Date post: | 17-Jan-2016 |
Category: |
Documents |
Upload: | angel-greer |
View: | 216 times |
Download: | 0 times |
1
PDCWG Report to ROS
October 13, 2011
Sydney Niemeyer
2
ERCOT Frequency Control Performance
September, 2011
3
ERCOT CPS1 By Day -
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
Day
NE
RC
CP
S 1
0
3500
7000
10500
14000
17500
21000
24500
28000
31500
35000
38500
42000
45500
49000
52500
56000
59500
63000
66500
70000
ER
CO
T P
eak
En
erg
y
CPS 1 Avg CPS 1 Peak Energy
September-2011
152.34ERCOT Monthly CPS1 =
4
ERCOT CPS1 15 Minute Average - Monthly Score
0
20
40
60
80
100
120
140
160
180
200
0:15
1:15
2:15
3:15
4:15
5:15
6:15
7:15
8:15
9:15
10:1
511
:1512
:1513
:1514
:1515
:1516
:1517
:1518
:1519
:1520
:1521
:1522
:1523
:15
Interval Ending
September-2011 152.34CPS 1 =
5
ERCOT CPS1
100
110
120
130
140
150
160
170
CP
S1
Ave
rag
e
100
110
120
130
140
150
160
170
Monthly Average 12 Month Rolling Average
6
Daily RMS1 of ERCOT Frequency
0.0100
0.0150
0.0200
0.0250
0.0300
0.0350
0.0400
0.0450
0.0500
7
Daily RMS1 of ERCOT Frequency
0.0100
0.0150
0.0200
0.0250
0.0300
0.0350
0.0400
0.0450
0.0500
1/1/
2004
4/1/
2004
7/1/
2004
10/1
/200
4
1/1/
2005
4/1/
2005
7/1/
2005
10/1
/200
5
1/1/
2006
4/1/
2006
7/1/
2006
10/1
/200
6
1/1/
2007
4/1/
2007
7/1/
2007
10/1
/200
7
1/1/
2008
4/1/
2008
7/1/
2008
10/1
/200
8
1/1/
2009
4/1/
2009
7/1/
2009
10/1
/200
9
1/1/
2010
4/1/
2010
7/1/
2010
10/1
/201
0
1/1/
2011
4/1/
2011
7/1/
2011
8
Daily RMS1 of ERCOT Frequency
0.0100
0.0150
0.0200
0.0250
0.0300
0.0350
0.0400
0.0450
0.0500
9
Comparing September 2010 vs September 2011 profile of frequency in 5 mHz bins
0
0.02
0.04
0.06
0.08
0.1
0.12
59.9
00
59.9
10
59.9
20
59.9
30
59.9
40
59.9
50
59.9
60
59.9
70
59.9
80
59.9
90
60.0
00
60.0
10
60.0
20
60.0
30
60.0
40
60.0
50
60.0
60
60.0
70
60.0
80
60.0
90
60.1
00
Sep-10
Sep-11
10
ERCOT Total Energy
0
5,000,000
10,000,000
15,000,000
20,000,000
25,000,000
30,000,000
35,000,000
40,000,000
45,000,000
MW
H
2008 2009 2010 2011
11
ERCOT Total Energy from Wind Generation
0
500,000
1,000,000
1,500,000
2,000,000
2,500,000
3,000,000
3,500,000
MW
H
2008 2009 2010 2011
12
ERCOT % Energy from Wind Generation
0.00%
2.00%
4.00%
6.00%
8.00%
10.00%
12.00%
14.00%
Janu
ary
Febru
ary
Mar
chApr
ilM
ayJu
ne July
Augus
t
Septe
mbe
r
Octob
er
Novem
ber
Decem
ber
2008 2009 2010 2011
13
NERC Frequency Response Field Trial
14
NERC BAL-003 Field Trial
• Sets Interconnection minimum frequency response.– Goal to prevent activation of UFLS for the
largest N-2 event 2750 MW.– Present recommendation for Texas is
minimum of -286 MW/0.1 Hz measured at Point B.
• 2750 – 1150 = 1600 MW/(-0.600 x 10) = -266 MW/0.1 Hz.
15
September 28, 2011 PDCWG Open Meeting
• Review of 20% limit of RRS based on Generator Capacity (HSL).
• Discussed history of limit.– Primary Frequency Response (Droop) of 5% will
cause the Governor to move 20% of the output of the generator with a -0.600 Hz change in frequency.
