ON LOAD GEARS 11KV TAP CHANGER TYPE [A] ABS TECHNICAL DETAILS [A]ABS11 OLTC is air insulated, externally mounted On Load Tap Changer. This OLTC works on the principle of high speed transition resistance & is suitable for both star and delta connected dry type or oil less transformer winding with linear or change-over (coarse-fine/reverser) type tapping arrangement. It has 2 different models rated for 65 and 100Amps. (Refer tech. data for details). The OLTC follows the principle of flag cycle resulting in Bidirectional power flow The 65A tap changer may be used on star connected transformers up to 1.25MVA and on delta connected transformers up to 2MVA whereas 100A tap changer may be used up to 2MVA on star connected transformers and up to 3.3MVA on delta connected transformers. It can be used up to maximum 17 positions, when connected with a change-over switch. The compact design makes its operationally more efficient than any other tap changer in its voltage and current rating class. The complete tap-changer is housed in a sheet metal enclosure, where the drive mechanism and the selector switch chambers are separated by a metal sheet. The fixed contacts are mounted on phase boards, over which the moving contact moves and selects the tap. The selection of tap position in all the TECHNICAL DATA TRated voltage : 12kV Max.Rated through current : 100A Max.Rated step voltage : 250V Rated insulation level : 28kV power freq and 75kVP impulse Max.number of tapping positions : 17 with change over Power Switch three phases simultaneously by a selector switch. The selector switch combines the function of a tap selector and a diverter switch and has a main contact and an auxiliary contacts. The drive mechanism is coupled to the selector switch by drive shaft and series of gearsand has an energy storage device that releases energy to drive the selector switch. MOUNTING ON TRANSFORMER The tap changer is mounted on the transformer by taking out leads via the terminal board of the tap-changer, which is a part of OLG supply. PROTECTIVE DEVICE The tap-changer is protected by a smoke detector, positioned on the power switch chamber of the tap-changer. Selector Switch (2) Drive Mechanism (3) Terminal Board (9) CONSTRUCTION DETAILS
Transcript
Page 1: 11KV TAP CHANGER TYPE [A] ABS - On Load Gears

ON LOAD GEARS

11KV TAP CHANGER

TYPE [A] ABS

TECHNICAL DETAILS

[A]ABS11 OLTC is air insulated, externally mounted On Load Tap Changer. This OLTC works on the principle of high speed transition resistance & is suitable for both star and delta connected dry type or oil less transformer winding with linear or change-over (coarse-fine/reverser) type tapping arrangement. It has 2 different models rated for 65 and 100Amps. (Refer tech. data for details). The OLTC follows the principle of flag cycle resulting in Bidirectional power flow The 65A tap changer may be used on star connected transformers up to 1.25MVA and on delta connected transformers up to 2MVA whereas 100A tap changer may be used up to 2MVA on star connected transformers and up to 3.3MVA on delta connected transformers. It can be used up to maximum 17 positions, when connected with a change-over switch. The compact design makes its operationally more efficient than any other tap changer in its voltage and current rating class.

The complete tap-changer is housed in a sheet metal enclosure, where the drive mechanism and the selector switch chambers are separated by a metal sheet. The fixed contacts are mounted on phase boards, over which the moving contact moves and selects the tap. The selection of tap position in all the

TECHNICAL DATA

TRated voltage : 12kVMax.Rated through current : 100AMax.Rated step voltage : 250VRated insulation level : 28kV power freq and 75kVP impulseMax.number of tapping positions : 17 with change over

Power Switch

three phases simultaneously by a selector switch. The selector switch combines the function of a tap selector and a diverter switch and has a main contact and an auxiliary contacts. The drive mechanism is coupled to the selector switch by drive shaft and series of gearsand has an energy storage device that releases energy to drive the selector switch.

MOUNTING ON TRANSFORMER

The tap changer is mounted on the transformer by taking out leads via the terminal board of the tap-changer, which is a part of OLG supply.

PROTECTIVE DEVICE

The tap-changer is protected by a smoke detector, positioned on the power switch chamber of the tap-changer.

Selector Switch (2) Drive Mechanism (3) Terminal Board (9)

CONSTRUCTION DETAILS

Page 2: 11KV TAP CHANGER TYPE [A] ABS - On Load Gears

11KV TAP CHANGER

TYPE [A] ABS

ON LOAD GEARS432, 433, SIDCO Ambattur, Chennai - 600 098.Tel : +91-44-43935800, 4393 5811.Fax : +91-44-4393 5888

E-mail : [email protected]

TEST LEVELS

TESTINGAs per IEC 60214 and IS 8468 all type tests are successfully performed on this On-load tap-changer.

1. ALL DIMENSIONS ARE IN MM.(d) TRANSPORTATION DIMNS ARE MARKED

NOTE

NOTE:

(a) APPROX. WT. OF OLTC : - 380 KG

1.CRANK ENTRY GLAND PLATE

2.REMOVABLE CRANK HANDLE

3.PUSH BUTTON FOR RAISE AND LOWER

4.EARTHING BOSS

5.WINDOW FOR TAP NO & COUNTER

6.DOOR HANDLE

7.LIFTING LUG

8.POWER SWITCH CHAMBER

9.DRIVE MECHANISM

THUS X

1011

3

5

34

8

4

5

7

144

13

12

6

108

9 9

11

6

4

14

7 12 13

3

4

7

6

8

9

4

5

13

11

12

14

10

RATED CURRENT OLTC

ON LOAD TAPCHANGER TO I.S.8468

CHENNAI-600 098 - INDIA

CONNECTION DIAGRAM DRG. NO.

NUMBER OF SERVICE TAPPING POSITION

MOTOR VOLTAGE/FREQUENCY

CONTROL VOLTAGE/FREQUENCY

DIRECTION OF POWER FLOW.

REGD.OFFICE : 338,SIDCO ESTATE,AMBATTUR.

CLIENT REF.

TRANSFORMER RATING

RATED INSULATION LEVEL

TRANSITION RESISTANCE

RATED STEP VOLTAGE

SERIAL NUMBER

TYPE

V/50HZ

V/50HZ

KVP

V

YEAR OF MFR.

V

ATR.A

348.059.059.0

377.0

59.0

377.0

7

4

1

2

3

5

6

8

9

C

B

D

E

A

TECHNICAL DATA

Model No of Current Tap Transition Cycle Tap changer No positions rating in A arrangement Wt with oil

1 17 65 Change over Bi-directional flag 300 Kg

2 17 100 Change over Bi-directional flag 380 Kg

No of positions

17 position 100A

17 position 65A

1985 1450 996 752 940

A B C D E

1668 1200 996 752 940