5
- - - - - - - - - - - - - - - - - - - - - - - - ILL-01 MSB JA NUMBER DRAWING NUMBER DRAWING INDEX OF DRAWINGS DRAWING TITLE DRAWING TITLE BEEN PERSONALLY CHECKED BY THE UNDERSIGNED. NOT TO BE CONSTRUED TO MEAN THAT ALL ASPECTS OF THE DESIGN HAVE THE DESIGN APPEARS TO CONFORM TO APPLICABLE CRITERIA. APPROVAL IS DESIGNER/DRAFTER: CHECKED BY: PROJECT TITLE: TOWN: DRAWING TITLE: PROJECT NO. DRAWING NO. SHEET NO. Filename: SHEET NO. REVISION DESCRIPTION DATE REV. DEPARTMENT OF TRANSPORTATION STATE OF CONNECTICUT OF WORK WHICH WILL BE REQUIRED. THE CONDITIONS OF ACTUAL QUANTITIES IN NO WAY WARRANTED TO INDICATE INVESTIGATIONS BY THE STATE AND IS SHEETS IS BASED ON LIMITED QUANTITIES OF WORK, SHOWN ON THESE THE INFORMATION, INCLUDING ESTIMATED 7/15/2015 BLOCK: SIGNATURE/ Plotted Date: C O N N E C T I C U T D E P A R T M E N T O F T R A N S P O R T A T I O N 10 - ELECTRICAL- ILLUMINATION ON ROUTE 4 (FARMINGTON AVE) FROM GARDEN ST. TO MOUNTAIN SPRING RD. FARMINGTON 51-260 SAFETY & TRAFFIC OPERATIONAL IMPROVEMENTS ELECTRICAL INDEX OF DRAWINGS ILLUMINATION PLAN ILL-02 ELECTRICAL INDEX OF DRAWINGS ILL-01 ELECTRICAL DETAILS 1 ILL-03 ELECTRICAL DETAILS 2 ILL-04 ELECTRICAL DETAILS 3 ILL-05 10.01
Transcript

- -

-

-

-

- -

- - -

- - - -

- - -

- - -

- - - -

ILL-01

MSB

JA

NUMBER

DRAWING

NUMBER

DRAWING

INDEX OF DRAWINGS

DRAWING TITLE DRAWING TITLE

BEEN PERSONALLY CHECKED BY THE UNDERSIGNED.

NOT TO BE CONSTRUED TO MEAN THAT ALL ASPECTS OF THE DESIGN HAVE

THE DESIGN APPEARS TO CONFORM TO APPLICABLE CRITERIA. APPROVAL IS

DESIGNER/DRAFTER:

CHECKED BY:

PROJECT TITLE: TOWN:

DRAWING TITLE:

PROJECT NO.

DRAWING NO.

SHEET NO.

Filename:SHEET NO.REVISION DESCRIPTIONDATEREV.

DEPARTMENT OF TRANSPORTATION

STATE OF CONNECTICUT

OF WORK WHICH WILL BE REQUIRED.

THE CONDITIONS OF ACTUAL QUANTITIES

IN NO WAY WARRANTED TO INDICATE

INVESTIGATIONS BY THE STATE AND IS

SHEETS IS BASED ON LIMITED

QUANTITIES OF WORK, SHOWN ON THESE

THE INFORMATION, INCLUDING ESTIMATED

7/15/2015

BLOCK:

SIGNATURE/

Plotted Date:

CONNECTICU

T

DE

PA

RT

ME

NT

O F TRANS

PO

RT

ATI

ON

10 - ELECTRICAL- ILLUMINATION

ON ROUTE 4 (FARMINGTON AVE) FROM

GARDEN ST. TO MOUNTAIN SPRING RD.

