Date post: | 03-Apr-2018 |
Category: |
Documents |
Upload: | thavaselvan |
View: | 217 times |
Download: | 0 times |
of 41
7/28/2019 1.2 Terminology...
1/41
E l e c t r i c a l S t a n d a r d P r o d u c t s
S w i t c h g e a r T r a i n i n g C e n t r e , C o o n o o r
7/28/2019 1.2 Terminology...
2/41
UNDERSTANDING SWITCHGEAR TERMINOLOGY
S w i t c h g e a r T r a i n i n g C e n t r e , C o o n o o r
E l e c t r i c a l S t a n d a r d P r o d u c t s
7/28/2019 1.2 Terminology...
3/41
W h a t i s S w i t c h g e a r ?
S w i t c h g e a r T r a i n i n g C e n t r e , C o o n o o r
UNDERSTANDING SWITCHGEAR TERMINOLOGY
7/28/2019 1.2 Terminology...
4/41
A device or a combination of devices,
primarily intended for the purpose of
making, carrying and breaking electriccurrents in circuits during normal circuit
conditions as well as under abnormal
(faulty) circuit conditions
S w i t c h g e a r T r a i n i n g C e n t r e , C o o n o o r
WhatisSwitchgear?
UNDERSTANDING SWITCHGEAR TERMINOLOGY
7/28/2019 1.2 Terminology...
5/41
L o w Vo l t a ge Sw it c hg e a r Terminology
WhataretheLVSwitchgearTerminologies?
TheLVSwitchgearTerminologiesaregenerallywithrespecttothefollowingparameters:
Voltages
Currents
BehaviorunderNormal&OverloadConditions
Behaviorunder
Short
Circuit
Conditions
Utilisationcategories
S w i t c h g e a r T r a i n i n g C e n t r e , C o o n o o r
7/28/2019 1.2 Terminology...
6/41
RATEDOPERATIONAL
VOLTAGE
(Ue)
RATEDINSULATION
VOLTAGE
(Ui)
RATEDIMPULSEVOLTAGE(Uimp)
L O W V O L T A G E S W I T C H G E A R
T E R M I N O L O G Y V O L T A G E S
S w i t c h g e a r T r a i n i n g C e n t r e , C o o n o o r
7/28/2019 1.2 Terminology...
7/41
Rated Operational Voltage (Ue): This is the voltagethat would normally be available continuously
across the terminals of different phases of the
switchgear. Unless otherwise specified, this ratingwill be 415V for LV Switchgear. This implies that
even while 415V @50Hz is present between the
terminals, there will not be any flashover (i.e.) the
insulation between phases is sufficient to tolerate a
potential difference of 415V continuously.
LOW VOLTAGE SWITCHGEAR TERMINOLOGY
V O L T A G E S
7/28/2019 1.2 Terminology...
8/41
Rated Insulation Withstand Voltage (Ui): Then, one
might ask, at what voltage the interphase
insulation would fail, if it would not fail for 415V.
What is be the probability of such a happening,that the system voltage can go beyond 415V?
LOW VOLTAGE SWITCHGEAR TERMINOLOGY
V O L T A G E S
7/28/2019 1.2 Terminology...
9/41
There are two possibilities (viz.) transformer tap
changers & the system fluctuation on the upperside. One can go by the permissible fluctuationsin the supply voltage (+10%) and the worst
probable tap ratios in transformers (+/
12.5%).Considering that the worst condition of thetransformer tap in the maximum position and at
the same time, the system voltage too fluctuateson the plus side, there could be a net systemvoltage variation of +25% + +10% on the
switchgear.
LOW VOLTAGE SWITCHGEAR TERMINOLOGY
V O L T A G E S
7/28/2019 1.2 Terminology...
10/41
If the switchgear is exactly rated for 415V, then
under the above conditions, it would fail. So,
another rating called Ui is specified. Normallythis would be 690V for LV Switchgear. Even
under the worst condition as described above,
the 415V system voltage would not go beyond595V. So, a switchgear rated for an Ui of 690V
would very well withstand the above condition.
