+ All Categories
Home > Documents > 1-5 Synchronizing Relay

1-5 Synchronizing Relay

Date post: 04-Dec-2014
Category:
Upload: leon-williams
View: 234 times
Download: 20 times
Share this document with a friend
12
Functional Range Synchronising Relay : UN1, FN2, SY1, SY/SP C&S Protection & Control Ltd.
Transcript
Page 1: 1-5 Synchronizing Relay

Functional RangeSynchronising Relay : UN1, FN2, SY1, SY/SP

C&S Protection & Control Ltd.

Page 2: 1-5 Synchronizing Relay

22222

Contentss

PPPPPage No.age No.age No.age No.age No.

1 .1 .1 .1 .1 . IntroductionIntroductionIntroductionIntroductionIntroduction 33333

2 .2 .2 .2 .2 . VVVVVoltage Balance Relay Toltage Balance Relay Toltage Balance Relay Toltage Balance Relay Toltage Balance Relay Type UN1ype UN1ype UN1ype UN1ype UN1 3-43-43-43-43-4

3 .3 .3 .3 .3 . FFFFFrequency Balance Relay Trequency Balance Relay Trequency Balance Relay Trequency Balance Relay Trequency Balance Relay Type FN2ype FN2ype FN2ype FN2ype FN2 55555

4 .4 .4 .4 .4 . Synchronising Relay TSynchronising Relay TSynchronising Relay TSynchronising Relay TSynchronising Relay Type SY1ype SY1ype SY1ype SY1ype SY1 6-86-86-86-86-8

5 .5 .5 .5 .5 . Synchronising Check Relay TSynchronising Check Relay TSynchronising Check Relay TSynchronising Check Relay TSynchronising Check Relay Type SY/SPype SY/SPype SY/SPype SY/SPype SY/SP 9-119-119-119-119-11

Page 3: 1-5 Synchronizing Relay

33333

1. Introduction

Each time a Generator is connected to another power system it has got to be electrically connected, the method of thisconnection is called Synchronisation.

Generator can be sychronised only when the conditions as below are satisfied :

Voltage of the two sources to be equal or within tolerance of 1%,

Frequency of the two sources to be equal or within tolerance of 0.15 Hz &

Phase angle difference to be zero or maximum difference to 70.

These conditions can be satisfied Automatically by using UN1UN1UN1UN1UN1 -Voltage Balance Relay, FN2 FN2 FN2 FN2 FN2 -Frequency Balance Relay,SY1SY1SY1SY1SY1 -Synchronisation Relay and for manual synchronisation the SY/SPSY/SPSY/SPSY/SPSY/SP -Check Synchronisation Relay.

Further more, a complete automatic power station should also have Load Balancing Relay -WLA2WLA2WLA2WLA2WLA2 and FrequencyRegulator Relays -SFG3-SFG3-SFG3-SFG3-SFG3.

Semi-automatic synchronization by synchronizing unit SY1SY1SY1SY1SY1 means :

Manual speed up or slow down the genset to equalize the frequency / manual setting of alternator voltage / monitoringof frequency difference, voltage difference and phase angle by paralleling unit SY1SY1SY1SY1SY1 / impulse to close alternator CBCBCBCBCB byunit SY1.SY1.SY1.SY1.SY1.

Fully-automatic balance FN2FN2FN2FN2FN2 senses the frequency difference between bus bars and genset. It provides correction pulsesto the electrical governor of the driving motor to speed up or slow the generator as required for synchronization.

Voltage balancer UN1UN1UN1UN1UN1 senses the voltage difference between bus bars and alternator. It provides correction pulses to themotorized setting potentiometer to adjust alternator voltage as required for synchronization.

Paralleling unit SY1SY1SY1SY1SY1 monitors frequency difference voltage difference and phase angle and provides closing impules forthe alternator circuit breaker. With the load balancing unit WLA2WLA2WLA2WLA2WLA2 automatic load balance can subsequently be carriedout.

UN1 - Voltage Balance Relay

Application

This unit is used for automatic voltage balancing betweenthree-phase alternators, preferably paralleling alternatorswith the mains supply and alternators with out paralleledexcitation systems.

The motorized potentiometer for the voltage settingreceives impulses to adjust the required voltage.

