+ All Categories
Home > Documents > 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine,...

1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine,...

Date post: 26-Mar-2015
Category:
Upload: ethan-hunter
View: 216 times
Download: 0 times
Share this document with a friend
Popular Tags:
45
1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.
Transcript
Page 1: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

11February, 2007

Medford, Oregon

March 2011

Medford, Oregon

Grounding Transformers

John S. Levine, P.E.Levine Lectronics and Lectric, Inc.

Page 2: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• It is used to provide a ground path on either an It is used to provide a ground path on either an ungrounded Wye or a Delta connected systemungrounded Wye or a Delta connected system

• The relatively low impedance path to ground maintains the system The relatively low impedance path to ground maintains the system neutral at ground potentialneutral at ground potential

Page 3: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• On Ungrounded systems you can have On Ungrounded systems you can have overvoltages of 6 to 8 times normal with overvoltages of 6 to 8 times normal with arcing faultsarcing faults

Page 4: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

•Plot of transient over-voltage for an arcing ground faultPlot of transient over-voltage for an arcing ground fault

Arcing Ground FaultsArcing Ground Faults Intermittent or Re-strikeIntermittent or Re-strike

Page 5: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

•Intermittent ground fault:Intermittent ground fault: A re-striking ground fault can create a high frequency A re-striking ground fault can create a high frequency oscillator (RLC circuit), independent of L and C values, causing high transient over-oscillator (RLC circuit), independent of L and C values, causing high transient over-voltages.voltages.

– i.e. re-striking due to ac voltage waveform or loose wire caused by vibrationi.e. re-striking due to ac voltage waveform or loose wire caused by vibration

V V

480V Delta Source3Ø Load

Cb bC

Rfe

faS

Page 6: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

CONTROL OF TRANSIENT OVERVOLTAGE

Page 7: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• It supports the voltage on a faulted It supports the voltage on a faulted phasephase– If a single line-to-ground fault occurs on an ungrounded or If a single line-to-ground fault occurs on an ungrounded or

isolated system, no return path exists and no current flowsisolated system, no return path exists and no current flows

– The system will continue to operate but the other two un-The system will continue to operate but the other two un-faulted lines will rise in in voltage by the square root of 3, faulted lines will rise in in voltage by the square root of 3, possibly overstressing the transformer insulation, and possibly overstressing the transformer insulation, and other components, by 173%other components, by 173%

Page 8: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.
Page 9: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.
Page 10: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• Provides a metering point to measure faultsProvides a metering point to measure faults

Page 11: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

A typical example is a Wind Farm. They utilize grounding transformers for fault protection on ungrounded lines

When a ground fault occurs on a collector cable causes the substation circuit breaker to open, the wind turbine string becomes isolated

Turbines do not always detect the fault and the generators continue to energize the cable.

Voltages between the un-faulted cable and the ground rise by the 173%

The transformer, placed on the turbine string, provides the ground path

Page 12: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

A typical example is a Wind Farm.

When the feeder breaker Opens, the collector bus and the step up transformer delta connected MV windingsrely on the Grounding Transformer for their ground path and voltage support.

Page 13: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

Two different constructions:

ZIG ZAG (Zn)

WYE CONNECTED

Page 14: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

•What if no neutral exists (i.e. delta systems)?What if no neutral exists (i.e. delta systems)?– A grounding transformer is installed (either a zig-zag or a wye-delta) A grounding transformer is installed (either a zig-zag or a wye-delta)

from all three phases to create an artificial neutral for grounding from all three phases to create an artificial neutral for grounding purposes purposes onlyonly..

HRG

Broken DeltaGroundingTransformers

Wye-DeltaGroundingTransformers

HRGHRG

Zig-ZagGroundingTransformer

CØBØAØ AØ BØ CØAØ BØ CØ

Page 15: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• The zigzag transformer contains six coils on three cores. The first coil on each core is connected contrariwise to the second coil on the next core.

• The second coils are then all tied together to form the neutral and the phases are connected to the primary coils.

• Each phase, therefore, couples with each other phase and the voltages cancel out

Page 16: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

Typical Wye connection with Neutral end of windings connectedTogether

A B C

Symmetrical three phase source

A B C

Vector diagram of balanced system

A

B

C

Page 17: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

The Zig-Zag connection has 2 windings on each leg.

A

B

Cc

a

b

Page 18: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

C

B

A

b

c

a Each leg of the Zig-Zag Connection is connected to a winding from another which is out of phase

B

C

A

c

b

a

Page 19: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

Cz

Az

Bz

The resulting Zig-Zag connection Is phase shifted with respect to the incoming three phase source

Page 20: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• Limits circulation of triplen harmonics ( 3 rd, 6th, 9th, etc)• Can be used without a Delta connected or 5-

legged core• Elimination of secondary winding results in

smaller footprint, lower cost (25-30%)

Page 21: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• Includes a Delta or Wye connected secondary• Utilizes 4 or 5 legged core when Wye

connected secondary is specified• Multi-functional, provides benefit of auxiliary

power

Page 22: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• Primary Voltage• Phase to Phase continuous

primary current (or Rated kVA)

• Continuous Neutral current• Available Fault Current and

Duration

• Impedance as a % or as an ohms/phase value

• Primary Winding connection

• Secondary connection• Basic overall construction

Know the basic parameters

Page 23: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• This is the system voltage to which the grounded winding is to be connected.