– Distributes reserves on multiple generators to improve Interconnection frequency response and deliverability of reserves.
– 80% loading point on traditional steam turbines had the lowest average heat rate.
16
Historical Performance
• May 15, 2003 event where frequency declined to 59.261 Hz.– From 60.012 to 59.297 in 4.5 seconds.– How much energy can a traditional generator
deliver in 4.5 seconds?• 1511 MW from turbines.• 475 MW from load dampening.• 471 MW from LaaR• 979 MW from Firm Load. (first event)
17
Today: Increased Load Resources and More Turbine Response
– How much energy can a traditional generator deliver in 4.5 seconds?
• 1811 MW from turbines (for same 3434 MW loss)• 475 MW from load dampening.• 1150 MW from LaaR• 0 MW from Firm Load
– For 2750 MW event instead of 3434 MW• 1127 MW from turbines.
18
-600
-540
-480
-420
-360
-300
-240
-180
-120
-60
0
59.30
59.35
59.40
59.45
59.50
59.55
59.60
59.65
59.70
59.75
59.80
59.85
59.90
59.95
60.00
60.05
60.10
MW
/0.1
Hz
Pri
mar
y F
req
uen
cy R
esp
on
se
Fre
qu
ency
-H
z
Frequency Hz Average FrequencyInterconnection Primary Frequency Response Interconnection Average Primary Frequency Response
Thursday, May 15, 20033434
-1450
1984
Total MW Lost
MW Net Loss to Grid
NCLR Tripped or non-conforming load change
-356.9 Average Interconnection Primary Frequency Response MW/0.1 Hz
59.3130
59.4521
60.0124
-356.9-283.7 MW/0.1 Hz MW/0.1 Hz 59.09% of Bias Setting
Primary Frequency Response at Point C
Primary Frequency Response at Point B average
May 15, 2003 Actual Performance
19
59.2
59.3
59.4
59.5
59.6
59.7
59.8
59.9
60
60.1
-10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
Seconds
Hz
-0.3
-0.25
-0.2
-0.15
-0.1
-0.05
0
0.05
0.1
Hz/
seco
nd
Frequency Hz/sec Change
-0.268 Hz/second maximum rate of change.
Resources MW Loss 3434 12.34%
-0.000078043 Max Hz/second/MW Loss
of Total Energy
of Peak Energy
of Total Energy
Total Spinning MW
Total Energy MW 27806 45.65%
13265 47.71%May 15, 2003 02:53
20
If the % of RRS Was Changed
RRS 1150 Supplied by GeneratorsPresent
Limit 20%10% 18% 20% 22% 30% 40% 50% Percent of Generator Capacity allowed for RRS
RRS Generator MW Capacity 11500 6389 5750 5349 3833 2875 2300
Expected PFR @ 5% droop -383.3 -213.0 -191.7 -178.3 -127.8 -95.8 -76.7
59.7 59.46 59.4 59.355 59.1 58.8 58.5
Minimum Generator Capacity required to provide service.MW/0.1 Hz from Minimum Generator Capacity measured at the B Value (Point B settling frequency).
Frequency (Hz) required to move the turbine governor the maximum percentage of RRS on the generator.
Expected Primary Frequency Response from RRS
providers if all capacity is frequency responsive.
21
What FERC wants: loss of two largest generators interconnected at a single switchyard and not trip UFLS.n-2 2750 Simultaneous trip of two largest generators (STP 1 & 2)
RRS Supplied by Load Resources 1150 Trips at 59.700 Hz in one half second.
Remaining MW loss 1600
These MWs must be replaced by turbine frequency response and load dampening of synchronous motors. Worse case would be 344 MW from load dampening and 1256 MW from generators in about 4 seconds.
Frequency Response (MW/0.1 Hz) req for -228.571 59.3 Hz Minimum FrequencyFrequency Response (MW/0.1 Hz) req for -266.667 59.4 Hz Minimum Frequency
Winter peak will be around -73 MW/0.1 Hz since resistive heat load is not frequency responsive.
Load Dampening ranges from -53 MW/0.1 Hz at ERCOT minimum load of 22,000 MW to -166 MW/0.1 Hz at summer peak of 68,294 MW.
Highest risk of UFLS tripping is during the shoulder months, light load periods when the electrical mass of the grid is lowest and frequency moves fastest.
To Prevent UFLS
22
Is 20% the Right Amount?
• Increasing % allowed to be provided by a single Resource would decrease PFR.– Increase risk of UFLS.– Governor can not move Gen full % before UFLS.