FARMINGTON 51-260SAFETY & TRAFFIC OPERATIONAL IMPROVEMENTS

ELECTRICAL INDEXOF DRAWINGS

ILLUMINATION PLANILL-02

ELECTRICAL INDEX OF DRAWINGSILL-01

ELECTRICAL DETAILS 1ILL-03

ELECTRICAL DETAILS 2ILL-04

ELECTRICAL DETAILS 3ILL-05

10.01

bearms
Stamp
The plans have been checked that the following tasks have been completed correctly: 1. Page Labels 2. Sheet Numbers 3. Watermarked 4. Comments Flattened 5. Digital Signature was applied allowing for markups

228.7

0

LA

NDIN

G

220.6

2

IN

VE

RT

WB-67 - Interstate Semi-Trailer

242.8

LANDING

+222.

88'

+223.

67'

+222.

78'

+222.

49'

+223.

89'

+218.3

0'

+219.4

4'

+217.2

9'

+218.1

1'

+221.8

5'

+225.

92'

+223.

16'

+221.3

9'

+224.

32'

700+00

701+

00

1+60

920+00

920+90

911+00

980+

00

961+

00

101+

00

102+00

103+00

104+

00

105+

00

106+

00

107+

00

108+

00

109+00

110+72

900+00

901+00

902+00

903+00

904+00

904+60

904+60

500+

00

501+00502+00502+82

962+

00

960+

00

970+

00

960+00

961+

00

961+

56

961+

56

110+00

930+

00

931+

00

932+

00

933+00933+10

933+10

940+

00

941+

00

941+

60

941+

60

941+59.

95

PI

950+00

951+00

951+50

951+50

41+

00

42+

00

43+

00

44+

00

45+

00

46+00

47+00

48+00

49+00

800+00

801+

00

DESIGNER/DRAFTER:

CHECKED BY:

PROJECT TITLE: TOWN:

DRAWING TITLE:

PROJECT NO.

DRAWING NO.

SHEET NO.

Filename:SHEET NO.REVISION DESCRIPTIONDATEREV.

DEPARTMENT OF TRANSPORTATION

STATE OF CONNECTICUT

SCALE 1"=40'

40 800

SCALE IN FEETOF WORK WHICH WILL BE REQUIRED.

THE CONDITIONS OF ACTUAL QUANTITIES

IN NO WAY WARRANTED TO INDICATE

INVESTIGATIONS BY THE STATE AND IS

SHEETS IS BASED ON LIMITED

QUANTITIES OF WORK, SHOWN ON THESE

THE INFORMATION, INCLUDING ESTIMATED

7/15/2015

BLOCK:

SIGNATURE/

DATE: APPROVED BY:

OFFICE OF ENGINEERING

...\HW_MSH_0051-0260_ILL-02.dgnPlotted Date:

CONNECTICU

T

DE

PA

RT

ME

NT

O F TRANS

PO

RT

ATI

ON

SAFETY & TRAFFIC OPERATIONAL IMPROVEMENTS

ON ROUTE 4 (FARMINGTON AVE) FROM

GARDEN ST. TO MOUNTAIN SPRING RD.

ILL-02

51-260

#2018

SNET

LOCATION WITH TRAFFIC SIGNAL SPAN POLE

LOCATE WITHIN TOWN R.O.W. COORDINATE

SERVICE ENTRANCE AND CABINET - TYPE II

COORDINATE GRIDCONNECTICUT

U.G. SERVICE WITH UTILITY COMPANY

COORDINATE 120/240V, SINGLE PHASE

RO

UTE 4

FAR

MIN

GT

ON

AVE.

SPECIFICATIONS, AND WHERE APPLICABLE, UTILIITY COMPANY REGULATIONS.

ALL ELECTRICAL WORK SHALL CONFORM TO THE NATIONAL ELECTRIC CODE, CONNECTICUT STANDARD

INSTALL ONE NUMBER 8 BARE COPPER GROUNDING CONDUCTOR THROUGHOUT ALL LIGHTING CIRCUITS.

1)

2)

3)

4)

5)

6)

7)

ILLUMINATION NOTES

ILLUMINATION LEGEND

AND INSTALLING THE PULL-LINE SHALL BE INCLUDED IN THE COST OF THE CONDUCTORS.

