output voltage. The regulator senses the generator output voltage through the sensing leads and then adjusts the dc output excitation current to the generator exciter field. This excitation current maintains the generator terminal voltage at the regulation setpoint.
• This is the basic function of any voltage regulator on a standalone generator set
• AVR mode is the default operating mode and can be disabled by a switch input or the J4 port with CDVR PC Software.
20
EP Basic AP Service Learning
Service Excellence &Relentless Execution
VAR Control Mode
• Reactive or VAR mode regulates “Volt-Amps Reactive” when paralleling with an infinite bus. The CDVR calculates generator VARs from output voltage and droop CT current quantities and adjusts the excitation current to maintain VARs at the programmed setpoint. VAR mode and PF mode are mutually exclusive modes that both work in conjunction with AVR mode.
• VAR mode is enabled by a switch input and the CDVR PC Software. VAR is adjustable from 100 percent absorb to 100 percent generate.
• Typically used when paralleled with utility.
11
21
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Power Factor Control Mode
• PF mode regulates Power Factor when paralleling with an infinite bus. The CDVR calculates PF using the sensed output voltage and current and then adjusts the dc excitation current to maintain PF at theprogrammed setpoint. Again, VAR mode and Power Factor mode are mutually exclusive modes that both work in conjunction with AVR mode.
• PF mode is enabled by a switch input and the J4 port with CDVR PC Software. PF setpoint is adjustable from 0.6 –1.0 lag and 0.6 – 1.0 lead.
• Typically used when paralleled with utility.
22
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Regulation Characteristic. Below the Knee Frequency, the generator voltage follows a decreasing slope based on generator frequency. When generator frequency is between the Knee Frequency and Knee Frequency minus 5 hertz, voltage follows Slope 1. When generator frequency is between the Knee Frequency minus 5 hertz and theUnderfrequency Point, voltage follows Slope 2 down to the Minimum Voltage Setpoint. When generator frequency is below the Minimum Frequency Point, excitation is removed. Programming Decreasing Slope 2 is optional.
0Hz 25 45 55 60Hz
480
VAC
0 Knee Frequency (45-65Hz)
Min. Voltage Setpoint (50-100%)
5 Hz (Not Adjustable)
Decreasing Slope 1 (0-10 V/Hz)
Decreasing Slope 2 (0-10 V/Hz)
Generator Output VoltageMinimum Frequency Point (20-40Hz)
12
23
EP Basic AP Service Learning
Service Excellence &Relentless Execution
10 CDVR Protective Functions
• Generator Overvoltage
• Generator Undervoltage
• Loss of Excitation
• Instantaneous Field Overcurrent
• Over Excitation
• Loss of Sensing Voltage
• Diode Fault Monitor
• Internal CDVR Processor Watchdog Failure
• Internal CDVR Memory Failure
• Fault Reset Switch Closed Too Long
24
EP Basic AP Service Learning
Service Excellence &Relentless Execution
General Specifications
• Voltage Regulation:
– ± 0.25% from no load to full load with < 30% THD
• Temperature Drift:
– Less than ±1% for a 40°C (72°F) change over the ambient operating temperature range.
• Regulator response time:
– Maximum of 10 milliseconds.
• Variable Sense Range:
– 90 to 600 volts.
• Control Power:
– 24Vdc Supply (18 to 30Vdc, 5VA)
13
25
EP Basic AP Service Learning
Service Excellence &Relentless Execution
General Specifications
• Regulator Filtering:– THF 3% per IEC34-1
– TIF of 50 NEMA MG1-22.43
• Harmonic Tolerance:– 0.5% Voltage regulation with up to 40% THD
• Power Dissipation:– 55W Maximum
• Weight:– 1.47 kg (3.24 lbs.)
26
EP Basic AP Service Learning
Service Excellence &Relentless Execution
General Specifications
• Regulator sensing:– True RMS 3-phase sensing is standard. Single phase sensing is
available.
• Configurable Volts/Hz Regulation Characteristic– Two slope ranges adjustable from 0 to 10 V/Hz. See Regulation
Characteristic Illustrations.
• Fine voltage adjust range:– ± 15% Maximum of regulator sensing voltage.
• Regulator voltage gain (line loss compensation)– Adjustable from 0 to 10%.
14
27
EP Basic AP Service Learning
Service Excellence &Relentless Execution
General Specifications
• Reactive droop adjustment:– Adjustable from 0 to 10%.
• Fault detection and identification:– Diagnostics identify operation outside of programmed limits.
Specific fault information is available after the unit has been powered down.
• Over Excitation protection:– Shuts off generator output when excitation current exceeds normal
operating currents for 10 seconds or instantaneous shut-off if output current exceeds approximately 28 Amperes.
28
EP Basic AP Service Learning
Service Excellence &Relentless Execution
General Specifications
• Voltage Regulation Rating– 120 to 15000 VAC
• Generator Excitation Type– PM – Permanent Magnet
– SE – Self Excited
– AREP – Auxiliary Winding Capable
• AC Input Power– Three phase, 80 to 264 VAC, 50 to 400 Hz, 1150VA
– Single phase, 100 to 280 VAC, 50 to 400Hz, 1900 VA
15
29
EP Basic AP Service Learning
Service Excellence &Relentless Execution
General Specifications
• Output Power Maximum Continuous:– 12 Amps DC @ 63VDC – 10 Amps DC @ 125 VDC
• Output Power Maximum Forcing (10 seconds):– 25 Amps DC @ 125 VDC– 20 Amps DC @ 250 VDC
• AC Sensing Voltage:– True RMS three phase or single phase, 90 to 600 VAC, maximum 1 VA
per phase burden.
