+ All Categories
Home > Documents > 124479095 PSV Calculation Ppt

124479095 PSV Calculation Ppt

Date post: 09-Oct-2015
Category:
Upload: raghavan0189
View: 331 times
Download: 51 times
Share this document with a friend
Description:
sizing
Popular Tags:
79
OIL & GAS WorleyParsons  OIL&GAS  PSV Sizing Calculation 23-June-05 
Transcript
  • 5/20/2018 124479095 PSV Calculation Ppt

    1/79

    OIL & GAS

    WorleyParsons

    OIL&GAS

    PSV Sizing Calculation

    23-June-05

  • 5/20/2018 124479095 PSV Calculation Ppt

    2/79

    OIL & GAS

    CONTENT

    INTRODUCTION

    PSV TYPES

    CHATTERING PROBLEM

    SIZING CALCULATION

    EXAMPLE

  • 5/20/2018 124479095 PSV Calculation Ppt

    3/79

    OIL & GAS

    INTRODUCTION

    Relief systems are provided on a platform in order toensure the safe operation of the facilities.

    In accordance with API RP 14C, all hydrocarbons handling

    equipment and pressure vessels will be provided with two

    levels of over protection, high pressure trip (PSHH) withshutdown action, and protection by mechanical devices,

    Pressure Safety Valve (PSV) or Rupture Disc.

    PSVs are installed at every point identified as potentially

    hazardous, that is, at points where upset conditions

    create pressure which may exceed the maximum

    allowable working pressure.

  • 5/20/2018 124479095 PSV Calculation Ppt

    4/79

    OIL & GAS

    INTRODUCTION

    How High Pressure Develop

    Over heating

    High head ( from pumping or compression)

    Over Filling

    Failure of Regulator / Control valve.External Fire

    Runaway Reaction

    Combustion of gas/dust

    Freezing

    Thermal Expansion

    Loss of Mixing

    Others

  • 5/20/2018 124479095 PSV Calculation Ppt

    5/79

    OIL & GAS

    INTRODUCTION

    Definitions

    Operating pressure: The gauge pressure during normal

    service.

    Set Pressure: The pressure at which the relief device

    begins to activate or open.

    Maximum Allowable Working Pressure (MAWP): The

    maximum guage pressure permissible at the top of a vessel

    for a designated temperature.

    Vessel fails at 4 to 5 times of MAWP!!!! . But onlyhydrostatically tested to 1.5 times.

    Accumulation: The pressure increase over the maximum

    allowable working pressure of a vessel during the relief

    process. Expressed as % of MAWP.

  • 5/20/2018 124479095 PSV Calculation Ppt

    6/79

    OIL & GAS

    INTRODUCTION

    Set Pressure

    Relief begin to open

    Accumulation

    Pressure

    Time

  • 5/20/2018 124479095 PSV Calculation Ppt

    7/79

    OIL & GAS

    Definitions

    Over Pressure: The pressure increase in vessel over the set

    pressure during the relieving process. Overpressure is

    equivalent to the accumulation when the set pressure is at the

    MAWP. Expressed as % of set pressure. Must be specified prior

    relief design. Typically 10 % ( or for fire 21%) will be used.

    Pressure

    Time

    Relief begin to open

    Set Pressure

    Over Pressure

    INTRODUCTION

  • 5/20/2018 124479095 PSV Calculation Ppt

    8/79

    OIL & GAS

    Definitions

    Blow-down: The pressure difference between the relief

    set pressure and the relief reseating pressure.

    Maximum Allowable Accumulated Pressure: The sum of

    the maximum allowable working pressure plus the allowable

    accumulation.

    INTRODUCTION

  • 5/20/2018 124479095 PSV Calculation Ppt

    9/79

    OIL & GAS

    INTRODUCTION

    Guideline for relief pressures

    (Adapted from API RP 520 : Sizing, Selection, and Installation of Pressure-RelievingDevices in Refineries., page 3)

  • 5/20/2018 124479095 PSV Calculation Ppt

    10/79

    OIL & GAS

    Definitions

    Back Pressure: The pressure at the outlet of the relief

    device during the relief process due to pressure in the

    discharge system.

