INSPECTION REPORT
For the Property at:
123 ANYSTREETMYTOWN, NY
Prepared for: HOME BUYERInspection Date: Wednesday, October 19, 2016
Prepared by: Jim Freebody
Nassau Home Inspections135 Aspinwall St
Westbury, NY 11590516 840 9400
www.nshinspection.com
December 16, 2016
Dear Home Buyer,
RE: Report No. 1451, v.3123 AnystreetMytown, NY
Your report is now accessible by clicking the link at the bottom of this message - this report is protected and can only beviewed from this link - It will be available online for 180 days.
If your inspection included a Termite (Wood Destroying Insect Inspection), it can be found under the appendix tab at theend of the report.
To send a full copy of this report to your Realtor or Attorney, simply forward them this email.
Our business is mostly on a referral basis. We hope that you were satisfied with our service.Any feedback and referrals are greatly appreciated.
We sincerely thank You for your business. Best wishes and good luck in your new home,
Sincerely,
Jim Freebodyon behalf ofNassau Home Inspections
Nassau Home Inspections135 Aspinwall St
Westbury, NY 11590516 840 9400
SUMMARY
Nassau-suffolk Home Inspections wishes to remind you, every home requires a certain amount of ongoing maintenance,such as, clogged drains, servicing of furnaces, air conditioners, water heaters, etc. It is suggested that you budget forregular maintenance/repairs.
The following summary is based on a visual inspection of the accessible areas of this property.
Roofing
SLOPED ROOFING \ Asphalt shinglesCondition: Old, worn outImplication(s): Chance of water damage to contents, finishes and/or structureLocation: GarageTask: Replace
Exterior
ROOF DRAINAGE \ DownspoutsCondition: Downspouts end too close to buildingImplication(s): Chance of water damage to contents, finishes and/or structureLocation: Various ExteriorTask: Correct
WALLS \ TrimCondition: RotImplication(s): Chance of water damage to contents, finishes and/or structure | Material deteriorationLocation: GarageTask: Repair or replace
EXTERIOR GLASS \ Glass (glazing)Condition: Putty missing, cracked or deterioratedImplication(s): Chance of water entering building | Increased heating and cooling costsLocation: Right Side and Rear Bay Window ExteriorTask: Repair or replace
EXTERIOR GLASS \ Exterior trimCondition: Missing or loose piecesImplication(s): Cosmetic defects | Chance of water damage to contents, finishes and/or structureLocation: GarageTask: Repair or replace
EXTERIOR GLASS \ Window wellsCondition: Deep Window Well should have protective cover/fencing to prevent fallsLocation: Various Exterior
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 1 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
SUMMARY
PORCHES, DECKS, STEPS, PATIOS AND BALCONIES \ Steps and landingsCondition: recommend repointing brick/stone on stepsLocation: Front and Right Side
LANDSCAPING \ DrivewayCondition: Deteriorated Asphalt DrivewayLocation: Right SideTask: Monitor
LANDSCAPING \ GeneralCondition: Note: Termite Baiting System installed around exterior perimeter of foundation - Request Disclosure as toreason and if currently under Service Contract.Location: Throughout Exterior
Electrical
DISTRIBUTION SYSTEM \ Outlets (receptacles)Condition: old style 2 prong ungrounded outletsLocation: VariousTask: Upgrade
Condition: LooseImplication(s): Electric shock | Fire hazardLocation: BathroomTask: Improve
Condition: Ground Fault Circuit Interrupter (GFCI) neededImplication(s): Electric shockLocation: Second Floor BathroomTask: Upgrade
Condition: Ground Fault Circuit Interrupter (GFCI) neededImplication(s): Electric shockLocation: KitchenTask: Upgrade
Heating
GAS HOT WATER BOILER \ Radiators, convectors and baseboardsCondition: Leaning out at top -Not standing up straightLocation: Second Floor BedroomTask: Further evaluation
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 2 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
SUMMARY
Cooling & Heat Pump
AIR CONDITIONING \ Life expectancyCondition: Near end of life expectancyImplication(s): Equipment failure | Reduced comfortTask: Monitor
Plumbing
WATER HEATER \ Temperature/pressure relief valveCondition: Discharge tube missingImplication(s): ScaldingLocation: BasementTask: Provide
FIXTURES AND FAUCETS \ FaucetCondition: Sink Sprayer taped upLocation: KitchenTask: Repair or replace
FIXTURES AND FAUCETS \ Hose bib or bibbCondition: exterior faucet(s) not frost proof type - must be turned off from inside basement during winter to preventfreezing or replace with frost free faucet(s).Location: Various ExteriorTask: Upgrade
Interior
EXHAUST FANS \ Exhaust fanCondition: InoperativeImplication(s): Chance of condensation damage to finishes and/or structureLocation: KitchenTask: Repair or replace
APPLIANCES \ DryerCondition: Dryer Vent Hose should be made of flexible metal.Location: BasementTask: Replace
This concludes the Summary section.
