1 Allen M. Weiss, PE, LC ([email protected] ) SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 www.sescolighting.com Florida’s Energy Code Florida’s Energy Code 2007 Florida Building Code-Including 2007 Florida Building Code-Including 2007 Energy Glitch Amendments 2007 Energy Glitch Amendments Effective March 1 Effective March 1 st st , 2009 , 2009 Chapter 13-415 Chapter 13-415 Commercial Lighting Compliance Commercial Lighting Compliance Florida Energy Code
Transcript
Page 1: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

1

Allen M. Weiss, PE, LC ([email protected])

SESCO Lighting1133 W. Morse Blvd.

Winter Park Florida 32789

407-629-6100

www.sescolighting.com

Florida’s Energy CodeFlorida’s Energy Code

2007 Florida Building Code-Including2007 Florida Building Code-Including2007 Energy Glitch Amendments2007 Energy Glitch Amendments

Effective March 1Effective March 1stst, 2009, 2009

Chapter 13-415Chapter 13-415 Commercial Lighting ComplianceCommercial Lighting Compliance

Florida Energy Code

Page 2: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

2

SESCO Lighting is a registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES records for AIA members. Certificates of Completion for non-AIA are available on request.

This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.

Florida Energy Code

Page 3: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

3

SESCO Lighting is a registered Provider with DBPR, the Florida Department of Business and Professional Regulations. Continuing Education Credit earned on completion of this program will be reported to DBPR records for Registered Landscape Architects, Registered Architects, Registered Interior Designers, and licensed Electrical Contractors. Certificates of Completion will be provided for all in attendance for the entire seminar.

This program is registered with DBPR for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the DBPR of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.

Florida Energy Code

Page 4: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

4

Allen M. Weiss P.E, LC is approved and authorized as a Continuing Education Provider by the Florida Board of Professional Engineers (# 0003992), offering “Area of Practice” courses.

In addition, Mr. Weiss is an employee of the Sesco Lighting Company and is offering this lecture to both the attendees and to Sesco Lighting on a “Pro-Bono” basis.

Every attempt has been made to keep this lecture completely generic. At no time during this lecture will products represented by Sesco Lighting be discussed, either by manufacturer’s name, product name or product part number.

Florida Energy Code

Page 5: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

5

Learning ObjectivesLearning Objectives

Florida Energy Code

Students will;

•Obtain a working knowledge of Chapter 13 of the Florida Building Code.

• Compare and evaluate power limiting (watts/sq.ft) requirements pertaining to new, renovated and existing commercial building lighting. •Compare and evaluate control requirements pertaining to new, renovated and existing commercial building lighting.

•Identify and differentiate between indoor and outdoor lighting energy related requirements.

Page 6: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

6

History of the CodeHistory of the Code

Florida Energy Code

In 2001 the Energy Conservation and Protection Act mandated that all states adopt a commercial energy code (ASHRAE 90.1-1999 or something more stringent for Energy standards)

In 2001 Florida adopted only the Power Allowance portion of ASHRAE 90.1

In 2004 Florida adopted their own code, calling it “The Florida Building Code, Chapter 13-Florida Energy Efficiency for Building Construction 2004” (which remains very similar to ASHRAE 90.1). This code was expanded to include both the Power Allowance and the Lighting Control sections

In 2007 the code was revised and published but not yet adopted

On March 1st of 2009, the revised (2007) Florida Energy code was adopted complete with the 2009 Glitch amendments in their legislative format

This is the Law !!!

Page 7: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

7

Current CodesCurrent Codes

Florida Energy Code

Page 8: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

8

Intent & Scope of Energy CodeIntent & Scope of Energy Code

Florida Energy Code

• The provisions of The Florida Building Code - Chapter 13, Florida Energy Efficiency for Building Construction shall regulate:

(1) Building Envelopes

(2) Energy Systems: Mechanical, Electrical, & Illumination Systems for- New building construction- Additions- Alterations- Any change in building configuration

Page 9: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

9

Florida Energy Code - SectionsFlorida Energy Code - Sections

Florida Energy Code

• This code is a statewide code and shall not be made more stringent or lenient by local government.