30
EP Basic AP Service Learning
Service Excellence &Relentless Execution
General Specifications
• Reactive Voltage Droop circuit:
• 5 Amp Current Transformer, maximum 1 VA burden
– Regulator has internal CT burden resistor
• Exciter Field Resistance Range– 3 Ohms minimum, 39 ohms maximum
16
31
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Environmental Specifications
• Operating Temperature:– -40°C to 70°C (-40°F to 158°F)
• Storage Temperature:– -40°C to 85°C (-40°F to 185°F)
• Relative Humidity:– 95% non-condensing 30°C to 60°C
• Salt Fog:– 5% for 48 hours at 38°C (100°F) at 115% of the nominal operating
voltage
32
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Environmental Specifications
• Vibration:– 4.5G (peak) 18-2000Hz in 3 perpendicular planes
• Shock:– Withstands up to 20 g’s in three mutually perpendicular planes.
• Certifications:– CE Approved
– UL 508 Recognized
– CSA Listed
– Meets MIL STD 461C
17
33
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Caterpillar Digital Voltage Regulator(CDVR)
Wiring Connections
Prepared by Service Traininghttps://psmktg.cat.com/srvtrng/
34
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Regulator Connectors and LED
(1) 6-pin connector “P6”
(2) LED Indicator
(3) 12-pin connector “P12”
(4) 9-pin connector “P9”
(5) 9-pin D-sub Connector “J4”
Note: Items 1, 3 & 4 are Molex brand Connector plugs
18
35
EP Basic AP Service Learning
Service Excellence &Relentless Execution
P6 connector pin numbering
���� ���� ����
������������
View as looking at P6 on the regulator plug
36
EP Basic AP Service Learning
Service Excellence &Relentless Execution
P6 Wiring
• Pins 1, 2 & 3: AC power inputs from either SE or PM stator winding
• Pins 4 (-) & 5 (+): DC field voltage output to the generator exciter stator
• Pin 6 should be hard-wired to earth ground with at least a 16AWG copper wire
19
37
EP Basic AP Service Learning
Service Excellence &Relentless Execution
P9 connector pin numbering
���
��
View as looking at P9 on the regulator plug
38
EP Basic AP Service Learning
Service Excellence &Relentless Execution
P9 Wiring• Pins 1, 2 & 3: CANbusdata link
connections
• Pins 4, 5 & 6: Raise and Lower connections for voltage level adjustments in AVR mode, KVAR level in KVAR mode and P.F. level adjustment in P.F. Mode
• Pin 7: Excitation Disable of field voltage to exciter stator
• Pin 8: Fault Shutdown Reset
• Pin 9: VAR/PF mode enable
20
39
EP Basic AP Service Learning
Service Excellence &Relentless Execution
P12 connector pin numbering
�����
������
40
EP Basic AP Service Learning
Service Excellence &Relentless Execution
P12 Wiring
• Pins 1 & 2: droop CT input
• Pins 3 & 6: +/-10 DCV in
• Pin 4: Alarm output
• Pin 5: Fault SD output
• Pins 7 & 8: 24VDC Input
• Pin 9: Alarm and Fault Shutdown Supply Driver
• Pins 10, 11, & 12: Generator AC voltage sensing phases “C” , “B” , and “A” respectively.
21
41
EP Basic AP Service Learning
Service Excellence &Relentless Execution
J4 connector pin numbering
The digital voltage regulator has the capability to communicate with a personal computer or programmable logic controller. The J4 connector of the digital voltage regulator provides an RS-232 port necessary for communication. Pin locations and numbers are shown above.
42
EP Basic AP Service Learning
Service Excellence &Relentless Execution
J4 RS-232 Wiring
The J4 RS-232 port is a 9-pin connector including a pins for Receive, Transmit, common Signal Ground. The common signal ground is NOT a bonding ground and should not be grounded to the case or frame. It is to be connected to the RS-232 device Signal Ground connection point. Cable length should be limited to 15 m (50 ft) maximum for the RS-232 signal wiring
Part 1U-9494 – RS232 cable.
22
43
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Example PMG Diagram
44
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Example PMG Diagram
Required only for Var/PF control. Var/PF permitted with 52a closed, inactive with 52a open.
23
45
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Example PMG Diagram
Excitation is disabled when closed, enabled when open.
46
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Example PMG Diagram
Momentary closure resets any shutdown fault.
24
47
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Example PMG Diagram
S1 (SPDT, spring-return to center-off position) adjusts regulator setpoint or KVAR/PF setpoint when in KVAR/PF mode
48
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Example PMG Diagram
Normally-off, turns on for user alarm or trip.
25
49
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Example PMG Diagram
Analog input voltage between -10 and +10 Vdcprovides adjustment of operating voltage.
50
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Example PMG Diagram
External fuses should be sized to match the PMG and protect the field. Maximum fuse size should be limited to Bussmann type KTK-12.
