+ All Categories
Home > Documents > 09_safetyengineering

09_safetyengineering

Date post: 02-Jun-2018
Category:
Upload: mersium
View: 220 times
Download: 0 times
Share this document with a friend

of 67

Transcript
  • 8/10/2019 09_safetyengineering

    1/67

    g

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.1

    ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    GE Energy

    9. Safety Engineering

    Page9.1 General ....................................................................................9.2

    9.2 Hazardous Area Classification .................................................9.7

    9.3 Building and Compartment Ventilation Design.......................9.19

    9.4 System Vent Design...............................................................9.24

    9.5 Gas and Chemical Storage and Distribution Systems............9.28

    9.6 Provision and Control of Personnel Access ...........................9.32

    9.7 Design of Emergency Eyewash / Shower Stations ................9.45

    9.8 Design of Work Areas for Appropriate Noise Levels ..............9.50

    9.9 Signs and Pipe Marking .........................................................9.51

    9.10 Design of Lighting and Power ................................................9.56

    9.11 Fire Protection........................................................................9.58

    9.12 Reference Materials ...............................................................9.63

    9.13 Review Documentation Deliverables......................................9.67

    9.14 Revision Table........................................................................9.67

  • 8/10/2019 09_safetyengineering

    2/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.2

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    9.1 General

    This document details design requirements for personnel safety in the

    permanent facility. The information provided herein describes good power

    plant safety engineering practices.

    Applicable National and Local safety regulations that require additional or

    specialized equipment or designs beyond those described in the proposal shall

    be included in the plant design or take precedence as required by law.

    Similarly, if National or Local safety regulations, or Owner preference

    requires additional safety studies and services to be performed, they may be

    included as contract adjustments.

    In cases where Country/Local practices and codes are determined to be

    equivalent or more stringent than the practices and codes, cited in the GE

    Safety Engineering DBD, these Country/Local practices and codes should be

    referenced within the project specific Safety Summary Report.

    9.1.1 Owners Responsibility

    The Owner is responsible for providing a site free of hazardous material risks

    to Personnel prior to project mobilization. This shall be addressed by

    removal, disposal and/or treatment of pre-existing contaminated materials(e.g. soil, ground water, etc.) at the site.

    9.1.2 Design Criteria Documentation

    A site specific Safety Engineering Plan shall be submitted to GE Engineering

    Review Board (ERB) prior to the reviews and shall address all of the elements

    of this Safety Engineering section of the design basis document. It shal

    describe how it to meet the requirements of the GE Design Basis Document

    (DBD). This plan shall also include:

    A tabulated summary of all of the potentially hazardous materials beingused in the construction and operation of the power plant including: type

    of hazards, location (use and storage), and required PPE (Personal

    Protective Equipment) including locations where PPE is required.

    Requirement that specifications for procurement of the above materialshall include the requirement to provide MSDS (Material Safety Data

    Sheets).

  • 8/10/2019 09_safetyengineering

    3/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.3

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    Hazardous Area Classification Map for systems and equipment within the

    scope of supply. This is required for the Initial Review.

    Hazardous Area Classification Map for the entire site. It is important tobegin creating this map as soon as there is a tentative site layout since

    hazardous areas will impact the final site layout. A preliminary site

    hazardous area map shall be provided for the Progress Review.

    Consolidated map of all ventilation intake and exhaust locations, and ventdischarge locations, including elevations.

    A detailed listing of all codes and standards (including date issued) forsupply of equipment and construction of systems and facility, for example:

    NFPA 101 Life Safety Code, 2000 or ANSI/ASME B31.3 Code for

    Process Piping, 1999 (Not just ANSI, ASME, NFPA).

    9.1.2.1 Project Specific Safety Summary Report Guidance

    To help GE understand the design philosophy being used to address safety

    issues associated with the specific project. A safety summary report is useful

    to provide safety design philosophy information that is not readily called out

    on the project design documents (e.g. why a pipe is sized a certain way) to GE

    Suggested partner & A/E design relevant aspects for inclusion in the safety

    engineering design basis document summary report.

    Top-level narratives describing what safety aspects are addressed for theproject, including reference to compliance with customers technica

    specification as well as regional, national, and local codes, standards and

    regulations.

    Hazardous Area Classification: methodology / assumptions used to createthe Hazardous Area Map(s) for the plant, what specific codes, standards

    references, internal calculation done by hand or using software, etc.

    Ventilation Design: for the Heating, Ventilation & Air ConditioningDesign (HVAC) describes the basis and methodology for the

    determination of the ventilation rates in hazardous areas. GE HazardousArea Maps are based on equivalent outdoor ventilation as defined by

    NFPA 497 for the United States and projects in other countries subscribing

    to the NFPA approach or IEC 60079-10 for the European Union and

    projects in other countries subscribing to the IEC approach.

    Gas and Chemical Storage and Distribution Systems: asphyxiating &flammable gases design, including discussion related to prevention of

  • 8/10/2019 09_safetyengineering

    4/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.4

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    above normal concentrations in confined space; plus automatic shut-off

    provisions in event of emergency or major leak occurrence.

    Gas and Chemical Storage Distribution Systems: storage of petroleum &chemical products design, including discussion related to containment of

    minor/major spills; plus health & safety considerations from workplace

    personnel exposure.

    Gas and Chemical Storage Distribution Systems: fuel gas equipmentdesign, including discussion related to compliance to what specific codes

    standards, and references that are used for the design.

    Gas and Chemical Storage Distribution Systems: compressed gas design,

    including discussion related to compliance to what specific codes

    standards, and references that are used for the design.

    Provisions and Control of Personnel Access: overall workplace personnel

    protection provisions, including discussion related to fall heights &

    protection, safe touch temperatures, security fencing, mechanical &

    electrical equipment lockout provisions including discussion related to

    compliance to what specific codes, standards, and references that are used

    for the design.

    Provision and Control of Personnel Access: mechanical & electricaguarding provisions, including discussion related to personnel access

    workplace maintenance provisions and what specific codes, standards, andreferences that are used for the design.

    Design of Emergency Eye Wash / Shower Stations: provide a summary

    and a map of where all emergency eye wash and shower stations are

    located throughout the plant, acknowledge that the site is meeting the

    minimum requirements defined in this document for location and type.

    Design of Work Areas for Appropriate Noise Levels: near field noise

    compliance means, plus health & safety considerations from workplace

    personnel exposure.

    Design of Lighting and Power: lighting provisions and groundingprotection including discussion related to compliance to what specific

    codes, standards, and references that are used for the design.

    Fire Protection: design details, including discussion on which plant areasare covered by what type of fire protection / suppression, portable fire

    extinguishers and locations and rating of fire rated walls; plus integration

  • 8/10/2019 09_safetyengineering

    5/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.5

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    into hazardous area classification development and plant emergency egress

    means.

    9.1.3 Acronyms and Definitions of Key Terms

    9.1.3.1 Acronyms

    AE - Architect Engineer

    BOP Balance of Plant

    EN European Normative standard

    EPC Entity responsible for Engineering / Procuring / Constructing the plant

    GT Gas Turbine

    GE DBD General Electric Design Basis Document

    HRSG Heat Recovery Steam Generator

    IEC International Electrotechnical Commission

    LEL Lower Explosive Limit

    MSDS Material Safety Data Sheet

    PPE Personal Protective Equipment

    PPM Parts Per Million

    ST Steam Turbine

    9.1.3.2 Definitions

    Confined or Enclosed Spaces (extracted from OSHA 1910.146) means any

    space that:

    1. Is large enough and so configured that an employee can enter andperform assigned work; and

    2. Has limited or restricted entry or exit (such as tanks, vessels, silos

    storage bins, hoppers, vaults and pits); and

  • 8/10/2019 09_safetyengineering

    6/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.6

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    3. Is not designed for continuous employee occupancy

    Permit required confined space means a confined space that has one or more

    of the following characteristics:

    1. Contains or has the potential to contain a hazardous atmosphere (e.g. is

    subject to the accumulation of toxic or flammable contaminants or has

    an oxygen deficientatmosphere);

    2. Contains a material that has the potential for engulfing an entrant (e.ggrain, sawdust, sand);

    3. Has an internal configuration; in which an entrant could be trapped or

    asphyxiated by inwardly converging walls or a floor that slopesdownward and tapers to a smaller cross section; or

    4. Contains any other recognized serious safety or health hazard.

  • 8/10/2019 09_safetyengineering

    7/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.7

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    9.2 Hazardous Area Classification

    The Hazardous Area Classification evaluates all the locations within the

    power plant and classifies them based on the potential existence of hazardous

    properties due to the presence of flammable vapors, liquids, or gases, or

    combustible concentrations of dust or fibers. This classification shall be done

    in accordance to applicable standards. It is to be cautioned that Internationa

    Standards and specific Country Standards may differ from the NFPA

    Standards followed in the U.S.

