SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATED
QUANTITIES OF WORK, SHOWN ON THESE
SHEETS IS BASED ON LIMITED
INVESTIGATIONS BY THE STATE AND IS
IN NO WAY WARRANTED TO INDICATE
THE CONDITIONS OF ACTUAL QUANTITIES
OF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUT
DEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
C:\Users\HMarshall\Documents\ARCH_CT DOT_Rocky Hill Repair Facility_Central_HMarshall.rvt10/10/2014 1:53:00 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-001
MECHANICAL LIST OF
DRAWINGS
ROCKY HILL
DRAWING NUMBER DRAWING TITLE
MEC-301 MECHANICAL ROOF - PART PLAN A
MEC-302 MECHANICAL ROOF - PART PLAN B
MEC-303 MECHANICAL ROOF - PART PLAN C
MEC-304 MECHANICAL ROOF - PART PLAN D
MEC-305 MECHANICAL ROOF - PART PLAN E
MEC-306 MECHANICAL ROOF - PART PLAN F
MEC-307 MECHANICAL ROOF - PART PLAN G
MEC-500 MECHANICAL CONTROLS I
MEC-501 MECHANICAL CONTROLS II
MEC-502 MECHANICAL CONTROLS III
MEC-503 MECHANICAL CONTROLS IV
MEC-600 MECHANICAL DETAILS I
MEC-601 MECHANICAL DETAILS II
MEC-602 MECHANICAL DETAILS III
MEC-603 MECHANICAL DETAILS IV
MEC-604 MECHANICAL DETAILS V
MEC-605 MECHANICAL DETAILS VI
MEC-700 MECHANICAL SCHEDULES I
MEC-701 MECHANICAL SCHEDULES II
DRAWING NUMBER DRAWING TITLE
MEC-001 MECHANICAL LIST OF DRAWINGS
MEC-002 MECHANICAL LEGEND
MEC-003 MECHANICAL LEGEND II
MEC-100 MECHANICAL ZONE PLAN
MEC-200 OVERALL DUCT PLAN
MEC-201 MECHANICAL - PART PLAN A
MEC-202 MECHANICAL - PART PLAN B
MEC-203 MECHANICAL - PART PLAN C
MEC-204 MECHANICAL - PART PLAN D
MEC-205 MECHANICAL - PART PLAN E & EQUIP. PLATFORM
MEC-206 MECHANICAL - PART PLAN F
MEC-207 MECHANICAL - PART PLAN G
MEC-200P OVERALL PIPE PLAN
MEC-201P MECHANICAL PIPE - PART PLAN A
MEC-202P MECHANICAL PIPE - PART PLAN B
MEC-203P MECHANICAL PIPE - PART PLAN C
MEC-204P MECHANICAL PIPE - PART PLAN D
MEC-205P MECHANICAL PIPE - PART PLAN E & EQUIP. PLATFORM
MEC-206P MECHANICAL PIPE - PART PLAN F
MEC-207P MECHANICAL PIPE - PART PLAN G
10 - MECHANICAL
INDEX OF DRAWINGS
NO. Revision Description Date
NTS10.01
FS
PS
VB
PT
AV
MV
EJ
CO
S
SD
FMT
PIPING ABBREVIATIONS
PIPING LEGEND DUCTWORK DUCTWORK
HWR
HWS
MU
PC
V
D
10"
10x6
W
DIA
R/D
VD VD
DIA"
WxD
R/D
VDVD
VD
PLENUMBY LD MF'R
VD
VDVD
D
DIA
W
10"
10x6
R
W
R
W
VD
VD
10x6
6"
WxD
DIA"
10x6
6"
10x6
6"
VD
VD
VD
AFMS
ACD
SGD
VD
SD
SFD
FD
BDD
SDET
OR
VD
HARDELBOW
HOT WATER RETURNHOT WATER SUPPLY
MAKE-UP WATERPUMPED CONDENSATEVENT
GLOBE VALVE (OUTSIDE SCREW & YOKE UNLESS SPECIFIED OTHERWISE)
BALL VALVE
BUTTERFLY VALVE
HOSE END BALL VALVE WITH CAP AND CHAIN
PLUG VALVE
PRESSURE REDUCING VALVE
ANGLE VALVE (SECTION VIEW)
ANGLE VALVE (PLAN VIEW)
GLOBE ANGLE VALVE
CHECK VALVE (SILENT CHECK TYPE ON PUMP DISCHARGE)
STRAINER WITH HOSE END BLOWOFF VALVE, CAP AND CHAIN
SUCTION DIFFUSER/STRAINER (NON-REDUCING) WITH BLOWOFF
SOLENOID VALVE
2-WAY MODULATING PRESSURE INDEPENDENT ACV
2-WAY AUTOMATIC CONTROL VALVE (MODULATING)
2-WAY AUTOMATIC CONTROL VALVE (TWO POSITION)
3-WAY AUTOMATIC CONTROL VALVE (MODULATING)
3-WAY AUTOMATIC CONTROL VALVE (TWO POSITION)
AUTOMATIC FLOW LIMITING VALVE (PRESSURE INDEPENDENT)
COMBINATION FLOW METER/SHUT-OFF/BALANCING VALVE (CIRCUIT SETTER)
TRIPLE DUTY PUMP VALVE, CHECK, BALANCING (FLOW METER), SHUT-OFF
FLOW METER/TRANSMITTER (HOT TAP TYPE WITH VALVE)
FLOW SWITCH
RELIEF/SAFETY VALVE
UNION
BLIND FLANGE
PIPE - CAPPED
PRESSURE GAUGE (W/ BALL VALVE(S), SNUBBER)
PRESSURE SWITCH
THERMOMETER
VACUUM BREAKER
PRESSURE/THERMOMETER WELL
AIR VENT - AUTOMATIC
AIR VENT - MANUAL
EXPANSION JOINT
FLEXIBLE CONNECTOR
PIPE ANCHOR
PIPE GUIDE
PIPE CONNECTION - TOP
PIPE CONNECTION - BOTTOM
PIPE - DOWN
PIPE - UP
REDUCER - CONCENTRIC
REDUCER - ECCENTRIC
CLEANOUT FOR CONDENSATE DRAIN
DIRT LEG
RISE (DOUBLE LINE - PLAN VIEW)
DROP (DOUBLE LINE - PLAN VIEW)
PIPE BREAK (DOUBLE LINE)
PIPE BREAK (SINGLE LINE)
RETURN DUCT DOWN
RETURN DUCT UP
ROUND RETURN DUCT DOWN
ROUND EXHAUST DUCTDOWN
ROUND RETURN DUCT UP
ROUND SUPPLY DUCT DOWN
DOUBLE LINE
BELLMOUTHCONNECTION
SINGLE LINE
45° TAP TAKE-OFF
45° TAKEOFF
CONVERGE RETURN/EXHAUSTW/45° TAKE-OFFS
SIDEWALL DUCT MOUNTEDREGISTER/GRILLE
90° TAPTAKE-OFF
EXHAUST DUCT DOWN
EXHAUST DUCT UP
ROUND EXHAUST DUCT UP
ROUND RETURN/EXHAUSTDUCT (DIA=INSIDE
DIAMETER)
CHANGE OF ELEVATION(R)RISE OR (D)DROP
SUPPLY/RETURN/EXHAUST
HORIZONTAL OFFSETSUPPLY/RETURN/EXHAUST
RECTANGULAR RETURN/EXHAUST DUCTW=WIDTH, D=DEPTH
(INCHES UNLESS NOTED OTHERWISE)AS VIEWED
45° TAKE-OFFTRANSITION TO ROUND
SQUARE TO ROUNDCONNECTION
BACKDRAFT DAMPER
SLIDE GATE DAMPER
3-WAY BLOW SUPPLY DIFFUSER
STANDARD 4-WAY BLOW SUPPLY DIFFUSER
DUCT MOUNTED SMOKE DETECTOR
MANUAL VOLUME DAMPER
SUPPLY CEILING LINEARDIFFUSER (W/SHEETMETALPLENUM, LINING & BRANCH
CONN. FOR EVERY 4' OFLINEAR.)
SUPPLY AIR FLOW
RETURN OR EXHAUST AIR FLOW
ROOF EXHAUST FAN SHOWN ON FLOORPLAN
ROOF EXHAUST FAN SHOWN ON ROOF
RETURN/EXHAUST GRILLE OR REGISTER
ONE-WAY BLOW SUPPLY DIFFUSER
2-WAY BLOW SUPPLY DIFFUSER
COMBINATION SMOKE/FIRE DAMPER W/ ACCESS DOOR
SELF-CLOSING FIRE DAMPER W/ ACCESS DOOR
OPEN END DUCT W/1/2"x1/2" WMS
SUPPLY SIDEWALL LINEARDIFFUSER (W/ SHEETMETALPLENUM, LINING & BRANCH
CONN. FOR EVERY 4' OFLINEAR.)
DOUBLE LINE
SUPPLY DUCT UP
SPLIT TAKE-OFF
FULL LENGTH SPLITTERVANES
(R < W)SUPPLY/RETURN/ EXHAUST
TAKE-OFF TODIFFUSER/GRILLE
CEILING DUCT MOUNTEDDIFFUSER/GRILLE
RECTANGULAR WYE SUPPLY
SINGLE LINE
ROUND SUPPLY DUCT UP
RECTANGULAR DUCT TOROUND SUPPLY/RETURN/
EXHAUST
STANDARD RADIUS ELBOW(R = W)
SUPPLY/RETURN/EXHAUST
SUPPLY DUCT DOWN
ROUND SUPPLY DUCT(DIA=INSIDE DIAMETER)
RECTANGULAR SUPPLY DUCTW=WIDTH, D=DEPTH
(INCHES UNLESS NOTEDOTHERWISE) AS VIEWED
FLEXIBLE DUCT
ACOUSTICALLY LINEDDUCT
CEILING DUCT MOUNTEDDIFFUSER/GRILLE
AUTOMATIC SMOKE DAMPER W/ ACCESS DOOR
AIR FLOW MONITORING STATION
AUTOMATIC CONTROL DAMPER W/ ACCESS DOOR
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:29:22 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-002
MECHANICAL LEGEND
ROCKY HILL
NO. Revision Description Date 10.02
H
C
C
HR
C
C
AV
VFD
T
H
DIAGRAM EQUIPMENT SYMBOLS CONTROL POINT DESCRIPTOR LEGENDCONTROL ABBREVIATIONSCALLOUT SYMBOLS
S/S ALM
VFDS
VFDSO
S/S
CTSTARTER
TAG
ELECPLBG
TAG
TAG
TAG
(XXX, XXX, XXX)
(XXX, XXX, XXX)
TAG
3.1
1
B = BASEMENT 1 = FIRST FLOOR M = MEZZANINE R = ROOFSECOND DIGIT(S): 1 = FIRST UNIT OF THIS EQUIPMENT TYPE ON THIS LEVEL. 2 = SECOND UNIT OF THIS EQUIPMENT TYPE ON THIS LEVEL. 3 = THIRD UNIT OF THIS EQUIPMENT TYPE ON THIS LEVEL, ETC. (DUE TO EDITING NOT ALL NUMBERS MAY BE USED)
3-WAY AUTOMATIC CONTROLVALVE (TWO POSITION)
3-WAY AUTOMATIC CONTROLVALVE (MODULATING)
2-WAY AUTOMATIC CONTROLVALVE (TWO POSITION)
2-WAY AUTOMATIC CONTROLVALVE (MODULATING)
VARIABLEFREQUENCY DRIVE
STARTER
FILTER BANK
HEATING COIL
HEAT RECOVERY COIL
COOLING COIL
CABINET HEATER
UNIT HEATER
AIR SEPARATOR
BOILER
EXPANSION TANKCHEMICAL FEED SYSTEM
AIR TERMINAL BOX
AIR VALVE
FINNED TUBE RADIATION
BACKDRAFT DAMPER
PARALLEL BLADE DAMPER W/MODULATING ACTUATOR
PARALLEL BLADE DAMPER W/TWO POSITION ACTUATOR
OPPOSED BLADE DAMPERW/ MODULATING ACTUATOR
OPPOSED BLADE DAMPERW/ TWO POSITIONACTUATOR
ROOF FAN
PROPELLER FAN
CENTRIFUGAL FANWITH INLET GUIDEVANES
CENTRIFUGAL FAN
PUMP
ATC CONTRACTOR PROVIDEDLOCAL CONTROL POINT
LH
ATC CONTRACTOR PROVIDEDDDC POINT AND HARDWARE
CONTROL DEVICE FURNISHED BYELECTRICAL OR PLUMBING CONTRACTORBUT INTERFACED TO DDC SYSTEM BYATC CONTRACTOR
ATC CONTRACTOR INTERFACE TOEQUIPMENT MANUFACTURER'S HARDWARE
AUTOMATIC CONTROL DAMPERAUTOMATIC CONTROL VALVEAIR FLOW MEASURING STATIONALARMAUTOMATIC TEMPERATURE CONTROL
BASEBOARD CONTROL VALVEBACKDRAFT DAMPER (ADJUSTABLE COUNTERWEIGHT)BYPASS VALVECARBON DIOXIDE SENSORCAPACITY CONTROL
CARBON MONOXIDE SENSORCURRENT TRANSFORMER (STATUS FEEDBACK)COOLING COIL CONTROL VALVE
DISCHARGE AIR TEMPERATURE SENSORDIRECT DIGITAL CONTROLDIRECT DIGITAL CONTROL FIELD PANEL
DIFFERENTIAL PRESSURE SWITCHDIFFERENTIAL PRESSURE SENSOR/TRANSMITTERDIFFERENTIAL PRESSURE BYPASS VALVEDISCHARGE STATIC PRESSURE SENSORDOUBLE WIDTH DOUBLE INLETEXHAUST AIR DAMPER
EXHAUST HEAT RECOVERY COIL ENTERING AIR TEMPERATURE SENSOREXHAUST HEAT RECOVERY COIL LEAVING AIR TEMPERATURE SENSOREXHAUST HEAT RECOVERY COIL CONTROL VALVEEND SWITCH
FAULT ALARMFAN ISOLATION DAMPERFLOW METER/TRANSMITTERFLOW SWITCHFREEZESTAT
HEATING COIL LEAVING AIR TEMPERATURE SENSORHOT GAS BYPASSHIGH HUMIDITY LIMIT SENSORHIGH/LOW HUMIDITY LIMIT SENSORHANDS-OFF AUTOMATIC SWITCHHEAT RECOVERY COIL ENTERING AIR TEMPERATURE SENSORHEAT RECOVERY COIL LEAVING AIR TEMPERATURE SENSORHEAT RECOVERY LOOP TEMPERATURE SENSORHEAT RECOVERY COIL CONTROL VALVEHEAT RECOVERY LOOP CONTROL VALVEHAND SWITCHHIGH STATIC PRESSURE SWITCH
HEATING COIL CONTROL VALVEHOT WATER RETURN TEMPERATURE SENSORHOT WATER SUPPLY TEMPERATURE SENSORINTEGRAL FACE & BYPASS DAMPERINLET GUIDE VANES
LEAVING AIR TEMPERATURE SENSORLOW STATIC PRESSURE SWITCHLEVEL SENSOR OR LIGHT SWITCH INTERFACELEVEL SENSOR HIGH ALARMLEVEL SENSOR HIGH SWITCHLEVEL SENSOR LOW ALARMLEVEL SENSOR LOW SWITCH
MIXED AIR TEMPERATURE SENSORMAIN EXHAUST DAMPER
NORMALLY CLOSED (ON LOSS OF POWER)NORMALLY OPEN (ON LOSS OF POWER)
OUTSIDE AIR DAMPEROUTSIDE AIR HUMIDITY SENSOR (FOR WET BULB READING)OUTSIDE AIR TEMPERATURE SENSOR (DRY BULB)
PRIMARY AIR DAMPERPRESSURE SENSOR (ROOM)
RETURN AIR DAMPERRETURN AIR HUMIDITY SENSORRETURN AIR TEMPERATURE SENSORREHEAT CONTROL VALVERELATIVE HUMIDITYRUN INDICATORSWITCHSUPPLY AIR DAMPERSMOKE DAMPERSMOKE DETECTORSMOKE/FIRE DETECTORSTATIC PRESSURE SENSORSPEED CONTROLSTART/STOPSTART/STOP HIGH SPEED/CAPACITYSTART/STOP LOW SPEED/CAPACITYSUPPLY SMOKE ISOLATION DAMPERSUCTION STATIC PRESSURE SENSOR
TEMPERATURE SENSOR/THERMOSTATTEMPERATURE SENSOR/THERMOSTAT (ROOM)
VARIABLE FREQUENCY DRIVE SPEEDVARIABLE FREQUENCY DRIVE SPEED OUTPUT (FEEDBACK)VOLUME DAMPER
WATER COLUMNWC
VDVFDOVFDS
TRT
SSPSSIDS/SS/SS/SSPDSPSFDSDETSDSADSRIRHRVRATRAHRAD
PRPAD
OATOAHOAD
NONC
MEDMAT
LSLSLSLALSHSLSHALSLSPSLAT
IGVIFBDHWSTHWRTHV
HSPSHSHRVHRCVHRTHRLTHRETHOAHLHHHLHGBHCLT
FZFSFMTFIDFA
ESEHRVEHRLTEHRET
EADDWDI
DATDDCDDCFP
DPSDPTDPVDSP
CVCTCO
CAPCBVBDDBCV
ATCALMAFMSACVACD
DEMAND LIMITDL
UNIT CAPACITY INFORMATION (IF APPLICABLE-DATA VARIESDEPENDING ON TYPE OF EQUIPMENT) i.e. FOR FAN POWERED VAV BOXES: FIRST NUMBER = MAX. CFM SECOND NUMBER = MIN. CFM OR PERCENT OF MAX. CFM THIRD NUMBER = COIL GPM OR KW
EQUIPMENT REQUIRING ELECTRICAL SERVICE,SEE SCHEDULE FOR PERFORMANCE REQUIREMENTS:
REFER TO EQUIPMENT REQUIRING ELECTRICALSERVICE SYMBOL ABOVE FOR TAG AND DATAINFORMATION.
SECTION DESIGNATIONSHEET NUMBER
REVISION NUMBER
TEMPERATURE SENSOR OR THERMOSTAT
HUMIDITY SENSOR OR HUMIDISTAT
SA(100)
RA(100)
EA(100)
TA(100)
SCHEDULED EQUIPMENT UNIT NUMBER
EQUIPMENT NOT REQUIRING ELECTRICAL SERVICE,SEE SCHEDULE FOR PERFORMANCE REQUIREMENTS:
T = TRANSFER A = SCHEDULED REGISTER/GRILLE (100) = CFM TO BALANCED TO
E = EXHAUST A = SCHEDULED REGISTER/GRILLE (100) = CFM TO BALANCED TO
R = RETURN A = SCHEDULED GRILLE. (100) = CFM TO BALANCED TO
S = SUPPLY A = SCHEDULED DIFFUSER. (100) = CFM TO BALANCE TO
FIRST DIGIT(S) = LEVEL WHERE UNIT IS LOCATED:
EXHAUST CONTROL DAMPERECD
GENERAL EXHAUST DAMPERGED
MAKE-UP WATER VALVEMUWV
OPPOSING BLADE DAMPEROBD
VEHICLE EXHAUST DAMPERVES
VIBRATION SWITCHVS
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:29:23 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-003
MECHANICAL LEGEND II
ROCKY HILL
NO. Revision Description Date 10.03
DDEC
A B
E FF G
GF
C
A
BF
1 2 3 4 5 6 6.1 7 7.1 8 9 10 10.7 11 12 13 14 14.4 15 15.2 16 17 17.7 18 18.9 19 20 21
K
J
I.5
I
H
G
F
E.4
E.2
E
D.6
D.1
D
C.1
C
B.1
B
A
REPAIR BAYS28
LUBE BAYS25
LUBRICANTSTORAGE /
COMPRESSOR24
WASH BAY23
STORESSTOCKROOM
22
STORES MATERIALMANAGEMENT
20
STORES STOCKROOM
SUPERVISOR21
SERVICEVESTIBULE
19
MACHINE SHOP31
AERIAL BUCKETBAYS32
WELD /FABRICATION
SHOP33
PAINT BOOTHS36
PARTS WASHER34
PAINT EQUIPMENTROOM
35
WELD SHOP30
EQUIPMENTINSPECTION / CNG
INSPECTION26
BREAK ROOM07
CONFERENCEROOM
05
MACHINE SHOPCREW LEADER &CLERK OFFICE
04
MACHINE SHOPSUPERVISIOR
03VEST01
HALL02 JAN
06
MENS ROOM12
WOMENS ROOM13
REPAIR CREWLEADER &
SUPERVISOROFFICE
16
GARAGESUPERVISOR
15
EQUIPMENTGENERAL
SUPERVISOR14
EQUIPMENTINSPECTION AND
IN SERVICEOFFICE
17
MEDIA STORAGEROOM
18
VEST11
MECHANICALROOM
10
ELECTRICAL ROOM09
COMM08
PAINT REMOVALBOOTH
37
PAINT SPRAYBOOTH
38
PAINT MIX ROOM39
TOOL CRIB WITHSTORES
29
TOOL CRIB27
EMERG. ELEC09.1
SPRINKLER ROOM40
R
ERU-4
RTU-1ERU-3ERU-3
ERU-2ERU-1
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
3/64" = 1'-0"10/21/2014 3:29:27 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-100
MECHANICAL ZONE PLAN
ROCKY HILL
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
SCALE: 3/64" = 1'-0"1 MECHANICAL ZONE PLAN
NO. Revision Description Date
NOTE:
1) ALL ELECTRICAL IN ROOM 26 & 27 SHALL BE IN COMPLIANCEWITH NFPA 52. ALL ELECTRICAL SHALL BE NFPA CLASS I DIV. 2GROUP D.
10.04
VDVD
VD
VD
VD
VD
VD
VD
VDVD
VD
VD
VD
VD
VDVD
VD
VD
VD VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
BD
D
BDD BDDAFM
SAFMS
AFMSAFMS
AFM
S
AFMS AFM
S
AFM
S
AFMS
AFM
S
AFM
S
AFMS
AFMS
AFMS
AFMS
BD
D
BDD
FD
BDDBDD
BD
D
BDD BD
D
BDD BD
D
BDD BD
D
BDD BD
D
BDD
AFMS
T
T
T
TT T
T
T
T
T
T
TT
T
T
FD
FD
FD FD
FDFD FD
FDFDFD
FD
FDFD
FD
1 3 4 5 6 7 7.2 8 9 10 10.7 11 12 13 14 14.6 15 15.4 16 17 18 18.8 19.1 19.5 21
K
J
I.5
I
G.9
GF
E.4
E
D.9
D.6
D
C
B
A
J.9
19 20
H
14.5
G.1
11.7
11.9
58"x28"
74"x28"
40"x28"
28"x16"
40"x
20"
24"x
20"
14"x
20"
14"x
20"
24"x
20"
40"x
20"
28"x16"
12"x
12"
16"x
16"
20"x
16"
28"x
16"
10"x
16"
24"x
24"
16"x
16"
10"x
6"
24"x
24"
24"x24"
12"x
12"
16"ø
14"x
30"
14"x
30"
20"x28"16"x
30"
30"x
20"
30"x20"
16"x
30"
14"x14"
16"x
30"
ø6"
14"x14"
30"x20"
30"x20"
30"x
20"
28"x28" 58"x28"
74"x28"
30"x16"
30"x16"
30"x
16"16
"x14
"
30"x16"
70"x22"
74"x
28"
74"x
28"
12"ø
74"x
28"
74"x
28"
ø6"
ø6"
16"ø
ECD
ACDGED
MED
VED
SAD
18"x
18"SAD
MEDMEDSAD
ECD
ACDGED
SAD
ACDø6"
ECDACD
MED
MED
SAD
SAD
16"x
16"
14"x14"
24"x
16"
14"ø
10"ø
12"x
8"12"ø
14"ø
GED
ACD
ECD
SAD
ACD
GED
GED BELOW GED BELOWGED BELOW GED BELOW
60"x28" 46"x28"
HOSEREEL
HOSEREEL
HOSEREEL
HOSEREEL
HOSEREEL
HOSEREEL
28"x
28"
28"x28"
28"x28"
46"x28"
30"x28"16"x28"
30"x28"
16"x28"
60"x28"
8"ø
16"ø
8"ø16"x14"
16"x
14"
ACD
ECD
VES1
28"x
28"
18"x
14"
18"x
14"
16"x
14"
30"x
16" 18
"x18
"
HOSEREEL
8"ø 8"ø
HOSEREEL
12"x12"
20"x28"
20"x
28"
16"x16"
SADSAD
17.914.7 18.6
13.6
18.1 20.814.1 20.9
H.4
E.9
D.8
B.8
H.1
EHF1
EHF2
EHF3
VES10
EHF4
VES9
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
3/64" = 1'-0"10/21/2014 3:29:35 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-200
OVERALL DUCT PLAN
ROCKY HILL
SCALE: 3/64" = 1'-0"1 HVAC - 00 DUCT OVERALL
NO. Revision Description Date
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
10.05
VD
BDD
AFMS
AFMS
AFMS
AFMS
BD
D
BDD
FD
BDD
BD
D
BDD
BD
D
BDD
BD
D
T
FDFD
FD FD
FDFD
FD
FDFD
4 5 6 7 7.2 8 9 10 10.7 11 12 13
K
J
I.5
I
G.9
G
F
J.9
H
G.1
30"x16"
74"x28"
30"x
20"
30"x16" VAV6
(2 GPM)
REPAIR BAYS28
EQUIPMENTINSPECTION /
CNGINSPECTION
26
TOOL CRIB27
SERVICEVESTIBULE
19
11.7 11.9
6"ø
12"x8"SA(150)
ø8"
12"x8"
SB(275)
VAV6
PART
PLAN
B
PART
PLAN
A
PART PLAN C
PART PLAN A
SG(1580) SG(1580) SG(1580) SG(1580) SG(1580)
24"x
22"
SG(1580) SG(1580)
24"x
22"
24"x
22"
24"x
22"
24"x
22"
24"x
22"
24"x
22"
50"x24" EXHAUST DROP WITHGED AND WMS (5600 CFM)
50"x24" EXHAUST DROP WITHGED AND WMS (5600 CFM)
16"ø
8"ø 16"x
14"
30"x20"
SADSAD
SAD
MED MED
28"x28"
MED
OBD OBD OBD OBD OBD OBD OBD
OBD OBDOBD
OBD
60"x28"46"x28"
28"x28"
28"x28"
74"x
28"
16"x28" 30"x28"58"x28"
8"ø
DUCT ABOVE CRANE RAIL
DUCT BELOW CRANE RAIL
VED
SAD
SAD
MED
HOSEREEL
HOSEREEL
16"x14"
16"x
14"
VES1
8"ø 8"ø
16"øACD
ECD
24x24 SUPPLY DUCT, DOWN TOFLOOR LEVEL SUPPLY. OBD IN24X24 DROP FOR BALANCING.
28"x
28"
28"x
28"
28"x28"
SK(3350)SK(3350)
28"x28"
EK(3350) EK(3350)
OBDOBD
18"x
18"
18"x
18"
18"x
14"
18"x
14"
24"X24" FUSIBLE LINKFIRE DAMPER & TRANSFERDUCT W/WMS 10'-0" AFF
LV7
H.4
E.9
H.1
REFER TO ARCH 801 FORHOSE REEL MOUNTINGDETAIL. (TYP 8.) SEEMECHANICAL DETAILVES01 AND SEQUENCE ONMEC-502.
DS
DOOR SENSOR WIRE TOBMS. SEE DETAIL H-1557 ON MEC-605 (TYP.)
DS
DS
DOOR SENSORWIRE TO BMS.
