    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 100 200 300 400 500 600 700

    450

    400

    350

    300

    250

    200

    150

    100

    50

    0

    Curve speed controlled to required duty (86.3%)

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataEST-X - Ecosmart External Duct Mounted Twinfan,Direct Drive, Single Phase

    Ecosmart External Duct Mounted TwinfanFan Code: EST5-XInstallation Manual Links: 671142

    Required Duty: 430 l/s @ 120 PaActual Duty: 498 l/s @ 160 PaActual at Required Flow: 430 l/s @ 221 Pa

    When Speed Controlled to Required Duty (86.3%):Motor Input Power: 0.349 kWSpecific Fan Power: 0.813 W/(l/s)

    Motor Input Power: 0.542 kWSpecific Fan Power: 1.09 W/(l/s)

    Nominal Fan Speed: 1,110 RPMElectrical Supply: 1 PhaseNominal Motor Rating: 0.66 kWMotor Current: flc: 2.95 A

    Motor Current: sc: 2.95 A

    Max. Operating Temp.: 40C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 35 dBA @ 3m (90% of Max Pa)Breakout level is hemi-spherical. For spherical deduct 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 72 67 56 47 46 47 45 40Induct Outlet 80 75 66 62 65 65 62 57Breakout 59 62 58 53 48 46 43 35

    Above noise calculated speed controlled to required duty (86.3%)For 100% Speed: +1 +1 +2 +2 +3 +3 +3 +3

    Breakout Noise (dBA): +5 (90% of Max Pa)Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Performance Curve

    Project DetailsDG TRANSPORT COMPLEX PH2Location: EF-1 - MAIN BUILDING

    SpecificationEcosmart external ducted twin fan unit manufactured fromaluzinc. All internal chamber surfaces are acoustically treated.Fan assemblies incorporate forward curved centrifugal impellersdirectly driven by BS5000 motors fitted with air flow fail monitors.Fans are suitable for operation in ambient temperatures up to40C. All units are suitable for internal and external use and maybe installed up to a maximum angle of 5. (Care must be taken toensure the back draught dampers operate correctly). The fanshould be fitted with an Ecosmart control together with an inverterspeed controller. The fan shall have the following energy savingfunctions integrally mounted within the fan unit on a purposemade PCB, all components pre-wired by the manufacturer:integral maximum and minimum speed adjustment/setting;integral auto-changeover/duty share, fans changeover every 12

    hours of run time; integral adjustable run on timer; integral BMSinterfaces, 0-10v and volt free failure indication.

    Fan Dimensions

    A B C D kgmm: 1,165 980 575 400 75

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671142 attached to this document.

    http://www.nuaire.co.uk/iandm/nl/671142.pdfhttp://www.nuaire.co.uk/iandm/nl/671142.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    2/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 100 200 300 400 500 600 700

    450

    400

    350

    300

    250

    200

    150

    100

    50

    0

    Curve speed controlled to required duty (86.3%)

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataEST-X - Ecosmart External Duct Mounted Twinfan,Direct Drive, Single Phase

    Ecosmart External Duct Mounted TwinfanFan Code: EST5-XInstallation Manual Links: 671142

    Required Duty: 430 l/s @ 120 PaActual Duty: 498 l/s @ 160 PaActual at Required Flow: 430 l/s @ 221 Pa

    When Speed Controlled to Required Duty (86.3%):Motor Input Power: 0.349 kWSpecific Fan Power: 0.813 W/(l/s)

    Motor Input Power: 0.542 kWSpecific Fan Power: 1.09 W/(l/s)

    Nominal Fan Speed: 1,110 RPMElectrical Supply: 1 PhaseNominal Motor Rating: 0.66 kWMotor Current: flc: 2.95 A

    Motor Current: sc: 2.95 A

    Max. Operating Temp.: 40C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 35 dBA @ 3m (90% of Max Pa)Breakout level is hemi-spherical. For spherical deduct 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 72 67 56 47 46 47 45 40Induct Outlet 80 75 66 62 65 65 62 57Breakout 59 62 58 53 48 46 43 35

    Above noise calculated speed controlled to required duty (86.3%)For 100% Speed: +1 +1 +2 +2 +3 +3 +3 +3

    Breakout Noise (dBA): +5 (90% of Max Pa)Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Performance Curve

    Project DetailsDG TRANSPORT COMPLEX PH2Location: EF-2 - MAIN BUILDING

    SpecificationEcosmart external ducted twin fan unit manufactured fromaluzinc. All internal chamber surfaces are acoustically treated.Fan assemblies incorporate forward curved centrifugal impellersdirectly driven by BS5000 motors fitted with air flow fail monitors.Fans are suitable for operation in ambient temperatures up to40C. All units are suitable for internal and external use and maybe installed up to a maximum angle of 5. (Care must be taken toensure the back draught dampers operate correctly). The fanshould be fitted with an Ecosmart control together with an inverterspeed controller. The fan shall have the following energy savingfunctions integrally mounted within the fan unit on a purposemade PCB, all components pre-wired by the manufacturer:integral maximum and minimum speed adjustment/setting;integral auto-changeover/duty share, fans changeover every 12

    hours of run time; integral adjustable run on timer; integral BMSinterfaces, 0-10v and volt free failure indication.

    Fan Dimensions

    A B C D kgmm: 1,165 980 575 400 75

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671142 attached to this document.

    http://www.nuaire.co.uk/iandm/nl/671142.pdfhttp://www.nuaire.co.uk/iandm/nl/671142.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    3/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 200 400 600 800

    400

    350

    300

    250

    200

    150

    100

    50

    0

    Curve speed controlled to required duty (87.2%)

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataEST-X - Ecosmart External Duct Mounted Twinfan,Direct Drive, Single Phase

    Ecosmart External Duct Mounted TwinfanFan Code: EST6-XInstallation Manual Links: 671142

    Required Duty: 580 l/s @ 120 PaActual Duty: 665 l/s @ 157 PaActual at Required Flow: 580 l/s @ 221 Pa

    When Speed Controlled to Required Duty (87.2%):Motor Input Power: 0.607 kWSpecific Fan Power: 1.047 W/(l/s)

    Motor Input Power: 0.915 kWSpecific Fan Power: 1.376 W/(l/s)

    Nominal Fan Speed: 1,272 RPMElectrical Supply: 1 PhaseNominal Motor Rating: 1.11 kWMotor Current: flc: 4.84 A

    Motor Current: sc: 4.84 A

    Max. Operating Temp.: 40C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 42 dBA @ 3m (90% of Max Pa)Breakout level is hemi-spherical. For spherical deduct 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 77 70 62 53 55 55 52 45Induct Outlet 84 75 66 65 68 68 65 57Breakout 68 69 65 60 56 54 50 45

    Above noise calculated speed controlled to required duty (87.2%)For 100% Speed: +1 +1 +1 +2 +3 +3 +3 +3

    Breakout Noise (dBA): +5 (90% of Max Pa)Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Performance Curve

    Project DetailsDG TRANSPORT COMPLEX PH2Location: EF-3 - MAIN BUILDING

    SpecificationEcosmart external ducted twin fan unit manufactured fromaluzinc. All internal chamber surfaces are acoustically treated.Fan assemblies incorporate forward curved centrifugal impellersdirectly driven by BS5000 motors fitted with air flow fail monitors.Fans are suitable for operation in ambient temperatures up to40C. All units are suitable for internal and external use and maybe installed up to a maximum angle of 5. (Care must be taken toensure the back draught dampers operate correctly). The fanshould be fitted with an Ecosmart control together with an inverterspeed controller. The fan shall have the following energy savingfunctions integrally mounted within the fan unit on a purposemade PCB, all components pre-wired by the manufacturer:integral maximum and minimum speed adjustment/setting;integral auto-changeover/duty share, fans changeover every 12

    hours of run time; integral adjustable run on timer; integral BMSinterfaces, 0-10v and volt free failure indication.

    Fan Dimensions

    A B C D kgmm: 1,165 980 575 400 86

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671142 attached to this document.

    http://www.nuaire.co.uk/iandm/nl/671142.pdfhttp://www.nuaire.co.uk/iandm/nl/671142.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    4/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire International, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom.

    Tel:+44 (0)29 2085 8200 Fax:+44 (0)29 2085 8300 email:[email protected] the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 50 100 150 200

    500

    450

    400

    350

    300

    250

    200

    150

    100

    50

    0

    Curve speed controlled to required duty (85.3%)

    Volume Flow Rate (l/s)

    Static

    Pressure

    (Pa)

    Technical DataNALT-H - High Performance In-line Centrifugal FanHigh Performance In-line Centrifugal Fan

    Fan Code: NALT-150HInstallation Manual Links: 671372

    Required Duty: 140 l/s @ 80 PaActual Duty: 164 l/s @ 109 PaActual at Required Flow: 140 l/s @ 178 Pa

    Nominal Fan Speed: 2,700 RPMElectrical Supply: 1 PhaseNominal Motor Rating: 0.12 kWMotor Current: flc: 0.53 A

    Max. Operating Temp.: -60C to +60C

    Sound DataBreakout Noise (dBA): 48 dBA @ 3mBreakout level is hemi-spherical. For spherical deduct 3 dBA.

