of 67
8/10/2019 09_safetyengineering
1/67
g
GE PROPRIETARY INFORMATION Safety Engineering Page 9.1
ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
GE Energy
9. Safety Engineering
Page9.1 General ....................................................................................9.2
9.2 Hazardous Area Classification .................................................9.7
9.3 Building and Compartment Ventilation Design.......................9.19
9.4 System Vent Design...............................................................9.24
9.5 Gas and Chemical Storage and Distribution Systems............9.28
9.6 Provision and Control of Personnel Access ...........................9.32
9.7 Design of Emergency Eyewash / Shower Stations ................9.45
9.8 Design of Work Areas for Appropriate Noise Levels ..............9.50
9.9 Signs and Pipe Marking .........................................................9.51
9.10 Design of Lighting and Power ................................................9.56
9.11 Fire Protection........................................................................9.58
9.12 Reference Materials ...............................................................9.63
9.13 Review Documentation Deliverables......................................9.67
9.14 Revision Table........................................................................9.67
8/10/2019 09_safetyengineering
2/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.2
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
9.1 General
This document details design requirements for personnel safety in the
permanent facility. The information provided herein describes good power
plant safety engineering practices.
Applicable National and Local safety regulations that require additional or
specialized equipment or designs beyond those described in the proposal shall
be included in the plant design or take precedence as required by law.
Similarly, if National or Local safety regulations, or Owner preference
requires additional safety studies and services to be performed, they may be
included as contract adjustments.
In cases where Country/Local practices and codes are determined to be
equivalent or more stringent than the practices and codes, cited in the GE
Safety Engineering DBD, these Country/Local practices and codes should be
referenced within the project specific Safety Summary Report.
9.1.1 Owners Responsibility
The Owner is responsible for providing a site free of hazardous material risks
to Personnel prior to project mobilization. This shall be addressed by
removal, disposal and/or treatment of pre-existing contaminated materials(e.g. soil, ground water, etc.) at the site.
9.1.2 Design Criteria Documentation
A site specific Safety Engineering Plan shall be submitted to GE Engineering
Review Board (ERB) prior to the reviews and shall address all of the elements
of this Safety Engineering section of the design basis document. It shal
describe how it to meet the requirements of the GE Design Basis Document
(DBD). This plan shall also include:
A tabulated summary of all of the potentially hazardous materials beingused in the construction and operation of the power plant including: type
of hazards, location (use and storage), and required PPE (Personal
Protective Equipment) including locations where PPE is required.
Requirement that specifications for procurement of the above materialshall include the requirement to provide MSDS (Material Safety Data
Sheets).
8/10/2019 09_safetyengineering
3/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.3
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
Hazardous Area Classification Map for systems and equipment within the
scope of supply. This is required for the Initial Review.
Hazardous Area Classification Map for the entire site. It is important tobegin creating this map as soon as there is a tentative site layout since
hazardous areas will impact the final site layout. A preliminary site
hazardous area map shall be provided for the Progress Review.
Consolidated map of all ventilation intake and exhaust locations, and ventdischarge locations, including elevations.
A detailed listing of all codes and standards (including date issued) forsupply of equipment and construction of systems and facility, for example:
NFPA 101 Life Safety Code, 2000 or ANSI/ASME B31.3 Code for
Process Piping, 1999 (Not just ANSI, ASME, NFPA).
9.1.2.1 Project Specific Safety Summary Report Guidance
To help GE understand the design philosophy being used to address safety
issues associated with the specific project. A safety summary report is useful
to provide safety design philosophy information that is not readily called out
on the project design documents (e.g. why a pipe is sized a certain way) to GE
Suggested partner & A/E design relevant aspects for inclusion in the safety
engineering design basis document summary report.
Top-level narratives describing what safety aspects are addressed for theproject, including reference to compliance with customers technica
specification as well as regional, national, and local codes, standards and
regulations.
Hazardous Area Classification: methodology / assumptions used to createthe Hazardous Area Map(s) for the plant, what specific codes, standards
references, internal calculation done by hand or using software, etc.
Ventilation Design: for the Heating, Ventilation & Air ConditioningDesign (HVAC) describes the basis and methodology for the
determination of the ventilation rates in hazardous areas. GE HazardousArea Maps are based on equivalent outdoor ventilation as defined by
NFPA 497 for the United States and projects in other countries subscribing
to the NFPA approach or IEC 60079-10 for the European Union and
projects in other countries subscribing to the IEC approach.
Gas and Chemical Storage and Distribution Systems: asphyxiating &flammable gases design, including discussion related to prevention of
8/10/2019 09_safetyengineering
4/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.4
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
above normal concentrations in confined space; plus automatic shut-off
provisions in event of emergency or major leak occurrence.
Gas and Chemical Storage Distribution Systems: storage of petroleum &chemical products design, including discussion related to containment of
minor/major spills; plus health & safety considerations from workplace
personnel exposure.
Gas and Chemical Storage Distribution Systems: fuel gas equipmentdesign, including discussion related to compliance to what specific codes
standards, and references that are used for the design.
Gas and Chemical Storage Distribution Systems: compressed gas design,
including discussion related to compliance to what specific codes
standards, and references that are used for the design.
Provisions and Control of Personnel Access: overall workplace personnel
protection provisions, including discussion related to fall heights &
protection, safe touch temperatures, security fencing, mechanical &
electrical equipment lockout provisions including discussion related to
compliance to what specific codes, standards, and references that are used
for the design.
Provision and Control of Personnel Access: mechanical & electricaguarding provisions, including discussion related to personnel access
workplace maintenance provisions and what specific codes, standards, andreferences that are used for the design.
Design of Emergency Eye Wash / Shower Stations: provide a summary
and a map of where all emergency eye wash and shower stations are
located throughout the plant, acknowledge that the site is meeting the
minimum requirements defined in this document for location and type.
Design of Work Areas for Appropriate Noise Levels: near field noise
compliance means, plus health & safety considerations from workplace
personnel exposure.
Design of Lighting and Power: lighting provisions and groundingprotection including discussion related to compliance to what specific
codes, standards, and references that are used for the design.
Fire Protection: design details, including discussion on which plant areasare covered by what type of fire protection / suppression, portable fire
extinguishers and locations and rating of fire rated walls; plus integration
8/10/2019 09_safetyengineering
5/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.5
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
into hazardous area classification development and plant emergency egress
means.
9.1.3 Acronyms and Definitions of Key Terms
9.1.3.1 Acronyms
AE - Architect Engineer
BOP Balance of Plant
EN European Normative standard
EPC Entity responsible for Engineering / Procuring / Constructing the plant
GT Gas Turbine
GE DBD General Electric Design Basis Document
HRSG Heat Recovery Steam Generator
IEC International Electrotechnical Commission
LEL Lower Explosive Limit
MSDS Material Safety Data Sheet
PPE Personal Protective Equipment
PPM Parts Per Million
ST Steam Turbine
9.1.3.2 Definitions
Confined or Enclosed Spaces (extracted from OSHA 1910.146) means any
space that:
1. Is large enough and so configured that an employee can enter andperform assigned work; and
2. Has limited or restricted entry or exit (such as tanks, vessels, silos
storage bins, hoppers, vaults and pits); and
8/10/2019 09_safetyengineering
6/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.6
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
3. Is not designed for continuous employee occupancy
Permit required confined space means a confined space that has one or more
of the following characteristics:
1. Contains or has the potential to contain a hazardous atmosphere (e.g. is
subject to the accumulation of toxic or flammable contaminants or has
an oxygen deficientatmosphere);
2. Contains a material that has the potential for engulfing an entrant (e.ggrain, sawdust, sand);
3. Has an internal configuration; in which an entrant could be trapped or
asphyxiated by inwardly converging walls or a floor that slopesdownward and tapers to a smaller cross section; or
4. Contains any other recognized serious safety or health hazard.
8/10/2019 09_safetyengineering
7/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.7
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
9.2 Hazardous Area Classification
The Hazardous Area Classification evaluates all the locations within the
power plant and classifies them based on the potential existence of hazardous
properties due to the presence of flammable vapors, liquids, or gases, or
combustible concentrations of dust or fibers. This classification shall be done
in accordance to applicable standards. It is to be cautioned that Internationa
Standards and specific Country Standards may differ from the NFPA
Standards followed in the U.S.