Function

The unit UN1UN1UN1UN1UN1 consists of two measuring circuits, one is themain or reference supply and the other is connected to thesystem which is to be balanced. It is useful to have anadditional selector switch “Manual-Automatic” in thesynchronisation scheme.

The Unit compares the two supplied voltage and givesoutgoing impulses to the motorized potentimeter. In case ofhigh voltage difference between two systems the intervalsbetween the impulses are shorter and in case of lowerdifference between the voltages the various motorizedpotentiometers, the impulses are adjustable using two built-in potentiometers.

A built-in voltage measuring circuit closes a contact onterminal 2/10 when the voltage difference between thetwo supplies is smaller than 1%. This contact can be usedin series with the impulses contact of the paralleling unitSY1. That means the closing impulse for the alternatorcircuit breaker is given only when the voltage difference islower than 1%.

It is recommended that the supply voltages are switched offafter paralleling.

Page 4: 1-5 Synchronizing Relay

44444

Contact Positions Front Panel

Technical Data

UN1- Voltage Balancing Unit

Connection voltage : 230V, 110V

Nominal frequency : 50Hz, 60Hz

Pulse duration : 0.3s

Pulse interval : 0.3 ... 1s

Power consumption : 5VA per system

Automatic tracking at : deviation> 1%

Duty : 100% (continuous)

Adjustability : Self-locking spindle-potentiometer for both adjustments, inside cover.

Contact equipment : 1 NO for voltage U1>U2, 1 NO for voltage U1<U2, 1NC for voltageU1:U2<1%

Contact rating : 1250VA at 230V AC

Connection terminals : 2.5 mm2

Housing Dimensions : CSPC -standard case W x H x D : 105 x142 x 91 mm

Outer case material : Track-resistant moulded base with transparent cover

Type of protection : Case IP 10, terminals IP 00

Weight : 0.4kg

Maintenance : None

Service life : 105 operations

Mounting : Flush mounting

closed ifdifference U1 : U2 < 1%

2

10

3

11

4

12

Impulse given if U1 < U2

Impulse given if U1 > U2

UN1

L1 L2

2

U1

>U

2

U1

<U

2

12

9675

11107

<UoUU2U1 >

6

3 4

VOLTAGE BALANCE UNIT

Pulse pause Pulse pause

ba

<1%

Page 5: 1-5 Synchronizing Relay

55555

FN2 - Frequency Balance Relay

Aplication

This unit has been developed for automatic equalization ofthe frequency of generating sets. Output control impulsesare given for speed governor motors, motorizedpotentiometers, steam control valves and the like.

Functions

The frequency control unit is supplied from one phase ofeach system (one phase busbar system and one phasealternator). A selector switch for “manual and automatic”selection is useful.

This unit compares the two frequencies and gives outputimpulses in the right direction (slower or faster) to thespeed governor motor. The interval between the impulsesis shorter when the difference in frequency is high andlonger when the difference is low, in order to achievefastest regulation. The length of the output impulses areadjustable on two potentiometers, to adapt this unit todifferent types of speed governot motors. It isrecommended that the frequency control unit should beswitched off when the generating set is already in parallel,to prevent interferences with the load balancing.

Contact Positions

Front Panel

Technical Data

FN2- Frequency Balancing Relay

Type : FN2

Connection voltage : 230V, 110V

Nominal frequency : 50Hz, 60Hz

Impulse time : 0.2...1s

Power consumption : 3VA per system

Permissible voltage tolerance : +10/-15%

Duty : 100%

Adjustability : Self-locking potentiometer with screw for fine adjustment

Contacts : 1 NO for frequency f1>f2, 1 NO for frequency f1<f2

Contact rating : Max.1250VA at 230V AC

Connection terminals : Metric 4, wires max. 2.5 mm2

Case : CSPC -standard case W x H x D : 105 x141 x 91 mm

Material : Track-resistant moulded base with transparent cover

Type of protection : Case IP 20, terminals IP 00

Weight : 0.4kg

Maintenance : None

Service life : 106 operations

Mounting : Flush mounting

3

11

4

12

Impulse given if 1 < 2f f

Impulse given if f1 > f2

FN

L1 L2

F1

>F

2

F1

<F

2

12

0.2 s0.2 s

1 9673

1172N

<NF2F1 >

61N

3 4

1

FREQUENCY BALANCER

Pulse duration Pulse duration

ba

9573

Page 6: 1-5 Synchronizing Relay

66666

Adjustments

1. Max. permissible difference infrequency

The max. permissible frequency difference is dependenton the kind and size of the driving engine and the fly wheelof the generating set.

