This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
100% Outside Air and Dehumidification
Management
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
100% Outside Air - What is it ?
• Referred to as “Make-up Air”– Unit operates continually during occupied
mode– Replaces exhausted air– No mixture with return air– Totally changing load
• Summer design (High temperature and high humidity)
• Winter design (Cold temperature)
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
Why 100% Outside Air?
• Ventilation standards indicating recommended air changes for a variety of space usages and occupancy have been established by ASHRAE. The ventilation requirements for a given structure or space are based either on desired number of air changes or the number of occupants.
• The amount of outside air fresh air required for each change per hour equals the amount of inside air that must be removed from the space during the same time span.
• CFM= Area of space / Minutes of air changes
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
Ventilation Requirements (continued)
• College classroom 8 air changes 20-30 cfm/person• Hospitals 9-17 air changes 40-50
cfm/person• Kitchens 10-20 air changes 40-50
cfm/person• Schools 8-12 air changes 30-35
cfm/person• Theaters 5-10 air changes 10-15
cfm/person• Factory Buildings 10-15 air changes 25-30
cfm/person
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
•Return Air Ducts –Typically will not affect space conditions– May not require Reheat– Control is not as critical
•Direct to Space–Usually applied to large areas
•(Auditoriums, Kitchens, Corridors)
– More precise control is necessary– Reheat is required for control
Applications of Make-Up Air
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
100% Outside Air “Supply Air Properties”
• Unit discharge air properties– Main purpose – positively impact building
humidity• Lowest dew point possible
– Ideally close to room (neutral) conditions• Typically between 68 -72 degrees• Not to overcool or overheat space
– Below 70% RH per ASHRAE standards
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
Dew Point Comparison Reheating to Neutral Air
DRY BULB TEMPERATURE - °F
70°F 72°F 75°F
DEW POINT RELATIVE HUMIDITY – RH %
45°F 40.6 37.9 34.3
50°F 49 45.8 41.4
55°F 58.9 55.1 49.8
60°F 70.6 65.9 59.6
65°F 84.2 78.6 71.1
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
Air Control
• Leaving Air Control– Hot Gas Reheat
• Cycling Control• Modulating Control
• Room Control– Hot Gas Reheat
• Cycling in conjunction with a reheat thermostat• Modulating in conjunction with a reheat sensor
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
100 % Outside Air - Room Reheat Control
Reheat Control - room thermostat in series with
discharge thermostat
(neutral or cold air)
T
T
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
Compressors Usage
• Single Compressor -- Single Circuit – Used when low dew point in required– Dehumidifies all the air all of the time
• Dual Circuits – Single Compress each circuit– Used when leaving air conditions are not critical– Air will bypass lag circuit and then mix with lead circuit
• Dual Circuits – Two compressors (Tandem) each circuit)– Lag compressor cycles based on suction pressure.– Four (4) stage operation– Large Tonnage
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
“Refrigeration” Control• Hot Gas Bypass
– Modulates to match the evaporator load– Evaporator freeze protection– Suction pressure activated
• Hot Gas Reheat – Raises leaving air temperature to room neutral conditions– Cycling with discharge air thermostat– Modulating with sensor.
• Liquid Subcool Coil– Raises leaving air temperature– Subcools liquid– Two (2) degrees of subcool equals one (1) percent increase
in evaporator capacity
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
Standard Cycling Hot Gas Reheat
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
Hot Gas Reheat Plus Sub-Cooling
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
Hot Gas Reheat Using Digital Scroll
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
100% Outside Air Example
• Summer design
– 1800 cfm– 92/75 ambient– Leaving air
• 55 deg Dew Point• 65 deg leaving air temperature
• Winter design– 0 degree ambient– Leaving air (minimum 70 deg)
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
100% Outside Air Summer Design w/Reheat
Ambient92/75
Supply Temp.55.0/55.0
Leaving Air79.7/64.1 10 ton
1800 cfm
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
100% Outside Air Summer Design w/Reheat Plus
Ambient92/75
Supply Temp.52.2 D.P.