To create a Hazardous Area Map for US projects refer to:
United States Codes and Standards
NFPA 70 National Electrical Code (NEC)
NFPA 497 Recommended Practice for the Classification of FlammableLiquids, Gases, or Vapors and of Hazardous Locations for Electrical
Installations in Chemical Process Areas
API 500 Recommended Practice for Classification of Locations forElectrical Installations At Petroleum Facilities Classified As Class 1,
Division 1 and Division 2
API 505 Recommended Practice for Classification of Locations forElectrical Installations At Petroleum Facilities Classified As Zone 0, Zone
1 and Zone 2
To create a Hazardous Area Map for European Union projects refer to:
European Codes and Standards
IEC / EN 60079-10 - Electrical Apparatus for Explosive Atmospheres -
Classification of Hazardous Areas
EN 1127-1 Explosion prevention and protection
94/9/EC, Directive 94/9/EC of the European Parliament and the Council of23 MARCH 1994 on the Approximation of the Laws of the Member
States Concerning Equipment and Protective Systems Intended for the Use
in Potentially Explosive Atmospheres. (ATEX)
8/10/2019 09_safetyengineering
8/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.8
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
IP-15 Institute of Petroleum Area Classification Code for Petroleum
Installations (Part 15 of the Institute of Petroleum Model Code of Safe
Practice in the Petroleum Industry)
IGE SR 25 Hazardous Classification of Natural Gas Installations
This area classification shall include associated interconnections and
equipment designed by the AE/EPC as well as the GE supplied equipment
All interconnections and equipment with the potential to create a hazard shall
be clearly indicated on a comprehensive site map indicating size, location, and
elevation of the hazard created. Special consideration shall be made for
equipment not provided by the AE/EPC. The considerations for this
equipment shall include:
1. Ensuring equipment is rated for use as located (e.g. rated equipment ina hazardous area).
2. Identifying the hazardous area(s) it may create and ensuring that non-rated equipment (not suitable for hazardous zone) is not located within
these identified hazardous areas .
3. Ensuring that inlets to fan ventilated enclosures / compartments
cannot draw potentially hazardous atmospheres into the enclosure /
compartment.
NOTE: specific hazardous area dimensions listed in this document are based
on US Standards.
This classification should include, as a minimum, any of the items below that
are associated with the particular project:
Natural Gas: Gas Turbine Enclosure, Fuel Gas Module/Compartment,
Flow Metering Tube, Piping, Filter/Separator, Heater(s), Scrubber,
Pressure Reducing Station, Fuel Gas Booster Compressor, HRSG duct
burner or auxiliary Boiler.
Syn-gas (gas derived from coal or residuals): Syn-gas Compartment, Gas
Turbine Enclosure, piping, processing equipment.
Hydrogen: Generator, generator shaft seals, detraining enlargement vent,Collector Cab/Compartment, hydrogenstorage bottles, hydrogen manifold,
battery compartment/room, Load Compartment.
Liquid Fuel Vapor/Mist: Liquid fuel Module, Gas Turbine Enclosure,
piping, processing equipment, storage and drains tank(s).
8/10/2019 09_safetyengineering
9/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.9
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
Lube Oil Vapor/Mist: Mist Eliminator discharge, high-pressure
piping/tubing, Accessory Module, Lube Oil Skids with Lift Oil.
Mechanical Connections (Non-Welded) in the above systems.
Ventilation exhausts or vent discharges for the above systems.
9.2.1 Hazardous Area Philosophy Document
A Hazardous Area philosophy document shall be created. It defines the
assumptions used to create the Hazardous Area Map. Each area of the
Hazardous Area Map shall have its own assumption criteria that includes, but
is not limited to, the following items:
Ventilation (e.g. air changes per hour / flow for area)
Hazardous gas / liquid vapor (e.g. natural gas, hydrogen)
Volume / quantity of release of gas / liquid vapor - this can be duringnormal modes of operation or during a credible failure scenario
Interconnection points (e.g. flanges, welds, compression fittings)
All areas should have dimensions in x, y, and z directions and / or defined
shape
Identification of compartments and components that are to be located inareas outside of Hazardous Areas.
9.2.2 Hazardous Area Map
The Hazardous Area Map is a pictorial representation of the hazardous areas
as defined in the philosophy documentation (9.2.1). A Hazardous Area is an
area with the potential to contain hazardous atmosphere due to the presence of
gas / liquid vapor / liquid mist at an ignitable concentration. The Hazardous
Area map is required to have the following features:
Plan and elevation views
Each area shall have dimensions in x, y, and z directions and / or definedshape
Approximate locations for all field installed pipe vents. The Hazardous
Area bubble can either be shown directly on the Hazardous Area Map or
its dimensions can be tabulated in an attachment.
8/10/2019 09_safetyengineering
10/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.10
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
Restricted areas are those areas that must be isolated from potentially
hazardous leak sources. Items that are not rated for use in a Hazardous Area
must be in a Restricted Area. There shall not be any potential for a Hazardous
gas / liquid vapor to exist in a Restricted Area. Examples of Restricted Areas
include:
Compartment air inlets as defined in the Ventilation Design section of thisdocument
Areas where non-rated components external to the compartments arelocated (as a general rule external components are non-rated for use in a
Hazardous Area)
Any other areas that may reasonably be expected to include a source of
ignition (e.g. welding area).
Once the site Hazardous Area Map has been compiled, a review shall be
conducted to verify that the equipment located in the hazardous areas is
properly rated, and address any non-compliance issues. This may require
relocating either equipment that creates a hazard or the non-rated equipment,
or upgrading the components affected by the hazards.
Examples of different hazardous area map views can be seen in FIGURES 1, 2
and 3.
8/10/2019 09_safetyengineering
11/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.11
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
FIGURE 1 SAMPLE: Isometric View of Accessory Module Hazardous
Areas Created During Normal Operation.
FIGURE 2 SAMPLE: End View of Accessory Module Hazardous
Areas Created at Gas Compartment Doors During Ventilation Shut
Down
8/10/2019 09_safetyengineering
12/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.12
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
FIGURE 3 SAMPLE: Pipe Vent Termination With High Pressure Flow
of Gas Indicating Large Release Source.
8/10/2019 09_safetyengineering
13/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.13
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
9.2.3 Design of Equipment Located in Hazardous Areas
For equipment located in a hazardous area,
Properly locate electrical wiring conduit seal fittings in the conduit runsper the NEC, and install the manufacturers recommended conduit sealer
in the fitting
Pressurize and vent electrical junction boxes that potentially contain arcing/ sparking devices.
9.2.4 Hazard Identification Reference
The tables and figures in this section provide a reference for potential areas
within the basic designs of a typical power plant that may be deemed
hazardous due to the potential for:
Gas / liquid vapor /liquid mist resulting in a fire/explosion
Chemical releases
Electrical energy release
Note: not all of the hazards listed above are required to be identified on a site
Hazardous Area Map as identified by NFPA or EN 60079-10 (IEC 79-10)Other hazards may need to be considered depending on the applicable codes
for example, hot surfaces.
8/10/2019 09_safetyengineering
14/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.14
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
TABLE 1 Hazard Identification Reference associated with Figures 4, 5, and 6
Chemical Electrical Fire / Explosion
1 HRSG Duct Burner System X2 Exhaust Enclosure X
3 GT Turbine Compartment X
4 Liquid Fuel / Atomizing Air Module X
5 Gas Valve Module / Compartment X
6 Fuel Gas Performance & Start-Up Heaters X
7 Coalescing Filter / Separator X
8 Fuel Gas Scrubber X
9 Fuel Gas Pre-Heater X
10 Filter Separator X11 Gas Drain Tank X
12 GT False Start Drains Tank X
13 ST HPU Module (not shown) X
14 Generator X X
15 H2 Generator Bottle Storage & Manifold (not shown) X
16 Collector Cab X X
17 Collector Enclosure X
18 Generator Terminal Enclosure (GTE) X X
19 LCI & Excitation Module X20 Battery Room(s) GT (end of the PEECC), ST X X X
21 ST Electrical Room X X
22 Oil Filled Transformers X X
23 Switch Yard (not shown) X
24 Biofouling Chemicals X
25 Water Treatment Chemicals X
26 Waste Neutralization Tank X
27 Fuel Oil Storage Tank X
28 Fuel Gas Flow Metering Tube X
FIGURES 4, 5, and 6 are Hazard Identification Maps that identify where the
chemical, electrical, and fire / explosion hazards outlined in the above table
are located. These figures are representative of a typical Combined Cycle
power plant with 2 7FA Gas Turbines and a Steam Turbine, but elements
depicted can be applied to any plant.
8/10/2019 09_safetyengineering
15/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.15
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
FIGURE 4 Chemical Hazard Identification Map.
8/10/2019 09_safetyengineering
16/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.16
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
FIGURE 5 Electrical Component Hazard Identification Map.