    1. Superimposed Back Pressure.

    2. Built-up Back Pressure.

    Total Back Pressure = Superimposed Back Pressure + Built-up Back Pressure

    INTRODUCTION

  • 5/20/2018 124479095 PSV Calculation Ppt

    11/79

    OIL & GAS

    INTRODUCTION

    Definitions

    1. Superimposed Back Pressure is the back pressure which

    may exist at the outlet of a particular relief valve when connected

    to a closed system. The pressure can be constant or variable. The

    Superimposed back pressure always exists even when the relief

    valve is closed.

    2. Built-up Back Pressure is the pressure at the discharge of a

    relief device which develops due to the relief flow through the

    device when the relief valve opens. The built-up back pressure

    depends on the valve itself but also on the design of the relief

    piping. It can reach excessive values in the case of vary highset pressures and/or poorly designed piping with too much pressure

    Loss. The built-up back pressure is variable.

  • 5/20/2018 124479095 PSV Calculation Ppt

    12/79

    OIL & GAS

    PSV TYPES

    General Design of PSV

    1. Direct acting type

    Oldest and most common.

    Kept closed by a spring or weight to oppose

    lifting force of process pressure.

    2. Balanced Bellows.

    3. Pilot operated type

    Kept closed by process pressure

    4. Modulating Pilot.

  • 5/20/2018 124479095 PSV Calculation Ppt

    13/79

    OIL & GAS

    PSV TYPES

    The following types of PSV are generally used.

    1. Conventional PSV

    2. Balanced Type PSV (Balanced Bellow)

    3. Pilot Operated PSV

    4. Modulating Pilot Operated PSV5. Thermal PSV

  • 5/20/2018 124479095 PSV Calculation Ppt

    14/79

    OIL & GAS

    PSV TYPES

    Conventional PSV

    AdvantagesMost reliable type if properly sized

    and operated

    Versatile -- can be used in many services

    Compatible with fouling or dirty service.

    Disadvantages

    Relieving pressure affected byback pressure

    Susceptible to chatter if built-up

    back pressure is too high

  • 5/20/2018 124479095 PSV Calculation Ppt

    15/79

    OIL & GAS

    Balanced Bellow PSV

    PSV TYPES

    AdvantagesRelieving pressure not affected by back

    pressure.

    Can handle higher built-up back pressure.

    Protects spring from corrosion.

    Wide range of materials available &

    chemical compatibility.

    Disadvantages

    Bellows susceptible to fatigue/rupture.

    May release flammables/toxics to

    atmosphere.

    High maintenance costs.

  • 5/20/2018 124479095 PSV Calculation Ppt

    16/79

    OIL & GAS

    Pilot Operated PSV

    Advantages

    Relieving pressure not affected by

    backpressure

    Can operate at up to 98% of set pressure

    Less susceptible to chatter (some models)

    Disadvantages

    Pilot is susceptible to plugging (thereforenot recommended for fouling service,

    eg. Wax).

    Limited chemical and high temperature

    use by O-ring seals

    Vapor condensation and liquid

    accumulation above the piston may

    cause problems

    Potential for back flow

    PSV TYPES

  • 5/20/2018 124479095 PSV Calculation Ppt

    17/79

    OIL & GAS

    CHATTERING PROBLEM

    Modulating Pilot Operated

    There are two main types of pilot control operation

    Pop action Main valve fully open at set pressure

    Modulating : Main valve opens according to relief demand.

    Modulating pilots have additional advantages:

    They only open the main valve enough to keep the system at set

    pressure which leads to less wasted product being relieved

    through the valve.

    Less noise generated by the valve when it is required to relieve.

    Recommended for Wellhead platform PSV.