LOW VOLTAGE SWITCHGEAR TERMINOLOGY
V O L T A G E S
7/28/2019 1.2 Terminology...
11/41
Rated Impulse Withstand Voltage (Uimp): Therecould be impulse voltages striking the system either a Lightning Impulse (LI) or a SwitchingImpulse (SI). These are very high magnitude butvery short duration voltage waves. Typically, theyare high frequency. They can strike our system
and our switchgear might fail. So, this rating isalso given for switchgear.
LOW VOLTAGE SWITCHGEAR TERMINOLOGY
V O L T A G E S
7/28/2019 1.2 Terminology...
12/41
R a t e d I m p u l s e V o l t a g e ( U i m p )
Impulse voltage values are selected based on
Rated voltage range
Installation category
Parameters considered for selection
Internally generated Overvoltage
Ability to withstand externally applied
Overvoltage
Both to conform to values given in the table
Use of surge suppressors, if necessary
7/28/2019 1.2 Terminology...
13/41
7/28/2019 1.2 Terminology...
14/41
I n s t a l l a t i o n C a t e g o r y( O v e r v o l t a g e c a t e g o r y )
CategoryI Speciallyprotectedlevel
CategoryII Load(Appliancesor
Equipment
level)
CategoryIII DistributionCircuit
level
CategoryIV Originofinstallationi.e.serviceentrancelevel
7/28/2019 1.2 Terminology...
15/41
I m p u l s e v o l t a g e l e v e l sSystemVoltage
Vrms
Cat.IVimp
Cat.IIVimp
Cat.IIIVimp
Cat.IVVimp
50 330 500 800 1500
100 500 800 1500 2500
150 800 1500 2500 4000
300 1500 2500 4000 6000
600 2500 4000 6000 8000
1000 4000 6000 8000 12000
7/28/2019 1.2 Terminology...
16/41
CONVENTIONALFREEAIRTHERMALCURRENT
(Ith)
CONVENTIONALENCLOSEDTHERMAL
CURRENT(Ithe)
RATEDOPERATIONALCURRENT(Ie)
RATEDUNINTERRUPTED
CURRENT
(Iu)
RATEDCURRENT(In)
LOW VOLTAGE SWITCHGEAR TERMINOLOGY
C U R R E N T S
7/28/2019 1.2 Terminology...
17/41
Low Voltage Switchgear Terminology Currents
Rated Free Air Thermal Current (Ith): The current rating
for any equipment given based on the temperature riseonly. As such, the heating current is important.
This specification implies the maximum current thatthe switchgear can carry continuously for a period of 8
hours, without the temperature rise of any part
reaching beyond permissible limits. This test isconducted in openair conditions.
7/28/2019 1.2 Terminology...
18/41
Low Voltage Switchgear Terminology Currents
Rated Enclosed Thermal Current (Ithe): But no LVswitchgear is used in open air. Most of the LV switchgear is
used under enclosed conditions. The heat dissipation willbe poor. So, a more precise rating would be the Ithe.
This implies the maximum current that the switchgear cancarry continuously for a period of 8 hours, without thetemperature rise of any part reaching beyond permissiblelimits. This test is conducted in enclosed conditions.
7/28/2019 1.2 Terminology...
19/41
Low Voltage Switchgear Terminology Currents
Rated Uninterrupted Current (Iu): Again, electricalequipment are utilized, not in intermittent loading periods
of 8 hours each. Rather they are used and loadedcontinuously, much beyond 8 hours.
This rating obviously implies the maximum current theswitchgear can carry continuously for periods extending toeven hours, weeks & months, without the temperaturerise of any part reaching beyond permissible limits. Unless
otherwise specified, this will be equal to the ratedoperational current of the switchgear.
7/28/2019 1.2 Terminology...
20/41
Low Voltage Switchgear Terminology Currents
Rated Operational Current (Ie): All the above three currents
take into account only one function the carry function of the Switchgear. But, a switchgear must also make &break. The making and breaking capacities would varydepending upon the application of the switchgear and are
normally specified as a multiple of the rated continuouscurrent. So, the continuous current of a switchgear wouldalso vary depending upon the application and the making &
breaking capacities expected in that application. Such arating is the Ie rating.