    To create a Hazardous Area Map for US projects refer to:

    United States Codes and Standards

    NFPA 70 National Electrical Code (NEC)

    NFPA 497 Recommended Practice for the Classification of FlammableLiquids, Gases, or Vapors and of Hazardous Locations for Electrical

    Installations in Chemical Process Areas

    API 500 Recommended Practice for Classification of Locations forElectrical Installations At Petroleum Facilities Classified As Class 1,

    Division 1 and Division 2

    API 505 Recommended Practice for Classification of Locations forElectrical Installations At Petroleum Facilities Classified As Zone 0, Zone

    1 and Zone 2

    To create a Hazardous Area Map for European Union projects refer to:

    European Codes and Standards

    IEC / EN 60079-10 - Electrical Apparatus for Explosive Atmospheres -

    Classification of Hazardous Areas

    EN 1127-1 Explosion prevention and protection

    94/9/EC, Directive 94/9/EC of the European Parliament and the Council of23 MARCH 1994 on the Approximation of the Laws of the Member

    States Concerning Equipment and Protective Systems Intended for the Use

    in Potentially Explosive Atmospheres. (ATEX)

  • 8/10/2019 09_safetyengineering

    8/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.8

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    IP-15 Institute of Petroleum Area Classification Code for Petroleum

    Installations (Part 15 of the Institute of Petroleum Model Code of Safe

    Practice in the Petroleum Industry)

    IGE SR 25 Hazardous Classification of Natural Gas Installations

    This area classification shall include associated interconnections and

    equipment designed by the AE/EPC as well as the GE supplied equipment

    All interconnections and equipment with the potential to create a hazard shall

    be clearly indicated on a comprehensive site map indicating size, location, and

    elevation of the hazard created. Special consideration shall be made for

    equipment not provided by the AE/EPC. The considerations for this

    equipment shall include:

    1. Ensuring equipment is rated for use as located (e.g. rated equipment ina hazardous area).

    2. Identifying the hazardous area(s) it may create and ensuring that non-rated equipment (not suitable for hazardous zone) is not located within

    these identified hazardous areas .

    3. Ensuring that inlets to fan ventilated enclosures / compartments

    cannot draw potentially hazardous atmospheres into the enclosure /

    compartment.

    NOTE: specific hazardous area dimensions listed in this document are based

    on US Standards.

    This classification should include, as a minimum, any of the items below that

    are associated with the particular project:

    Natural Gas: Gas Turbine Enclosure, Fuel Gas Module/Compartment,

    Flow Metering Tube, Piping, Filter/Separator, Heater(s), Scrubber,

    Pressure Reducing Station, Fuel Gas Booster Compressor, HRSG duct

    burner or auxiliary Boiler.

    Syn-gas (gas derived from coal or residuals): Syn-gas Compartment, Gas

    Turbine Enclosure, piping, processing equipment.

    Hydrogen: Generator, generator shaft seals, detraining enlargement vent,Collector Cab/Compartment, hydrogenstorage bottles, hydrogen manifold,

    battery compartment/room, Load Compartment.

    Liquid Fuel Vapor/Mist: Liquid fuel Module, Gas Turbine Enclosure,

    piping, processing equipment, storage and drains tank(s).

  • 8/10/2019 09_safetyengineering

    9/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.9

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    Lube Oil Vapor/Mist: Mist Eliminator discharge, high-pressure

    piping/tubing, Accessory Module, Lube Oil Skids with Lift Oil.

    Mechanical Connections (Non-Welded) in the above systems.

    Ventilation exhausts or vent discharges for the above systems.

    9.2.1 Hazardous Area Philosophy Document

    A Hazardous Area philosophy document shall be created. It defines the

    assumptions used to create the Hazardous Area Map. Each area of the

    Hazardous Area Map shall have its own assumption criteria that includes, but

    is not limited to, the following items:

    Ventilation (e.g. air changes per hour / flow for area)

    Hazardous gas / liquid vapor (e.g. natural gas, hydrogen)

    Volume / quantity of release of gas / liquid vapor - this can be duringnormal modes of operation or during a credible failure scenario

    Interconnection points (e.g. flanges, welds, compression fittings)

    All areas should have dimensions in x, y, and z directions and / or defined

    shape

    Identification of compartments and components that are to be located inareas outside of Hazardous Areas.

    9.2.2 Hazardous Area Map

    The Hazardous Area Map is a pictorial representation of the hazardous areas

    as defined in the philosophy documentation (9.2.1). A Hazardous Area is an

    area with the potential to contain hazardous atmosphere due to the presence of

    gas / liquid vapor / liquid mist at an ignitable concentration. The Hazardous

    Area map is required to have the following features:

    Plan and elevation views

    Each area shall have dimensions in x, y, and z directions and / or definedshape

    Approximate locations for all field installed pipe vents. The Hazardous

    Area bubble can either be shown directly on the Hazardous Area Map or

    its dimensions can be tabulated in an attachment.

  • 8/10/2019 09_safetyengineering

    10/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.10

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    Restricted areas are those areas that must be isolated from potentially

    hazardous leak sources. Items that are not rated for use in a Hazardous Area

    must be in a Restricted Area. There shall not be any potential for a Hazardous

    gas / liquid vapor to exist in a Restricted Area. Examples of Restricted Areas

    include:

    Compartment air inlets as defined in the Ventilation Design section of thisdocument

    Areas where non-rated components external to the compartments arelocated (as a general rule external components are non-rated for use in a

    Hazardous Area)

    Any other areas that may reasonably be expected to include a source of

    ignition (e.g. welding area).

    Once the site Hazardous Area Map has been compiled, a review shall be

    conducted to verify that the equipment located in the hazardous areas is

    properly rated, and address any non-compliance issues. This may require

    relocating either equipment that creates a hazard or the non-rated equipment,

    or upgrading the components affected by the hazards.

    Examples of different hazardous area map views can be seen in FIGURES 1, 2

    and 3.

  • 8/10/2019 09_safetyengineering

    11/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.11

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    FIGURE 1 SAMPLE: Isometric View of Accessory Module Hazardous

    Areas Created During Normal Operation.

    FIGURE 2 SAMPLE: End View of Accessory Module Hazardous

    Areas Created at Gas Compartment Doors During Ventilation Shut

    Down

  • 8/10/2019 09_safetyengineering

    12/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.12

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    FIGURE 3 SAMPLE: Pipe Vent Termination With High Pressure Flow

    of Gas Indicating Large Release Source.

  • 8/10/2019 09_safetyengineering

    13/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.13

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    9.2.3 Design of Equipment Located in Hazardous Areas

    For equipment located in a hazardous area,

    Properly locate electrical wiring conduit seal fittings in the conduit runsper the NEC, and install the manufacturers recommended conduit sealer

    in the fitting

    Pressurize and vent electrical junction boxes that potentially contain arcing/ sparking devices.

    9.2.4 Hazard Identification Reference

    The tables and figures in this section provide a reference for potential areas

    within the basic designs of a typical power plant that may be deemed

    hazardous due to the potential for:

    Gas / liquid vapor /liquid mist resulting in a fire/explosion

    Chemical releases

    Electrical energy release

    Note: not all of the hazards listed above are required to be identified on a site

    Hazardous Area Map as identified by NFPA or EN 60079-10 (IEC 79-10)Other hazards may need to be considered depending on the applicable codes

    for example, hot surfaces.

  • 8/10/2019 09_safetyengineering

    14/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.14

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    TABLE 1 Hazard Identification Reference associated with Figures 4, 5, and 6

    Chemical Electrical Fire / Explosion

    1 HRSG Duct Burner System X2 Exhaust Enclosure X

    3 GT Turbine Compartment X

    4 Liquid Fuel / Atomizing Air Module X

    5 Gas Valve Module / Compartment X

    6 Fuel Gas Performance & Start-Up Heaters X

    7 Coalescing Filter / Separator X

    8 Fuel Gas Scrubber X

    9 Fuel Gas Pre-Heater X

    10 Filter Separator X11 Gas Drain Tank X

    12 GT False Start Drains Tank X

    13 ST HPU Module (not shown) X

    14 Generator X X

    15 H2 Generator Bottle Storage & Manifold (not shown) X

    16 Collector Cab X X

    17 Collector Enclosure X

    18 Generator Terminal Enclosure (GTE) X X

    19 LCI & Excitation Module X20 Battery Room(s) GT (end of the PEECC), ST X X X

    21 ST Electrical Room X X

    22 Oil Filled Transformers X X

    23 Switch Yard (not shown) X

    24 Biofouling Chemicals X

    25 Water Treatment Chemicals X

    26 Waste Neutralization Tank X

    27 Fuel Oil Storage Tank X

    28 Fuel Gas Flow Metering Tube X

    FIGURES 4, 5, and 6 are Hazard Identification Maps that identify where the

    chemical, electrical, and fire / explosion hazards outlined in the above table

    are located. These figures are representative of a typical Combined Cycle

    power plant with 2 7FA Gas Turbines and a Steam Turbine, but elements

    depicted can be applied to any plant.

  • 8/10/2019 09_safetyengineering

    15/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.15

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    FIGURE 4 Chemical Hazard Identification Map.