  • 5/20/2018 124479095 PSV Calculation Ppt

    18/79

    OIL & GAS

    CHATTERING PROBLEM

    Main valve

    piston lift

    Pressure

    Opening

    Closing

    100 % Lift POP Action

  • 5/20/2018 124479095 PSV Calculation Ppt

    19/79

    OIL & GAS

    CHATTERING PROBLEM

    Main valve

    piston lift

    Pressure

    Opening

    Closing

    100 % LiftModulating

  • 5/20/2018 124479095 PSV Calculation Ppt

    20/79

    OIL & GAS

    Chattering Problem

    Chattering is the rapid, alternating opening and closing

    of a PSV.

    Resulting vibration may cause misalignment, valve seatdamage and, if prolonged, can cause mechanical failure

    of valve internals and associated piping.

    Chatter may occur in either liquid or vapor services

    CHATTERING PROBLEM

  • 5/20/2018 124479095 PSV Calculation Ppt

    21/79

    OIL & GAS

    Cause of Chattering

    Excessive inlet pressure drop

    Excessive built-up back pressure

    Oversized valve

    Valve handling widely differing rates

    CHATTERING PROBLEM

  • 5/20/2018 124479095 PSV Calculation Ppt

    22/79

    OIL & GAS

    Excessive inlet pressure drop

    Normal PSV has definite pop

    and reseat pressures.

    CHATTERING PROBLEM

    Reseat orclose pressure

    Pop or opening pressure

    Blow-down = Different between pop and reseat pressure

  • 5/20/2018 124479095 PSV Calculation Ppt

    23/79

    OIL & GAS

    CHATTERING PROBLEM

    Excessive inlet pressure drop : Solution

    If you cant change the

    piping

    Install smaller PSV

    Install different type of

    PSV

  • 5/20/2018 124479095 PSV Calculation Ppt

    24/79

    OIL & GAS

    CHATTERING PROBLEM

    Excessive Built-up Back Pressure

    Excessive outlet pressure will also cause chatter.

    Avoid

    Long outlet piping runs. Elbows and turns.

    Sharp edge reductions.

    But if you must

    Make outlet piping large!

  • 5/20/2018 124479095 PSV Calculation Ppt

    25/79

    OIL & GAS

    CHATTERING PROBLEM

    Improper Valve Size

    Oversized valve

    Must flow at least 25% of capacity to keep valve open.

    Especially bad in larger sizes.

    Valve handling widely differing rates

    Leads to oversized valve case.

  • 5/20/2018 124479095 PSV Calculation Ppt

    26/79

    OIL & GAS

    SIZING CALCULATION

    Step Of Sizing CalculationDevelop Process Safety Diagram (PSD)

    Develop relief scenarios by using general possible cause and PSD

    Determine required relief area for each cases (Gas, Liquid, 2-Phases)

    Choose the worst case scenario to be a governing case

    Select proper orifice and valve body size based on STD

    Calculate inlet line size (Line P < 3%of RP)

    Perform preliminary estimate of tail pipe

    Perform Flare system modeling to indicate total back pressureand most suitable tail pipe size.

    Select PSV type (Conventional, Balanced Bellow, Pilot Operated

  • 5/20/2018 124479095 PSV Calculation Ppt

    27/79

    OIL & GAS

    SIZING CALCULATION

    Develop Process Safety Diagram (PSD)

    Process safety diagram is the diagram which show

    all installation of all process safety equipments (PSHH,

    TSHH, PSV, BDV, Rupture disc, etc.) intend to be used in

    evaluation of all possible relieving scenarios in process

    facilities. Process safety diagram must be developed beforeperforming any PSV calculation.

  • 5/20/2018 124479095 PSV Calculation Ppt

    28/79

    OIL & GAS

    SIZING CALCULATION

    Develop Process Safety Diagram (PSD)

  • 5/20/2018 124479095 PSV Calculation Ppt

    29/79

    OIL & GAS

    SIZING CALCULATION

    Develop relief scenarios by using general possible cause and PSD

    EquipmentPossible Scenarios

    PumpHEX LineVessel /Column

    Compressor

    Blocked Outlet

    Thermal Expansion

    Tube Rupture

    Gas Blow-by

    Inlet Control Valve Failure

    Exterior Fire

    Note : Exterior Fire is not applicable for PHEX!!