WHERE CONDUCTORS ARE TO BE PULLED INTO NEW CONDUIT, THE COST OF FURNISHING

MSB

JA

ILLUMINATION

PLAN

OF FARMINGTON.

(860-651-2560). PAYMENT FOR THE MONTHLY ENERGY COSTS SHALL BE THE RESPONSIBILITY OF THE TOWN

COORDINATE METERED ELECTRIC SERVICE HOOK-UP: KEVIN O'BRIEN (860-280-2445) OR JOHN SCHERDECHNY

THE CONTRACTOR SHALL CONTACT THE FOLLOWING EVERSOURCE REPRESENTATIVE 30 DAYS IN ADVANCE TO

TAPE ALL UNUSED CONDUCTORS.

10)

SUBMERSIBLE CONNECTORS.

ALL CONDUCTOR SPLICES IN CONCRETE HANDHOLES SHALL BE MADE WITH INSULATED

8)

9)

TO CENTERLINE OF POLE) OR AS INDICATED ON THE PLANS.

LIGHT STANDARD FOUNDATIONS SHALL BE INSTALLED AS FOLLOWS (DISTANCE

11) ALL PVC CONDUIT SHALL BE SCHEDULE 80.

PRECAST POLYMER CONCRETE HANDHOLE

EXISTING LUMINAIRE ON EXISTING UTILITY POLE

HANDHOLES AND CONDUIT.

CONTRACTOR SHALL VERIFY R.O.W. LINE PRIOR TO INSTALLING FOUNDATIONS,12)

CAP CONDUIT 24" BELOW GRADE

FOR FUTURE USE

AND CAP BOTH ENDS

BELOW DRIVEWAY

INSTALL CONDUIT 24"

CIR. #1 & 2

CIR. #1

CIR. #2

CIR. #2

CIR. #2

CIR. #1

CIR. #1

CIR. #1

FOR FUTURE USE

TERMINATE CIR. #1 IN HANDHOLE

LIGHT POLE BASE

TERMINATE CIR. #2 IN

ALL DECORATIVE LUMINAIRES SHALL BE RATED I.E.S. FULL-CUTOFF WITH TYPE 4 LIGHT DISTRIBUTION.

OF R.O.W. BOUNDARY

LOCATE FOUNDATION IN FRONT

- DIRECTLY BEHIND SIDEWALK (SEE DRAWING NO. ILL-04)

AS FOLLOWS: BLACK, WHITE AND GREEN.

SHALL BE COLORED CROSS LINKED POLYETHELENE (XLP). SINGLE PHASE CIRCUIT COLORS SHALL BE

CONDUCTORS SHALL BE COPPER, INSULATION TYPE XHHW AND RATED FOR 600 VOLTS. INSULATION

(TYPE 4, FULL-CUTOFF, 20' MOUNTING HEIGHT ALUMINUM POLE)

DECORATIVE LIGHT POLE AND SINGLE LUMINAIRE

CIR. #2

FOUNDATION

BYPASS LIGHT POLE

CIR. #2 CONDUIT TO

WORKS DEPARTMENT TO COORDINATE SYSTEM TURN OVER AND MONTHLY ENERGY BILL RECIPIENT.

THE CONTRACTOR SHALL CONTACT MR. RUSSELL ARNOLD (860-675-2305) OF THE CITY OF FARMINGTON PUBLIC

ENERGY COSTS ASSOCIATED WITH THE LIGHTING SHALL BE THE RESPONSIBILITY OF THE CITY OF FARMINGTON.

LATERAL CONDUCTORS SHALL BE THE PROPERTY OF THE CITY OF FARMINGTON. ALL SYSTEM MAINTENANCE AND

THE PROPOSED LIGHTING EQUIPMENT SHOWN ON THIS PLAN WITH THE EXCEPTION OF THE UTILITY SERVICE

CABINET, 120/240V, 1 PHASE. SERVICE SHALL BE METERED.