26
51
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Example PMG Diagram
Three-phase PMG is shown. For single-phase PMG, omit P6-3 connection.
52
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Example PMG Diagram
Sensing potential transformer is required if line voltage exceeds 600 Vac.
27
53
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Example PMG Diagram
Items No.10 are not supplied by Caterpillar.
54
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Example PMG Diagram
When generator rotation is ACB, the connections shown for CTB should be reversed.
28
55
EP Basic AP Service Learning
Service Excellence &Relentless Execution
9
8
CTBGEN
10
9
52 9
P0018-2507-16-03
FIELD OUTPUT
P6-4 (F2,-) P6-5 (F1,+) P6-1
POWER INPUT
P6-2 P6-3
CURRENTSENSING
P12-1 P12-2 P12-10
VOLTAGESENSING
P12-11 P12-12
P9-6
RAISE/LOWERINPUTS
P9-4 P9-5
+/-10 VDCCONTROL INPUT
P12-6 (+) P12-3 (-)
VAR/PFCONTROL
P9-9
EXCITATIONDISABLE
P9-7
FAULTRESET
P9-8 P12-4 (-)
ALARMDRIVER
SHUTDOWNFAULT DRIVER
P12-9 (+) P12-5 (-)
CAT DVR-II
GROUND
P6-6
24 Vdc+ _
24 Vdc CONTROLPOWER
P12-8 (+) P12-7 (-)
1 52a
2 3
S1
4
9
5 5 6
A
B
C
Required only for Var/PF control. Var/PF is active with 52a closed, inactive with 52a open.
Excitation is disabled when closed, enabled when open.
Momentary closure resets any shutdown fault.
S1 (SPDT, spring-return to center-off position) adjusts CAT DVR-II setpoint.
Normally-off, turns on for user alarm or trip.
Analog input voltage between -10 and +10 Vdc provides adjustment of operating setpoint.
External fuses should be sized to match the AREP windings and protect the field. Maximumfuse size should be limited to Bussmann type KTK-12 or equivalent.
Sensing potential transformer is required if line voltage exceeds 660 Vac.
Item not supplied by Caterpillar.
When generator rotation is ACB, the connections shown for CTB should be reversed.
1
2
3
4
5
6
7
8
9
10
9
7
+
Auxiliary WindingsShunt Series
X1 X2 Z1 Z2
AREPWiring
Example
56
EP Basic AP Service Learning
Service Excellence &Relentless Execution
The VR-3 (not shown), VR-6, DVR and new CDVR all have the same bolt pattern and mount in the same location in the generator enclosure.
Mounting
VR-6 DVR CDVR
29
57
EP Basic AP Service Learning
Service Excellence &Relentless Execution
The VR-6 and CDVR both present an electrical shock risk. Terminals and heatsinksare live at potentially lethal voltages when power is applied and for up to 8 minutes after power is removed. This high voltage may cause electrical shock that could result in injury or death. Service by trained personnel only.
Reminder – Live Terminals and Heatsinks
VR-6 CDVR
58
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Wiring Comparisons to the DVR
• Droop CT wiring
• Fault Alarm and Shutdown Output Driver Logic
• VAR/PF enable, fault reset, and excitation disable inputs
• Remote voltage and VAR/PF adjustment
30
59
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Wiring Comparisons to the DVR
DVR
60
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Wiring Comparisons to the DVR
• The DVR uses an 8-ohm resistor with a 1 Amp droop CT or a 1-ohm resistor with a 5 Amp droop CT.
• The CDVR requires a 5 Amp droop CT and no resistor across the CT output.
• Note: CT leads which are not connected to the regulator must be shorted to avoid a potential shock hazard.
DVR
31
61
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Wiring Comparisons to the DVR
• DVR and CDVR have the output driver logic reversed.
• The DVR low side driver outputs for the fault alarm and shutdown are active high (driver output floats when a fault is active).
• The CDVR low side driver outputs for the alarm and shutdown are active low (driver output pulls low when a fault is active).
• A CDVR output is N/O and would energize to close the output circuit upon an alarm or shutdown.
DVR
62
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Wiring Comparisons to the DVR
• The DVR VAR/PF enable, fault reset, and excitation disable inputs activate with +24VDC.
• The CDVR VAR/PF enable, fault reset, and excitation disable inputs require a normally open dry contact to enable the function.
DVR
32
63
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Wiring Comparisons to the DVR
• The DVR utilizes a 10K-ohm potentiometer for remote voltage adjust another for remote VAR/PF adjustments
• The CDVR uses a singlemomentary switch with raise and lower contacts. The switch adjusts voltage in AVR mode and also adjusts VAR or PF if operating in that mode.
DVR
64
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Caterpillar Digital Voltage Regulator(CDVR)
PC Software Installation
Prepared by Service Traininghttps://psmktg.cat.com/srvtrng/
33
65
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR PC Software Download
• The CDVR PC software and an IBM Compatible Personal Computer or Laptop is required for the service technician to program CDVR set points and parameters and to access status indicators and regulator metering functions.
• This Presentation has detailed steps for downloading the PC Software from SIS (Service Information System), establishing communications and programming the CDVR.