  • 5/20/2018 124479095 PSV Calculation Ppt

    30/79

    OIL & GAS

    SIZING CALCULATION

    Blocked Outlet/ Blocked Discharge

    CLOSED

    CLOSED

    CLOSED

    CLOSED

    CLOSED

    Process Vessel

    Compressor Pump

    This situation arises from the inadvertent closure of a block valve or failure

    of a control valve in the closed position on an outlet line. Typical

    overpressure application where this form of protection is required includes

    production separators, compressor discharge piping or pump discharge

    piping. The safety relief valves are sized to handle 100% of the anticipated

    upstream flow. If the feed stream(s) is multi-phase, the relief rate is the totalinlet flow (gas plus liquids).

  • 5/20/2018 124479095 PSV Calculation Ppt

    31/79

    OIL & GAS

    SIZING CALCULATION

    Thermal Expansion/ Thermal Relief

    Heat Exchanger

    Line

    Hot Side

    Cold Side

    CLOSED CLOSED CLOSED

    Thermal expansion relief valves (TERVs) are required in liquid-full systemsif the system can be blocked in and/or subjected to heat input from theatmosphere or process that results in overpressure.

  • 5/20/2018 124479095 PSV Calculation Ppt

    32/79

    OIL & GAS

    SIZING CALCULATION

    Tube Rupture

    Heat Exchanger

    Hot Side

    Cold SideOR

    Heat Exchanger

    Hot Side

    Cold Side

    Tube rupture causing vapour to enter either the tubeside or shellside

    of a heat exchanger will cause a pressure spike to travel through the

    fluid at sonic velocity. Generally, a PSV will not lift fast enough to protect

    the system. Protection against tube rupture is typically by the useof bursting discs.

  • 5/20/2018 124479095 PSV Calculation Ppt

    33/79

    OIL & GAS

    SIZING CALCULATION

    Suddenly OpeningPressure at PSHH

    Liquid at LSLL

    Gas blow-by occurs when liquid level in a partially filled vessel drops solow that gas exits via the liquid outlet nozzle due to level control failure.

    Loss of liquid level will result in gas from the high pressure vessel passinginto the low pressure system downstream of the liquid level control valve.

    Gas Blow-by

  • 5/20/2018 124479095 PSV Calculation Ppt

    34/79

    OIL & GAS

    SIZING CALCULATION

    Fail to openPressure at normalLiquid at normal

    Inlet Control Valve Failure

    The relief rate is equal to the difference between the maximum inlet

    flow and the flow, at relief conditions, from the outlet valves that

    remain open. No credit for outlet valves response will be taken i.e.

    they will be assumed to remain at their normal operating point

    (% open).

  • 5/20/2018 124479095 PSV Calculation Ppt

    35/79

    OIL & GAS

    SIZING CALCULATION

    Exterior Fire

    Generally, the production & processing facilities will be segregated into fire

    areas, by means of plated decks, fire walls, or edge of the platform. During

    a fire in one of the fire areas, all equipment within that area is assumed to be

    fully exposed to the fire.

    It is assumed that during a fire there is no feed to or product from an

    affected system, and all normal heat inputs have ceased.

    No credit will be taken for the presence of any water spray systems.No credit will be taken for thermal insulation on vessels.

  • 5/20/2018 124479095 PSV Calculation Ppt

    36/79

    OIL & GAS

    SIZING CALCULATION

    Pool Fire

    Jet Fire

    Fire Type

    Systems with significant liquid

    hydrocarbon inventory will be

    considered for pool fire case.

    Heat flux will be calculated as

    per API RP521. Credit for a 40%

    reduction in heat flux may be

    taken for good drainage and

    the presence of prompt fire

    fighting efforts as specified inAPI RP 521.

    Where potential for jet fire exists, relief

    load will be calculated for higher heat flux

    from heat fire. The heat flux generated by

    jet fire ranges from 50 kW/m2 to 300 kW /m2.

