BICSI002/TIA942/UptimeWhichDataCenterStandard
ShouldIFollow
PhilIsaak,PE,P.Eng.,RCDD,DCDCPresident,MasterInstructor
IsaakTechnologiesInc.
www.isaaktech.com
Standards WhoarethesePeople PowerStandards
Distribution&Grounding NetworkStandards
Protocols ITHardwareManufacturers
MediaStandards CablingManufacturers
Design&InstallationStandards EndUsers,Contractors,Consultants,Manufacturers
www.isaaktech.com
Uptime TIA BICSI
OpenIndustryStandard NOT VendorNeutral
ANSI/TIA942A(2012)TelecommunicationsInfrastructureStandard
forDataCenters118pages
ANSI/BICSI0022011DataCenterDesignandImplementation
BestPractices392pages
UptimeInstitute(2010)DataCenterSiteInfrastructure
TierStandard:Topology12pages
OpenIndustryStandard VendorNeutral
ForProfitPrivatelyHeld NOT aStandard
www.isaaktech.com
ANSICertifiedStandardRequirements
Openness: Participationshallbeopentoallpersonswhoaredirectlyandmateriallyaffectedbytheactivityinquestion.
LackofDominance:Thestandardsdevelopmentprocessshallnotbedominatedbyanysingleinterestcategory,individualororganization.
Balance:Participantsfromdiverseinterestcategoriesshallbesoughtwiththeobjectiveofachievingbalance.
www.isaaktech.com
BICSISubjectMatterExpertsMorethan150subjectmatterexpertsfromaroundtheworldparticipatedindevelopingthestandard.
Perspectives: DataCenterManagers DataCenterOperators Consultants Contractors RiskAssessors Manufacturers CommissioningAgents
Expertise: FacilityEngineers/Architects ITEngineers/Architects SystemAdministrators Telecommunications Security FireProtection ProjectManagers
www.isaaktech.com
ANSI/BICSI0022011Providesareferenceofcommonterminologyanddesignpracticesaframeworkfordeterminingtherecommendedfacilityandtechnologyredundancytomeettheoperationalrequirements,achieveITobjectives
andtodevelopoptimumdesign&implementationsolutions
UptimeTiersOnlydatacenterbenchmarkingsystemdevelopedbyandfordatacenterowners,notachecklist,designmenu,orcookbook
Source:UptimeInstitute:TierClassificationSystem&OperationalSustainabilitypresentedbyDanaSmith,DirectorofDevelopment,UptimeInstituteatBICSIAndino 2012
DesignGuidevs Benchmarking
www.isaaktech.com
UptimeBenchmarks
UptimeInstitute TierI TierII TierIII TierIV
ScheduledOutages/Year 2x12hrs 1x12hrs None None
AveFailures/Year(4hrs/failure) 1.2 1.0 1.0 1.0
AveAnnualDowntimeHours 28.8 22 1.6 0.8
Availability 99.67% 99.75% 99.98% 99.99%
**Basisisontop10%ofsitesasdeterminedbyUptimeInstituteBenchmarking**
www.isaaktech.com
ComparingtheStandards TIA942Achapters (normative)
Datacenterdesignoverview Datacentercablingsysteminfrastructure Datacentertelecommunicationsspaces&relatedtopologies Datacentercablingsystems Datacentercablingpathways Datacenterredundancy
TIA942Aannexes (informative) Cablingdesignconsiderations Accessproviderinformation Coordinationofequipmentplanswithotherengineers Datacenterspaceconsiderations Datacentersiteselectionandbuildingdesignconsiderations Datacenterinfrastructuretiers Datacenterdesignexamples
www.isaaktech.com
Spaceplanning Siteselection Architectural Structural Electricalsystems Mechanical Fireprotection
BICSI002annexes Designprocess Reliabilityandavailability
Security Buildingautomationsystems Telecommunications Informationtechnology Commissioning Datacentermaintenance
BICSI002sections
ComparingtheStandards
www.isaaktech.com
ANSI/BICSI0022011
ComprehensiveDataCenterStandard
www.isaaktech.com
MethodologytoDefineReliability
DefineOperationalRequirements
AnnualPlannedDowntime
OperationalLevel
> 400hrs 0
100 400hrs 1
50 99hrs 2
0 49hrs 3
0hrs 4
www.isaaktech.com
MethodologytoDefineReliability
DefineOperationalRequirements
Minutes Numberof9s
>5,000 >99%
500 5,000 99% 99.9%
50 500 99.9% 99.99%
5 50 99.99% 99.999%
0.5 5 99.999% 99.9999%
DefineAvailabilityRequirements
www.isaaktech.com
MethodologytoDefineReliability
DefineOperationalRequirements
Description ClassificationLocalinscope,affectingonlyasinglefunctionoroperation,resultinginaminordisruptionordelayinachievingnoncriticalorganizationalobjectives.