    Above noise calculated speed controlled to required duty (85.3%)For 100% Speed: +1 +2 +2 +3 +3 +3 +3Breakout Noise (dBA): +2

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671372 attached to this document.

    Performance Curve

    Project DetailsDG TRANSPORT COMPLEX PH2Location: EF-4 - MAIN BUILDING

    Selected Ancillaries1 x NALTUBE-BRKT Mounting bracket

    SpecificationCircular in-line duct centrifugal fans, manufactured from highgrade corrosion resistant pressed galvanised steel. All models aresupplied as standard with a pre-wired junction box. All modelsinclude an enclosed type single-phase external rotor motor withfactory matched backward curved non-standing impeller. Suitablefor operating in temperatures 60up to +60. IP44, Class Binsulation, and all motors include an internal safety thermaloverload protection devise as standard. All models are fully speedcontrollable using either electronic or autotransformer voltageregulations controllers.

    Fan Dimensions

    A B C D kg

    mm: 214 24 333 147 5The drawing is for dimensional purposes only.

    http://www.nuaire.co.uk/iandm/nl/671372.pdfhttp://www.nuaire.co.uk/iandm/nl/671372.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    5/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire International, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom.

    Tel:+44 (0)29 2085 8200 Fax:+44 (0)29 2085 8300 email:[email protected] the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 50 100 150 200

    500

    450

    400

    350

    300

    250

    200

    150

    100

    50

    0

    Curve speed controlled to required duty (85.3%)

    Volume Flow Rate (l/s)

    Static

    Pressure

    (Pa)

    Technical DataNALT-H - High Performance In-line Centrifugal FanHigh Performance In-line Centrifugal Fan

    Fan Code: NALT-150HInstallation Manual Links: 671372

    Required Duty: 140 l/s @ 80 PaActual Duty: 164 l/s @ 109 PaActual at Required Flow: 140 l/s @ 178 Pa

    Nominal Fan Speed: 2,700 RPMElectrical Supply: 1 PhaseNominal Motor Rating: 0.12 kWMotor Current: flc: 0.53 A

    Max. Operating Temp.: -60C to +60C

    Sound DataBreakout Noise (dBA): 48 dBA @ 3mBreakout level is hemi-spherical. For spherical deduct 3 dBA.

    Above noise calculated speed controlled to required duty (85.3%)For 100% Speed: +1 +2 +2 +3 +3 +3 +3Breakout Noise (dBA): +2

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671372 attached to this document.

    Performance Curve

    Project DetailsDG TRANSPORT COMPLEX PH2Location: EF-5 - MAIN BUILDING

    Selected Ancillaries1 x NALTUBE-BRKT Mounting bracket

    SpecificationCircular in-line duct centrifugal fans, manufactured from highgrade corrosion resistant pressed galvanised steel. All models aresupplied as standard with a pre-wired junction box. All modelsinclude an enclosed type single-phase external rotor motor withfactory matched backward curved non-standing impeller. Suitablefor operating in temperatures 60up to +60. IP44, Class Binsulation, and all motors include an internal safety thermaloverload protection devise as standard. All models are fully speedcontrollable using either electronic or autotransformer voltageregulations controllers.

    Fan Dimensions

    A B C D kg

    mm: 214 24 333 147 5The drawing is for dimensional purposes only.

    http://www.nuaire.co.uk/iandm/nl/671372.pdfhttp://www.nuaire.co.uk/iandm/nl/671372.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    6/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 100 200 300 400

    350

    300

    250

    200

    150

    100

    50

    0

    Curve speed controlled to required duty (91.0%)

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataEST-X - Ecosmart External Duct Mounted Twinfan,Direct Drive, Single Phase

    Ecosmart External Duct Mounted TwinfanFan Code: EST4-XInstallation Manual Links: 671142

    Required Duty: 265 l/s @ 120 PaActual Duty: 291 l/s @ 144 PaActual at Required Flow: 265 l/s @ 165 Pa

    When Speed Controlled to Required Duty (91%):Motor Input Power: 0.239 kWSpecific Fan Power: 0.901 W/(l/s)

    Motor Input Power: 0.316 kWSpecific Fan Power: 1.086 W/(l/s)

    Nominal Fan Speed: 1,140 RPMElectrical Supply: 1 PhaseNominal Motor Rating: 0.37 kWMotor Current: flc: 1.6 A

    Motor Current: sc: 1.6 A

    Max. Operating Temp.: 40C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 31 dBA @ 3m (90% of Max Pa)Breakout level is hemi-spherical. For spherical deduct 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 73 67 58 50 47 44 40 33Induct Outlet 81 75 63 60 64 59 56 51Breakout 58 58 55 50 46 40 39 35

    Above noise calculated speed controlled to required duty (91%)For 100% Speed: +0 +1 +1 +1 +2 +2 +2 +2

    Breakout Noise (dBA): +6 (90% of Max Pa)Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Performance Curve

    Project DetailsDG TRANSPORT COMPLEX PH2Location: EF-6 - MAIN BUILDING

    SpecificationEcosmart external ducted twin fan unit manufactured fromaluzinc. All internal chamber surfaces are acoustically treated.Fan assemblies incorporate forward curved centrifugal impellersdirectly driven by BS5000 motors fitted with air flow fail monitors.Fans are suitable for operation in ambient temperatures up to40C. All units are suitable for internal and external use and maybe installed up to a maximum angle of 5. (Care must be taken toensure the back draught dampers operate correctly). The fanshould be fitted with an Ecosmart control together with an inverterspeed controller. The fan shall have the following energy savingfunctions integrally mounted within the fan unit on a purposemade PCB, all components pre-wired by the manufacturer:integral maximum and minimum speed adjustment/setting;integral auto-changeover/duty share, fans changeover every 12

    hours of run time; integral adjustable run on timer; integral BMSinterfaces, 0-10v and volt free failure indication.

    Fan Dimensions

    A B C D kgmm: 1,165 980 575 250 72

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671142 attached to this document.

    http://www.nuaire.co.uk/iandm/nl/671142.pdfhttp://www.nuaire.co.uk/iandm/nl/671142.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    7/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire International, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom.

    Tel:+44 (0)29 2085 8200 Fax:+44 (0)29 2085 8300 email:[email protected] the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 20 40 60 80

    400

    350

    300

    250

    200

    150

    100

    50

    0

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataNALT-H - High Performance In-line Centrifugal FanHigh Performance In-line Centrifugal Fan

    Fan Code: NALT-100HInstallation Manual Links: 671372

    Required Duty: 60 l/s @ 60 PaActual Duty: 67 l/s @ 75 PaActual at Required Flow: 60 l/s @ 118 Pa

    Nominal Fan Speed: 2,500 RPMElectrical Supply: 1 PhaseNominal Motor Rating: 0.078 kWMotor Current: flc: 0.33 A

    Max. Operating Temp.: -60C to +60C

    Sound DataBreakout Noise (dBA): 47 dBA @ 3mBreakout level is hemi-spherical. For spherical deduct 3 dBA.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671372 attached to this document.

    Performance Curve

    Project DetailsDG TRANSPORT COMPLEX PH2Location: EF-7 - MAIN BUILDING

    Selected Ancillaries1 x NALTUBE-BRKT Mounting bracket

    SpecificationCircular in-line duct centrifugal fans, manufactured from highgrade corrosion resistant pressed galvanised steel. All models aresupplied as standard with a pre-wired junction box. All modelsinclude an enclosed type single-phase external rotor motor withfactory matched backward curved non-standing impeller. Suitablefor operating in temperatures 60up to +60. IP44, Class Binsulation, and all motors include an internal safety thermaloverload protection devise as standard. All models are fully speedcontrollable using either electronic or autotransformer voltageregulations controllers.

    Fan Dimensions

    A B C D kg

    mm: 194 23 243 98 3The drawing is for dimensional purposes only.

    http://www.nuaire.co.uk/iandm/nl/671372.pdfhttp://www.nuaire.co.uk/iandm/nl/671372.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    8/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire International, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom.