  • 8/10/2019 09_safetyengineering

    16/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.16

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    FIGURE 5 Electrical Component Hazard Identification Map.

  • 8/10/2019 09_safetyengineering

    17/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.17

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    FIGURE 6 Fire / Explosion Hazard Identification Map.

    The locations of potential Fire / Explosion hazards shown in this figure are for

    reference only.. This figure does not meet the requirements of a Hazardous

    Area Map as required by either the US NFPA requirements defined in NFPA

    70 (NEC) and NFPA 497 or the European Union requirements as defined by

    ATEX and EN 60079-10.

  • 8/10/2019 09_safetyengineering

    18/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.18

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    TABLE 2 Additional Hazard Identification References (Not shown on Figures

    4, 5, and 6)

    Chemical Electrical Fire / Explosion

    Generator Line Accessory Compartment (GLAC) X

    Generator Neutral Accessory Compartment (GNAC) X

    Switch Gear / Medium Voltage Cell X

    GT Electrical Room / PEECC / TCC / MCC X X

    Water Wash Skid X

    Closed Cooling Water System (closed w/ antifreeze) X

    Fuel Gas Shut of Valve and Vent Valve skid (SSOV) X

  • 8/10/2019 09_safetyengineering

    19/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.19

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    9.3 Building and Compartment Ventilation Design

    Building and compartment ventilation is defined as airflow through any

    building or compartment of a power plant. GE uses a variety of compartment

    ventilation methods: positive pressure (forced draft), negative pressure

    (induced draft), and natural/convective.

    Positive pressure occurs when air is pushed into the building or

    compartment by ventilation fans, creating a higher pressure inside the

    building or compartment than the ambient pressure.

    Negative pressure occurs when air is drawn out of the building orcompartment by ventilation fans, creating a lower pressure inside of the

    building or compartment than the ambient pressure.

    Natural/convective ventilation is created by wind, temperature or gasdensity differentials that cause the air within the building or compartment

    to move.

    Ventilation air may enter a building or compartment through a variety of

    inlets. An inlet is any opening into a building or compartment through which

    air may enter. This includes, but is not limited to, ducts and damper covered

    openings, doorways, windows that open, and easily opened access panels

    The air drawn in through the inlet shall be safe air, which does not contain

    hazards. Safe air is defined as:

    Air with no significant contamination by flammable gasses or vapors thatmight be harmful to either the equipment or personnel (greater than 25%

    LEL Lower Explosive Limit per US-NFPA and EU guidance). Note: US

    requirement specifies not greater than 10% LEL for personnel exposure.

    Air that is not significantly above the ambient air temperature.

    Ventilation air exits from a building or compartment through exhaust outlet(s)

    Precautions must be taken when establishing exhaust outlet locations if there

    are potential hazards in the exhaust air from power plant buildings and

    compartments. The potential for hazards in exhaust air is dependent upon

    what is contained within the building or compartment being ventilated. For

    example:

    Buildings and compartments containing hot equipment, in excess of 60C

    (140F), use the ventilation for cooling purposes; exposure to the elevated

  • 8/10/2019 09_safetyengineering

    20/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.20

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    temperature of this exhaust air may potentially harm personnel or

    equipment. Note: this may include steam.

    Buildings or compartments containing parts of a fuel system have thepotential for fuel leaks from equipment and the piping system, which may

    contaminate the ventilation air. The ventilation exhaust of each building

    or compartment, along with the estimated potential concentration of fuel in

    the ventilation duct, should be factored into the location/orientation of the

    building or compartment exhaust outlet(s). The potential fuel sources

    may include natural gas, syn-gas, liquid fuel vapor/mist, or other

    alternative fuel source.

    Buildings or compartments containing high-pressure oil lines have thepotential for lube oil mist or vapor to leak into the building or

    compartment, which may contaminate the ventilation air. The ventilationexhaust of each building or compartment along with the estimated

    potential concentration of lube oil vapor or mist in the duct should be

    factored into the location/orientation of the building or compartment

    exhaust outlet(s).

    Buildings or compartments containing hydrogen system equipment or DCbatteries have the potential for hydrogen to accumulate in the building or

    compartment, which may contaminate the ventilation air. The ventilation

    exhaust of each building or compartment along with the estimated

    potential concentration of hydrogen in the enclosed space should be

    factored into the location/orientation of the building or compartmentexhaust outlet(s).

    Buildings or compartments containing a CO2fire suppression system shallnot exhaust into an enclosed area that could present a personnel hazard.

    For indoor installations, the compartment exhaust outlet(s) must be taken

    outside the main building.

    Buildings or compartments that serve as maintenance areas wherewelding, cutting or other fume producing processes take place shall not

    circulate ventilation exhaust from those maintenance areas into the inlet

    ventilation of other non-maintenance areas located within the same

    building.

    Turbine-Generators installed within buildings have additional ventilation

    considerations. Each compartment placed inside of the building needs to be

    evaluated for the requirements of both its inlet and exhaust air, for example:

    When installing compartments within a building with the associatedventilation fans mounted external to the building, the location of the

  • 8/10/2019 09_safetyengineering

    21/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.21

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    ventilation fan must be considered carefully with respect to the impact

    created by this exhaust. (e.g. away from the face of the inlet filter house,

    personnel access areas, non-rated equipment, etc.).

    When installing compartments within a building with the ventilation fansmounted internal to the building, the location of the outlet duct termination

    must be considered carefully with respect to the impact created by this

    exhaust (e.g. away from the face of the inlet filter house, personnel access

    areas, non-rated equipment, etc.).

    Compartments with temperatures significantly above ambient should bereviewed for location of the ventilation exhaust outlet to ensure that the air

    does not exhaust into personnel access areas or other ventilation inlets.

    Also, impact on the overall building ventilation design must accommodate

    the additional heat load if this exhaust air is released inside of the building,as some compartments may draw inlet air from inside of the building.

    Note: For each project, the specific model of GE gas turbines and their

    accessories must be reviewed since GE designs vary.

    9.3.1 Design for Gas Turbine Compartment VentilationExhaust

    Potential ventilation exhaust hazards include: high temperature and / or the

    presence of any of the following in the ventilation exhaust: natural gas, syn-

    gas, liquid fuel vapor, alternative fuel gas or vapor/mist, lube oil mist orvapor, and CO2. Refer to the project specific GE Gas Turbine Heating &

    Ventilation Schematic (0426) for design requirements.

    9.3.2 Design for Fuel Gas Module (Compartment) VentilationExhaust

    Potential ventilation exhaust hazards include: high-temperature and / or the

    presence of any of the following in the ventilation exhaust: natural gas

    hydraulic oil vapor or mist, and CO2. Refer to the project specific GE Gas

    Turbine Heating & Ventilation Schematic (0426) for design requirements.

    9.3.3 Design for Generator and Collector Cab Ventilation

    Potential ventilation exhaust hazards include: high-temperature and / or the

    presence of any of the following in the ventilation exhaust: lube oil vapor or

    mist and hydrogen (hydrogen generators only). Refer to GE Generator

    Equipment Documentation for design requirements.

  • 8/10/2019 09_safetyengineering

    22/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.22

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    For indoor installations of hydrogen generators, the building design must

    prevent the accumulation of hydrogen either by natural or forced ventilation of

    ceiling / roof high points. The ventilation flow capacity must be sized for

    the maximum generation rate of hydrogen to preclude gas build-up.

    9.3.4 Design for Load Compartment Ventilation (whenapplicable).

    Potential exhaust hazards include: high-temperature and /or the presence of

    hydrogen in the ventilation (when attached to hydrogen generators only)

    Refer to the project specific GE Gas Turbine Heating & Ventilation Schematic

    (0426) for design requirements.

    For indoor installations with hydrogen generators, either the ventilation mustbe taken outside the building or the building design must prevent the

    accumulation of hydrogen either by natural or forced ventilation of ceiling /

    roof high points. The ventilation flow capacity must be sized for the

    maximum generation rate of hydrogen to preclude gas build-up.

    9.3.5 Design of Battery Room Ventilation

    Hydrogen is the only potential exhaust hazard. Hydrogen evolution occurs

    during battery charging. Battery locations include: the PEECC, steam turbine

    UPS batteries, and plant facilities batteries.

    Battery room design must prevent the accumulation of hydrogen by ventilation

    of ceiling / roof high points. Irrespective of the type of ventilation used

    (convection or forced), flow requirements must be sized for the maximum

    generation rate of hydrogen. In the case of forced ventilation, the ventilation

    system shall have a redundant fan system with a method for starting the back-

    up fan if the primary fan should fail. A means for detecting hydrogen

    accumulation may be required by local codes or standards.

    9.3.6 Design for Liquid Fuel/Atomizing Air Compartment

    Ventilation

    Potential ventilation exhaust hazards include the presence of any of the

    following in the ventilation exhaust: liquid fuel vapor / mist and CO2. Refer

    to the project specific GE Gas Turbine Heating & Ventilation Schematic

    (0426) for design requirements.