• Don’t forget to specify the BIL also. • In some cases the BIL will be dictated by

equipment considerations, such as 150 kV BIL on 34.5 kV wind farms because of the limitation of dead front connectors

Page 24: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• The Transformer must be sized to carry the rated continuous, phase-to-phase current without exceeding its temperature limit

• The higher the current, the larger and more costly the transformer

• Typical values can be as low as 5 amps to as high as a few hundred

• Include any auxiliary loading requirements

Page 25: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• Is defined as 3X the Phase-to-Phase current (Zero Sequence Current)

• It is the value that is expected to flow in the neutral circuit without tripping protective circuits

• Used to design for thermal capacity of the transformer

Page 26: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• Used to determine the short time heating resulting from a fault on the system which returns through the transformer

• Typical ranges run from a few hundred to a few thousand amps

• Duration is expressed in seconds (i.e. 400 amps for 10 seconds)

Page 27: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• Can be expressed as either a percentage or as an ohmic value

• Either should be chosen such that the un-faulted phase voltages are within the temporary over-voltage capability of:

• The Transformer• Associated equipment (i.e. arresters, terminal connectors, etc.)

• Typical values can be as low as 8% and as much as 100%

• Must be determined by the system designer

Page 28: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• Zig Zag or Grounded Wye

Page 29: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• Specify the secondary voltage and connection for primary Wye connected transformers

• Specify size of auxiliary loading to be connected

• If two winding with no secondary load, advise if the delta winding can be “buried” (not brought out) or if only one bushing is to be brought out for grounding to the tank or testing

Page 30: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• Compartmental pad mount or unit substation design

• Indoor or outdoor• Fluid type (Mineral Oil,

Silicone, or Envirotemp FR3)

• Site Elevation or Environmental conditions

• Connectivity• Dead Front or Live Front• Spade terminals• Cover-mounted or

sidewall• Exposed or enclosed

• Temperature Rise• 65 degrees C• 55 degrees C• 55/65 deg. C

• Special Coating requirements

Page 31: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.
Page 32: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

360 degree cooling ducts

Round CoilsRound Coils

Radial forces are equalized during short circuits & overloads

Page 33: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

Cruciform stacked core constructionCruciform stacked core construction

Page 34: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.
Page 35: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.
Page 36: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.
Page 37: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

The following transformers are for The following transformers are for reference only to let you be aware of reference only to let you be aware of

different type transformers for different different type transformers for different applications. applications.

Page 38: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.
Page 39: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• A Scott – T Transformer is a transformer that A Scott – T Transformer is a transformer that is designed for converting 2 phase current to 3 is designed for converting 2 phase current to 3 phase current or vice-versa.phase current or vice-versa.

Page 40: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• An autotransformer is a transformer that only An autotransformer is a transformer that only have one winding with taps. No isolation is have one winding with taps. No isolation is provided between the primary and secondary. provided between the primary and secondary.

Page 41: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• A Buck-Boost A Buck-Boost transformer is one transformer is one that is designed to that is designed to lower (buck) or raise lower (buck) or raise (boost) the voltage (boost) the voltage in the range of 5% in the range of 5% to 25%. This is a to 25%. This is a great (low cost) way great (low cost) way to get between 208 to get between 208 and 240 Volts, or and 240 Volts, or between 480 and between 480 and 575 Volts. Used on 575 Volts. Used on 1 and 3 Phase 1 and 3 Phase applications.applications.

Page 42: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• A drive isolation A drive isolation transformer is one transformer is one that is typically used that is typically used on AC or DC Drive on AC or DC Drive systems. It typically systems. It typically has the same primary has the same primary and secondary and secondary voltages and is used voltages and is used for isolation. In for isolation. In addition you typically addition you typically have a shield to have a shield to attenuate line to attenuate line to ground noise.ground noise.

Page 43: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

• A constant voltage transformer is one in which A constant voltage transformer is one in which the secondary stays constant with large the secondary stays constant with large swings on the primary voltage. This is swings on the primary voltage. This is accomplished by operating the primary in a accomplished by operating the primary in a saturated mode so even when the primary saturated mode so even when the primary voltage dips you can still maintain a constant voltage dips you can still maintain a constant output. Typical input may be 80% to 110% output. Typical input may be 80% to 110% with the output maintaining 1% voltage with the output maintaining 1% voltage regulation.regulation.

Page 44: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

A copy of this A copy of this presentation presentation can be found can be found

at:at:

www.L-www.L-3.com3.com

Page 45: 1 February, 2007 Medford, Oregon March 2011 Medford, Oregon Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.

www. PacificCrestTrans.comwww. PacificCrestTrans.com

For more information and specification sheets


Recommended