    However, the net heat flux into the fluid will

    depend on many factors such as fuel type,

    vessel temperature, the surface emissivity,

    the fire environment, the radiative andconvective components of the fire.

  • 5/20/2018 124479095 PSV Calculation Ppt

    37/79

    OIL & GAS

    SIZING CALCULATION

    Vessel Type & Fluid relief type

    Vessel type could be :

    Dry or empty vessel

    Vessels containing liquid -> Need to consider effect ofwetted area of vessel

    Fluid relief type could be :

    Fluid is sub-critical: P 1.1*Pc

    Pc = Critical PressureP = Relieving Pressure

  • 5/20/2018 124479095 PSV Calculation Ppt

    38/79

    OIL & GAS

    SIZING CALCULATION

    Fire case

    Jet Fire

    Dry Vessel Wetted vessel

    Sub Critical FlowNear Critical FlowSuper Critical Flow

    Pool Fire2 CASES

    2 CASES

    3 CASES

    Totally = 2x2x3 = 12 cases possibleHence 12 methods of calculation for Fire case

  • 5/20/2018 124479095 PSV Calculation Ppt

    39/79

    OIL & GAS

    SIZING CALCULATION

    Determine required relief area for each case (Gas, Liquid, 2-Phases)

    Target of sizing relief valve

    1. Determine the relief rate.

    2. Determine the required relief area.

    3. Select the standard relief area.

    Code and standard required

    API RP 520 : Sizing, Selection, and Installation of Pressure-Relieving

    Devices in Refineries.

    API RP 521 : Guide for Pressure Relieving and Depressuring Systems.

  • 5/20/2018 124479095 PSV Calculation Ppt

    40/79

    OIL & GAS

    SIZING CALCULATION

    Relief Phase

    Single Phase Relief

    Two Phase Relief

    Vapor Phase Relief

    Liquid Phase Relief

    Relief Type

    Continuous Relief

    Transient Relief Thermal Relief

    Generally

    Gas/Vapor

    Steam

    Relief fluid category

    Determine required relief area for each case (Gas, Liquid, 2-Phases)

  • 5/20/2018 124479095 PSV Calculation Ppt

    41/79

    OIL & GAS

    SIZING CALCULATION

    Determine relief rate, some cases (eg. Gas blow-by, tube rupture,

    fire case etc.) are very complicated and contain many steps of calculation

    especially fire case.

    API RP520/ 521 shows the simple method of calculation in order todetermine the relief rate. This does not govern all relief scenarios. Hence

    some companies have developed their own procedure to determine the

    relief rate.

    Determine required relief area for each case (Gas, Liquid, 2-Phases)

  • 5/20/2018 124479095 PSV Calculation Ppt

    42/79

    OIL & GAS

    SIZING CALCULATION

    Vapor Phase Relief

    Relief valves for single phase vapour flow will be sized according

    to the methodology presented in API RP 520, Section 3 (reference 4).

    The sizing equations fall into 2 categories, depending on whether

    flow is critical or subcritical.

    The critical pressure must be checked using the equation below:

    )1(

    1

    1

    2.

    k

    k

    cf

    k

    PP

    where

    Pcf= critical flow throat pressure (psia)

    P1= upstream relieving pressure (psia)k= ratio of specific heats

    Ref. API 520 section 3.6.1.4

  • 5/20/2018 124479095 PSV Calculation Ppt

    43/79

    OIL & GAS

    SIZING CALCULATION

    Vapor Phase Relief

    If flow is critical (Pcf > downstream pressure P2), the criticalsizing equation is used:

    A W

    C K P K

    TZ

    Md b

    1

    Ref. API 520 section 3.6.2.1

    WhereA = required effective discharge area of the valve ( in2).

    W = required flow through the valve (lb/hr).

    C = coefficient determined from an expression of the ratio of the specific heats of the gas

    or vapour at standard conditions. This can be obtained from Figure 26 or Table 9 in

    API 520.