66
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR PC Software Download• Navigate to SIS at https://sis.cat.com
34
67
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR PC Software Download
• Click on “Downloads”
68
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR PC Software Download
• Click on “CDVR PC Software.exe”
35
69
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR PC Software Download
• Verify “Save this file to disk” is selected as shown and then click the “OK” button
70
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR PC Software Download
• Select where to save the file. The example shows the file being saved as “CDVR PC Software” to the computer Desktop.
36
71
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR PC Software Download
• The “CDVR PC Software” file will download and a Download Complete box will appear when the download is complete. Click “Close” .
• This file is 6.17MB in size and may take longer with slower network or modem connections.
• This completes the software download.
72
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR PC Software Installation
• Run the file by double-clicking
on the file “CDVR PC Software”
• If the file has not been saved to the desktop, navigate to the folder where it was saved and open the CDVR PC Software program file as shown below.
or
37
73
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR PC Software InstallationCDVR PC Software Installation
• Follow the installation instructions and click “Next” when ready.
74
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR PC Software InstallationCDVR PC Software Installation
• Verify the folder location and click “Next”.
38
75
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR PC Software InstallationCDVR PC Software Installation
• Click “Next”…
76
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR PC Software InstallationCDVR PC Software Installation
• Click “Next”…
39
77
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR PC Software InstallationCDVR PC Software Installation
• Click “Next”
78
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR PC Software InstallationCDVR PC Software Installation
• A window will appear with the bars showing the installation…
40
79
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR PC Software InstallationCDVR PC Software Installation• When the installation is complete click “Finish”
• This completes the software Installation
80
EP Basic AP Service Learning
Service Excellence &Relentless Execution
To start the CDVR PC softwarefollow these four steps. 1. Click the Start button2. Click Programs3. Click Caterpillar Software4. Click Cat PC Software
1
2
3
4
41
81
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR PC SoftwareCDVR PC Software• Startup Screen when the software is launched
82
EP Basic AP Service Learning
Service Excellence &Relentless Execution
What’s needed for communication?
1. Computer with the CDVR Software installed (the computer must meet the minimum requirements in the CDVR Service Manual)
2. Cable to connect the computer to the CDVR RS-232 port. Newer computers may not have an RS-232 port and may require a USB to RS-232 adapter (237-7547). Cables are not provided.
3. 24VDC power to the CDVR input power connections. AC Sensing and/or PMG power voltage is not needed for communication.
42
83
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Caterpillar Digital Voltage Regulator(CDVR)
PC Software Overview
Prepared by Service Traininghttps://psmktg.cat.com/srvtrng/
84
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR Programming Overview
• The next few slides provide only a brief explanation of the CDVR PC Software screens and parameters. The CDVR Service Manual, RENR7941, should be referenced for more detail on the parameters and functions not covered in this overview.
43
85
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR Programming Overview
• “File” pull down menu is used to Open, Save or Print CDVR program configuration (* .DV2) files
86
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR Programming Overview• “Communications” pull down menu is used to connect or disconnect CDVR
communication
44
87
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR Programming Overview• “Screens” pull down menu or the buttons are used to select the five configuration
screens
Both is the same
88
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR Programming Overview
• “Upgrade” pull down is for upgrading the CDVR embedded software
45
89
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR Programming Overview
• “Help” pull down will display the version of PC Software being used. Also shown here.
90
EP Basic AP Service Learning
Service Excellence &Relentless Execution
System Configuration Screen• “Configuration” screen has generator voltage and current output and sensing parameters.
Only fields with a white background can be changed. In this case, “Rated Voltage” has been selected and is high lighted.
The bottom screen bars show the minimum, maximum and step or increment allowed for the selected parameter.
46
91
EP Basic AP Service Learning
Service Excellence &Relentless Execution
System Configuration Screen• “Configuration” screen has generator voltage and current output and sensing parameters.
Rated voltage is changed from 120V to 240V by typing “240” and then the “Enter” key. (Do not use the Tab key). When 240 is entered the Rated KVAR automatically changes from 75 to 150. Fields with a black background cannot be clicked on and changed.
92
EP Basic AP Service Learning
Service Excellence &Relentless Execution
System Configuration Screen
• There are two operating frequency parameters.
“Power Input Freq” is the frequency of the input power. On SE this is the same as the generator operating frequency which is 50 or 60Hz only. For PMG It is the frequency from the PMG exciter stator from 50-400hz.“Frequency” comes from the generator nameplate and will be 50 or 60 Hertz.
47
93
EP Basic AP Service Learning
Service Excellence &Relentless Execution
System Configuration Screen
• Other sensing parameters explained
Sensing Mode can be Three or Single Phase
PT Primary and Secondary voltages
Droop CT is programmed to 600 on the primary. 5 on the secondary is not adjustable so the droop CT ratio is 600:5
94
EP Basic AP Service Learning
Service Excellence &Relentless Execution
System Configuration Screen
• Get From Unit Button
Voltage regulator settings are retrieved by clicking the “Get From Unit” button. This causes the current settings of the CDVR to be displayed on the “settings” screen. This button will be grayed out until the communication is established.
Parameter changes are sent to the CDVR by pressing the Enter key on the PC or by selecting a setting from a pull-down menu. This causes the selected setting displayed on the setting screen to become the active voltage regulator setting.