8/10/2019 09_safetyengineering
17/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.17
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
FIGURE 6 Fire / Explosion Hazard Identification Map.
The locations of potential Fire / Explosion hazards shown in this figure are for
reference only.. This figure does not meet the requirements of a Hazardous
Area Map as required by either the US NFPA requirements defined in NFPA
70 (NEC) and NFPA 497 or the European Union requirements as defined by
ATEX and EN 60079-10.
8/10/2019 09_safetyengineering
18/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.18
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
TABLE 2 Additional Hazard Identification References (Not shown on Figures
4, 5, and 6)
Chemical Electrical Fire / Explosion
Generator Line Accessory Compartment (GLAC) X
Generator Neutral Accessory Compartment (GNAC) X
Switch Gear / Medium Voltage Cell X
GT Electrical Room / PEECC / TCC / MCC X X
Water Wash Skid X
Closed Cooling Water System (closed w/ antifreeze) X
Fuel Gas Shut of Valve and Vent Valve skid (SSOV) X
8/10/2019 09_safetyengineering
19/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.19
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
9.3 Building and Compartment Ventilation Design
Building and compartment ventilation is defined as airflow through any
building or compartment of a power plant. GE uses a variety of compartment
ventilation methods: positive pressure (forced draft), negative pressure
(induced draft), and natural/convective.
Positive pressure occurs when air is pushed into the building or
compartment by ventilation fans, creating a higher pressure inside the
building or compartment than the ambient pressure.
Negative pressure occurs when air is drawn out of the building orcompartment by ventilation fans, creating a lower pressure inside of the
building or compartment than the ambient pressure.
Natural/convective ventilation is created by wind, temperature or gasdensity differentials that cause the air within the building or compartment
to move.
Ventilation air may enter a building or compartment through a variety of
inlets. An inlet is any opening into a building or compartment through which
air may enter. This includes, but is not limited to, ducts and damper covered
openings, doorways, windows that open, and easily opened access panels
The air drawn in through the inlet shall be safe air, which does not contain
hazards. Safe air is defined as:
Air with no significant contamination by flammable gasses or vapors thatmight be harmful to either the equipment or personnel (greater than 25%
LEL Lower Explosive Limit per US-NFPA and EU guidance). Note: US
requirement specifies not greater than 10% LEL for personnel exposure.
Air that is not significantly above the ambient air temperature.
Ventilation air exits from a building or compartment through exhaust outlet(s)
Precautions must be taken when establishing exhaust outlet locations if there
are potential hazards in the exhaust air from power plant buildings and
compartments. The potential for hazards in exhaust air is dependent upon
what is contained within the building or compartment being ventilated. For
example:
Buildings and compartments containing hot equipment, in excess of 60C
(140F), use the ventilation for cooling purposes; exposure to the elevated
8/10/2019 09_safetyengineering
20/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.20
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
temperature of this exhaust air may potentially harm personnel or
equipment. Note: this may include steam.
Buildings or compartments containing parts of a fuel system have thepotential for fuel leaks from equipment and the piping system, which may
contaminate the ventilation air. The ventilation exhaust of each building
or compartment, along with the estimated potential concentration of fuel in
the ventilation duct, should be factored into the location/orientation of the
building or compartment exhaust outlet(s). The potential fuel sources
may include natural gas, syn-gas, liquid fuel vapor/mist, or other
alternative fuel source.
Buildings or compartments containing high-pressure oil lines have thepotential for lube oil mist or vapor to leak into the building or
compartment, which may contaminate the ventilation air. The ventilationexhaust of each building or compartment along with the estimated
potential concentration of lube oil vapor or mist in the duct should be
factored into the location/orientation of the building or compartment
exhaust outlet(s).
Buildings or compartments containing hydrogen system equipment or DCbatteries have the potential for hydrogen to accumulate in the building or
compartment, which may contaminate the ventilation air. The ventilation
exhaust of each building or compartment along with the estimated
potential concentration of hydrogen in the enclosed space should be
factored into the location/orientation of the building or compartmentexhaust outlet(s).
Buildings or compartments containing a CO2fire suppression system shallnot exhaust into an enclosed area that could present a personnel hazard.
For indoor installations, the compartment exhaust outlet(s) must be taken
outside the main building.
Buildings or compartments that serve as maintenance areas wherewelding, cutting or other fume producing processes take place shall not
circulate ventilation exhaust from those maintenance areas into the inlet
ventilation of other non-maintenance areas located within the same
building.
Turbine-Generators installed within buildings have additional ventilation
considerations. Each compartment placed inside of the building needs to be
evaluated for the requirements of both its inlet and exhaust air, for example:
When installing compartments within a building with the associatedventilation fans mounted external to the building, the location of the
8/10/2019 09_safetyengineering
21/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.21
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
ventilation fan must be considered carefully with respect to the impact
created by this exhaust. (e.g. away from the face of the inlet filter house,
personnel access areas, non-rated equipment, etc.).
When installing compartments within a building with the ventilation fansmounted internal to the building, the location of the outlet duct termination
must be considered carefully with respect to the impact created by this
exhaust (e.g. away from the face of the inlet filter house, personnel access
areas, non-rated equipment, etc.).
Compartments with temperatures significantly above ambient should bereviewed for location of the ventilation exhaust outlet to ensure that the air
does not exhaust into personnel access areas or other ventilation inlets.
Also, impact on the overall building ventilation design must accommodate
the additional heat load if this exhaust air is released inside of the building,as some compartments may draw inlet air from inside of the building.
Note: For each project, the specific model of GE gas turbines and their
accessories must be reviewed since GE designs vary.
9.3.1 Design for Gas Turbine Compartment VentilationExhaust
Potential ventilation exhaust hazards include: high temperature and / or the
presence of any of the following in the ventilation exhaust: natural gas, syn-
gas, liquid fuel vapor, alternative fuel gas or vapor/mist, lube oil mist orvapor, and CO2. Refer to the project specific GE Gas Turbine Heating &
Ventilation Schematic (0426) for design requirements.
9.3.2 Design for Fuel Gas Module (Compartment) VentilationExhaust
Potential ventilation exhaust hazards include: high-temperature and / or the
presence of any of the following in the ventilation exhaust: natural gas
hydraulic oil vapor or mist, and CO2. Refer to the project specific GE Gas
Turbine Heating & Ventilation Schematic (0426) for design requirements.
9.3.3 Design for Generator and Collector Cab Ventilation
Potential ventilation exhaust hazards include: high-temperature and / or the
presence of any of the following in the ventilation exhaust: lube oil vapor or
mist and hydrogen (hydrogen generators only). Refer to GE Generator
Equipment Documentation for design requirements.
8/10/2019 09_safetyengineering
22/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.22
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
For indoor installations of hydrogen generators, the building design must
prevent the accumulation of hydrogen either by natural or forced ventilation of
ceiling / roof high points. The ventilation flow capacity must be sized for
the maximum generation rate of hydrogen to preclude gas build-up.
9.3.4 Design for Load Compartment Ventilation (whenapplicable).
Potential exhaust hazards include: high-temperature and /or the presence of
hydrogen in the ventilation (when attached to hydrogen generators only)
Refer to the project specific GE Gas Turbine Heating & Ventilation Schematic
(0426) for design requirements.
For indoor installations with hydrogen generators, either the ventilation mustbe taken outside the building or the building design must prevent the
accumulation of hydrogen either by natural or forced ventilation of ceiling /
roof high points. The ventilation flow capacity must be sized for the
maximum generation rate of hydrogen to preclude gas build-up.
9.3.5 Design of Battery Room Ventilation
Hydrogen is the only potential exhaust hazard. Hydrogen evolution occurs
during battery charging. Battery locations include: the PEECC, steam turbine
UPS batteries, and plant facilities batteries.
Battery room design must prevent the accumulation of hydrogen by ventilation
of ceiling / roof high points. Irrespective of the type of ventilation used
(convection or forced), flow requirements must be sized for the maximum
generation rate of hydrogen. In the case of forced ventilation, the ventilation
system shall have a redundant fan system with a method for starting the back-
up fan if the primary fan should fail. A means for detecting hydrogen
accumulation may be required by local codes or standards.
9.3.6 Design for Liquid Fuel/Atomizing Air Compartment
Ventilation
Potential ventilation exhaust hazards include the presence of any of the
following in the ventilation exhaust: liquid fuel vapor / mist and CO2. Refer
to the project specific GE Gas Turbine Heating & Ventilation Schematic
(0426) for design requirements.