  • 8/10/2019 09_safetyengineering

    23/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.23

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    9.3.7 Turbine-Generator Building

    Potential exhaust hazards include: high-temperature, lube oil vapor / mist and

    hydraulic fluid vapor / mist, fuel gases and liquid fuel vapor / mist (if Gas

    Turbine is located indoors) and hydrogen (when hydrogen generator is

    included).

    The turbine building ventilation system design must consider the inlet and

    outlet requirements under all potential modes of operation (e.g. minimum

    allowable number of building fans in operation) and ambient conditions (e.g

    cold winter or hot summer temperatures) to ensure that the individual

    compartments / modules have sufficient ventilation to meet their safe

    operating requirements.

    Refer to GE DBD Mechanical Systems Documentation for general designrequirements.

    9.3.8 Design for Control Room and Office Area Ventilation

    Control Room and Office Areas are intended for continuous human

    occupancy. These areas are not designed for hazardous air. Ventilation

    design must draw air in from a safe area outside the building. The air must

    be free from contaminant levels that could be harmful to human health.

    When these areas are part of a building that has the potential to contain

    hazardous air, there must be a separate ventilation system that draws in airfrom outside the building, and a slight positive pressure must be maintained

    inside the office or control room areas.

    9.3.9 Design for Exhaust Compartment Ventilation

    Potential ventilation exhaust hazards include: high temperature and / or the

    presence of CO2 in the ventilation exhaust. Refer to the project specific GE

    Gas Turbine Heating & Ventilation Schematic (0426) for design requirements.

  • 8/10/2019 09_safetyengineering

    24/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.24

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    9.4 System Vent Design

    Vents are defined as piping or tubing that discharge to the atmosphere. Vent

    lines can either be isolated by a manual or automatic valve, or be continuously

    open. Common examples are vent lines connected to return lines, open

    funnels, drains, tanks, chemical storage tanks, pressure relief valves, gas

    turbine gas fuel stop-ratio valve cavity (P2) vents, valve stem packing leak-off

    tubing, hydrogen casing purge, hydrogen scavenging, hydrogen detraining

    enlargements, and stator cooling water system vents.

    For all vents, the following must be shown on the P&ID:

    Whether of not the vent is a source of hazardous release

    What type of release it is

    Reference to the Hazardous Area documentation for all vents that

    create a hazardous area as defined in the Hazardous Area

    Classification section of this document.

    All hazardous vents shall be routed individually to a safe discharge area based

    on the potential hazards. Potential areas to avoid are:

    Personnel access ways (e.g. platforms, walkways)

    Arcing & sparking devices

    Maintenance areas (e.g. grinding, welding)

    Designated smoking areas

    Note: Information denoted in blue with square brackets [ ] in the below

    sections refers to the European Union classification for hazardous area

    designation using Zone and Group, which is different from the US Class

    Division, Group system.

    9.4.1 Fuel Gas Vents

    All fuel gas vents shall be individually routed and discharged to a safe areaclear of all ventilation inlets, non-rated electrical devices, other potential

    ignition sources (e.g. hot components, furnaces, etc.), and walkways /

    personnel access areas. Occasional releases from a small vent of a known

    volume (e.g. block and bleed vent valve) has a minimum Class I, Div 1, Group

    D [Zone 1, Group IIA]1.5 m. (5 ft) spherical radius hazardous area inside of a

    Class I, Div 2, Group D [Zone 2, Group IIA]3.0 m (10 ft) spherical radius

    hazardous area around the vent terminus. Large releases will have a larger

  • 8/10/2019 09_safetyengineering

    25/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.25

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    hazardous area based on the pressure and amount of gas released (e.g. gas

    compartment/module strainer blow-down connection (FG2)). Pressure Relie

    lines shall not be ganged with each other or any other vent lines. Do no

    route fuel gas vents to any drains tanks.

    Note: Follow ALL notes and recommendations found on the GE Fuel Gas

    System Schematic (0422) for additional information on routing of field run

    vents, this includes requirements for vent lines to be run individually

    recommended vent discharge design per GEK 110743 and hazardous area

    size/shape at the discharge of the vent.

    9.4.2 Purge Vents

    All purge vents shall be individually routed and discharged to a safe area clearof all ventilation inlets, non-rated electrical devices, other potential ignition

    sources (e.g. hot components, furnaces, etc.), and walkways / personnel access

    areas. Occasional releases from a small vent of known volume (e.g. block and

    bleed vent valve) that are purging fuel gas piping has a minimum Class I, Div

    1, Group D [Zone 1, Group IIA]1.5 m (5 ft) spherical radius hazardous area

    inside of a Class I, Div 2, Group D [Zone 2, Group IIA]3.0 m (10 ft) spherical

    radius hazardous area around the vent terminus.

    Note: Follow ALL notes and recommendations found on the GE Purge Air

    System Schematic (0477) for additional information on routing of field run

    vents, this may include requirements for vent lines to be run separately,recommended vent discharge design per GEK 110743 and hazardous area

    size/shape at the discharge of the vent.

    9.4.3 Hydrogen Vents

    All Hydrogen vents shall be individually routed to a safe area clear of all

    ventilation inlets, non-rated electrical devices, other potential ignition sources

    (e.g. hot components, furnaces, etc.), and walkways / personnel access areas

    Occasional releases from a small vent of known volume has a minimum Class

    I, Div 1, Group B [Zone 1, Group IIC]1.5 m (5 ft) spherical radius hazardous

    area inside of a Class I, Div 2, Group B [Zone 2, Group IIC]3.0 m (10 ft)spherical radius hazardous area around the vent terminus (Note: this guidance

    is per NFPA 497 and is superceded by any GE provided hazardous area

    information). Pressure Relief lines shall NOT be ganged with each other or

    any other vent lines.

    Note: Follow ALL recommendations found on the GE Customer drawings

    provided for the Generator Accessories (potentially Generator Gas System

  • 8/10/2019 09_safetyengineering

    26/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.26

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    Installation Design Specification 357A2258 and Specification, BDE Vent

    Piping 358A4741) for additional information on routing of field run vents, this

    may include requirements for vent lines to be run separately, recommended

    vent discharge design and hazardous area size/shape at the discharge of the

    vent.

    9.4.4 Lube Oil Vents

    Lube oil mist and vapor shall be exhausted outside of the Turbine Building

    Lube oil mist and vapors should be considered potentially hazardous and this

    should be taken into account when locating the terminus of the lube oil

    demister vent. The vent from the lube oil mist eliminator has a minimum

    Class I, Div 2, Group D [Zone 2, Group IIA] 1.5 m (5 ft) spherical radius

    hazardous area. Note: depending on the efficiency of the technology used foroil mist elimination, the concentration of oil released in parts per million

    (ppm) of will vary. This may result in this area not requiring a hazardous

    classification for oil.

    Note: Follow ALL notes and recommendations found on the GE Lube Oi

    System Schematic (Gas Turbine: 0416, and Steam Turbine VD01L) for

    additional information on routing of field run vents, this may include

    requirements for vent lines to be run separately and hazardous area size/shape

    at the discharge of the vent.

    9.4.5 Steam Vents

    All Steam vents shall be routed to an area away from personnel access areas to

    allow for safe release of the steam. Recommendations include locating

    silencer and vent discharges away from any personnel access areas including

    floors, platforms, ladders or stairs at a minimum of 6.0m (20 ft) horizontally

    and 3.0 m (10 ft) vertically and situated in such a manner that the vents do not

    direct steam towards stairs, ladders, walkways, platforms, maintenance areas

    and/or heat detection devices.

    9.4.6 Liquid Fuel Vents

    All liquid fuel oil vents and open funnels shall be routed to a safe area clear of

    all ventilation inlets, non-rated electrical devices, other potential ignition

    sources (e.g. hot components, furnaces, etc.), and walkways / personnel access

    areas. The vent from a liquid fuel oil storage / drains tank has a minimum

    Class I, Div 2, Group D [Zone 2, Group IIA]0.5 m (0.5 ft) spherical radius

    hazardous area. Note: Depending on the design of the piping to the liquid

  • 8/10/2019 09_safetyengineering

    27/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.27

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    fuel False Start Drain Tank, this area can be larger based on the fail open

    properties of the GE inline drain valves, which may allow the drain line to be

    pressurized during GT operation.

  • 8/10/2019 09_safetyengineering

    28/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.28

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    9.5 Gas and Chemical Storage and Distribution Systems

    These sections address design requirements for chemical storage areas and

    compressed gas storage areas. This section does not cover design standards

    for bulk fuel storage; this is covered in the GE DBD Mechanical Systems

    Documentation. Typical chemicals that need to be addressed include aqueous

    ammonia, anhydrous ammonia, anionic and cationic resins, ethylene glycol,

    phosphate ester (a.k.a. Fyrquel), fire suppression foam, propylene glycol

    sodium hypochloride, sodium hydroxide, sodium sulfite/sulfate, sulfuric acid

    and various water treatment chemicals. Compressed gases, which need to be

    considered typically include: Nitrogen, Hydrogen, and Carbon Dioxide (CO2)

    Storage areas for chemicals and compressed gases must be provided with

    appropriate signs. Ventilation of chemical storage areas shall be inaccordance with OSHA 29 CFR 1910, NFPA, Uniform Fire Code and / or

    applicable local requirements.