    Tel:+44 (0)29 2085 8200 Fax:+44 (0)29 2085 8300 email:[email protected] the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 10 20 30 40 50 60 70

    200

    175

    150

    125

    100

    75

    50

    25

    0

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataNALT-L - In-line Centrifugal FanIn-line Centrifugal Fan

    Fan Code: NALT-100LInstallation Manual Links: 671371

    Required Duty: 41 l/s @ 60 PaActual Duty: 44 l/s @ 68 PaActual at Required Flow: 41 l/s @ 79 Pa

    Nominal Fan Speed: 2,550 RPMElectrical Supply: 1 PhaseNominal Motor Rating: 0.085 kWMotor Current: flc: 0.6 A

    Max. Operating Temp.: -60C to +60C

    Sound DataBreakout Noise (dBA): 38 dBA @ 3mBreakout level is hemi-spherical. For spherical deduct 3 dBA.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671371 attached to this document.

    Performance Curve

    Project DetailsDG TRANSPORT COMPLEX PH2Location: EF-8 - MAIN BUILDING

    Selected Ancillaries1 x NALTUBE-BRKT Mounting bracket

    SpecificationCircular in-line duct centrifugal fans, manufactured from highgrade corrosion resistant pressed galvanised steel. All models aresupplied as standard with a pre-wired junction box. All models(except SAVT-100L & SAVT-125L) include an enclosed typesingle-phase external rotor motor with factory matched backwardcurved non- standing impeller. Suitable for operating intemperatures 60up to +60. IP44, Class B insulation, and allmotors include an internal safety thermal overload protectiondevise as standard. All models are fully speed controllable usingeither electronic or autotransformer voltage regulations controllers.

    Fan Dimensions

    A B C D kg

    mm: 194 23 243 98 3The drawing is for dimensional purposes only.

    http://www.nuaire.co.uk/iandm/nl/671371.pdfhttp://www.nuaire.co.uk/iandm/nl/671371.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    9/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire International, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom.

    Tel:+44 (0)29 2085 8200 Fax:+44 (0)29 2085 8300 email:[email protected] the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 10 20 30 40 50 60 70

    200

    175

    150

    125

    100

    75

    50

    25

    0

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataNALT-L - In-line Centrifugal FanIn-line Centrifugal Fan

    Fan Code: NALT-100LInstallation Manual Links: 671371

    Required Duty: 41 l/s @ 60 PaActual Duty: 44 l/s @ 68 PaActual at Required Flow: 41 l/s @ 79 Pa

    Nominal Fan Speed: 2,550 RPMElectrical Supply: 1 PhaseNominal Motor Rating: 0.085 kWMotor Current: flc: 0.6 A

    Max. Operating Temp.: -60C to +60C

    Sound DataBreakout Noise (dBA): 38 dBA @ 3mBreakout level is hemi-spherical. For spherical deduct 3 dBA.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671371 attached to this document.

    Performance Curve

    Project DetailsDG TRANSPORT COMPLEX PH2Location: EF-9 - MAIN BUILDING

    Selected Ancillaries1 x NALTUBE-BRKT Mounting bracket

    SpecificationCircular in-line duct centrifugal fans, manufactured from highgrade corrosion resistant pressed galvanised steel. All models aresupplied as standard with a pre-wired junction box. All models(except SAVT-100L & SAVT-125L) include an enclosed typesingle-phase external rotor motor with factory matched backwardcurved non- standing impeller. Suitable for operating intemperatures 60up to +60. IP44, Class B insulation, and allmotors include an internal safety thermal overload protectiondevise as standard. All models are fully speed controllable usingeither electronic or autotransformer voltage regulations controllers.

    Fan Dimensions

    A B C D kg

    mm: 194 23 243 98 3The drawing is for dimensional purposes only.

    http://www.nuaire.co.uk/iandm/nl/671371.pdfhttp://www.nuaire.co.uk/iandm/nl/671371.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    10/50

  • 7/31/2019 11N95-DGT-PH2-DS

    11/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire International, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom.

    Tel:+44 (0)29 2085 8200 Fax:+44 (0)29 2085 8300 email:[email protected] the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 50 100 150

    350

    300

    250

    200

    150

    100

    50

    0

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataNALT-H - High Performance In-line Centrifugal FanHigh Performance In-line Centrifugal Fan

    Fan Code: NALT-125HInstallation Manual Links: 671372

    Required Duty: 84 l/s @ 60 PaActual Duty: 92 l/s @ 72 PaActual at Required Flow: 84 l/s @ 96 Pa

    Nominal Fan Speed: 2,450 RPMElectrical Supply: 1 PhaseNominal Motor Rating: 0.08 kWMotor Current: flc: 0.35 A

    Max. Operating Temp.: -60C to +60C

    Sound DataBreakout Noise (dBA): 47 dBA @ 3mBreakout level is hemi-spherical. For spherical deduct 3 dBA.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671372 attached to this document.

    Performance Curve

    Project DetailsDG TRANSPORT COMPLEX PH2Location: EF-11 - MAIN BUILDING

    Selected Ancillaries1 x NALTUBE-BRKT Mounting bracket

    SpecificationCircular in-line duct centrifugal fans, manufactured from highgrade corrosion resistant pressed galvanised steel. All models aresupplied as standard with a pre-wired junction box. All modelsinclude an enclosed type single-phase external rotor motor withfactory matched backward curved non-standing impeller. Suitablefor operating in temperatures 60up to +60. IP44, Class Binsulation, and all motors include an internal safety thermaloverload protection devise as standard. All models are fully speedcontrollable using either electronic or autotransformer voltageregulations controllers.

    Fan Dimensions

    A B C D kg

    mm: 195 27 243 123 3The drawing is for dimensional purposes only.

    http://www.nuaire.co.uk/iandm/nl/671372.pdfhttp://www.nuaire.co.uk/iandm/nl/671372.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    12/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 100 200 300 400 500 600 700

    150

    125

    100

    75

    50

    25

    0

    Curve speed controlled to required duty (86.1%)

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataAX - Axus Circular, GRP BladesCircular Cased Axial Fan

    Fan Code: AX35D-413Installation Manual Links: 671220

    Required Duty: 360 l/s @ 60 PaActual Duty: 418 l/s @ 80 PaActual at Required Flow: 360 l/s @ 94 Pa

    When Speed Controlled to Required Duty (86.1%):Fan Input Power: 0.045 kWMotor Input Power: 0.107 kWSpecific Fan Power: 0.298 W/(l/s)

    Fan Efficiency: 54 %Fan Input Power: 0.07 kWMaximum Fan Input Power: 0.07 kWMotor Input Power: 0.167 kWSpecific Fan Power: 0.401 W/(l/s)

    Nominal Fan Speed: 4 Pole 1,350 RPM

    Electrical Supply: 3 PhaseNominal Motor Rating: 0.18 kWMotor Current: flc: 0.56 AMotor Current: sc: 1.68 AOverload Setting: 0.616 AStarting currents are nominal.

    Blade Angle: 25

    Max. Operating Temp.: 55C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 41 dBA @ 3mBreakout level is spherical. For hemi-spherical add 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):

    Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 73 77 69 65 59 57 52 45Induct Outlet 73 72 75 68 62 60 52 46Open Inlet 61 69 65 64 59 57 52 45Open Outlet 60 65 70 67 62 60 52 46Breakout 68 70 67 60 49 47 36 23Noise calculated at actual duty of fan.

    Above noise calculated speed controlled to required duty (86.1%)For 100% Speed: +1 +1 +2 +2 +3 +3 +3 +3Breakout Noise (dBA): +2

    Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Project DetailsDG TRANSPORT COMPLEX PH2Location: FF-1 - MAIN BUILDING-FAF

    Selected Ancillaries1 x CMB35 Mounting bracket (pair)2 x CMF35 Matching flange

    SpecificationAxus circular inline axial flow fan manufactured from pre-galvanized mild steel for sizes 250-1250 diameter. 1400 diameterand above are manufactured from mild steel with hot dipgalvanized finish. Fan incorporates inlet and outlet flanges withpre-drilled bolt holes, and an external terminal box to IP55. Themotor is totally enclosed and protected to IP55, foot mountedclass 'F' insulated and has sealed for life ball bearings. Bladesmanufactured from injection moulded GRP mounted in a die castaluminium alloy hub as standard.

    NOTE: This unit cannot be inverter speed controlled.

    Fan Dimensions

    A B C D E F G H J K kgmm: 350 430 380 240 300 8 12 395 250 300 14

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671220 attached to this document.