8/10/2019 09_safetyengineering
23/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.23
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
9.3.7 Turbine-Generator Building
Potential exhaust hazards include: high-temperature, lube oil vapor / mist and
hydraulic fluid vapor / mist, fuel gases and liquid fuel vapor / mist (if Gas
Turbine is located indoors) and hydrogen (when hydrogen generator is
included).
The turbine building ventilation system design must consider the inlet and
outlet requirements under all potential modes of operation (e.g. minimum
allowable number of building fans in operation) and ambient conditions (e.g
cold winter or hot summer temperatures) to ensure that the individual
compartments / modules have sufficient ventilation to meet their safe
operating requirements.
Refer to GE DBD Mechanical Systems Documentation for general designrequirements.
9.3.8 Design for Control Room and Office Area Ventilation
Control Room and Office Areas are intended for continuous human
occupancy. These areas are not designed for hazardous air. Ventilation
design must draw air in from a safe area outside the building. The air must
be free from contaminant levels that could be harmful to human health.
When these areas are part of a building that has the potential to contain
hazardous air, there must be a separate ventilation system that draws in airfrom outside the building, and a slight positive pressure must be maintained
inside the office or control room areas.
9.3.9 Design for Exhaust Compartment Ventilation
Potential ventilation exhaust hazards include: high temperature and / or the
presence of CO2 in the ventilation exhaust. Refer to the project specific GE
Gas Turbine Heating & Ventilation Schematic (0426) for design requirements.
8/10/2019 09_safetyengineering
24/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.24
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
9.4 System Vent Design
Vents are defined as piping or tubing that discharge to the atmosphere. Vent
lines can either be isolated by a manual or automatic valve, or be continuously
open. Common examples are vent lines connected to return lines, open
funnels, drains, tanks, chemical storage tanks, pressure relief valves, gas
turbine gas fuel stop-ratio valve cavity (P2) vents, valve stem packing leak-off
tubing, hydrogen casing purge, hydrogen scavenging, hydrogen detraining
enlargements, and stator cooling water system vents.
For all vents, the following must be shown on the P&ID:
Whether of not the vent is a source of hazardous release
What type of release it is
Reference to the Hazardous Area documentation for all vents that
create a hazardous area as defined in the Hazardous Area
Classification section of this document.
All hazardous vents shall be routed individually to a safe discharge area based
on the potential hazards. Potential areas to avoid are:
Personnel access ways (e.g. platforms, walkways)
Arcing & sparking devices
Maintenance areas (e.g. grinding, welding)
Designated smoking areas
Note: Information denoted in blue with square brackets [ ] in the below
sections refers to the European Union classification for hazardous area
designation using Zone and Group, which is different from the US Class
Division, Group system.
9.4.1 Fuel Gas Vents
All fuel gas vents shall be individually routed and discharged to a safe areaclear of all ventilation inlets, non-rated electrical devices, other potential
ignition sources (e.g. hot components, furnaces, etc.), and walkways /
personnel access areas. Occasional releases from a small vent of a known
volume (e.g. block and bleed vent valve) has a minimum Class I, Div 1, Group
D [Zone 1, Group IIA]1.5 m. (5 ft) spherical radius hazardous area inside of a
Class I, Div 2, Group D [Zone 2, Group IIA]3.0 m (10 ft) spherical radius
hazardous area around the vent terminus. Large releases will have a larger
8/10/2019 09_safetyengineering
25/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.25
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
hazardous area based on the pressure and amount of gas released (e.g. gas
compartment/module strainer blow-down connection (FG2)). Pressure Relie
lines shall not be ganged with each other or any other vent lines. Do no
route fuel gas vents to any drains tanks.
Note: Follow ALL notes and recommendations found on the GE Fuel Gas
System Schematic (0422) for additional information on routing of field run
vents, this includes requirements for vent lines to be run individually
recommended vent discharge design per GEK 110743 and hazardous area
size/shape at the discharge of the vent.
9.4.2 Purge Vents
All purge vents shall be individually routed and discharged to a safe area clearof all ventilation inlets, non-rated electrical devices, other potential ignition
sources (e.g. hot components, furnaces, etc.), and walkways / personnel access
areas. Occasional releases from a small vent of known volume (e.g. block and
bleed vent valve) that are purging fuel gas piping has a minimum Class I, Div
1, Group D [Zone 1, Group IIA]1.5 m (5 ft) spherical radius hazardous area
inside of a Class I, Div 2, Group D [Zone 2, Group IIA]3.0 m (10 ft) spherical
radius hazardous area around the vent terminus.
Note: Follow ALL notes and recommendations found on the GE Purge Air
System Schematic (0477) for additional information on routing of field run
vents, this may include requirements for vent lines to be run separately,recommended vent discharge design per GEK 110743 and hazardous area
size/shape at the discharge of the vent.
9.4.3 Hydrogen Vents
All Hydrogen vents shall be individually routed to a safe area clear of all
ventilation inlets, non-rated electrical devices, other potential ignition sources
(e.g. hot components, furnaces, etc.), and walkways / personnel access areas
Occasional releases from a small vent of known volume has a minimum Class
I, Div 1, Group B [Zone 1, Group IIC]1.5 m (5 ft) spherical radius hazardous
area inside of a Class I, Div 2, Group B [Zone 2, Group IIC]3.0 m (10 ft)spherical radius hazardous area around the vent terminus (Note: this guidance
is per NFPA 497 and is superceded by any GE provided hazardous area
information). Pressure Relief lines shall NOT be ganged with each other or
any other vent lines.
Note: Follow ALL recommendations found on the GE Customer drawings
provided for the Generator Accessories (potentially Generator Gas System
8/10/2019 09_safetyengineering
26/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.26
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
Installation Design Specification 357A2258 and Specification, BDE Vent
Piping 358A4741) for additional information on routing of field run vents, this
may include requirements for vent lines to be run separately, recommended
vent discharge design and hazardous area size/shape at the discharge of the
vent.
9.4.4 Lube Oil Vents
Lube oil mist and vapor shall be exhausted outside of the Turbine Building
Lube oil mist and vapors should be considered potentially hazardous and this
should be taken into account when locating the terminus of the lube oil
demister vent. The vent from the lube oil mist eliminator has a minimum
Class I, Div 2, Group D [Zone 2, Group IIA] 1.5 m (5 ft) spherical radius
hazardous area. Note: depending on the efficiency of the technology used foroil mist elimination, the concentration of oil released in parts per million
(ppm) of will vary. This may result in this area not requiring a hazardous
classification for oil.
Note: Follow ALL notes and recommendations found on the GE Lube Oi
System Schematic (Gas Turbine: 0416, and Steam Turbine VD01L) for
additional information on routing of field run vents, this may include
requirements for vent lines to be run separately and hazardous area size/shape
at the discharge of the vent.
9.4.5 Steam Vents
All Steam vents shall be routed to an area away from personnel access areas to
allow for safe release of the steam. Recommendations include locating
silencer and vent discharges away from any personnel access areas including
floors, platforms, ladders or stairs at a minimum of 6.0m (20 ft) horizontally
and 3.0 m (10 ft) vertically and situated in such a manner that the vents do not
direct steam towards stairs, ladders, walkways, platforms, maintenance areas
and/or heat detection devices.
9.4.6 Liquid Fuel Vents
All liquid fuel oil vents and open funnels shall be routed to a safe area clear of
all ventilation inlets, non-rated electrical devices, other potential ignition
sources (e.g. hot components, furnaces, etc.), and walkways / personnel access
areas. The vent from a liquid fuel oil storage / drains tank has a minimum
Class I, Div 2, Group D [Zone 2, Group IIA]0.5 m (0.5 ft) spherical radius
hazardous area. Note: Depending on the design of the piping to the liquid
8/10/2019 09_safetyengineering
27/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.27
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
fuel False Start Drain Tank, this area can be larger based on the fail open
properties of the GE inline drain valves, which may allow the drain line to be
pressurized during GT operation.
8/10/2019 09_safetyengineering
28/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.28
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
9.5 Gas and Chemical Storage and Distribution Systems
These sections address design requirements for chemical storage areas and
compressed gas storage areas. This section does not cover design standards
for bulk fuel storage; this is covered in the GE DBD Mechanical Systems
Documentation. Typical chemicals that need to be addressed include aqueous
ammonia, anhydrous ammonia, anionic and cationic resins, ethylene glycol,
phosphate ester (a.k.a. Fyrquel), fire suppression foam, propylene glycol
sodium hypochloride, sodium hydroxide, sodium sulfite/sulfate, sulfuric acid
and various water treatment chemicals. Compressed gases, which need to be
considered typically include: Nitrogen, Hydrogen, and Carbon Dioxide (CO2)
Storage areas for chemicals and compressed gases must be provided with
appropriate signs. Ventilation of chemical storage areas shall be inaccordance with OSHA 29 CFR 1910, NFPA, Uniform Fire Code and / or
applicable local requirements.