    Kd = effective coefficient of discharge = 0.975

    P1 = upstream relieving pressure, in psia.Kb = capacity correction factor due to back-pressure. This can be obtained from the

    manufacturers literature or estimated from Figure 27 in API 520. The back-pressure

    correction factor applies to balanced-bellows valves only.

    T = relieving temperature of the inlet gas or vapour, in R.

    Z = compressibility factor for the deviation of the actual gas from a perfect gas, a ratio

    evaluated at inlet conditions.M = molecular weight of the gas or vapour.

  • 5/20/2018 124479095 PSV Calculation Ppt

    44/79

    OIL & GAS

    SIZING CALCULATION

    Vapor Phase Relief

    If flow is subcritical, the following equation will be used:

    )(..735 2112 PPPM

    ZT

    KF

    WA

    d Ref. API 520 section 4.3.3.1

    Where A = required effective discharge area of the valve, in square inches.

    W = required flow through the valve, in pounds per hour.F2 = coefficient of subcritical flow

    =

    r

    rr

    k

    k kk

    k

    1

    1)(

    )1(

    12

    Ref. API 520 section 4.3.3.1

  • 5/20/2018 124479095 PSV Calculation Ppt

    45/79

    OIL & GAS

    SIZING CALCULATION

    k = ratio of the specific heats.

    r = ratio of back pressure to upstream relieving pressure, P2/P1.

    Kd = effective coefficient of discharge = 0.975

    Z = compressibility at relieving inlet conditions.

    T = relieving temperature of the inlet gas or vapour (R)

    M = molecular weight of the gas or vapour.P1& P2 = upstream relieving pressure and back-pressure pressure respectively (psia)

    Vapor Phase Relief

  • 5/20/2018 124479095 PSV Calculation Ppt

    46/79

    OIL & GAS

    SIZING CALCULATION

    Vapor Phase Relief

    Relief valves in steam servicewill be sized as follows:

    A W

    P K K Kd N SH

    51 5 1.Ref API 520 Section 3.7.1

    Where

    A = required effective discharge area of the valve ( in2).

    W = required flow through the valve (lb/hr).

    P1 = upstream relieving pressure (psia)

    Kd = effective coefficient of discharge = 0.975

    KN = correction factor for Napier equation.= 1 where P11515 psia.

    = (0.1906P11000)/(0.2292P11061) where P11515 psia and 3215 psia

    KSH = superheat steam correction factor. This can be obtained from Table 9 in API RP520.For saturated steam at any pressure, KSH-= 1.0.

  • 5/20/2018 124479095 PSV Calculation Ppt

    47/79

    OIL & GAS

    SIZING CALCULATION

    Liquid Phase Relief

    For single phase liquid flow, the sizing method specified for

    certified relief valves will be used.

    The following equation only applies to non-flashing liquids.

    A Q

    K K K

    G

    P Pd w v

    38 1 2Ref. API 520 section 4.5.1

    Where

    A = required effective discharge area of the valve ( in2).

    Q = flow rate, in U.S. gallons per minute.

    Kd = effective coefficient of discharge that should be obtained from the valve manufacturer.For a preliminary sizing estimation, a discharge coefficient of 0.65 can be used.

    Kw = correction factor due to back-pressure. If the back-pressure is atmospheric, KW= 1.

    Balanced-bellows valves in back-pressure service will require the correction factor

    determined in Figure 31 in API RP520. Conventional valves require no special correction.

    K-V = correction factor due to viscosity as determined from Figure 32 in API RP520.G = specific gravity of the liquid at the flowing temperature referred to water = 1.0 at 70F.

    P1 = upstream relieving pressure, set pressure plus allowable overpressure (psia).P2 = back-pressure (psia).

  • 5/20/2018 124479095 PSV Calculation Ppt

    48/79

    OIL & GAS

    SIZING CALCULATION

    Two Phase Relief

    For 2-phase relief, the methodology in the newly released API 520Part 1 Appendix D Sizing for Two-Phase Liquid/Vapour Relief shall

    be used (see Appendix 1).