7/28/2019 1.2 Terminology...
21/41
Low Voltage Switchgear Terminology Currents
Rated Current (In): This rating is similar to the Rated
Operational Current Rating, but is applied to Fuses & CircuitBreakers.
7/28/2019 1.2 Terminology...
22/41
C H A R A C T E R I S T I C Q U A N T I T I E S
NORMAL LOAD & OVERLOAD CHARACTERISTICSRATED BREAKING CAPACITY
RATED MAKING CAPACITY
7/28/2019 1.2 Terminology...
23/41
Low Voltage Switchgear Terminology Normal
C o n d i t i o n B e h a v i o r
Rated Normal Condition Making Current: Even during the
normal conditions, a switchgear may be expected toswitchon more than its rated current. For example, whileswitching on an induction motor. The switchgear shouldnot fail then.
This specification implies the maximum current told as amultiple of Ie, that the switchgear can safely make,
without causing any damage to itself or to the installationor to the operator.
7/28/2019 1.2 Terminology...
24/41
Rated Normal Condition Breaking Current: Even during the
normal conditions, a switchgear may be expected toswitchoff more than its rated current. For example, whilethe overload relay of an induction motor senses a overloadand trips the switchgear. The switchgear should not fail
then.
This specification implies the maximum current told as a
multiple of Ie, that the switchgear can safely break,without causing any damage to itself or to the installationor to the operator.
Low Voltage Switchgear Terminology Normal
C o n d i t i o n B e h a v i o r
7/28/2019 1.2 Terminology...
25/41
RATEDSHORTCIRCUITMAKINGCAPACITY(Icm
)
RATEDSHORTTIMEWITHSTANDCURRENT(Icw)
RATEDSHORTCIRCUITBREAKINGCAPACITY(Icn)
Low Voltage Switchgear Terminology Short
C i r c u i t C o n d i t i o n B e h a v i o r
7/28/2019 1.2 Terminology...
26/41
Low Voltage Switchgear Terminology Behavioru n d e r S h o r t C i r c u i t C o n d i t i o n
Rated Short Circuit Making Current: It might be possible thatthe switchgear might be closing on to a fault. (i.e.) theremight be an existing fault and unaware of the same, anattempt is made to close the switchgear. Quite a huge electro
dynamic force is developed under such conditions and theswitchgear shall not explode. It should withstand suchstresses too. This capacity of the switchgear is called the rated
short circuit making capacity. This will tell the maximumcurrent that the switchgear can safely make, under shortcircuit conditions, without causing any damage to itself or tothe installation or to the operator.
7/28/2019 1.2 Terminology...
27/41
Rated Short Circuit Breaking Current: Similarly, a
switchgear is also expected to break short circuit currents.
The capacity of the switchgear to break short circuit
currents is called the rated short circuit breaking capacity.This will tell the maximum current that the switchgear can
safely break, under short circuit conditions, without
causing any damage to itself or to the installation or to theoperator.
Low Voltage Switchgear Terminology Behavior
u n d e r S h o r t C i r c u i t C o n d i t i o n
7/28/2019 1.2 Terminology...
28/41
Rated Short time withstand Current (Icw): When there is ashort circuit, the nearest switchgear to the fault shall tripand isolate the fault. In case, it doesnt trip, the next
upstream breaker would trip after a time delay, and so on.This is called discrimination.
In the worst case of the uppermost stream breaker onlytripping on a down
most stream fault, all the breakers in
series, would have to carry the fault current for the entireduration, without any damage.
Low Voltage Switchgear Terminology Behavior
u n d e r S h o r t C i r c u i t C o n d i t i o n
7/28/2019 1.2 Terminology...
29/41
The ability of the switchgear to carry the short circuitcurrent for the coordinated short circuit time, is called
Icw. Obviously, the more Icw, that a switchgear has got,
the more coordination interval that one has got. This is
normally specified as, say, 50kA for 1 sec. Many switchgear
may have making and breaking capacities of, say, 50kA, but
their oneminute Icw will be lower at, say, 35kA only. So,
this specification must also be paid attention to, while
specifying switchgear.