The location of chemical storage areas shall be shown on the appropriate
drawings including the General Arrangement, Plot Plan, and, for all areas
containing flammable/explosive liquids or gases, on the Hazardous Area Map.
9.5.1 Storage and Distribution of Gases
Compressed gas systems for power plants in general fit into the following gas
categories and uses:
Carbon Dioxide Generator purge and Fire Suppression
Compressed Air Instrument and Service air
Gas Fuel Fuel for Gas Turbine, auxboiler and / or HRSG
supplemental firing
Hydrogen Generator fill and makeup for cooling
Nitrogen HRSG / BOP equipment blanketing and various system
purges
These systems will be under high pressure and require careful considerations
during design, construction and operation. The systems and components shal
be designed in accordance with ASME Boiler and Pressure Vessel Code
Section VIII and ASME Power Piping Code 31.1. For European Community
Countries the local pressure code (or already mentioned ASME Code)
97/23/EC, the Pressure Equipment Directive (PED) and 87/404/EEC Simple
Pressure Vessels shall apply. Additionally all systems shall address container
8/10/2019 09_safetyengineering
29/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.29
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
specifications; safety relief devices; design of piping, tubing and fittings
ventilation; and heating. Systems shall be tested and proved to be tight at
maximum operating pressure. Facilities design shall comply with OSHA
1910 Subpart M. Non-US projects shall conform to either the US Codes or
the national codes and standards specified by that country per contract
requirements. Proper ventilation is required for processing and storage areas
to mitigate any combustion and/or asphyxiation potential.
Each one of these systems may contain the following:
High pressure gas storage cylinders
High pressure safety relief devices
Gas pressure control valves
Compressors
Extensive runs of interconnecting piping
Storage and handling facilities
Gas venting requirement
In general equipment and cylinders should be protected against mechanical
damage. Racks should be provided or other means to hold them securely. Ful
bottles should be kept separately from empty bottles. Caution signs should
address depressurizing systems before disassembly. There should be loca
gauges for the technician to verify depressurization of the system. Cylinders
should be located where they will not be exposed to excessive heat. Outdoor
installations should include a roof for solar radiation protection.
Bulk storage facilities should be located in the plant yard away from the main
structure. Limited numbers of cylinders are acceptable in main building areas.
Safety shutoff valves between bulk hydrogen storage facilities and the
regulating valve manifold assembly is recommended per NFPA 850,
paragraph 5-7.1.
GE specification 357A2258, Generator gas System Design Specification
provides guidelines for the design and installation of CO2 and Hydrogen gassupply systems for Generator Applications.
Carbon dioxide (CO2), Hydrogen (H2), and Nitrogen (N2) shall be stored in an
outside area, inside an enclosure with forced or otherwise wellventilation, or
inside an enclosure that precludes the unrestricted entrance of personnel
Enclosed compressed gas storage areas shall be designed to address exposure
to potentially hazardous or asphyxiating atmospheres through adequate forced
8/10/2019 09_safetyengineering
30/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.30
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
ventilation, gas monitoring and warning systems, or a design that precludes
entrance into the gas storage area. Compressed gas storage areas shall be
provided with means of securing cylinders.
CO2 used for generator purge gas must be stored indoors or in a compartment
that maintains a temperature above 10C (50F). Refer to GE Generator
Station Designers Handbook, C411 Document for specific project
requirements. If unventilated, this compartment should be sized to store the
CO2 bottles only and preclude the entry of personnel. Refer to GE DBD
Mechanical System Description for design requirements of storage area.
Hydrogen storage enclosures shall be well ventilated enclosure, as defined per
NFPA 497 for hydrogen storage, is one that has any 3 of the possible 5 sides
(4 walls and roof) open, that arrangement allows for ventilation equivalent to
the equipment being outdoors.
CO2storage used for Fire Suppression systems shall have signs / monitoring
of any pits into which the CO2 can settle that meet the recommendations of
NFPA 12.
9.5.2 Design Considerations for Gas Fuel ConditioningEquipment
The design of an outdoor installation shall include a risk assessment based on
the probability of a gas leak and the possible consequences to personnel safetyand equipment safety (e.g. Classification of Hazardous Locations published
by Institution of Chemical Engineers Rugby, Warwickshire England 1990
authored by AW Cox, FP Lees, and ML Ang or British Standard IGE SR 25
Hazardous Classification of Natural Gas Installations). All Gas Turbine
Steam Turbine, and Generator equipment is designed to be installed in a safe
area regardless of the hazards that equipment may generate. Refer to GE DBD
Mechanical System documentation for design requirements.
9.5.3 Chemical Storage
A variety of chemicals are used throughout the power plant. Each chemica
has specific requirements for safe handling, storage, and use.
The main chemicals in use are:
Acids for demineralizer regeneration, and demineralizer waste
neutralization, e.g. sulfuric acid
8/10/2019 09_safetyengineering
31/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.31
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
Caustics for demineralizer regeneration and demineralizer waste
neutralization, e.g. sodium hydroxide
Biocides for circulating water system treatment, e.g. sodiumhypochlorite
Ammonia, phosphates and carbohydrazide for cycle water treatment
Refer to the chemicals MSDS for details. These requirements shall be taken
into consideration when designing various chemical storage areas
Additionally there may be National or Local requirements that will mandate
additional requirements be addressed for various chemicals. For example
Ammonia storage in the US must comply with 40 CFR 68: General Guidance
for Risk Management Programs. Chemical storage areas shall be provided
with secondary adequate containment sized per the specifications in the GE
DBD Environmental Engineering Systems Documentation. Materials used for
construction of containment areas and associated equipment shall be
compatible with the chemicals that will be stored in that area. Separate
containment areas shall be designed for incompatible chemicals (i.e. acids and
bases). Ventilation shall be provided as a means of controlling excessive
temperature build-up in storage areas. To comply with NFPA 497 and loca
fire codes, specific fire protection measures for storage of combustible and
flammable materials shall be addressed. Design specifications for systems
including storage and piping which use highly hazardous chemicals (as
defined by 29 CFR 1910.119 Appendix A, or other appropriate nationa
standards) - shall include safety measures such as interlocks, detectionsystems, and suppression systems. Additional requirements may apply to the
use of highly hazardous chemicals.
8/10/2019 09_safetyengineering
32/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.32
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
9.6 Provision and Control of Personnel Access
9.6.1 Provision of Access to Work and Maintenance Areas
Safe access and working platforms shall be provided for all work and
maintenance areas. A stairway or ladder must be provided at all worker points
of access where there is a break in elevation of 0.5 m (19 in) or more, and no
ramp, runway, embankment, or personnel hoist is provided. Access via stairs
or ladders shall be provided for access from one structure level to another
where operations necessitate regular travel between levels, and for access to
operating platforms for any equipment that requires routine attention. Fixed
stairs or ladders shall also be provided where access to elevations occurs daily
or during each shift for such purposes as gauging, inspection, regular
maintenance, etc.
9.6.2 Design for Provision of Fall Protection
Areas and equipment with work/maintenance areas higher than 1.2 m (4 ft)
above grade, and for which permanent means of fall protection (e.g. standard
railings) are not feasible or are inappropriate, shall have a means of anchoring
a personnel fall protection system. Anchors to which personal fall arrest
equipment is attached shall be capable of supporting at least 2270 kg (5,000
lbs) per employee attached or meet the specific load requirements for anengineered fall arrestment system under OSHA 29 CFR 1910.66 or other
applicable codes / laws. The location of the anchorage point should also
consider hazards presented by obstructions in the potential fall path of the
employee. OSHA 29 CFR 1910.23.
9.6.3 Design of Platforms, Walkways, Stairways, and Ladders
The design of platforms, walkways, ladders, and stairways shall conform to
NFPA 101 and, OSHA 29 CFR 1910 for US projects. Non-US projects shal
conform to either the US codes or the national codes and standards specified
by that country per the contract requirements, such as EN Standards forEuropean Community Countries. Note: requirements for the European
Community are provided in blue and square brackets [ ] per the following
specifications: Pr-EN 12437-2, 3, 4, EN-131-2, EN 292-1, EN-292-2, EN 353-
1. These design requirements are to ensure safe and easy access to al
components and required access areas in a safe manner by personnel. Refer to
the GE DBD Civil / Structural System documentation for design requirements
8/10/2019 09_safetyengineering
33/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.33
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
9.6.3.1 Platforms
Platforms shall be designed and installed in accordance with 29 CFR 1910.23
Platforms are designed to serve as a working space for persons elevated abovethe surrounding floor or ground, including balconies or walkways provided for
access to machinery and equipment. All platforms where a potential fall of
over 1.2 m (4 ft) [EN: 0.5 m.] can occur shall be guarded with a standard
guardrail system.
