Date post: | 29-Dec-2015 |
Category: |
Documents |
Upload: | magdalene-mcdowell |
View: | 219 times |
Download: | 1 times |
1
©A
BB
AB
, 20
08
2008-02-05
Application of Unit Protection Schemes for Auto-Transformers
Zoran Gajić
ABB AB
Vasteras, Sweden
Authors:Z. Gajić, ABB SwedenS. Holst, ABB Sweden
2
©A
BB
AB
, 20
08
2008-02-05
An auto-transformer is a power transformer in which at least two windings have a common part
Typically auto-transformers are used to interconnect two electrical networks with similar voltage levels (e.g. system intertie transformer)
In practice auto-transformer tertiary delta winding is normally included. It serves to limit generation of third harmonic voltages caused by magnetizing currents and to lower the zero sequence impedance for five-limb core constructions or for auto-transformers built from three single phase units
Auto-Transformer
3
©A
BB
AB
, 20
08
2008-02-05
Example Auto-Transformer
L1 L2 L3
L1 L2 L3
L1
L2
L3
400/400/130 MVA400/231/10.5 kV
YNautod5
150o
L1_400
L2_400L3_400
L3_10.5
L1_10.5
L2_10.5
400kV
220kV
10.5kV
L1_220
L2_220L3_220
Auto-transformer Common Winding
Auto-transformer Tertiary, delta-connected Winding
Auto-transformer Serial Winding
4
©A
BB
AB
, 20
08
2008-02-05
Auto-Transformer has Dual Rating
It can be shown that power is transferred in two different ways through an auto-transformer.
One part of the power is transferred by galvanic connection and the other part is transferred via magnetic circuit (i.e. transformer action)
Auto-transformer is cheaper that corresponding two/three winding power transformer design
Possible problem with short circuit current withstand
220 220 220 400 220 400 2203 3 ( ) 3 3
CW CW G TS U I U I I U I U I S S
5
©A
BB
AB
, 20
08
2008-02-05
Auto-transformer Construction
One three-phase unit Typically has five-limb core
Three single-phase units connected to form three-phase group
6
©A
BB
AB
, 20
08
2008-02-05
Possible CT Locations for Auto-Transformer
L1 L2 L3
L1 L2 L3
L1
L2
L3
400kV
220kV
10.5kV
IL1_400_CT1IL2_400_CT1IL3_400_CT1
IL3_10.5_CT7IL2_10.5_CT7IL1_10.5_CT7
IL3_10.5_CT8IL2_10.5_CT8IL1_10.5_CT8
IL1_N_CT5IL2_N_CT5IL3_N_CT5
IL1
_22
0_C
T2
IL2
_22
0_C
T2
IL3_
220_
CT
2
IN_CT4
IL1_N_CT6IL2_N_CT6IL3_N_CT6
IL1_10.5_CT3IL2_10.5_CT3IL3_10.5_CT3
IL1_10.5_CT9IL2_10.5_CT9IL3_10.5_CT9
CT1; 800/1A
CT3; 7000/5A
CT5; 500/1A
CT6; 500/1A
CT7; 4000/1A
CT8; 4000/1A
CT9; 4000/1A
CT4; 1000/1A
CT2; 1200/1A
7
©A
BB
AB
, 20
08
2008-02-05
Possible Differential Protection Principles
Based on autotransformer ampere-turn balance 87T
Based on the first Kirchhoff’s law between galvanically interconnected parts 87B
1 1 2 20N I N I
1 2 30I I I
8
©A
BB
AB
, 20
08
2008-02-05
Special Unit Protections
Restricted Earth-Fault Zero-sequence current based
Dedicated delta winding unit protections
9
©A
BB
AB
, 20
08
2008-02-05