Page 10: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

10

New Construction & AdditionsNew Construction & Additions

Florida Energy Code

• The provisions of this chapter apply to the Lighting Power Density and the Control requirements of:- All commercial occupancy buildings of any size- Additions to existing commercial occupancy buildings- Multiple-family residential buildings 4 stories or more

above grade- Interior & Exterior Lighting

Alterations & RenovationsAlterations & Renovations• Generally treated as New Construction• Replacement of lighting systems must comply• New or replacement control devices must comply

Page 11: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

11

13-415: Applicable Areas13-415: Applicable Areas

Florida Energy Code

This section of Chapter 13 shall apply to the following:

1. Interior Spaces of buildings;

2. Exterior building features, including facades, illuminated roofs, architectural features, entrances, exits, loading docks, and illuminated canopies; and

3. Exterior building grounds lighting provided through the building’s electrical service.

Page 12: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

12

13-415: Exempt Areas13-415: Exempt Areas

Florida Energy Code

1. Emergency lighting that is automatically off during normal building operation (ex: emergency lighting bug-eyes, recessed ceiling drop down emergency units, etc.)

2. Lighting within living units (ex: individual condo units)

3. Lighting that is specifically designated as required by a health or life safety statute, ordinance, or regulation(ex: NFPA 101 – Life Safety states stairs must have 10fc of lighting and lighting for that purpose would be exempt.)

4. Decorative gas lighting systems

5. Historic buildings, Federally Mandated buildings, and buildings with a total power density of <1W/ft2

* The following are exempt from both the Power Allowance & Controls…

Page 13: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

13

Mandatory: Types of ControlsMandatory: Types of Controls

Florida Energy Code

13-415.1.AB.1.1 Automatic Lighting Shutoff

• Required if building is over 5,000 ft2

• Required to control lighting in all spaces (unless exempt)

• (3) Options for Controls:

1. A scheduled basis using time-of-day operated control device that turns lighting off at specific programmed times (Dimming or Relay System with Low Voltage Switches in spaces)- controls ≤ 25,000ft2 or not more than (1) floor

2. Occupant Sensor (max setting of 30 min.)

3. Signal from another control or alarm device that indicates the area is unoccupied

* You can mix and match the above techniques

Page 14: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

14 Florida Energy Code

Clarification per the DOE:- A building is clarified as a “Building area

surrounded by exterior walls or fire walls.”

Ex: If you have a 10,000 square foot strip mall, with (5) 2,000 square foot tenants, and there are fire walls in between each tenant, you DO NOT need to meet the automatic shutoff requirements for each tenant.

Mandatory: Types of ControlsMandatory: Types of Controls

Ex: If you have a 10,000 square foot, 3-story office building, with (4) 2,000 square foot tenants and 2,000 square feet of common area you DO need to have a control system for the tenants and the building common spaces.

The following interpretation is per the U.S. Department of Energy, Building Energy Codes Program available online at:

http://www.energycodes.gov/training/onlinetraining/video_standard9012004_lighting.stm

* Per the DOE, The intent of the code is to apply to business entities where the whole building control is practical (however, up to local electrical plan reviewer interpretation)

Page 15: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

15

Mandatory: Control ExceptionsMandatory: Control Exceptions

Florida Energy Code

13-415.1.AB.1.1 Automatic Lighting Controls:

Exceptions:

a. Lighting intended for 24-hour operation. (ex: 24-hour pharmacy, 24-hour shift manufacturing facilities, etc.)

b. Lighting in spaces where patient care is rendered. (ex: hospital rooms, assisted living suites, etc.)

c. Spaces where an automatic shutoff would endanger the safety or security of the room or building occupant(s).(ex: mechanical and electrical equipment room, operating room, dental suites, workshops, etc.)

Page 16: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

16Florida Energy Code

13-415.1.AB.1.2 Space Control:

• Each space enclosed by ceiling-height partitions shall have at least one control device to independently control the general lighting within a space.

• Each control shall be capable of overriding any time-of-day scheduled shut-off control for no more than 4 hours

• In ≤10,000 ft2 spaces, each control can serve a max of 2,500 ft2

• In > 10,000 ft2 spaces, each control can serve a max of 10,000 ft2

Mandatory: Indiv. Space Mandatory: Indiv. Space ControlsControls

Page 17: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

17Florida Energy Code

13-415.1.AB.1.2 Space Control:

• Controls can be activated:• Automatically by sensing an occupant (oc. sensor) or• Manually by an occupant (oc. sensor with an override

button or a low voltage “smart” switch tied to a relay panel)

• Each manual device shall be readily accessible and located so the occupants can see the controlled lighting.

