+ All Categories
Home > Documents > 100% Outside Air and Dehumidification Management

100% Outside Air and Dehumidification Management

Date post: 04-Jan-2016
Category:
Upload: wilmet
View: 34 times
Download: 2 times
Share this document with a friend
Description:
100% Outside Air and Dehumidification Management. 100% Outside Air - What is it ?. Referred to as “Make-up Air” Unit operates continually during occupied mode Replaces exhausted air No mixture with return air Totally changing load Summer design (High temperature and high humidity) - PowerPoint PPT Presentation
30
This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison 100% Outside Air and Dehumidification Management
Transcript
Page 1: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

100% Outside Air and Dehumidification

Management

Page 2: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

100% Outside Air - What is it ?

• Referred to as “Make-up Air”– Unit operates continually during occupied

mode– Replaces exhausted air– No mixture with return air– Totally changing load

• Summer design (High temperature and high humidity)

• Winter design (Cold temperature)

Page 3: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

Why 100% Outside Air?

• Ventilation standards indicating recommended air changes for a variety of space usages and occupancy have been established by ASHRAE. The ventilation requirements for a given structure or space are based either on desired number of air changes or the number of occupants.

• The amount of outside air fresh air required for each change per hour equals the amount of inside air that must be removed from the space during the same time span.

• CFM= Area of space / Minutes of air changes

Page 4: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

Ventilation Requirements (continued)

• College classroom 8 air changes 20-30 cfm/person• Hospitals 9-17 air changes 40-50

cfm/person• Kitchens 10-20 air changes 40-50

cfm/person• Schools 8-12 air changes 30-35

cfm/person• Theaters 5-10 air changes 10-15

cfm/person• Factory Buildings 10-15 air changes 25-30

cfm/person

Page 5: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

•Return Air Ducts –Typically will not affect space conditions– May not require Reheat– Control is not as critical

•Direct to Space–Usually applied to large areas

•(Auditoriums, Kitchens, Corridors)

– More precise control is necessary– Reheat is required for control

Applications of Make-Up Air

Page 6: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

100% Outside Air “Supply Air Properties”

• Unit discharge air properties– Main purpose – positively impact building

humidity• Lowest dew point possible

– Ideally close to room (neutral) conditions• Typically between 68 -72 degrees• Not to overcool or overheat space

– Below 70% RH per ASHRAE standards

Page 7: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

Dew Point Comparison Reheating to Neutral Air

DRY BULB TEMPERATURE - °F

70°F 72°F 75°F

DEW POINT RELATIVE HUMIDITY – RH %

45°F 40.6 37.9 34.3

50°F 49 45.8 41.4

55°F 58.9 55.1 49.8

60°F 70.6 65.9 59.6

65°F 84.2 78.6 71.1

Page 8: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

Air Control

• Leaving Air Control– Hot Gas Reheat

• Cycling Control• Modulating Control

• Room Control– Hot Gas Reheat

• Cycling in conjunction with a reheat thermostat• Modulating in conjunction with a reheat sensor

Page 9: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

100 % Outside Air - Room Reheat Control

Reheat Control - room thermostat in series with

discharge thermostat

(neutral or cold air)

T

T

Page 10: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

Compressors Usage

• Single Compressor -- Single Circuit – Used when low dew point in required– Dehumidifies all the air all of the time

• Dual Circuits – Single Compress each circuit– Used when leaving air conditions are not critical– Air will bypass lag circuit and then mix with lead circuit

• Dual Circuits – Two compressors (Tandem) each circuit)– Lag compressor cycles based on suction pressure.– Four (4) stage operation– Large Tonnage

Page 11: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

“Refrigeration” Control• Hot Gas Bypass

– Modulates to match the evaporator load– Evaporator freeze protection– Suction pressure activated

• Hot Gas Reheat – Raises leaving air temperature to room neutral conditions– Cycling with discharge air thermostat– Modulating with sensor.

• Liquid Subcool Coil– Raises leaving air temperature– Subcools liquid– Two (2) degrees of subcool equals one (1) percent increase

in evaporator capacity

Page 12: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

Standard Cycling Hot Gas Reheat

Page 13: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

Hot Gas Reheat Plus Sub-Cooling

Page 14: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

Hot Gas Reheat Using Digital Scroll

Page 15: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

100% Outside Air Example

• Summer design

– 1800 cfm– 92/75 ambient– Leaving air

• 55 deg Dew Point• 65 deg leaving air temperature

• Winter design– 0 degree ambient– Leaving air (minimum 70 deg)

Page 16: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

100% Outside Air Summer Design w/Reheat

Ambient92/75

Supply Temp.55.0/55.0

Leaving Air79.7/64.1 10 ton

1800 cfm

Page 17: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

100% Outside Air Summer Design w/Reheat Plus

Ambient92/75

Supply Temp.52.2 D.P.