SERVICE ENTRANCE AND CABINET - TYPE II. PEDESTAL MOUNTED

- 4' BEHIND EDGE OR ROADWAY WHERE NO SIDEWALK IS PRESENT

UTILITY COMPANY

LATERAL. CONDUCTORS BY

3" PVC (SCHED. 80) SERVICE

1‚" PVC CONDUIT (SCHED. 80) IN TRENCH (2 #4, 1 #8 BARE GND.)

3" PVC CONDUIT (SCHED. 80) UNDER ROADWAY (UTILITY SERVICE LATERAL)

FARMINGTON

10.02

NO SCALE

DESIGNER/DRAFTER:

CHECKED BY:

PROJECT TITLE: TOWN:

DRAWING TITLE:

PROJECT NO.

DRAWING NO.

SHEET NO.

Filename:SHEET NO.REVISION DESCRIPTIONDATEREV.

DEPARTMENT OF TRANSPORTATION

STATE OF CONNECTICUT

OF WORK WHICH WILL BE REQUIRED.

THE CONDITIONS OF ACTUAL QUANTITIES

IN NO WAY WARRANTED TO INDICATE

INVESTIGATIONS BY THE STATE AND IS

SHEETS IS BASED ON LIMITED

QUANTITIES OF WORK, SHOWN ON THESE

THE INFORMATION, INCLUDING ESTIMATED

7/15/2015

BLOCK:

SIGNATURE/

APPROVED BY:

OFFICE OF ENGINEERING

...\HW_MSH_0051-0260_ILL-03.dgnPlotted Date:

CONNECTICU

T

DE

PA

RT

ME

NT

O F TRANS

PO

RT

ATI

ON

JA

MSB

ON ROUTE 4 (FARMINGTON AVE) FROM

GARDEN ST. TO MOUNTAIN SPRING RD.

FARMINGTON

ILL-03

51-260 SAFETY & TRAFFIC OPERATIONAL IMPROVEMENTS

S

PRECAST PEDESTAL BASE - TYPE I

A

-

SECTION A

-

SERVICE ENTRANCE AND CABINET TYPE II

SERVICE ENTRANCE AND CABINET TYPE II

PANEL LAYOUT

RECEPTACLE

LAMP

BLOCK

FUSE

SWITCH

MANUAL

AUTO ON

CONTROL

PHOTO RELAY

CONTACTOR BAR

GND.

BREAKER

MAIN CIRCUIT

WIRING DIAGRAM

UNLATCH

LATCH

MAIN CIRCUIT BREAKER

30 AMP, 2 POLE, 240 VOLT

STEEL BARS

12 #3 REINFORCING

TRANSFORMER BASE

GROUNDING STUD

NUT AND WASHER (TYP.)

ANCHOR BOLT WITH HEX

SHIM AS REQUIRED

ON PLANS

AND QUANTITY AS INDICATED

R.M.C. SWEEP, SIZE, DIRECTION

BUSHING

INSULATED BONDING

WIRE

#8 BARE GROUND

METER SOCKET

METER

UTILITY CO.

PRECAST BASE

ALUMINUM PEDESTAL

FOR PEDESTAL MOUNT

REINFORCED BOTTOM

UTILITY CO. REQUIREMENTS

P.V.C. SLIP JOINT AS PER

STRAP

2 HOLE

GRADE

FINISHED

"TWIST LOCK" TYPE

PHOTO CONTROL

PLYWOOD BACKBOARD

(MECHANICALLY HELD)

CONTACTOR W/120 VOLT COIL

30 AMP, 2 POLE, 240 VOLT

NEUTRAL BUS BAR

10 AMP FUSE

D.P.D.T. RELAY

20 AMP, 125 VOLT

G.F.C.I. DUPLEX RECEPTACLE

MANUAL SWITCH

CIRCUIT BREAKER

20 AMP, 1 POLE, 240 VOLT

STRAP

2 HOLE

"LB" FITTING

PULL CHAIN

LAMP HOLDER WITH

BREAKER

BRANCH CIRCUIT

TO LUMINAIRES (120 VOLT)

CIR #1 CIR #2

ELECTRICAL DETAILS 1

CONDUIT TO LIGHTS

10'

NO. 8 BARE CU. GROUND WIRE - BOND TO GROUND ROD

O-Z GEDNEY TYPE CG OR APPROVED EQUAL

BONDING CLAMP APRROVED FOR DIRECT BURIAL.