The remainder of the report describes each of the home's systems and also details any recommendations we have forimprovements. Limitations that restricted our inspection are included as well.
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 3 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
ROOFING
Description
Sloped roofing material: Approximate age of roof is 5-10 years
Sloped roofing material:Asphalt shingles
Limitations
General: The precise age of the roof cannot always be determined, due to certain roof materials, such as slate andwood styles. Leaks in roof and roof flashings may not be discovered at the time of the inspection and/or may sometimesdevelop after the inspection, due to severe weather conditions or impact. This inspection is not a guarantee against roofleakage in the future.
Recommendations
SLOPED ROOFING \ Asphalt shinglesCondition: Old, worn outImplication(s): Chance of water damage to contents, finishes and/or structureLocation: GarageTask: Replace
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 4 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
ROOFING123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 5 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
EXTERIOR
Description
General: General Exterior Photos
Gutter & downspout material: Aluminum
Gutter & downspout type: Eave mounted
Downspout discharge: Above grade
Lot slope: Away from building
Wall surfaces - wood: Shingles
Driveway: Asphalt
Walkway: Concrete Pressure-treated wood
Deck: Ground level Pressure-treated wood
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 6 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
EXTERIOR
Exterior steps: Concrete
Recommendations
ROOF DRAINAGE \ DownspoutsCondition: Downspouts end too close to buildingImplication(s): Chance of water damage to contents, finishes and/or structureLocation: Various ExteriorTask: Correct
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 7 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
EXTERIOR
WALLS \ TrimCondition: RotImplication(s): Chance of water damage to contents, finishes and/or structure | Material deteriorationLocation: GarageTask: Repair or replace
EXTERIOR GLASS \ Glass (glazing)Condition: Putty missing, cracked or deterioratedImplication(s): Chance of water entering building | Increased heating and cooling costsLocation: Right Side and Rear Bay Window ExteriorTask: Repair or replace
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 8 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
EXTERIOR
EXTERIOR GLASS \ Exterior trimCondition: Missing or loose piecesImplication(s): Cosmetic defects | Chance of water damage to contents, finishes and/or structureLocation: GarageTask: Repair or replace
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 9 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
EXTERIOR
EXTERIOR GLASS \ Window wellsCondition: Keep window wells free from debris - bottom of well should be 6-8 inches below window frames
Condition: Deep Window Well should have protective cover/fencing to prevent fallsLocation: Various Exterior
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 10 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
EXTERIOR
PORCHES, DECKS, STEPS, PATIOS AND BALCONIES \ Steps and landingsCondition: recommend repointing brick/stone on stepsLocation: Front and Right Side
LANDSCAPING \ DrivewayCondition: Deteriorated Asphalt DrivewayLocation: Right SideTask: Monitor
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 11 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
EXTERIOR
LANDSCAPING \ GeneralCondition: Note: Termite Baiting System installed around exterior perimeter of foundation - Request Disclosure as toreason and if currently under Service Contract.Location: Throughout Exterior
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 12 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
STRUCTURE
Description
Configuration: Basement
Foundation material: Poured concrete
Floor construction: Joists Steel columns Laminated wood beams Subfloor - plank
Exterior wall construction: Wood frame
Roof and ceiling framing: original cedar shingle roofing, used as roof sheathing
Roof and ceiling framing:Rafters/roof joists
Limitations
General: Please note that an inspection is not a guarantee that you do not have termites or damage in visuallyinaccessible areas, such as inside walls or behind finished basement surfaces. This is one reason why an annualTermite or Carpenter Ant inspection is valuable. Keep records of all such inspections.