    Performance Curve

    http://www.nuaire.co.uk/iandm/nl/671220.pdfhttp://www.nuaire.co.uk/iandm/nl/671220.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    13/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 200 400 600 800

    125

    100

    75

    50

    25

    0

    Curve speed controlled to required duty (98.2%)

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataAX - Axus Circular, GRP BladesCircular Cased Axial Fan

    Fan Code: AX35F-433Installation Manual Links: 671220

    Required Duty: 695 l/s @ 60 PaActual Duty: 707 l/s @ 62 PaActual at Required Flow: 695 l/s @ 67 Pa

    When Speed Controlled to Required Duty (98.2%):Fan Input Power: 0.124 kWMotor Input Power: 0.228 kWSpecific Fan Power: 0.328 W/(l/s)

    Fan Efficiency: 51 %Fan Input Power: 0.131 kWMaximum Fan Input Power: 0.14 kWMotor Input Power: 0.24 kWSpecific Fan Power: 0.34 W/(l/s)

    Nominal Fan Speed: 4 Pole 1,350 RPM

    Electrical Supply: 3 PhaseNominal Motor Rating: 0.18 kWMotor Current: flc: 0.56 AMotor Current: sc: 1.68 AOverload Setting: 0.616 AStarting currents are nominal.

    Blade Angle: 35

    Max. Operating Temp.: 55C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 44 dBA @ 3mBreakout level is spherical. For hemi-spherical add 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):

    Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 72 69 78 64 64 63 56 49Induct Outlet 76 72 81 66 65 63 55 49Open Inlet 59 62 74 63 64 63 56 49Open Outlet 63 65 78 65 64 63 55 49Breakout 69 65 73 58 53 51 40 26Noise calculated at actual duty of fan.Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Project DetailsDG TRANSPORT COMPLEX PH2Location: FF-2 - MAIN BUILDING-FAF

    Selected Ancillaries1 x CMB35 Mounting bracket (pair)2 x CMF35 Matching flange

    SpecificationAxus circular inline axial flow fan manufactured from pre-galvanized mild steel for sizes 250-1250 diameter. 1400 diameterand above are manufactured from mild steel with hot dipgalvanized finish. Fan incorporates inlet and outlet flanges withpre-drilled bolt holes, and an external terminal box to IP55. Themotor is totally enclosed and protected to IP55, foot mountedclass 'F' insulated and has sealed for life ball bearings. Bladesmanufactured from injection moulded GRP mounted in a die castaluminium alloy hub as standard.

    NOTE: This unit cannot be inverter speed controlled.

    Fan Dimensions

    A B C D E F G H J K kgmm: 350 430 380 240 300 8 12 395 250 300 15

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671220 attached to this document.

    Performance Curve

    http://www.nuaire.co.uk/iandm/nl/671220.pdfhttp://www.nuaire.co.uk/iandm/nl/671220.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    14/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 100 200 300 400 500 600 700

    150

    125

    100

    75

    50

    25

    0

    Curve speed controlled to required duty (86.1%)

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataAX - Axus Circular, GRP BladesCircular Cased Axial Fan

    Fan Code: AX35D-413Installation Manual Links: 671220

    Required Duty: 360 l/s @ 60 PaActual Duty: 418 l/s @ 80 PaActual at Required Flow: 360 l/s @ 94 Pa

    When Speed Controlled to Required Duty (86.1%):Fan Input Power: 0.045 kWMotor Input Power: 0.107 kWSpecific Fan Power: 0.298 W/(l/s)

    Fan Efficiency: 54 %Fan Input Power: 0.07 kWMaximum Fan Input Power: 0.07 kWMotor Input Power: 0.167 kWSpecific Fan Power: 0.401 W/(l/s)

    Nominal Fan Speed: 4 Pole 1,350 RPM

    Electrical Supply: 3 PhaseNominal Motor Rating: 0.18 kWMotor Current: flc: 0.56 AMotor Current: sc: 1.68 AOverload Setting: 0.616 AStarting currents are nominal.

    Blade Angle: 25

    Max. Operating Temp.: 55C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 41 dBA @ 3mBreakout level is spherical. For hemi-spherical add 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):

    Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 73 77 69 65 59 57 52 45Induct Outlet 73 72 75 68 62 60 52 46Open Inlet 61 69 65 64 59 57 52 45Open Outlet 60 65 70 67 62 60 52 46Breakout 68 70 67 60 49 47 36 23Noise calculated at actual duty of fan.

    Above noise calculated speed controlled to required duty (86.1%)For 100% Speed: +1 +1 +2 +2 +3 +3 +3 +3Breakout Noise (dBA): +2

    Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Project DetailsDG TRANSPORT COMPLEX PH2Location: FF-3 - MAIN BUILDING-FAF

    Selected Ancillaries1 x CMB35 Mounting bracket (pair)2 x CMF35 Matching flange

    SpecificationAxus circular inline axial flow fan manufactured from pre-galvanized mild steel for sizes 250-1250 diameter. 1400 diameterand above are manufactured from mild steel with hot dipgalvanized finish. Fan incorporates inlet and outlet flanges withpre-drilled bolt holes, and an external terminal box to IP55. Themotor is totally enclosed and protected to IP55, foot mountedclass 'F' insulated and has sealed for life ball bearings. Bladesmanufactured from injection moulded GRP mounted in a die castaluminium alloy hub as standard.

    NOTE: This unit cannot be inverter speed controlled.

    Fan Dimensions

    A B C D E F G H J K kgmm: 350 430 380 240 300 8 12 395 250 300 14

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671220 attached to this document.

    Performance Curve

    http://www.nuaire.co.uk/iandm/nl/671220.pdfhttp://www.nuaire.co.uk/iandm/nl/671220.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    15/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 200 400 600 800

    125

    100

    75

    50

    25

    0

    Curve speed controlled to required duty (98.2%)

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataAX - Axus Circular, GRP BladesCircular Cased Axial Fan

    Fan Code: AX35F-433Installation Manual Links: 671220

    Required Duty: 695 l/s @ 60 PaActual Duty: 707 l/s @ 62 PaActual at Required Flow: 695 l/s @ 67 Pa

    When Speed Controlled to Required Duty (98.2%):Fan Input Power: 0.124 kWMotor Input Power: 0.228 kWSpecific Fan Power: 0.328 W/(l/s)

    Fan Efficiency: 51 %Fan Input Power: 0.131 kWMaximum Fan Input Power: 0.14 kWMotor Input Power: 0.24 kWSpecific Fan Power: 0.34 W/(l/s)

    Nominal Fan Speed: 4 Pole 1,350 RPM

    Electrical Supply: 3 PhaseNominal Motor Rating: 0.18 kWMotor Current: flc: 0.56 AMotor Current: sc: 1.68 AOverload Setting: 0.616 AStarting currents are nominal.

    Blade Angle: 35

    Max. Operating Temp.: 55C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 44 dBA @ 3mBreakout level is spherical. For hemi-spherical add 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):

    Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 72 69 78 64 64 63 56 49Induct Outlet 76 72 81 66 65 63 55 49Open Inlet 59 62 74 63 64 63 56 49Open Outlet 63 65 78 65 64 63 55 49Breakout 69 65 73 58 53 51 40 26Noise calculated at actual duty of fan.Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Project DetailsDG TRANSPORT COMPLEX PH2Location: FF-4 - MAIN BUILDING-FAF

    Selected Ancillaries1 x CMB35 Mounting bracket (pair)2 x CMF35 Matching flange

    SpecificationAxus circular inline axial flow fan manufactured from pre-galvanized mild steel for sizes 250-1250 diameter. 1400 diameterand above are manufactured from mild steel with hot dipgalvanized finish. Fan incorporates inlet and outlet flanges withpre-drilled bolt holes, and an external terminal box to IP55. Themotor is totally enclosed and protected to IP55, foot mountedclass 'F' insulated and has sealed for life ball bearings. Bladesmanufactured from injection moulded GRP mounted in a die castaluminium alloy hub as standard.

    NOTE: This unit cannot be inverter speed controlled.

    Fan Dimensions

    A B C D E F G H J K kgmm: 350 430 380 240 300 8 12 395 250 300 15

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671220 attached to this document.

    Performance Curve

    http://www.nuaire.co.uk/iandm/nl/671220.pdfhttp://www.nuaire.co.uk/iandm/nl/671220.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    16/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 200 400 600 800

    175

    150

    125

    100

    75

    50

    25

    0

    Curve speed controlled to required duty (93.2%)

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataAX - Axus Circular, GRP BladesCircular Cased Axial Fan

    Fan Code: AX40D-413Installation Manual Links: 671220

    Required Duty: 507 l/s @ 80 PaActual Duty: 544 l/s @ 91 PaActual at Required Flow: 507 l/s @ 99 Pa

    When Speed Controlled to Required Duty (93.2%):Fan Input Power: 0.089 kWMotor Input Power: 0.173 kWSpecific Fan Power: 0.342 W/(l/s)

    Fan Efficiency: 51 %Fan Input Power: 0.109 kWMaximum Fan Input Power: 0.11 kWMotor Input Power: 0.213 kWSpecific Fan Power: 0.393 W/(l/s)

    Nominal Fan Speed: 4 Pole 1,350 RPM

    Electrical Supply: 3 PhaseNominal Motor Rating: 0.18 kWMotor Current: flc: 0.56 AMotor Current: sc: 1.68 AOverload Setting: 0.616 AStarting currents are nominal.