    The location of chemical storage areas shall be shown on the appropriate

    drawings including the General Arrangement, Plot Plan, and, for all areas

    containing flammable/explosive liquids or gases, on the Hazardous Area Map.

    9.5.1 Storage and Distribution of Gases

    Compressed gas systems for power plants in general fit into the following gas

    categories and uses:

    Carbon Dioxide Generator purge and Fire Suppression

    Compressed Air Instrument and Service air

    Gas Fuel Fuel for Gas Turbine, auxboiler and / or HRSG

    supplemental firing

    Hydrogen Generator fill and makeup for cooling

    Nitrogen HRSG / BOP equipment blanketing and various system

    purges

    These systems will be under high pressure and require careful considerations

    during design, construction and operation. The systems and components shal

    be designed in accordance with ASME Boiler and Pressure Vessel Code

    Section VIII and ASME Power Piping Code 31.1. For European Community

    Countries the local pressure code (or already mentioned ASME Code)

    97/23/EC, the Pressure Equipment Directive (PED) and 87/404/EEC Simple

    Pressure Vessels shall apply. Additionally all systems shall address container

  • 8/10/2019 09_safetyengineering

    29/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.29

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    specifications; safety relief devices; design of piping, tubing and fittings

    ventilation; and heating. Systems shall be tested and proved to be tight at

    maximum operating pressure. Facilities design shall comply with OSHA

    1910 Subpart M. Non-US projects shall conform to either the US Codes or

    the national codes and standards specified by that country per contract

    requirements. Proper ventilation is required for processing and storage areas

    to mitigate any combustion and/or asphyxiation potential.

    Each one of these systems may contain the following:

    High pressure gas storage cylinders

    High pressure safety relief devices

    Gas pressure control valves

    Compressors

    Extensive runs of interconnecting piping

    Storage and handling facilities

    Gas venting requirement

    In general equipment and cylinders should be protected against mechanical

    damage. Racks should be provided or other means to hold them securely. Ful

    bottles should be kept separately from empty bottles. Caution signs should

    address depressurizing systems before disassembly. There should be loca

    gauges for the technician to verify depressurization of the system. Cylinders

    should be located where they will not be exposed to excessive heat. Outdoor

    installations should include a roof for solar radiation protection.

    Bulk storage facilities should be located in the plant yard away from the main

    structure. Limited numbers of cylinders are acceptable in main building areas.

    Safety shutoff valves between bulk hydrogen storage facilities and the

    regulating valve manifold assembly is recommended per NFPA 850,

    paragraph 5-7.1.

    GE specification 357A2258, Generator gas System Design Specification

    provides guidelines for the design and installation of CO2 and Hydrogen gassupply systems for Generator Applications.

    Carbon dioxide (CO2), Hydrogen (H2), and Nitrogen (N2) shall be stored in an

    outside area, inside an enclosure with forced or otherwise wellventilation, or

    inside an enclosure that precludes the unrestricted entrance of personnel

    Enclosed compressed gas storage areas shall be designed to address exposure

    to potentially hazardous or asphyxiating atmospheres through adequate forced

  • 8/10/2019 09_safetyengineering

    30/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.30

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    ventilation, gas monitoring and warning systems, or a design that precludes

    entrance into the gas storage area. Compressed gas storage areas shall be

    provided with means of securing cylinders.

    CO2 used for generator purge gas must be stored indoors or in a compartment

    that maintains a temperature above 10C (50F). Refer to GE Generator

    Station Designers Handbook, C411 Document for specific project

    requirements. If unventilated, this compartment should be sized to store the

    CO2 bottles only and preclude the entry of personnel. Refer to GE DBD

    Mechanical System Description for design requirements of storage area.

    Hydrogen storage enclosures shall be well ventilated enclosure, as defined per

    NFPA 497 for hydrogen storage, is one that has any 3 of the possible 5 sides

    (4 walls and roof) open, that arrangement allows for ventilation equivalent to

    the equipment being outdoors.

    CO2storage used for Fire Suppression systems shall have signs / monitoring

    of any pits into which the CO2 can settle that meet the recommendations of

    NFPA 12.

    9.5.2 Design Considerations for Gas Fuel ConditioningEquipment

    The design of an outdoor installation shall include a risk assessment based on

    the probability of a gas leak and the possible consequences to personnel safetyand equipment safety (e.g. Classification of Hazardous Locations published

    by Institution of Chemical Engineers Rugby, Warwickshire England 1990

    authored by AW Cox, FP Lees, and ML Ang or British Standard IGE SR 25

    Hazardous Classification of Natural Gas Installations). All Gas Turbine

    Steam Turbine, and Generator equipment is designed to be installed in a safe

    area regardless of the hazards that equipment may generate. Refer to GE DBD

    Mechanical System documentation for design requirements.

    9.5.3 Chemical Storage

    A variety of chemicals are used throughout the power plant. Each chemica

    has specific requirements for safe handling, storage, and use.

    The main chemicals in use are:

    Acids for demineralizer regeneration, and demineralizer waste

    neutralization, e.g. sulfuric acid

  • 8/10/2019 09_safetyengineering

    31/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.31

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    Caustics for demineralizer regeneration and demineralizer waste

    neutralization, e.g. sodium hydroxide

    Biocides for circulating water system treatment, e.g. sodiumhypochlorite

    Ammonia, phosphates and carbohydrazide for cycle water treatment

    Refer to the chemicals MSDS for details. These requirements shall be taken

    into consideration when designing various chemical storage areas

    Additionally there may be National or Local requirements that will mandate

    additional requirements be addressed for various chemicals. For example

    Ammonia storage in the US must comply with 40 CFR 68: General Guidance

    for Risk Management Programs. Chemical storage areas shall be provided

    with secondary adequate containment sized per the specifications in the GE

    DBD Environmental Engineering Systems Documentation. Materials used for

    construction of containment areas and associated equipment shall be

    compatible with the chemicals that will be stored in that area. Separate

    containment areas shall be designed for incompatible chemicals (i.e. acids and

    bases). Ventilation shall be provided as a means of controlling excessive

    temperature build-up in storage areas. To comply with NFPA 497 and loca

    fire codes, specific fire protection measures for storage of combustible and

    flammable materials shall be addressed. Design specifications for systems

    including storage and piping which use highly hazardous chemicals (as

    defined by 29 CFR 1910.119 Appendix A, or other appropriate nationa

    standards) - shall include safety measures such as interlocks, detectionsystems, and suppression systems. Additional requirements may apply to the

    use of highly hazardous chemicals.

  • 8/10/2019 09_safetyengineering

    32/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.32

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    9.6 Provision and Control of Personnel Access

    9.6.1 Provision of Access to Work and Maintenance Areas

    Safe access and working platforms shall be provided for all work and

    maintenance areas. A stairway or ladder must be provided at all worker points

    of access where there is a break in elevation of 0.5 m (19 in) or more, and no

    ramp, runway, embankment, or personnel hoist is provided. Access via stairs

    or ladders shall be provided for access from one structure level to another

    where operations necessitate regular travel between levels, and for access to

    operating platforms for any equipment that requires routine attention. Fixed

    stairs or ladders shall also be provided where access to elevations occurs daily

    or during each shift for such purposes as gauging, inspection, regular

    maintenance, etc.

    9.6.2 Design for Provision of Fall Protection

    Areas and equipment with work/maintenance areas higher than 1.2 m (4 ft)

    above grade, and for which permanent means of fall protection (e.g. standard

    railings) are not feasible or are inappropriate, shall have a means of anchoring

    a personnel fall protection system. Anchors to which personal fall arrest

    equipment is attached shall be capable of supporting at least 2270 kg (5,000

    lbs) per employee attached or meet the specific load requirements for anengineered fall arrestment system under OSHA 29 CFR 1910.66 or other

    applicable codes / laws. The location of the anchorage point should also

    consider hazards presented by obstructions in the potential fall path of the

    employee. OSHA 29 CFR 1910.23.

    9.6.3 Design of Platforms, Walkways, Stairways, and Ladders

    The design of platforms, walkways, ladders, and stairways shall conform to

    NFPA 101 and, OSHA 29 CFR 1910 for US projects. Non-US projects shal

    conform to either the US codes or the national codes and standards specified

    by that country per the contract requirements, such as EN Standards forEuropean Community Countries. Note: requirements for the European

    Community are provided in blue and square brackets [ ] per the following

    specifications: Pr-EN 12437-2, 3, 4, EN-131-2, EN 292-1, EN-292-2, EN 353-

    1. These design requirements are to ensure safe and easy access to al

    components and required access areas in a safe manner by personnel. Refer to

    the GE DBD Civil / Structural System documentation for design requirements

  • 8/10/2019 09_safetyengineering

    33/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.33

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    9.6.3.1 Platforms

    Platforms shall be designed and installed in accordance with 29 CFR 1910.23

    Platforms are designed to serve as a working space for persons elevated abovethe surrounding floor or ground, including balconies or walkways provided for

    access to machinery and equipment. All platforms where a potential fall of

    over 1.2 m (4 ft) [EN: 0.5 m.] can occur shall be guarded with a standard

    guardrail system.