87T Differential protection using CT1 and CT2
L1 L2 L3
L1 L2 L3
L1
L2
L3
400kV
220kV
10.5kV
IL1_400_CT1IL2_400_CT1IL3_400_CT1
IL3_10.5_CT7IL2_10.5_CT7IL1_10.5_CT7
IL3_10.5_CT8IL2_10.5_CT8IL1_10.5_CT8
IL1_N_CT5IL2_N_CT5IL3_N_CT5
IL1
_2
20
_C
T2
IL2
_2
20
_C
T2
IL3
_2
20
_C
T2
IN_CT4
IL1_N_CT6IL2_N_CT6IL3_N_CT6
IL1_10.5_CT3IL2_10.5_CT3IL3_10.5_CT3
IL1_10.5_CT9IL2_10.5_CT9IL3_10.5_CT9
CT1; 800/1A
CT3; 7000/5A
CT5; 500/1A
CT6; 500/1A
CT7; 4000/1A
CT8; 4000/1A
CT9; 4000/1A
CT4; 1000/1A
CT2; 1200/1A
SBase=Throughput Power(400MVA)
Tertiary delta winding can not be loaded
Mandatory zero sequence current reduction
10
©A
BB
AB
, 20
08
2008-02-05
87T Differential protection using CT1 and CT2
Winding W1 W2
Base Power [MVA] 400 400
Ph-Ph, No-Load Voltage [kV]
400 231
Base Primary Current [A] 577 1000
Vector Group Y y0
Zero Sequence Current Elimination
Yes (Mandatory) Yes (Mandatory)
Connected to CT (See Figure 3) CT1 CT2
Base current on CT secondary side [A]
0.721 0.833
11
©A
BB
AB
, 20
08
2008-02-05
87T Differential protection using CT1, CT2 and CT3
L1 L2 L3
L1 L2 L3
L1
L2
L3
400kV
220kV
10.5kV
IL1_400_CT1IL2_400_CT1IL3_400_CT1
IL3_10.5_CT7IL2_10.5_CT7IL1_10.5_CT7
IL3_10.5_CT8IL2_10.5_CT8IL1_10.5_CT8
IL1_N_CT5IL2_N_CT5IL3_N_CT5
IL1
_2
20
_C
T2
IL2
_2
20
_C
T2
IL3
_2
20
_C
T2
IN_CT4
IL1_N_CT6IL2_N_CT6IL3_N_CT6
IL1_10.5_CT3IL2_10.5_CT3IL3_10.5_CT3
IL1_10.5_CT9IL2_10.5_CT9IL3_10.5_CT9
CT1; 800/1A
CT3; 7000/5A
CT5; 500/1A
CT6; 500/1A
CT7; 4000/1A
CT8; 4000/1A
CT9; 4000/1A
CT4; 1000/1A
CT2; 1200/1A
SBase=Throughput Power(400MVA)
Tertiary delta winding can be loaded
Mandatory zero sequence current reduction
12
©A
BB
AB
, 20
08
2008-02-05
87T Differential protection using CT1, CT2 and CT3
Winding W1 W2 W3
Base Power [MVA] 400 400 400
Ph-Ph, No-Load Voltage [kV]
400 231 10.5
Base Primary Current [A] 577 1000 21994
Vector Group Y y0 d5
Zero Sequence Current Elimination
Yes (Mandatory) Yes (Mandatory) No / (Yes)
Connected to CT (See Figure 3) CT1 CT2 CT3
Base current on CT secondary side [A]
0.721 0.833 15.71
13
©A
BB
AB
, 20
08
2008-02-05
87T Differential protection using CT1, CT2 and CT7
L1 L2 L3
L1 L2 L3
L1
L2
L3
400kV
220kV
10.5kV
IL1_400_CT1IL2_400_CT1IL3_400_CT1
IL3_10.5_CT7IL2_10.5_CT7IL1_10.5_CT7
IL3_10.5_CT8IL2_10.5_CT8IL1_10.5_CT8
IL1_N_CT5IL2_N_CT5IL3_N_CT5
IL1
_2
20
_C
T2
IL2
_2
20
_C
T2
IL3
_2
20
_C
T2
IN_CT4
IL1_N_CT6IL2_N_CT6IL3_N_CT6
IL1_10.5_CT3IL2_10.5_CT3IL3_10.5_CT3
IL1_10.5_CT9IL2_10.5_CT9IL3_10.5_CT9
CT1; 800/1A
CT3; 7000/5A
CT5; 500/1A
CT6; 500/1A
CT7; 4000/1A
CT8; 4000/1A
CT9; 4000/1A
CT4; 1000/1A
CT2; 1200/1A
SBase=Throughput Power(400MVA)
Tertiary delta winding can be loaded
CT location within delta winding requires “special attention”
Zero sequence current reduction not required if it is a five-limb or single-phase construction
14
©A
BB
AB
, 20
08
2008-02-05