    Blade Angle: 25

    Max. Operating Temp.: 55C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 47 dBA @ 3mBreakout level is spherical. For hemi-spherical add 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):

    Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 76 76 80 68 64 62 56 49Induct Outlet 77 79 83 68 64 62 57 50Open Inlet 64 69 75 67 63 62 56 49Open Outlet 65 71 79 67 63 62 57 50Breakout 72 71 75 61 52 50 41 26Noise calculated at actual duty of fan.

    Above noise calculated speed controlled to required duty (93.2%)For 100% Speed: +0 +0 +1 +1 +2 +2 +2 +2Breakout Noise (dBA): +1

    Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Project DetailsDG TRANSPORT COMPLEX PH2Location: FF-5 - MAIN BUILDING-FAF

    Selected Ancillaries1 x CMB40 Mounting bracket (pair)2 x CMF40 Matching flange

    SpecificationAxus circular inline axial flow fan manufactured from pre-galvanized mild steel for sizes 250-1250 diameter. 1400 diameterand above are manufactured from mild steel with hot dipgalvanized finish. Fan incorporates inlet and outlet flanges withpre-drilled bolt holes, and an external terminal box to IP55. Themotor is totally enclosed and protected to IP55, foot mountedclass 'F' insulated and has sealed for life ball bearings. Bladesmanufactured from injection moulded GRP mounted in a die castaluminium alloy hub as standard.

    NOTE: This unit cannot be inverter speed controlled.

    Fan Dimensions

    A B C D E F G H J K kgmm: 400 490 440 270 370 8 12 450 290 340 16

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671220 attached to this document.

    Performance Curve

    http://www.nuaire.co.uk/iandm/nl/671220.pdfhttp://www.nuaire.co.uk/iandm/nl/671220.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    17/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 200 400 600 800

    125

    100

    75

    50

    25

    0

    Curve speed controlled to required duty (89.3%)

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataAX - Axus Circular, GRP BladesCircular Cased Axial Fan

    Fan Code: AX35F-433Installation Manual Links: 671220

    Required Duty: 600 l/s @ 60 PaActual Duty: 671 l/s @ 75 PaActual at Required Flow: 600 l/s @ 97 Pa

    When Speed Controlled to Required Duty (89.3%):Fan Input Power: 0.098 kWMotor Input Power: 0.177 kWSpecific Fan Power: 0.296 W/(l/s)

    Fan Efficiency: 50 %Fan Input Power: 0.137 kWMaximum Fan Input Power: 0.14 kWMotor Input Power: 0.248 kWSpecific Fan Power: 0.37 W/(l/s)

    Nominal Fan Speed: 4 Pole 1,350 RPM

    Electrical Supply: 3 PhaseNominal Motor Rating: 0.18 kWMotor Current: flc: 0.56 AMotor Current: sc: 1.68 AOverload Setting: 0.616 AStarting currents are nominal.

    Blade Angle: 35

    Max. Operating Temp.: 55C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 43 dBA @ 3mBreakout level is spherical. For hemi-spherical add 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):

    Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 70 68 77 62 62 60 54 47Induct Outlet 74 71 80 64 63 61 53 47Open Inlet 57 61 73 61 62 60 54 47Open Outlet 61 64 77 63 62 61 53 47Breakout 67 63 72 56 51 49 38 24Noise calculated at actual duty of fan.

    Above noise calculated speed controlled to required duty (89.3%)For 100% Speed: +1 +1 +1 +2 +2 +2 +2 +2Breakout Noise (dBA): +1

    Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Project DetailsDG TRANSPORT COMPLEX PH2Location: FF-6 - MAIN BUILDING-FAF

    Selected Ancillaries1 x CMB35 Mounting bracket (pair)2 x CMF35 Matching flange

    SpecificationAxus circular inline axial flow fan manufactured from pre-galvanized mild steel for sizes 250-1250 diameter. 1400 diameterand above are manufactured from mild steel with hot dipgalvanized finish. Fan incorporates inlet and outlet flanges withpre-drilled bolt holes, and an external terminal box to IP55. Themotor is totally enclosed and protected to IP55, foot mountedclass 'F' insulated and has sealed for life ball bearings. Bladesmanufactured from injection moulded GRP mounted in a die castaluminium alloy hub as standard.

    NOTE: This unit cannot be inverter speed controlled.

    Fan Dimensions

    A B C D E F G H J K kgmm: 350 430 380 240 300 8 12 395 250 300 15

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671220 attached to this document.

    Performance Curve

    http://www.nuaire.co.uk/iandm/nl/671220.pdfhttp://www.nuaire.co.uk/iandm/nl/671220.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    18/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 100 200 300 400 500 600 700

    150

    125

    100

    75

    50

    25

    0

    Curve speed controlled to required duty (90.6%)

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataAX - Axus Circular, GRP BladesCircular Cased Axial Fan

    Fan Code: AX35D-413Installation Manual Links: 671220

    Required Duty: 409 l/s @ 60 PaActual Duty: 451 l/s @ 73 PaActual at Required Flow: 409 l/s @ 83 Pa

    When Speed Controlled to Required Duty (90.6%):Fan Input Power: 0.052 kWMotor Input Power: 0.124 kWSpecific Fan Power: 0.305 W/(l/s)

    Fan Efficiency: 55 %Fan Input Power: 0.07 kWMaximum Fan Input Power: 0.07 kWMotor Input Power: 0.167 kWSpecific Fan Power: 0.371 W/(l/s)

    Nominal Fan Speed: 4 Pole 1,350 RPM

    Electrical Supply: 3 PhaseNominal Motor Rating: 0.18 kWMotor Current: flc: 0.56 AMotor Current: sc: 1.68 AOverload Setting: 0.616 AStarting currents are nominal.

    Blade Angle: 25

    Max. Operating Temp.: 55C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 42 dBA @ 3mBreakout level is spherical. For hemi-spherical add 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):

    Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 72 75 70 66 60 59 53 46Induct Outlet 72 72 76 68 63 60 53 47Open Inlet 60 68 66 64 60 59 53 46Open Outlet 60 65 72 67 63 60 53 47Breakout 68 69 68 60 50 48 37 24Noise calculated at actual duty of fan.

    Above noise calculated speed controlled to required duty (90.6%)For 100% Speed: +1 +1 +1 +1 +2 +2 +2 +2Breakout Noise (dBA): +1

    Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Project DetailsDG TRANSPORT COMPLEX PH2Location: FF-7 - MAIN BUILDING-FAF

    Selected Ancillaries1 x CMB35 Mounting bracket (pair)2 x CMF35 Matching flange

    SpecificationAxus circular inline axial flow fan manufactured from pre-galvanized mild steel for sizes 250-1250 diameter. 1400 diameterand above are manufactured from mild steel with hot dipgalvanized finish. Fan incorporates inlet and outlet flanges withpre-drilled bolt holes, and an external terminal box to IP55. Themotor is totally enclosed and protected to IP55, foot mountedclass 'F' insulated and has sealed for life ball bearings. Bladesmanufactured from injection moulded GRP mounted in a die castaluminium alloy hub as standard.

    NOTE: This unit cannot be inverter speed controlled.

    Fan Dimensions

    A B C D E F G H J K kgmm: 350 430 380 240 300 8 12 395 250 300 14

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671220 attached to this document.

    Performance Curve

    http://www.nuaire.co.uk/iandm/nl/671220.pdfhttp://www.nuaire.co.uk/iandm/nl/671220.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    19/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 100 200 300 400 500 600 700

    150

    125

    100

    75

    50

    25

    0

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataAX - Axus Circular, GRP BladesCircular Cased Axial Fan

    Fan Code: AX35D-413Installation Manual Links: 671220

    Required Duty: 500 l/s @ 60 PaActual Duty: 500 l/s @ 60 PaActual at Required Flow: 500 l/s @ 60 Pa

    Fan Efficiency: 56 %Fan Input Power: 0.067 kWMaximum Fan Input Power: 0.07 kWMotor Input Power: 0.164 kWSpecific Fan Power: 0.328 W/(l/s)

    Nominal Fan Speed: 4 Pole 1,350 RPMElectrical Supply: 3 PhaseNominal Motor Rating: 0.18 kWMotor Current: flc: 0.56 AMotor Current: sc: 1.68 A

    Overload Setting: 0.616 AStarting currents are nominal.