48
95
EP Basic AP Service Learning
Service Excellence &Relentless Execution
System Configuration Screen
• EEPROM Button
Settings are saved in the CDVR EEPROM (nonvolatile memory). When power is removed, the EEPROM saved settings will be active at power-up. If the settings are changed and sent to the voltage regulator by hitting the enter key, they are not sent to the EEPROM. They will be lost if the CDVR is powered off. When closing communication the software will prompt the user to save the settings to the EEPROM. This question is asked even if no changes were made to the settings. While communicating the user can save changes to the EEPROM anytime by clicking the “EEPROM” button.
96
EP Basic AP Service Learning
Service Excellence &Relentless Execution
System Configuration Screen
• Information for PC Software and CDVR
PC Software version
The CDVR serial number, internal embedded software version and CDVR part number will show in these three boxes
49
97
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Setting Adjustments Screen
• Setpoint Parameters
AVR Voltage is the terminal output voltage of the generator in the AVR mode.
VAR percentage sets VAR level maintained in the VAR mode.
Power Factor sets the PF maintained in the Power Factor mode.
98
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Setting Adjustments Screen• Setpoint Parameters
Load Compensation Mode settings are “Off, Droop, or Line Drop”. “Off” is no voltage droop. “Droop” allows up to 10% droop at full load. “Line Drop” allows voltage to increase up to 10% for line loss compensation.
The Setpoint (%) for “Droop” and “Line Drop” is 0 to 10%.
50
99
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Setting Adjustments Screen
• Startup Parameters Soft Start Mode
Soft Start Bias (%) determines the generator voltage at startup. 0 to 90 may be entered.
Soft Start Time (sec) establishes the length of time for the generatorvoltage to increase to the rated level. 0 to 120 sec. may be entered.
100
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Setting Adjustments Screen
• Startup Parameters Under Frequency Mode
The five programmable Under Frequency Mode parameters determine the CDVR under frequency voltage regulation characteristic curve.
The next slide has a graph of the under frequency voltage regulation characteristic curve and setpoints.
51
101
EP Basic AP Service Learning
Service Excellence &Relentless Execution
0Hz 25 45 55 60Hz
480
VAC
0
Minimum Frequency Point (20-40Hz)
Regulation Characteristic. Below the Knee Frequency, the generator voltage follows a decreasing slope based on generator frequency. When generator frequency is between the Knee Frequency and Knee Frequency minus 5 hertz, voltage follows Slope 1. When generator frequency is between the Knee Frequency minus 5 hertz and theUnderfrequency Point, voltage follows Slope 2 down to the Minimum Voltage Setpoint. When generator frequency is below the Minimum Frequency Point, excitation is removed. Programming Decreasing Slope 2 is optional.
102
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Control Gain Screen
Control Gain
Generators delivered with a CDVR installed will have these parameters set for optimal generator operation. These settings may vary on different packages.
These parameters are covered in detail in the Service Manual and it should be referenced when making changes.
52
103
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Protection Settings Screen
• Protection
The Shutdown Override button can be toggled from DISABLED to ENABLED during set-up or troubleshooting.
If the Fault Reset Switch is held too long the CDVR will take programmed action.
104
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Protection Settings Screen• Protection
Protective settings like Generator Overvoltagehave the following:1. Enable check box,2. Fault Type (Alarm or Shutdown)3. Trip Value (%)4. Time Delay (Sec.)
If output voltage exceeds 135% for 2 seconds, an Alarm condition will activate.
53
105
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Protection Settings Screen• Protection
Excitation (Exciter Stator) current is monitored and if the programmed limits are exceeded the excitation current will be disabled.
Excitation current will also be disabled if the Exciter Diode Monitor or Loss of Sensing limits are exceeded.
106
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Metering, Operation and Alarms Screen
• Metering Password
When the “Metering” button is clicked a password prompt window opens.
This screen has password protection to prohibit an untrained person from changing parameters which may cause damage to the generator or force the generator into an unsafe operating mode.
54
107
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Metering, Operation and Alarms Screen
When the password “cat” is entered, full access is granted.
If “Cancel” is selected the Metering data is available only for viewing. Fields with white backgrounds cannot be changed and the soft buttons will be inactive.
cat
108
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Generator operating parameters values are displayed in green.
Operating Mode is AVR and can be changed to VAR or PF if VAR/PF contact is closed.
Fine Adjustment acts as the raise/lower switch and varies the voltage setpointin AVR mode. This would vary PF/VARs if in the PF/VAR mode.
Metering, Operation and Alarms Screen
55
109
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Setpoint allows the user to change the AVR, VAR or PF level to be maintained while the generator is operating.
Caution: While the generator running, the CDVR will immediately change its regulation to obey the values or buttons changed on this screen. Customer access is discouraged.
Metering, Operation and Alarms Screen
1VDC change cause a 1% AVR volt change or 10% KVAR change or .04 PF change
110
EP Basic AP Service Learning
Service Excellence &Relentless Execution
“Status” will light the soft LED modes that apply when active.
“Contact Inputs” will light when switched inputs are activated.
“Alarms” will light when the alarm is active or if a shutdown has occurred due to an alarm. The hard wired reset switch will reset.