CLAMP AS PER N.E.C.

U.G. SERVICE LATERAL AT UTILITY POLE

UTILITY POLE

BY UTILITY COMPANY)

CONTRACTOR, CONDUCTORS

& CONDUIT BY BACKFILLING

SERVICE LATERAL (TRENCHING,

#8 BARE GROUNDING CONDUCTORS

BONDING BUSHINGS

TO CABINET & INSULATED

(METER BY UTIL. CO.)

COMPANY REQUIREMENTS

METER SOCKET - PER UTILITY

SERVICE - 120/240V, 1~

10'-0"

25"

40"

36"

5'-0"

4"

24"

24"

THICKNESS

.125" WALL

17"

3" R.M.C.

TO UTILITY SERVICE POLE

3" SCHEDULE 80 P.V.C.

3" R.M.C. ELBOWBARE COPPER GROUND

ƒ" R.M.C. WITH 1#8

1•" R.M.C.

3" R.M.C.

24"

CABINET

TO SERVICE ENTRANCE

3" SCHEDULE 80 P.V.C.

3" R.M.C. ELBOW

20"

4"

4"

CIRCLE

12•" BOLT

20"

†" x 8' GROUND ROD

WASHERS AND NUTS TO BE GALVANIZED.

ENTIRE LENGTH AFTER THREADING. FLAT

SHALL BE HOT DIPPED GALVANIZED FOR

ANCHOR BOLTS TO BE ƒ" x 18" MIN. AND

2"

30"

4"

4"

8†" DIA. CENTER CORE

36" ALUMINUM PEDESTAL

10.03

NO SCALE

DESIGNER/DRAFTER:

CHECKED BY:

PROJECT TITLE: TOWN:

DRAWING TITLE:

PROJECT NO.

DRAWING NO.

SHEET NO.

Filename:SHEET NO.REVISION DESCRIPTIONDATEREV.

DEPARTMENT OF TRANSPORTATION

STATE OF CONNECTICUT

OF WORK WHICH WILL BE REQUIRED.

THE CONDITIONS OF ACTUAL QUANTITIES

IN NO WAY WARRANTED TO INDICATE

INVESTIGATIONS BY THE STATE AND IS

SHEETS IS BASED ON LIMITED

QUANTITIES OF WORK, SHOWN ON THESE

THE INFORMATION, INCLUDING ESTIMATED

7/15/2015

BLOCK:

SIGNATURE/

APPROVED BY:

OFFICE OF ENGINEERING

...\HW_MSH_0051-0260_ILL-04.dgnPlotted Date:

CONNECTICU

T

DE

PA

RT

ME

NT

O F TRANS

PO

RT

ATI

ON

JA

MSB

SAFETY & TRAFFIC OPERATIONAL IMPROVEMENTS

ON ROUTE 4 (FARMINGTON AVE) FROM

GARDEN ST. TO MOUNTAIN SPRING RD.

FARMINGTON

ILL-04

51-260

CRUSHED STONE

12" GRAVEL OR

ALL SIDES (TYP.)

GRADE LINE ON

•"

AS REQUIRED

CONDUIT - LENGTH

12"

18"

PULL SLOT

BOLT HOLE (TYP.)