Following are a few examples :

0.1Hz When sets of medium and big size

0.2Hz When sets of small size, turbine sets andDiesel engine generating sets above 500kW.

0.4-0.6Hz Diesel engine generating sets from 50-500kW.

0.7-1.5Hz Diesel engine and combustion engine drivengenerating sets up to 60 kW, with thesuppositions : no heavy fly wheel, compoundalternators and quick switching circuitbreakers.

The max. permissible 2. This is the decisive adjustment forthe permissible switching time for the alternator circuitbreaker, adjusted with potentiometers 1 and 3.

2. Permissible switching time andadjustment of impulse length

Only quick switching circuit breakers should be used, e.g.air contactors, magnet operated circuit breakers. Choosethe max. permissible switching time of the circuit breakerin the right hand part of the diagram.

Example

Frequency difference 0.3 Hz-cuts the line for a switchingtime of 87 ms. Quick circuit breakers are moreadvantageous, slow ones not to be used.

For adjustment of potentiometer 3 do the following :

Switching time of the circuit breaker if used with switchingtime of an auxiliary relay add additional 100 ms. e.g.switching time of the circuit brteaker 40ms makes 160 msto be set at potentiometer 3.

SY1 - Synchronising Relay

Application

This unit is normally used for switching on parallel gener-ating sets with either the mains supply or with othergenerating sets.

Suppositions for switching in parallel are :

coincidence of the phase

equal voltage

equal frequencies

Synchronizing unit SY1 is monitoring these values andgives an output impulse, when they are within their pre-setlimits.

Function

The synchronizer unit SY1 is supplied from one phase ofeach system. The unit compares the two frequencies, thedifference in voltage and measures the phase coincidenceand gives lead impulse to close the alternator circuitbreaker.

Note :Note :Note :Note :Note : The synchronizing unit SY1 is not suitable forparalleling of synchronous mains i.e. if same supplyvoltage is applied to terminals a-6 & to terminals b-7. Thesynchronisation impulse contact does not close.

For paralleling, the SY1 requires a beat of the systems tobe synchronized. As this “beat” is not available fromsynchronous mains, the SY1 can not give the switch-onimpulse, not even if the angular system difference shouldbe “O”. For paralleling of synchronous mains the CSPCsynchronizing unit PSY2/N can be used.

For gensets with a higher capacity (>1000kV) and anincreased rotating mass, we would recommend the use ofour automatic synchronizing units PSY2 or PSY3. Theycombine all functions of the individual units, FN2, UN1and SY1, and provide improved adjustment possibilities.

Possible adjustments, taking into account specific valuesare :

Page 7: 1-5 Synchronizing Relay

3. Leading of the impulse

The main contacts of the circuit breaker should closeexactly at the moment when the phase coincidence isgiven.

This is the reason why the output impulse is leaded. Thenecessary leading time is dependent on the max.permissible frequency difference (potentiometer 2 and theswitching time of the alternator circuit breaker.

This unit measures the voltage difference of the twosystems in order to give the exact lead time.

This permissible voltage difference should beset atpotentiometer 1 in acordance to the left hand part of thediagram.

Example

With the above used values :

Frequency difference 0.3 Hz; circuit breaker 40 ms:

Note : For HT system (using 110V) do not short terminals 6 & 7 as shown on the front plate.Note : For HT system (using 110V) do not short terminals 6 & 7 as shown on the front plate.Note : For HT system (using 110V) do not short terminals 6 & 7 as shown on the front plate.Note : For HT system (using 110V) do not short terminals 6 & 7 as shown on the front plate.Note : For HT system (using 110V) do not short terminals 6 & 7 as shown on the front plate.

auxiliary relay 20 ms makes 60 ms starting at 0.3 Hzcrossing the line for 60 ms one finds under this crossingthe adjustment of 52V for the potentiometer-adjustment52V.

For alternators with a voltage difference between idle andfull load higher value up to 10V is necessary.

The dashed range of the straight line (difference voltagebelow 10V) is normally not reached, since the voltage ofthe alternators has a large harmonic content.