    Standard guardrail systems shall consist of a top rail, intermediate rail, and

    posts, and shall have a vertical height of 1.0 m (3.5 ft) [EN: 1.1 m]nomina

    from upper surface of top rail to floor, platform, runway, or ramp level. The

    top rail shall be smooth-surfaced throughout the length of the railing. The

    intermediate rail shall be approximately halfway between the top rail and the

    floor [EN: 0.5 m], platform, runway, or ramp. The ends of the rails shall nooverhang the terminal posts except where such overhang does not constitute a

    projection hazard.

    A standard toe-board shall be provided whenever the platform is located

    above an area where people may pass or where objects may fall. The toe-

    board shall be 100 mm (4 in) nominal in vertical height from its top edge to

    the level of the floor, platform, runway, or ramp. It shall be securely fastened

    in place and with not more than 6.4 mm (0.25 in) clearance above floor level

    It may be made of any substantial material either solid or with openings not

    over 25 mm (1 in) in greatest dimension.

    Pipe railings, posts, top and intermediate railings shall be at least 38 mm (1.5

    in) nominal diameter with posts spaced not more than 2.5 m (8 ft) on centers

    [EN: 1.5 m]. The anchoring of posts and framing of members for railings of

    all types shall be of such construction that the completed structure shall be

    capable of withstanding a load of at least 90 kgs (200 lbs) applied in any

    direction at any point on the top rail [EN: Note: Testing of Guard Rails

    Horizontal deflection of handrail shall not exceed 30 mm when loaded for a

    minute with a force equal of 300 N times the distance in meters between the

    stanchions. The measurement must be done at the junction point between

    stanchions and the handrail and repeated halfway between the posts].

    Walking surfaces shall be nominally level. The slope of a walking surface in

    the direction of travel shall not exceed 1 to 20 (1:20) unless the ramp

    requirements of NFPA 101 are met. The slope perpendicular to the direction

    of travel shall not exceed 1 to 48 (1:48). Abrupt changes in elevation of

    walking surfaces shall not exceed 6.4 mm (0.25 in)[EN 4 mm]. Changes in

    elevation exceeding 6.4 mm (0.25 in), but not exceeding 13 mm (0.5 in), shall

  • 8/10/2019 09_safetyengineering

    34/67

  • 8/10/2019 09_safetyengineering

    35/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.35

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    platforms shall be provided for each 6.1 m (20 ft) of height. Each ladder

    section shall be offset from adjacent sections. Where installation conditions

    (even for a short, unbroken length) require that adjacent sections be offset,

    landing platforms shall be provided at each offset. [EN: When a fixed ladder

    exceeds 10 m. it shall be provided with a rest platform. Platforms shall be

    provided not more than 6 m. apart. Recommended intermediate platform

    length is 0.7 m]

    All rungs shall have a minimum diameter of 19 mm (0.75 in) for metal

    ladders. The distance between rungs, cleats, and steps shall not exceed 0.3 m

    (12 in) [EN: between 0.25 and 0.3 m] and shall be uniform throughout the

    length of the ladder. The minimum clear length of rungs or cleats shall be 0.4

    m (16 in) [EN: between 0.4 and 0.6 m]. The rungs of an individual-rung

    ladder shall be designed so that the foot cannot slide off the end "Climbing

    side." On fixed ladders, the perpendicular distance from the centerline of therungs to the nearest permanent object on the climbing side of the ladder shall

    be 0.91 m (3 ft) for a pitch of 76 degrees, and 0.76 m (30 in) for a pitch of 90

    degrees. [EN: 0.65 m in front Climbing Side, 0.2 m back (0.15 m in case o

    discontinuous objects)]. The distance from the centerline to the nearest

    permanent object in back of the ladder shall not be less than 0.18 m (7 in)

    except when unavoidable obstructions are present. The clearance in back of

    each rung shall not be less than 0.1 m (4 in).

    FIGURE 7 Rail Ladder with Bar Steel Rails and Round Steel Rungs (from

    29 CFR 1910.27, Figure D)

  • 8/10/2019 09_safetyengineering

    36/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.36

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    The step across distance from the nearest edge of the ladder to the nearest edge

    of equipment or structure shall not be more than 0.30 m (12 in).

    Protection against the risk of falling through ladder openings shall be providedby a hatch cover or by guardrails in combination with a swing gate (Note

    chains are not sufficient to meet this requirement). If gates are utilized, they

    shall provide both top and mid rail protection. The hatch cover shall move

    upwards or horizontally and close automatically (e.g. by spring or gravity) not

    hindering the passage of the user. Counterweighted hatch covers shall open a

    minimum of 60 degrees from the horizontal. There shall be no protruding

    potential hazards within 0.61 m (24 in) of the centerline of rungs or cleats

    The relationship of a fixed ladder to an acceptable counterweighted hatch

    cover is illustrated in FIGURE 8. [EN: Exit in the platform; Trap doors

    Protection against the risk of falling through such an opening shall be

    provided by a trap door or by guard-rails in combination with gate. The trapdoor shall move upwards or horizontally and close automatically (e.g. by

    spring or gravity) not hindering the passage of the user.]

    FIGURE 8 - Relationship of Fixed Ladder to a Safe Access Hatch (29 CFR

    -

  • 8/10/2019 09_safetyengineering

    37/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.37

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    9.6.3.4 Ladder Cages or Wells

    Ladders, cages, and wells shall be designed and installed in accordance with

    29 CFR 1910.27.

    All fixed ladders of more than 3.7 m (12 ft) shall be provided with cages

    [EN: ladders of more than 3 m or the distance from the center of the ladder to

    the unprotected side of a platform (or similar) is less than 3 m, then an anti-

    fall device (such as a safety cage or a guided type fall arrester on rigid line)

    shall be provided].

    Cages shall extend a minimum of 1.1m (3.5 ft) above the top of landing [EN

    1.1 m], unless other acceptable protection is provided.

    Cages shall extend down the ladder to a point not less than 2.1 m (7 ft) normore than 2.4 m (8 ft) above the base of the ladder [EN: between 2.5 and 3

    m], with bottom flared not less than 0.1 m (4 in), or portion of cage opposite

    ladder shall be carried to the base.

    Ladder cages shall have a clear width of at least 0.38 m (15 in) measured each

    way from the centerline of the ladder [EN: Cage diameter shall be between 0.7

    and 0.8 m]. Smooth-walled wells shall be a minimum of 0.7 m (27 in) from

    the centerline of rungs to the well wall on the climbing side of the ladder

    Where other obstructions on the climbing side of the ladder exist, there shall

    be a minimum of 0.8 m (30 in) from the centerline of the rungs.

    The spacing between vertical bars on the cage shall not exceed 0.24 m (9.5 in)

    [EN: The spacing of safety cages shall be designed so that the empty spaces

    are not more than 0.42 m2whereby the horizontal width of these space shall

    not exceed 0.3 m].

    When ladders provide access to landings that measure 1.2 m (48 in) or less

    from the ladder rungs to the platforms guardrails, special means shall be used

    to prevent personnel from falling over the guardrail. (See FIGURE 9)

  • 8/10/2019 09_safetyengineering

    38/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.38

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    9.6.4 Emergency Egress

    All buildings and structures designed for human occupancy shall be provided

    with exits sufficient to permit the prompt escape of occupants in case of fire or

    other emergency. Every building or structure shall be provided with exits of

    the kind, number, location, and capacity appropriate to the individual building

    or structure, with due regard to the character of the occupancy, the number of

    persons exposed, the fire protection available, and the height and type of

    construction of the building or structure, to afford all occupants convenient

    facilities for escape.

    The design of exits and other safeguards shall be such that reliance for safety

    to life in case of fire or other emergency will not depend solely on any singlesafeguard. Additional safeguards shall be provided for life safety in case any

    single safeguard is ineffective due to a human or mechanical failure.

    Exits shall be arranged and maintained to provide free and unobstructed egress

    from all parts of the occupied building or structure at all times. Every building

    or structure, section, or area meant for human occupancy shall have at least

    two means of egress remote from each other and arranged to minimize any

    FIGURE 9 Special Means for Guarding Ladders Ending on

    Platforms (29 CFR 1910.27 Figure D-9)

  • 8/10/2019 09_safetyengineering

    39/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.39

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    possibility that any one fire or other emergency condition may block both

    Exits and means of egress shall comply with the requirements of 29 CFR

    1910.37 for US projects. Under US code, a single means of egress is

    permitted for Special Purpose industrial occupancies from a story of section

    in low or ordinary hazard industrial occupancies (e.g. the interior of a GE or

    fuel handling enclosure is a high hazard area) where the distance to the exit

    does not exceed 15 m (50 ft). Non-US projects shall conform to either the US

    codes or the national codes and standards specified by that country per the

    contract requirements, for European Community Countries IEC 60364.