ECD
16"ø
ACD
16"x14"
HOSEREEL
HOSEREEL
16"x14"
16"x
14"
VES2
8"ø 8"ø
16"øACD
ECD
LV7
HOSEREEL
HOSEREEL
16"x14"
16"x
14"
VES3
8"ø 8"ø
16"øACD
ECD
LV7
16"x14"
16"x
14"
VES4
ACD
ECD
LV7
16"x
14"
8"ø 8"ø
HOSE REEL
16"x14"
16"x
14"
48"x
24"
48"x
24"
24"x
48"
24"x
48"
16"x14" 16"x14" 16"x14" 16"x14"
16"x14" EXHAUSTUP GOOSENECKABOVE ROOF WITHBIRD SCREEN
VES7
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:30:32 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-201
MECHANICAL - PART PLAN A
ROCKY HILL
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
SCALE: 1/8" = 1'-0"1 HVAC - DUCTWORK - PART PLAN A - NORTH REPAIR BAYS
NO. Revision Description Date 10.06
BDD
AFM
S
AFMS
AFMS
AFMS
AFM
S
AFM
S
BDD
BDD
BD
D
BDD
BD
D
BDD
AFMS
13 14 14.6 15 15.4 16 17 18 18.8 19.1 19.5 21
K
J
I.5
I
G.9
G
F
J.9
19 20
H
14.5
G.1
16"x
30"
SH(750)
SH(750)
SH(750)
SH(750)
SH(750)
30"x
20"
74"x28"
58"x28"
16"x14"
16"ø
WELD SHOP30
TOOL CRIBWITH NO
CHARGE AREA29
OXYGEN /ACETYLENE
STORAGE CRIB30.2
REPAIR BAYS28
OXYGEN /ACETYLENE
STORAGE CRIB30.1P
ART
PLAN
B
PART
PLAN
A
PART PLAN F
PART PLAN B
SG(1580) SG(1580) SG(1580) SG(1580) SG(1580) SG(1580) SG(1580)
EHF1
WEA1
16"x
30"
20"x28" 20"x28"
EH(250)
EH(250)
EH(250)
5'-0" x 3'-0" WELDINGTABLE HOOD WITH 14" X14" NECK (1500 CFM)
14"x14"
5'-0" x 3'-0" WELDINGTABLE HOOD WITH 14" X14" NECK (1500 CFM)
14"x14"
20"x28"
14"x
30"
50"x24" EXHAUST DROPWITH GED AND WMS(5600 CFM)
50"x24" EXHAUST DROP WITHGED AND WMS (5600 CFM)
30"x20"
12"x12" EXHAUSTUP GOOSENECKABOVE ROOF WITHBIRD SCREEN
8"ø 8"ø
ø6"
16"x
30"
ACD ECD
MED
MED
ECD
ACD
GED
VED SAD
SAD
SAD
12"x12" EXHAUST UPGOOSENECK ABOVE ROOFWITH BIRD SCREEN
ECD
12"x
12"
ACD
MED
OBD OBD OBD OBD OBD OBD OBD
OBD
OBD
OBD
OBD
OBD
OBD
OBD
OBD
OBD
OBDDUCT ABOVE CRANE RAIL
DUCT BELOW CRANE RAIL
REFER TO ARCH 801 FOR HOSEREEL MOUNTING DETAIL. (TYP.OF 8) SEE MECHANICAL DETAILVES01 AND SEQUENCE ON MEC-502.
46"x28"60"x28"
46"x28"
17.914.7 18.6
13.6
18.1 20.814.1 20.9
H.4
E.9
H.1
REFER TO ARCH 801FOR EXHAUST ARMMOUNTING DETAIL.
DOOR SENSOR WIRE TOBMS. SEE DETAIL H-1557ON MEC-605 (TYP.)
DS
DOOR SENSORWIRE TO BMS.DS
HOSE REEL
VES8
16"ø8"ø
ECDACD
8"ø
16"x14"
16"x14"
16"x30"
16"x14"
HOSEREEL
HOSEREEL
16"x14"
16"x
14"
VES4
8"ø 8"ø
16"ø
HOSEREEL
HOSEREEL
16"x14"
16"x
14"
VES5
8"ø 8"ø
16"øACD
ECD
LV7
16"x
14"
HOSEREEL
HOSEREEL
16"x14"
16"x
14"
VES6
8"ø 8"ø
16"øACD
ECD
LV7
16"x
14"
30"x14"
12"x
12"
12"x12"
REFER TO ARCH 801 FOR HOSE REELMOUNTING DETAIL. SEE MECHANICALDETAIL VES01 AND SEQUENCE ON MEC-502.
DUCT BELOW CRANE RAIL
DUCT BELOW CRANE RAIL
24"x
22"
24"x
22"
24"x
22"
24"x
22"
24"x
22"
24"x
22"
24"x
22"
18"x18"
18"x18"
18"x18"
16"x14" 16"x14"
16"x14" EXHAUSTUP GOOSENECKABOVE ROOF WITHBIRD SCREEN
20"x28"
30"x28"16"x28"
18"x18"
18"x18"
18"x18"
18"x18"
18"x18"
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:30:47 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-202
MECHANICAL - PART PLAN B
ROCKY HILL
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
SCALE: 1/8" = 1'-0"1 HVAC - DUCTWORK - PART PLAN B - SOUTH REPAIR BAYS
NO. Revision Description Date 10.07
BD
D
BDD
AFM
S
AFMS
FD
FD
FD FD
FDFD
FD
1 3 4 5 6
G
F
E.4
D.9
D.6
G.1
30"x16"
30"x
16"
LUBE BAYS25
LUBRICANTSTORAGE /
COMPRESSOR24 WASH BAY
23
CLCL
CL
PART PLAN C
PART PLAN A
PART PLAN D
PART PLAN C
HOSEREEL
30"x
16"
30"x
16"
30"x16"
16"x
14"
16"ø
8"ø 16"x
14"
18"x14"
18"x14"
18"x14"
SI(970)
SI(970)
SI(970)
EI(970)
EI(970)
EI(970)
18"x14"
18"x14"
18"x14"
ECD
ACD
SAD
SAD
MEDMED
OBD
OBD
OBD
GED
OBD
OBD
OBD
OBD OBD
LV7
8"øHOSEREEL 18
"x14
"
18"x
14"
SI(900)
EI(900)E.9
D.8
REFER TO ARCH 801 FORHOSE REEL MOUNTINGDETAIL. SEE MECHANICALDETAIL VES01 ANDSEQUENCE ON MEC-502.
DS
DOOR SENSOR WIRE TOBMS. SEE DETAIL H-1557ON MEC-605 (TYP.)
DS
DOOR SENSORWIRE TO BMS.
DOOR SENSORWIRE TO BMS.
DS
DS
VES10
ECD
16"x14"
DUCT BELOW CRANE RAIL
DUCT ABOVE CRANE RAIL
16"x14"
16"x
14"
16"x14"
FLOORLEVELEXHAUST
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:30:53 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-203
MECHANICAL - PART PLAN C
ROCKY HILL
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
SCALE: 1/8" = 1'-0"1 HVAC - DUCTWORK - PART PLAN C - LUBE & WASH BAYS
NO. Revision Description Date 10.08
VD
VD
VD
AFMS
BDD
T
T
T
FD
FD
FD
FD
FD
FD
14"x12"
14"x
12"
14"x
10"
8"ø12"x10"
12"x8" 6"ø
8"ø
6 7 7.2 8 9 10 10.7 11 12
G
F
E.4
E
D.9
D.6
D
G.1
30"x16"
VAV8
VAV6
STORESSTOCKROOM
22STORES
MATERIALMANAGEMENT
20
SERVICEVESTIBULE
19
STORESSTOCK ROOMSUPERVISOR
21
COMM ROOM08
VEST11
11.7 11.9
SF(500) ø15"
12"x8"
SA(150)
ø8"
SA(150)
ø8"
12"x12"
6"ø
12"x8"SA(150)
ø8"
ø8"
SA(165)
12"x
12"
VAV6
PART
PLAN
D
PART
PLAN
C
PART PLAN E
PART PLAN D
AC2
SH(400)EH(400)
SAD
MED
?
OBDOBD
ATCPANEL
18"x
18"
18"x
18"
E.9
D.8
DOOR SENSOR WIRE TOBMS. SEE DETAIL H-1557ON MEC-605 (TYP.)
DS
ECD
16"ø16"x14" 8"ø 8"ø16"x
14"
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:30:57 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-204
MECHANICAL - PART PLAN D
ROCKY HILL
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
SCALE: 1/8" = 1'-0"1 HVAC - DUCTWORK - PART PLAN D - STORES
NO. Revision Description Date 10.09
F
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
T
T
T
T
T
T
T
T
T
T
T
TT
T
T
FD
FD
FDFD
FD
AFMS
AFM
S
10.7 11 12 13 14 14.6
G
F
E.4
E
D.9
D.6
D
C
B
14.5
G.1
14"x12"14
"x12
"14
"x10
"
6"ø
12"x10"
12"x8"
6"ø
8"ø
12"x10"
24"x12"
24"x
12"
16"x
12"
14"x
12"
8"ø12"x10"
10"ø14"x12"
8"ø
10"ø
12"x10"
14"x12"
16"x
14"
24"x
16"
16"x
15"
VAV12
VAV8
VAV6
VAV12
VAV8
VAV6
SB(225)SD(360)
SD(355)
SB(250)
SB(250)
SD(350)
SC(250)
SC(250)SA(175)
12"x
8"
8"x8"
12"x10"
SA(150)
SA(165)
SA(150)
SA(150)
VAV8
VAV10
VAV12
6"ø
VAV8
VAV10
SB(275)
SB(285)SB(285)
BREAK ROOM07
CONFERENCEROOM
05
MACHINESHOP CREWLEADER &
CLERK OFFICE04
MACHINESHOP
SUPERVISIOR03
VEST01
JANITOR06
MENS ROOM12
REPAIR CREWLEADER &
SUPERVISOROFFICE
16
GARAGESUPERVISOR
15
EQUIPMENTGENERAL
SUPERVISOR14
MECHANICALROOM
10
FIRE PUMPROOM
40
MEDIASTORAGE
ROOM18
STORESMATERIAL
MANAGEMENT20
SERVICEVESTIBULE
19
STORESSTOCK ROOMSUPERVISOR
21 LOCKER/SHOWER13A
HALL02
ELECTRICALROOM
09
COMM ROOM08
WOMENSROOM
13
VEST11
EQUIPMENTINSPECTION
ANDIN-SERVICE
OFFICE17
11.7 11.9
PART
PLA
NF
PART
PLAN
E
PART PLAN E
PART PLAN D
(BELOW)
ø15"
18"x16"
SB(275)
SB(275)
18"x
16"
12"x
12"
ø12"
ø10"
12"x8"
6"ø
VAV6
12"x8"
SA(150)
ø8"8"ø
12"x12"
RG(285)
12"x12"
RG(315)
14"ø
SF(500)
ø15"
ø14"
12"ø
16"x15"
SD(350)
12"ø
ø14"
12"ø24
"x24
"
12"x
12"
ø12"
6"ø
10"ø
ø12"
ø12"
10"ø14"ø
14"ø
6"øSE(500)
ø15"
ø20"
12"x12"14"x
12"
RG(285)
70"x22"
24"x
12"
SA(175)
14"x
12"
14"ø
VAV12
ø10"
ø10"
ø10"
12"x
12"
VAV8
ø14"
ø8"
ø8"
ø12"
ø12"
8"ø
12"x
12"
SE(500)
12"ø10"ø
14"x12"
ø10"ø8"12"ø
6"ø
SB(285)
ø12"
ø8"
ø15"14"x14"
12"ø
16"x
15"
50"x
24"
20"x76"ø20"
ø20"
SA(150)
RG(315)RG(150)
RG(275)
RG(275)
RG(900)
RG(285)
RG(285)
RG(285)
RG(285)12"x12"
RG(715)
RG(715)
RG(225)
RG(225)
RG(910)RG(910)
RG(910)RG(910)RG(910)
RG(910)
EG(200)
ø6"
6"ø
EG(200)EG(150)
EG(200)
EG(200)
EG(200)
EG(450)
12" FLUE VENT THRUROOF. PROVIDE STACKCAP AND DRAIN TEE.
AC2
AC1
DIRECTCOMBUSTION AIRFROM ROOF.PROVIDEGOOSENECK ANDDRAIN TEE.
BAS CONTROLS PANEL
24"X24" UPTO TE-1
UP TO RTU-1
VAV6
(2 GPM)
ALUMINUMDUCT
HC1
14.7
13.6
14.1
E.9
D.8
B.8
RG(150)
RG(900)
20"x16"
20"x
16"
20"x
16"
20"ø
20"ø
20"x16"ø18"
10"ø16"x15"
12 13 14 14.6
G
F
E.4
E
D.9
D.6
D
14.5
G.1
30"x
16"
RTU1
0 kW)(0, 0,
ERU4
0 kW)(0, 0,
ERU3
0 kW)(0, 0,
ERU1&2
0 kW)(0, 0,
ERU1&2
0 kW)(0, 0,
30"x
16"
EQUIPMENTPLATFORM
41
153' - 9"
11.7 11.9
PART
PLA
NF
PART
PLAN
D
74"x
28"
74"x
28"
40"x
28"
74"x
28"
120"X34" PLENUM BUILTAROUND TRUSS JOISTS INMECH. PLATFORM ROOF.
58”X58” DUCTFROM 120” X 34”PLENUM UP TO EF-1A,B,C,D (TYP. 4)
CONNECT ERU TO 120”X 34 EXHAUST PLENUM.(TYP. 4)
74"x
28"
74"x
28"
40"x
28"
LV9
LV9
LV9
LV9
LV9
LV9 LV
8
14.7
13.6
14.1
E.9
D.8
SG(0) SG(0)
22x24 TRANSFERDUCT W/WMS12" A.F.F
22x24 TRANSFERDUCT W/WMS 84"A.F.F.
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:31:09 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-205MECHANICAL - PART PLAN E
& EQUIP. PLATFORM
ROCKY HILL
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
SCALE: 1/8" = 1'-0"1 HVAC - DUCTWORK - PART PLAN E - OFFICE AREA
SCALE: 1/8" = 1'-0"2 HVAC - DUCTWORK - EQUIPMENT PLATFORM
NO. Revision Description Date 10.10
VD
VD
VD
VD
BDD
AFM
S
AFMS
AFMS
AFMS
AFM
S
AFM
S
BDD
T
FD
FD
24"x
12"
16"x
12"
14"x
12"
8"ø
8"ø
14.6 15 15.4 16 17 18 18.8 19.1 19.5 21
G
F
E.4
E
D.9
D.6
D
C
B
19 2014.5 G.1
14"x
30"
28"x16"
VES9
EH(660)
SH(660)
74"x28"
16"x14"
16"ø
SB(225)
EHF4
28"x
16"
MACHINESHOP
31
AERIALBUCKET BAYS
32
PAINT BAYS36
PARTSWASHER
34
PAINTREMOVALBOOTH
37
PAINT MIXROOM
39
OXYGEN/ACETYLENESTORAGE CRIB
33.1
OXYGEN /ACETYLENE
STORAGE CRIB33.2
WELD /FABRICATION
SHOP33
12"x
12"
ø12"
SB(250)
SE(500)
PART PLAN G
PART PLAN F
PART PLAN G
PART PLAN F
PART PLAN F
PART PLAN B
PART
PLA
NF
PART
PLAN
E
EHF2
1
EHF3
WEA1
LV4
HOSEREEL
HOSEREEL
WEA1
WEA
WEA1
16"x16"
16"x
16"
SH(660)
SH(660)
SH(660)
EH(660)
EH(660)
EH(660)
5'-0" x 3'-0" WELDING TABLEHOOD WITH 14" X 14" NECK(1500 CFM)
40"x
20"
18"x18"
SH(980)
SH(980)18"x18"
18"x18"
SH(980)
SH(980)
18"x18"
14"x
20"
18"x18"
SH(980)
24"x
20"
20"x28"
40"x
20"
24"x
20"
14"x
20"
EH(980)
EH(980)
EH(980)
EH(980)
EH(980)
40"x28"40"x28"
40"x28"
16"x
16"
20"x
28"
28"x16"
14"x
30"
14"x
30"
14"x14"
SI(950)
SI(950)
SI(950)
18"x14"
18"x14"
18"x14"
20"x
16"
10"x
16"
28"x
16"
EH(675)
EH(675)
18"x18"
18"x18"
12"x12" EXHAUST UPGOOSENECK ABOVE ROOFWITH BIRD SCREEN
16"x14" EXHAUST UP GOOSENECKABOVE ROOF WITH BIRD SCREEN
8"ø 8"ø
12"x
12"
ø6"
ø6"
ACD
ACD ECD
12"x
12"
ECD
GED
GEDMED
MED
MED
SAD
GED
SAD
12"x12" EXHAUST UPGOOSENECK ABOVE ROOFWITH BIRD SCREEN
ECD
12"x
12"
ACD
SE(500)
SE(500)
10"x
6"
?
?
?
?
OBD
OBD
OBD
OBD
OBD
OBD
OBD
OBD
OBD
ACD
OBD
OBD
OBD
OBD
OBDOBD
OBD
OBD
OBD
OBD
OBD
VD (IN VERTICAL)
VD (IN VERTICAL)
OBD
OBD
OBD
OBD
46"x28"60"x28"
PART PLAN G
PART PLAN F
17.914.7 18.618.1 20.8 20.9
E.9
D.8
B.8
REFER TO ARCH 801FOR HOSE REELMOUNTING DETAIL.SEE MECHANICALDETAIL VES01 ANDSEQUENCE ON MEC-502.
REFER TO ARCH 801 FOREXHAUST ARMMOUNTING DETAIL.
REFER TO ARCH 801 FOREXHAUST ARM MOUNTINGDETAIL.
DS
DS
DOOR SENSORWIRE TO BMS.
DS
DOOR SENSORWIRE TO BMS.
DS
DOOR SENSOR WIRE TOBMS. SEE DETAIL H-1557ON MEC-605 (TYP.)
DS
REFER TOARCH 801 FOREXHAUST ARMMOUNTINGDETAIL.
VES8
16"ø8"ø
ECDACD
8"ø
16"x14"
16"x14"
12"x12" EXHAUST UPGOOSENECK ABOVE ROOFWITH BIRD SCREEN
ECD
20"x
28"
20"x
28"
20"x
28"
12"x12"
ACD
DUCT BELOW CRANE RAIL
DUCT ABOVE CRANE RAIL
DUCT BELOW CRANE RAIL
DUCT ABOVE CRANE RAILDUCT ABOVE CRANE RAIL
DUCT ABOVE CRANE RAIL
18"x18"
18"x18"
18"x18"
18"x18"
18"x18"
12"x
12"
12"x12"
18"x18"
18"x18"
18"x18"
18"x18"
12" ROUND EXHAUST DUCT BYPAINT BOOTH MANUFACTURER.PROVIDE FLANGE, SUPPORTS, ANDCOLLARS AS REQUIRED ROOFPENETRATION.
96"x
54"
TIE INTO LV-10 INTAKE LOUVER(SEE MEC 307 FOR LOCATION)
166"x74"
166"x74"
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:31:23 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-206
MECHANICAL - PART PLAN F
ROCKY HILL
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
SCALE: 1/8" = 1'-0"1 HVAC - DUCTWORK - PART PLAN F - MACHINE SHOP
NO. Revision Description Date 10.11
FD
17 18 18.8 19.1 19.5 21
C
B
A
19 20
PAINT BAYS36
PARTSWASHER
34
PAINTREMOVALBOOTH
37
PAINT SPRAYBOOTH
38
PAINT MIXROOM
39
OXYGEN /ACETYLENE
STORAGE CRIB33.2
PAINTEQUIPMENT
ROOM35
PART PLAN G
PART PLAN F
PART PLAN G
PART PLAN F
LV4
24"x24"
16"x16"
16"x
16"
16"x
16"
5'-0" x 3'-0" WELDING TABLEHOOD WITH 14" X 14" NECK(1500 CFM)
EH(980)14"x14"
SE(500)
SE(500)
SE(500)
SE(300)
24"x
24"10
"x6"
24x24 UP TO LV-20. TIE INTOAIR COMPRESSOR AS SHOWN
ON DETAIL.
ACD
16"x16" THRUWALL W/WMS.BALANCE FOR1250 CFM
OBDOBD
OBD
VD (IN VERTICAL)
VD (IN VERTICAL)
VD (IN VERTICAL)
VD (IN VERTICAL)
17.9 18.618.1 20.8 20.9
B.8
DOOR SENSORWIRE TO BMS.
DS
DOOR SENSORWIRE TO BMS.
DS
DOOR SENSORWIRE TO BMS.
DS
DUCT BELOW CRANE RAIL
18"x18"
48" ROUND EXHAUST DUCT BYPAINT BOOTH MANUFACTURER.PROVIDE FLANGE, SUPPORT,AND COLLARS AS REQUIRED FORROOF PENETRATION.
12" ROUND EXHAUST DUCT BYPAINT BOOTH MANUFACTURER.PROVIDE FLANGE, SUPPORTS, ANDCOLLARS AS REQUIRED ROOFPENETRATION.
TIE IN TO PAINT BOOTHMANUFACTURER'S AHU INLET(SEE ARCHITECTURALS FORADDTIONAL DETAILS.)
96"x
54"
96"x54"
TIE INTO LV-10 INTAKE LOUVER(SEE MEC 307 FOR LOCATION)
166"x74"
166"x74"
17 18 18.8 19.1 19.5 21
C
B
A
19 20
PAINT BAYS36
PARTSWASHER
34
PAINTREMOVALBOOTH
37
PAINT SPRAYBOOTH
38
PAINT MIXROOM
39
OXYGEN /ACETYLENE
STORAGE CRIB33.2
PAINTEQUIPMENT
ROOM35
PART PLAN G
PART PLAN F
PART PLAN G
PART PLAN F
EF4
16"x16"
16"x
16"
5'-0" x 3'-0" WELDINGTABLE HOOD WITH 14"X 14" NECK (1500 CFM)
EH(980)14"x14"
SE(500)
SE(500)
SE(500)
24x24 UP TO LV-20. TIEINTO AIR COMPRESSORAS SHOWN ON DETAIL.
AIR COMPRESSOR(BY OTHERS)
16"x16" THRU WALL W/WMS.BALANCE FOR 1250 CFM
OBDOBD
OBD
VD (IN VERTICAL)
VD (IN VERTICAL)
VD (IN VERTICAL)
VD (IN VERTICAL)
17.9 18.618.1 20.8 20.9
B.8
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:31:34 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-207
MECHANICAL - PART PLAN G
ROCKY HILL
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
SCALE: 1/8" = 1'-0"1 HVAC - DUCTWORK - PART PLAN G - PAINT AREA
NO. Revision Description Date
1/8" = 1'-0"2
DUCTWORK - PART PLAN G - PAINTAREA MECHANICAL PLATFORM
10.12
T
TTTTTT
T
T T
T
T
T
T
T
T
TT T
T
T
T
TT
T
T
T
T
T
1 3 4 5 6 7 7.2 8 9 10 10.7 11 12 13 14 14.6 15 15.4 16 17 18 18.8 19.1 19.5 21
K
J
I.5
I
G.9
GF
E.4
E
D.9
D.6
D
C
B
A
J.9
19 20
H
14.5
G.1
11.7
11.9
1 1/4"1 1/4"
11/
4"11/
4"11/
4"11/
4"
11/
4"11/
4"1"
1"
4"4"
2"2" 1"1"
1"
1"1"
11/
2"1
1/2"
11/
2"1
1/2"
2"2"
21/
2" 21/
2"3"
3"
4"4"
11/
4" 11/
4"
11/
4"1
1/4"
2"3"
3"2"
3" 3"4"4"
6"6"
3"
2 1/2"
1 1/4"1 1/4"
2"2"
2"2"
11/
4" 11/
4"
3"3"
11/
2"1
1/2"
1" 1" 1" 1" 2"2"
4"4"
2 1/2"2 1/2" 3"
3"2"2"
1 1/4"1 1/4"
3"3"
6"6"
6"
6"6"
2 1/2"11/
4"1
1/4"
1 1/4"1 1/4"
1/2"1/2"
1/2"1/2"
1/2"
1 1/4"1 1/4"
3"
UH7
UH8
UH9
UH10
UH31
11/
4"1
1/4"
2"2"
1 1/4"
UH2
UH1
UH4
UH3
UH15
UH16
UH17
UH13
UH12
UH20
UH21
UH22
FTR2
FTR1
UH18
UH19
UH30
UH28
UH29
UH27
UH26
UH24
UH23
UH25
11/
4"11/
4"
2" 2"
RADIANT FLOOR ZONE (TYP.)
RADIANT FLOOR ZONE (TYP.)
RADIANT FLOOR ZONE (TYP.)
RADIANT FLOOR ZONE (TYP.)
1"
1"1" 1"
1" 1"
1"
1"
2"2"
11/
2"1
1/2"
1"3"
21/
2"
21/
2"
1 1/2"1 1/2"
1"
17.914.7 18.6
13.6
18.1 20.814.1 20.9
H.4
E.9
D.8
B.8
H.1
UH5
UH6
UH11
UH14
CUH1
FTR6
FTR7
FTR8
FTR13
FTR15
FTR10
FTR9
FTR14
CUH2
UH32
FTR5
FTR4
FTR11
FTR3
FTR12
FTR12
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
3/64" = 1'-0"10/21/2014 3:30:25 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-200P
OVERALL PIPE PLAN
ROCKY HILL
SCALE: 3/64" = 1'-0"1 HVAC - 00 PIPING OVERALL
NO. Revision Description Date
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
NOTES:1) COORDINATE RADIANT SLAB PIPING WITH LIFTLOCATIONS. REFER TO ARC-100
2) COORDINATE RADIANT SLAB PIPING WITH FLOORANCHOR LOCATIONS. REFER TO ARC-102
10.13
TTT
T
T
T
T
2"2"
1 1/4"1 1/4"
1 1/4"1 1/4"
2"2"
1 1/4"1 1/4"
11/
4" 11/
4"
1 1/4"1 1/4"
2"2"
11/
4" 11/
4"
4 5 6 7 7.2 8 9 10 10.7 11 12 13
K
J
I.5
I
G.9
G
F
J.9
H
G.1
UH1
UH4
UH3
UH2
UH11
UH5
REPAIR BAYS28
EQUIPMENTINSPECTION /
CNGINSPECTION
26
TOOL CRIB27
SERVICEVESTIBULE
19
11.7 11.9
PART
PLAN
B
PART
PLAN
A
PART PLAN C
PART PLAN A
35' X 15' RADIANTFLOOR ZONE. (3) 1/2"CIRCUITS
35' X 15' RADIANTFLOOR ZONE. (3) 1/2"CIRCUITS
35' X 15' RADIANT FLOORZONE. (3) 1/2" CIRCUITS
35' X 15' RADIANT FLOORZONE. (3) 1/2" CIRCUITS35' X 15' RADIANT FLOOR
ZONE. (3) 1/2" CIRCUITS
35' X 15' RADIANT FLOORZONE. (3) 1/2" CIRCUITS
35' X 15' RADIANT FLOORZONE. (3) 1/2" CIRCUITS
1 1/4"1 1/4"
1"
1"
1"1"
1"1"
2"2"
1"1" 2 1/2"
2 1/2"1"1" 1"
1"
1 1/4"
11/
4"11/
4"
1"1"
1"1"
1"
1"
1 1/4"1 1/4"
2"
1"1"
2"2"
EJ-3
ANCHORGUIDES GUIDES
GUIDES
GUIDES
ANCHOR
GUIDES
GUIDES
GUIDES
RAD. ZONE HEADER BYMANUFACTURER REFER TO DETAILH1556 ON MEC-605 (TYP.)
RAD. ZONE HEADER BYMANUFACTURER REFERTO DETAIL H1556 ONMEC-605 (TYP.) RAD. ZONE HEADER BY
MANUFACTURERREFERTO DETAIL H1556 ONMEC-605 (TYP.)
RAD. ZONE HEADER BYMANUFACTURER REFER TO DETAILH1556 ON MEC-605 (TYP.)
RAD. ZONE HEADER BYMANUFACTURER REFER TODETAIL H1556 ON MEC-605(TYP.)
RAD. ZONE HEADER BYMANUFACTURER REFER TODETAIL H1556 ON MEC-605 (TYP.)
RAD. ZONE HEADER BYMANUFACTURER REFER TODETAIL H1556 ON MEC-605(TYP.) SEE ARC-801 FOR PIPINGBUMPER
RAD. ZONEHEADER BYMANUFACTURER
(2) 35' X 5' RADIANT FLOORZONE. (2) 1/2" CIRCUITSCOORDINATE WITH LIFTPLACEMENT
RADIANT HWS&R
RADIANT HWS&RRADIANT HWS&R
RADIANT HWS&RRADIANT HWS&R
RADIANT HWS&R
UH LOOP HWS&R
UH LOOP HWS&R
UH LOOP HWS&R
UH LOOP HWS&R
UH LOOP HWS&R
H.4
E.9
H.1
RAD. ZONE HEADER BYMANUFACTURER REFERTO DETAIL H1556 ONMEC-605 (TYP.) SEEARC-801 FOR PIPINGBUMPER
BELOW CRANE RAIL
2"2"
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:30:41 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-201PMECHANICAL PIPE - PART
PLAN A
ROCKY HILL
SCALE: 1/8" = 1'-0"1 HVAC - PIPING - PART PLAN A - NORTH REPAIR BAYS
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
NO. Revision Description Date 10.14
T
T
TT
T
T
4"
2"2"
1 1/4"1 1/4"
1 1/4"1 1/4"
1 1/4"
1 1/4"1 1/4"
1 1/4"
4"4"4"
13 14 14.6 15 15.4 16 17 18 18.8 19.1 19.5 21
K
J
I.5
I
G.9
G
F
J.9
19 20
H
14.5
G.1
UH10
UH9
UH8
UH7
UH6
WELD SHOP30
TOOL CRIBWITH NO
CHARGE AREA29
OXYGEN /ACETYLENE
STORAGE CRIB30.2
REPAIR BAYS28
OXYGEN /ACETYLENE
STORAGE CRIB30.1P
ART
PLAN
B
PART
PLAN
A
PART PLAN F
PART PLAN B
35' X 15' RADIANTFLOOR ZONE. (3)1/2" CIRCUITS
35' X 15' RADIANT FLOORZONE. (3) 1/2" CIRCUITS
35' X 15' RADIANT FLOORZONE. (3) 1/2" CIRCUITS
35' X 15' RADIANT FLOORZONE. (3) 1/2" CIRCUITS
35' X 15' RADIANT FLOORZONE. (3) 1/2" CIRCUITS
35' X 15' RADIANT FLOORZONE. (3) 1/2" CIRCUITS
1"1"1
1/2"
11/
2"
2"2"
11/
4" 11/
4"
11/
4"11/
4"
1"1"
1"1"
1 1/4"1 1/4"
1 1/4"1 1/4"
2 1/2"2 1/2"
1"1"
1 1/4"1 1/4"
3"3"
3"3"
1"1" 1"
1" 1"1"
2 1/2"2 1/2" 3"
3" 3"3"
1 1/4"1 1/4"
3"3"
3"3"EJ-2
EJ-1
EJ-4 GUIDES GUIDES ANCHORGUIDESGUIDESGUIDES
GUIDES GUIDES GUIDESGUIDES GUIDES ANCHOR
ANCHOR
RAD. ZONE HEADER BYMANUFACTURER REFERTO DETAIL H1556 ONMEC-605 (TYP.)