Exceptions:

• Remote locations are permitted where security or safety are a concern• Remote control must be labeled to identify the controlled lighting• Remote control must have an indicator pilot light on or next to the

device

Mandatory: Indiv. Space Mandatory: Indiv. Space ControlsControls

Page 18: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

18

Mandatory: Indiv. Space Mandatory: Indiv. Space ControlsControls

Florida Energy Code

13-415.1.AB.1.2 Space Control:

• Occupancy Sensors, that turn lights off within 30 min. of an occupant leaving the space are required in the following specific spaces:

(1) Certain Classrooms (2) Conference/Meeting Rooms(3) Employee Lunch & Break Rooms* Reasoning: Because these spaces are rarely used, an occupancy sensor will save more energy than

another type of control

• If you put an occupancy sensor in these spaces, these spaces are not required to be connected to other automatic lighting shutoff controls.

• This requirement does not apply to spaces with multi-scene control, shop classrooms, laboratory classrooms, and preschool through twelfth grade classrooms. (They are treated as any other space & require (1) of the (3) types of mandatory controls!!!)

Exceptions:

Page 19: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

19Florida Energy Code

13-415.1.AB.1.3 Additional Control:

• Controls are required in the following cases:

• Hotel and motel guest rooms lighting. Hotel and motel guest rooms and guest suites shall have a master control device at the main room entry that controls all permanently installed luminaires and switched receptacles.

Mandatory: Additional ControlsMandatory: Additional Controls

(ex: A card reader that requires you to insert your card when you enter the room in order to turn the lights on. Or a master switch which overrides all other switches in the space. )

Page 20: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

20

Mandatory: Additional ControlsMandatory: Additional Controls

Florida Energy Code

13-415.1.AB.1.3 Additional Control:

• Separate controls are required in the following cases: (if additional to ambient lighting)

• Display or accent lighting. • Case Lighting. Lighting in cases used for display purposes shall have a

separate control device.• Task Lighting. Supplemental task lighting shall have a control device

integral to the luminaires or be controlled by a wall mounted control device provided the control device is readily accessible and located so that the occupant can see the controlled lighting.

• Non-visual lighting. Lighting for nonvisual applications, such as plant growth and food warming.

• Demonstration Lighting. Lighting equipment that is for sale or for demonstration in lighting education.

Page 21: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

21

Mandatory: Exterior Ltg ControlsMandatory: Exterior Ltg Controls

Florida Energy Code

13-415.1.AB.1.4 Exterior Lighting Control:• Photocell or astronomical time switch with 10

hour memory for dusk-to-dawn lighting (or)

• Lighting not designated as dusk-to-dawn shall be controlled only with an astronomical time switch with 10 hour memory

• Exceptions:• Covered vehicle entrances• Exits from buildings or parking

structures where required for safety, security, or eye adaptation

Page 22: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

22

Mandatory: Exterior Ltg EfficiencyMandatory: Exterior Ltg Efficiency

Florida Energy Code

13-415.1.AB.2 Exterior Building Grounds Lighting:

• Exterior Lighting > 100 Watts must also be > 60 lumens/watt

• Exception: the luminaire is controlled by a motion sensor or is exempt under Section 13-415.0 or Section 13-415.AB.1.3)

Page 23: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

23

Mandatory: Tandem WiringMandatory: Tandem Wiring

Florida Energy Code

13-415.1.AB.3 Tandem Wiring:

• This section of the code must only be adhered to if Magnetic ballasts are used (T12 lamps) because magnetic ballasts work best if driving two lamps, not one

• One of several exceptions to this section of the code is to use an electronic ballast

Mandatory: ExitsMandatory: Exits13-415.1.AB.4 Exit Signs:

• Internally illuminated exit signs shall not exceed 5 watts per face.

Page 24: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

24

Prescriptive: 2 Methods Prescriptive: 2 Methods

Florida Energy Code

This chapter contains two methods to comply with the prescriptive requirements of the code:

• Method A: Whole Building Performance Method• Method B: Building Envelope Trade-off Method

Question: Who chooses which Method to use?

Answer: Typically the Mechanical Engineer running the EnergyGuage FLA/COM software program

* Energy compliance printouts from EnergyGuage FLA/COM are required by Florida to be submitted during the permitting stage

Page 25: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

25

Prescriptive: Interior LightingPrescriptive: Interior Lighting

Florida Energy Code

13-415.AB.5 Interior lighting power, Scope

• The interior lighting power allowance for a building or a separately metered or permitted portion of a building shall be determined by the:

Space by Space Method – described in section 13-415.B.1

• Trade-Offs of interior lighting power allowance among portions of the building for which a different method of calculation has been used are not permitted

• Installed interior lighting power must be < than the Allowed interior lighting power