Low Voltage Switchgear Terminology Behavior
u n d e r S h o r t C i r c u i t C o n d i t i o n
7/28/2019 1.2 Terminology...
30/41
Low Voltage Switchgear Terminology Utilisation
c a t e g o r y
Switchgear is a switching device. As such, it could beemployed for any kind of switching operation. But, its
characteristics like the operational current, the making &breaking currents will greatly depend on the application.Based on the applications, switchgear are categorizedunder different Utilization categories.
7/28/2019 1.2 Terminology...
31/41
N O R M A L S E R V I C E C O N D I T I O NAMBIENT TEMPERATURE
MAXIMUM 40C AVERAGE OVER 24 HRS NOT
MORE THAN 35C
MINIMUM 5C
ALTITUDE
DOES NOT EXCEED 2000m
7/28/2019 1.2 Terminology...
32/41
HUMIDITY
RELATIVE HUMIDITY DOES NOT
EXCEED 50% AT MAXIMUM
TEMPERATURE OF 40 C
POLLUTION DEGREE
POLLUTION DEGREE 3
N O R M A L S E R V I C E C O N D I T I O N
7/28/2019 1.2 Terminology...
33/41
P O L L U T I O N D E G R E E 1 ( L I G H T )
Areas without industries and with low density of houses
equipped with heating.
Areas with low density of industries or houses but
subjected to winds and/or rainfall.
Agricultural areas
Mountainous areas
These areas shall be situated at least 20 km from the sea
and thus not exposed to wind from the sea.
7/28/2019 1.2 Terminology...
34/41
P O L L U T I O N D E G R E E 2 ( M E D I U M )
Areas with industries not producing particularly
polluting smoke and / or with average density of housesequipped with heating.
Areas with high density of houses and / or industries butsubjected to frequent winds and / or rainfall.
Areas exposed to wind from the sea but not too close tothe coast.
7/28/2019 1.2 Terminology...
35/41
P O L L U T I O N D E G R E E 3 ( H E A V Y )
Areas with high density of industries and suburbs
of large cities with high density of heating plants
producing pollution.
Areas close to the sea or in any case exposed to
relatively strong winds from the sea.
7/28/2019 1.2 Terminology...
36/41
P O L L U T I O N D E G R E E 4( V E R Y H E A V Y )
Areas generally of moderate extent, subjected toconductive dusts and to industrial smoke producingparticularly thick conductive deposits.
Areas generally of moderate extent, very close tothe coast and exposed to sea-spray or very strongand polluting winds from the sea.
Desert areas, characterized by no rain for longperiods, exposed to strong winds carrying sand andsalt, and subject to regular condensation.
7/28/2019 1.2 Terminology...
37/41
POLLUTION DEGREEPollution Degree 1- No Pollution or only dry non-conductingpollution
Pollution Degree 2- Normally non-conductive pollution, butoccasionally temporary conductivity caused by condensationmust be expected
Pollution Degree 3- Conductive pollution or dry non-conductive pollution which becomes conducting due tocondensation
Pollution Degree 4- Pollution generates persistent conductivitycaused by conductive dust and/or rain or snow
7/28/2019 1.2 Terminology...
38/41
P o l l u t i o n d e g r e e
Guidelines:
A/c and/or drydustfree areas Degree 1
Household & similar areas Degree 2
Normal industrial
environment Degree 3
Outdoor Installation Degree 4
7/28/2019 1.2 Terminology...
39/41
P O L L U T I O N D E G R E E S
Pollutionlevel Minimumnominal
specificcreepage
distance(mm/kV)
I
Light 16
II Medium 20
III Heavy 25
IV
Very Heavy 31
7/28/2019 1.2 Terminology...
40/41
M a t e r i a l g r o u p
Classification of Insulating materials
Group I 600 < CTI
Group II 400 < CTI < 600
Group III a 175 < CTI < 400
Group III b 100 < CTI < 175
(CTI = Comparative Tracking Index)
7/28/2019 1.2 Terminology...
41/41
ThankYou