Metering, Operation and Alarms Screen
56
111
EP Basic AP Service Learning
Service Excellence &Relentless Execution
The “Alarm Signal” LED will light if there is an active alarm condition.
When the “Disabled” button is toggled to “Enabled” the CDVR will not allow normal shutdown faults to shutdown excitation for troubleshooting. This must be used carefully to protect the generator from unsafe conditions.
Metering, Operation and Alarms Screen
112
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Summary
This concludes the training overview of the CDVR. This presentation will be updated as needed and available on the Caterpillar Service Training Website at: https://psmktg.cat.com/srvtrng/
Again, the proper service information for the regulators in SIS should be used for the latest specific details for operation, adjustments, programming and troubleshooting.
57
113
EP Basic AP Service Learning
Service Excellence &Relentless Execution
CDVR Laboptional
114
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Control Panels
58
115
EP Basic AP Service Learning
Service Excellence &Relentless Execution
The 3N8900 Type 5
This is the 3N8900 type V control panel. It's been around for a number of years and there are
still many of them in use today. This panel will be covered in detail later. The panel has AC Ammeter,
frequency meter, AC Voltmeter,; Off / Reset, Auto, Start, Stop Engine Control Switch,
Governor Speed Control, Alarm Panel, etc. Four fault lights for Low Oil Pressure,
Excessive Water Temperature, Over Crank, and Over Speed.
116
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Caution VACCaution VACThis is the inside of the Type V control panel. Notice the tapeon the back of the meters.
There is 480 volts on the meters so opening the panel during operation is not recommended.
There is a KVAR controller mounted on this particular one but Cat does not use it any longer.
59
117
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Junction Box
Around 1985 Caterpillar started to standardize the control panels making this “Engine Junction Box"
with all of the electromechanical inputs inside. Oil pressure switches are mounted on the rear of the box and
Water Temperature switches are mounted elsewhere on the engine. Before this box was used, wiring was done
using a schematic without a wire routing diagram or “common” wiring strategy. Cat developed the harness
and a Junction box to make a common wiring for all. This junction box is still being used today not only
in genset applications but also in many industrial and marine as well as other commercial applications.
118
EP Basic AP Service Learning
Service Excellence &Relentless Execution
TDRTDR
ESSESS
EmergEmerg. Stop. StopSw.Sw.Power RelayPower Relay
Hr. MeterHr. Meter
Here is the internal view of the Junction Box. In it are the Engine Speed Switch (ESS), a Time Delay Relay
(TDR), an emergency stop switch, a power relay, and an hour meter. The standard harness is inside of the
corregated plastic conduit. The wires are labeled with a wire code for to make troubleshooting easier.
The box is shock mounted to absorb engine vibration to protect the components inside the junction box.
With out proper shock mounting the small relay contacts inside the ESS and TDR may chatter cause a failure
or shutdown.
60
119
EP Basic AP Service Learning
Service Excellence &Relentless Execution
The 4W8000 with auto start/stop
This electromechanical control panel 4W8000 was used with the engine mounted junction box. It has an
Automatic Stop/Start module with 4 fault lights for Oil Pressure, Water Temperature, Overspeed, and
Overcrank. There is an Emergency Stop switch. The control switch has four positions:. Auto, Manual,
Stop and Reset. The panel also has a Voltmeter, Ammeter, Frequency Meter, Oil Pressure and
Water Temperature gauges, and an optional Alarm Module that warns when some things are about to fail.
If the oil pressure is low, but not too low, it will turn on the low oil pressure alarm light.
120
EP Basic AP Service Learning
Service Excellence &Relentless Execution
EMCP I Engine Control Engine Control ModuleModule
Alarm Alarm ModuleModule AC Meter AC Meter
ModuleModule
61
121
EP Basic AP Service Learning
Service Excellence &Relentless Execution
• In 1987 the Electronic Modular Control Panel (EMCP) was put intoproduction. This was abbreviated as ECMP, not “EMCP I” . Folks later began to call it “EMCP I” when the ECMP II panel was released in the mid-90’s to distinguish between the two.
• The EMCP panel simplified the genset control system by eliminating a lot of wires, senders and switches. The LCD displayed hours, Engine Speed, Battery Voltage, Oil Pressure, and Coolant Temperature. These controls are used in many switchgear applications also.
• This panel needs only one magnetic pick-up, one oil pressure sensor, and one coolant temperature sensor mounted on the engine. The engine junction box was no longer needed.
122
EP Basic AP Service Learning
Service Excellence &Relentless Execution
“ 2 “ 2 PotentiometersPotentiometers
” and Switch” and Switch
Switches Switches and Resistorand Resistor
Alarm Module Set Alarm Module Set point Adjustmentpoint Adjustment
62
123
EP Basic AP Service Learning
Service Excellence &Relentless Execution
• EMCP Panel interior. This EMCP panel was actually cost effective too because the enclosures are very rugged and reliable. To program, the technician needed to remove a rear cover and use switches and a pot to change parameters. Notice the single phase AC meter module. The ECM and AC Meter module are installed in many switchgear applications. The Annunciator is on the left.
• “Pots” and switch are used to program the parameters of the ECM.
• Switches and Resistor are used to program the AC Module voltageand CT Ratios.