Leaving Air90.5/67.7

10 ton

1800 cfm

Liq. Sub-cool66.1/59.4

Page 18: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

100% Outside Air Summer Part Load w/Reheat

Ambient75/75

Supply Temp.53.9 D.P.

Leaving Air86.1/64.3

10 ton

1800 cfm

Page 19: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

100% Outside AirPart Load w/Reheat Plus

Ambient75/75

Supply Temp.50.8 D.P.

Leaving Air94.0/67.1

10 ton

1800 cfm

Liq. Sub-cool65.7/58.8

Page 20: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

100% Outside AirSummer Part Load w/Reheat

Ambient70/70

Supply Temp.48.8/48.8

Leaving Air79.5/61.2 10 ton

1800 cfm

Page 21: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

100% Outside AirPart Load w/Reheat Plus

Ambient70/70

Supply Temp.48.1 D.P.

Leaving Air83.1/64.3

10 ton

1800 cfm

Liq. Sub-cool59.9/54.3

Page 22: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

100% Outside AirSummer Part Load w/Reheat

Ambient65/65

Supply Temp.46.8/46.8

Leaving Air73.7/63.8

10 ton

1800 cfm

Page 23: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

100% Outside AirPart Load w/Reheat Plus

Ambient

65/65

Supply Temp.

47.0 D.P.

Leaving Air79.4/61.0

10 ton

1800 cfm

Liq. Sub-cool55.8/51.5

Page 24: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

100% Outside AirSummer Part Load w/Reheat

Ambient60/60

Supply Temp.51.4/51.4

Leaving Air64.3/56.2

10 ton

1800cfm

Page 25: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

100% Outside AirPart Load w/Reheat Plus

Ambient60/60

Supply Temp.50.4 D.P.

Leaving Air72.6/57.4

10 ton

1800 cfm

Liq. Sub-cool55.2/52.1

Page 26: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

100% Outside AirWinter Design Conditions

Ambient0

Leaving Air72 10 ton

1800 cfm

175,000 BTUH Furnace

Page 27: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

Recap

• Do No Harm– Dehumidify to 55 0 Dew Point or less.– Reheat to Room Neutral.– Temper to Room Neutral– Possible humidify when ambient

temperatures are below 35 0

Page 28: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

Energy Conservation Wheel Applications

• Require exhaust air from the building

• Require defrost in most areas

• Total Unit EER can exceed 25 on some water source heat pump applications

Page 29: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

Load Reduction Example:

Dedicated Outdoor Air

Cooling Dehum. Cooling Dehum.

(db / wb) 93.9 / 74.8 82.0 / 76.4 93.9 / 74.8 82.0 / 76.4(enthalpy) 38.22 39.91 38.22 39.91(db / wb) --- --- 80.7 / 67.0 77.1 / 67.6(enthalpy) --- --- 31.50 32.02(db / wb) 52.0 / 52.0 52.0 / 52.0 52.0 / 52.0 52.0 / 52.0(enthalpy) 21.43 21.43 21.43 21.43

196.58 206.61-40.0% -42.7%136.49 119.37-31.5% -16.3%60.09 87.24

-53.2% -60.0%

Outdoor Air (db)

ECW Supply Air (db)

Unit Supply Air (db)

Cooling Mode

MBH

MBH

Outdoor Air

ECW Supply Air

Evaporator Discharge Air

Total Capacity

Sensible Capacity

Latent Capacity

142.67

128.36MBH

Heating Capacity

ASHRAE Design Conditions for Atlanta, GA

MBH97.31

---

321.30-69.7%

48.870

Heating Mode

100% OA w/ Energy Conservation Wheel

70

0

327.62 360.63

199.26

0

100% OA

217.96

Loads based on:• 4250 cfm supply and exhaust airflow• 48” Energy Conservation Wheel• 75F/ 50%RH summer exhaust air• 70F / 30%RH winter exhaust

•Source: www.novelaire.com (graphic)

Page 30: 100% Outside Air and Dehumidification Management

This document is intended to assist licensed professionals in the exercise of their professional judgment.

2011 Addison

for your attention


Recommended