Page 26: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

26Florida Energy Code

13-415.AB.5.1 Installed Interior Lighting Power

• Exceptions:

- The 15 Items listed in the next few slides shall NOT be included in BOTH the lighting power allowance and the installed interior lighting power

- However…- the lighting listed must be in addition to the general lighting - the lighting listed must be independently controlled

Prescriptive: Interior LightingPrescriptive: Interior Lighting

Page 27: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

27Florida Energy Code

Exceptions:

1. Display or accent lighting that is an essential element for the function performed in galleries, museums, monuments.

2. Lighting that is integral to equipment or instrumentation and is installed by its manufacturer.

3. Lighting specifically designed for use only during medical or dental procedures and lighting integral to medical equipment.

4. Lighting integral to both open and glass enclosed refrigerator and freezer cases.

5. Lighting integral to food warming and food preparation equipment.

6. Lighting for plant growth or maintenance.

7. Lighting in spaces specifically designed for use by the visually impaired.

Prescriptive: Exempt Interior Ltg.Prescriptive: Exempt Interior Ltg.

Page 28: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

28Florida Energy Code

8. Lighting in retail display windows, provided the display area is enclosed by ceiling-height partitions. (ex: Macy’s store windows in NYC)

9. Lighting in interior spaces that have been specifically designated as a registered historic landmark. (ex: Inside Independence Hall in Philly)

10.Lighting that is an integral part of advertising or directional signage. (ex: lighting within a sign that is purchased for the building)

11.Exit signs.

12.Lighting that is for sale or lighting educational demonstration systems.

13.Lighting for theatrical purposes, including performance, stage, and film, and video production.

14.Lighting for television broadcasting in sporting activity areas.

15.Casino gaming areas.

Prescriptive: Exempt Interior Ltg.Prescriptive: Exempt Interior Ltg.

Page 29: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

29Florida Energy Code

13-415.AB.5.1 Installed Interior Lighting Power & Appendix B:

When calculating watts, you must include ALL power used by the luminaire • Lamps• Ballasts/Drivers• Current Regulators• Control Devices

Prescriptive: Installed Interior Ltg.Prescriptive: Installed Interior Ltg.

Screw Based Medium Socket Incandescents & Halogens– maximum labeled wattage of the luminaire

Luminaires with Ballasts, Drivers or Transformers – max. UL labeled wattage of lamp/ballast/driver combination or transformer

Line Voltage Track – max. wattage of luminaires in the system or a min. of 30W per linear foot (whichever is greater)

Low Voltage Track – wattage of the transformer supplying the systemException: if two systems are in a space and you can only turn one on at a

time

Page 30: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

30Florida Energy Code

Prescriptive: Calculation Methods Prescriptive: Calculation Methods 13-415.B.1 Space-By- Space Method of Calculating Interior Lighting Power Allowance (LPA)

1.Determine the appropriate building type from table 13-415.B.12.For each space enclosed by partitions 80 % or greater than the ceiling height determine the floor area3.Determine the LPA by using the columns designated space-by-space.4.Multiply the floor area (s) times the allowed Lighting Power Density (LPD) for the space type that most closely represents the proposed use of the space5.The product is the LPA for the space6.The interior LPA is the sum of LPA’s for all spaces

Note: You can go to the IESNA website to see how ASHRAE and IESNA came up with the LPD for each space.

Note: Tradeoffs of Spaces are Allowed (see 13-415.B.1.4) provided that the total installed interior lighting power does not exceed the interior lighting power allowance.

Page 31: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

31Florida Energy Code

Prescriptive: Calculation Methods Prescriptive: Calculation Methods Table 13-415.B.1-Lighting Power Densities (LPD) Using the Space-By Space Method

Common Space Types LPD (W/ft²) Common Space Types LPD

(W/ft²)

Office – enclosed 1.1 for Gymnasium 0.4

Office – open plan 1.1 for Exercise Center 0.3

Conference/Meeting/Multipurpose 1.3 for Convention Center 0.7

Classroom/Lecture/Training 1.4 for Penitentiary 0.7

for Penitentiary 1.3 for Religious Buildings 1.7

Lobby 1.3 for Sports Arena 0.4

for Hotel 1.1 for Performing Arts Theatre 2.6

for Performing Arts Theatre 3.3 for Motion Picture Theatre 1.2

for Motion Picture Theatre 1.1 for Transportation 0.5

Audience/seating area 0.9 Atrium-First three floors 0.6

Page 32: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

32Florida Energy Code

Prescriptive: Calculation Methods Prescriptive: Calculation Methods

Common Space Types LPD (W/ft²) Common Space Types LPD

(W/ft²)