Isolated
Localinscope,affectingonlyasinglesite,orresultinginaminordisruptionordelayinachievingkeyorganizationalobjectives.
Minor
Regionalinscope,affectingaportionoftheenterpriseorresultinginamoderatedisruptionordelayinachievingkeyorganizationalobjectives.
Major
Multiregionalinscope,affectingamajorportionoftheenterpriseorresultinginamajordisruptionordelayinachievingkeyorganizationalobjectives.
Severe
Affectingthequalityofservicedeliveryacrosstheentireenterprise,orresultinginasignificantdisruptionordelayinachievingkeyorganizationalobjectives.
Catastrophic
DefineAvailabilityRequirements
DefineImpactofDowntime
www.isaaktech.com
MethodologytoDefineReliability
DefineOperationalRequirements
DefineAvailabilityRequirements
DefineImpactofDowntime
RecommendedPerformanceIdentified
Class0Class1Class2Class3Class4
www.isaaktech.com
Class0/1SinglePath
BPSUAPSU
PowerCircuitA1
APOU
RPPA
NCRAHModules
NChiller,Pumps&Condenser
Pipingandvalveredundancynotrequired.
LargeFrame
Processing
WANCarrier
DiskArray
Core
EdgeInternet
AccessSwitch
Server n
Aggregation
Server 1
EdgeWAN
NASDiskArray
Transfer Switchgear
Electrical Distribution
Alternate Power Source
UPS
PDU
CriticalLoads
Non-CriticalLoads
Mechanical Switchgear
MechanicalLoads
Static Bypass
Maint.Bypass
Utility
2013IsaakTechnologiesInc.
www.isaaktech.com
Class2RedundantComponents
BPSUAPSU
PowerCircuitA1
APOU
BPOU
PowerCircuitA2
RPPA
+1CRAHModule
N+1Chillers,Pumps&Condensers
MorethanN+1redundancyisrecommendedasthenumberofmodulestomeetNincreases
NCRAHModules
Pipingandvalveredundancynotrequiredoutsidecomputerroom.
RefertoChillerPipingandValveRedundancysectionforcomputerroomrecommendations
LargeFrame
Processing
WANCarrier
DiskArray
NASDiskArray
Core
AccessSwitch
Server n
Aggregation
Server 1
EdgeWAN
EdgeInternet
Transfer Switchgear
Electrical Distribution
Alternate Power Source
Alternate Power Source
UPS UPS
PDU
CriticalLoads
Non-CriticalLoads
Mechanical Switchgear
MechanicalLoads
Static Bypass
Maint.Bypass
Utility
2013IsaakTechnologiesInc.
www.isaaktech.com
Class3ConcurrentMaintainability
BPSUAPSU
APOU
BPOU
STSA
STSB
PowerCircuit
RPPB12
PowerCircuit
RPPB11
RPPB1
PDUB1
PowerCircuit
RPPA12
PowerCircuit
RPPA11
RPPA1
PDUA1
+1CRAHModule
N+1Chillers,Pumps&Condensers
MorethanN+1redundancyisrecommendedasthenumberofmodulestomeetNincreases
NCRAHModules
Pipingandvalveredundancynotrequired,butrecommended,outsidecomputerroom.