    Blade Angle: 25

    Max. Operating Temp.: 55C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 42 dBA @ 3mBreakout level is spherical. For hemi-spherical add 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 72 74 69 66 62 61 55 48Induct Outlet 72 73 78 68 64 62 55 49Open Inlet 60 66 65 65 62 61 55 48Open Outlet 60 66 73 67 64 62 55 49

    Breakout 68 69 69 61 51 50 39 26Noise calculated at actual duty of fan.Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Performance Curve

    Project DetailsDG TRANSPORT COMPLEX PH2Location: FF-1 - PRAYER HALL

    Selected Ancillaries1 x CMB35 Mounting bracket (pair)2 x CMF35 Matching flange

    SpecificationAxus circular inline axial flow fan manufactured from pre-galvanized mild steel for sizes 250-1250 diameter. 1400 diameterand above are manufactured from mild steel with hot dipgalvanized finish. Fan incorporates inlet and outlet flanges withpre-drilled bolt holes, and an external terminal box to IP55. Themotor is totally enclosed and protected to IP55, foot mountedclass 'F' insulated and has sealed for life ball bearings. Bladesmanufactured from injection moulded GRP mounted in a die castaluminium alloy hub as standard.

    NOTE: This unit cannot be inverter speed controlled.

    Fan Dimensions

    A B C D E F G H J K kgmm: 350 430 380 240 300 8 12 395 250 300 14

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671220 attached to this document.

    http://www.nuaire.co.uk/iandm/nl/671220.pdfhttp://www.nuaire.co.uk/iandm/nl/671220.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    20/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 100 200 300 400

    350

    300

    250

    200

    150

    100

    50

    0

    Curve speed controlled to required duty (81.5%)

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataEST-X - Ecosmart External Duct Mounted Twinfan,Direct Drive, Single Phase

    Ecosmart External Duct Mounted TwinfanFan Code: EST4-XInstallation Manual Links: 671142

    Required Duty: 200 l/s @ 120 PaActual Duty: 245 l/s @ 180 PaActual at Required Flow: 200 l/s @ 217 Pa

    When Speed Controlled to Required Duty (81.5%):Motor Input Power: 0.157 kWSpecific Fan Power: 0.785 W/(l/s)

    Motor Input Power: 0.289 kWSpecific Fan Power: 1.181 W/(l/s)

    Nominal Fan Speed: 1,140 RPMElectrical Supply: 1 PhaseNominal Motor Rating: 0.37 kWMotor Current: flc: 1.6 A

    Motor Current: sc: 1.6 A

    Max. Operating Temp.: 40C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 30 dBA @ 3m (90% of Max Pa)Breakout level is hemi-spherical. For spherical deduct 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 72 67 57 48 45 42 38 31Induct Outlet 80 75 62 58 62 57 54 49Breakout 57 58 54 48 44 38 37 33

    Above noise calculated speed controlled to required duty (81.5%)For 100% Speed: +1 +1 +2 +3 +4 +4 +4 +4

    Breakout Noise (dBA): +7 (90% of Max Pa)Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Performance Curve

    Project DetailsDG TRANSPORT COMPLEX PH2Location: EF-1 - PRAYER HALL

    SpecificationEcosmart external ducted twin fan unit manufactured fromaluzinc. All internal chamber surfaces are acoustically treated.Fan assemblies incorporate forward curved centrifugal impellersdirectly driven by BS5000 motors fitted with air flow fail monitors.Fans are suitable for operation in ambient temperatures up to40C. All units are suitable for internal and external use and maybe installed up to a maximum angle of 5. (Care must be taken toensure the back draught dampers operate correctly). The fanshould be fitted with an Ecosmart control together with an inverterspeed controller. The fan shall have the following energy savingfunctions integrally mounted within the fan unit on a purposemade PCB, all components pre-wired by the manufacturer:integral maximum and minimum speed adjustment/setting;integral auto-changeover/duty share, fans changeover every 12

    hours of run time; integral adjustable run on timer; integral BMSinterfaces, 0-10v and volt free failure indication.

    Fan Dimensions

    A B C D kgmm: 1,165 980 575 250 72

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671142 attached to this document.

    http://www.nuaire.co.uk/iandm/nl/671142.pdfhttp://www.nuaire.co.uk/iandm/nl/671142.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    21/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 100 200 300 400

    350

    300

    250

    200

    150

    100

    50

    0

    Curve speed controlled to required duty (81.5%)

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataEST-X - Ecosmart External Duct Mounted Twinfan,Direct Drive, Single Phase

    Ecosmart External Duct Mounted TwinfanFan Code: EST4-XInstallation Manual Links: 671142

    Required Duty: 200 l/s @ 120 PaActual Duty: 245 l/s @ 180 PaActual at Required Flow: 200 l/s @ 217 Pa

    When Speed Controlled to Required Duty (81.5%):Motor Input Power: 0.157 kWSpecific Fan Power: 0.785 W/(l/s)

    Motor Input Power: 0.289 kWSpecific Fan Power: 1.181 W/(l/s)

    Nominal Fan Speed: 1,140 RPMElectrical Supply: 1 PhaseNominal Motor Rating: 0.37 kWMotor Current: flc: 1.6 A

    Motor Current: sc: 1.6 A

    Max. Operating Temp.: 40C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 30 dBA @ 3m (90% of Max Pa)Breakout level is hemi-spherical. For spherical deduct 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 72 67 57 48 45 42 38 31Induct Outlet 80 75 62 58 62 57 54 49Breakout 57 58 54 48 44 38 37 33

    Above noise calculated speed controlled to required duty (81.5%)For 100% Speed: +1 +1 +2 +3 +4 +4 +4 +4

    Breakout Noise (dBA): +7 (90% of Max Pa)Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Performance Curve

    Project DetailsDG TRANSPORT COMPLEX PH2Location: EF-2 - PRAYER HALL

    SpecificationEcosmart external ducted twin fan unit manufactured fromaluzinc. All internal chamber surfaces are acoustically treated.Fan assemblies incorporate forward curved centrifugal impellersdirectly driven by BS5000 motors fitted with air flow fail monitors.Fans are suitable for operation in ambient temperatures up to40C. All units are suitable for internal and external use and maybe installed up to a maximum angle of 5. (Care must be taken toensure the back draught dampers operate correctly). The fanshould be fitted with an Ecosmart control together with an inverterspeed controller. The fan shall have the following energy savingfunctions integrally mounted within the fan unit on a purposemade PCB, all components pre-wired by the manufacturer:integral maximum and minimum speed adjustment/setting;integral auto-changeover/duty share, fans changeover every 12

    hours of run time; integral adjustable run on timer; integral BMSinterfaces, 0-10v and volt free failure indication.

    Fan Dimensions

    A B C D kgmm: 1,165 980 575 250 72

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671142 attached to this document.

    http://www.nuaire.co.uk/iandm/nl/671142.pdfhttp://www.nuaire.co.uk/iandm/nl/671142.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    22/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 100 200 300 400

    350

    300

    250

    200

    150

    100

    50

    0

    Volume Flow Rate (l/s)

    Static

    Pressure

    (Pa)

    Technical DataEST-X - Ecosmart External Duct Mounted Twinfan,Direct Drive, Single Phase

    Ecosmart External Duct Mounted TwinfanFan Code: EST4-XInstallation Manual Links: 671142

    Required Duty: 320 l/s @ 120 PaActual Duty: 319 l/s @ 119 PaActual at Required Flow: 320 l/s @ 118 Pa

    Motor Input Power: 0.334 kWSpecific Fan Power: 1.049 W/(l/s)

    Nominal Fan Speed: 1,140 RPMElectrical Supply: 1 PhaseNominal Motor Rating: 0.37 kWMotor Current: flc: 1.6 AMotor Current: sc: 1.6 A

    Max. Operating Temp.: 40C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 37 dBA @ 3m (90% of Max Pa)Breakout level is hemi-spherical. For spherical deduct 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 73 68 59 51 49 46 42 35Induct Outlet 81 76 64 61 66 61 58 53Breakout 58 59 56 51 48 42 41 37Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Wiring Information

    For complete wiring details please refer to the Installation &Maintenance Manual reference 671142 attached to this document.

    Performance Curve

    Project DetailsDG TRANSPORT COMPLEX PH2Location: EF-1 - STAFF FACILTY

    SpecificationEcosmart external ducted twin fan unit manufactured fromaluzinc. All internal chamber surfaces are acoustically treated.Fan assemblies incorporate forward curved centrifugal impellersdirectly driven by BS5000 motors fitted with air flow fail monitors.Fans are suitable for operation in ambient temperatures up to40C. All units are suitable for internal and external use and maybe installed up to a maximum angle of 5. (Care must be taken toensure the back draught dampers operate correctly). The fanshould be fitted with an Ecosmart control together with an inverterspeed controller. The fan shall have the following energy savingfunctions integrally mounted within the fan unit on a purposemade PCB, all components pre-wired by the manufacturer:integral maximum and minimum speed adjustment/setting;integral auto-changeover/duty share, fans changeover every 12

    hours of run time; integral adjustable run on timer; integral BMSinterfaces, 0-10v and volt free failure indication.