Standard guardrail systems shall consist of a top rail, intermediate rail, and
posts, and shall have a vertical height of 1.0 m (3.5 ft) [EN: 1.1 m]nomina
from upper surface of top rail to floor, platform, runway, or ramp level. The
top rail shall be smooth-surfaced throughout the length of the railing. The
intermediate rail shall be approximately halfway between the top rail and the
floor [EN: 0.5 m], platform, runway, or ramp. The ends of the rails shall nooverhang the terminal posts except where such overhang does not constitute a
projection hazard.
A standard toe-board shall be provided whenever the platform is located
above an area where people may pass or where objects may fall. The toe-
board shall be 100 mm (4 in) nominal in vertical height from its top edge to
the level of the floor, platform, runway, or ramp. It shall be securely fastened
in place and with not more than 6.4 mm (0.25 in) clearance above floor level
It may be made of any substantial material either solid or with openings not
over 25 mm (1 in) in greatest dimension.
Pipe railings, posts, top and intermediate railings shall be at least 38 mm (1.5
in) nominal diameter with posts spaced not more than 2.5 m (8 ft) on centers
[EN: 1.5 m]. The anchoring of posts and framing of members for railings of
all types shall be of such construction that the completed structure shall be
capable of withstanding a load of at least 90 kgs (200 lbs) applied in any
direction at any point on the top rail [EN: Note: Testing of Guard Rails
Horizontal deflection of handrail shall not exceed 30 mm when loaded for a
minute with a force equal of 300 N times the distance in meters between the
stanchions. The measurement must be done at the junction point between
stanchions and the handrail and repeated halfway between the posts].
Walking surfaces shall be nominally level. The slope of a walking surface in
the direction of travel shall not exceed 1 to 20 (1:20) unless the ramp
requirements of NFPA 101 are met. The slope perpendicular to the direction
of travel shall not exceed 1 to 48 (1:48). Abrupt changes in elevation of
walking surfaces shall not exceed 6.4 mm (0.25 in)[EN 4 mm]. Changes in
elevation exceeding 6.4 mm (0.25 in), but not exceeding 13 mm (0.5 in), shall
8/10/2019 09_safetyengineering
34/67
8/10/2019 09_safetyengineering
35/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.35
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
platforms shall be provided for each 6.1 m (20 ft) of height. Each ladder
section shall be offset from adjacent sections. Where installation conditions
(even for a short, unbroken length) require that adjacent sections be offset,
landing platforms shall be provided at each offset. [EN: When a fixed ladder
exceeds 10 m. it shall be provided with a rest platform. Platforms shall be
provided not more than 6 m. apart. Recommended intermediate platform
length is 0.7 m]
All rungs shall have a minimum diameter of 19 mm (0.75 in) for metal
ladders. The distance between rungs, cleats, and steps shall not exceed 0.3 m
(12 in) [EN: between 0.25 and 0.3 m] and shall be uniform throughout the
length of the ladder. The minimum clear length of rungs or cleats shall be 0.4
m (16 in) [EN: between 0.4 and 0.6 m]. The rungs of an individual-rung
ladder shall be designed so that the foot cannot slide off the end "Climbing
side." On fixed ladders, the perpendicular distance from the centerline of therungs to the nearest permanent object on the climbing side of the ladder shall
be 0.91 m (3 ft) for a pitch of 76 degrees, and 0.76 m (30 in) for a pitch of 90
degrees. [EN: 0.65 m in front Climbing Side, 0.2 m back (0.15 m in case o
discontinuous objects)]. The distance from the centerline to the nearest
permanent object in back of the ladder shall not be less than 0.18 m (7 in)
except when unavoidable obstructions are present. The clearance in back of
each rung shall not be less than 0.1 m (4 in).
FIGURE 7 Rail Ladder with Bar Steel Rails and Round Steel Rungs (from
29 CFR 1910.27, Figure D)
8/10/2019 09_safetyengineering
36/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.36
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
The step across distance from the nearest edge of the ladder to the nearest edge
of equipment or structure shall not be more than 0.30 m (12 in).
Protection against the risk of falling through ladder openings shall be providedby a hatch cover or by guardrails in combination with a swing gate (Note
chains are not sufficient to meet this requirement). If gates are utilized, they
shall provide both top and mid rail protection. The hatch cover shall move
upwards or horizontally and close automatically (e.g. by spring or gravity) not
hindering the passage of the user. Counterweighted hatch covers shall open a
minimum of 60 degrees from the horizontal. There shall be no protruding
potential hazards within 0.61 m (24 in) of the centerline of rungs or cleats
The relationship of a fixed ladder to an acceptable counterweighted hatch
cover is illustrated in FIGURE 8. [EN: Exit in the platform; Trap doors
Protection against the risk of falling through such an opening shall be
provided by a trap door or by guard-rails in combination with gate. The trapdoor shall move upwards or horizontally and close automatically (e.g. by
spring or gravity) not hindering the passage of the user.]
FIGURE 8 - Relationship of Fixed Ladder to a Safe Access Hatch (29 CFR
-
8/10/2019 09_safetyengineering
37/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.37
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
9.6.3.4 Ladder Cages or Wells
Ladders, cages, and wells shall be designed and installed in accordance with
29 CFR 1910.27.
All fixed ladders of more than 3.7 m (12 ft) shall be provided with cages
[EN: ladders of more than 3 m or the distance from the center of the ladder to
the unprotected side of a platform (or similar) is less than 3 m, then an anti-
fall device (such as a safety cage or a guided type fall arrester on rigid line)
shall be provided].
Cages shall extend a minimum of 1.1m (3.5 ft) above the top of landing [EN
1.1 m], unless other acceptable protection is provided.
Cages shall extend down the ladder to a point not less than 2.1 m (7 ft) normore than 2.4 m (8 ft) above the base of the ladder [EN: between 2.5 and 3
m], with bottom flared not less than 0.1 m (4 in), or portion of cage opposite
ladder shall be carried to the base.
Ladder cages shall have a clear width of at least 0.38 m (15 in) measured each
way from the centerline of the ladder [EN: Cage diameter shall be between 0.7
and 0.8 m]. Smooth-walled wells shall be a minimum of 0.7 m (27 in) from
the centerline of rungs to the well wall on the climbing side of the ladder
Where other obstructions on the climbing side of the ladder exist, there shall
be a minimum of 0.8 m (30 in) from the centerline of the rungs.
The spacing between vertical bars on the cage shall not exceed 0.24 m (9.5 in)
[EN: The spacing of safety cages shall be designed so that the empty spaces
are not more than 0.42 m2whereby the horizontal width of these space shall
not exceed 0.3 m].
When ladders provide access to landings that measure 1.2 m (48 in) or less
from the ladder rungs to the platforms guardrails, special means shall be used
to prevent personnel from falling over the guardrail. (See FIGURE 9)
8/10/2019 09_safetyengineering
38/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.38
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
9.6.4 Emergency Egress
All buildings and structures designed for human occupancy shall be provided
with exits sufficient to permit the prompt escape of occupants in case of fire or
other emergency. Every building or structure shall be provided with exits of
the kind, number, location, and capacity appropriate to the individual building
or structure, with due regard to the character of the occupancy, the number of
persons exposed, the fire protection available, and the height and type of
construction of the building or structure, to afford all occupants convenient
facilities for escape.
The design of exits and other safeguards shall be such that reliance for safety
to life in case of fire or other emergency will not depend solely on any singlesafeguard. Additional safeguards shall be provided for life safety in case any
single safeguard is ineffective due to a human or mechanical failure.
Exits shall be arranged and maintained to provide free and unobstructed egress
from all parts of the occupied building or structure at all times. Every building
or structure, section, or area meant for human occupancy shall have at least
two means of egress remote from each other and arranged to minimize any
FIGURE 9 Special Means for Guarding Ladders Ending on
Platforms (29 CFR 1910.27 Figure D-9)
8/10/2019 09_safetyengineering
39/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.39
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
possibility that any one fire or other emergency condition may block both
Exits and means of egress shall comply with the requirements of 29 CFR
1910.37 for US projects. Under US code, a single means of egress is
permitted for Special Purpose industrial occupancies from a story of section
in low or ordinary hazard industrial occupancies (e.g. the interior of a GE or
fuel handling enclosure is a high hazard area) where the distance to the exit
does not exceed 15 m (50 ft). Non-US projects shall conform to either the US
codes or the national codes and standards specified by that country per the
contract requirements, for European Community Countries IEC 60364.