    This method has superseded the previous API methods because, in

    certain circumstances, it has been found that the previous APImethods for 2-phase flow can undersize PSVs significantly.

    This sizing method is based on the Leung Omega method, which

    assumes thermal and mechanical equilibrium; these assumptionscorrespond to the Homogeneous Equilibrium Model (HEM).

  • 5/20/2018 124479095 PSV Calculation Ppt

    49/79

    OIL & GAS

    SIZING CALCULATION

    Required relief area is calculated from relief rate. Hence

    relief rate calculation is very important step

    The case which giving the maximum relief area will be a

    governing case.

    Choose the worst case scenario to be a governing case

    Determine required relief area for each case (Gas, Liquid, 2-Phases)

  • 5/20/2018 124479095 PSV Calculation Ppt

    50/79

    OIL & GAS

    SIZING CALCULATION

    Selected standard relief area follows API RP526 or

    GPSA chapter 5 Figure 5-7

    Valve body size ( Inlet diameter x Outlet diameter) follows

    API STD 526 Flanged Steel Pressure Relief Valve 4th Ed June 1995

    Rated flow = (STD relief area) x Relief rate

    (Required relief area)

    Select proper orifice and valve body size based on STD

  • 5/20/2018 124479095 PSV Calculation Ppt

    51/79

    OIL & GAS

    SIZING CALCULATION

    Calculate inlet line size (Line P < 3%of RP)

    Inlet line sizing is based on pressure drop less than 3 % of

    relieving pressure

    Inlet Line design Consideration

    Inlet line size must be at least equal to PSV inlet flange size.

    Inlet piping should slope continuously upward from vessel

    to avoid traps.

    Inlet piping should be heat traced if freezing or congealing

    of viscous liquids could occur.

  • 5/20/2018 124479095 PSV Calculation Ppt

    52/79

    OIL & GAS

    SIZING CALCULATION

    Inlet Line design Consideration

    A continual clean purge should be provided if coke/polymer

    formation or solids deposition could occur

    CSO valves should have the stem horizontal or vertically

    downward

  • 5/20/2018 124479095 PSV Calculation Ppt

    53/79

    OIL & GAS

    SIZING CALCULATION

    Perform preliminary estimate of tail pipe

    Discharge line sizing is based on Mach No. less than 0.75

    Tail Pipe Design Consideration

    Discharge line diameter must be at least equal to PSV outletflange size.

    Atmospheric risers should discharge at least 10 ft above

    platforms within 50 ft horizontally

    Radiant heat due to ignition of release should be considered.

  • 5/20/2018 124479095 PSV Calculation Ppt

    54/79

    OIL & GAS

    SIZING CALCULATION

    Tail Pipe Design Consideration

    No check valves, orifice plates or other restrictions

    permitted.

    Atmospheric discharge risers should have drain hole.

    CSO valves should have the stem oriented horizontally or

    vertically.

    Piping design must consider thermal expansion due to

    hot/cold release.

    Autorefrigeration and need for brittle fracture resistant

    materials.

  • 5/20/2018 124479095 PSV Calculation Ppt

    55/79

    OIL & GAS

    SIZING CALCULATION

    Tail Pipe Design Consideration

    Closed discharge piping should slope continuously downward

    to header to avoid liquid traps

  • 5/20/2018 124479095 PSV Calculation Ppt

    56/79

    OIL & GAS

    SIZING CALCULATION

  • 5/20/2018 124479095 PSV Calculation Ppt

    57/79

    OIL & GAS

    SIZING CALCULATION

    Perform Flare system modeling to indicate total back pressure and most

    suitable tail pipe size.