RAD. ZONE HEADERBY MANUFACTURER
RAD. ZONE HEADER BYMANUFACTURER REFER TODETAIL H1556 ON MEC-605(TYP.)
RAD. ZONE HEADER BYMANUFACTURER REFERTO DETAIL H1556 ONMEC-605 (TYP.)
RAD. ZONE HEADERBY MANUFACTURER
RAD. ZONE HEADER BYMANUFACTURER REFER TO DETAILH1556 ON MEC-605 (TYP.)
RAD. ZONE HEADER BYMANUFACTURER REFERTO DETAIL H1556 ONMEC-605 (TYP.) SEEARC-801 FOR PIPINGBUMPER
(2) 35' X 5' RADIANT FLOORZONE. (2) 1/2" CIRCUITS.COORDINATE WITH LIFTPLACEMENT
RADIANT HWS&R
RADIANT HWS&RRADIANT HWS&R
RADIANT HWS&R RADIANT HWS&R
RADIANT HWS&R
UH LOOP HWS&R UH LOOP HWS&R
UH LOOP HWS&R
UH LOOP HWS&R
UH LOOP HWS&R
UH LOOP HWS&R
17.914.7 18.6
13.6
18.1 20.814.1 20.9
H.4
E.9
H.1
BELOW CRANE RAIL
BELOW CRANE RAIL
COORINATE AROUND SPIRAL STAIRWAY.
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:30:51 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-202PMECHANICAL PIPE - PART
PLAN B
ROCKY HILL
SCALE: 1/8" = 1'-0"1 HVAC - PIPING - PART PLAN B - SOUTH REPAIR BAYS
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
NO. Revision Description Date 10.15
T
T
T
T
2 1/2"2 1/2"
1 1/4"1 1/4"
11/
4"1
1/4"
11/
4" 11/
4"
2"2"
1 1/4"1 1/4"
1 3 4 5 6
G
F
E.4
D.9
D.6
G.1
UH14
UH12
UH13
UH16
35' X 15' RADIANT FLOORZONE. (3) 1/2" CIRCUITS
LUBE BAYS25
LUBRICANTSTORAGE /
COMPRESSOR24 WASH BAY
23
CLCL
CL
PART PLAN C
PART PLAN A
PART PLAN D
PART PLAN C
(2) 35' X 5' RADIANT FLOORZONE. (2) 1/2" CIRCUITS
11/
4" 11/
4"
1 1/4"1 1/4"
1 1/4"1 1/4"
1 1/4"1 1/4"
11/
4"1
1/4"
1"1"
1"1"
ANCHOR
GUIDES
RAD. ZONE HEADER BYMANUFACTURER REFER TODETAIL H1556 ON MEC-605(TYP.) SEE ARC-801 FORPIPING BUMPER
RAD. ZONE HEADER BYMANUFACTURER.SEE ARC-801 FOR PIPINGBUMPER
(2) 35' X 5' RADIANT FLOORZONE. (2) 1/2" CIRCUITS
RADIANT HWS&R
UH LOOP HWS&R
PROVIDE WITH WATERPROOF T-STAT
E.9
D.8
BELOW CRANE RAIL
BELOW CRANE RAIL
2"2"
2 1/2"2 1/2"
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:30:55 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-203PMECHANICAL PIPE- PART
PLAN C
ROCKY HILL
SCALE: 1/8" = 1'-0"1 HVAC - PIPING - PART PLAN C - LUBE & WASH BAYS
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
NO. Revision Description Date 10.16
TT
T
T
T
T
6"6"
4"4"
UH18
2" 2"
2"2"
6 7 7.2 8 9 10 10.7 11 12
G
F
E.4
E
D.9
D.6
D
G.1
UH17
UH19
WB1
STORESSTOCKROOM
22STORES
MATERIALMANAGEMENT
20
SERVICEVESTIBULE
19
STORESSTOCK ROOMSUPERVISOR
21
COMM ROOM08
VEST11
11.7 11.9
PART
PLAN
D
PART
PLAN
C
PART PLAN E
PART PLAN D
11/
4" 11/
4"
3"
2"2"
1 1/4"1 1/4"
2 1/2"2 1/2"
1 1/4"1 1/4"
EJ-3
EJ-1
ANCHOR
GUIDESGUIDESGUIDESGUIDESGUIDES
GUIDES
GUIDES
RADIANT HWS&R
RADIANT HWS&RRADIANT HWS&R
UH LOOP HWS&R
CUH2
E.9
D.8
UH HWS&R
4"4"
3"3"3"
2"
UH LOOP HWS&R
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:31:00 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-204PMECHANICAL PIPE - PART
PLAN D
ROCKY HILL
SCALE: 1/8" = 1'-0"1 HVAC - PIPING - PART PLAN D - STORES
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
NO. Revision Description Date 10.17
FT
T
T
T
T
T
T
T
T
T
T
T
T
TT
T
T
10.7 11 12 13 14 14.6
G
F
E.4
E
D.9
D.6
D
C
B
14.5
G.1
6"6"
WB1
WB2
WB3
UH21
UH20
ET1
FTR1
CUH1
BREAK ROOM07
CONFERENCEROOM
05
MACHINESHOP CREWLEADER &
CLERK OFFICE04
MACHINESHOP
SUPERVISIOR03
VEST01
JANITOR06
MENS ROOM12
REPAIR CREWLEADER &
SUPERVISOROFFICE
16
GARAGESUPERVISOR
15
EQUIPMENTGENERAL
SUPERVISOR14
MECHANICALROOM
10
FIRE PUMPROOM
40
MEDIASTORAGE
ROOM18
STORESMATERIAL
MANAGEMENT20
SERVICEVESTIBULE
19
STORESSTOCK ROOMSUPERVISOR
21 LOCKER/SHOWER13A
HALL02
ELECTRICALROOM
09
COMM ROOM08
WOMENSROOM
13
VEST11
EQUIPMENTINSPECTION
ANDIN-SERVICE
OFFICE17
HWP1
HWP2
HWP3
HWP4
11.7 11.9
1" 1"
3/4"
3/4"
1"1"
1"1"
1"1"
1"
2"2"
1"1"
2"2"
1"1"
4"4"
6"6"
4" 4"
4"4"
4" 4"
3"3"
6"6"
3"3"
6"
21/
2"2
1/2"
1" 1"
3"
2"2"
1"
1"
PART
PLA
NF
PART
PLAN
E
PART PLAN E
PART PLAN D
RADIANT HWS&R
ERU LOOP HWS&R
RADIANT FLOORLOOP HWS&R
UH LOOP HWS&R
UH LOOP HWS&R
UH LOOP HWS&R
SHOT FEEDER &COUPON RACK
4" ERU HWS&R UPTO MECHANICALPLATFORM
FTR6
FTR7
FTR8
FTR13
FTR9
FTR14
FTR10
FTR15
FTR5
FTR4
FTR11
FTR3
FTR12
FTR12
FTR2
1"
1"1"
1" 1"
1 1/2"1 1/2"
11/
2"11/
2"
1"
1"
1"
1"
1"1"1 1/4"
1 1/4"
1"
1"1"
2"2" 2"
2" 1 1/4"1 1/4"
3"3"
3"3"
11/
2"1
1/2"
3" 3"
6"
HWP5
HWP6
4" 6" 3"
4"6"
3"
1 1/4"1 1/4"
1 1/4"1 1/4"
3"3"
11/
2"6" 1 1/2"
CHEMICAL TREATMENT SKIDW/SHOT FEEDER & COUPONRACK
3"3"
1 1/2"
HEATING COILLOOP HWS&R
6"
3" 1 1/2" 3"3"
6"
6"
11/
4" 11/
4"
3"3"
11/
2"
AS1
NOTE: ALL PUMPS SHALL BE 42"AFF FOR EASE OF MAINTENANCE
3"
FTR LOOPHWS&R
FTR LOOP HWS&R
HC1
14.7
13.6
14.1
E.9
D.8
B.8
CUH2
FTR12
3/4"3/4"
3/4"3/4"
12 13 14 14.6
G
F
E.4
E
D.9
D.6
D
14.5
G.1
2 1/2"2 1/2"
21/
2"21/
2"
21/
2"2
1/2"
11/
4"1
1/4"
4"4"
4"
4"
1 1/4"1 1/4"
ERU1&2
0 kW)(0, 0,
ERU1&2
0 kW)(0, 0,
ERU4
0 kW)(0, 0,ERU3
0 kW)(0, 0,
UH32
EQUIPMENTPLATFORM
41
153' - 9"
11.7 11.9
PART
PLA
NF
PART
PLAN
D
4"HWS&R DN
14.7
13.6
14.1
E.9
D.8
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:31:17 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-205PMECHANICAL PIPE - PART
PLAN E & EQUIP. PLATFORM
ROCKY HILL
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
SCALE: 1/8" = 1'-0"1 HVAC - PIPING - PART PLAN E - OFFICE AREA
SCALE: 1/8" = 1'-0"2 HVAC - PIPING - EQUIPMENT PLATFORM
NO. Revision Description Date 10.18
T
T
T
T
T
T
TT T
1 1/4"1 1/4"
1 1/4"
3"3"
1 1/4"
2"2"
2"2"
14.6 15 15.4 16 17 18 18.8 19.1 19.5 21
G
F
E.4
E
D.9
D.6
D
C
B
19 2014.5
G.1
UH23
UH22
UH27
UH31
UH29
UH10
UH26
UH28
UH30
MACHINESHOP
31
AERIALBUCKET BAYS
32
PAINT BAYS36
PARTSWASHER
34
PAINTREMOVALBOOTH
37
PAINT MIXROOM
39
OXYGEN/ACETYLENESTORAGE CRIB
33.1
OXYGEN /ACETYLENE
STORAGE CRIB33.2
WELD /FABRICATION
SHOP33
PART PLAN G
PART PLAN F
PART PLAN G
PART PLAN F
PART PLAN F
PART PLAN B
PART
PLA
NF
PART
PLAN
E
35' X 15' RADIANT FLOORZONE. (3) 1/2" CIRCUITS
35' X 15' RADIANT FLOORZONE. (3) 1/2" CIRCUITS
35' X 15' RADIANT FLOORZONE. (3) 1/2" CIRCUITS
2"2"
11/
4"1
1/4"
11/
4"1
1/4"
1"1"
11/
2"11/
2"1
1/2"
11/
2"
1"1"
21/
2"2
1/2"
1"1"1
1/2"
11/
2"
1 1/4"1 1/4"
1 1/4"1 1/4"
11/
4"11/
4"
1 1/4"
1 1/4"1 1/4"
UH24
ANCHOR
ANCHOR
EJ-4
GUIDES
GUIDES
GUIDES
GUIDES
RAD. ZONE HEADERBY MANUFACTURERREFER TO DETAILH1556 ON MEC-605(TYP.)
RAD. ZONE HEADERBY MANUFACTURERREFER TO DETAILH1556 ON MEC-605(TYP.)
RAD. ZONE HEADERBY MANUFACTURERREFER TO DETAILH1556 ON MEC-605(TYP.)
UH LOOP HWS&R
UH LOOP HWS&R
UH LOOP HWS&R
UH LOOP HWS&R
UH LOOP HWS&R
RADIANT HWS&R
RADIANT HWS&R
17.914.7 18.618.1 20.8 20.9
E.9
D.8
B.8
BELOW CRANE RAIL
BELOW CRANE RAIL
BELOW CRANE RAIL
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:31:29 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-206PMECHANICAL PIPE - PART
PLAN F
ROCKY HILL
SCALE: 1/8" = 1'-0"1 HVAC - PIPING - PART PLAN F - MACHINE SHOP
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
NO. Revision Description Date 10.19
T
T
TT
T
18 18.8 19.1 19.5 21
C
B
A
19 20
UH23
UH27
UH26
UH25
PAINT BAYS36
PARTSWASHER
34
PAINTREMOVALBOOTH
37
PAINT SPRAYBOOTH
38
PAINT MIXROOM
39
PAINTEQUIPMENT
ROOM35
PART PLAN G
PART PLAN F
PART PLAN G
PART PLAN F
35' X 15' RADIANT FLOORZONE. (3) 1/2" CIRCUITS
11/
4"1
1/4"
11/
4"1
1/4"
1 1/4"1 1/4"
11/
4"11/
4"
UH24
ANCHOR
UH LOOP HWS&R
17.9 18.618.1 20.8 20.9
B.8
PROVIDE SLEEVE AND PENETRATION FOR 5"PIPE WITH GOOSENECK. SEE ARCHITECTURALSFOR ADDITIONAL DETAILS.
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:31:38 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-207PMECHANICAL PIPE - PART
PLAN G
ROCKY HILL
SCALE: 1/8" = 1'-0"1 HVAC - PIPING - PART PLAN G - PAINT AREA
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
NO. Revision Description Date 10.20
4 5 6 7 7.2 8 9 10 10.7 11 12
K
J
I.5
I
G.9
G
F
J.9
H
G.1
VF12
VF1
164' - 8 1/4"167' - 5 1/2"
187' - 3 1/4"
173' - 5 3/4"
173' - 5 3/4"
11.7 11.9
PART
PLAN
B
PART
PLAN
A
PART PLAN C
PART PLAN A
H.4
E.9
H.1
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:31:40 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-301MECHANICAL ROOF - PART
PLAN A
ROCKY HILL
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
SCALE: 1/8" = 1'-0"1 HVAC - DUCTWORK - ROOF LEVEL - PART PLAN A
NO. Revision Description Date 10.21
13 14 14.6 15 15.4 16 17 18 18.8 19.1 19.5 21
K
J
I.5
I
G.9
GF
J.9
19 20
H
14.5
G.1
VF2
VF3
PART
PLAN
B
PART
PLAN
A
PART PLAN F
PART PLAN B
17.914.7 18.6
13.6
18.1 20.814.1 20.9
H.4
E.9
H.1
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:31:42 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-302MECHANICAL ROOF - PART
PLAN B
ROCKY HILL
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
SCALE: 1/8" = 1'-0"1 HVAC - DUCTWORK - ROOF LEVEL - PART PLAN B
NO. Revision Description Date 10.22
1 3 4 5 6
GF
E.4
D.9
D.6
G.1
EF2
VF7VF
8
167' - 5 1/2"
166' - 5" 166' - 5"
PART PLAN C
PART PLAN A
PART PLAN D
PART PLAN C
E.9
D.8
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:31:43 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-303MECHANICAL ROOF - PART
PLAN C
ROCKY HILL
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
SCALE: 1/8" = 1'-0"1 HVAC - DUCTWORK - ROOF LEVEL - PART PLAN C
NO. Revision Description Date 10.23
6 7 7.2 8 9 10 10.7 11 12
G
F
E.4
E
D.9
D.6
D
G.1
VF5
VF6
164' - 8"
164' - 8 1/4"
173' - 5 3/4"
11.7 11.9
PART
PLAN
D
PART
PLAN
C
PART PLAN E
PART PLAN D
E.9
D.8
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:31:45 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-304MECHANICAL ROOF - PART
PLAN D
ROCKY HILL
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
SCALE: 1/8" = 1'-0"1 HVAC - DUCTWORK - ROOF LEVEL - PART PLAN D
NO. Revision Description Date 10.24
10.7 11 12 13 14 14.6
G
F
E.4
E
D.9
D.6
D
C
B
14.5
G.1
EF3
RTU1
0 kW)(0, 0,
EF1B
EF1A
TE1
EF1C
EF1D
11.7 11.9
PART
PLA
NF
PART
PLAN
E
PART PLAN E
PART PLAN D
ACCU2
ACCU1
LV1
LV2
14.7
13.6
14.1
E.9
D.8
B.8
EF5
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:31:48 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-305MECHANICAL ROOF - PART
PLAN E
ROCKY HILL
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
SCALE: 1/8" = 1'-0"1 HVAC - DUCTWORK - ROOF LEVEL - PART PLAN E
NO. Revision Description Date 10.25
14.6 15 15.4 16 17 18 18.8 19.1 19.5 21
GF
E.4
E
D.9
D.6
D
C
B
19 2014.5
G.1
VF11
VF10
VF4
VF9
PART PLAN G
PART PLAN F
PART PLAN G
PART PLAN F
PART PLAN F
PART PLAN B
PART
PLA
NF
PART
PLAN
E
VF13
VF15
LV10
LV3
17.914.7 18.618.1 20.8 20.9
E.9
D.8
B.8
LV10
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:31:50 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-306MECHANICAL ROOF - PART
PLAN F
ROCKY HILL
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
SCALE: 1/8" = 1'-0"1 HVAC - DUCTWORK - ROOF LEVEL - PART PLAN F
NO. Revision Description Date 10.26
17 18 18.8 19.1 19.5 21
C
B
A
19 20
PART PLAN G
PART PLAN F
PART PLAN G
PART PLAN F
VF13
VF15
VF14
LV5
LV6
LV10
LV3
17.9 18.618.1 20.8 20.9
B.8
LV10
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:31:52 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-307MECHANICAL ROOF - PART
PLAN G
ROCKY HILL
A B
C
KEY PLAN
DE
F
G
N
G
K
41
D
13 21
1814.51210.76
CB.1
A
D.6
PARTIAL PLAN LEGEND:
• A - NORTH REPAIR BAYS• B - SOUTH REPAIR BAYS• C - LUBE AND WASH BAYS• D - STORES• E - OFFICE AREA• F - MACHINE SHOP• G - PAINT AREA
SCALE: 1/8" = 1'-0"1 HVAC - DUCTWORK - ROOF LEVEL - PART PLAN G
NO. Revision Description Date 10.27
S/S
VFDSO
VFDS
ALM
AMFS
SPL
OAD
AMFS
SPL
FID FID
DPTFMS
AMFS
SPL
FID
S/S
VFDSO
VFDS
ALM
S/S
VFDSO
VFDS
ALM
S/S
VFDSO
VFDS
ALM
AMFS
SPL
OAD
FID
DPT-2
DPT-3
RTC
CONDENSING BOILER PLANT CONTROL / FLOW DIAGRAM AND SEQUENCE OF OPERATIONQUADRA PLEX EXHAUST FAN AIR CONTROL
SEQUENCES (EF-1A,1B,1C,1D)
AS
CHEMICAL SHOTFEEDER
NC
NC
HWR
HWST
GENERAL
1. BOILER MANUFACTURER SHALL PROVIDE BOILER CONTROLLER TO SEQUENCE AND MODULATE ALL BOILERS, AND PROVIDE MODBUS, BACNET, OR LONTALK 2-WAY COMMUNICATIONS, INCLUDING ALARMS, BETWEEN THE BOILER CONTROLLER AND THE BAS. BOILER CONTROLS SHALL BE SET-UP BY THE MANUFACTURER TO INTERLOCK WITH ANYASSOCIATED COMBUSTION AIR DAMPERS, ISOLATION VALVES, AND VENT DAMPERS. BAS CONTRACTOR SHALL INSTALL AND WIRE REMOTE SENSORS FURNISHED BY THE BOILER MANUFACTURER, PROVIDE LINE SIZED 2-POSITION BOILER ISOLATION VALVES (WITH POSITION INDICATION AND CONTROL SIGNALS INTERFACED WITH BOILER CONTROLS),PROVIDE ALL PUMP CONTROLS, AND PROVIDE DYNAMIC GRAPHICS (ALL DATA) OF THE BOILER SYSTEM AT THE OPERATOR'S WORKSTATION.
2. BAS CONTRACTOR SHALL MEET WITH BOILER CONTROLS MANUFACTURER TO COORDINATE THE REQUIRED CONTROL SIGNALS, STATUS SIGNALS (FOR THE GRAPHICS), AND ALARMS FOR THE BOILER SYSTEM. BAS CONTRACTOR IS RESPONSIBLE FOR IMPLEMENTATION OF ALL NECESSARY CONTROL SEQUENCES INCLUDING ALL CONTROL DEVICES ANDLOGISTICS REQUIRED TO MEET THE DESIGN INTENT REGARDLESS OF WHAT MAY OR MAY NOT BE PROVIDED BY EQUIPMENT MANUFACTURERS.
3. ALL SET POINTS AND TIME DELAYS SHALL BE ADJUSTABLE WITHOUT ANY PROGRAM CHANGES. ALL ACTUATORS SHALL BE ELECTRONIC. PROVIDE FOR LOCAL EQUIPMENT OVERRIDE OF CONTROL SYSTEM.4. BOILERS HAVE DUCTED COMBUSTION AIR. INDIVIDUAL COMBUSTION AIR DAMPERS (CAD) PROVIDED BY BOILER MANUFACTURER SHALL PROVE AT LEAST 85% OPEN BEFORE BURNER CAN START AND PROVE CLOSED AFTER BURNER STOPS. IF ANY CAD OR FID FAILS, AN ALARM SHALL BE SENT TO THE BAS AND, IF NEEDED, THE NEXT BOILER IN
SEQUENCE SHALL BE ENERGIZED.5. PROVIDE TEMPERATURE SENSORS AND OTHER DEVICES SHOWN AND COORDINATE ALL SENSOR INSTALLATION LOCATIONS WITH THE MECHANICAL CONTRACTOR. COORDINATE AND INSURE MANUFACTURER'S RECOMMENDED UPSTREAM AND DOWNSTREAM PIPE DIAMETERS ARE PROVIDED - ESPECIALLY FOR FLOW METERS. WIRE BOILER
MANUFACTURER'S CONTROLLER TO EACH BOILER AND SENSOR PER MANUFACTURER'S DIAGRAMS. COORDINATE TO OBTAIN ALL INFO FOR BAS GRAPHICS.6. BAS CONTRACTOR SHALL PROVIDE AND WIRE INDIVIDUAL FIRESTATS (NOT SHOWN) TO SHUTDOWN EACH BOILER AND INSURE THE BOILER EMERGENCY SHUT-OFF SWITCHES STOP ALL BOILERS.
HOT WATER CONTROL
1. THE BOILER SYSTEM SHALL NORMALLY BE ON AND SHALL BE CAPABLE OF BEING AUTOMATICALLY STARTED AND STOPPED BY THE BAS. THE CONTROL OF BOILER STAGING AND CAPACITY SHALL BE BY THE BOILER MANUFACTURER.2. BEFORE THE BOILERS ARE STARTED, THE LEAD BOILERS ISOLATION VALVE (BIV) SHALL BE OPENED AND THE HOT WATER PUMP ASSOCIATED WITH THE SYSTEM CALLING FOR HEAT SHALL BE STARTED AT LOW SPEED BY THE BAS. IF PUMP FAILS, THE BAS SHALL ALARM.3. OPERATING SPEED FOR THE PUMP SHALL BE THE LOWEST REQUIRED TO MAINTAIN THE SET POINT OF THE ASSOCIATED REMOTE DIFFERENTIAL PRESSURE SENSOR (DPT) LOCATED NEAR THE FURTHEST EQUIPMENT (TYP OF 3). INITIAL SET POINT OF REMOTE DPT SHALL BE 15 PSI WITH FINAL SET POINT COORDINATED WITH THE BALANCING
CONTRACTOR TO THE LOWEST NEEDED TO GET FULL FLOW TO THE MOST REMOTE EQUIPMENT (WITH THE EQUIPMENT CONTROL VALVE NO MORE THAN 90% OPEN).4. THE BOILER SUPPLY WATER TEMPERATURE AT SENSOR BST SHALL BE INITIALLY SET TO A MAXIMUM OF 140°F. BOILERS SHALL STAGE CAPACITY AT OPTIMAL EFFICIENCY TO MAINTAIN COMMON SUPPLY WATER TEMPERATURE CONTROL.
BOILER CONTROL SYSTEM
1. WHEN A BOILER IS NEEDED TO OPERATE, THE ASSOCIATED COMBUSTION AIR DAMPER (CAD), AND BOILER ISOLATION VALVE (BIV) SHALL PROVE OPEN FIRST. WHEN A BOILER IS NOT NEEDED THE CAD, FID, AND BIV SHALL CLOSE 20 SECONDS (ADJ.) AFTER THE BURNER IS STOPPED. AN EXCEPTION IS THE LEAD BOILER WHOSE BIV SHALL ALWAYSREMAIN OPEN TO ALLOW PUMP FLOW. AS PROVIDED BY CONTROLS CONTRACTOR.
2. ON A CALL FOR HEATING, THE LEAD BOILER SHALL START ON LOW FIRE. THE BOILER HOT SUPPLY WATER TEMPERATURE AT BST SHALL BE MAINTAINED BY STAGING OF BOILERS AND MODULATING THE BURNERS. MANUFACTURER'S BOILER CONTROLLER SHALL START AND OPERATE THE LAG BOILERS WHEN NEEDED TO MAINTAIN EITHER THE SYSTEMSUPPLY TEMPERATURE AT BST OR WHEN THE SYSTEM WOULD OPERATE MORE EFFICIENTLY WITH MORE BOILERS ON.
3. THE BOILER CONTROLLER SHALL ROTATE THE LEAD AND LAG BOILERS TO ASSURE THAT ALL BOILERS RECEIVE EQUAL RUN TIME.4. WHEN LOAD DROPS (BASED ON BOILER CAPACITY AND EFFICIENCY) LAG BOILERS SHALL BE STOPPED AS REQUIRED.5. THE BOILER CONTROLLER SHALL ENABLE/DISABLE, MONITOR STATUS, AND DISPLAY ALARM SIGNALS FOR FLAME FAILURE AND LOW WATER ALARM. UPON A BOILER FAILURE ALARM, FLAME FAILURE ALARM, OR LOW WATER ALARM, THE RESPECTIVE BOILER SHALL BE DE-ENERGIZED, THE NEXT BOILER IN THE LEAD/LAG SEQUENCE OF OPERATION SHALL
BE ENERGIZED, AND EACH ALARM SHALL BE COMMUNICATED TO THE BAS FOR ALARM/DISPLAY AT THE OPERATOR'S WORKSTATION.
BOILER MOUNTED CONTROLS (BY BOILER MANUFACTURER)
1. ALL CONTROLS SHALL BE LOCATED IN A HINGED LOCKING METAL CABINET WITH NEMA 1A ENCLOSURE AND NEOPRENE DUST SEAL. CONTROLS SHALL BE ELECTRONIC. ALL WIRING SHALL BE COLOR CODED. PROVIDE CONTROL TRANSFORMER, AND FUSING IN ACCORDANCE WITH ALL CODE REQUIREMENTS. PROVIDE DUAL ADJUSTABLE HIGH LIMITCONTROLS WITH ONE SET AT 190°F WITH MANUAL RESET AND ALARM CONTACT, AND ONE SET AT 180°F WITH AUTO RESET AFTER AN ADJUSTABLE DIFFERENTIAL; ADJUSTABLE, RESETTABLE OPERATING CONTROL (WITH INITIAL RESET SCHEDULE BETWEEN 140°F AND 100°F BASED ON OAT); AND LOW WATER CUT OFF DEVICE WITH MANUAL RESET.BURNER CONTROLS SHALL HAVE MINIMUM 5:1 TURNDOWN.
2. THE SEQUENCE OF BURNER OPERATION SHALL BE CONTROLLED BY A PROGRAMMING RELAY OF THE ELECTRONIC TYPE PROVIDING PRE-PURGE AND POST-PURGE CYCLES AND WITH FULL PROTECTION AGAINST FLAME FAILURE DURING BOTH IGNITION AND NORMAL BURNER OPERATING PERIODS. OPERATING OF THE PROGRAMMING RELAY SHALL BEGOVERNED BY EXCESS TEMPERATURE LIMIT SWITCH, AN ELECTRONIC FLAME FAILURE PROTECTION DEVICE AND THE LOW WATER CUT-OFF TO SHUT DOWN THE BOILER. AFTER THE SAFETY SHUTDOWN MANUAL RESET SHALL BE REQUIRED. THE BURNER BLOWER CONTROLS SHALL BE INTERLOCKED TO PREVENT BURNER OPERATION WITHOUT FORCEDDRAFT. MEANS SHALL BE PROVIDED FOR AUTOMATICALLY DELAYING BURNER OPERATION WHILE ALLOWING FAN TO SCAVENGE BOILER PASSES OF COMBUSTION GASES AFTER FLAME OR OTHER BURNER STOPPAGE. EACH BURNER SHALL BE PROVIDED WITH COMBUSTION AIR, FLUE DAMPER, AND ISOLATION VALVE OPEN/CLOSE CONTACTS AND ALARM.