9.6.5 Access and Working Space around Power GenerationEquipment
Sufficient access and working space shall be provided and maintained aroundelectric equipment to permit safe operation and maintenance of such
equipment in accordance with 29 CFR 1910.269.
Note: Guidelines for the dimensions of access and working space around
electric equipment in generating stations are contained in American National
Standard - National Electrical Safety Code, ANSI C2-1987 and in NFPA 70
National Electrical Code.
9.6.6 Access, Limiting Access, and Providing Sufficient Work
Space Around High and Low Voltage AreasNote: The below information is extracted from NFPA 70 Nationa
Electrical Code. This information shall be used for US projects. Non-US
projects shall conform to either the US codes or the national codes and
standards specified by that country per the contract requirements. For
European Community IEC 60364 is to be utilized.
9.6.6.1 Low Voltage (< 600 V)
At least one entrance of sufficient area shall be provided to gain access to the
working space around electrically energized equipment. For equipment rated1200 amps or more, and over 1.8 m (6 ft) wide, that contain over current
devices, switching devices, or control devices, there shall be one entrance to
the required working space not less than 0.6 m (24 in) wide and 2.0 m (6.5 ft)
high at each end of the working space. Any doors shall open in the direction
of egress and be equipped with panic bars, pressure plates, or other devices
that are normally latched but open under simple pressure. A single entrance
shall be permitted if :
8/10/2019 09_safetyengineering
40/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.40
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
a) the location permits a continuous and unobstructed way of exit travel (e.g.away from the equipment), or
b) the depth of the workspace is twice that shown in TABLE 3 and thedistance from the entrance to the nearest edge of the equipment is not less
that shown in Table 3 for the voltage and condition applicable to the
equipment.
The minimum headroom of working spaces around service equipment,
switchboards, panel-boards, or motor control centers shall be 2.0 m (6.5 ft)
Where the electrical equipment exceeds 2.0 m (6.5 ft) in height, the minimum
headroom shall not be less than the height of the equipment.
Live parts of electric equipment operating at 50 volts or more shall be guarded
against accidental contact. Acceptable guards include approved enclosures(e.g. NEMA enclosures); limited access rooms or vaults; suitable
permanent, substantial partitions or screens with limited access; location on a
gallery, balcony, or platform elevated and restricted so as to exclude
unauthorized personnel; or an elevation of more than 2.5 m (8 ft) above the
floor or other working surface.
The working space for equipment operating at 600 volts nominal, or less to
ground, and likely to require examination, adjustment, servicing, or
maintenance while energized may not be less than indicated in TABLE 3. The
workspace shall be adequate to permit at least a 90-degree opening of doors or
hinged panels. In addition to the dimensions shown in TABLE 3, the workingspace in front of electrical equipment shall be the width of the equipment or
0.76 m (30 in), whichever is greater. Distances shall be measured from the
exposed live parts, or from the enclosure or opening if the live parts are
enclosed. Working space is not required behind or on the sides of assemblies
such as dead-front switchboards or motor control centers, where al
connections or renewable or adjustable parts, such as fuses or switches, are
accessible from locations other than the back or sides. Where rear access is
required to work on nonelectrical parts on the back of enclosed equipment, a
minimum horizontal workspace of 0.76 m (30 in) shall be provided.
Switchboards, panelboards, distribution boards, and motor control centersshall be located in dedicated spaces and protected from damage. For indoor
locations, this space is equal to the width and depth of the equipment and
extends from the floor to a height of 1.8 m (6 ft) above the equipment or to the
structural ceiling, whichever is lower. No piping, ducts, leak protection
apparatus, or other equipment foreign to the electrical installation shall be
located in this zone.
8/10/2019 09_safetyengineering
41/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.41
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
TABLE 3 Working Spaces
Minimum clear distance [mm(ft)]
Nominal
voltage to
ground
Condition
(a)
Condition
(b)
Condition
(c)
0-150 900 mm (3 ft) 900 mm (3 ft) 900 mm (3 ft)
151-600 900 mm (3 ft) 1 m (3.5 ft) 1.2 m (4 ft
Conditions (a), (b), and (c), are as follows:
(a) Exposed live parts on one side and no live or grounded parts on the otherside of the working space, or exposed live parts on both sides effectively
guarded by suitable wood or other insulating materials.
(b) Exposed live parts on one side and grounded parts on the other side.
Concrete, brick, or tile walls shall be considered grounded
(c) Exposed live parts on both sides of the workspace [not guarded as
provided in Condition (a)] with the operator between.
Note: this table is taken from the 2005 version of the NEC article 110, table
110.26(a)(1).
9.6.6.2 High Voltage (> 600V)
Buildings, rooms, or enclosures containing exposed live parts or exposed
conductors operating at over 600 volts, nominal, shall be equipped with a
means of preventing access. A wall, screen, or fence shall be used to enclose
outdoor electrical installations to deter access by unqualified persons. A fence
shall not be less than 2.1 m (7 ft) in height or a combination of 1.8 m (6 ft) or
more of fence and a 0.30 m (12in) extension utilizing three or more strands of
barbed wire or equivalent. At least one entrance not less than 0.61 m (24 in)
wide and 2.0 m (6.5 ft) high shall be provided to give access to the working
space about electric equipment. On switchboard and control panels exceeding1.6 m (6 ft) in width, there shall be one entrance at each end of the equipment
A single entrance shall be permitted if
a) the location permits a continuous and unobstructed way of exit travel
(e.g. away from the equipment), or
8/10/2019 09_safetyengineering
42/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.42
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
b) the depth of the workspace is twice that shown in TABLE 4 and thedistance from the entrance to the nearest edge of the equipment is not
less that shown in TABLE 4 for the voltage and condition applicable to
the equipment. Where bare energized parts (at any voltage) or
insulated energized parts (above 600 volts) are located adjacent to the
entrance, they shall be suitably guarded with a partition, screen, or
other barrier against accidental contact. Entrances shall be equipped
with a means of locking
Sufficient space shall be provided and maintained around electrical equipment
to permit safe operation and maintenance of equipment. The minimum
headroom and working space width is the same as defined above for systems
energized to 600 volts or less. The working space depth shall be as required in
TABLE 4. The workspace shall be adequate to permit at least a 90-degree
opening of doors or hinged panels. The minimum clear working space in fron
of electric equipment such as switchboards, control panels, switches, circuit
breakers, motor controllers, relays, and similar equipment may not be less than
specified in TABLE 4 unless otherwise specified in this section. Distances
shall be measured from the exposed live parts or from the enclosure or
opening, if the live parts are enclosed. However, working space is no
required behind equipment such as dead front switchboards or contro
assemblies where there are no renewable or adjustable parts (such as fuses or
switches) on the back and where all connections are accessible from locations
other than the back. Where rear access is required to work on de-energized
parts on the back of enclosed equipment, a minimum working space of 0.75 m(30 in) horizontally shall be provided.
TABLE 4 Minimum Depth of Clear Working Space At Electrical Equipment
Minimum Depth of Clear Working Space [mm (ft)]
Nominal voltage
to ground
Condition
(a)
Condition
(b)
Condition
(c)
601 to 2,500 900 mm (3 ft) 1.2 m (4 ft) 1.5 m (5 ft)
2,501 to 9,000 1.2 m (4 ft) 1.5 m (5 ft) 1.8 m (6 ft)
9,001 to 25,000 1.5 m (5 ft) 1.8 m (6 ft) 2.8 m (9 ft)
25,001 to 75kV 1.8 m (6 ft) 2.5 m (8 ft) 3.0 m (10 ft)
Above 75kV 2.5 m (8 ft) 3.0 m (10 ft) 3.7 m (12 ft)
8/10/2019 09_safetyengineering
43/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.43
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
Conditions (a), (b), and (c) are as follows:
(a) Exposed live parts on one side and no live or grounded parts on the other
side of the working space, or exposed live parts on both sides effectivelyguarded by suitable wood or other insulating materials.
(b) Exposed live parts on one side and grounded parts on the other side.
Concrete, brick, or tile walls will be considered as grounded surfaces.
(c) Exposed live parts on both sides of the workspace (not guarded as
provided in Condition (a)) with the operator between.
Note: this table is taken from the 2005 version of the NEC article 110, table
110.34(A).
Unguarded live parts located above the working space shall be maintained at
elevations not less than specified in TABLE 5.