+17"

+10"

1/2" WALL THICKNESS

30"

WASHER

3/8" MIN. DIAMETER, WITH

STAINLESS STEEL HEX BOLT

STAMP

ANSI TIER RATING

PRECAST POLYMER HANDHOLE

SURFACE

SKID RESISTANT

POLYMER HANDHOLE INSTALLATION

FLOW

TRAFFIC

LIGHT STANDARD FOUNDATION (TYPE I)

PARALLEL TO ROADWAY

THESE BOLTS ARE TO BE

ALL SIDES

GRADE LINE

45°BEVEL

CLASS "F" CONCRETE

4"

GROUND WIRE

AND SYSTEM

WIRE TO POLE

NO. 8 CU GROUND

PAVEMENT OR SIDE WALK

DO NOT INSTALL UNDER

5/8" X 10' GROUND ROD

WELDING

COMPOUND AFTER

WITH BITUMASTIC

CLEAN AND COAT

EXOTHERMIC WELD.

4' - 0"

SIDEWALK

E.O.R.

+ 1"

FOUNDATION OFFSET

TYPICAL LIGHT POLE

(SIDEWALK)

FOUNDATION OFFSET

TYPICAL LIGHT POLE

20' - 0"

24"

21"

52"

25‚

"

18"

CLAMSHELL BASE AND LUMINAIRE

FINISH TYPICAL FOR POLE, ARM,

TEXTURED BLACK POWDERCOAT

ELECTRICAL DETAILS 2

12"

18"

ALUMINUM TUBE

DIAMETER ROUND EXTRUDED

ONE PIECE, SEAMLESS 5Œ"

2…" EXTRUDED ALUMINUM TUBE

11‚"

1ƒ"

18„

"

(2 SIDES)

2•" x 4" MOUSE HOLE

20‚

"

13…"

+10"

E.O.R.

8ƒ"

TO ORDERING

POLE MANUFACTURER PRIOR

12•" - VERIFY WITH

26"

26"

3"

2"

2"

1•"

9•" RADIUS

1‚" R.M.C. (TYP.)

1•

"

26"

PRIOR TO ORDERING

WITH POLE MANUFACTURER

WITH NUTS - VERIFY

1" X 36" ANCHOR BOLTS

72"

22" (TYP.)

ƒ" PVC GROUND ROD SWEEP

10.04

NO SCALE

DESIGNER/DRAFTER:

CHECKED BY:

PROJECT TITLE: TOWN:

DRAWING TITLE:

PROJECT NO.

DRAWING NO.

SHEET NO.

Filename:SHEET NO.REVISION DESCRIPTIONDATEREV.

DEPARTMENT OF TRANSPORTATION

STATE OF CONNECTICUT

OF WORK WHICH WILL BE REQUIRED.

THE CONDITIONS OF ACTUAL QUANTITIES

IN NO WAY WARRANTED TO INDICATE

INVESTIGATIONS BY THE STATE AND IS

SHEETS IS BASED ON LIMITED

QUANTITIES OF WORK, SHOWN ON THESE

THE INFORMATION, INCLUDING ESTIMATED

7/15/2015

BLOCK:

SIGNATURE/

APPROVED BY:

OFFICE OF ENGINEERING

...\HW_MSH_0051-0260_ILL-05.dgnPlotted Date:

CONNECTICU

T

DE

PA

RT

ME

NT

O F TRANS

PO

RT

ATI

ON

JA

MSB

SAFETY & TRAFFIC OPERATIONAL IMPROVEMENTS

ON ROUTE 4 (FARMINGTON AVE) FROM

GARDEN ST. TO MOUNTAIN SPRING RD.

FARMINGTON

ILL-05

51-260

WATERTIGHT CAP (TYP.)

QUANTITY AS REQUIRED

SCREW CONNECTOR PORT (TYP.)

CONNECTOR BAR

INTERNAL 6061-T6 ALUMINUM

CONDUCTOR (TYP.)

NO. 4 AWG LIGHTING CIRCUIT

QUANTITY AS REQUIRED

WITH WATERTIGHT FIT TO CABLE.

CABLE CONNECTION PORT (TYP.)