REPORTING FUNCTIONS
1. HISTORIES/TRENDINGa. THE BAS SHALL PRINT OUT ANY TEMPERATURE OR DATA FROM ANY SENSOR OR DEFINED VARIABLE ON REQUEST OF OPERATOR. THIS SHALL BE PROVIDED FOR BOTH INDIVIDUAL BOILERS AND COMMON SENSORS.b. THE BAS SHALL BE PROGRAMMED TO RECORD HISTORIES OF ALL TEMPERATURES (BOILER WATER SUPPLY AND RETURN TEMPERATURES, HOT WATER SUPPLY AND RETURN TEMPERATURES, ETC.), STATUS, FLOW RATE, HOUR OF DAY, HOURS OF OPERATION ASSOCIATED WITH EACH PIECE OF EQUIPMENT. IN ADDITION, RECORD HISTORIES OF ANY
OTHER ITEM OVER ANY TIME PERIOD REQUESTED BY OPERATOR. COORDINATE WITH OWNER FOR INITIAL LIST OF HISTORY ITEMS.c. THE BAS SHALL PRINT OUT ALL CHANGES IN EQUIPMENT STATUS AS THEY OCCUR.d. INITIALLY THE BAS SHALL TREND AND LOG BOILER PLANT CAPACITY (FLOW AT FMT AND DIFFERENTIAL TEMPERATURE BETWEEN MATCHED SENSORS HWST AND HWRT), PUMP SPEED, REMOTE DPT READING, OAT, WHICH BOILERS ARE ON AND AT WHAT CAPACITY, ALONG WITH TIME OF DAY.
2. ALARMSa. ALARM MESSAGES SHALL BE DISPLAYED AND PRINTED AT THE OPERATORS WORKSTATION.b. IN ADDITION TO THE ALARMS PREVIOUSLY LISTED, ALL SENSORS AND VARIABLES SHALL BE CAPABLE OF HIGH/LOW ALARM POINTS. AS A MINIMUM, THE FOLLOWING SHALL BE ALARMED AFTER APPROPRIATE TIME DELAYS:
1) IF ANY PIECE OF EQUIPMENT IS INDICATED AS OFF WHEN IT SHOULD BE ON.2) IF HWST IS 10 DEGREES ABOVE OR BELOW THE SET POINT DURING HEATING CYCLE. IGNORE THIS ALARM IF CYCLE HAS JUST BEEN STARTED WITHIN 20 MINUTES.3) IF ANY PIECE OF EQUIPMENT IS ON THAT IS INDICATED AS OFF OR FAILS.
3. GRAPHICSa. PROVIDE OVERALL SYSTEM, INDIVIDUAL BOILER AND PUMP GRAPHICS WITH REAL TIME UPDATING OF CONDITIONS (STATUS, TEMPERATURES, FLOWS, ETC.).b. PROVIDE FLOW DIAGRAMS FOR EVERY SYSTEM WITH ALL INSTRUMENTATION AND DATA (IN SPECIFICATIONS).
USER INTERFACE
1. BAS CONTRACTOR SHALL PROVIDE PROGRAMMING TO PROVIDE A MENU ALLOWING THE OPERATOR TO EASILY OPEN ALL CONTROL VALVES CONNECTED TO THE HOT WATER SYSTEM ON A FLOOR BY FLOOR BASIS AND GLOBALLY (ALL VALVES) FOR USE DURING CLEANING/FLUSHING, TESTING AND BALANCING WORK, AND FOR AIR PURGING.
STAND-BY POWER
1. BOILERS, ALL BOILER CONTROLS, AND THE HW PUMPS SHALL BE ON STANDBY POWER AND SHALL AUTOMATICALLY RESTART AND OPERATE NORMALLY DURING A POWER FAILURE AFTER THE GENERATOR HAS STARTED.2. PROVIDE AUTOMATIC RE-START OF BOILER PLANT UPON RETURN TO NORMAL POWER.
HWRT
S/S
BST
HWP-1
HWP-2
BOILERCONTROLLERBY BOILERMANUFACTURER
ALM
WB-2
CAD
HWR
BOILER ROOM
DPT-1
REMOTE
BIV-3
S/S
S/S
COMMTO BAS
COUPON RACK
(5 GPM)
NOTE:1. ALL BOILER RELIEF VALVES SHALL BE PIPEDTO FLOOR DRAIN. COORDINATE LOCATION INFIELD.
OAT
NOTE:REFER TO DETAIL DRAWINGS FOR LOCATION AND QUANTITIES OFADDITIONAL TEMPERATURE SENSORS, GAUGES, FITTINGS, VALVES,AND PIPING SYSTEM APPURTENANCES.
BAS
BOILERS
HWS
CAP
S/S
ALM
WB-1
CAD
BIV-2
S/S
1-1/4" 10 GPM MINIMUM FLOW BYPASS
AUTOMATICAIR VENT
OAT
CAP FID FID
NC
POS POS
TYP.ET
HWP-3
CAP
S/S
ALM
WB-1
BIV-1
S/S
FID
NC
POS
TO UH'S LOOP
FROM UH'S LOOP
FROM ERU LOOP
FROM RADIANT FLOOR LOOP
TO ERU'S LOOP
TO RADIANT FLOORLOOP
HWP-4(SPARE)
NC
REMOTE1-1/4" 10 GPM MINIMUM FLOW BYPASS
REMOTE1-1/4" 10 GPM MINIMUM FLOW BYPASS
GENERAL
1.EACH EXHAUST FAN SHALL BE STARTED, STOPPED, AND CONTROLLED VIA DEDICATED FULLY PROGRAMMABLE DDC CONTROLLER AND SHALLBE CAPAPLE OF STAND-ALONE OPERATION SHOULD ONE FAN OR CONTROLLER FAIL. ALL SET POINTS SHALL BE ADJUSTABLE. ALL ACTUATORSSHALL BE ELECTRONIC. NO = NORMALLY (FAIL) OPEN ON LOSS OF POWER. NC = NORMALLY (FAIL) CLOSED ON LOSS OF POWER. VFD SHALLMODULATE FANSPEED TO MAINTAIN DUCT STATIC PRESSURE IN EACH OF THE 4 EXHAUST DUCTS AS DETERMINED BY BALANCER.
2.ALL SAFETIES SHALL BE ACTIVE IN BOTH "H" AND "A" POSITIONS OF THE FAN'S HAND-OFF-AUTOMATIC SWITCHES (H-O-A).
3.ALL TEMPERATURES LISTED ARE FAHRENHEIT.
4.ALL TEMPERATURE SENSORS IN THE UNIT AND DUCTWORK SHALL BE AVERAGING TYPE.
FAN CONTROL
1.THE LEAD EXHAUST FAN SHALL NORMALLY OPERATE CONTINUOUSLY.
2.WHILE AN EXHAUST FAN IS EITHER OFF ON SAFETY OR MANUAL DISCONNECT, THE ASSOCIATED OUTSIDE AIR AND FAN ISOLATION DAMPERS(OAD & FID) SHALL BE CLOSED.
3.WHEN AN EXHAUST FAN IS TO BE STARTED, THE FID SHALL OPEN AND THE FAN SHALL START AT MINIMUM SPEED.
4.THE EXHAUST FAN VFD SHALL SLOWLY INCREASE IN SPEED TO MAINTAIN HIGHEST SETPOINT OF ALL REMOTE EXHAUST DIFFERENTIALPRESSURE SENSORS (DPT) OF THE CURRENTLY RUNNING ERU'S AS DETERMINED BY BALANCER . INITIAL SETPOINT SHALL BE NEGATIVE 1.0"W.G. WITH FINAL SETPOINT DETERMINED BY THE BALANCING CONTRACTOR.
5.EACH ACTIVE FAN SHALL MAINTAIN A MINIMUM 3,000 FPM EXIT VELOCITY, BASED ON IT'S AIRFLOW MEASURING STATION (AFMS), BY SLOWLYMODULATING THE ASSOCIATED OAD OPEN AS REQUIRED.
6.THE LEAD AND STANDBY EXHAUST FANS SHALL BE ROTATED BIWEEKLY.
MAIN EXHAUST DAMPERS (TYP OF 8).
1.MAIN EXHAUST DAMPERS (MED) SHALL ALL MODULATE TO THE OPEN POSITION UPON THE START OF THE FAN. DAMPERS WILL THEN CLOSERESPECTIVELY UPON DETECTION OF UNOCCUPIED SPACES ASSOCIATED WITH THOSE DAMPERS.
2.WHILE A ROOM IS OCCUPIED AND THE ASSOCIATED ERU IS RUNNING THE MAIN EXHAUST DAMPER (MED) ASSOCIATED WITH THAT ERU SHALLMODULATE TO MAINTAIN THE FLOW AS PREVIOUSLY BALANCED. THE DUPLEX EXHAUST FAN SET SHALL MODULATE TO MAINTAIN THE CFMREQUIRED BY ALL ACTIVE ZONES AS TOTALED BY THEIR RESPECTIVE FLOW MEASURING STATIONS (FMS).
3.WHILE A ROOM IS UNOCCUPIED AND THE ASSOCIATED ERU IS OFF, THE MAIN EXHAUST DAMPER (MED) ASSOCIATED WITH THOSE SYSTEMSSHALL BE SHUT.
EXHAUST FAN FAILURE OR MAINTENANCE SHUTDOWN
1.IF THE LEAD EXHAUST FAN FAILS, STOPS ON A SAFETY TRIP, OR IS SHUTDOWN FOR ROUTINE MAINTENANCE, A STANDBY EXHAUST FAN SHALLBE STARTED AFTER IT'S EAD OPENS AND SHALL OPERATE UNDER NORMAL CONTROL.
SAFETIES
1.THE FOLLOWING SAFETY, WITH ITS OWN MANUAL RESET BUTTON, SHALL SHUT DOWN THE ASSOCIATED EXHAUST FAN BEFORE THE H-O-A.
a. WHEN THE PRESSURE AT STATIC PRESSURE LOW LIMIT (SPL) DROPS BELOW NEGATIVE 4 INCHES W.G.b. ON TOTAL FAILURE OF ALL ERU'S.
ALARMS
6.IF AN EXHAUST FAN FAILS OR IF ANY SAFETY IS TRIPPED, THE EXHAUST FAN'S CONTROLLER SHALL GIVE A DETAILED ALARM SIGNAL TO THEFRONT END.
STAND-BY POWER
1.UNIT AND ALL COMPONENTS AND CONTROLS SHALL BE WIRED TO STAND-BY POWER. PROVIDE AUTOMATIC RE-START UPON POWER FAILUREAND UPON RETURN TO NORMAL POWER.
EXHAUST AIR
OAD
EXHAUST AIR
NO
OUTDOOR AIR OUTDOOR AIR
NC
BUILDINGEXHAUST
REMOTE(TYP. OF 8)
NO
REMOTE(TYP. OF 8)
NO
NCNO
NCNO
OAD
EXHAUST AIR
NO
OUTDOOR AIR
NC
EXHAUST AIR
OUTDOOR AIR
NO
MED
(TYP. SEE FLOOR PLANS)
FROM FTR LOOP
FROM HEATING COIL LOOP
TO FTRLOOP
TO HEATING COIL LOOP
HWP-5
HWP-6
BALL VALVE(TYPICAL)
BLR01
NC
VFD
NC
NO
VFD VFDVFD
NC
1"
1"
6"
6"
4" 4"
4" 4"
6"
6"
6"
6"
6"
6"
4"
4"
6"
6"
FULL PORT, 3 WAY VALVE(TYP 3)
FRO
MERU
-1
FRO
MERU
-2
FRO
MERU
-3
FRO
MERU
-4
3"
1-1/2"
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:31:54 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-500
MECHANICAL CONTROLS I
ROCKY HILL
NO. Revision Description Date 10.28
ALM
S/S
S/S
ALM
VFDS
VFDSO
VFDS
VFDSO
DPT-1
S/S
ALM
VFDS
VFDSO
S/S
ALM
VFDS
VFDSO
DPT-2
DPT-3
RTCV
FMT-1
FMT-2
FMT-3
PIV-1
PIV-2
PIV-3
S/S
ALM
VFDS
VFDSO
FMT-5
DPT-5
S/S
ALM
VFDS
VFDSO
FMT-5
ES
ES
ES
DPT-6
AFMS
OAT
AFMSDAT
CO
HWV-1
HRLT
DPT
S/S
VFDSO
VFDS
ALM
ERBD
DPT OAD
SPL
SPH
HCLT
EAT
FDPS
FZ
EAD
OCC
HV
HWV
UHV
OAD
ACD
DPT
ACD
HV-1
HCV
GENERAL SUPPLY AIR HANDLING UNIT WITH HEAT-PLATE ENERGY RECOVERY CONTROL SEQUENCES (ERU-1,2,3,4) HEATING WATER PUMP CONTROL SEQUENCES
SUPPLY AIR
SUPPLYFAN
OUTDOOR AIRH
C
VFDSDET
ELEC
GENERAL
1. EACH AIR HANDLING UNIT SHALL BE STARTED, STOPPED, AND CONTROLLED VIA DEDICATED FULLY PROGRAMMABLE DDC CONTROLLER AND SHALL BE CAPAPLE OF STAND-ALONE OPERATION. UNITS SHALL OPERATE WHEN ASSOCIATED SPACES ARE EITHER OCCUPIED (AS DETERMINEDBY OCCUPANCY SENSORS [OCC] ), MANUAL OVER RIDE BY USER COMMAND, OR AT BUILDING SCHEDULED TIMES (ADJ.). ALL SET POINTS SHALL BE ADJUSTABLE. ALL ACTUATORS SHALL BE ELECTRONIC. NO = NORMALLY (FAIL) OPEN ON LOSS OF POWER. NC = NORMALLY (FAIL) CLOSEDON LOSS OF POWER.
2. ALL SAFETIES SHALL BE ACTIVE IN BOTH "H" AND "A" POSITIONS OF THE FAN'S HAND-OFF-AUTOMATIC SWITCHES (H-O-A).
3. ALL TEMPERATURES LISTED ARE FAHRENHEIT.
4. ALL TEMPERATURE SENSORS IN THE UNIT AND DUCTWORK SHALL BE AVERAGING TYPE.
FAN CONTROL
1. WHILE AN AHU IS EITHER OFF ON SAFETY OR MANUAL DISCONNECT, THE AHU SUPPLY FAN SHALL BE OFF WITH THE OUTSIDE AIR AND UNIT DISCHARGE AIR DAMPERS (OAD & EAD) CLOSED.
2. THE HEATING COIL CONTROL VALVE (HWV) SHALL ALWAYS (WHETHER THE AHU IS OFF OR ON) BE CONTROLLED BY THE HEATING COIL LEAVING AIR TEMPERATURE SENSOR (HCLT) TO MAINTAIN 70°F LEAVING AIR TEMPERATURE IN THE CASING.
3. WHEN AN AHU IS TO BE STARTED, THE OAD AND DAD SHALL OPEN AND THE SUPPLY FAN SHALL START AT MINIMUM SPEED AFTER PROOF OF DAMPER OPENING.
4. THE SUPPLY FAN VFD SHALL SLOWLY INCREASE IN SPEED TO MAINTAIN SETPOINT OF REMOTE SUPPLY DIFFERENTIAL PRESSURE SENSOR (DPT). INITIAL SETPOINT SHALL BE 1.0" W.G. WITH FINAL SETPOINT DETERMINED BY THE BALANCING CONTRACTOR TO BE AS LOW AS NEEDED TOPROVIDE FULL AIRFLOW TO THE FURTHEST DIFFUSER WITH THE OPPOSING BLADE DAMPERS AT LEAST 90% OPEN.
5. EVERY DPT SHALL HAVE ITS SETPOINT MET AT ALL TIMES.
HEATING CONTROL
1. UPON A DROP IN DISCHARGE AIR TEMPERATURE (AT DAT) BELOW THE DAT SET POINT OF 70°F, DAT SHALL MODULATE HEATING CONTROL VALVE TO MAINTAIN DAT SETPOINT AT 70-75°F (ADJ).
2. THE FIRST STAGE OF HEATING SHALL BE THE HEAT PLATE. WHEN OA IS COOLER THAN EXHAUST AIR TEMPERATURE AS MEASURED AT EXHAUST AIR TEMPERATURE SENSOR (EAT), HRLT SHALL MODULATE THE ENERGY RECOVERY BYPASS DAMPER (ERBD) CLOSED AS REQUIRED TOMAINTAIN SET POINT. WHEN ADDITIONAL HEATING IS NEEDED, ERBD SHALL REMAIN CLOSED AND THE HEATING COIL HEATING WATER VALVE (HWV) SHALL BE MODULATED OPEN AS REQUIRED. THE REVERSE SHALL OCCUR ON A RISE IN HCLT ABOVE HEATING SET POINT.
EXHAUST CONTROL DAMPER CONTROL1.SEE EXHAUST FAN SEQUENCES FOR EXHAUST CONTROL DAMPER (ECD) CONTROL
BYPASS MODE
1. WHEN THE OAT IS ABOVE 65°F (ADJ.) THE EXHAUST AIR DAMPER (EAD) SHALL SHUT AND THE ENERGY RECOVERY BYPASS DAMPER (ERBD) SHALL OPEN SIMULTANEOUSLY . THE REVERSE SHALL OCCUR UPON A DROP IN OUTDOOR AIR TEMPERATURE (OAT) BELOW 60°F (ADJ.). ONCETHE OAD'S IN THE BUILDING SPACES HAVE BEEN PROVED OPEN, THE SUPPLY FAN SHALL BE COMMANDED OFF, AND THE OAD FOR THE UNIT SHALL SHUT.
PURGE MODE
1. UPON A CO ALARM IN A SPACE SERVED BY AN ERU, THE ASSOCIATED ERU SHALL BE COMMANDED ON AND TO RUN AT MAXIMUM CAPACITY FOR AFFECTED ZONE . THE UNIT SHALL ALARM AT THE BMS AND UNIT SHALL AUTOMATICALLY RESET WHEN THE CO ALARM CEASES.
AHU FAILURE OR MAINTENANCE SHUTDOWN
1. IF ANY AHU FAILS, STOPS ON A SAFETY TRIP, OR IS SHUTDOWN FOR ROUTINE MAINTENANCE, THE REMAINING AHU'S SHALL RAMP UP IN SPEED (WITHIN 30 SECONDS) TO SUPPLY 100% OF THE REQUIRED AIRFLOW.
SAFETIES
1. THE FOLLOWING SAFETIES, EACH WITH ITS OWN MANUAL RESET BUTTON, SHALL SHUT DOWN THE AHU BEFORE THE H-O-A.
a. WHEN THE SMOKE DETECTOR (SDET) IS ACTIVATED.
b. WHEN THE PRESSURE AT STATIC PRESSURE HIGH LIMIT (SPH) RISES ABOVE 4 INCHES W.G.
c. WHEN THE PRESSURE AT STATIC PRESSURE LOW LIMIT (SPL) DROPS BELOW NEGATIVE 4 INCHES W.G.
d. ON TOTAL FAILURE OF PRIMARY EXHAUST SYSTEM, AHU SHALL SHUT DOWN.
ALARMS
1. IF THE SUPPLY FAN FAILS OR IF ANY UNIT SAFETY IS TRIPPED, THE AHU CONTROLLER SHALL GIVE A DETAILED ALARM SIGNAL TO THE FRONT END.
2. IF, FOR 10 MINUTES, A PRE-FILTER PRESSURE DROP EXCEEDS SET POINT (INITIALLY 0.6") OR THE FINAL-FILTER PRESSURE DROP EXCEEDS SET POINT (INITIALLY 1.0"), THE AHU CONTROLLER SHALL GIVE A DETAILED ALARM SIGNAL TO THE FRONT END.3. IF THE OUTDOOR AIR TEMPERATURE IS BELOW 35°F, UPON FAILURE OF BOILER PLANT OR HWP-2, AN ALARM SHALL BE SENT TO THE FRONT END. THE UNITS SHALL ENTER STANDBY MODE AND THE OUTDOOR AIR DAMPER (OAD) AND EXHAUST AIR DAMPER (EAD) SHALL BE SHUT.
STAND-BY POWER
1. UNIT FAN AND CONTROLS SHALL BE WIRED TO STAND-BY POWER. PROVIDE RE-START UPON POWER FAILURE AS INDICATED IN EMERGENCY OPERATION CONTROL SEQUENCES AND UPON RETURN TO NORMAL POWER.
ERU
HWP-1
HWP-2
HWR
REMOTE1 1/4" 10 GPM MINIMUM FLOW BYPASS
HWP-3
TO UH'S LOOP
FROM UH'S LOOP
FROM ERU LOOP
FROM RADIANTFLOOR LOOP
TO ERU'S LOOP
TO RADIANTFLOOR LOOP
HWP-4(SPARE)
REMOTE
REMOTE
RWT
GENERAL1. EACH PUMP SHALL BE STARTED, STOPPED, AND CONTROLLED VIA DEDICATED FULLY PROGRAMMABLE DDC CONTROLLER AND SHALL BE CAPABLE OF STAND-ALONE OPERATION. ALL SET POINTS SHALL BE ADJUSTABLE.
ALL ACTUATORS SHALL BE ELECTRONIC. NO = NORMALLY (FAIL) OPEN ON LOSS OF POWER. NC = NORMALLY (FAIL) CLOSED ON LOSS OF POWER.2. ALL SAFETIES SHALL BE ACTIVE IN BOTH "H" AND "A" POSITIONS OF THE HAND-OFF-AUTOMATIC SWITCHES (H-O-A).3. ALL TEMPERATURE SENSORS SHALL BE AVERAGING TYPE.
UNIT HEATER LOOPS PUMP CONTROLS (HWP-1)1. UPON A CALL FOR HEAT BY ANY UNIT HEATER CONTROL VALVE (UHV), HWP-1 SHALL START ONCE END SWITCH (ES) IS PROVEN OPEN.2. PUMP SHALL MODULATE ITS VFD TO MAINTAIN BALANCED DESIGN SETPOINT AT REMOTE DIFFERENTIAL PRESSURE SENSORS (DPT-1) LOCATED ON THE FURTHEST RUN OF EQUIPMENT.3. UPON PUMP FAILURE, AN ALARM SHALL BE SENT TO THE BMS.4. IF FMT-1 READS ZERO FLOW AND ASSOCIATED PUMP IS LISTED AS RUNNING, AN ALARM SHALL BE SENT TO THE BMS AND THE PUMP SHALL SHUT DOWN.
ENERGY RECOVERY UNIT PUMP CONTROLS (HWP-2)1. UPON A CALL FOR HEAT BY ANY ERU HEATING WATER VALVE (HWV), HWP-2 SHALL START ONCE END SWITCH (ES) IS PROVEN OPEN.2. PUMP SHALL MODULATE ITS VFD TO MAINTAIN BALANCED DESIGN SETPOINT AT REMOTE DIFFERENTIAL PRESSURE SENSORS (DPT-2) LOCATED ON MEZZANINE ABOVE.3. UPON PUMP FAILURE, AN ALARM SHALL BE SENT TO THE BMS AND THE ERU'S SHALL ENTER STANDBY MODE.4. UPON FAILURE OF ALL ERU'S , PUMP SHALL ENTER STANDBY MODE.5. IF FMT-2 READS ZERO FLOW AND ASSOCIATED PUMP IS LISTED AS RUNNING, AN ALARM SHALL BE SENT TO THE BMS AND THE PUMP SHALL SHUT DOWN.
RADIANT FLOOR PUMP CONTROLS (HWP-3)1. UPON A CALL FOR HEAT BY ANY RADIANT FLOOR VALVE (RWV), HWP-3 SHALL START ONCE END SWITCH (ES) IS PROVEN OPEN.2. PUMP SHALL MODULATE ITS VFD TO MAINTAIN BALANCED DESIGN SETPOINT AT REMOTE DIFFERENTIAL PRESSURE SENSORS (DPT-3) LOCATED ON THE FURTHEST RUN OF EQUIPMENT.3. UPON PUMP FAILURE, AN ALARM SHALL BE SENT TO THE BMS AND THE ERU'S SHALL ENTER STANDBY MODE.4. RADIANT TEMPERATURE CONTROL VALVE SHALL MODULATE AS REQUIRED TO MAINTAIN 107° LEAVING WATER TEMPERATURE AS SENSED AT RADIANT WATER TEMPERATURE SENSOR (RWT).5. IF FMT-3 READS ZERO FLOW AND ASSOCIATED PUMP IS LISTED AS RUNNING, AN ALARM SHALL BE SENT TO THE BMS AND THE PUMP SHALL SHUT DOWN.
SPARE PUMP CONTROLS (HWP-4)1. UPON FAILURE OF ONE OTHER PUMP, THE 3-WAY, 2 POSITION PUMP ISOLATION VALVE (PIV) ASSOCIATED WITH THAT PUMP SHALL SWITCH THE NORMALLY OPEN AND NORMALLY CLOSED SIDES OF THE VALVE. THE SPARE
PUMP (HWP-4) SHALL THEN START. THIS SEQUENCE SHALL SEND A NOTIFICATION TO THE BMS AND SHALL BE FULLY REVERSIBLE ON USER COMMAND.2. PUMP SHALL MODULATE ITS VFD TO MAINTAIN BALANCED DESIGN SETPOINT FOR THE SYSTEM BEING BACKED UP AT REMOTE DIFFERENTIAL PRESSURE SENSOR (DPT) LOCATED ON THE FURTHEST RUN OF EQUIPMENT.3. UPON PUMP FAILURE, AN ALARM SHALL BE SENT TO THE BMS.4. IF THE ASSOCIATED SYSTEM'S FMS READS ZERO FLOW AND ASSOCIATED PUMP IS LISTED AS RUNNING, AN ALARM SHALL BE SENT TO THE BMS AND THE PUMP SHALL SHUT DOWN.
FIN TUBE RADIATION (FTR) PUMP CONTROLS (HWP-5)1. UPON A CALL FOR HEAT BY ANY FTR ZONE VALVE (HV-1), HWP-5 SHALL START.2. PUMP SHALL MODULATE ITS VFD TO MAINTAIN BALANCED DESIGN SETPOINT AT REMOTE DIFFERENTIAL PRESSURE SENSORS (DPT-5) LOCATED ON THE FURTHEST RUN OF EQUIPMENT.3. UPON PUMP FAILURE, AN ALARM SHALL BE SENT TO THE BMS.4. IF FMT-5 READS ZERO FLOW AND ASSOCIATED PUMP IS LISTED AS RUNNING, AN ALARM SHALL BE SENT TO THE BMS. AND THE PUMP SHALL SHUT DOWN.
HEATING COIL PUMP CONTROLS (HWP-6)1. UPON A CALL FOR HEAT BY HEATING COIL VALVE (HCV), HWP-6 SHALL START.2. PUMP SHALL MODULATE ITS VFD TO MAINTAIN BALANCED DESIGN SETPOINT AT REMOTE DIFFERENTIAL PRESSURE SENSORS (DPT-6) LOCATED ON THE FURTHEST RUN OF EQUIPMENT.3. UPON PUMP FAILURE, AN ALARM SHALL BE SENT TO THE BMS.4. IF FMT-6 READS ZERO FLOW AND ASSOCIATED PUMP IS LISTED AS RUNNING, AN ALARM SHALL BE SENT TO THE BMS. AND THE PUMP SHALL SHUT DOWN.
ALARMS
1. PROVIDE ALARM ON FAILURE TO MEET SETPOINT FOR 10 MINUTES OR ANY EQUIPMENT FAILURE.
TO BOILERS
FROM BOILERS
NC
NC
NC
1 1/4" 10 GPM MINIMUM FLOW BYPASS
1 1/4" 10 GPM MINIMUM FLOW BYPASS
SDET
ELEC
HWP-5
TO FTR LOOP
FROM FTR LOOP
REMOTE1 1/4" 10 GPM MINIMUM FLOW BYPASS
NC
HWP-5
FROM HEATINGCOIL LOOP
TO HEATING COILLOOP
NC
REMOTEHEAT PLATE
ENERGYRECOVERY
BUILDING HWS
HWHEATING
COILFILTER
TOEXHAUST
FAN
FILTERS
EXHAUST ACD'S ANDDPT'S PER AREA ATMIDPOINT OF EACHMAIN.)
FROM BUILDINGEXHAUST
(SUPPLY ACD'S ANDDPT'S PER AREA ATMIDPOINT OF EACHMAIN.)
