  • 09CDF50 HERTZ

    FORM SSI 09CDF (89)

    ? ?

    09CDFAir-Cooled CondensersNominal cooling capacity 11~128.5 ton

  • Air-Cooled Condensers - Quality and Value

    1

    With the 09CDF air - cooled condensers SSI offers a Fanschoice of 21 models with capacities from 11 to 128.5 36 in diameter with high-efficiency blade design. Extra ton for vertical and horizontal airflow. 09CDF deep fan shroud for optimum air flow.condensers are manufactured to the highest quality standards and offer the following distinct advantages:

    Fan MotorsStandard voltage 400 V ( 10%), 3 phase, 50 HertzHeavy-duty construction with casing madeOperating in - 40F to 122F ambient temperature. from galvanized sheet metal for maximum UV and Protection IP55 (IEC 34-5), Class F (IEC 85 and IEC corrosion resistance.34-1). Each motor mounted on rigid four cross beam Advanced circuitry and fin design with a wideand wired to a terminal box close to the refrigerant selection of fin and tube materials.connections. Maximum 6 starts per hour. Motors must High-efficiency fan motors and propellers withrun at least two hours per month.optimized air management design.

    Improved serviceability through large accessdoors for each fan motor section. Fan Cycling Control

    During intermediate season,proper condensing temperature is controlled by fan control packages which permit shutoff from one to six Technical Descriptioncondenser fans.

    CasingCoilsSelf supporting design, fan sections individually High performance aluminum fins and copper partitioned.tubes, staggered tube arrangement.Casing made from galvanized sheet metal. Lifting lugs One Schrader valve for each circuit.for all models provided. Service access doors for each Holding charge of minimum 1 bar.fan motor.

    OptionsMultiple circuits.Copper Tube and Copper Fins.Copper Tube and Coated Aluminum Fins

    Electrical Connection

    Model Number Nomenclature

    Coil designation

    Fan arrangement:S = One row of fansD = Two rows of fans

    Number of fans

    09CDF Series designation

    09CDF XX M X X

    Delta

  • For other conditions, the required nominal sound Sound pressure level pressure level has to be determined as follows:

    1. Select correction value for other conditions:All nominal sound pressure level information is given for the following conditions:

    2. The required nominal sound pressure level to belooked up in the selection data is:

    Sn= S+ dSRemarks about the sound pressure level?The sound pressure level has been measured by precision instruments in open field on a (S = your required sound level)compact semi-reverberent base.?The results obtained on a site may be different than the stated value, due to sound reflection phenomena (walls, etc).?Reduction of sound pressure as a function of distance is theoretical. Reflection Example:phenomena may modify the final result on site, on total sound pressure level or on some frequencies. Sound pressure level of 55 dB required at 60 ft.

    Nominal capacity

    All catalogue capacities are based on:Ambient temperature: 77 F

    For other conditions the required nominal capacity Refrigerant: R-22has to be determined as follows:Altitude: 0 ft

    Air temperature difference between condensing 1. Select correction factors for other conditionstemperature

    and air inlet temperature ? t = 27 F

    2. The required nominal capacity to be looked up in the Example:selection data is:

    R-22, 90 F ambient temperature, ?t 20 F, altitude 2000 ft required capacity 30 Ton. Qn = Q/(f1 x f2 x f3 x f4)

    (Q= your required capacity)

    Correction factor for different ambient temperatures:

    Ambient temperature (F) 60

    1.032

    70

    1.014

    77

    1

    80

    0.993

    90

    0.971

    100

    0.949

    110

    0.929

    120

    0.91

    Correction factor for ? t:

    ? t (F) 15

    0.555

    20

    0.740

    25

    0.926

    27

    1

    30

    1.111

    35

    1.296

    Correction factor for different refrigerants:

    Refrigerant R-134a

    0.97

    R-22

    1

    R-407 C

    0.98

    Correction factor for different altitudes:

    Altitude (ft) 0

    1

    1000

    0.980

    2000

    0.958

    3000

    0.936

    4000

    0.917

    5000

    0.896

    6000

    0.875

    7000

    0.854

    Determination of required nominal sound pressure leveland nominal capacity

    2

    Factor f1:

    Factor f2:

    Factor f3:

    Factor f4:

    8000

    0.834

    33.0 ft

    4.0 ft

    Correction values for different distances

    15 30 60 90 120 150

    -6 0 6 10 12 14

    Distance (ft)

    Correction by (dB)

    dS: 6 dB

    S

    Sn:

    55 dB

    55+6=61 dB

    Correction factor:

    Required sound level:

    Required nominal sound level:

    Factor f3:

    Factor f2:

    Factor f1:

    1

    0.740

    0.971

    Factor f4:

    Q:

    Qn:

    0.958

    30 Ton

    30/(0.971 x 0.740 x 1 x 0.95843.6 Ton

    Refrigerant:

    ?t:

    Ambient temperature:

    Altitude:

    Required capacity:

    Required nominal capacity:

  • No. ofFan(s) KW

    2.2

    2.2

    2.2

    2.2

    2.2

    2.2

    2.2

    2.2

    2.2

    2.2

    2.2

    2.2

    2.2

    2.2

    2.2

    2.2

    2.2

    2.2

    2.2

    2.2

    2.2

    6

    6

    6

    6

    6

    6

    6

    6

    6

    6

    6

    6

    6

    6

    6

    6

    6

    6

    6

    6

    6

    Technical Data

    3

  • Approximate Dimensions (in)

    4

of 6/6