    Synchronous GeneratorOperation

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    2/29

    Effect of Generator Loads Lagging Power Factor

    If lagging loads (+Q or inductive reactive power loads) are added to a generator,the phase voltage V f and the terminal voltage V T decrease.

    Keep field excitation the same'

    A A E E

    A s A jX f E V I

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    3/29

    Effect of Generator Loads Unity Power Factor

    A s A jX f E V I

    If unity-power-factor loads (no reactive power) are added to a generator,the phase voltage V f and the terminal voltage V T slightly decrease.

    Keep field excitation the same'

    A A E E

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    4/29

    Effect of Generator Loads Leading Power Factor

    A s A jX f E V I

    If leading loads (-Q or capacitive reactive power loads) are added to a generator,the phase voltage V f and the terminal voltage V T may increase.

    Keep field excitation the same'

    A A E E

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    5/29

    Generator Voltage Regulation

    100%nl fl

    fl

    V V VRV

    Lagging Load -> large positive voltage regulationUnit Power Factor Load -> small positive voltage regulationLeading load -> may be negative voltage regulation

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    6/29

    Generator V Curves

    The shape is like the letter V For each fixed real power, plot

    armature current vs. fieldcurrent.

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    7/29

    Example 1 (1)

    A 480 V, 60 Hz, D connected, four pole synchronous generator has the OCC curve shown in the figure.

    This generator has a synchronous reactance of 0.1 W and an armature resistance of 0.015 W .At full load, the machine supplies 1200 A at 0.8 PF lagging. Under full load conditions, the frictionand windage losses are 40 kW, and the core losses are 30 kW. Ignore any field circuit losses.

    (a) What is the speed of rotation of this generator?(b) How much field current must be supplied to the generator to make the terminal voltage 480 V at

    no load?(c) If the generator is now connected to a load and the load draws 1200 A at 0.8 PF lagging, how much

    field current is required to keep the terminal voltage equal to 480 V?(d) How much power is the generator now supplying? How much power is supplied to the generator

    by the prime mover? What is the machines overall efficiency? (e) If the generators load were suddenly disconnected from the line, what would happen to its

    terminal voltage?(f) Finally, suppose that the generator is connected to a load drawing 1200 A at 0.8 PF leading , howmuch field current would be required to keep V T at 480 V?

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    8/29

    Example 1 (2)

    sg1.m

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    9/29

    Example 2 (1)

    After the MatLab program can work, please change the load current to be 60 Aat 1.0 PF, and 60 A at 0.8 PF leading and redo the above.

    A 480V, 60 Hz, Y connected, six pole synchronous generator has a synchronous reactance of 1 W and

    an armature resistance of 0.1W

    .

    At full load, the machine supplies 60 A at 0.8 PF lagging. Under full load conditions, the frictionand windage losses are 1.5 kW, and the core losses are 1.0 kW. Ignore any field circuit losses.

    (a) What is the speed of rotation of this generator?(b) What is the terminal voltage of this generator at full load assuming the field excitation current

    keeps the same as no load?(c) What is the efficiency of this generator at full load?(d) How much shaft torque must be supplied by the prime mover at full load? How large is the

    induced counter torque?(e) What is the voltage regulation of this generator ?

    sg2.m

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    10/29

    Example 2 (2)

    s A s A A R jX f V I I Edq

    0 sin cos sin A A s A s A A

    R I X I E q q d I I

    Imaginary part of

    Let the angle of : =0.f f

    q VV

    becomes:

    cos sinsin A A s A s A

    A

    X I R I

    E

    q q d

    I I

    Note: is negative when current is lagging.

    cos cos sin A A A s A s A

    V E R I X I f d q q I I

    Aq

    I

    Af q q q V I

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    11/29

    Synchronous GeneratorCapability Curve

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    12/29

    Generator Capability Curves (1)

    (1) Stator Copper Loss (stator heating):

    (2) Rotor Copper Loss (rotor heating):

    (3) Prime- movers Power Limit.