Inspection limited/prevented by: Basement Mostly Finished Living Space
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 13 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
STRUCTURE123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 14 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
ELECTRICAL
Description
General: The National Fire Protection Agency (NFPA) urges homeowners to replace smoke detectors and CO detectorsmore than 10 years old, and to replace all smoke detectors when moving into a new residence unless you know that thesmoke detectors and CO detectors are new. Replacements are inexpensive and readily available.
Service entrance cable and location:Overhead copper
Service size: 100 Amps (240 Volts)
Main disconnect/service box rating: 100 Amps
Main disconnect/service box type and location:Breakers - basement
System grounding material and type: Copper - water pipe and ground rod
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 15 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
ELECTRICAL
Distribution wire material and type:Copper - non-metallic sheathedCopper - metallic sheathed
Circuit interrupters: Ground Fault (GFCI) & Arc Fault (AFCI): Ground Fault (GFCI) & Arc Fault (AFCI): Ground Faulted outlets(GFCI) and/or breakers are required for safety, in all interior and exterior areas where water will be incontact with an electrical power source. Standard cover plates should be labeled for "GFCI" when wired on the GFCIcircuit. Proper GFCI functionality may not always be fully tested at the time of the inspection because GFCI resets maybe hidden and not able to be reset.
Smoke detectors: Present
Recommendations
DISTRIBUTION SYSTEM \ Outlets (receptacles)Condition: old style 2 prong ungrounded outletsLocation: VariousTask: Upgrade
Condition: LooseImplication(s): Electric shock | Fire hazardLocation: BathroomTask: Improve
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 16 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
ELECTRICAL
Condition: Ground Fault Circuit Interrupter (GFCI) neededImplication(s): Electric shockLocation: Second Floor BathroomTask: Upgrade
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 17 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
ELECTRICAL
Condition: Ground Fault Circuit Interrupter (GFCI) neededImplication(s): Electric shockLocation: KitchenTask: Upgrade
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 18 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
HEATING
Description
General: Exterior Gas Main - Recommend keeping an adjustable wrench in a zip-lock bag, attached to meter, tofacilitate emergency gas shut-off.
Fuel/energy source: Gas
System type: Boiler
Boiler manufacturer: Slant/Fin
Heat distribution: Radiators
Approximate capacity: 150,000 BTU/hr
Efficiency: Conventional
Exhaust venting method: Natural draft
Approximate age: 6 years
Typical life expectancy:Boiler (cast iron) 25 to 50 years
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 19 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
HEATING
Main fuel shut off at: Basement
Fireplace: Masonry wood burning fireplace
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 20 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
HEATING
Chimney/vent: Masonry
Chimney liner:MetalClay
Limitations
General: Note: Flue not inspected. Annual cleaning recommended.Zone, boiler and radiator valves: Zone valves, radiator valves, circulators, integrated humdification units and internalparts of the heating system are inspected for proper functionality, but can not be fully tested, as full tests would beconsidered invasive.