87T Differential protection using CT1, CT2 and CT7
3 10.5 18.187 kV
Winding W1 W2 W3
Base Power [MVA] 400 400 400
Ph-Ph, No-Load Voltage [kV]
400 231 *
Base Primary Current [A]
577 1000 12698
Vector Group Y y0 y0*
Zero Sequence Current Elimination
No / (Yes) No / (Yes) No / (Yes)
Connected to CT (See Figure 3)
CT1 CT2 CT7
Base current on CT secondary side [A]
0.721 0.833 3.175
* Influenced by CT location within tertiary delta winding
15
©A
BB
AB
, 20
08
2008-02-05
87T Differential protection using CT1, CT5 and CT7
L1 L2 L3
L1 L2 L3
L1
L2
L3
400kV
220kV
10.5kV
IL1_400_CT1IL2_400_CT1IL3_400_CT1
IL3_10.5_CT7IL2_10.5_CT7IL1_10.5_CT7
IL3_10.5_CT8IL2_10.5_CT8IL1_10.5_CT8
IL1_N_CT5IL2_N_CT5IL3_N_CT5
IL1
_2
20
_C
T2
IL2
_2
20
_C
T2
IL3
_2
20
_C
T2
IN_CT4
IL1_N_CT6IL2_N_CT6IL3_N_CT6
IL1_10.5_CT3IL2_10.5_CT3IL3_10.5_CT3
IL1_10.5_CT9IL2_10.5_CT9IL3_10.5_CT9
CT1; 800/1A
CT3; 7000/5A
CT5; 500/1A
CT6; 500/1A
CT7; 4000/1A
CT8; 4000/1A
CT9; 4000/1A
CT4; 1000/1A
CT2; 1200/1A
SBase=Magnetic Power(169MVA)
Tertiary delta winding can be loaded
CT location at neutral point and within delta winding requires “special attention”
Zero sequence current reduction not required if it is a five-limb or single-phase construction
MV (i.e. 220kV) bushings not protected!
16
©A
BB
AB
, 20
08
2008-02-05
87T Differential protection using CT1, CT5 and CT7
* Influenced by CT7 location within tertiary delta winding
Winding W1 W2 W3
Base Power [MVA] 169 169 169
Ph-Ph, No-Load Voltage [kV]
169 231 *
Base Primary Current [A] 577 422 5365
Vector Group Y y0 y0*
Zero Sequence Current Elimination
No / (Yes) No / (Yes) No / (Yes)
Connected to CT (See Figure 3)
CT1 CT5 CT7
Base current on CT secondary side [A]
0.721 0.844 1.341
3 10.5 18.187kV
Influenced by CT5 location in neutral point
17
©A
BB
AB
, 20
08
2008-02-05
87T Differential protection using CT1, CT2, CT7 and CT8
L1 L2 L3
L1 L2 L3
L1
L2
L3
400kV
220kV
10.5kV
IL1_400_CT1IL2_400_CT1IL3_400_CT1
IL3_10.5_CT7IL2_10.5_CT7IL1_10.5_CT7
IL3_10.5_CT8IL2_10.5_CT8IL1_10.5_CT8
IL1_N_CT5IL2_N_CT5IL3_N_CT5
IL1
_2
20
_C
T2
IL2
_2
20
_C
T2
IL3
_2
20
_C
T2
IN_CT4
IL1_N_CT6IL2_N_CT6IL3_N_CT6
IL1_10.5_CT3IL2_10.5_CT3IL3_10.5_CT3
IL1_10.5_CT9IL2_10.5_CT9IL3_10.5_CT9
CT1; 800/1A
CT3; 7000/5A
CT5; 500/1A
CT6; 500/1A
CT7; 4000/1A
CT8; 4000/1A
CT9; 4000/1A
CT4; 1000/1A
CT2; 1200/1A
SBase=Throughput Power(400MVA)
Tertiary delta winding can be loaded
Double CT location within delta winding requires “special attention”
Relay with four restraint inputs required
Mandatory zero sequence current reduction
18
©A
BB
AB
, 20
08
2008-02-05
87T Differential protection using CT1, CT2, CT7 and CT8
* Influenced by double CT location within tertiary delta winding
10.53 9.093
2kV
Winding W1 W2 W3 W3
Base Power [MVA] 400 400 400 400
Ph-Ph, No-Load Voltage [kV]
400 231 * *
Base Primary Current [A] 577 1000 25396 25396