Atrium- each additional floor 0.2 Laboratory 1.4

Lounge/Recreation 1.2 Restrooms 0.9

for Hospital 0.8 Dressing/Locker/Fitting room 0.6

Dining Area 0.9 Corridor/Transition 0.5

for Penitentiary 1.3 for Hospital 1.0

for Hotel 1.3 for Manufacturing facility 0.5

for Motel 1.2 Stairs - active 0.6

for Bar lounge/Leisure dining 1.4 Active storage 0.8

for Family dining 2.1 for Hospital 0.9

Food preparation 1.2 Inactive storage 0.3

Table 13-415.B.1- ContinuedLighting Power Densities (LPD) Using the Space-By Space Method

Page 33: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

33Florida Energy Code

Prescriptive: Calculation Methods Prescriptive: Calculation Methods

Common Space Types LPD (W/ft²) Building Specific Space Types LPD

(W/ft²)

for Museum 0.8 Judges chambers 1.3

Electrical/Mechanical 1.5 Fire stations

Workshop 1.9 Fire station engine room 0.8

Building Specific Space Types LPD (W/ft²

Sleeping quarters 0.3

Gymnasium/Exercise center Post Office – sorting area 1.2

Playing area 1.4 Convention center – exhibit space 1.3

Exercise area 0.9 Library

Courthouse/Police station/Penitentiary Card file & cataloguing 1.1

Courtroom 1.9 Stacks 1.7

Confinement cells 0.9 Reading area 1.2

Table 13-415.B.1- ContinuedLighting Power Densities (LPD) Using the Space-By Space Method

Page 34: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

34Florida Energy Code

Prescriptive: Calculation Methods Prescriptive: Calculation Methods

Building Specific Space Types LPD (W/ft²) Building Specific Space Types LPD

(W/ft²)

Hospital Physical therapy 0.9

Emergency 2.7 Radiology 0.4

Recovery 0.8 Laundry/Washing 0.6

Nurse station 1.0 Automotive/Service/Repair 0.7

Exam/Treatment 1.5 Manufacturing

Pharmacy 1.2 Low bay (<25 ft floor to ceiling height) 1.2

Patient room 0.7 High bay (>25 ft floor to ceiling height) 1.7

Operating room 2.2 Detailed manufacturing 2.1

Nursery 0.6 Equipment room 1.2

Medical supply 1.4 Control room 0.5

Table 13-415.B.1- ContinuedLighting Power Densities (LPD) Using the Space-By Space Method

Page 35: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

35Florida Energy Code

Prescriptive: Calculation Methods Prescriptive: Calculation Methods

Building Specific Space Types LPD (W/ft²) Building Specific Space Types LPD

(W/ft²)

Dormitory – Living quarters 1.1 Mall concourse 1.7

Museum Sports arena

General exhibition 1.0 Ring sports area 2.7

Restoration 1.7 Court sports area 2.3

Bank/Office –banking activity area 1.5 Indoor playing field area 1.4

Religious buildings Warehouse

Worship – pulpit, choir 2.4 Fine material Storage 1.4

Fellowship hall 0.9 Medium/bulky material storage 0.9

Retail (for accent lighting see Sec. 415.B.2) Parking garage – garage area 0.2

Sales area² 1.7 Transportation

Table 13-415.B.1- ContinuedLighting Power Densities (LPD) Using the Space-By Space Method

Page 36: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

36Florida Energy Code

Prescriptive: Calculation Methods Prescriptive: Calculation Methods

Building Specific Space Types LPD (W/ft²) Building Specific Space Types LPD

(W/ft²)

Airport – concourse 0.6 ----

Air/Train/Bus –Baggage area 1.0 ----

Terminal – Ticket counter 1.5 ----

Table 13-415.B.1- ContinuedLighting Power Densities (LPD) Using the Space-By Space Method

In cases where both a common space type and a building specific space type are listed, the building specific space type shall apply.

Page 37: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

37Florida Energy Code

Prescriptive: Exterior PowerPrescriptive: Exterior PowerAllowances Allowances

Exterior Building Lighting Power Densities

See enclosed table 13-415.AB.2.2

The upper part of the table includes tradable surfaces. An example would be if you used less than the allowable 0.15 W/ft² for the Parking Lots, you could use the left over power in your walkways or possible the outdoor stairways.