BUILDING OAD'S (SEEDETAIL HC503)
VFD
VFD
HWC01
VFD
VFD
NCNO
NCNO
NCNO
VFD
VFD
6"
6"
6"
6"
6"
6"
6"
X"
X"
X" X"
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:31:55 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-501
MECHANICAL CONTROLS II
ROCKY HILL
NO. Revision Description Date 10.29
ON/OFF
AFMSECD
ACD
MED
SAD
OCC
AFMS
LEL
S/S
CT
OAD
S/S
S/S
HEATER (UH)SEQUENCE OF OPERATION
VENTILATION FAN (VF)CONTROL SEQUENCES
HEATER (CUH)SEQUENCE OF OPERATION
EXHAUST SYSTEMS SEQUENCE OF OPERATION(CNG INSPECTION, LUBE BAYS, WELDING, MAIN REPAIR BAYS, AERIAL BUCKET)
VF-7 SEQUENCE OF OPERATION RADIANT FLOOR CONTROLSSEQUENCES
6" HOSE
6" HOSE
16"
T
RADIANT FLOOR HEATING SYSTEMBY MANUFACTURER
BMS
NC
RADIANT FLOOR SLABTEMPERATURE SENSOR
LOCATED 5' FROMPERIMETER, 3" BELOW TOP
OF SLAB OR ASPRESCRIBED BYMANUFACTURER
HV
CONTROLLER
TR
S/SSTARTER
STA
RTE
R
OAT
LEL
BY ELEC(CNG INSP. ONLY)
BMS
HWST
HWRT
BY CONTROLSMANUFACTURER
OAT
OVERRIDE
DOOR INTERLOCK
TSNO
HV
TR
S/SSTARTER
ON/OFF
GED
EXHAUST HOSE REEL WITH FANON/OFF SWITCH AND SPRING
RETRACTION. PROVIDE WITH 33'HIGH TEMPERATURE HOSE.
BDD
STARTER
ON/OFF
VD VD
BGD
TO OUTDOORS. PROVIDEBIRD AND INSECTSCREEN ATTERMINATION POINT.(SEE FLOOR PLANS FORARRANGEMENTS OFSIDEWALL TERMINATIONTHRU LOUVER ORGOOSENECK W/WMSTHRU ROOF)
VED
BY ELEC
BY ELEC
ON/OFF24 X 24 SMOKE/FIREDAMPER AND TRANSFERDUCT WITH WMS
VF-17 (SEE MECHANICALSCHEDULES FORFURTHER DETAILS)
FD
TR
STARTER
ON/OFF
WELD EXHAUST ARM (WEA)
(CNG BAY ONLY)
FCUV-1
GENERAL1. RADIANT FLOOR HEATING SHALL BE CONTROLLED BY AN APPLICATION SPECIFIC
CONTROLLER (ASC). COORDINATE OCCUPIED/UNOCCUPIED SCHEDULES WITHOWNER. ALL SETPOINTS SHALL BE ADJUSTABLE. ALL ACTUATORS SHALL BEELECTRONIC.
2. ALL TEMPERATURES LISTED ARE FAHRENHEIT AND SHALL BE ADJUSTABLE.3. MANIFOLD SHALL BE BALANCED TO PROVIDE FOR EVEN FLOW THROUGH EACH
INDIVIDUAL PIPE RUN.4. RADIANT HEATING SHALL BE LOCKED OUT DURING VENTILATION FAN OPERATION
ABOVE 65°F (ADJ) OUTDOOR AIR TEMPERATURE.
CONTROL VALVE CONTROL1. CONTROL VALVE SHALL MODULATE OPEN TO MAINTAIN SLAB TEMPERATURE
SETPOINT (ADJ.). INITIALLY THE SLAB TEMPERATURE SHALL BE SET MAINTAIN 70°FWHEN THE OUTDOOR AIR IS BELOW 54°F. AT OUTDOOR AIR TEMPERATURES ABOVE55°F THE VALVE SHALL BE SHUT AND CIRCULATING PUMP (HWP-3) SHALL BE OFF.
2. CONTROL VALVE SHALL MODULATE OPEN WHEN COMMANDED BY SLAB TEMPERATURESENSOR PROVIDED EXCLUSIVELY FOR RADIANT FLOORING OR BY BAS SETPOINTDEPENDENT ON OUTDOOR AIR TEMPERATURE (OAT) WITH AN INITIAL SET POINT OF54°F (ADJ.) OR BY LOCAL OVERRIDE.
GENERAL:
1. THE HEATER FAN SHALL BE CONTROLLED BY A SPACETEMPERATURE SENSOR (WHERE INDICATED ON PLANS).
2. THE HEATER SHALL BE CONNECTED INTO THE BUILDINGAUTOMATION SYSTEM (BAS) FOR ALARMS. ALARMNOTIFICATIONS SHALL BE SENT TO BAS IF THE EQUIPMENTFAILS OR IF TEMPERATURE FALLS BELOW 50°F FOR 10MINUTES.
3. PROVIDE HARDWARE, WIRING, PROGRAMMING, ANDGRAPHICS TO THE BUILDING BAS.
4. WHERE APPLICABLE THE HEATER SPACE TEMPERATURESENSOR CAN ALSO CONTROL RADIANT FLOOR HEATING.
5. UNIT HEATERS AND RADIANT HEATING SHALL BE LOCKEDOUT DURING VENTILATION FAN OPERATION ABOVE 65°FOUTDOOR AIR TEMPERATURE.
SEQUENCE:
1. ON A CALL FOR HEATING FROM SPACE TEMPERATURESENSOR (60°F), THE TEMPERATURE SENSOR SHALL:
HOT WATER UNITS :
1. THE FAN SHALL BE TURNED ON TO MAINTAIN SPACETEMPERATURE SETTING WITH AN ADJUSTABLE 3°FDIFFERENTIAL.
2. THE REVERSE SHALL OCCUR UPON A RISE INTEMPERATURE
3. UPON AN ASSOCIATED GARAGE DOOR BEING OPEN FOR10 MINS (ADJ). THE BMS SHALL SHUT THE UH FAN OFF.UPON GARAGE DOOR BEING CLOSED THE UH FAN SHALLRESET TO NORMAL OPERATION. THIS SHALL BE TYPICAL OFALL AREAS EXCEPT THE MAIN REPAIR BAYS WHERE UH FANSWILL RUN CONSTANTLY OFF OF SPACE TEMPERATURE.
4. CNG BAY ONLY - UPON ACTIVATION OF LEL ALL UH'S INCNG BAY SHALL SHUT DOWN.
HC801
EXHAUST AIR
VF
HC503
VENTILATION FAN - SEQUENCE OF OPERATION
FAN CONTROLS
1. FAN SYSTEM SHALL BE CONTROLLED BY THE DDC SYSTEM OR ROOMMOUNTED ON/OFF SWITCH.
2. PROVIDE FAN FAILURE ALARM (CT) AND HIGH TEMP ALARM AT 104°F(FOR 10 MINUTES).
3. DAMPER SHALL BE RUSKIN CD51 LOW-LEAKAGE TYPE, OR APPROVEDEQUAL.
4. UNIT HEATERS AND RADIANT HEATING SHALL BE LOCKED OUT DURINGVENTILATION FAN OPERATION ABOVE 65°F OUTDOOR AIR TEMPERATURE.
5. LOCAL ROOM MOUNTED ON/OFF SWITCH SHALL ALLOW USER TO TURNFAN ON. WHEN SWITCH IS IN THE ON POSITION OR GARAGE DOOR BEINGOPENED, THE OAD SHALL OPEN AND THE VF SHALL START. UPON SWITCHBEING IN THE OFF POSITION THE REVERSE SHALL OCCUR.
6. EACH FAN SHALL BE TIED TO A DOOR INTERLOCK. WHEN THEASSOCIATED DOOR IS OPEN, THE FAN SHALL BE ON. THE FAN SHALL BEOFF WHEN THE DOOR IS CLOSED.
7. (CNG INSPECTION BAY ONLY) UPON LEL DETECTION. OAD SHALL OPENAND VF SHALL RUN AT FULL SPEED UNTIL LEL IS SILENCED OR MANUALLYOVERRIDDEN.
GENERAL:
1. THE HEATER SHALL BE CONTROLLED BY ASPACE TEMPERATURE SENSOR (WHEREINDICATED ON PLANS).
2. THE HEATER SHALL BE CONNECTED INTOTHE BUILDING AUTOMATION SYSTEM (BAS)FOR ALARMS. ALARM NOTIFICATIONS SHALLBE SENT TO BAS IF THE EQUIPMENT FAILSOR IF TEMPERATURE FALLS BELOW 50°F FOR10 MINUTES.
3. PROVIDE HARDWARE, WIRING,PROGRAMMING, AND GRAPHICS TO THEBUILDING BAS.
SEQUENCE:
1. ON A CALL FOR HEATING FROM SPACETEMPERATURE SENSOR (60°F), THETEMPERATURE SENSOR SHALL:
HOT WATER UNITS : OPEN THE HEATING VALVE(HV). UPON PROOF OF HOT WATER FLOW ASSENSED BY A TEMPERATURE SENSOR (TS)SET AT 90°F, THE FAN SHALL BE TURNED ONTO MAINTAIN SPACE TEMPERATURE SETTINGWITH AN ADJUSTABLE 3°F DIFFERENTIAL.
2. THE REVERSE SHALL OCCUR UPON A RISEIN TEMPERATURE
HC802
VES FAN
600 CFM 600 CFM
(200/600) CFM
(1,400 CFM)
HOSE REELS AND VES FANS
1. WHEN BOTH HOSE REELS ARE RETRACTED THE VES FAN SHALL BEOFF.
2. WHILE EITHER HOSE REEL IS IN USE, FAN SHALL BE COMMANDEDON TO RUN AT BALANCED VALUE OF 1400 CFM.
3. COUNTER BALANCED BACKDRAFT DAMPER (BDD) SHALL BEBALANCED FOR NO MORE THAN 200 CFM LEAKAGE WHILE THE VESFAN IS RUNNING AND BOTH VES HOSE REELS ARE EXHAUSTING 600CFM EACH. THE BACKDRAFT DAMPER SHALL PROVIDE 600 CFM OF AIRWHILE ONLY ONE ASSOCIATED EXHAUST HOSE IS IN USE.
4. PROVIDE HARDWARE, WIRING, PROGRAMMING, AND GRAPHICS TOTHE BUILDING BAS.
5. THE BLAST GATE DAMPER (BGD) SHALL BE MANUALLY BALANCEDTO ENSURE THE PRESSURE AT POINT 1 IS ALWAYS NEGATIVE.
GENERAL EXHAUST DAMPER (GED)
1. THE GENERAL EXHAUST DAMPER (GED) SHALL BE INITIALLYBALANCED FOR FULL GENERAL EXHAUST FLOW (AS SHOWN ON THEFLOOR PLANS) WITH ALL ASSOCIATED VES AND EHF FANS IN THEOFF POSITION.
2. UNDER NORMAL OPERATION THE AIR FLOW MEASURING STATION(AFMS) SHALL MODULATE THE GENERAL EXHAUST DAMPER (GED) TOMAINTAIN THE CFM GENERAL EXHAUST FLOW (WHICH WAS INITIALLYBALANCED AS DESCRIBED ABOVE), LESS THE ANY/ALL (SEE FLOORPLANS FOR SPECIFIC CASE) OF THE FOLLOWING TOTALS: 1)OPERATING VEHICLE EXHAUST SYSTEM (VES) 2) CONSTANT VOLUMEWELDING HOODS 3) EXHAUST HOOD FAN (EHF). IN THE MAIN REPAIRBAY, THE EXHAUST AIR FLOW FROM THE MAIN REPAIR BAY SHALL BEOBTAINED BY TAKING THE AFMS READING IN THAT ZONE LESS ALLOTHER EXHAUST ZONES CURRENTLY IN OPERATION ON THE SAMEEXHAUST MAIN.
3. PROVIDE HARDWARE, WIRING, PROGRAMMING, AND GRAPHICS TOTHE BUILDING BAS.
VES01
POINT
BDD
ACD AND ECD
1. ACD SHALL BE NORMALLY OPEN. ECD SHALL BE NORMALLY CLOSED.
2. UPON FAILURE OR SHUTDOWN OF THE MAIN EXHAUST FANS, EMERGENCYCONTROL DAMPER (ECD) SHALL OPEN, AUTOMATIC CONTROL DAMPER (ACD)SHALL SHUT. UPON MAIN EXHAUST FAN RE-START, DAMPERS SHALL RESUMENORMAL OPERATION.
3. WHILE THE LOCAL VENTILATION FAN (VF) IS IN OPERATION THE ACDSHALL BE SHUT, AND ECD SHALL BE OPEN.
MED - MAIN EXHAUST DAMPER
1. WHILE ASSOCIATED VENTILATION FAN (VF) IS IN OPERATION, OR THEZONE IS UNOCCUPIED AS DETERMINED BY OCCUPANCY SENSOR (OCC) THEMAIN EXHAUST DAMPER (MED) SHALL BE SHUT.
SAD - SUPPLY AIR DAMPER
1. WHILE ASSOCIATED VENTILATION FAN (VF) IS IN OPERATION, OR THEZONE IS UNOCCUPIED AS DETERMINED BY OCCUPANCY SENSOR (OCC) THESUPPLY AIR DAMPER (SUPPLY AIR) SHALL BE SHUT.
2. UPON A ZONE BECOMING ACTIVE DUE TO OCCUPANCY OR NORMALSCHEDULING, SAD SHALL MODULATE OPEN. AFMS SHALL MODULATE SAD TOMAINTAIN BALANCED AIRFLOW FOR THE ZONE AFFECTED.
VED - VEHICLE EXHAUST DAMPER (MAIN REPAIR BAY ONLY)
1. WHILE THE VEHICLE EXHAUST SYSTEMS ARE NOT IN OPERATION, THEVEHICLE EXHAUST DAMPER SHALL BE SHUT.
2. IF A VEHICLE EXHAUST SYSTEM FAN IS ON, AND THE ASSOCIATED ECD ISSHUT, VED SHALL MODULATE OPEN.
LOWER EXPLOSIVE LIMIT (LEL) SEQUENCE (CNG BAY ONLY)
1. UPON LEL DETECTION. ASSOCIATED MED SHALL OPEN FULLY, AND SADSHALL OPEN FULLY. ERU'S AND MAIN EXHAUST FANS SHALLPROVIDE/EVACUATE PURGE AIR AT ROOM BALANCE VALUE UNTIL LEL HASBEEN SILENCED.
(REPAIR BAY ONLY)
TO ERU'S TO ERU'S
FROM ERU'SSUPPLY DUCT
EXHAUST DUCT
GENERAL:
1. THE FAN SHALL BE CONTROLLABLE BY ROOM LOCAL ON/OFF SWITCH, BMS,OR T-STAT.
CONTROLS SEQUENCE
1. IF TR IS GREATER THAN 70 DEGREES. FAN SHALL RUN.2. UPON A DROP IN TEMPERATURE BELOW TR SET POINT. FAN SHALL TURN OFF.3. UPON FAILURE TO START, AN ALARM SHALL BE SENT TO THE FRONT END.
HC803
EHF FAN(600 CFM)
(600 CFM)
D
1
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:31:57 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-502
MECHANICAL CONTROLS III
ROCKY HILL
NO. Revision Description Date 10.30
LV5
C
C
DAT
STARTER
NC
EF
TOILETEXHAUST
RTU"AIM" BLADES AT EACH
OTHER FOR BETTERMIXING
ELECSDET
UNITCONDENSING
STARTER
BDD (ADJUSTABLE)
AIRRELIEF
AIR
RETURN
NO
OUTDOORAIR
FILTER SUPPLYAIR
SUPPLYFAN
NC.
LOCATED
INDOORS
SPACE CO 2 SENSOR (TYPICAL)
ELECSDET
ROOFTOP UNIT CONTROL SEQUENCES (CV, <15,000 CFM)
ROOF TOP UNIT CONTROLS
GENERAL
1. ROOFTOP UNIT AND EXHAUST FAN SHALL BE STARTED AND STOPPED VIA DDC CONTROLLER. COORDINATE OCCUPIED ANDUNOCCUPIED SCHEDULES WITH OWNER. ALL SETPOINTS SHALL BE ADJUSTABLE. ALL ACTUATORS SHALL BE ELECTRONIC.
2. LOCAL HAND-OFF-AUTOMATIC SWITCH (H-O-A) FOR FANS SHALL OVERRIDE DDC START/STOP (S/S) COMMANDS. ALLHARDWIRED SAFETIES SHALL BE ACTIVE IN BOTH "H" AND "A" POSITIONS.
3. ALL TEMPERATURES LISTED ARE FAHRENHEIT.
4. ALL TEMPERATURE SENSORS IN THE UNIT AND DUCTWORK SHALL BE AVERAGING TYPE EXCEPT FOR FREEZESTATS WHICHSHALL BE LOW POINT READING TYPE.
5. PROVIDE APPROPRIATE ANTI-RECYCLE TIME DELAYS AND SAFETIES ON COMPRESSOR AND GAS HEATER STAGING.
FAN CONTROL
1. WHILE IN UNOCCUPIED MODE (OR OFF ON SAFETY OR MANUAL DISCONNECT) THE SUPPLY AND EXHAUST FAN (EF) SHALL BEOFF WITH THE OUTSIDE AIR DAMPER (OAD) AND EXHAUST AIR DAMPER (EAD) CLOSED, THE CONDENSING UNIT AND GASHEATER OFF, AND THE RETURN AIR DAMPER (RAD) OPEN.
2. WHEN STARTED IN OCCUPIED MODE, THE SUPPLY FAN SHALL START IN RECIRCULATION MODE, THEN THE OAD AND RADSHALL OPEN TO THE MINIMUM OUTDOOR AIR POSITION AS CONTROLLED BY AIR FLOW MONITORING STATION (AFMS - SEECO2 CONTROL), THE EAD SHALL OPEN, AND THE EXHAUST FAN (EF) SHALL START.
OCCUPIED CARBON DIOXIDE CONTROL
1. THE ACTUAL MINIMUM OUTDOOR AIRFLOW SHALL VARY BETWEEN 40% AND 100% OF THE SCHEDULED MINIMUMOUTDOOR AIR VOLUME. NORMAL MINIMUM OUTDOOR AIR (OA) QUANTITY SHALL BE CONTROLLED BY THE OUTDOOR AIRAFMS TO 40% OF THE SCHEDULED MINIMUM OA. IF EITHER OF THE FOLLOWING OCCURS, THE OUTDOOR AIR AFMS SHALLSLOWLY MODULATE THE OAD AND RAD AS REQUIRED TO MAINTAIN THE MAXIMUM CO2 WITHIN 50 PPM OF THE LISTED LIMIT:
a. IF ANY VARIABLE OCCUPANCY SPACE CO2 SENSOR SERVEDBY THE UNIT RISES ABOVE THE LIMIT OF 1200 PPM FOR 5 MINUTES.
b. IF THE RETURN AIR CO2 LEVEL AT SENSOR (C) RISESABOVE LIMIT OF 1000 PPM.
OCCUPIED MODE
1. DURING OCCUPIED PERIODS, THE SUPPLY FAN SHALL RUN CONTINUOUSLY AND THE OUTSIDE AIR DAMPER SHALL OPEN TOMAINTAIN MINIMUM VENTILATION REQUIREMENTS UNLESS THE DEMAND VENTILATION OR ECONOMIZING SEQUENCES AREACTIVE. THE RETURN DAMPER WILL BE INVERSELY INTERLOCKED WITH THE OUTDOOR AIR DAMPER.
2. THE DX COOLING SHALL STAGE AND HOT WATER HEAT SHALL MODULATE TO MAINTAIN THE CURRENT DISCHARGE AIRTEMPERATURE SETPOINT COMPARED TO A SPACE SETPOINT AND THE AMOUNT OF HEAT OR COOL CALLS. IF ECONOMIZING ISENABLED THE OUTSIDE AIR DAMPER SHALL MODULATE TO MAINTAIN THE CURRENT DISCHARGE AIR TEMPERATURE SETPOINT.
3. THE SUPPLY AIR SENSOR SHALL MEASURE THE DRY BULB TEMPERATURE OF THE AIR LEAVING THE EVAPORATOR COIL WHILEECONOMIZING. WHEN ECONOMIZING IS ENABLED AND THE UNIT IS OPERATING IN THE COOLING IF THE OUTSIDE AIRENTHALPY RISES ABOVE THE ROOM AIR ENTHALPY THE ECONOMIZER SHALL BE POSITIONED TO PROVIDE MINIMUM OUTDOORAIRFLOW AND THE CONDENSING UNIT STAGED TO MAINTAIN ROOM COOLING SETPOINT TEMPERATURE. DAT SHALL LIMITSUPPLY AIR TO 48°F MINIMUM, DURING MECHANICAL COOLING.
4. THE TRACER SC WILL POLL THE SPACE SENSORS AND COMPARE THE TEMPERATURES WITH ITS INDIVIDUAL SETPOINTTEMPERATURES (ADJUSTABLE).
5. IF THE MAJORITY OF THE SPACE REQUIRES COOLING THE RTU WILL ENABLE THE D/X COOLING TO START. THE D/X COOLINGWILL REMAIN “ON” UNTIL THE SPACE SENSORS REACH SETPOINT, AT WHICH TIME THE RTU WILL CYCLE THE D/X COOLING TO“OFF”.
6. IF THE MAJORITY OF THE SPACE REQUIRES HEATING THE RTU WILL ENABLE THE HOT WATER HEATING COIL AND MODULATEHEATING COIL VALVE (HCV) AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMP (DAT). THE HEAT WILL REMAIN “ON” UNTILTHE SPACE SENSORS REACH SETPOINT, AT WHICH TIME THE RTU WILL CYCLE “OFF”.
OCCUPIED BYPASS:
1. THE BAS SHALL MONITOR THE STATUS OF THE “ON” AND “CANCEL” BUTTONS OF THE SPACE TEMPERATURE SENSORS.WHEN AN OCCUPIED BYPASS REQUEST IS RECEIVED FROM A SPACE SENSOR, THE UNIT SHALL TRANSITION FROM ITSCURRENT OCCUPANCY MODE TO OCCUPIED BYPASS MODE AND THE UNIT SHALL MAINTAIN THE SPACE TEMPERATURE TOTHE OCCUPIED SETPOINTS (ADJ.).
BYPASS DAMPER CONTROL
1. WHEN THE SUPPLY FAN IS ON, THE BYPASS DAMPER (BPD) WILL SLOWLY OPEN, AND MODULATE TO MAINTAIN THEPROPER DISCHARGE DUCT STATIC PRESSURE SETPOINT AS DETERMINED BY (DPS). DETERMINATION OF THE DISCHARGEDUCT STATIC PRESSURE SETPOINT WILL BE PER THE DISCHARGE DUCT STATIC PRESSURE SETPOINT SECTION OF THERTU SYSTEM LEVEL OPERATION SECTION OF THIS SEQUENCE.
UNOCCUPIED CONTROL
1. WHEN THE AVERAGE SPACE TEMPERATURE IS BELOW THE UNOCCUPIED HEATING SETPOINT OF 60.0 DEG. F (ADJ.) THESUPPLY FAN SHALL OPERATE, THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED AND THE HEATING COIL VALVE (HCV)SHALL BE ENABLED.
2. WHEN THE AVERAGE SPACE TEMPERATURE RISES ABOVE THE UNOCCUPIED HEATING SETPOINT OF 60.0 DEG. F (ADJ.)PLUS THE UNOCCUPIED DIFFERENTIAL OF 4.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL STOP AND THE HEATING COIL SHALLBE DISABLED.
3. WHEN THE AVERAGE SPACE TEMPERATURE IS ABOVE THE UNOCCUPIED COOLING SETPOINT OF 85.0 DEG. F (ADJ.) THESUPPLY FAN, THE OUTSIDE AIR DAMPER SHALL OPEN IF ECONOMIZING IS ENABLED AND REMAIN CLOSED IFECONOMIZING IS DISABLED AND THE DX COOLING SHALL BE ENABLED.
4. WHEN THE AVERAGE SPACE TEMPERATURE FALLS BELOW THE UNOCCUPIED COOLING SETPOINT OF 85.0 DEG. F (ADJ.)MINUS THE UNOCCUPIED DIFFERENTIAL OF 4.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL STOP, THE DX COOLING SHALL BEDISABLED AND THE OUTSIDE AIR DAMPER SHALL CLOSE.
WARM-UP CONTROL
1. DDC CONTROLLER SHALL PROVIDE OPTIMUM START CAPABILITY. IF SPACE TEMPERATURE IS BELOW 63°F, WARM-UPSHALL BE DONE WITH RAD OPEN, OAD CLOSED, AND GAS HEATER CONTROLLED BY DAT TO SUPPLY 90°F AIR. WHENROOM TEMPERATURE RISES ABOVE 69°F, OCCUPIED MODE SHALL START. EF SHALL REMAIN OFF WITH EAD CLOSED.
SAFETIES
1. IN ADDITION TO THE CO SAFETY SHOWN ABOVE ( FOR BUILDINGS WITH RESIDENTIAL UNITS), THE FOLLOWINGSAFETIES EACH WITH ITS OWN MANUAL RESET BUTTON, SHALL SHUT DOWN THE UNIT VIA HARDWARE BEFORE H-O-A.
a. ANY FREEZESTAT (FZ) SHALL SHUTDOWN THE UNIT WHENEVER THE TEMPERATURE IS LESS THAN 35°F.
b. WHEN ANY SMOKE DETECTOR (SDET) IS ACTIVATED THE UNIT SHALL SHUT DOWN.
ALARMS
1. IF EITHER THE SUPPLY OR EXHAUST FAN FAILS OR IF ANY SAFETY IS TRIPPED, THE DDC CONTROLLER SHALL GIVE ADETAILED ALARM SIGNAL TO THE FRONT END.
2. IF FILTER PRESSURE DROP EXCEEDS SETPOINT (INITIALLY 0.6") FOR 10 MINUTES, THE DDC CONTROLLER SHALL GIVE ADETAILED ALARM SIGNAL TO THE FRONT END.
S/S
CT
EAD
FDPSOAD
RAD
TR HR
S/S
CCLT
DAT
S/S
CT
OAT
OAH
FZ
C
AFMS
ALM
C
CO
HC002
OUTSIDEAIR
ACD
TOP OF BLOCK WALL OVER DOOR
BLOCK WALL
LOUVER
DUCTWORK
INDOORAIR
CONTROL NOTES:
1. ACD SHALL MODULATE AS REQUIRED TO MAINTAIN A DIFFERENTIAL PRESSURE OF +/- 0.05" W.C.BETWEEN INTERIOR AND EXTERIOR SPACES.
2. DAMPER SHALL BE RUSKIN CD51 LOW-LEAKAGE TYPE, OR APPROVED EQUAL.
DPT
AIR COMPRESSOR
ROOF
24" GREENHECK GRSR RELIEF WITHINSECT SCREEN
CONTROL NOTES:
1. UPON A RISE IN OUTDOOR AIR TEMPERATURE ABOVE 65°F BYP SHALL MODULATE CLOSED AND ACDSHALL OPEN.
2. T-STAT IN HALLWAY SHALL MODULATE DAMPERS TO MAINTAIN SPACE TEMPERATURE SET POINT.
3. WHILE AIR COMPRESSOR IS ON, EXHAUST FAN (EF-4) SHALL RUN AT BALANCED VALUE OF 3,000 CFM
4. WHEN PAINT EQUIP ROOM TEMP EXCEEDS 70°F (ADJ.) VENTILATION CONTROL DAMPER (VCD) SHALLOPEN. FAN SHALL RUN TO MAINTAIN TEMPERATURE SET POINT. UPON A DROP IN TEMPERATUREBELOW 70°F (ADJ). VCD SHALL SHUT AND FAN SHALL TURN OFF.