The values are related to a unit with a nominal voltages itis necessary to multiply the values by appropriatemultiplication factor, which is indicated on the front panel.

3.1 Dead Bus Contact

Synchronizer unit SY1 has one additional contact which isopen when the bus bar system is under voltage and closedwhen there is no voltage at terminals a and 6. This contatcan be used to switch in the alternator circuit breakerdirectly without synchronization in case of no voltage onthe bus bar system.

77777

20 msswitching

time

1.4

40 ms

60 ms

80 ms

100 ms

�U[V] 52 V 45 30 15 0 20 40 60 8075 60

1.2

1

0.8

0.6

0.2

0.4

�f[Hz]

87ms 100 t[ms]

ΔU = 25 V

Page 8: 1-5 Synchronizing Relay

Additional information for marine appli-cations

According to the Germanischer Lloyd it is not allowed to setthe frequency difference higher than 1 Hz.

Front Panel

Contact Positions

Technical Data

SY1- Paralleling Unit

Type : SY1SY1SY1SY1SY1

Connection voltage : 230V, 110V

Nominal frequency : 50Hz, 60Hz, 400Hz

Adjustable limit of

Frequency difference : 0.1...2Hz

Adjustable limit of

Floating Voltage difference : 45 ... 95V AC

Adjustable length of impulse : 0.1 ... 0.5s

Power consumption : ca 3 VA

Permissible voltage tolerance : +10/-15%

Permissible switch-on time : 100% ED

Adjustability : Self-blocking potentiometer with screw for fine adjustment

Contacts : 2 NO-contact for switching in parallel; 2 NC-contact for bus bur voltage

Contacts capacity : Max. 1250VA at 230V AC

Case : CSPC-standard case H x B x T : 141 x 105 x 91 mm

Connection terminal : Matric 4, wires max. 2.5 mm2

Type of protection : Case IP10, terminal IP00

Weight : 0.4kg

Maintenance : None

Mounting : Flush mounting

88888

90 V

70

60

50

0.2

0.3O.4O.5

1.02.0

9612

3 2 4

SA SYSY

1210118

1

0.1 Hz

80

SA

7S26S1

U2U1

R2SY

R1 ba

SYNCHRONIZING UNIT

Voltage Diff. freq. Pulse duration

Closed if bus bar voltagefree ( i.e. Voltage notavailable at terminal a & 6)

Impulse when u1 equalto u 2 ( i.e. Synchronisationimpulse)

2 4

11

1 3

8

1210

4

MP

Page 9: 1-5 Synchronizing Relay

K1 - Generator contactor

K2 - Auxiliary Contact Higher

K3 - Auxiliary Contact Lower

F1/U2 - Reference station bus input

F2/U2 - Oncoming machine input

Connection Example for UN1, FN2, SY1

SY/SP - Synchronizing Check Relay

Application

Unit SY/SPSY/SPSY/SPSY/SPSY/SP is used to prevent wrong synchronization ofalternators at manual operation e.g. by unskilledpersonnel.

To prevent high current and mechanical stress atparalleling the following conditions must be fulfilled beforeswitching in parallel :

voltage difference

frequency difference

and phase angle must be inside limits.

Synchronizing check relay SY/SPSY/SPSY/SPSY/SPSY/SP monitors these valuesand provides closure of contact 4-12 if these are insidepresent limits.

Function

Synchronizing check relay SY/SPSY/SPSY/SPSY/SPSY/SP is to connect accordingto connection diagram: bus voltage to terminals a-6, alter-nator voltage to terminals b-7. All inputs are galvanicalisolated and thus connection phase/neutral as well asphase/phase is possible, provided that bus bar voltage,

generator voltage and the connected neutral points of bothsystems have identcal connection features.

The SY/SPSY/SPSY/SPSY/SPSY/SP monitors the difference in frequency andvoltage as well as phase angle of both systems and if thesevalues are in their present limits, switching on the generatorC.B. is released via contacts 4-12.

The SY/SPSY/SPSY/SPSY/SPSY/SP is additionally provided with a contact (3-11)which is opened when voltage is applied to terminals a-6and closed when these terminals are dead. This contactallows closing of the generator C.B. with a dead busbar.