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 21 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
HEATING
Recommendations
GAS HOT WATER BOILER \ Radiators, convectors and baseboardsCondition: Leaning out at top -Not standing up straightLocation: Second Floor BedroomTask: Further evaluation
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 22 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
COOLING & HEAT PUMP
Description
Air conditioning type: Air cooled
Manufacturer: Bryant
Cooling capacity: 24,000 BTU/hr
Compressor type: Electric
Compressor approximate age: 19 years
Typical life expectancy: 15 to 20 yearsNote: Central A/C for top floor only
Recommendations
AIR CONDITIONING \ Life expectancyCondition: Near end of life expectancyImplication(s): Equipment failure | Reduced comfortTask: Monitor
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 23 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
INSULATION AND VENTILATION
Description
Attic/roof insulation material: Glass fiber
Attic/roof ventilation:Gable ventPower ventilator
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 24 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
PLUMBING
Description
Water supply source: Public
Service piping into building: Copper
Supply piping in building: PEX (Cross-linked polyethylene)
Supply piping in building: Copper
Main water shut off valve at the:BasementMeter
Water flow and pressure: Typical for neighborhood
Water heater fuel/energy source: Gas
Water heater type: Conventional
Water heater exhaust venting method: Natural draft
Water heater manufacturer: General Electric
Tank capacity: 50 gallons
Water heater approximate age: 6 years
Typical life expectancy:8 to 12 years
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 25 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
PLUMBING
Waste disposal system: Public
Waste and vent piping in building: PVC plastic Cast Iron
Limitations
General: The following plumbing system items are not covered, as they are beyond the scope of this inspection;Isolated or hidden plumbing pipes and relief valves. Main exterior water shut-off valves will not be turned on/off. Tub/sinkoverflows will not be tested. Water quality not tested. Water treatment equipment will not be inspected. Solar andGeo-Thermal plumbing, heating and cooling systems are not inspected.French Drain Systems cannot be pressure tested and cannot be tested for their performance. It is recommended thatthey be fully tested and inspected by a professional technician. Cesspools cannot be opened.
Recommendations
WATER HEATER \ Temperature/pressure relief valveCondition: Discharge tube missingImplication(s): ScaldingLocation: BasementTask: Provide
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 26 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
PLUMBING
FIXTURES AND FAUCETS \ FaucetCondition: Sink Sprayer taped upLocation: KitchenTask: Repair or replace
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 27 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
PLUMBING
FIXTURES AND FAUCETS \ Hose bib or bibbCondition: exterior faucet(s) not frost proof type - must be turned off from inside basement during winter to preventfreezing or replace with frost free faucet(s).Location: Various ExteriorTask: Upgrade
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 28 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
PLUMBING123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 29 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
INTERIOR
Description
General: General Interior Photos
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 30 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
INTERIOR
General: General Interior Photos
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 31 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
INTERIOR123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 32 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
INTERIOR
Major floor finishes: Hardwood Laminate Ceramic
Major wall and ceiling finishes: Plaster/drywall
Windows: Single/double hung Vinyl
Glazing: Double
Exterior doors - type/material: Metal/Glass
Exterior doors - type/material: Hinged French Storm Wood Garage door - wood
Oven type: Conventional
Oven fuel: Gas
Range fuel: Gas
Appliances: Refrigerator Range hood Dishwasher
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 33 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
INTERIOR
Laundry facilities:WasherLaundry tubHot/cold water supplyDryerVented to outside120-Volt outletWaste standpipe
Limitations
Inspection limited/prevented by: Garage filled with personal belongings
Not tested/not in service:Range
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 34 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
INTERIOR
Gas turned off - not tested
Recommendations
EXHAUST FANS \ Exhaust fanCondition: InoperativeImplication(s): Chance of condensation damage to finishes and/or structureLocation: KitchenTask: Repair or replace
APPLIANCES \ DryerCondition: Dryer Vent Hose should be made of flexible metal.Location: BasementTask: Replace
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 35 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
INTERIOR
END OF REPORT
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 36 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
APPENDIX
Nassau-suffolk Home Inspections135 Aspinwall StreetWestbury, NY 11590(515) 894-9400
N/A 10/19/2016
123 Anystreet, Mytown, NY
James Freebody 16000005080 Single Family Residence
Basement Mostly Finished Living Space 1,3,4,5,6,7,8
Termite Baiting System Installed Around Exterior
123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 37 of 38
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
APPENDIX
APPENDIX123 Anystreet, Mytown, NY October 19, 2016 www.nshinspection.com
Providing great home inspections for every client every time
Report No. 1451, v.3
Page 38 of 38