24"X24"
BY PAINT BOOTH VENDOR
24"X24"
HALL
ACD
BYP
PAINT EQUIP ROOM
500 CFM TYP. (3)
EF4
VF14
BDD VCD
PAD
SUPPLYAIR
NC NO
BASEBOARD RADIATION
VAV BOX WITH HW COIL, CO2, AND RADIATION CONTROL SEQUENCES
SEQUENCE OF OPERATION: VAV TERMINAL UNITSA. GENERAL1. BASEBOARD RADIATION SHALL BE FIRST MODE OF HEATING.2. A DDC VAV ZONE DAMPER CONTROLLER PER VAV TERMINAL UNIT WILL INDIVIDUALLY CONTROL THE
VAV ZONE DAMPER.3. THE BAS WILL PERFORM THE FOLLOWING VAV TERMINAL UNIT CONTROL STRATEGIES AND PROVIDE
THE POINTS AS LISTED ON THE DDC/VAV POINT LIST AND THE SPECIFIED MONITORING ANDDIAGNOSTICS.
a. GROUPING _ THE BAS WILL BE ABLE TO GROUP VAV BOXES VIA KEYBOARD COMMANDS. THESEGROUPS WILL MAKE IT POSSIBLE FOR THE OPERATOR TO SEND A COMMON COMMAND TO ALL BOXES IN AGROUP TO OPERATE IN THE SAME MODE. BAS WILL ALSO COMPILE ON A GROUP BASIS, THE FOLLOWING:
1. MINIMUM GROUP TEMPERATURE2. MAXIMUM GROUP TEMPERATURE3. AVERAGE GROUP TEMPERATURE
b. SETPOINT CONTROL _ THE BAS WILL EDIT THE ZONE SPACE TEMPERATURE SETPOINT OF EACH VAVBOX. INDIVIDUAL ZONE SETPOINT AND CONTROL LOGIC WILL RESIDE AT THE ZONE LEVEL, AND NOT BEDEPENDENT UPON THE BAS FOR CONTROL. IN THE EVENT OF COMMUNICATION LOSS, THE BOX WILLCONTINUE TO CONTROL TO DEFAULT SETPOINTS.
c. COOLING STAGES CONTROL _ THE BAS WILL CONTROL THE COOLING DAMPER TO A FULLY OPEN, FULLYCLOSED, MAXIMUM, OR MINIMUM POSITION BASED ON OPERATOR COMMANDS. THE OPERATOR WILL ALSOHAVE THE CAPABILITY TO ADJUST THE MAXIMUM & MINIMUM POSITIONS THROUGH THE BAS.
d. OPERATING MODE _ THE BAS WILL PLACE THE ZONE IN EITHER THE OCCUPIED OR UNOCCUPIED MODEBASED ON AN OPERATOR ADJUSTABLE TIME SCHEDULE. SEPARATE HEATING & COOLING SETPOINTS WILLBE ENTERABLE FOR EACH MODE THROUGH THE BAS. OTHER MODES AVAILABLE FOR SPECIALAPPLICATIONS WILL INCLUDE FULL OPEN OR FULL CLOSED.
e. CONTROL OFFSET _ THE BAS WILL BE CAPABLE OF OFFSETTING THE COOLING OR HEATING SETPOINTSOF ONE OR MORE GROUPS OF BOXES BY AN OPERATOR ADJUSTABLE AMOUNT. THIS CAPABILITY WILLALLOW FOR AUTOMATIC ZONE SETPOINT CHANGES BASED ON SYSTEM REQUIREMENTS, SUCH AS DEMANDLIMITING.
f. OVERRIDE BUTTON _ THE VAV ZONE WILL BE CAPABLE OF BEING PLACED IN THE "OCCUPIED" MODE BYPRESSING AN OVERRIDE BUTTON MOUNTED ON THE ZONE TEMPERATURE SENSOR. THIS IS TO ONLY BEON THE SENSOR FOR THE CLERK OFFICE 103.
h. ZONE STATUS REPORTS _ FOR EACH ZONE, THE BAS WILL PROVIDE AN OPERATING STATUS SUMMARYOF ALL UNIT SENSED VALUES (ZONE TEMPERATURE, ETC.), SETPOINTS, AND MODES.
i. ZONE GROUP REPORT _ FOR EACH GROUP OF VAV ZONES, THE BAS WILL REPORT THE GROUP MODE,DAMPER POSITION, AVERAGE ZONE TEMPERATURE, MINIMUM ZONE TEMPERATURE, AND MAXIMUM ZONETEMPERATURE. THE REPORT WILL ALSO DISPLAY FOR EACH TERMINAL UNIT IN THE GROUP THE PRESENTTEMPERATURE CONTROL SETPOINTS AND THE CURRENT ZONE TEMPERATURE.
4. ZONE SENSORSa. THE ZONE SENSOR WILL BE ACCURATE TO WITHIN 0.5 F. THE SENSOR WILL BE A PRODUCT OF THEVAV BOX CONTROLS MANUFACTURER AND DESIGNED SPECIFICALLY FOR THE INSTALLED CONTROLLER.
5. VAV ZONE DIAGNOSTICS.a. IF ZONE TEMPERATURE SENSOR INPUT FAILS ABOVE ITS HIGH RANGE, UNIT WILL CONTROL AT ITSMAXIMUM POSITION. IF SENSOR INPUT FAILS BELOW ITS LOW RANGE, UNIT WILL CONTROL TO ITSMINIMUM POSITION.
b. IN BOTH CASES, A DIAGNOSTIC MESSAGE WILL BE DISPLAYED UPON OPERATOR INQUIRY.c. IF POSITION INDICATION FAILS, DIAGNOSTIC MESSAGE WILL BE DISPLAYED UPON OPERATOR INQUIRY.a. IF ZONE TEMPERATURE SETPOINT POTENTIOMETER ON ZONE SENSOR FAILS, UNIT WILLAUTOMATICALLY CONTROL TO PROGRAMMED OCCUPIED SETPOINTS. DIAGNOSTIC MESSAGE WILL BEDISPLAYED UPON OPERATOR INQUIRY.
PAD
FMT
TR
HV-1
C
PRIMARYAIR
AFMS
LV6
24"X24"
HEATINGCOIL
NO
HWR
HWS
BPD
HCV
AFMSDPS
GENERAL:
TYPICAL FOR LV-1, 2,3,6 AND EF-3,EF-5,VF-13,VF-14
1. THE FAN SHALL BE CONTROLLED BY ROOM LOCAL ON/OFFSWITCH AND T-STAT.
ON/OFF
BDD
WRH TYPE GRAVITY VENTILATOR (SEEMECHANICAL SCHEDULES FORFURTHER DETAILS.)
EF/VF (SEE MECHANICALSCHEDULES FOR FURTHERDETAILS)
HC893
GENERATOR
GENERAL:1. REFER TO CONTROLS SEQUENCES ON PLUMBING, FIRE PROTECTION, HVAC, AND ELECTRICAL PLANS FOR ADDITIONAL
POINTS AND DETAILS. HVAC CONTROLS CONTRACTOR RESPONSIBLE FOR ALL HARDWARE AND SOFTWARE NECESSARYFOR MONITORING OF POINTS LISTED ABOVE AND IN CONTROLS SEQUENCES.
2. ALL POINTS SHALL MONITOR START, STOP AND STATUS.3. ALL POINTS SHALL BE TRENDABLE AND ACCESSIBLE THRU BAS.4. TERMS BAS - BUILDING AUTOMATION SYSTEM, AND BMS- BUILDING MANAGEMENT SYSTEM SHALL BE INTERCHANGEABLE
FAN VFD'S
RTU
UPS / PANELS
COMPRESSORS
BLOCK HEATERS
LEL/GAS DETECTION
EF'S
BAS
AIR COMPRESSOR
VAV BOXES
CONTROL VALVES
CONTROL DAMPERS
TOILET EXHAUST
OVERHEAD DOORS
UNIT HEATERS
PUMPS
PRESSURES/TEMPS
AIR DRYER
FIRE PUMP
DOM. HW CIRC. PUMPS
T-STAT
LOUVER 4 (LV-4) CONTROL DETAIL
VAV
VARIABLE AIR VOLUME BOX WITH HOTWATER HEATING COIL, CO2, ANDRADIATION CONTROL SEQUENCES
ROOFTOP UNIT CONTROL SEQUENCES (CV, <15,000 CFM)
PAINT EQUIP ROOM CONTROLS
GRAVITY VENTILATOR / EF / VF CONTROLSEQUENCE OF OPERATION
HC002
HC002
HC711
HC803ADDITIONAL BAS CONTROL POINTS
T
VD
T
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:31:58 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-503
MECHANICAL CONTROLS IV
ROCKY HILL
NO. Revision Description Date 10.31
MAX. OFFSET = 1"
RECTANGULAR DUCT
PLENUM
ROUND DUCT
FLEX CONN
R=DEPTH OF DUCT
R
MAX OFFSET = 1"
NOTES:1. THESE DETAILS ALLOW DUCTWORK TO BE PROVIDED BEFORE CEILING GRID IS INSTALLED THEN DIFFUSER/REGISTER CAN BE POSITIONED INTO GRID.2. PROVIDE INSULATED TRANSITION ROUND TO SQUARE IF REQUIRED AT DIFFUSER.3. PROVIDE NYLON TY-WRAP TOOL OR REUSABLE SS DRAW BAND PER SPECS.4. FLEX DUCT SHALL NOT HAVE MORE THAN 1/2" SAG PER FOOT.5. LENGTH OF FLEX DUCT SHALL NOT EXCEED 5'-0".6. PROVIDE DUCT MOUNTED VOLUME DAMPER WHENEVER POSSIBLE. TRY TO AVOID NECK DAMPERS.
MIN. HEIGHT =NECK SIZE + 2"
WITH 14" MAX HEIGHT
PLENUM LENGTH AND WIDTH = 2" MINIMUM GREATERTHAN NECK / COLLAR DIMENSION.
NOTES:- TYPE "C" CONNECTION MAY BE USED WHEN SPACE DOESNOT ALLOW TYPE "A" OR "B" CONNECTIONS.- BUCKLEY ASSOCIATES DIFFUSER CONNECTION BOOTTRANSITION DCBTR MAY BE USED.
NOTE:TYPE "B" CONNECTION MAY BE USEDWHEN SPACE DOES NOT ALLOW TYPE"A" CONNECTION.
TYPE "B" CONNECTION
TYPE "A" CONNECTION(PREFERRED)
FLEX CONN. REFER TOSPECS FORINSULATED TYPE
SUPPLY DIFFUSERREGISTER (TYP.)
TYPE "C" CONNECTION
HANGER
NOTES:ALL ROUND AND RECTANGULAR BELLMOUTH FITTINGS SHALL BE INCLUDED WITH THE FOLLOWINGSTANDARD FEATURES:
1. NEOPRENE GASKET TO MINIMIZE AIR LEAKAGE.2. PRE-DRILLED HOLES FOR QUICK MOUNTING.3. CONSTRUCTED OF HEAVY GALVANIZED STEEL.4. 26 GAUGE GALV. QUADRANT VOLUME DAMPER W/ TIGHT FITTING GASKETING TO MINIMIZE LEAKAGEAT DAMPER PIVOT POINTS. (FOR LOW PRESSURE DUCTWORK)
VD
STANDARD 45°RECTANGULAR TO ROUNDBOOT CONNECTIONMODEL 3300D
TAKE-OFFFITTING
* ALTERNATE
VD
AIR FLOWMODEL BMDBELLMOUTH
FITTING
* ALTERNATETAKE-OFF
W/ END FLAPS
VDVD
BENT OVER
MINI-BELLMOUTHCONNECTIONMODEL MBMD
TAKE-OFFFITTING
* ALTERNATE
OVAL-BELLMOUTHCONNECTIONMODEL OVBMD
TAKE-OFFFITTING
* ALTERNATE
8"7"
HEIGHTDUCT
8-1/2"8-1/2"8-1/2"
8"
12"10-1/2"
6"
SIZEDUCT
5"
10"9"8"7"
HEIGHTDUCT
10"10"10"10"
16"14"
10"10"
12"10"
5" x 10"
SIZEHOLE
6" x 12"6" x 12"
6-1/2" x 12"6-1/2" x 14"6-1/2" x 16"8-1/2" x 18"
10" x 20"
45° RECTANGULARTAKE-OFF
TAKE-OFF FITTING
ALTERNATE
VD
BRANCH
ALTERNATE
SIZEHOLE
6"5"
9"8"7"
9"
13"
11"
10"
SIZEDUCT
16"14"12"
7"
SIZEHOLE
6"
SIZEDUCT
5"
11"
9"
10"9"8"7"
DUCT
9"10"
HEIGHT
11"12"13"14"
16"14"18"
20"
16" 12"
HEIGHTDUCT
PREFERRED
MODEL RBMDMOUTH FITTING
TAKE-OFF FITTING
RECTANGULAR BELL
DUCTHEIGHT
7.5
MINIMUM
8.57.57.57.5
HOLESIZE
7.5 x 5.5
7.5 x 6.525.5 x 5.517.5 x 5.511.5 x 5.5
9.58.58.5
9.59.59.511.511.5
7.5 x 7.525.5 x 6.517.5 x 6.5
11.5 x 7.517.5 x 7.525.5 x 7.59.5 x 9.517.5 x 9.5
11.5 x 6.5 8.5
BRANCH
VD
PREFERRED
9"x 10-9/16"9"x 12-1/8"9"x 13-11/16"9"x 15-1/4"9"x 18-3/8"9"x 21-1/2"9"x 24-5/8"
* ALTERNATE FITTING'S TO BE USED WHEN DUCT HEIGHTDOES NOT PERMIT THE USE OF THE FULL SIZE BELLMOUTH
AIR FLOW
13.513.513.5
11.5 x 11.517.5 x 11.525.5 x 11.5
11.525.5 x 9.5
MINIMUM MINIMUM MINIMUM MINIMUM
PREFERREDTAKE-OFF
BELLMOUTHCONNECTION
FITTING
VD
MODEL BMD
SIZE
8"9"
5"
DUCTSIZE
6"7"8"9"10"
14"16"
12"
DUCTSIZE
6 x 410 x 416 x 424 x 46 x 5
16 x 524 x 56 x 610 x 6
16 x 88 x 824 x 616 x 6
10 x 5
16 x 1010 x 10
24 x 10
24 x 8
HOLE
10"11"12"13"15"17"19"
NOTES:1. ALL SUPPORTS SHALL BE GALVANIZED STEEL FOR STEELDUCT, STAINLESS STEEL FOR STAINLESS STEEL DUCT, ORALUMINUM FOR ALUMINUM DUCT.2. HANGERS MUST NOT DEFORM DUCT SHAPE.3. ATTACHEMENTS TO STRUCTURE SHALL BE PER SMACNA.
HANGER
HANGER STRAPS OR RODS
OVER 36" DIA.
HANGER RODSMAX.
SPACINGFEET
MAX. DUCT DIA.
10
10
10
10
ONE 1" x 22 GA. STRAP
ONE 1" x 18 GA. STRAP
TWO 3/8" DIA. RODS
TWO 1/2" DIA. RODS
20"
36"
60"
84"
MINIMUM16 GA.BAND
LOAD RATEDFASTENERS
BAND SAMESIZE ASHANGER STRAP
36" DIA.& UNDER
6"x6" OR 8"8"x6" OR 8"10"x8" OR 10"12"x10" OR 12"14"x12" OR 14"16"x14" OR 16"18"x16" OR 18"
MAIN RECTANGULAR
TYPICAL RECTANGULARSIZES OR EQUIVALENTUNLESS SHOWNDIFFERENTLY ON PLANS
CORRESPONDING
ROUND DUCT(VAV BOX NECK SIZE)
DUCT W
L
SEE TERMINAL ORFAN BOX DETAIL
(HSM021) FOR OPTIONS.
SEE DUCT TAKE-OFF DETAIL
16"14"12"10" 8" 6" 5"
TO TERMINAL BOX.LOCATE TRANSITION CLOSE
NOTE:THIS DETAIL HAS TO BE USED WHEN DISTANCE BETWEEN BOX AND TAKE-OFFEXCEEDS 10 FEET. FOR SHORTER DISTANCES USE BELLMOUTH TYPE FITTINGWITH DIAMETER TO MATCH BOX INLET. UTILIZE ROUND TO OVALTRANSITION WHEN BOX INLET IS OVAL.
PROVIDE EXTRA LENGTHTO AVOID "PINCHING"OF INSULATION ATCORNERS.
BUTT ENDS & SEAL
PROVIDE LOCKINGQUADRANT ARMSTANDOFF
NOTE:FOR HANGING DUCT: TRAPEZE DUCT OR STRAP HANGER AROUND DUCT COMPLETELY. DO NOT USE ANYSCREWS, BECAUSE THEY INTERFERE WITH DAMPER BLADE(S).
ROUND METAL DUCT HANGERS
TYPICAL DUCT TAKE-OFFTYPICAL SUPPLY DIFFUSER/ REGISTERDUCTWORK & CONNECTION
TYPICAL DUCT INSTALLATION & SUPPORTNEAR VOLUME DAMPERS TAKE-OFF TO TERMINAL BOX
RECTANGULAR DUCT
FLEX TO ROUND INLET
HSM017 HSM021
ALTERNATE ROUND BRANCH DUCT TAKE-OFFS
BRANCH DUCT TAKE-OFFALTERNATE RECTANGULAR
HAS008
HSM002HSM009
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:32:00 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-600
MECHANICAL DETAILS I
ROCKY HILL
NO. Revision Description Date 10.32
PT
MV
PT PT
PT
D D
D
(b)
(a)
SUPPLY
NOTES:1. FOR PIPING LARGER THAN 2" PROVIDE BUTTERFLY VALVESIN PLACE OF BALL VALVES.2. PROVIDE CONDENSATE DRAIN PAN AND DRAIN WITH TRAPFOR COOLING COILS.3. TWO FOOT LONG STAINLESS STEEL BRAIDED FIRERETARDANT HOSE KITS MAY BE USED (PRE-PIPED WITH ALLCOMPONENTS AS SHOWN) PROVIDING ALL COMPONENTSMEET THEIR INDIVIDUAL SPECIFICATION REQUIREMENTS.4. PROVIDE REDUCERS AS REQUIRED.
DOV W/HB
SEE NOTE 1
AIR FLOW
RETURNPIACV
18" MIN
OBD
MAIN
SIDEWALL GRILLE
DUCT BOOT
LOCKING NUTSUPPORT NUT
INSULATION
PIPE
NOTES:1. SEE SPECIFICATION FOR HANGER SIZES.2. PIPES 8" AND LARGER SHALL BE ROLLER SUPPORTED W/ DUAL RODS.3. FOR CHW SERVICE OVER 3", REPLACE SADDLE W/ 12" LONG, 14 GAUGE SHIELDW/ RIGID INSULATION BETWEEN THE PIPE AND SHIELD. PROTECT WITHCONTINUOUS VAPOR BARRIER.
NON-COMPRESSIBLERIGID INSULATIONAT SHIELD
GALVANIZEDINSULATIONSHIELD 12" LONG
HEAVY DUTY CLEVISHANGER(FOR 1/2" UP TO &INCLUDING 3" PIPE)
ADJUSTABLE HANGERW/ ROLLER(FOR 4" TO 6" PIPE)
PIPE COVERINGPROTECTION16 GA SADDLE
AV
COMPRESSION TANKDIAPHRAGM EXPANSION/
FLOOR MOUNTED
SEE NOTE 1
FLOOR
MAKE-UP SIZE (d)
TOTAL SYSTEMPUMP FLOW (GPM)
UP TO 200
201-500
501-1,200
1,201-3,000
3,001-5,000
5,001-12,000
d(INCHES)
1/2
3/4
1
1 1/4
1 1/2
2
3
5
10
20
30
60
PRV MIN.FLOW (GPM)
WITH HOSE BIBBDRAIN OUT VALVE
AV (LARGE CAPACITY)
N.C. P.O.S.
PREVENTERBACKFLOW
AIR SEPARATOR
TO 6" AFF
TO 6" AFF
COLDWATER
HOUSEKEEPINGPAD
SYSTEM RELIEF VALVE
MAKE-UP PRV
SEE NOTE 2 (TYP)
%%132" MIN
1"
RISER CLAMP
CONTINUOUS WELD
FIREPROOF MINERAL WOOL OROTHER APPROVED MATERIALFIREPROOF CAULK (TOP & BOTTOM)
STEEL SLEEVE(WITH ANCHORCOLLAR) WITH MINIMUM 1/4"ANNULAR GAP AROUND THEINNER PIPE
NOTE: SLEEVE MAY BE DELETEDIF HOLE IS CORE DRILLED.
RETURN FROM SYSTEM
SEE NOTE 3
NO DIRECT MAKE-UP WATER FORGLYCOL SYSTEMS. REFER TO GLYCOLCHARGING SYSTEM DETAIL (HPW005).
TO PUMP SUCTION
TANK RELIEF VALVE (FORCOLD WATER SYSTEMSONLY)
NOTES:
1. CONNECT TO SIDE OF MAIN TO PREVENT AIR OR DEBRISFROM ENTERING PIPE TO TANK. TOP OR BOTTOMCONNECTION NOT PERMITTED.
2. PROVIDE BUTTERFLY VALVES FOR 2-1/2" PIPES ANDLARGER; BALL VALVES FOR 2" PIPES AND SMALLER (SEESPECS).
3. FOR HOT WATER SYSTEMS, IF ELEVATION AT INLET TOTANK IS NOT BELOW MAIN BY 24", PROVIDE 24" TRAP TOPREVENT GRAVITY HEATING OF TANK.
PIPE HANGER SUPPORT
PIPE RISER SUPPORT DRAW THRU UNIT CONDENSATE TRAP
TYPICAL SIDEWALL SUPPLY/RETURN GRILLE
INLINE PUMP PIPING (EACH PUMP)
HC023SINGLE WATER COIL WITH 2-WAY
MODULATING PI AUTOMATIC CONTROL VALVE
H1201
NOTES:1. VALVES SHALL BE SAME SIZE AS PIPE, REDUCE TO PUMP CONNECTIONS ASREQUIRED.2. FOR PUMPS OVER 1/4 HP: PUMP & PIPE WITHIN 20' SHALL HAVE SPRING-ISOLATORSUPPORTS
3. SUBSTITUTE BUTTERFLY VALVES FOR BALL VALVES FOR PIPING GREATER THAN 2".
10 D STRAIGHT PROVIDE UNIONS FOR THREADEDPUMPS, FLANGES FOR FLANGED PUMPS.
-
NOTES:1. SEE FLOOR PLANS FOR BALANCING NOTES.
HAS001
d
HPW003FULL SIZE AIR SEPARATOR, MAKE-UP WATER &
DIAPHRAGM EXPANSION TANK FOR CLOSED LOOPWATER & GLYCOL SYSTEMS (UP TO 8" PIPING)
SCHEDULE 80 PIPE ONENOMINAL SIZE LARGERTHAN SLEEVE
HAS002 HPW010
THIS DIMENSION IN INCHES MUST BE 1"GREATER THAN THE MAXIMUM FAN SUCTIONSTATIC PRESSURE IN INCHES W.C. (WITHDIRTY FILTERS, COILS, AND MAXIMUM AIRFLOW).
FLOOR OR ROOF
AHU OR RTUOVERSIZED LOOSE CAP LOCATED LEVEL WITHTOP OF DRAIN PAN. PIPE BELOW CAP SHALLHAVE FOUR 1/2" DEEP "V" SHAPED GROOVES TOALLOW VISUAL OVERFLOW AND VENTFUNCTIONS.
DRAIN PAN
FOR INDOOR UNITS WITH PIPES 1 1/2" ANDLARGER, PROVIDE 11/2"HIGH AUXILIARY DRAINPAN UNDER TRAP WITH1/8"THICK NEOPRENEPAD ANDLEAK ALARM TO DDC SYSTEM
THIS DIMENSION IN INCHES MUST BE AT LEAST1/2 OF (a).
CLEANOUT(TYP)
HOUSEKEEPINGPAD, ROOF CURB,OR SUPPLEMENTALSTEEL (HEIGHT ASNEEDED FOR DRAINPIPING)
DRAIN PIPE TOMATCH DRAINOUTLET SIZE.
NOTE: OUTDOOR UNIT CONDENSATE DRAIN PIPING SHALL BE UV RESISTANT, ASTM D 1785 SCHEDULE 40 PVC WITH SOCKET TYPE FITTINGS AND SOLVENT/CEMENT JOINTS. EXTEND AT 1
4"/FOOT PITCH TO NEAREST DRAIN.
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:32:01 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-601
MECHANICAL DETAILS II
ROCKY HILL
NO. Revision Description Date 10.33
H213
HWR
AV
HWS
PT
PT PT
H703
6"
3/4"
1-1/2"
6"
3/4"
1-1/2"
4"
18" MIN
5'-0"3'-0"
H213
AV
HWS
PT
PT PT
24"
36"
12"
HPW007 HPW012
HPW011
???
????
???
????
AUTOMATIC AIR VENT ASSEMBLY CHEMICAL FEED (SHOT FEEDER) HOT WATER UNIT HEATER
HOT WATER CABINET HEATER
COUPON RACK WELD TABLE HOOD ELEVATIONS (NOT TO SCALE)
PT
SEE NOTE #1
DOV W/HB
CABINETHEATER
NOTE:1. REFER TO AUTOMATIC CONTROL DRAWINGS AND SPECIFICATIONS FOR
CONTROL VALVE REQUIREMENTS.2. TWO FOOT LONG STAINLESS STEEL BRAIDED FIRE RETARDANT HOSE KITS MAY
BE USED (PRE-PIPED WITH ALL COMPONENTS AS SHOWN) PROVIDING ALLCOMPONENTS MEET THEIR INDIVIDUAL SPECIFICATION REQUIREMENTS.
3. PROVIDE REDUCERS AS REQUIRED.4. FOR MULTIPLE ROW COILS, PIPE COIL COUNTER FLOW TO THE AIR FLOW
(WARMEST WATER LOCATED ON THE SIDE WITH WARMEST AIR)
STRAINERWITHBLOWDOWNVALVE
COILAIR FLOW
FRONT ELEVATION
STRUCTURE
FACE OF WALL
SIDE ELEVATION
NOTES:1. HOODS SHALL BE OF ALL WELDED STAINLESS STEELCONSTRUCTION.2. REFER TO ARCHITECTURAL DETAILS FOR FINISH DETAILING.3. CONFIRM HEIGHT ABOVE WELDING BENCH WITH OWNER.
18 GA. S.S.CANOPYHOUSING
DUCTCONNECTION
3/8" HANGROD AT38" O.C. MAX.
5/16" BOLTS &SHIELDS12 GA. 2" WIDECLIPS AT 18" O.C.
3/8" HANGRODAT 38" O.C. MAX.
18 GA. S.S.CANOPY HOUSING
STRUCTUREDUCT
CONNECTION
HWR MAIN
HWS MAIN
S.O. VALVE NEAR MAIN
SEE NOTE #1
DOV W/HB
HWR
UNITHEATER
NOTE:1. REFER TO AUTOMATIC CONTROL DRAWINGS AND SPECIFICATIONS FOR
ADDITIONAL INFORMATION.2. TWO FOOT LONG STAINLESS STEEL BRAIDED FIRE RETARDANT HOSE KITS MAY
BE USED (PRE-PIPED WITH ALL COMPONENTS AS SHOWN) PROVIDING ALLCOMPONENTS MEET THEIR INDIVIDUAL SPECIFICATION REQUIREMENTS.
3. PROVIDE REDUCERS AS REQUIRED.4. FOR MULTIPLE ROW COILS, PIPE COIL COUNTER FLOW TO THE AIR FLOW
(WARMEST WATER LOCATED ON THE SIDE WITH WARMEST AIR)
STRAINERWITHBLOWDOWNVALVE
COILAIR FLOW
HWR MAIN
HWS MAIN
S.O. VALVE NEAR MAIN
WELDING BENCH (BY OTHERS)
FIRE RETARDANT STRIPTYPE CURTAINS
WELDINGBENCH (BY
OTHERS)
FIRE RETARDANTSTRIP TYPECURTAINS
4 PIPE DIAMETERS (WITH 18"MAX)
HIGHEST POINT IN SYSTEM
REDUCER1/4" BRASS NIPPLE
1/4" GAGE COCK
FLOAT-TYPE AIR VENT
1/4" TUBE TO SCHRAEDER ADAPTER
1/4" TYPE "L" COPPER TUBE
NOTE:1. USE TFE TAPE ON ALL THREADED JOINTS.
SHUNT
RETURN
SUPPLYN.C.
5 GALLON SHOTFEEDER TANK OROTHER SIZE ASSPECIFIED ASMERATED
TO CHILLED ORHOT WATER RETURN
3/4"
FROM CHILLEDOR HOT WATERSUPPLY
3/4"
N.C.
BALL VALVE
1 X 1 TEE WITH PLUGGED ENDTYPICAL FOR 6RETURN MAIN
SUPPLY MAIN
NOTE:1. TYPICAL FOR COND. WATER, CHILLED WATER AND HOT WATER.LOCATE IN MECH ROOM AS INSTRUCTED BY CHEMICAL TREATMENTCONTRACTOR AND OWNER.
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:32:03 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-602
MECHANICAL DETAILS III
ROCKY HILL
NO. Revision Description Date 10.34
10
100908070
60
50
40
30
20
1
2
3
4
5
6
7891
20
30
40
50
60
708090100
10987
6
5
4
3
2
1
NO.1OF3
NO.2
OF3
NO.3
OF3
NO.2
OF2
NO.1OF2
NO.1OF1
PROVIDE CONTINUOUS HINGE
PROVIDE TWO LOCKS ON DOORS OVER 16"
PROVIDE INSULATED DOUBLE SKIN DOOR
PROVIDE FOAM GASKET SEALS
NOTE:REFER TO THE SPECIFICATION FORSIZE AND LOCATION OF ACCESSDOORS.
h = DUCT HEIGHTw = DUCT WIDTH
NO. OF VANES
EQUIVALENT DIAMETER = (w+h)/2
1233
WITHIN 2 EQUIV. DIA.:WHEN 2 ELBOWS ARENO. OF VANES
DEPICTED HERE:EXAMPLE AT LEFT IS
OF 3 VANES.NO. 2 VANE OF A TOTAL"NO. 2 OF 3" =
OF 3 VANES.NO. 1 VANE OF A TOTAL"NO. 1 OF 3" =
TERMINOLOGY:
= INSIDE RADIUS= CENTERLINE RADIUS
Rr
r/w = 0.5 IS A SQUARE THROAT ELBOW!