• Alarm Module Dc Volt “pot” can be used to adjust the DC Alarm level
124
EP Basic AP Service Learning
Service Excellence &Relentless Execution
EMCP II
This is a picture of the EMCP II GSC. It is the brain of the EMCP II system.
The GSC (Generator Set Control) combines the AC Meter, Annunciator and ECM into one module.
Also added was a Transformer box in the back of the panel for more accurate AC metering of all
three phases. Lights for E-Stop, coolant level and fault lights were added. The “EMCP II” adds even more
features than the EMCP I. If there was a need to program the EMCP I ECM, the technician had to
remove a cover, push buttons and select a rotary switch to the proper position and then do the programming.
All of these switches and pots are on the back of the panel and the display is in the front. The EMCP II GSC
is programmed using the pushbuttons on the front of the panel. The programming password is 13231.
Notice the engine display (on bottom) is a little shorter in length than the generator display (on top).
EMCP II was introduced in 1994.
63
125
EP Basic AP Service Learning
Service Excellence &Relentless Execution
EMCP II+
EMCP II+. The “+” or “Plus” has large displays on the top and bottom of the GSC. In the “Plus” onecan read Kw, Kva, Power Factor, Kw hours, percent of load or percent Kw, etc. The AC metering can display separate phases or totals, average voltage, average frequency and total current. When the customer sees the “ total cur rent” of all three phases he may see the result of 500 Ampsper phase which will show 1500 AMPs. This usually surprises them until it is explained. This works very much like the EMCP II. The “plus” also has Protective Relay functions. There is not a typical relay but it can be programmed for alarm or shutdown parameters such as over current or over voltage to provide industrial grade relay protection. This slide actually shows two alarm modules.
126
EP Basic AP Service Learning
Service Excellence &Relentless Execution
GSCGSC
Alarm Alarm ModuleModule
Customer Customer Alarm Alarm
ModuleModule
ControlsControls
64
127
EP Basic AP Service Learning
Service Excellence &Relentless Execution
EMCP 3EMCP 3
128
EP Basic AP Service Learning
Service Excellence &Relentless Execution
EMCP I & II Control Panel Attachments
65
ALARM MODULESAmberAmber
RedRed
Alarm modules can be used to annunciate low fuel level, outside switch closures, air damper,
air flapper down, battery charger, not in auto, etc. The Annunciator gets information from the EMCP
or EMCP II via a serial data link from the main control panel or from external switches. Changing the
type of Annunciator or its function is a matter of sticking a new graphics film on the front and changing
the jumper wires located in on the rear terminals. There are at least six configurations for these modules.
Any one can be converted to the other usually by changing the jumpers configuration and the film on the
front. Each film has a part number listed on the lower right corner, that part number is for the film and not
the Annunciator. The Annunciator number is located on the rear of the module.
Horn and Alarm silence button are at the bottom as well as the test lamp.
GENERATOR SET
TROUBLE
GENERATOR SET
SUPPLYING LOAD
Remote Annunciators
66
131
EP Basic AP Service Learning
Service Excellence &Relentless Execution
• This is a slightly different version with the same control used as a Remote Annunciator. Shown also an NFPA 110 remote Annunciator which just has a “generator trouble light” , a “generator supplying load light” , a horn, and a horn silence button. An EMCP system can use as many as three Annunciators or remote Annunciator combinations. One can be located on the control panel, and two may be 500 feet away. 1000 feet total of wire is the limitation of the data link because the long run of wires add capacitance which rounds off the edges of the digital serial link pulses. If the serial data link is corrupted or lost the Annunciatorwill flash its lights at a 1/2 hertz cycle.
Remote Annunciators
Customer Interface Module (looks like the relay driver module)
67
133
EP Basic AP Service Learning
Service Excellence &Relentless Execution
This is the Customer Interface Module (CIM) and relay hardware. Instead of activating LEDs from the serial data link like the Annunciator, it receives the data link information to activates relays. Soinstead of turning LEDs on, it turns relays on. The relays can then be used to activate lamps in various locations. A lot of switchgear builders and customers like that because they want to have the lights instead of a single Annunciator with a set number and color of LEDs. One mis-application that happens is that some people wire the relays to trigger a shutdown for a certain fault. It's not intended to be a shutdown because if the generator is running and someonepushes the “ lamp test” button, all of the relays activate and any that can cause a shutdown will shutdown the engine. Also, if there is any problem with the datalink, then the ‘shutdown’ circuit will not work properly or possible in an unsafe manner.
Troubleshooting Tip:
Pin 18 goes in and out on relay board (which may have electrical noise) to terminal 4 on the dark brown terminal brick. If the CIM is shutting down, run the shielded 18 line to terminal 4 skipping the relay board altogether. If there is a a CIM, RDM and an Annunciator all in one system and one loses power, the un-powered unit will pull the data link down and this un-powered unit will be completely dead and the others will have all the lights on.
134
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Customer Communications Module
Customer Communications ModuleCustomer Communications Module
68
135
EP Basic AP Service Learning
Service Excellence &Relentless Execution
The Customer Communications Module (CCM) is simply a ‘ translator box’ . It takes the Cat Data Link output out of the EMCP II and translates it into an RS232 protocol that will communicate with a computer if that computer has the CCM desktop software installed.