Note :Note :Note :Note :Note : The SY/SPSY/SPSY/SPSY/SPSY/SP cannot be used for monitoring theparallel connection of synchronous systems i.e. if the samesupply voltage is given to terminal a-6 & terminal b-7. Thesynchronisation impulse contact does not close.

This relay would need a “beat” of the systems to besynchronized. Since synchronous systems do not have sucha “beat”, the relay cannot provide release impulses evennot so if the angular difference of the systems would be“O”. For monitoring parallel connection of synchronoussystems our paralleling unit PSY/N can be used.

Note for the use in marine design systems. According toGerman Lloyd approbation the frequency differencesetting must not be more than 1 Hz.

99999

L1

L2

L3

N

F1 F2 F3 F4

4

121212 111111 108777 666

SY1

K2

F1 F2

F1

>F

2

F1<

F2

K3K2

K2

n M

3 ~ /N

G

K3

442 333 21aaa

K1

S1

bbb

K2 K3

K3

K1K1

F5

S1S1

U1

>U

2

U1

<U

2

U2U1

10

K1

K1

Page 10: 1-5 Synchronizing Relay

Contact Positions Front Panel

Technical Data

SY/SP- Synchronising Check Relay

Type : SY/SP

Connection voltage : 230V, 110V

Nominal frequency : 50Hz, 60Hz, 400Hz

Adjustable limit of

Frequency difference : 0.1...2Hz

Adjustable limit of

Voltage difference : 45 ... 95V AC

Consumption : ca 3 VA

Permissible voltage limit : +10/-15%

Permissible switch-on time : 100% ED

Adjustability : Self-blocking potentiometer with screw for fine adjustment

Contacts : 2 NO-contact for switching in parallel; 2 NC-contact for bus bur voltage

Contacts power : Max. 660VA at 230V AC

Type of protection : CSPC-standard case H x B x T : 141 x 105 x 91 mm

Connection terminals : Metric 4 max. wires 2.5 mm2

Type of protection : Case IP 10, terminals IP00

Mounting : Flush mounting

Weight : 0.4kg

Service life : 106 switching operations

Maintenance : None

1 01 01 01 01 0

Closed if bus bar voltagefree ( i.e. Voltage not

available at terminal a & 6)

Impulse when u1 equal tou2 (i.e. Synchronisation

impulse)

1

2

11

12

8

10

3

4 90 V

12101187S2S1

SA

UU

SY

R2R1SY / SP

4231ba

6

2.0

9615

1.00.50.4

0.3

0.2

0.1 Hz

50

60

7080

SYNCHRONIZING UNIT

Voltage Diff. freq.

SA SY

MP

Page 11: 1-5 Synchronizing Relay

Connection Example for SY/SP

Dimensions and drilling sizes for UN1, FN2, SY1 & SY/SP

1 11 11 11 11 1

S2 S3

S1S1

F2 F3F1

L2

L3

N

L1

K1

SY-SP

S1 - Synchronization ON-OFF

S2 - Generator switch ON

S3 - Generator switch OFF

K1 - Generator contactor

G

3 ~ /N

121110876

4321ba

K1

K1K1

91

6 0

a

105

34

b 1 2 3 4

6 7 8 10 11 12

Dm-4.2mm

141

4.515

126.

5

6.5

4.5

52.5

105

98.5

136.

5

b a

Page 12: 1-5 Synchronizing Relay

8. InformationRequiredwith Order

When placing an or-der, please fill in theform on the or mentionin your order the com-plete type key.

Voltage Balance Relay UN1

SupplyVoltage

UN1-

50 = 50/60Hz

Nominalfrequency

Frenquency Balance Relay FN2

SupplyVoltage

FN2-

50 = 50/60Hz

Nominalfrequency

Synchronizing Relay SY1

SupplyVoltage

SY1-

50 = 50/60Hz

Nominalfrequency

Synchronizing Check Relay SY/SP

SupplyVoltage

SY/SP-

400 = 400Hz

Nominalfrequency

*Data subject to change without notice.

110 = 110V230 = 230V

110 = 110V230 = 230V

110 = 110V230 = 230V

110 = 110V230 = 230V

50 = 50/60Hz

400 = 400Hz

FR/F

N2/

05.0

6.01

/160

405

Number

Number

Number

Number


Recommended