The lower part of the table includes non tradable surfaces. Each application can be used only for the specific application and cannot be traded between surfaces or with other exterior lighting. It is a use it or lose it application.

The total exterior lighting power allowance would be the sum of all individual power allowances plus a bonus of 5%

Page 38: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

38Florida Energy Code

Prescriptive: Exterior PowerPrescriptive: Exterior PowerAllowances Allowances

Applications Lighting Power Densities

Tradable Surfaces (Lighting power densities for uncovered parking areas, building grounds, building entrances, and exits, canopies and overhangs and outdoor sales areas may be traded.)

Uncovered Parking Areas

Parking Lots & Drives 0.15W/ft²

Building Grounds

Walkways less than 10 feet wide 1.0W/linear foot

Walkways 10 feet wide or greater, Plaza areas, Special Feature areas 0.2W/ft²

Stairways 1.0W/ft²

Building Entrances and Exits

Main entries 30W/linear foot of door width

Other doors 20W/linear foot of door width

Canopies and Overhangs

Canopies (free standing and attached and overhangs 1.25W/ft²

Page 39: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

39Florida Energy Code

Prescriptive: Exterior PowerPrescriptive: Exterior PowerAllowances Allowances

Applications Lighting Power Densities

Tradable Surfaces (Lighting power densities for uncovered parking areas, building grounds, building entrances, and exits, canopies and overhangs and outdoor sales areas may be traded.)

Outdoor Sales

Open areas (including vehicle sales lots) 0.5W/ft²

Street frontage for vehicle sales lots in addition to “open area” allowance 20W/linear foot

Non Tradable Surfaces (Lighting power density calculations for the following applications can be used only for the specific application and cannot be traded between surfaces or with other exterior lighting. The following allowances are in addition to any allowance otherwise permitted in the “Tradable Surfaces” section of this table.

Source: Table 9.4.5, ANSI/ASHRAE/IESNA 90.1-2007

Building Facades0.2W/ft² for each illuminated wall or surface or 5.0W/linear foot for each illuminated wall or surface length

Automated teller machines and night depositories

270W per location plus 90W per additional ATM per location

Entrances and gatehouse inspection stations at guarded facilities

1.25W/ft² of uncovered area (covered areas are included in the “Canopies and Overhangs” section of “Tradable Surfaces”)

Loading areas for law enforcement, fire, ambulance and other emergency service vehicles

0.5W/ft² of uncovered area (covered areas are included in the “Canopies and Overhangs” section of “Tradable Surfaces”)

Drive-up windows at fast food restaurants 400W per drive-through

Parking near 24 hour retail entrances 800W per main entry

Page 40: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

40Florida Energy Code

Prescriptive: Exterior PowerPrescriptive: Exterior PowerExemptionsExemptions

• Exceptions:

- The (9) items listed in the next few slides shall NOT be included in the exterior lighting power allowance

- However…- the lighting listed must be independently controlled

(a) Specialized signal, directional, and marker lighting associates with transportation;

(b) Advertising signage or directional signage;

(c) Lighting that is integral to equipment or instrumentation and is installed by its manufacturer;

(d) Lighting for theatrical purposes, including performance, stage, film, and video production

Page 41: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

41Florida Energy Code

Prescriptive: Exterior PowerPrescriptive: Exterior PowerExemptionsExemptions

(e) Lighting for athletic playing areas; (ex: a football and soccer field)

(f) Temporary lighting;

(g) Lighting for industrial production, material handling, transportation sites and associated storage areas; (ex: A concrete facility that produces tilt-up walls outside and ships them out)

(h) Theme elements in theme/amusement parks; (ex: Disney World)

(i) Lighting used to highlight features of public monuments and registered historic landmark structures or buildings. (ex: lighting the Washington Monument in D.C., lighting the American Flag)

Page 42: 1 Allen M. Weiss, PE, LC (aweiss@sescolighting.com)aweiss@sescolighting.com SESCO Lighting 1133 W. Morse Blvd. Winter Park Florida 32789 407-629-6100 .

Florida Energy Code 42

THANK YOU

FOR YOUR TIME !

Course Title: The Florida Energy Code– SESCO Lecture #8

Provider: Allen Weiss / Shayna Bramley

AIA/CES Provider # / Course #: L140 / SES8

FL DBPR-Arch Provider # / Course #: 8190 / AR.12.1371

FL DBPR-Land. Arch Provider # / Course #: N/A

FL DBPR-Int. Des. Provider # / Course #: 8190 / 05.11.713

FL DBPR-Elec.Contr. Provider # / Course #: 0003283 / 0007607