RefertoChillerPipingandValveRedundancysectionforcomputerroomrecommendations
LargeFrame
Processing
WANCarrier 1
DiskArray n
SANSwitch2
DiskArray1
SANSwitch1
Core2Core1
Edge2Internet
Edge1Internet
AccessSwitch 1
Server n
Aggregation1
AccessSwitch 2
Server 1
WANCarrier 2
Aggregation2
Edge2WAN
Edge1WAN
Carrier 1 Carrier 2
NASDiskArray
SwitchgearUtility
Electrical Distribution
Switchgear
Alternate Power Source
Electrical Distribution
Alternate Power Source
UPS UPS
Output Distribution Switchboard
PDU
Mechanical Switchboard
CriticalFans/Pumps
CriticalLoads
Non-CriticalLoads
Mechanical Switchgear
MechanicalLoads
Alternate Switchboard
PDU
Mechanical Switchboard
Non-CriticalLoads
Mechanical Switchgear
MechanicalLoads
Static Bypass
Maint.Bypass
2013IsaakTechnologiesInc.
www.isaaktech.com
Class4FaultTolerant
BPSUAPSU
APOU
BPOU
STSA
STSB
PowerCircuit
RPP2B1
PowerCircuit
RPP2A1
PowerCircuit
RPP1B1
PowerCircuit
RPP1A1
PDUA1 PDUA2
PanelA PanelBRPP1
PDUB1 PDUB2
PanelA PanelBRPP2
NCRAHModules
+2CRAHModule
N+2Chillers,Pumps&Condensers
MorethanN+2redundancyisrecommendedasthenumberofmodulestomeetNincreases
Pipingandvalveredundancyrequiredoutsidecomputerroom.
RefertoChillerPipingandValveRedundancysectionforcomputerroomrecommendations
LargeFrame
Processing
WANCarrier 1
DiskArray n
SANSwitch2
DiskArray1
SANSwitch1
Core2Core1
Edge2Internet
Edge1Internet
AccessSwitch 1
Server n
Aggregation1
AccessSwitch 2
Server 1
WANCarrier 2
Aggregation2
Edge2WAN
Edge1WAN
Carrier 1 Carrier 2
NASDiskArray
SwitchgearUtility
Electrical Distribution
Switchgear
Alternate Power Source
Electrical Distribution
Alternate Power Source
UPS UPS
Output Distribution Switchboard
PDU
Mechanical Switchgear
CriticalFans/Pumps
CriticalLoads
Non-CriticalLoads
Mechanical Switchgear
MechanicalLoads
Output Distribution Switchboard
PDU
Mechanical Switchgear
Non-CriticalLoads
Mechanical Switchgear
Static Bypass Maint.
Bypass
UPS UPS
Static Bypass Maint.
Bypass
Utility
Alternate Power Source
Alternate Power Source
2013IsaakTechnologiesInc.
www.isaaktech.com
EndtoEndReliability
Applications Systems Network CablingInfrastructure Facility
Facility
CablingInfrastructure
Network
DataProcessing&StorageSystems
Applications
www.isaaktech.com
DC125DataCenterDesignCourse
4DayCourse InDepthReviewofStandard
PrepareforDCDCExamDataCenterDesignConsultant
ContactFiberOpto AsiaPte LtdforcoursedatesandlocationsavailableinSouthEastAsia
www.isaaktech.com
BICSIDataCenterDocumentsANSI/BICSI0022011DataCenterDesignandImplementationBestPractices
AvailablefromBICSIwww.bicsi.org/standards
BICSIInternationalStandardsSupplementalInformation001
MethodologyforSelectingDataCenterDesignClassUtilizingPerformanceCriteria