Vector Group Y y0 y0 y0
Zero Sequence Current Elimination
No / (Yes) No / (Yes) No / (Yes) No / (Yes)
Connected to CT (See Figure 3)
CT1 CT2 CT7 CT8
Base current on CT secondary side [A]
0.721 0.833 6.349 6.349
10.53 9.093
2kV
19
©A
BB
AB
, 20
08
2008-02-05
87T Differential protection using CT1, CT5, CT7 and CT8
L1 L2 L3
L1 L2 L3
L1
L2
L3
400kV
220kV
10.5kV
IL1_400_CT1IL2_400_CT1IL3_400_CT1
IL3_10.5_CT7IL2_10.5_CT7IL1_10.5_CT7
IL3_10.5_CT8IL2_10.5_CT8IL1_10.5_CT8
IL1_N_CT5IL2_N_CT5IL3_N_CT5
IL1
_2
20
_C
T2
IL2
_2
20
_C
T2
IL3
_2
20
_C
T2
IN_CT4
IL1_N_CT6IL2_N_CT6IL3_N_CT6
IL1_10.5_CT3IL2_10.5_CT3IL3_10.5_CT3
IL1_10.5_CT9IL2_10.5_CT9IL3_10.5_CT9
CT1; 800/1A
CT3; 7000/5A
CT5; 500/1A
CT6; 500/1A
CT7; 4000/1A
CT8; 4000/1A
CT9; 4000/1A
CT4; 1000/1A
CT2; 1200/1A
SBase=Magnetic Power(169MVA)
Tertiary delta winding can be loaded
CT location at neutral point and within delta winding requires “special attention”
Relay with four restraint inputs required
Zero sequence current reduction not required if it is a five-limb or single-phase construction
MV (i.e. 220kV) bushings not protected!
20
©A
BB
AB
, 20
08
2008-02-05
87T Differential protection using CT1, CT5, CT7 and CT8
* Influenced by CT7, CT8 location within tertiary delta winding
Influenced by CT5 location in neutral point
Winding W1 W2 W3 W3
Base Power [MVA] 169 169 169 169
Ph-Ph, No-Load Voltage [kV] 400 231 * *
Base Primary Current [A] 577 422 10730 10730
Vector Group Y y0 y0 y0
Zero Sequence Current Elimination
No / (Yes) No / (Yes) No / (Yes) No / (Yes)
Connected to CT (See Figure 3)
CT1 CT5 CT7 CT8
Base current on CT secondary side [A]
0.721 0.844 2.683 2.683
10.53 9.093
2kV
10.53 9.093
2kV
21
©A
BB
AB
, 20
08
2008-02-05
87B Differential protection using CT1, CT2 and CT6
L1 L2 L3
L1 L2 L3
L1
L2
L3
400kV
220kV
10.5kV
IL1_400_CT1IL2_400_CT1IL3_400_CT1
IL3_10.5_CT7IL2_10.5_CT7IL1_10.5_CT7
IL3_10.5_CT8IL2_10.5_CT8IL1_10.5_CT8
IL1_N_CT5IL2_N_CT5IL3_N_CT5
IL1
_2
20
_C
T2
IL2
_2
20
_C
T2
IL3
_2
20
_C
T2
IN_CT4
IL1_N_CT6IL2_N_CT6IL3_N_CT6
IL1_10.5_CT3IL2_10.5_CT3IL3_10.5_CT3
IL1_10.5_CT9IL2_10.5_CT9IL3_10.5_CT9
CT1; 800/1A
CT3; 7000/5A
CT5; 500/1A
CT6; 500/1A
CT7; 4000/1A
CT8; 4000/1A
CT9; 4000/1A
CT4; 1000/1A
CT2; 1200/1A
SBase=Throughput Power(400MVA)
Zero sequence current reduction not required
Tertiary delta winding can be loaded
Not sensitive for winding turn to turn faults
22
©A
BB
AB
, 20
08
2008-02-05
87B Differential protection using CT1, CT2 and CT6
WindingW1 W2 W3
Base Power [MVA]400 400 400
Ph-Ph, No-Load Voltage [kV]231 231 231
Base Primary Current [A]1000 1000 1000
Vector GroupY y0 y0
Zero Sequence Current Elimination
No No No
Connected to CT (See Figure 3) CT1 CT2 CT6
Base current on CT secondary side [A]
1.25 0.833 2.00
23
©A
BB
AB
, 20
08
2008-02-05
REF protection using CT1, CT2 and CT4
L1 L2 L3
L1 L2 L3
L1
L2
L3
400kV
220kV