    23SCL A s

    P I R

    2

    RCL F F P I R

    The maximum allowable heating of the rotor sets a maximumfield current I F for the machine. Its equivalent to set a maximum

    E A for the machine.

    The maximum allowable heating of the stator sets a maximum phase current I A for the machine. Its equivalent to set a maximum

    apparent power for the machine. (power factor is irrelevant)

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    13/29

    Generator Capability Curves (2)

    rotor field current sets the rated power factor

    (rotor heating)

    (stator heating)

    A s A jX f E V I

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    14/29

    Generator Capability Curves (3)

    A s A jX f E V I

    Assume V f keeps rated value. Multiply the above figure by3

    S

    V

    X f

    P

    Q

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    15/29

    Generator Capability Curves (4)

    P

    Q

    capability curve

    Q

    P

    flip

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    16/29

    Generator Capability Curves (5)

    Q

    P

    Add prime movers power limit (real power)

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    17/29

    Example 3

    sg3.m

    A 480V, 50 Hz, Y connected, six pole synchronous generator is rated at 50 kVA at 0.8 PF lagging. Ithas a synchronous reactance of 1.0 W per phase. Assume that this generator is connected to a steamturbine capable of supplying up to 45 kW. The friction and windage losses are 1.5 kW, and the corelosses are 1.0 kW.

    (a) Sketch the capability curve for this generator, including the prime-mover power limit.(b) Can this generator supply a line current of 56 A at 0.7 PF lagging? Why or why not?(c) What is the maximum amount of reactive power this generator can produce?(d) If the generator supplies 30 kW of real power, what is the maximum amount of reactive power that

    can be simultaneously supplied?

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    18/29

    Synchronous MotorOperation

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    19/29

    UCF Synchronous Motor and Generator (1)

    motor generator

    net Rind k BBT

    d sinnet Rind BkBT

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    20/29

    UCF Synchronous Motor and Generator (2)

    GeneratorMotor

    s A s A A R jX f V I I E s A s A A R jX f V I I E

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    21/29

    UCF Torque of Synchronous Motor

    d sinnet Rind BkBT

    A s A s A R jX f V E I I

    )(forsin3

    cos3

    s A s

    A

    A

    X R X

    E V

    I V P

    d

    q

    f

    f

    sin3 d f

    sm

    A

    mind X

    E V P T

    Pull-out torque: when sin d =1, the maximum torque the machine can get.net R BkBT max 3max

    sm

    A

    X

    E V T

    f

    omaxTypically take 3 (or sin 1 / 3, 19.47 )

    in the design (leave margin).

    full load T T d d

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    22/29

    UCF Effect of Load Change

    magnets) permanentusingorfixed(whenfixed:

    course)electrical(fromfixed: sin3cos3

    F A

    s

    A

    A

    I E

    V

    X

    E V

    I V P

    f

    f

    f d q

    2(load increases) sin more heat (3 )

    (leading lagging) A A s P I I Rd

    q

    q

    At full load, typically pick up cos 1 in the design.

    sin , cos A

    s A

    A

    V E

    X E I

    f

    q

    d d

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    23/29

    UCF Example 1

    Details in sm1.m

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    24/29

    UCF Effects of Field Current Change

    A s A s A

    A s A

    R jX jX

    f

    V E I I

    E I

    q

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    25/29

    UCF Underexcited Synchronous Motor

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    26/29

    UCF Overexcited Synchronous Motor

    Behaves like a capacitor: can be used for power factor correction.Called synchronous capacitor or synchronous condenser .

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    27/29

    UCF Synchronous Motor V Curves

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    28/29

    UCF Example 2

    sm2.m

  • 8/10/2019 11 Synchronous Generator and Motor Operation

    29/29

    UCF

    Power factor Correction Using OverexcitedSynchronous Motor - Example 3

    sm3.m