• Decreasing % allowed to be provided by a single Resource would increase PFR.– Decrease risk of UFLS.– Easier for Generator to perform.
• No change in %. Continue effort to improve PFR from RRS providers.– Continue to expect PFR from all spinning reserve and
improve their performance.
23
Find Other Sources of PFR
• Short duration, fast response (less than 4 seconds) would decrease the risk of UFLS.– Storage– Flywheel
• Create a Product for this service.
24
Recent Frequency Response Performance
25
-1000.0
-900.0
-800.0
-700.0
-600.0
-500.0
-400.0
-300.0
-200.0
-100.0
0.0
12/0
6/10
11:
25:0
0
12/1
1/10
22:
38:1
8
12/1
6/10
06:
15:0
8
12/1
9/10
02:
39:0
0
12/2
3/10
14:
41:4
2
12/2
6/10
08:
32:0
2
01/1
1/11
06:
50:1
4
01/2
1/11
03:
46:2
8
01/2
8/11
05:
21:4
4
02/0
1/11
22:
27:4
8
02/0
2/11
05:
14:1
8
02/0
2/11
08:
24:3
0
02/0
9/11
13:
01:3
8
02/1
6/11
09:
25:4
0
03/1
4/11
06:
09:3
4
03/1
6/11
20:
45:0
8
03/2
4/11
13:
59:0
6
03/2
9/11
06:
43:0
8
04/0
5/11
22:
02:0
6
04/2
7/11
23:
27:0
6
05/1
6/11
08:
06:3
8
05/2
0/11
19:
34:5
5
05/2
3/11
17:
34:4
0
06/0
1/11
03:
56:3
1
06/0
9/11
14:
17:2
2
06/2
7/11
12:
54:0
2
06/2
7/11
14:
38:2
7
07/1
8/11
09:
13:1
6
07/2
0/11
19:
17:2
4
07/2
5/11
17:
57:1
2
08/0
4/11
12:
55:2
1
08/3
1/11
21:
36:3
2
09/0
4/11
10:
12:0
0
09/1
9/11
01:
35:0
0
MW
/0.1
Hz
ERCOT System Primary Frequency Response - Dec 2010 thru Jul 2011
Point C
B Value w/o LaaRs
-386.1
-545.583.54%
MW/0.1 Hz @ Pt C
of Bias Setting (Pt B)MW/0.1 Hz @ Pt B
Average Performance
26
-1200
-1140
-1080
-1020
-960
-900
-840
-780
-720
-660
-600
-540
-480
-420
-360
-300
-240
-180
-120
-60
0
59.70
59.72
59.74
59.76
59.78
59.80
59.82
59.84
59.86
59.88
59.90
59.92
59.94
59.96
59.98
60.00
60.02
60.04
60.06
60.08
60.10
MW
/0.1
Hz
Pri
mar
y F
req
uen
cy R
esp
on
se
Fre
qu
ency
-H
z
Frequency Hz Average FrequencyInterconnection Primary Frequency Response Interconnection Average Primary Frequency Response
Monday, September 19, 2011830.6
0
830.6
Total MW Lost
MW Net Loss to Grid
NCLR Tripped or non-conforming load change
-602.7 Average Interconnection Primary Frequency Response MW/0.1 Hz
59.7530
59.8393
59.9779 -602.7-369.4 MW/0.1 Hz MW/0.1 Hz 92.58% of Bias Setting
Primary Frequency Response at Point C
Primary Frequency Response at Point B average
27
-0.100
-0.080
-0.060
-0.040
-0.020
0.000
0.020
59.60
59.65
59.70
59.75
59.80
59.85
59.90
59.95
60.00
Frequency Rate of Change
830.6Resource MW Loss
of Peak Energy
of Total Energy
Total Spinning MW
Total Energy MWof Energy
of GenerationTotal Wind Generation MW
Max Hz/second/MW Loss
31383
0.013 -0.000097520
5.56%
22.62%
47.76%
2.65%
1745
7100
-0.081 Hz/second
Hz/second
9/19/2011 1:35
Higher frequency rate of change per MW tripped than the May 15, 2003 event.
28
PDCWG On-going Work
• Continue review of Generator’s Primary Frequency Response Performance.– Contacting low performers to help improve
performance.– Observed PFR from two wind farms during
minor high frequency following unit trips.
• Continue effort to review protocols and guides to clarify PFR and RRS responsibilities.