WATERTIGHT, 600 VOLT, 90 C, U.L. LISTED

INSULATED ALUMINUM BAR CONNECTOR

CHEMICAL RESISTANT

INSULATION, ABRASION AND

MOLDED EDPM RUBBER

HIGH STRENGTH DIELECTRIC

SCREW CONNECTOR (TYP.)

INTERNAL "BALL BOTTOM" HEX HEAD

INSULATING BOOT

LINE SIDE

SET SCREW TERMINAL

TO NEUTRAL

BRASS SLUG WHEN CONNECTED

PROVIDE WHITE NUT AND SOLID

CRIMP TYPE CONNECTION

LOAD SIDE INSULATING BOOT

NO. 10 TO BALLAST

FUSE CONNECTOR

BLACK

120v

GND.

WHITE

LEG (TYP.)

BRASS SLUG ON NEUTRAL

FUSE CONNECTOR WITH

TO BE USED IN HANDHOLES

WATERTIGHT CONNECTOR

1 PHASE 2 WIRE SYSTEM

ELECTRICAL DETAILS 3

CONDUCTORSCIRCUITB

NO. 4 AWG LIGHTING

GROUND

NO. 8 BARE CU.

CONDUCTORS

NO. 4 AWG BRANCH CIRCUIT

TO LUMINAIRE DRIVER

NO. 10 AWG CONDUCTORS

BACKFILL

SUITABLE

SAND

WARNING TAPE

GRADE LINEGRADE LINE

BURIED CONDUIT

PLANS

TO BE SHOWN ON

CONDUIT, QUANTITY

IN LUMINAIRE (TYPICAL)

POLE BASE TO GROUND LUG

FROM GROUNDING SYSTEM IN

INSTALL EQUIPMENT GROUND

OR BRASS SLUG AS REQUIRED

FUSE HOLDER W/10 AMP FUSE

OF LIGHT POLE

AMP FUSE (TYP.) IN BASE

FUSE CONNECTOR W/10

24" MAX.

24"

12" 4"

4"

1"

10.05

* Discipline subset includes the General subset and all other discipline subsets. The 02-Revisions does not need a checklist attached. The standard subsets already have a checklist attached to the index sheets.

– For Internal CTDOT Use Only Discipline Subset Submittal Checklist

The following check list shall be checked and attached to each discipline subset *

prior to being digitally signed.

Check Task Section in DPD

Manual

1. Attach this checklist to the discipline subset. Section 3.1

2. Ensure the plans conform to Section 1.4, step 1 of the Digital Project Development Manual.

Section 1.4

3. Complete the following tasks using Bluebeam on

the discipline subset?

a. Apply Page Labels Section 1.6.2

b. Apply Sheet Numbers Section 1.6.2

c. Apply Watermark Section 2.4

d. Flatten Markups Section 2.4

e. Digital Signature Field Section 2.5.1

4. Type name and telephone number below. 5. Upload, if not in Projectwise already, the

discipline subset into the 100_Contract_Plans folder in Projectwise and attribute the document

correctly?

Section 3.2.4

a. Discipline = CT

b. Main Category = CON

c. Sub Category = FDP, DCD, DCD2,

ADP, ACD, DCO where applicable d. Label = subset number and name.

Example of highways subset would be 03-Highways.

The label for a subset shall be the

same for both FDP and DCD submittals.

Addendum submittals shall match FDP submittals with the addition of “_A#”.

Change Order Submittals shall match FDP submittals with the addition of “_C#”. e. Description field is filled in with

a description of the subset. f. The applicable bridge no.(s) or signal

intersection(s) were selected that is/are associated with this subset.

6. Notify Principal Engineer/Engineer of Record so they can apply their Digital Signature

7. Apply the QA/QC stamp after the discipline subset has been digitally signed.

Section 3.1

I have performed and checked that all the tasks above were performed correctly.

Submitted By (Type in Name) Phone Number (Type in Phone Number)


Recommended