    9.6.5 Access and Working Space around Power GenerationEquipment

    Sufficient access and working space shall be provided and maintained aroundelectric equipment to permit safe operation and maintenance of such

    equipment in accordance with 29 CFR 1910.269.

    Note: Guidelines for the dimensions of access and working space around

    electric equipment in generating stations are contained in American National

    Standard - National Electrical Safety Code, ANSI C2-1987 and in NFPA 70

    National Electrical Code.

    9.6.6 Access, Limiting Access, and Providing Sufficient Work

    Space Around High and Low Voltage AreasNote: The below information is extracted from NFPA 70 Nationa

    Electrical Code. This information shall be used for US projects. Non-US

    projects shall conform to either the US codes or the national codes and

    standards specified by that country per the contract requirements. For

    European Community IEC 60364 is to be utilized.

    9.6.6.1 Low Voltage (< 600 V)

    At least one entrance of sufficient area shall be provided to gain access to the

    working space around electrically energized equipment. For equipment rated1200 amps or more, and over 1.8 m (6 ft) wide, that contain over current

    devices, switching devices, or control devices, there shall be one entrance to

    the required working space not less than 0.6 m (24 in) wide and 2.0 m (6.5 ft)

    high at each end of the working space. Any doors shall open in the direction

    of egress and be equipped with panic bars, pressure plates, or other devices

    that are normally latched but open under simple pressure. A single entrance

    shall be permitted if :

  • 8/10/2019 09_safetyengineering

    40/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.40

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    a) the location permits a continuous and unobstructed way of exit travel (e.g.away from the equipment), or

    b) the depth of the workspace is twice that shown in TABLE 3 and thedistance from the entrance to the nearest edge of the equipment is not less

    that shown in Table 3 for the voltage and condition applicable to the

    equipment.

    The minimum headroom of working spaces around service equipment,

    switchboards, panel-boards, or motor control centers shall be 2.0 m (6.5 ft)

    Where the electrical equipment exceeds 2.0 m (6.5 ft) in height, the minimum

    headroom shall not be less than the height of the equipment.

    Live parts of electric equipment operating at 50 volts or more shall be guarded

    against accidental contact. Acceptable guards include approved enclosures(e.g. NEMA enclosures); limited access rooms or vaults; suitable

    permanent, substantial partitions or screens with limited access; location on a

    gallery, balcony, or platform elevated and restricted so as to exclude

    unauthorized personnel; or an elevation of more than 2.5 m (8 ft) above the

    floor or other working surface.

    The working space for equipment operating at 600 volts nominal, or less to

    ground, and likely to require examination, adjustment, servicing, or

    maintenance while energized may not be less than indicated in TABLE 3. The

    workspace shall be adequate to permit at least a 90-degree opening of doors or

    hinged panels. In addition to the dimensions shown in TABLE 3, the workingspace in front of electrical equipment shall be the width of the equipment or

    0.76 m (30 in), whichever is greater. Distances shall be measured from the

    exposed live parts, or from the enclosure or opening if the live parts are

    enclosed. Working space is not required behind or on the sides of assemblies

    such as dead-front switchboards or motor control centers, where al

    connections or renewable or adjustable parts, such as fuses or switches, are

    accessible from locations other than the back or sides. Where rear access is

    required to work on nonelectrical parts on the back of enclosed equipment, a

    minimum horizontal workspace of 0.76 m (30 in) shall be provided.

    Switchboards, panelboards, distribution boards, and motor control centersshall be located in dedicated spaces and protected from damage. For indoor

    locations, this space is equal to the width and depth of the equipment and

    extends from the floor to a height of 1.8 m (6 ft) above the equipment or to the

    structural ceiling, whichever is lower. No piping, ducts, leak protection

    apparatus, or other equipment foreign to the electrical installation shall be

    located in this zone.

  • 8/10/2019 09_safetyengineering

    41/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.41

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    TABLE 3 Working Spaces

    Minimum clear distance [mm(ft)]

    Nominal

    voltage to

    ground

    Condition

    (a)

    Condition

    (b)

    Condition

    (c)

    0-150 900 mm (3 ft) 900 mm (3 ft) 900 mm (3 ft)

    151-600 900 mm (3 ft) 1 m (3.5 ft) 1.2 m (4 ft

    Conditions (a), (b), and (c), are as follows:

    (a) Exposed live parts on one side and no live or grounded parts on the otherside of the working space, or exposed live parts on both sides effectively

    guarded by suitable wood or other insulating materials.

    (b) Exposed live parts on one side and grounded parts on the other side.

    Concrete, brick, or tile walls shall be considered grounded

    (c) Exposed live parts on both sides of the workspace [not guarded as

    provided in Condition (a)] with the operator between.

    Note: this table is taken from the 2005 version of the NEC article 110, table

    110.26(a)(1).

    9.6.6.2 High Voltage (> 600V)

    Buildings, rooms, or enclosures containing exposed live parts or exposed

    conductors operating at over 600 volts, nominal, shall be equipped with a

    means of preventing access. A wall, screen, or fence shall be used to enclose

    outdoor electrical installations to deter access by unqualified persons. A fence

    shall not be less than 2.1 m (7 ft) in height or a combination of 1.8 m (6 ft) or

    more of fence and a 0.30 m (12in) extension utilizing three or more strands of

    barbed wire or equivalent. At least one entrance not less than 0.61 m (24 in)

    wide and 2.0 m (6.5 ft) high shall be provided to give access to the working

    space about electric equipment. On switchboard and control panels exceeding1.6 m (6 ft) in width, there shall be one entrance at each end of the equipment

    A single entrance shall be permitted if

    a) the location permits a continuous and unobstructed way of exit travel

    (e.g. away from the equipment), or

  • 8/10/2019 09_safetyengineering

    42/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.42

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    b) the depth of the workspace is twice that shown in TABLE 4 and thedistance from the entrance to the nearest edge of the equipment is not

    less that shown in TABLE 4 for the voltage and condition applicable to

    the equipment. Where bare energized parts (at any voltage) or

    insulated energized parts (above 600 volts) are located adjacent to the

    entrance, they shall be suitably guarded with a partition, screen, or

    other barrier against accidental contact. Entrances shall be equipped

    with a means of locking

    Sufficient space shall be provided and maintained around electrical equipment

    to permit safe operation and maintenance of equipment. The minimum

    headroom and working space width is the same as defined above for systems

    energized to 600 volts or less. The working space depth shall be as required in

    TABLE 4. The workspace shall be adequate to permit at least a 90-degree

    opening of doors or hinged panels. The minimum clear working space in fron

    of electric equipment such as switchboards, control panels, switches, circuit

    breakers, motor controllers, relays, and similar equipment may not be less than

    specified in TABLE 4 unless otherwise specified in this section. Distances

    shall be measured from the exposed live parts or from the enclosure or

    opening, if the live parts are enclosed. However, working space is no

    required behind equipment such as dead front switchboards or contro

    assemblies where there are no renewable or adjustable parts (such as fuses or

    switches) on the back and where all connections are accessible from locations

    other than the back. Where rear access is required to work on de-energized

    parts on the back of enclosed equipment, a minimum working space of 0.75 m(30 in) horizontally shall be provided.

    TABLE 4 Minimum Depth of Clear Working Space At Electrical Equipment

    Minimum Depth of Clear Working Space [mm (ft)]

    Nominal voltage

    to ground

    Condition

    (a)

    Condition

    (b)

    Condition

    (c)

    601 to 2,500 900 mm (3 ft) 1.2 m (4 ft) 1.5 m (5 ft)

    2,501 to 9,000 1.2 m (4 ft) 1.5 m (5 ft) 1.8 m (6 ft)

    9,001 to 25,000 1.5 m (5 ft) 1.8 m (6 ft) 2.8 m (9 ft)

    25,001 to 75kV 1.8 m (6 ft) 2.5 m (8 ft) 3.0 m (10 ft)

    Above 75kV 2.5 m (8 ft) 3.0 m (10 ft) 3.7 m (12 ft)

  • 8/10/2019 09_safetyengineering

    43/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.43

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    Conditions (a), (b), and (c) are as follows:

    (a) Exposed live parts on one side and no live or grounded parts on the other

    side of the working space, or exposed live parts on both sides effectivelyguarded by suitable wood or other insulating materials.

    (b) Exposed live parts on one side and grounded parts on the other side.

    Concrete, brick, or tile walls will be considered as grounded surfaces.

    (c) Exposed live parts on both sides of the workspace (not guarded as

    provided in Condition (a)) with the operator between.

    Note: this table is taken from the 2005 version of the NEC article 110, table

    110.34(A).

    Unguarded live parts located above the working space shall be maintained at

    elevations not less than specified in TABLE 5.

    TABLE 5 - Elevation of Unguarded Energized Parts Above Working Space

    Nominal voltage

    between phasesMinimum elevation

    601 to 7,500 2.8 m (9 ft)

    7,501 to 35,000 2.9 m (9.5 ft)

    Over 35kV 2.9 m (9.5 ft) + 9.5 mm (0.37 in) per kV above

    35kV.