    Fan Dimensions

    A B C D kgmm: 1,165 980 575 250 72

    The drawing is for dimensional purposes only.

    http://www.nuaire.co.uk/iandm/nl/671142.pdfhttp://www.nuaire.co.uk/iandm/nl/671142.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    23/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 100 200 300 400

    350

    300

    250

    200

    150

    100

    50

    0

    Curve speed controlled to required duty (85.2%)

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataEST-X - Ecosmart External Duct Mounted Twinfan,Direct Drive, Single Phase

    Ecosmart External Duct Mounted TwinfanFan Code: EST4-XInstallation Manual Links: 671142

    Required Duty: 226 l/s @ 120 PaActual Duty: 265 l/s @ 165 PaActual at Required Flow: 226 l/s @ 195 Pa

    When Speed Controlled to Required Duty (85.2%):Motor Input Power: 0.186 kWSpecific Fan Power: 0.824 W/(l/s)

    Motor Input Power: 0.3 kWSpecific Fan Power: 1.134 W/(l/s)

    Nominal Fan Speed: 1,140 RPMElectrical Supply: 1 PhaseNominal Motor Rating: 0.37 kWMotor Current: flc: 1.6 A

    Motor Current: sc: 1.6 A

    Max. Operating Temp.: 40C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 30 dBA @ 3m (90% of Max Pa)Breakout level is hemi-spherical. For spherical deduct 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 72 67 57 49 46 43 39 32Induct Outlet 80 75 62 59 63 58 55 50Breakout 57 58 54 49 45 39 38 34

    Above noise calculated speed controlled to required duty (85.2%)For 100% Speed: +1 +1 +2 +2 +3 +3 +3 +3

    Breakout Noise (dBA): +7 (90% of Max Pa)Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Performance Curve

    Project DetailsDG TRANSPORT COMPLEX PH2Location: EF-2 - STAFF FACILTY

    SpecificationEcosmart external ducted twin fan unit manufactured fromaluzinc. All internal chamber surfaces are acoustically treated.Fan assemblies incorporate forward curved centrifugal impellersdirectly driven by BS5000 motors fitted with air flow fail monitors.Fans are suitable for operation in ambient temperatures up to40C. All units are suitable for internal and external use and maybe installed up to a maximum angle of 5. (Care must be taken toensure the back draught dampers operate correctly). The fanshould be fitted with an Ecosmart control together with an inverterspeed controller. The fan shall have the following energy savingfunctions integrally mounted within the fan unit on a purposemade PCB, all components pre-wired by the manufacturer:integral maximum and minimum speed adjustment/setting;integral auto-changeover/duty share, fans changeover every 12

    hours of run time; integral adjustable run on timer; integral BMSinterfaces, 0-10v and volt free failure indication.

    Fan Dimensions

    A B C D kgmm: 1,165 980 575 250 72

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671142 attached to this document.

    http://www.nuaire.co.uk/iandm/nl/671142.pdfhttp://www.nuaire.co.uk/iandm/nl/671142.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    24/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 100 200 300 400

    350

    300

    250

    200

    150

    100

    50

    0

    Curve speed controlled to required duty (75.8%)

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataEST-X - Ecosmart External Duct Mounted Twinfan,Direct Drive, Single Phase

    Ecosmart External Duct Mounted TwinfanFan Code: EST4-XInstallation Manual Links: 671142

    Required Duty: 159 l/s @ 120 PaActual Duty: 210 l/s @ 208 PaActual at Required Flow: 159 l/s @ 244 Pa

    When Speed Controlled to Required Duty (75.8%):Motor Input Power: 0.119 kWSpecific Fan Power: 0.747 W/(l/s)

    Motor Input Power: 0.272 kWSpecific Fan Power: 1.299 W/(l/s)

    Nominal Fan Speed: 1,140 RPMElectrical Supply: 1 PhaseNominal Motor Rating: 0.37 kWMotor Current: flc: 1.6 A

    Motor Current: sc: 1.6 A

    Max. Operating Temp.: 40C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 29 dBA @ 3m (90% of Max Pa)Breakout level is hemi-spherical. For spherical deduct 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 72 66 56 47 43 40 36 29Induct Outlet 80 74 61 57 60 55 52 47Breakout 57 57 53 47 42 36 35 31

    Above noise calculated speed controlled to required duty (75.8%)For 100% Speed: +1 +2 +3 +4 +6 +6 +6 +6

    Breakout Noise (dBA): +8 (90% of Max Pa)Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Performance Curve

    Project DetailsDG TRANSPORT COMPLEX PH2Location: EF-3 - STAFF FACILTY

    SpecificationEcosmart external ducted twin fan unit manufactured fromaluzinc. All internal chamber surfaces are acoustically treated.Fan assemblies incorporate forward curved centrifugal impellersdirectly driven by BS5000 motors fitted with air flow fail monitors.Fans are suitable for operation in ambient temperatures up to40C. All units are suitable for internal and external use and maybe installed up to a maximum angle of 5. (Care must be taken toensure the back draught dampers operate correctly). The fanshould be fitted with an Ecosmart control together with an inverterspeed controller. The fan shall have the following energy savingfunctions integrally mounted within the fan unit on a purposemade PCB, all components pre-wired by the manufacturer:integral maximum and minimum speed adjustment/setting;integral auto-changeover/duty share, fans changeover every 12

    hours of run time; integral adjustable run on timer; integral BMSinterfaces, 0-10v and volt free failure indication.

    Fan Dimensions

    A B C D kgmm: 1,165 980 575 250 72

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671142 attached to this document.

    http://www.nuaire.co.uk/iandm/nl/671142.pdfhttp://www.nuaire.co.uk/iandm/nl/671142.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    25/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 50 100 150 200 250

    225

    200

    175

    150

    125

    100

    75

    50

    25

    0

    Curve speed controlled to required duty (96.1%)

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataEST-X - Ecosmart External Duct Mounted Twinfan,Direct Drive, Single Phase

    Ecosmart External Duct Mounted TwinfanFan Code: EST3-XInstallation Manual Links: 671142

    Required Duty: 114 l/s @ 120 PaActual Duty: 118 l/s @ 129 PaActual at Required Flow: 114 l/s @ 133 Pa

    When Speed Controlled to Required Duty (96.1%):Motor Input Power: 0.173 kWSpecific Fan Power: 1.521 W/(l/s)

    Motor Input Power: 0.194 kWSpecific Fan Power: 1.644 W/(l/s)

    Nominal Fan Speed: 1,260 RPMElectrical Supply: 1 PhaseNominal Motor Rating: 0.23 kWMotor Current: flc: 1.6 A

    Motor Current: sc: 1.6 A

    Max. Operating Temp.: 40C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 28 dBA @ 3m (90% of Max Pa)Breakout level is hemi-spherical. For spherical deduct 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 77 72 55 46 42 39 35 31Induct Outlet 79 74 61 53 56 53 50 44Breakout 52 58 53 45 41 37 32 26

    Above noise calculated speed controlled to required duty (96.1%)For 100% Speed: +0 +0 +0 +1 +1 +1 +1 +1

    Breakout Noise (dBA): +4 (90% of Max Pa)Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Performance Curve

    Project DetailsDG TRANSPORT COMPLEX PH2Location: EF-4 - STAFF FACILTY

    SpecificationEcosmart external ducted twin fan unit manufactured fromaluzinc. All internal chamber surfaces are acoustically treated.Fan assemblies incorporate forward curved centrifugal impellersdirectly driven by BS5000 motors fitted with air flow fail monitors.Fans are suitable for operation in ambient temperatures up to40C. All units are suitable for internal and external use and maybe installed up to a maximum angle of 5. (Care must be taken toensure the back draught dampers operate correctly). The fanshould be fitted with an Ecosmart control together with an inverterspeed controller. The fan shall have the following energy savingfunctions integrally mounted within the fan unit on a purposemade PCB, all components pre-wired by the manufacturer:integral maximum and minimum speed adjustment/setting;integral auto-changeover/duty share, fans changeover every 12

    hours of run time; integral adjustable run on timer; integral BMSinterfaces, 0-10v and volt free failure indication.

    Fan Dimensions

    A B C D kgmm: 970 720 485 200 45

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671142 attached to this document.

    http://www.nuaire.co.uk/iandm/nl/671142.pdfhttp://www.nuaire.co.uk/iandm/nl/671142.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    26/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 200 400 600 800

    150

    125

    100

    75

    50

    25

    0

    Curve speed controlled to required duty (97.2%)

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataAX - Axus Circular, GRP BladesCircular Cased Axial Fan

    Fan Code: AX40B-413Installation Manual Links: 671220

    Required Duty: 539 l/s @ 60 PaActual Duty: 554 l/s @ 63 PaActual at Required Flow: 539 l/s @ 66 Pa

    When Speed Controlled to Required Duty (97.2%):Fan Input Power: 0.069 kWMotor Input Power: 0.159 kWSpecific Fan Power: 0.296 W/(l/s)

    Fan Efficiency: 55 %Fan Input Power: 0.075 kWMaximum Fan Input Power: 0.076 kWMotor Input Power: 0.173 kWSpecific Fan Power: 0.313 W/(l/s)

    Nominal Fan Speed: 4 Pole 1,350 RPM

    Electrical Supply: 3 PhaseNominal Motor Rating: 0.18 kWMotor Current: flc: 0.56 AMotor Current: sc: 1.68 AOverload Setting: 0.616 AStarting currents are nominal.