10.5kV
IL1_400_CT1IL2_400_CT1IL3_400_CT1
IL3_10.5_CT7IL2_10.5_CT7IL1_10.5_CT7
IL3_10.5_CT8IL2_10.5_CT8IL1_10.5_CT8
IL1_N_CT5IL2_N_CT5IL3_N_CT5
IL1
_2
20
_C
T2
IL2
_2
20
_C
T2
IL3
_2
20
_C
T2
IN_CT4
IL1_N_CT6IL2_N_CT6IL3_N_CT6
IL1_10.5_CT3IL2_10.5_CT3IL3_10.5_CT3
IL1_10.5_CT9IL2_10.5_CT9IL3_10.5_CT9
CT1; 800/1A
CT3; 7000/5A
CT5; 500/1A
CT6; 500/1A
CT7; 4000/1A
CT8; 4000/1A
CT9; 4000/1A
CT4; 1000/1A
CT2; 1200/1A
Base quantity is current (either CT2 or W2 rating)
Tertiary delta winding can be loaded but it is not protected
Operates only for phase to ground faults
24
©A
BB
AB
, 20
08
2008-02-05
REF protection using CT1, CT2 and CT4
Winding
W1 W2 Neutral Point
Base Primary Current [A]
1000 1000 1000
Connected to CT (See Figure 3)
CT1 CT2 CT4
Base current on CT secondary side [A]
1.25 0.833 1.00
25
©A
BB
AB
, 20
08
2008-02-05
Dedicated unit scheme for tertiary winding
Use simple I> relay to provide only earth-fault protection for tertiary delta winding
IE
Auto-transformer Tertiary, delta-connected Winding
26
©A
BB
AB
, 20
08
2008-02-05
Field Recording
External L2-Gnd fault which before clearing evolved into a L2-L3-Gnd fault
CT1, CT2, CT4 and CT7 currents recorded
CT5 current calculated
Delta winding not loaded, thus CT7 currents are identical in all three phases
50 100 150 200 250500
0
500
1 103
IL1IL2IL3
400kV Current Waveforms
Time [ms]
[Pri
mar
y A
mpe
res]
50 100 150 200 2501.5 10
3
1 103
500
0
500
1 103
IL1IL2IL3
220kV Current Waveforms
Time [ms]
[Pri
mar
y A
mpe
res]
50 100 150 200 250400
200
0
200
400IL1IL2IL3
Common Winding Current Waveforms
Time [ms]
[Pri
mar
y A
mpe
res]
50 100 150 200 2503 10
3
2 103
1 103
0
1 103
2 103
I_in_DeltaIN
Zero Sequence Current Waveforms
Time [ms][P
rim
ary
Am
pere
s]
CT1
CT2
CT5
CT4 & CT7
27
©A
BB
AB
, 20
08
2008-02-05
Calculated Diff Currents from Field Recording
100 200 300 4000
0.5
1
1.5ID_L1ID_L2ID_L3
RMS Differential Currents (CT1 & CT2)
Time [ms]C
urre
nt [
%]
100 200 300 4000
0.5
1
1.5ID_L1ID_L2ID_L3
RMS Differential Currents (CT1, CT2 & CT7)
Time [ms]
Cur
rent
[%
]
100 200 300 4000
0.5
1
1.5ID_L1ID_L2ID_L3
RMS Differential Currents (CT1, CT5 & CT7)
Time [ms]
Cur
rent
[%
]
28
©A
BB
AB
, 20
08
2008-02-05
Calculated REF Diff Current from Field Recording
100 200 300 4000
0.5
1
1.5ID_REF
REF Function
Time [ms]
Cur
rent
[%
]
29
©A
BB
AB
, 20
08
2008-02-05
The following data are crucial for proper application of the selected differential protection scheme for Auto-transformer: Which base quantities (i.e. power, no load voltage and
current) shall be used
Which vector group shall be entered
Whether or not zero sequence current elimination shall be enabled
Conclusion
30
©A
BB
AB
, 20
08
2008-02-05
Selection of unit protection schemes for particular auto-transformer application depends on: Available CTs
User preference
Previous experience
Conclusion