    Note: this table is taken from the 2005 version of the NEC article 110, table

    110.34(E)

    9.6.7 Design for Safe Touch Temperature of Equipment

    Maximum surface temperature exceeding 60C (140F) per ASTM C 1055 /

    EN 563 within the power plant shall be guarded, covered, or equipped with a

    means to prevent accidental contact where personnel are likely to be in close

    proximity. Alternative protection can be provided to limit personnel access to

    high temperature areas with standoff systems or other means of preventingaccess. Refer to GE DBD Mechanical System for design requirements.

    9.6.8 Design for appropriate Equipment Guarding

    Appropriate OSHA compliant guards shall be provided to protect personnel in

    the power plant from all exposed hazardous surfaces, e.g. rotating, pinch

  • 8/10/2019 09_safetyengineering

    44/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.44

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    point, electrical, and hot temperatures. Refer to OSHA 29 CFR 1910 Subpart

    O, Machinery and Machine Guarding, for requirements. For projects in

    Europe, refer to EN-292 The Machinery Directive

    9.6.9 Design to Accept Locks (Control of Hazardous EnergyMechanical and Electrical)

    All energy isolating devices shall be designed to accept a lockout device. An

    energy-isolating device is capable of being locked out if it has a hasp or other

    means of attachment to which, or through which, a lock can be affixed, or it

    has a built-in locking mechanism. Energy isolating devices are defined as any

    mechanical device that physically prevents the transmission or release of

    energy, including but not limited to the following:

    A manually operated electrical circuit breaker

    A disconnect switch

    A manually operated switch by which the conductors of a circuit can

    be disconnected from all ungrounded supply conductors, and, in

    addition, no pole can be operated independently

    A line valve

    A block

    Any similar device used to block or isolate energy

    Refer to 29 CFR 1910.147 for design requirements.

    9.6.10 Design of Security Fencing

    Appropriate security fencing shall be provided to restrict access of personnel

    and the public to potentially hazardous power plant equipment (e.g

    switchyards) Refer to GE DBD Civil/Structural System for design

    requirements of the Security Fencing.

  • 8/10/2019 09_safetyengineering

    45/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.45

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    9.7 Design of Emergency Eyewash / Shower Stations

    The installation of emergency safety showers and eyewash fountains are

    required in locations where personnel may contact chemical, biological, or

    physical agents that require emergency washing facilities. Eyewash and

    shower equipment for the emergency treatment of the eyes or body of a person

    exposed to injurious materials shall meet the minimum performance

    requirements outlined below in the General Requirements for Emergency

    Eyewashes / Sowers. Emergency eyewash and shower stations shall mee

    ANSI Z358.1.

    9.7.1 General Requirements for Emergency Eyewashes/Showers

    Provide in accordance with TABLE 6.

    Provide eyewash units in any area where there is a potential for the eyes to

    be exposed to corrosive, irritating, or toxic chemicals, biological hazards,

    or physical hazards, such as chips or dust from sanding or grinding

    processes.

    Connect showers and eyewash units to potable water.

    Specific water temperature ranges are not specified by regulation.Coordinate with client to determine desired water temperature.

    Heat tracing shall be provided for outdoor installations with ambient

    temperatures below 0C (32F) to prevent freezing of piping and

    equipment.

    Emergency showers and eyewash units shall be accessible within 10seconds at walking speed from the potential exposure source. Do not

    locate in rooms or areas with lockable doors.

    The water supply to shower and/or shower/eyewash combination units

    shall be controlled by a shutoff valve, which is visible and accessible forshower testing or maintenance personnel in the event of leaking or failed

    showerhead valves.

    Definitions of the different types of emergency eyewash and shower units used

    in TABLE 6:

    Combination Shower and Eyewash unit*consisting of schedule 80 hot

    dipped galvanized steel, chrome plated bronze stay open ball valves with

  • 8/10/2019 09_safetyengineering

    46/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.46

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    chrome plated ball, stainless steel actuators and actuation graphics, ABS

    plastic shower head delivering a minimum 500 mm (20 in) diameter

    pattern to the target are 1.5 m (5 ft) above standing level, ABS plastic dual

    stream head with ABS plastic float off covers secured with stainless steel

    bead chains, self adjusting 0.5 lb/sec (8.0 gpm) eye/face wash regulator

    assuring a constant, even flow under varying hydraulic conditions.

    Self-contained, Gravity Feed Eyewash unit**with retractable trayprotecting eyewash heads, pinch valve design to ensure positive water

    flow within one second of activation.

    Eyewash / Body Wash unit*** consisting of piping which is hot dip

    schedule 80 steel drain/pedestal mount, 12 mm (0.5 in) chrome plated

    bronze stay open ball valve with chrome plated ball and stainless steel

    push plate with actuation graphic, ABS plastic dual stream head with ABS

    float off covers secured with stainless steel bead chain, self adjusting 0.22

    lb/sec (3.5 gpm) regulator assuring a constant, even flow under varying

    hydraulic conditions, ABS plastic bowl or stainless steel bowl.

  • 8/10/2019 09_safetyengineering

    47/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.47

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    TABLE 6 - Emergency Eyewash / Shower

    System Equipment

    Or Location

    Chemical(s) Wash Station

    Boiler Chemical Feed HRSG Phosphate

    (pH control, corrosioninhibitor, remove hardness)

    Combination Shower andEyewash *

    Selective CatalyticReduction (SCR)

    Ammonia StorageTank and Injection

    Skid

    HRSG 19% Aqueous Ammonia Eyewash / Body Wash

    ***

    Circulating CoolingWater Chemical Feed

    Cooling Tower Sodium Hypochlorite

    Sulfuric Acid, Inhibitor

    And Sulfite

    Combination Shower andEyewash *

    Once-through Cooling Intake Structure Sodium Hypochlorite

    (Reduce Biological Fouling)

    Self-contained, Gravity FeeEyewash **

    ST-G Bldg(Surface Condenser

    Outlet)

    Sodium Sulfite(Reduce Residual Chlorine)

    Utilize Station forCondensate Chemical

    Feed *

    Raw Water ChemicalFeed (if provided)

    Raw Water StorageTank

    Sodium Hypochlorite Eyewash / Body Wash

    ***

    Condensate ChemicalFeed

    ST-G Bldg Oxygen Scavenger andAmmonia

    Combination Shower andEyewash *

    DC Power Supply GT-G PEECCBatteries

    Battery Electrolyte

    (e.g. Sulfuric Acid)

    Personal Eyewash Station(Saline Solution in Bottles

    At Battery CompartmentLevel and CombinationShower and Eyewash

    Base * of Access Stairs

    ST-G Bldg

    Battery Room

    Battery Electrolyte

    (e.g. Sulfuric Acid)

    Eyewash / Body Wash

    ***

    Steam WaterSampling and

    Analysis Panel

    ST-G Bldg

    Ground Floor

    Testing Chemicals Personal Eyewash

    Station (Saline Solution inBottles)

    Water TestingLaboratory (if

    provided)

    ST-G Bldg

    Ground Floor

    Testing Chemicals Eyewash / Body Wash

    ***

    ST HPU ST-G Bldg

    Ground Floor

    Fyrquel (Phosphate Ester) Eyewash / Body Wash

    ***

    Fuel Oil Treatment (ifprovided)

    Fuel Oil Storage Area Magnesium Sulfinate(Vanadium Fuels),

    Hytec 580 made by EthylCorporation

    (Lubricity Additive for LightFuels Kerosene, Naphtha)

    Self Contained, Gravity FeeEyewash **

    Water Treatment Water Treatment Bldg Acid / Caustic storage Combination Shower andEyewash *

  • 8/10/2019 09_safetyengineering

    48/67

    GE PROPRIETARY INFORMATION Safety Engineering Page 9.48

    GE DESIGN BASIS DOCUMENT ERB/PDBD_Project Design Basis Document (05 Nov. 2004)

    9.7.2 Permanent Emergency Showers

    Emergency showers shall be designed and located in accordance with the

    following specifications.

    Provide quick-acting Ball valve for the shower. Shower valve toremain open after the initial pull until manually closed. Locate the

    face of the showerhead between 2.1 m (6.8 ft) and 2.5 m (8 ft) above

    the floor.

    Provide no greater than 0.6 m (23 in) horizontal distance from thecenter of the showerhead to the activating mechanism.

    Provide shower unit with one activating mechanism at no higher than

    1.7 m (5.75 ft) above the floor. Identify each shower location with ahighly visible sign within the area served by the shower.

    Provide well-lighted area around each shower location.

    Provide showerhead and pipe sizing with at least 1.26 l/sec (20 gpm)

    flow, with the operating valve in the open position. Drains are not

    generally provided for emergency showers. Address design and

    operational issues with curbs, sloped floors, and dry drain traps for

    designs incorporating drains. No obstructions, protrusions, or sharp

    objects shall be located within 0.4 m (16 in) from the center of the

    sp