TABLE 5 - Elevation of Unguarded Energized Parts Above Working Space
Nominal voltage
between phasesMinimum elevation
601 to 7,500 2.8 m (9 ft)
7,501 to 35,000 2.9 m (9.5 ft)
Over 35kV 2.9 m (9.5 ft) + 9.5 mm (0.37 in) per kV above
35kV.
Note: this table is taken from the 2005 version of the NEC article 110, table
110.34(E)
9.6.7 Design for Safe Touch Temperature of Equipment
Maximum surface temperature exceeding 60C (140F) per ASTM C 1055 /
EN 563 within the power plant shall be guarded, covered, or equipped with a
means to prevent accidental contact where personnel are likely to be in close
proximity. Alternative protection can be provided to limit personnel access to
high temperature areas with standoff systems or other means of preventingaccess. Refer to GE DBD Mechanical System for design requirements.
9.6.8 Design for appropriate Equipment Guarding
Appropriate OSHA compliant guards shall be provided to protect personnel in
the power plant from all exposed hazardous surfaces, e.g. rotating, pinch
8/10/2019 09_safetyengineering
44/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.44
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
point, electrical, and hot temperatures. Refer to OSHA 29 CFR 1910 Subpart
O, Machinery and Machine Guarding, for requirements. For projects in
Europe, refer to EN-292 The Machinery Directive
9.6.9 Design to Accept Locks (Control of Hazardous EnergyMechanical and Electrical)
All energy isolating devices shall be designed to accept a lockout device. An
energy-isolating device is capable of being locked out if it has a hasp or other
means of attachment to which, or through which, a lock can be affixed, or it
has a built-in locking mechanism. Energy isolating devices are defined as any
mechanical device that physically prevents the transmission or release of
energy, including but not limited to the following:
A manually operated electrical circuit breaker
A disconnect switch
A manually operated switch by which the conductors of a circuit can
be disconnected from all ungrounded supply conductors, and, in
addition, no pole can be operated independently
A line valve
A block
Any similar device used to block or isolate energy
Refer to 29 CFR 1910.147 for design requirements.
9.6.10 Design of Security Fencing
Appropriate security fencing shall be provided to restrict access of personnel
and the public to potentially hazardous power plant equipment (e.g
switchyards) Refer to GE DBD Civil/Structural System for design
requirements of the Security Fencing.
8/10/2019 09_safetyengineering
45/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.45
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
9.7 Design of Emergency Eyewash / Shower Stations
The installation of emergency safety showers and eyewash fountains are
required in locations where personnel may contact chemical, biological, or
physical agents that require emergency washing facilities. Eyewash and
shower equipment for the emergency treatment of the eyes or body of a person
exposed to injurious materials shall meet the minimum performance
requirements outlined below in the General Requirements for Emergency
Eyewashes / Sowers. Emergency eyewash and shower stations shall mee
ANSI Z358.1.
9.7.1 General Requirements for Emergency Eyewashes/Showers
Provide in accordance with TABLE 6.
Provide eyewash units in any area where there is a potential for the eyes to
be exposed to corrosive, irritating, or toxic chemicals, biological hazards,
or physical hazards, such as chips or dust from sanding or grinding
processes.
Connect showers and eyewash units to potable water.
Specific water temperature ranges are not specified by regulation.Coordinate with client to determine desired water temperature.
Heat tracing shall be provided for outdoor installations with ambient
temperatures below 0C (32F) to prevent freezing of piping and
equipment.
Emergency showers and eyewash units shall be accessible within 10seconds at walking speed from the potential exposure source. Do not
locate in rooms or areas with lockable doors.
The water supply to shower and/or shower/eyewash combination units
shall be controlled by a shutoff valve, which is visible and accessible forshower testing or maintenance personnel in the event of leaking or failed
showerhead valves.
Definitions of the different types of emergency eyewash and shower units used
in TABLE 6:
Combination Shower and Eyewash unit*consisting of schedule 80 hot
dipped galvanized steel, chrome plated bronze stay open ball valves with
8/10/2019 09_safetyengineering
46/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.46
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
chrome plated ball, stainless steel actuators and actuation graphics, ABS
plastic shower head delivering a minimum 500 mm (20 in) diameter
pattern to the target are 1.5 m (5 ft) above standing level, ABS plastic dual
stream head with ABS plastic float off covers secured with stainless steel
bead chains, self adjusting 0.5 lb/sec (8.0 gpm) eye/face wash regulator
assuring a constant, even flow under varying hydraulic conditions.
Self-contained, Gravity Feed Eyewash unit**with retractable trayprotecting eyewash heads, pinch valve design to ensure positive water
flow within one second of activation.
Eyewash / Body Wash unit*** consisting of piping which is hot dip
schedule 80 steel drain/pedestal mount, 12 mm (0.5 in) chrome plated
bronze stay open ball valve with chrome plated ball and stainless steel
push plate with actuation graphic, ABS plastic dual stream head with ABS
float off covers secured with stainless steel bead chain, self adjusting 0.22
lb/sec (3.5 gpm) regulator assuring a constant, even flow under varying
hydraulic conditions, ABS plastic bowl or stainless steel bowl.
8/10/2019 09_safetyengineering
47/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.47
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
TABLE 6 - Emergency Eyewash / Shower
System Equipment
Or Location
Chemical(s) Wash Station
Boiler Chemical Feed HRSG Phosphate
(pH control, corrosioninhibitor, remove hardness)
Combination Shower andEyewash *
Selective CatalyticReduction (SCR)
Ammonia StorageTank and Injection
Skid
HRSG 19% Aqueous Ammonia Eyewash / Body Wash
***
Circulating CoolingWater Chemical Feed
Cooling Tower Sodium Hypochlorite
Sulfuric Acid, Inhibitor
And Sulfite
Combination Shower andEyewash *
Once-through Cooling Intake Structure Sodium Hypochlorite
(Reduce Biological Fouling)
Self-contained, Gravity FeeEyewash **
ST-G Bldg(Surface Condenser
Outlet)
Sodium Sulfite(Reduce Residual Chlorine)
Utilize Station forCondensate Chemical
Feed *
Raw Water ChemicalFeed (if provided)
Raw Water StorageTank
Sodium Hypochlorite Eyewash / Body Wash
***
Condensate ChemicalFeed
ST-G Bldg Oxygen Scavenger andAmmonia
Combination Shower andEyewash *
DC Power Supply GT-G PEECCBatteries
Battery Electrolyte
(e.g. Sulfuric Acid)
Personal Eyewash Station(Saline Solution in Bottles
At Battery CompartmentLevel and CombinationShower and Eyewash
Base * of Access Stairs
ST-G Bldg
Battery Room
Battery Electrolyte
(e.g. Sulfuric Acid)
Eyewash / Body Wash
***
Steam WaterSampling and
Analysis Panel
ST-G Bldg
Ground Floor
Testing Chemicals Personal Eyewash
Station (Saline Solution inBottles)
Water TestingLaboratory (if
provided)
ST-G Bldg
Ground Floor
Testing Chemicals Eyewash / Body Wash
***
ST HPU ST-G Bldg
Ground Floor
Fyrquel (Phosphate Ester) Eyewash / Body Wash
***
Fuel Oil Treatment (ifprovided)
Fuel Oil Storage Area Magnesium Sulfinate(Vanadium Fuels),
Hytec 580 made by EthylCorporation
(Lubricity Additive for LightFuels Kerosene, Naphtha)
Self Contained, Gravity FeeEyewash **
Water Treatment Water Treatment Bldg Acid / Caustic storage Combination Shower andEyewash *
8/10/2019 09_safetyengineering
48/67
GE PROPRIETARY INFORMATION Safety Engineering Page 9.48
GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)
9.7.2 Permanent Emergency Showers
Emergency showers shall be designed and located in accordance with the
following specifications.
Provide quick-acting Ball valve for the shower. Shower valve toremain open after the initial pull until manually closed. Locate the
face of the showerhead between 2.1 m (6.8 ft) and 2.5 m (8 ft) above
the floor.
Provide no greater than 0.6 m (23 in) horizontal distance from thecenter of the showerhead to the activating mechanism.
Provide shower unit with one activating mechanism at no higher than
1.7 m (5.75 ft) above the floor. Identify each shower location with ahighly visible sign within the area served by the shower.
Provide well-lighted area around each shower location.
Provide showerhead and pipe sizing with at least 1.26 l/sec (20 gpm)
flow, with the operating valve in the open position. Drains are not
generally provided for emergency showers. Address design and
operational issues with curbs, sloped floors, and dry drain traps for
designs incorporating drains. No obstructions, protrusions, or sharp
objects shall be located within 0.4 m (16 in) from the center of the
sp