3210
FOR 1 ELBOW:
r/w >= 1.501.5 > r/w >= 0.700.7 > r/w >= 0.600.6 > r/w >= 0.55
HOWEVER, MINIMUM INSIDE RADIUS R SHOULD BE 2".NOTE:
r/w RATIO:
RADIUS ELBOW AND SPLITTER VANE REQUIREMENTS
R=20"R=2"R=4-1/4"R=9-1/4"
OU
TSID
ERAD
IUS
ININ
CH
ES
INSID
ERAD
IUS
OF
ELB
OW
ININ
CH
ES
NUMBER OF SPLITTERS
MAX. 60"SEE NOTE 3
ANGLE IRON
THREADEDHANGER ROD
UNISTRUT OR
HANGERSTRAP
OVER 60"
GALV. HANGER
NOTES:1. ON DUCTS OVER 48" WIDE, BOTTOM SHALL BE BRACED BY ANGLE. FOR CROSS SECTION AREA MORETHAN 8 SQ FT, DUCT SHALL BE BRACED BY ANGLES ON ALL FOUR SIDES.2. CUTTING AND PATCHING SHALL BE LIMITED TO A MINIMUM AS REQUIRED FOR PROPER INSTALLATION.3. SUPPORTS SHALL BE SPACED AND SIZED AS PER SMACNA.
BUTTERFLY BLADE LOCKING QUADRANTTYPE W/NON-METALLIC SHAFT ANDEXTERNAL SHAFT BEARING MOUNTS
NOTES:1. DAMPER SHALL BE MFR. OF SAMEMATERIAL AS DUCTWORK2. GAUGE OF DAMPER TO BE (2)GAUGES HEAVIER THAN DUCTWORK
INDICATOR TO SHOWOPEN/CLOSE/BALANCED POSITION
(IF MAIN DUCT IS ROUND) L=1/4 W; 4"MIN
RETURN/EXHAUST AIR
SUPPLY AIR
VD
IS RECTANGULAR) OR CONICAL CONNECTIONTAPERED CONNECTION 45° ANGLE(IF MAIN DUCT
MAIN DUCT
BRANCH DUCT
ROOF MEMBRANE
FLASHING
SS SHEETMETAL SCREW
S-SLIP CONNECTION
STEEL DECK
CONCRETE DECK
ANCHORCURB TODECK
COMPLETELY SEAL &COVER JOINT WITHOUTDOOR, UV RESISTANTSEALANT
PREFABRICATED, INSULATEDCURB WITH WOOD NAILER
TACK WELD CURBTO DECK
ROOF DECKINSULATION
TYPICAL CLEANOUT/ACCESS DOORFOR RECTANGULAR DUCTWORK
NUMBERING & SPACING OFDUCT SPLITTER VANES
DUCT HANGER SUPPORT BRANCH TAKE-OFFS
ROUND VOLUME DAMPERBELOW 14" - LOW PRESSURE
DUCT PENETRATION THRU ROOF
1"
HEIGHT
WIDTH
-
h
w
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . .
rR
. . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
HSM020
1"
HSM008
HSM014
W
L
DUCT TAKE-OFF
HSM001
HPE005
FLOW
AIR
NOTES:1. WALL OPENING SHALL BE SIZED TO MAINTAIN MANUFACTURER'S REQUIRED EXPANSION SPACE AROUND DAMPER.2. DAMPER BLADES SHALL BE OUT OF AIRSTREAM TYPE "3A,3B,7 OR 8" (SEE SMACNA FIRE DAMPER
AND HEAT STOP GUIDE - 2ND EDITION PAGE 9 OR NEWER VERSION IF APPLICABLE) WHEN OPEN100% FREE AREA IS REQUIRED. WHEN DUCT DIMENSIONS ARE LARGER THAN THE LARGESTAVAILABLE CURTAIN TYPE DAMPER (SHOWN), PROVIDE BLADE TYPE DAMPERS (SIMILAR TOFIRE/SMOKE DAMPERS). IF POWERED ACTIVATORS ARE REQUIRED, THE WIRING SHALL BEINCLUDED IN THE MECHANICAL CONTRACTOR'S COST.
3. PROVIDE SPRING LOADED CLOSURE FOR ALL FIRE DAMPERS.4. WHEN DUCTWORK IS INSULATED OR LINED, PROVIDE INSULATED ACCESS DOOR.5. ACCESS DOOR SHALL BE 12" X 12" OR LARGER IF REQUIRED FOR FUSIBLE LINK REPLACEMENT
WITH PERMANENTLY MOUNTED LABEL.6. TYPE "1" OR "2" FIRE DAMPERS (BLADES OR FRAME IN AIR STREAM) MAY BE SUBSTITUTED FOR
TYPE "3A OR 3B" WHERE VELOCITIES ARE UNDER 500 FPM IN LOW PRESSURE DUCT SYSTEMS ONLY.7. INSTALLATION SHOWN AS AN EXAMPLE. SPECIFIC INSTALLATION REQUIREMENTS, INCLUDING
BREAKAWAY CONNECTIONS, SHALL CONFORM WITH MANUFACTURER'S UL APPROVEDINSTRUCTIONS.
H1510FIRE DAMPER
FIREDAMPER
FIRE-RATED WALL OR PARTITION(TYPE AND SIZE VARIES).
FIREDAMPER
DUCT
SEE NOTE 3
ACCESS DOOR (ON LINKSIDE OF DAMPER, ON SIDEOR BOTTOM OF DUCT)
RETAINING ANGLE, TYP.EXPANSION SPACE
FASTENER TO SLEEVEDAMPER SLEEVE
MOUNT ANGLES TIGHT TO WALL
1" MIN. WALL OPENINGOVERLAP ON ALL
SIDES OF DAMPER
PROVIDE ACCESSDOOR LABEL WITHMIN. 1/2" HIGHLETTERING
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:32:04 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-603
MECHANICAL DETAILS IV
ROCKY HILL
NO. Revision Description Date 10.35
MVMV
PT
PT
PT
PT
MV
MV
S
PT PT
PT
PT
PT
PT PT
PT PT
REFRIGERANT PIPING COMPONENT DIAGRAM(WITH HOT GAS BYPASS)
HOT WATER FIN-TUBE RADIATION WITH 2-WAYMODULATING PI AUTOMATIC CONTROL VALVE
MULTIPLE OR SINGLE WATER COILS WITH 2-WAYMODULATING PI AUTOMATIC CONTROL VALVES
DETAIL OF PIPE THRU ROOF(EXCLUDING STEAM RELIEF)
TYPICAL PIPE INSULATION & VALVEHANDLE EXTENSION
TRANSFER BOOT W/ GRILLES
H1304
CONDENSING UNIT
NOTES:1. PIPING SHOWN IS FOR LEAD CIRCUIT. ADDITIONALCIRCUITS ARE SIMILAR, EXCEPT NO HOT GAS BYPASS.2. PIPE SIZING ON DRAWINGS ARE APPROXIMATE,CONFIRM ALL PIPE SIZES WITH UNIT MANUFACTURERBASED ON ACTUAL FIELD ROUTING.3. PROVIDE BYPASS CIRCUIT, CONTROL EQUIPMENT, ANYREQUIRED DOUBLE SECTION RISERS TRAPS, ANDAPPURTENANCES AS RECOMMENDED SIZED ANDDIAGRAMMED BY THE UNIT MANUFACTURER ANDSUBMITTED, ALONG WITH CALCULATIONS AND SIZINGCHARTS FOR ENGINEERS REVIEW.
1
LIQUID LINE2
3 INSULATEDSUCTION LINE
BALL SHUT-OFF4
FILTER DRYER
THERMAL EXPANSION VALVE WITHEQUALIZER LINE
SIGHT GLASS
SOLENOID VALVE
8
7
6
5
COOLING COIL
12
11
10
9
DRAIN PAN
DRAIN LINE-TRAP & ROUTE TONEAREST DRAIN
TRAP13
2
3
12
4 7
5
68
101311
1
9
HOT GAS BYPASS LINE AND VALVE
HC008
HWR
1/2" DOV W/HB
FIN-TUBE ELEMENT
HWS HWR
FLOOR LEVEL
RISER FEED
1/8" MANUAL AIR VENT
FLOOR LEVEL
HWS
H
FLOOR LEVEL
TOP FEED
BOTTOM FEED
DOV W/HB
NOTES:1. HEIGHT "H" AS REQUIRED TO ACCOMODATE ENCLOSURE.2. WHEN INSTALLING TWO ELEMENTS HIGH IN SERIES , CONNECTHWS TO BOTTOM ELEMENT AND PITCH UP TOWARD HWR.3. MINIMUM OF TWO ELBOW CONNECTIONS SHALL BE USED ATSUPPLY & RETURN CONNECTIONS FROM & TO RISERS TO SUIT JOBCONDITIONS.
HWRHWS
FIN-TUBE ELEMENT
FIN-TUBE ELEMENT
PIACV
H
PIACV
H
PIACV
HCO27
FZ
NOTES:1. FOR PIPING SMALLER THAN 2-1/2" PROVIDE BALL VALVES IN PLACE OF BUTTERFLY VALVES.2. FOR PIPING LARGER THAN 2" PROVIDE BUTTERFLY VALVES IN PLACE OF BALL VALVES.3. PROVIDE SIMILAR PIPING FOR 3 OR MORE COILS HIGH AND/OR 2 COILS WIDE. LOCATEPIPE UNIONS (OR FLANGED BODY) AND ARRANGE PIPING TO FACILITATE COIL REMOVAL.PROVIDE REDUCERS AT COIL AS REQUIRED.4. SINGLE TWO-WAY CONTROL VALVE SHOWN. SEE AUTOMATIC-TEMPERATURE-CONTROLDIAGRAM AND SPECIFICATIONS FOR ACTUAL JOB REQUIREMENTS.5. FOR WATER COILS ONLY (NOT GLYCOL) THAT ARE SUBJECT TO FREEZING, PROVIDEIMMERSION AQUASTAT WELL. FREEZESTAT, FZ (AN AQUASTAT) SHALL INITIATE AN ALARMTHROUGH THE CONTROL SYSTEM WHEN IT SENSES BELOW 38°F.
DOVW/HB
SEE NOTE 2 (TYP)
FZ NOTE 5
MV
SUPPLY
TO ADD'L COILSFROM ADD'L COILS
NOTE 5 6" DIRTLEG(TYP)
RETURN
SEE NOTE 4
SEE NOTE 1 (TYP)
MV
121-25061-12036-6020-3513-190-12
FLOW (GPM)SIZE (IN)RUNOUT SIZING
432&1/221&1/21&1/4
DRAINPANPIPING(COOLING ONLY)SEE CONDENSATETRAP DETAIL
DOVW/HB
PIACV
BUTT & SEALJOINTS
CAP INSULATION. LEAVENO EXPOSED INSULATIONANYWHERE
PROVIDE VALVE EXTENSIONKIT TO ALLOW PROPERINSULATION COVERAGE
HPW006
PIPE SLEEVE
HPE004
COUNTER FLASHING POS
BUILT-UP ROOF
PIPING SEE PLANS FOR SIZE
16 OUNCE COPPERFLASHING POS
ROOF CONSTRUCTIONSEE ARCHITECT'SDRAWINGS
SEAL ALL AROUND
FLASHING SLEEVE SIMILARTO JOSAM #26450
VALVES
D
PARTITION
CEILINGCEILING GRILLE
CEILING PLENUM
H1505
DUCT FULL SIZE OFTRANSFER GRILLENECK UNLESSOTHERWISE SHOWNON PLANS
DELETE THIS SECTIONWHERE PLANINDICATES TRANSFERTERMINATES INCEILING PLENUM
2 X D OR 3 FTMINIMUM
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:32:06 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-604
MECHANICAL DETAILS V
ROCKY HILL
NO. Revision Description Date 10.36
3"
4"
30"
MIN
.
DUCTSIZE
+25%
"D"
DN
LOUVER CONNECTION
RADIANT FLOOR PIPING ELEVATION GOOSENECK DETAILGARAGE DOOR SENSOR DETAIL
ROOF MEMBRANE
STEEL DECK
TACK WELD CURB
H1523
STANDARD DUCT MADE WATERTIGHT. STIFFENERS MAY BEINSIDE.
BOLTSSCREEN
ANCHOR CURB TODECK INACCORDANCE WITHCURBMANUFACTURER
ROOF DECKINSULATION
PREFABRICATED,INSULATED CURBWITH WOOD NAILER
COUNTER FLASHING(SEALED TO DUCT)
135° MIN.
1/2"GALVANIZED SCREEN
MOTOR OPERATEDOR GRAVITY DAMPER(AS SPECIFIED)
ANGLE IRON REINFORCING WHERE REQUIRED
ANGLE REVITED OR SPOT WELDED AS REQUIRED
CONTINUOUSNEOPRENE GASKET
CONCRETE DECK
PERFORATED METALLINER
METAL SCREENFRAME
STORM-PROOF LOUVER
PITCH TO OUTSIDE
SEE NOTE
1/2" BIRDSCREEN
NOTE:WHEN "D" IS OVER 24" PROVIDE 3/4" DRAIN AT 5'-0"CENTERS (IF DEPTH INTO PAPER IS GREATER THAN5'-0"), 6" FROM LOUVER WITH TRAP.
H1519
SEAL AND CAULKALL AROUND
ACCESS DOOR HALF HEIGHT OFDUCT, 12" X 12" MIN (UNLESSSHOWN OTHERWISE ON PLANS)
LOUVER PLENUM INSULATE ALLEXPOSED PARTS W/ 2" RIGIDBOARD INSULATION (ALSOINSULATE UNUSED LOUVER AREA)
SOLDER BOTTOM JOINT & UP 12"
H1556
CONC. SLAB (SEEARCH. FOR SLOPE)
2" METAL POURSTOP
RADIANT ZONE HEADERMOUNTED TO PANELATTACHED TO CMU.LOCATE NEXT TO STEELCOLUMN
1/2" RADIANTZONE TUBING
HWS&R MAINSS.O. VALVES
FRICTION CLAMPATTACHED TOCMU WALL. (TYP.)
INSUL. SHIELD.
PIPE SUPPORT ATTACHED TO LOCALSTEEL STRUCTURAL MEMBER. SEEARCHITECTURALS FOR FURTHERDETAILS.
42" A.F.F.
HWS&R BRANCH PIPING
CONTROL VALVE
TO DECK
REBAR BY OTHERS(REFER TO ARCH. DWG)
H1557
DOOR TRACK
DS
DOOR POSITIONSENSOR
BAC
GARAGE DOOR
NOTES:1) SEE DUCT PLANS FOR DOOR SENSOR LOCATIONS AND QUANTITIES.2) TYPICAL FOR BOTH ROLL UP AND TRACKED OVERHEAD TYPE DOORS.
BACNET INTERFACEMODULE
TO BAS
STEEL COLUMN (BY OTHERS)
ANGLE BRACKET PIPING SUPPORT (FOR BELOW CRANE) H1049
PIPE INSULATIONWITH ALUMINUM
JACKET GALVANIZED ORSTAINLESS STEELPIPE CAGE
GALVANIZED ORSTAINLESS STEELPIPE ROLL STAND
PIPE
MIN. 12" LONG GALVANIZEDOR STAINLESS STEEL
INSULATION SHIELD
NON-COMPRESSIBLE RIGIDINSULATION ON BOTTOM HALF
OF PIPE AT SHIELD
NOTE: CONTRACTOR TO SUBMIT ON ALLPROPOSED MEANS OF PIPE SUPPORT FOR
REVIEW AND APPROVAL
(FOR BELOW CRANE) H1051
NOTE: CONTRACTOR TO SUBMIT ON ALLPROPOSED MEANS OF DUCT SUPPORT FOR
REVIEW AND APPROVAL
ANGLE BRACKET DUCT SUPPORT
EQUIPMENT SUPPORTDESIGNED AS SPECIFIED
SECURE TO BUILDINGSTRUCTURE
EQUIPMENT SUPPORTDESIGNED AS SPECIFIED
SECURE TO BUILDINGSTRUCTURE
SUPPLY/EXHAUST/RETURN DUCT.
2 X 2 ANGLE BRAKET (TYP.)
SCREWED THRU BRACKETTO STRUT/CHANNEL AND
DUCT. (TYP.)
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:32:08 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-605
MECHANICAL DETAILS VI
ROCKY HILL
NO. Revision Description Date 10.37
ENERGY RECOVERY UNIT SCHEDULE
TAG LOCATIONOA
CFMTOTAL
FAN DATA HEATING COIL (HOT WATER) ENERGY RECOVERY PLATE
WT (LBS) MF'R AND MODEL NO.(AS STANDARD) REMARKS
CAPACITYCONTROL
STATIC PRESS. (IN.WG)
OUTLETVEL.
(FPM)
WHEEL MOTOR
CAPACITY(MBH)
FACEVEL.
(FPM)
AIR DATA HOT WATER DATA
NO. OFCOILS/ROWS
FIN/FT.
WINTER
RANGE(%) TYPE EXTERNAL
TOTALW/
DIRTYFILTERS
DIA.(IN.) TYPE RPM BHP HP V PH EAT
(°F)LAT(°F)
P.D.(IN.WC) GPM EWT
(°F)LWT(°F)
P.D.(FT.)
CAPACITY(MBH)
MAXP.D.(IN.)
SUPPLY EXHAUST
EAT LAT EAT LAT
ERU-1 ROOF 17,500 100 VFD 1.5 2.5 2512 25 PLENUM 1447 15.99 20 208 3 704 499 42 80 0.15 47 140 110 2.75 2 87 804 0.87 0 42 70 29 8871 TRANE CLIMATE CHANGER CSAA035UA 1 THRU 8
ERU-2 ROOF 17,500 100 VFD 1.5 2.5 2512 25 PLENUM 1447 15.99 20 208 3 704 499 42 80 0.15 47 140 110 2.75 2 87 804 0.87 0 42 70 29 8871 TRANE CLIMATE CHANGER CSAA035UA 1 THRU 8
ERU-3 ROOF 4,200 100 VFD 1.5 2.5 2032 15 PLENUM 1798 2.7 3 208 3 168 418 42 80 0.11 11.2 140 110 0.75 2 86 192 0.26 0 42 70 29 3324 TRANE CLIMATE CHANGER CSAA010UA 1 THRU 8
ERU-4 ROOF 9,000 100 VFD 1.5 2.5 3121 18 PLENUM 2071 7.9 10 208 3 369 432 42 80 0.12 24.5 140 110 1.41 2 84 453 0.6 0 42 70 29 5248 TRANE CLIMATE CHANGER CSAA021UA 1 THRU 8
NOTES:1 REFER TO SPECIFICATIONS, AND DETAILS FOR ADDITIONAL INFORMATION.2 UNITS TO BE DOUBLE WALLED WITH INSUL. PROVIDE INSULATED DOUBLE WALL ACCESS DOORS (WITH MULT-IPOINT DOOR LATCH AND VISION PANELS) FOR EACH SECTION. OUTDOOR AIR DAMPERS SHALL BE INSULATED ULTRA LOW LEAKAGE DAMPERS WITH BLADE SEALS. SUPPLY AIR FAN ASSEMBLY TO BEPROVIDED WITH INTERNAL VIBRATION ISOLATORS (WITH 2" INCH DEFLECTION SPRING ISOLATORS).3 PROVIDE ALL UNITS WITH FACTORY VFD AND PREMIUM EFFICIENCY VFD COMPATIBLE MOTORS.4 PROVIDE STAINLESS STEEL DRAIN PAN THAT EXTENDS 10" BEYOND FACE OF COIL.5 PROVIDE DISCHARGE PLENUM SECTION.6 PROVIDE FACTORY DISCONNECT SWITCH AND SINGLE POINT POWER.7 M.C. TO VERIFY LOCATION OF COIL CONNECTION, ACCESS DOORS, FILTER PULL, MOTOR ACCESS, ETC. PRIOR TO ORDERING UNITS. REFER TO PLANS.8 PROVIDE WITH FACTORY MOUNTED CONTROLS.
DUCTLESS SPLIT AIR-CONDITIONING UNIT SCHEDULE
TAG LOCATION
INDOOR UNIT REFRIGERANT OUTDOOR CONDENSING UNIT
REMARKSCFM MANUFACTURER AND MODEL
NUMBER (INDOOR UNIT)
CAPACITY(MBH)
TYPEMANUFACTURER AND
MODEL NUMBER (OUTDOORUNIT)
TAG LOCATIONSOUND
PRESSURE DB(A)
DESIGNAMBIENTTEMP (°F)
MINIMUMAMBIENTTEMP (°F)
ELECTRIC (OUTDOOR)
EFFICIENCY(SEER)
BTU'S/HR COND.(GPM) MCA HZ V PH
AC-1 ELEC. RM. 1,025 MITSUBISHI PCA 24,000 0.02 R410A PUY-A24NHA4 ACCU-1 ROOF 48 95° 0° 18 60 208 1 16.8 1 THRU 8
AC-2 COMM RM 670 MITSUBISHI PCA 42,000 0.03 R410A PUYA42NHA4 ACCU-2 ROOF 51 95° 0° 26 60 208 1 15.8 1 THRU 8
NOTES:1 REFER TO SPECIFICATIONS, DETAILS, AND CONTROL DRAWINGS FOR ADDITIONAL INFORMATION.2 SEE DRAWINGS FOR UNIT QUALITIES.3 PROVIDE 1-1/4" CONDENSATE DRAIN TO LOCAL FLOOR DRAIN.4 PROVIDE REFRIGERANT PIPING BETWEEN INDOOR AND OUTDOOR UNITS SIZED AS PER MANUFACTURERS RECOMMENDATIONS FOR LENGTH OF RUN.5 PROVIDE FIELD SUPPLIED INTERCONNECTED POWER WIRING FROM OUTDOOR UNIT TO INDOOR UNIT.6 PROVIDE WITH ROOM MOUNTED T-STAT.7 PROVIDE WITH DISCONNECT SWITCH.8 PROVIDE WITH FACTORY WIND BAFFLE ACCESSORY INSTALLED.
EXHAUST FAN SCHEDULE
TAG SERVICE LOCATION CFM FANTYPE
E.S.P.(IN.WG)
WHEELOUTLET
VELOCITY(FPM)
MOTOR
WEIGHT(LBS)
MANUFACTURER AND MODEL NUMBER(AS STANDARD) REMARKS
DIA. (IN.) TYPE DRIVE RPM BHP HP V PH
EF-1A,B,C,D ERU-1,2,3,4 ROOF 11,250 HIGHPLUME 5 - BELT 4000 1725 16.08 25 208 3 10,880 GREENHECK VEKTOR-MD-27-2-85 1,2,3,4,5
EF-2 WASH BAY ROOF 6,000 CENTUPBLAST .5 - BELT - 866 1.61 2 208 3 150 GREENHECK CUBE-220-20 1,2,3,4,5
EF-3 MECHANICAL RM ROOF 3,000 CENTDNBLAST .5 - BELT - 1725 .73 .75 208 3 80 GREENHECK CUBE-161-7 1,2,3,4,5
EF-4 PAINT EQUIP RM ROOF 3,500 INLINE 1 - DIRECT - 1725 1.84 2 208 3 164 GREENHECK SQ-160-A 1,2,3,4,5
EF-5 SPRINKLER ROOM ROOF 3,000 CENTDNBLAST .5 - BELT - 1725 .73 .75 208 3 80 GREENHECK CUBE-161-7 1,2,3,4,5
VF-1 REPAIR BAY ROOF 17,000 CENTUPBLAST .75 - BELT - 1725 4.3 5 208 3 363 GREENHECK CUBE-420-50 1,2,3,4,5
VF-2 REPAIR BAY ROOF 17,000 CENTUPBLAST .75 - BELT - 1725 4.3 5 208 3 363 GREENHECK CUBE-420-50 1,2,3,4,5
VF-3 WELD SHOP ROOF 3,500 CENTUPBLAST .5 - BELT - 1725 0.7 .75 208 3 103 GREENHECK CUBE-180-7 1,2,3,4,5
VF-4 AERIAL BUCKET ROOF 4,000 CENTUPBLAST .5 - BELT - 1725 0.9 1 208 3 117 GREENHECK CUBE-200-10 1,2,3,4,5
VF-5 STORES STOCKROOM ROOF 8,000 CENTUPBLAST .5 - BELT - 1725 1.2 1.5 208 3 194 GREENHECK CUBE-300-15 1,2,3,4,5
VF-6 STORES STOCKROOM ROOF 8,000 CENTUPBLAST .5 - BELT - 1725 1.2 1.5 208 3 194 GREENHECK CUBE-300-15 1,2,3,4,5
VF-7 LUBE/COMPRESSOR ROOF 2,000 CENTUPBLAST .5 - BELT - 1725 0.46 .5 208 3 77 GREENHECK CUBE-141-5 1,2,3,4,5
VF-8 LUBE BAYS ROOF 4,500 CENTUPBLAST .5 - BELT - 1725 1.15 1.5 208 3 122 GREENHECK CUBE-200-15 1,2,3,4,5
VF-9 WELD/FABRICATIONSHOP ROOF 7,500 CENT
UPBLAST .5 - BELT - 1725 0.7 2 208 3 184 GREENHECK CUBE 240-20 1,2,3,4,5
VF-10 MACHINE SHOP ROOF 7,500 CENTUPBLAST .5 - BELT - 1725 0.7 2 208 3 184 GREENHECK CUBE 240-20 1,2,3,4,5
VF-11 MACHINE SHOP ROOF 7,500 CENTUPBLAST .5 - BELT - 1725 0.7 2 208 3 184 GREENHECK CUBE 240-20 1,2,3,4,5
VF-12 CNG INSPECTION ROOF 6,000 CENTUPBLAST .5 - BELT - 1725 1.3 1.5 208 3 143 GREENHECK CUBE 240-15 1,2,3,4,5
VF-13 PARTS WASHER ROOF 900 CENTUPBLAST .5 - BELT - 1725 0.18 0.25 208 3 56 GREENHECK CUBE 101-4 1,2,3,4,5
VF-14 PAINT EQUIP. RM ROOF 600 CENTUPBLAST .5 - BELT - 1725 0.18 0.25 208 3 56 GREENHECK CUBE-101HP-4 1,2,3,4,5
VF-15 PAINT BOOTH HALL ROOF 2,000 CENTUPBLAST .5 - BELT - 1725 0.46 .5 208 3 77 GREENHECK CUBE-141-5 1,2,3,4,5
TE-1 MENS RM, WOMENSRM, JANITOR CLOSET ROOF 2,000 CENT
DNBLAST 1 - BELT - 1725 .59 .75 208 3 62 GREENHECK G-133-A 1,2,3,4,5
VES-1 THRU 10 VARIES IN-ROOM 1,400 UTILITYSET 5 - BELT - 3600 3.0 2.12 208 3 159 GREENHECK BISW 1,2,3,4,5
EHF-1 THRU 4 VARIES IN-ROOM 600 UTILITYSET 4 - BELT - 3600 - 1.5 208 3 158 GREENHECK BISW 1,2,3,4,5
NOTES:1 PROVIDE WITH FACTORY ROOF CURB2 PROVIDE WITH BACKDRAFT DAMPER3 PROVIDE NEMA-3R RATED DISCONNECT SWITCH.4 PROVIDE WITH BMS START/STOP AND SCHEDULING.5 PROVIDE WITH VFD
CONDENSING BOILER SCHEDULE (HOT WATER)
TAG LOCATION
CAPACITY PRESS. (PSIG) WATER BREECHING BURNER
WEIGHT(LBS)
MANUFACTURER ANDMODEL NUMBER (AS
STANDARD)REMARKS
OUTPUT(GROSS I=B=R) NATURAL GAS
MAXDESIGN
RELIEF
VALVE
ENT(°F)
LVG(°F) GPM °F SCFM TYPE TURN
DOWNMBH BHP INPUT
(MBH)PRESSURE
(IN.WG)EFFICIENCY
(%)
WB-1 MECH RM 2,190 65.4 2,200 - 98 - - 110 140 - - - NATURAL GAS 15:1 3,300 BUDERUS SB625WS-640 1 THRU 5
WB-2 MECH RM 2,190 65.4 2,200 - 98 - - 110 140 - - - NATURAL GAS 15:1 3,300 BUDERUS SB625WS-640 1 THRU 5
WB-3 MECH RM 2,190 65.4 2,200 - 98 - - 110 140 - - - NATURAL GAS 15:1 3,300 BUDERUS SB625WS-640 1 THRU 5
NOTES:1 REFER TO SPECIFICATIONS, AND DETAILS FOR ADDITIONAL INFORMATION.2 PROVIDE CONDENSATE NEUTRALIZATION KIT WITH PIPED DRAIN FROM EACH FLUE.3 PROVIDE SIDEWALL VENT AND COMBUSTION AIR TERMINATION KIT.4 PROVIDE FACTORY LOW WATER CUT-OFF, HIGH TEMPERATURE LIMIT, FLOW SWITCH, RELIEF VALVE, TEMPERATURE PRESSURE GAUGE.5 PROVIDE MANUFACTURER CONTROL PACKAGE.