    Blade Angle: 25

    Max. Operating Temp.: 55C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 45 dBA @ 3mBreakout level is spherical. For hemi-spherical add 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):

    Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 73 82 73 70 66 64 57 47Induct Outlet 75 84 74 71 67 64 58 50Open Inlet 62 75 69 69 66 64 57 47Open Outlet 63 76 70 69 66 64 58 50Breakout 69 77 66 64 55 52 42 26Noise calculated at actual duty of fan.

    Above noise calculated speed controlled to required duty (97.2%)For 100% Speed: +0 +0 +0 +0 +1 +1 +1 +1Breakout Noise (dBA): +1

    Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Project DetailsDG TRANSPORT COMPLEX PH2Location: FF-1 - STAFF FACILTY

    Selected Ancillaries1 x CMB40 Mounting bracket (pair)2 x CMF40 Matching flange

    SpecificationAxus circular inline axial flow fan manufactured from pre-galvanized mild steel for sizes 250-1250 diameter. 1400 diameterand above are manufactured from mild steel with hot dipgalvanized finish. Fan incorporates inlet and outlet flanges withpre-drilled bolt holes, and an external terminal box to IP55. Themotor is totally enclosed and protected to IP55, foot mountedclass 'F' insulated and has sealed for life ball bearings. Bladesmanufactured from injection moulded GRP mounted in a die castaluminium alloy hub as standard.

    NOTE: This unit cannot be inverter speed controlled.

    Fan Dimensions

    A B C D E F G H J K kgmm: 400 490 440 270 370 8 12 450 290 340 16

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671220 attached to this document.

    Performance Curve

    http://www.nuaire.co.uk/iandm/nl/671220.pdfhttp://www.nuaire.co.uk/iandm/nl/671220.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    27/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 100 200 300 400

    125

    100

    75

    50

    25

    0

    Curve speed controlled to required duty (96.4%)

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataAX - Axus Circular, GRP BladesCircular Cased Axial Fan

    Fan Code: AX31B-413Installation Manual Links: 671220

    Required Duty: 240 l/s @ 60 PaActual Duty: 249 l/s @ 64 PaActual at Required Flow: 240 l/s @ 67 Pa

    When Speed Controlled to Required Duty (96.4%):Fan Input Power: 0.036 kWMotor Input Power: 0.119 kWSpecific Fan Power: 0.499 W/(l/s)

    Fan Efficiency: 43 %Fan Input Power: 0.04 kWMaximum Fan Input Power: 0.04 kWMotor Input Power: 0.133 kWSpecific Fan Power: 0.537 W/(l/s)

    Nominal Fan Speed: 4 Pole 1,350 RPM

    Electrical Supply: 3 PhaseNominal Motor Rating: 0.18 kWMotor Current: flc: 0.56 AMotor Current: sc: 1.68 AOverload Setting: 0.616 AStarting currents are nominal.

    Blade Angle: 25

    Max. Operating Temp.: 55C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 39 dBA @ 3mBreakout level is spherical. For hemi-spherical add 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):

    Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 71 74 69 61 59 57 51 43Induct Outlet 75 81 73 63 59 56 50 44Open Inlet 57 65 64 59 58 57 51 43Open Outlet 61 72 67 61 59 56 50 44Breakout 68 73 64 55 48 45 35 22Noise calculated at actual duty of fan.

    Above noise calculated speed controlled to required duty (96.4%)For 100% Speed: +0 +0 +0 +1 +1 +1 +1 +1Breakout Noise (dBA): +1

    Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Project DetailsDG TRANSPORT COMPLEX PH2Location: EF-2 - STAFF FACILTY

    Selected Ancillaries1 x CMB31 Mounting bracket (pair)2 x CMF31 Matching flange

    SpecificationAxus circular inline axial flow fan manufactured from pre-galvanized mild steel for sizes 250-1250 diameter. 1400 diameterand above are manufactured from mild steel with hot dipgalvanized finish. Fan incorporates inlet and outlet flanges withpre-drilled bolt holes, and an external terminal box to IP55. Themotor is totally enclosed and protected to IP55, foot mountedclass 'F' insulated and has sealed for life ball bearings. Bladesmanufactured from injection moulded GRP mounted in a die castaluminium alloy hub as standard.

    NOTE: This unit cannot be inverter speed controlled.

    Fan Dimensions

    A B C D E F G H J K kgmm: 315 400 365 210 285 8 12 355 220 270 13

    The drawing is for dimensional purposes only.

    Wiring InformationFor complete wiring details please refer to the Installation &Maintenance Manual reference 671220 attached to this document.

    Performance Curve

    http://www.nuaire.co.uk/iandm/nl/671220.pdfhttp://www.nuaire.co.uk/iandm/nl/671220.pdf
  • 7/31/2019 11N95-DGT-PH2-DS

    28/50

    S U M M A R Y F A N D A T A S H E E T

    Nuaire Limited, Western Industrial Estate, Caerphilly, CF83 1NA, United Kingdom. email:[email protected]

    UK Technical Enquiries Tel:029 2085 8200 Fax:029 2085 8300 International Enquiries Tel:+44 29 2085 8335 Fax:+44 29 2085 8278Whilst the information given on this data sheet is fan specific, it is in summary and reference to the product selection catalogue and installation & maintenance documents is recommended.This data sheet produced on 07 Apr 2011 11:17 using software version 2.4.19 - 1 October 2010

    0 100 200 300 400 500

    90

    80

    70

    60

    50

    40

    30

    20

    10

    0

    Volume Flow Rate (l/s)

    StaticPressure

    (Pa)

    Technical DataAX - Axus Circular, GRP BladesCircular Cased Axial Fan

    Fan Code: AX31X-423Installation Manual Links: 671220

    Required Duty: 340 l/s @ 60 PaActual Duty: 342 l/s @ 60 PaActual at Required Flow: 340 l/s @ 62 Pa

    Fan Efficiency: 40 %Fan Input Power: 0.062 kWMaximum Fan Input Power: 0.07 kWMotor Input Power: 0.158 kWSpecific Fan Power: 0.462 W/(l/s)

    Nominal Fan Speed: 4 Pole 1,350 RPMElectrical Supply: 3 PhaseNominal Motor Rating: 0.18 kWMotor Current: flc: 0.56 AMotor Current: sc: 1.68 A

    Overload Setting: 0.616 AStarting currents are nominal.

    Blade Angle: 30

    Max. Operating Temp.: 55C

    Sound DataAcoustic perfomance to BS848 Part 2.2 and AMCA 300.Breakout Noise (dBA): 40 dBA @ 3mBreakout level is spherical. For hemi-spherical add 3 dBA.

    Sound Power Levels re 1 pWatts (Hz):Hz 63 125 250 500 1k 2k 4k 8kInduct Inlet 78 81 72 64 61 57 49 43Induct Outlet 71 78 71 64 61 57 48 43Open Inlet 63 72 67 62 61 56 49 43Open Outlet 58 69 66 62 60 57 48 43

    Breakout 71 73 65 57 49 45 33 20Noise calculated at actual duty of fan.Values shown are for inlet Lw and outlet Lw sound power levels for:Installation Type D: ducted inlet, ducted outlet. Ratings include theeffects of duct end correction.

    Performance Curve

    Project DetailsDG TRANSPORT COMPLEX PH2Location: FF-3 - STAFF FACILTY

    Selected Ancillaries1 x CMB31 Mounting bracket (pair)2 x CMF31 Matching flange

    SpecificationAxus circular inline axial flow fan manufactured from pre-galvanized mild steel for sizes 250-1250 diameter. 1400 diameterand above are manufactured from mild steel with hot dipgalvanized finish. Fan incorporates inlet and outlet flanges withpre-drilled bolt holes, and an external terminal box to IP55. Themotor is totally enclosed and protected to IP55, foot mountedclass 'F' insulated and has sealed for life ball bearings. Bladesmanufactured from injection moulded GRP mounted in a die castaluminium alloy hub as standard.

    NOTE: This unit cannot be inverter speed controlled.

    Fan Dimensions

    A B C D E F G H J K kgmm: 315 400 365 210 285 8 12 355 220 270 14

    The drawing is for dimensional


Recommended