Leaving Air90.5/67.7
10 ton
1800 cfm
Liq. Sub-cool66.1/59.4
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
100% Outside Air Summer Part Load w/Reheat
Ambient75/75
Supply Temp.53.9 D.P.
Leaving Air86.1/64.3
10 ton
1800 cfm
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
100% Outside AirPart Load w/Reheat Plus
Ambient75/75
Supply Temp.50.8 D.P.
Leaving Air94.0/67.1
10 ton
1800 cfm
Liq. Sub-cool65.7/58.8
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
100% Outside AirSummer Part Load w/Reheat
Ambient70/70
Supply Temp.48.8/48.8
Leaving Air79.5/61.2 10 ton
1800 cfm
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
100% Outside AirPart Load w/Reheat Plus
Ambient70/70
Supply Temp.48.1 D.P.
Leaving Air83.1/64.3
10 ton
1800 cfm
Liq. Sub-cool59.9/54.3
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
100% Outside AirSummer Part Load w/Reheat
Ambient65/65
Supply Temp.46.8/46.8
Leaving Air73.7/63.8
10 ton
1800 cfm
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
100% Outside AirPart Load w/Reheat Plus
Ambient
65/65
Supply Temp.
47.0 D.P.
Leaving Air79.4/61.0
10 ton
1800 cfm
Liq. Sub-cool55.8/51.5
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
100% Outside AirSummer Part Load w/Reheat
Ambient60/60
Supply Temp.51.4/51.4
Leaving Air64.3/56.2
10 ton
1800cfm
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
100% Outside AirPart Load w/Reheat Plus
Ambient60/60
Supply Temp.50.4 D.P.
Leaving Air72.6/57.4
10 ton
1800 cfm
Liq. Sub-cool55.2/52.1
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
100% Outside AirWinter Design Conditions
Ambient0
Leaving Air72 10 ton
1800 cfm
175,000 BTUH Furnace
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
Recap
• Do No Harm– Dehumidify to 55 0 Dew Point or less.– Reheat to Room Neutral.– Temper to Room Neutral– Possible humidify when ambient
temperatures are below 35 0
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
Energy Conservation Wheel Applications
• Require exhaust air from the building
• Require defrost in most areas
• Total Unit EER can exceed 25 on some water source heat pump applications
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
Load Reduction Example:
Dedicated Outdoor Air
Cooling Dehum. Cooling Dehum.
(db / wb) 93.9 / 74.8 82.0 / 76.4 93.9 / 74.8 82.0 / 76.4(enthalpy) 38.22 39.91 38.22 39.91(db / wb) --- --- 80.7 / 67.0 77.1 / 67.6(enthalpy) --- --- 31.50 32.02(db / wb) 52.0 / 52.0 52.0 / 52.0 52.0 / 52.0 52.0 / 52.0(enthalpy) 21.43 21.43 21.43 21.43
196.58 206.61-40.0% -42.7%136.49 119.37-31.5% -16.3%60.09 87.24
-53.2% -60.0%
Outdoor Air (db)
ECW Supply Air (db)
Unit Supply Air (db)
Cooling Mode
MBH
MBH
Outdoor Air
ECW Supply Air
Evaporator Discharge Air
Total Capacity
Sensible Capacity
Latent Capacity
142.67
128.36MBH
Heating Capacity
ASHRAE Design Conditions for Atlanta, GA
MBH97.31
---
321.30-69.7%
48.870
Heating Mode
100% OA w/ Energy Conservation Wheel
70
0
327.62 360.63
199.26
0
100% OA
217.96
Loads based on:• 4250 cfm supply and exhaust airflow• 48” Energy Conservation Wheel• 75F/ 50%RH summer exhaust air• 70F / 30%RH winter exhaust
•Source: www.novelaire.com (graphic)
This document is intended to assist licensed professionals in the exercise of their professional judgment.
2011 Addison
for your attention