CABINET UNIT HEATER (CUH) SCHEDULE (HOT WATER)
TAG LOCATION TYPE OUTPUTMBH
AIR MOTOR WATERMANUFACTURER AND MODEL NUMBER
(AS STANDARD) REMARKSCFM EAT
(°F)LAT(°F) RPM HP
ELECTRIC SERVICEFLUID GPM EWT
(°F)LWT(°F)
P.D. (FT.)AMPS V PH
CUH-1 VESTIBULE FLOOR 29.8 609 45 90 1050 1__30 .27 208 3 H20 2.55 140 110 0.3 TRANE FORCE-FLO 1 THRU 5
CUH-2 VESTIBULE FLOOR 29.8 609 45 90 1050 1__30 .27 208 3 H20 2.55 140 110 0.3 TRANE FORCE-FLO 1 THRU 5
NOTES:1 REFER TO SPECIFICATIONS, DETAILS, AND CONTROL DRAWINGS FOR ADDITIONAL INFORMATION.2 PROVIDE MINIMUM OF 20 GAUGE STEEL CASING PAINTED WITH A CORROSION RESISTANT, BAKED, POLYESTER POWDER COATED FINISH.3 PROVIDE FULLY ADJUSTABLE AIR DEFLECTORS AND OSHA APPROVED FAN GUARD.4 PROVIDE ALUMINUM FINS AND COPPER TUBE COILS.5 PROVIDE FACTORY WALL MOUNTED THERMOSTAT.
PUMP SCHEDULE
TAG SERVICE LOCATION CASINGTYPE
FLUID
GPM NPSHR(FT.)
HEAD(FT.)
SHUT-OFF
HEAD
(FT.)
IMPELLER
SIZE
(IN.)
MOTORMANUFACTURER AND MODEL NUMBER
(AS STANDARD) REMARKS
TYPE TEMP(°F) RPM HP V PH
HWP-1 ENERGY RECOVERY UNITS MECH RM CAST IRON H20 140 150 90 70 - 9.25 1760 5 208 3 TACO KS-2009 1,2
HWP-2 UH'S MECH RM CAST IRON H20 140 450 130 90 - 11.25 1760 20 208 3 TACO KS-4011 1,2
HWP-3 RADIANT FLOORING MECH RM CAST IRON H20 107 110 130 115 - 11.25 1760 10 208 3 TACO KS-2011 1,2
HWP-4 SPARE MECH RM CAST IRON H20 140 450 130 115 - 11.25 1760 20 208 3 TACO KS-4011 1,2
HWP-5 FIN TUBE RADIATION & CUH'S MECH RM CAST IRON H20 140 100 105 60 - 8.75 1760 5 208 3 TACO KS-1509 1,2
HWP-6 IN-DUCT HEATING COIL MECH RM CAST IRON H20 140 35 45 30 - 5.75 1760 3_4 208 3 TACO KS-1506 1,2
NOTES:1 REFER TO SPECIFICATIONS, AND DETAILS FOR ADDITIONAL INFORMATION.2 PROVIDE WITH SUCTION DIFFUSER (ONLY IF REQUIRED STRAIGHT LENGTHS UNACHIEVABLE), TRIPLE DUTY VALVE, FLEX CONNECTORS, STRAINERS, GAUGES AND ISOLATION VALVES.
AIR SEPARATOR SCHEDULE
TAG SERVICE LOCATION TYPEWATERFLOW(GPM)
PIPE SIZE(IN)
WEIGHT(LBS)
MANUFACTURER AND MODEL NUMBER(AS STANDARD) REMARKS
AS-1 HEATING WATER MECH RM TANGENTIAL 610 6" 236 TACO ACT06F-125 1 THRU 4
NOTES:1 REFER TO SPECIFICATIONS, AND DETAILS FOR ADDITIONAL INFORMATION.2 PROVIDE HIGH CAPACITY AIR VENT.3 PROVIDE FACTORY FLANGED INLET/OUTLET.4 PROVIDE UNIT LESS STRAINER.
WELD EXHAUST ARM (WEA) SCHEDULE
TAG LOCATION
AIR DIMENSIONAL DATAMANUFACTURER AND MODEL NUMBER
(AS STANDARD) REMARKSCFM P.D.
(IN W.G.) DIAMETER REACH
WEA VARIES 600 0 6" 14'-0" - NEDERMAN NEX MD 4 1,2
NOTES:1 REFER TO SPECIFICATIONS, DETAILS, AND CONTROL DRAWINGS FOR ADDITIONAL INFORMATION.2 PURCHASE WITH MOUNTING BRACKET.
PIPE EXPANSION JOINT SCHEDULE
TAG SERVICE LOCATION TYPE PIPE SIZE(IN)
MANUFACTURER AND MODEL NUMBER(AS STANDARD) REMARKS
EJ-1 HEATING WATER VARIOUS BELLOWS 4" HYSPAN 1500 SERIES 1
EJ-2 HEATING WATER VARIOUS BELLOWS 3" HYSPAN 1500 SERIES 1
EJ-3 HEATING WATER VARIOUS BELLOWS 2" HYSPAN 1500 SERIES 1
EJ-4 HEATING WATER VARIOUS BELLOWS 2-1/2" HYSPAN 1500 SERIES 1
NOTES:1 REFER TO SPECIFICATIONS, AND DETAILS FOR ADDITIONAL INFORMATION.
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:32:09 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-700
MECHANICAL SCHEDULES
ROCKY HILL
NO. Revision Description Date 10.38
LOCATION SUPPLY RETURNRAW
OUTDOORAIR
EXHAUST
WITH ENERGYRECOVERY
WITHOUT ENERGYRECOVERY
ATTIC TYPE SPACE (EXPOSED ROOF ABOVE) R-8 R-8 R-4 R-8 R-8*
OUTDOORS R-8 R-8 -0- R-8 R-8*
CRAWL SPACE R-6 R-6 R-6 R-6 -0-
UNCONDITIONED SPACE (SHAFT OR CEILING WITH DUCTEDRETURN AIR) R-6 R-6 R-6 R-6 -0-
RETURN AIR PLENUM R-4 -0- R-4 -0- -0-
EXPOSED IN MECHANICAL ROOM R-6 R-6 R-6 R-6 -0-
EXPOSED IN ZONE SERVED(**ONLY DUCTS THAT PROVIDECOOLING) R-4** -0- R-4 -0- -0-
* R-VALUE SHOWN IS ONLY IF AREA OF BUILDING BEING EXHAUSTED IS HUMIDIFIED. IF NOT HUMIDIFIED, NO INSULATION (-0-), UNLESS FIRE WRAPOR LINING IS NEEDED.DUCT LINING SCOPE: ACOUSTIC DUCT LINING OF THE TYPE AND THICKNESS SPECIFIED SHALL BE INSTALLED ON ALL SUPPLY, RETURN, ANDEXHAUST DUCTWORK WITHIN 20 FEET OF ALL TYPES OF AIR HANDLING UNITS (INCLUDING RTU, ERU, FCU, MUA, ETC., AND ALL BRANCHES WITHIN20') ALL FANS (INCLUDING BRANCHES), ALL LOW PRESSURE DUCTWORK DOWNSTREAM OF ALL TYPES OF SUPPLY VOLUME BOXES (CV, VAV, FPVAV,ETC.), AND WHERE DETAILED OR SHOWN ON DRAWINGS. LINING SHALL NOT BE USED ON DUCTWORK SERVING SURGICAL SUITES, DELIVERYROOMS, INTENSIVE CARE UNITS AND ISOLATION AREAS OF HOSPITALS AND MEDICAL FACILITIES OR ON KITCHEN AND FUME HOOD EXHAUST ANDWET/HUMID EXHAUST SUCH AS DISHWASHER, CLOTHES DRYER, AND SHOWER SYSTEMS.
NOTES: (SEE SPECIFICATIONS FOR R-VALUES OF VARIOUS DUCT INSULATION AND LINERS).
1. R-VALUES SHOWN MAY BE OBTAINED BY ADDING THE R-VALUES OF BOTH THE LINING (WHERE SHOWN OR USED) AND EXTERNAL DUCTINSULATION.2. R-VALUES SHOWN ARE AS INSTALLED. USE R-VALUES FOR 25% COMPRESSION FOR NON-RIGID INSULATION.3. REFER TO SPECIFICATIONS AND DETAILS FOR ADDITIONAL INFORMATION.
TAG CFM OUTPUT (MBH)SIZE (IN.) FACE
VELOCITY(FPM)
ROWSFINSPER
FOOT
AIR DATA WATER DATAMANUFACTURER AND MODELNUMBER (AS STANDARD) REMARKS
W H EAT(°F)
LAT(°F)
P.D.(IN.WG) GPM EWT
(°F)LWT(°F)
P.D.(FT.)
HC-1 7200 273.29 70 21 705 2 149 55 90 0.35 18.26 140 110 1.29 TRANE HTCL D5WB21 1,2
NOTES:
1 REFER TO SPECIFICATIONS, DETAILS, AND CONTROL DRAWINGS FOR ADDITIONAL INFORMATION.2 PROVIDE WITH PRESSURE INDEPENDENT CONTROL VALVE.
NOTES:1 REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION2 REFER TO DETAILS FOR ADDITIONAL INFORMATION.3 PROVIDE VIBRATION ISOLATION CURB WITH SUPPLY AND RETURN SOUND ATTENUATORS.4 PROVIDE SOFTWARE INTERFACE TO CONNECT TO BMS.5 PROVIDE WITH FACTORY MOUNTED CONTROLS6 PROVIDE WITH OUTDOOR AIR FLOW MEASURING STATION FOR O.A. CONTROLS MODULATION.
MINIMUM DUCT INSULATION R-VALUES (IECC - 2012)
HOT WATER HEATING COIL SCHEDULE (GPM)
PIPE INSULATION (IECC - 2012 ASHRAE 90.1 -2010 COMPLIANCE)MINIMUM INSULATION THICKNESS IN INCHES FOR INDOOR PIPE SIZES (SEE NOTES BELOW)
PIPING SYSTEM TYPES FLUID TEMP.RANGE (°F) < 1" 1" TO 11/4"
11/2" TO3" 4" TO 6" 8" AND
UP
K-FACTOR(BTU-INCH/°F-HR-SF) AT
AVE. TEMP. (°F)
LOW TEMPERATURE HEATING 141 TO 200 1.5 1.5 2 2 2 0.25-0.28 @ 125°F
CONDENSING BOILERS 105 TO 140 1 1 1.5 1.5 1.5 0.22-0.28 @ 100°F
NOTES:1. FOR MINIMUM THICKNESS OF ALTERNATIVE INSULATION TYPES OUTSIDE THE STATED CONDUCTIVITY RANGE, SEE TESTMETHOD FOR STEADY STATE HEAT TRANSFER PROPERTIES OF HORIZONTAL PIPE INSULATIONS, ASTM C 335-95, AND THE STATEENERGY CODE.2. FOR OUTDOOR STEAM, HEATING WATER PIPING, ADD 50% TO THICKNESS LISTED.3. REFER TO SPECIFICATIONS AND DETAILS FOR ADDITIONAL INFORMATION.
PACKAGED DX ROOFTOP AIR HANDING UNIT SCHEDULE
TAG SERVICE LOCATION
CFM DX COOLING COIL
MANUFACTURER ANDMODEL NUMBER
(AS STANDARD)REMARKS
TOTAL MIN.O.A.
STATIC PRESS. (IN. WG) MOTOR CAPACITY (MBH)FACE
VELOCITY(FPM)
REFRIG-ERANTTYPE
AIR DATA
ROWSFINSPERFT.
EXTERNAL TOTAL W/ DIRTYFILTERS RPM BHP BHP/ 1000
CFM HP V PH MOP MCA TOTAL SENS.EAT (°F) LAT (°F) P.D.
(IN.WG)DB WB DB WB
RTU-1 OFFICES ROOF 7,200 750 1.75 2.5 884 6.22 863.89 7.5 208 3 125 112 251 182 230 R-410A 80 67 59.6 56.7 0.3 4 180 TRANE THD240 SERIES 1 THRU 6
DIFFUSER AND GRILLE SCHEDULE
TAG SELECTIONRANGE (CFM)
NECKSIZE (IN.)
OVERALLSIZE (IN.) SERVICE MOUNTING TYPE NOTES
MANUFACTURER ANDMODEL NUMBER(AS STANDARD)
REMARKS
SA 0-150 8" 22x22 SUPPLY CEIILNG LAY-IN OR SURFACE - TITUS TMS 1 THRU 8
SB 0-285 12" 22x22 SUPPLY CEILING LAY-IN OR SURFACE - TITUS TMS 1 THRU 7
SC 0-250 15" 22x22 SUPPLY CEILING LAY-IN OR SURFACE - TITUS TMS 1 THRU 8
SD 0-360 14" 22x22 SUPPLY CEILING LAY-IN OR SURFACE - TITUS TMS 1 THRU 7
SE 0-500 15" 22x22 SUPPLY CEILING LAY-IN OR SURFACE - TITUS TMS 1 THRU 7
SF 0-500 12" 22x22 SUPPLY CEILING LAY-IN OR SURFACE - TITUS TMS 1 THRU 7
SG 0-1700 24"x22" 253_4"x233_
4" SUPPLY DUCT SIDEWALL GRILLE DOUBLE DEFLECTION TITUS 300FL 1,4,7
SH 0-800 18"x18" 193_4"x193_
4" SUPPLY DUCT SIDEWALL GRILLE DOUBLE DEFLECTION TITUS 300FL 1,4,7
SI 0-700 18"X14" 193_4"x153_
4" SUPPLY DUCT SIDEWALL GRILLE DOUBLE DEFLECTION TITUS 300FL 1,4,7
SJ 0-500 14"x14" 153_4"x153_
4" SUPPLY DUCT SIDEWALL GRILLE DOUBLE DEFLECTION TITUS 300FL 1,4,7
SK 0-3350 22"x46" 24"x48" SUPPLY DUCT SIDEWALL GRILLE DOUBLE DEFLECTION TITUS 300FL 1,4,7
EG 0-1700 24"X24" 24"X24" RETURN CEILING LAY-IN OR SURFACE - TITUS 23RS 1,3,4,5,7,8
EH 0-800 18"x18" 193_4"x193_
4" EXHAUST DUCT SIDEWALL GRILLE - TITUS 350FL 1,4,7
EI 0-700 18"x14" 193_4"x153_
4" EXHAUST DUCT SIDEWALL GRILLE - TITUS 350FL 1,4,7
EJ 0-500 14"x14" 153_4"x153_
4" EXHAUST DUCT SIDEWALL GRILLE - TITUS 350FL 1,4,7
EK 0-3350 22"x46" 24"x48" EXHAUST DUCT SIDEWALL GRILLE - TITUS 350FL 1,4,7
NOTES:1 REFER TO SPECIFICATIONS AND DETAILS FOR ADDITIONAL INFORMATION.2 RUNOUTS TO DIFFUSERS SHALL BE THE SAME SIZE AS INLET/NECK SIZE3 PROVIDE 24"x24" LAY-IN BORDER4 PROVIDE FACTORY POWDER COAT FINISH. COORDINATE FINAL COLOR WITH ARCHITECT/OWNER.5 NC RATING NOT TO EXCEED 306 COORDINATE BLOW PATTERN WITH HVAC PLANS, USE BAFFLES FROM MANUFACTURER AS REQUIRED TO OBTAIN FLOW PATTERNS FOR 1-WAY, 2-WAY, AND 3-WAYTYPES.7 CONTRACTOR SHALL VERIFY QUANTITY OF DIFFUSERS, GRILLES, REGISTERS, ETC... REQUIRED. REFER TO PLANS.8 PROVIDE ALUMINUM DIFFUSERS OR GRILLES IN LOCKER ROOMS AND BATHROOMS.
EXPANSION TANK SCHEDULE
TAG SERVICE LOCATION TYPE FLUID
SYSTEM TEMP(°F)
SYSTEMPRESSURE
(PSIG) AT TANKVOLUME (GALLONS) DIMENSIONS INITIAL
TANK AIRCHARGE
(PSIG)
MANUFACTURER ANDMODEL NUMBER
(AS STANDARD)REMARKS
MIN MAX MIN MAX TANK ACCEPTANCE DIA H
ET-1 HEATING WATER MECH RM FULL ACCEPTANCE H20 90 140 20 40 132 .366 24 86 20 TACO CA500-125 1
NOTES:1 REFER TO SPECIFICATIONS AND DETAILS FOR ADDITIONAL INFORMATION.
TERMINAL VOLUME BOX SCHEDULE
TAG TYPE SELECTIONRANGE (CFM)
INLET SIZE(IN.)
DISCHARGESIZE (IN.) MAX. S.P.
DROP W/COIL
(IN.WG)
NC RATING MANUFACTURER ANDMODEL NUMBER
(AS STANDARD)REMARKS
W H RAD DISCH
VAV-6 SINGLE DUCT 60-500 6 11.5 9.5 0.11 23 20 TRANE VCW SERIES 1 THRU 3
VAV-8 SINGLE DUCT 105-900 8 12.5 11.5 0.10 23 16 TRANE VCW SERIES 1 THRU 3
VAV-10 SINGLE DUCT 165-1400 10 15.5 13.5 0.25 22 23 TRANE VCW SERIES 1 THRU 3
VAV-12 SINGLE DUCT 240-2000 12 19.5 15.5 0.5 23 27 TRANE VCW SERIES 1 THRU 3
NOTES:1 REFER TO SPECIFICATIONS, AND DETAILS FOR ADDITIONAL INFORMATION.2 PROVIDE PRESSURE SWITCH TO PROVE AIRFLOW.3 COIL HEATING CAPACITY SHALL BE BASED ON MINIMUM CFM AND WATER FLOW LISTED ON DRAWINGS FOR EACH BOX (EXCEPT FOR BOXESWITH CO2 CONTROLS, IN WHICH CASE 75% OF MAXIMUM AIR FLOW SHALL BE USED).
FINNED TUBE RADIATOR SCHEDULE
TAG
WATER TEMP. PIPE FINSROWS
HIGH
BTUH
/FT AT
140°F
LENGTH
COVERMANUFACTURER ANDMODEL NUMBER (AS
STANDARD)REMARKS
ENT(°F)
LVG(°F) TYPE SIZE TYPE SIZE
FINS
/FTTYPE DEPTH HEIGHT
FTR-1 140 110 COP. 3_4" ALUM. 41_
4"X41_4" 50 2 1120 16'-0" SLOPE-
TOP 5-1/4" 18" MODINE S -18 1
FTR-2 140 110 COP. 3_4" ALUM. 41_
4"X41_4" 50 2 1120 28'-0" SLOPE-
TOP 5-1/4" 18" MODINE S -18 1
FTR-3 140 110 COP. 3_4" ALUM. 31_
4"X23_4" 50 1 360 18'-0" SLOPE-
TOP 3-5/8" 8" MODINE SP- 8 1
FTR-4 140 110 COP. 3_4" ALUM. 31_
4"X23_4" 50 1 360 12'-0" SLOPE-
TOP 3-5/8" 8" MODINE SP- 8 1
FTR-5 140 110 COP. 3_4" ALUM. 31_
4"X23_4" 50 1 360 16'-0" SLOPE-
TOP 3-5/8" 8" MODINE SP- 8 1
FTR-6 140 110 COP. 3_4" ALUM. 31_
4"X23_4" 50 1 360 12'-0" SLOPE-
TOP 3-5/8" 8" MODINE SP- 8 1
FTR-7 140 110 COP. 3_4" ALUM. 31_
4"X23_4" 50 1 360 10'-0" SLOPE-
TOP 3-5/8" 8" MODINE SP- 8 1
FTR-8 140 110 COP. 3_4" ALUM. 31_
4"X23_4" 50 1 360 12'-0" SLOPE-
TOP 3-5/8" 8" MODINE SP- 8 1
FTR-9 140 110 COP. 3_4" ALUM. 31_
4"X23_4" 50 1 360 12'-0" SLOPE-
TOP 3-5/8" 8" MODINE SP- 8 1
FTR-10 140 110 COP. 3_4" ALUM. 31_
4"X23_4" 50 1 360 8'-0" SLOPE-
TOP 3-5/8" 8" MODINE SP- 8 1
FTR-11 140 110 COP. 3_4" ALUM. 31_
4"X23_4" 50 1 360 12'-0" SLOPE-
TOP 3-5/8" 8" MODINE SP- 8 1
FTR-12 140 110 COP. 3_4" ALUM. 31_
4"X23_4" 50 1 360 8'-0" SLOPE-
TOP 3-5/8" 8" MODINE SP- 8 1
FTR-13 140 110 COP. 3_4" ALUM. 31_
4"X23_4" 50 1 360 14'-0" SLOPE-
TOP 3-5/8" 8" MODINE SP- 8 1
FTR-14 140 110 COP. 3_4" ALUM. 31_
4"X23_4" 50 1 360 14'-0" SLOPE-
TOP 3-5/8" 8" MODINE SP- 8 1
FTR-15 140 110 COP. 3_4" ALUM. 31_
4"X23_4" 50 1 360 10'-0" SLOPE-
TOP 3-5/8" 8" MODINE SP- 8 1
NOTES:1 REFER TO SPECIFICATIONS, DETAILS, AND CONTROL DRAWINGS FOR ADDITIONAL INFORMATION.
LOUVER AND VENTILATOR SCHEDULE
TAG LOCATIONDIMENSIONS
MOUNTINGFREEAREA
(SQFT)MANUFACTURER AND MODEL NUMBER
(AS STANDARD) REMARKSW H D
LV-1 MECH ROOM 24" 24" 34.75" ROOF 11.14 GREENHECK WRH 1,2,3
LV-2 SPRINKLER ROOM 24" 24" 34.75" ROOF 11.14 GREENHECK WRH 1,2,3
LV-3 PARTS WASHER 24" 24" 34.75" ROOF 11.14 GREENHECK WRH 1,2,3
LV-4 PAINT BOOTH HALL 48" 48" 6" WALL 8.32 GREENHECK EDJ-601 SERIES 1,2,3
LV-5 PAINT STORAGE . 36" 36" 34.75" ROOF 15.86 GREENHECK WRH 1,2,3
LV-6 PAINT STORAGE 18" 18" 12.25 ROOF 3.19 GREENHECK WRH 1,2,3
LV-7 VARIES 24" 24" 6" WALL 1.84 GREENHECK EDJ-601 SERIES 1,3
LV-8 MEZZ. LOUVER 102" 120" 6" WALL 50.14 GREENHECK EDJ-601 SERIES 1,3
LV-9 MEZZ LOUVER 108" 120" 6" WALL 54.31 GREENHECK EDJ-601 SERIES 1,3
LV-10 PAINT MECH PLAT. 166" 75" 6" WALL 49.53 GREENHECK EDJ-601 SERIES 1,3
NOTES:1 REFER TO SPECIFICATIONS, DETAILS, AND CONTROL DRAWINGS FOR ADDITIONAL INFORMATION.2 PROVIDE WITH ACTUATOR AND RUSKIN CD51 LOW-LEAKAGE CD51 TYPE DAMPER OR APPROVED EQUAL.3 PROVIDE WITH BIRD AND INSECT SCREEN
UNIT HEATER (UH) AND CABINET UNIT HEATER (CUH) SCHEDULE (HOT WATER)
TAG LOCATION TYPE OUTPUTMBH
AIR MOTOR WATERMANUFACTURER AND
MODEL NUMBER(AS STANDARD)
REMARKSCFM EAT
(°F)LAT(°F) RPM HP
ELECTRIC SERVICEFLUID GPM EWT
(°F)LWT(°F)
P.D. (FT.)AMPS V PH
UH-1 CNG BAY HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 6
UH-2 CNG BAY HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 6
UH-3 CNG BAY HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 6
UH-4 REPAIR BAY HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-5 REPAIR BAY HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-6 REPAIR BAY HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-7 REPAIR BAY HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-8 WELD SHOP HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-9 WELD SHOP HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-10 REPAIR BAY HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-11 REPAIR BAY HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-12 LUBE BAY HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-13 LUBE BAY HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-14 LUBE BAY HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-15 LUBE STORAGE HORIZ 25 550 0 103 1550 1__20 1.4 208 3 H20 2.7 140 110 0.09 TRANE S-36 SERIES 1 THRU 5
UH-16 WASH BAY HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-17 STORES STOCK HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-18 STORES STOCK HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-19 STORES STOCK HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-20 ELECTRIC RM HORIZ 25 550 0 103 1550 1__20 1.4 208 3 H20 2.7 140 110 0.09 TRANE S-36 SERIES 1 THRU 5
UH-21 SPRINKLER RM HORIZ 18 450 0 96 1550 1__32 0.4 208 3 H20 1.8 140 110 0.014 TRANE S-24 SERIES 1 THRU 5
UH-22 MACHINE SHOP HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-23 MACHINE SHOP HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-24 PARTS WASH HORIZ 18 450 0 96 1550 1__32 0.4 208 3 H20 1.8 140 110 0.014 TRANE S-24 SERIES 1 THRU 5
UH-25 PAINT STORAGE HORIZ 25 550 0 103 1550 1__20 1.4 208 3 H20 2.7 140 110 0.09 TRANE S-36 SERIES 1 THRU 5
UH-26 PAINT BAYS HORIZ 30 750 0 103 1000 1__20 1.4 208 3 H20 3.5 140 110 .12 TRANE S-48 SERIES 1 THRU 5
UH-27 WELD/FAB SHOP HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-28 WELD/FAB SHOP HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-29 WELD/FAB SHOP HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-30 AERIAL BUCKET HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-31 AERIAL BUCKET HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
UH-32 MECH PLATFORM HORIZ 153.9 5500 0 105 1075 1_2 2.6 208 3 H20 15.6 140 110 0.85 TRANE S-360 SERIES 1 THRU 5
NOTES:1 REFER TO SPECIFICATIONS, DETAILS, AND CONTROL DRAWINGS FOR ADDITIONAL INFORMATION.2 PROVIDE MINIMUM OF 20 GAUGE STEEL CASING PAINTED WITH A CORROSION RESISTANT, BAKED, POLYESTER POWDER COATED FINISH.3 PROVIDE FULLY ADJUSTABLE AIR DEFLECTORS AND OSHA APPROVED FAN GUARD.4 PROVIDE ALUMINUM FINS AND COPPER TUBE COILS.5 PROVIDE FACTORY WALL MOUNTED THERMOSTAT.6 PROVIDE AS EXPLOSION PROOF
SCALE
CHECKED BY:
PROJECT TITLEDESIGNER/DRAFTER PROJECT NO.
DRAWING NO.
SHEET NO.
TOWN
DRAWING TITLE
THE INFORMATION, INCLUDING ESTIMATEDQUANTITIES OF WORK, SHOWN ON THESESHEETS IS BASED ON LIMITEDINVESTIGATIONS BY THE STATE AND ISIN NO WAY WARRANTED TO INDICATETHE CONDITIONS OF ACTUAL QUANTITIESOF WORK WHICH WILL BE REQUIRED.
File Name:Plotted:
STATE OF CONNECTICUTDEPARTMENT OF TRANSPORTATION
SIGNATURE/BLOCK:
MPFP_CTDOT_Rocky Hill Repair Facility_Central.rvt
1/8" = 1'-0"10/21/2014 3:32:11 PM
TFC REPAIR FACILITY
WJS 118-0167
MEC-701
MECHANICAL SCHEDULES II
ROCKY HILL
NO. Revision Description Date 10.39
– For Internal CTDOT Use Only Discipline Subset Submittal Checklist
The following check list shall be checked and attached to each discipline subset *
prior to being digitally signed.
Check Task Section in DPD Manual
1. Attach this checklist to the discipline subset. Section 3.1
2. Complete the following tasks using Bluebeam on
the discipline subset?
a. Apply Page Labels Section 1.6.2
b. Apply Sheet Numbers Section 1.6.2
c. Apply Watermark Section 2.4
d. Flatten Markups Section 2.4
e. Digital Signature Field Section 2.5.1
3. Type name and telephone number below. 4. Consultants using Thin Client Only
Engineer of Record digitally sign the plans.
5. Upload, if not in Projectwise already, the
discipline subset into the 100_Contract_Plans folder in Projectwise and attribute the document
correctly?
Section 3.2.4
a. Discipline = CT
b. Main Category = CON
c. Sub Category = FDP, DCD, DCD2,
ADP, ACD, DCO where applicable d. Label = subset number and name.
Example of highways subset would be 03-Highways.
The label for a subset shall be the
same for both FDP and DCD submittals.
Addendum submittals shall match FDP submittals with the addition of “_A#”.
Change Order Submittals shall match FDP submittals with the addition of “_C#”. e. Description field is filled in with
a description of the subset. f. The applicable bridge no.(s) or signal
intersection(s) were selected that is/are associated with this subset.
6.CTDOT Engineers or Consultants Using Thick Client Forward link to Engineer of Record for Digital Signature
7. Apply the QA/QC stamp after the discipline subset has been digitally signed.
Section 3.1
I have performed and checked that all the tasks above were performed correctly.
Submitted By (Type in Name) Phone Number (Type in Phone Number)
* Discipline subset includes the General subset and all other discipline subsets. The 02Revisions does not needa checklist attached. The standard subsets already have a checklist attached to the index sheets.