In the paralleling class, a CCM is used to start an engine remotely with a modem over a phone line. It is convenient to use a CCM and Laptop PC when running an acceptance test on a generator set. There is a data logger mode so data can be loaded into the PC and put into a spreadsheet to show generator loading data for example. In “Primary Mode” a CCM can monitor four EMCP IIs and four ADEM II ECMs. In “Secondary Mode” one CCM can monitor up to eight EMCP IIs without any ADEM II ECMs. The ADEM II ECMsare sometimes monitored because they too have the Cat Data Link and have detailed engine sensor and operating information.
This does have an internal battery behind the display for internal memory. On the back, it has connections for the RS-232 serial cable for connection to a PC. The Cat Data link connection connects to the GSC Module in the EMCP.
136
EP Basic AP Service Learning
Service Excellence &Relentless Execution
EMCP II and EMCP 3 Control Panel
Attachment
69
137
EP Basic AP Service Learning
Service Excellence &Relentless Execution
PL1000T and PL1000EProduct
138
EP Basic AP Service Learning
Service Excellence &Relentless Execution
PL1000T Package Features
� M5X / M50 Protocol Support (CCM Replacement)
� Cat Data Link Boost
� Embedded Communications Adapter
� CAN Extension Bridge
� J1939 Bridge
� Cat Data Link Tunnel
� Sea Water Temperature and Depth Interface (NMEA-183)
� Global Position System Module Interface (NMEA-183)
� Engine Vision Module Interface Protocol
70
139
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Embedded Communications Adapter
CDL Boost
EVIM GPSIMM5X M50
J1939 Bridge
J1939 Long Distance Extension
CDL Tunnel
PL1000T Cross-Functional Matrix
Modules Previously Required
PL1000T Required
3
3
3
2
4
4
4
1
1
1
2
1
1
1
140
EP Basic AP Service Learning
Service Excellence &Relentless Execution
PL1000E Package Features
� CDL to Modbus Parameter Translation
� J1939 to Modbus Parameter Translation
� Embedded Webserver
� Embedded Communications Adapter
� Cat Data Link Boost
� Caterpillar Communications Tool Kit Configuration
� CDL to Webserver Parameter Translation
� J1939 to Webserver Parameter Translation
71
141
EP Basic AP Service Learning
Service Excellence &Relentless Execution
PL1000E Cross-Functional Matrix
J1939 to Web
CDL to Modbus
J1939 to Modbus
Embedded Web
Server
Embedded Communications
AdapterCDL Boost
CDL to Web
142
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Today Menu:
3. SIS access to System Operation/Testing and Adjusting• EMCP I (SENR3535 via SIS)
• EMCP I I+ (RENR1200 via SIS)
• EMCP I I I (RENR7902 via SIS)4. TMI web
72
143
EP Basic AP Service Learning
Service Excellence &Relentless Execution
TMI and Web Information
144
EP Basic AP Service Learning
Service Excellence &Relentless Execution
TMI on the Web
•• URL: URL: http://http://tmiwebtmiweb.cat.co.cat.comm
•• TMI Web pagesTMI Web pages–– Engine DataEngine Data
–– Generator DataGenerator Data
73
145
EP Basic AP Service Learning
Service Excellence &Relentless Execution
146
EP Basic AP Service Learning
Service Excellence &Relentless Execution
74
147
EP Basic AP Service Learning
Service Excellence &Relentless Execution
TMI on the Web
•• URL: URL: http://http://tmiwebtmiweb.cat.com.cat.com
•• TMI Web pagesTMI Web pages–– Engine DataEngine Data
148
EP Basic AP Service Learning
Service Excellence &Relentless Execution
75
149
EP Basic AP Service Learning
Service Excellence &Relentless Execution
150
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Entry Screen
76
151
EP Basic AP Service Learning
Service Excellence &Relentless Execution
152
EP Basic AP Service Learning
Service Excellence &Relentless Execution
77
153
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Test Cell Results
154
EP Basic AP Service Learning
Service Excellence &Relentless Execution
As Shipped
78
155
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Flash File
156
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Systems Data
79
157
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Physical Data
158
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Water Pump Physical Data
80
159
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Gasket Kit Data
160
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Re-man Parts Data
81
161
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Performance Data
162
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Par Dyno
82
163
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Engine Test Spec.
164
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Component Data
83
165
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Example Component Data
166
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Example Component Data
84
167
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Certify Rerate
168
EP Basic AP Service Learning
Service Excellence &Relentless Execution
TMI on the Web
•• URL: URL: http://http://tmiwebtmiweb.cat.com.cat.com
•• TMI Web pagesTMI Web pages–– Engine DataEngine Data
–– Generator DataGenerator Data
85
5N-5078
86
Select
87
88
89
90
180
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Questions ?
91
181
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Other Useful Electric Power Information available from the Web:
182
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Electronic Media Center
92
Electronic Media Center
Images are not well indexed & may not be described correctly.
Some of the Available Document Catagories
93
185
EP Basic AP Service Learning
Service Excellence &Relentless Execution
Electric Power Quicksize software for Olympian Generator Sets:
https://epd.cat.com/infocast/frames/ep
186
EP Basic AP Service Learning
Service Excellence &Relentless Execution
94
187
EP Basic AP Service Learning
Service Excellence &Relentless Execution
End of Slides End of Slides