  • 5/20/2018 124479095 PSV Calculation Ppt

    58/79

    OIL & GAS

    SIZING CALCULATION

    Select PSV type (Conventional, Balanced Bellow, Pilot Operated

    Type

    Value(% if set)

    Conventional

    Balanced Bellow

    Pilot Operated

    Effects on Valves : Gas applications

    Back Pressure

    Constant

    VariableSuperimposed

    VariableBuilt-up

    < 30%

    30-50%

    >50%

    No effect

    Lift/Capacity reducedNo effect

    Set point increasedby back pressure

    Set point increasedby back pressure

    Flow become sonic

    Generally unstableDo not use

    Flow becomesubsonic

    Set point varieswith back pressure

    10-30%

    < 10%

    No effect

    > 50%

    30-50%

    UnstableDo not use

    Lift/Capacity reduced

    Generally unstableDo not use

    No effect

    Flow becomesubsonic

    < 10%

    UnstableDo not use

    Lift/Capacity reduced

    No effect

    No effect

    No effect

    Generally unstableDo not use

    10-30%

    > 50%

    Flow becomesubsonic

  • 5/20/2018 124479095 PSV Calculation Ppt

    59/79

    OIL & GAS

    SIZING CALCULATION

    Select PSV type (Conventional, Balanced Bellow, Pilot Operated

    Type

    Value(% if set)

    Conventional

    Balanced Bellow

    Pilot Operated

    Effects on Valves : Liquid applications

    Back Pressure

    Constant

    VariableSuperimposed

    VariableBuilt-up

    < 20%

    20-50%

    >50%

    No effect

    Lift/Capacity reduced

    No effect

    Set point increasedby back pressure

    Set point increasedby back pressure

    Flow become sonic

    Generally unstableDo not use

    Set point varieswith back pressure

    10-20%

    < 10%

    No effect

    > 50%

    20-50%

    UnstableDo not use

    Lift/Capacity reduced

    Generally unstableDo not use

    No effect

    < 10%

    UnstableDo not use

    Lift/Capacity reduced

    No effect

    No effect

    No effect

    Generally unstableDo not use

    10-20%

    > 50%

  • 5/20/2018 124479095 PSV Calculation Ppt

    60/79

    OIL & GAS

    EXAMPLE

    DP = 400 psig

    PAH = 350 psig

    OP = 275 psig

    OT = 80 oF

    DP = 250 psig

    OT = 130 oF

    CV= 433

    SP = 250 psig

    SP = 400 psig

    CV= 433FC

    FC

    V-1

    V-2

    F-1

    F-2

    Process SchematicPSV-1

    PSV-2

  • 5/20/2018 124479095 PSV Calculation Ppt

    61/79

    OIL & GAS

    EXAMPLE

    Assess Relief Scenarios

    Scenario Source ofOverpressure

    JudementScenario to be

    consideredseparately

    1 Fire Case An external fire could cause the pressure

    in V-6010 to rise to the relief valve setting

    through vaporization of liquids. Equipment

    layout shown no potential that jet firewill happen on located area thus pool firewill be determined as a basis for calculation.

    Yes

    2 Tube Rupture This case is not applicable. No

    3 Inlet controlvalve failure

    CVs are fail to close type therefore this caseis not applicable for sizing PSV.

    No

  • 5/20/2018 124479095 PSV Calculation Ppt

    62/79

    OIL & GAS

    EXAMPLE

    Scenario Source ofOverpressure

    JudementScenario to be

    consideredseparately

    4

    Gas Blow-by Gas blow-by can occur by

    Liquid in a V-1 drop so low that gas

    exits via the liquid outlet nozzle due to level

    control failure. Loss of liquid level will result

    in gas from V-1 passing into V-2 via

    F-1 and/or F-2.

    Gas blow-by is based on follow assumption

    Control valve upstream fails 100 % open

    The upstream pressure is at the high

    pressure alarm. The downstream pressure is 110 % of the

    set point of the relief valve on the

    downstream vessel.

    No possibility that the bypass valve around

    the control valve is opened.

    Yes

    Assess Relief Scenarios

  • 5/20/2018 124479095 PSV Calculation Ppt

    63/79

    OIL & GAS

    EXAMPLE

    Scenario Source ofOverpressure

    JudementScenario to be

    consideredseparately

    5

    Blocked Outlet 1. Water Blocked Discharge.

    This scenario will relates to two trips; first

    LIAHH and secondly LAHH. Credit can be

    taken that either of these two will actuate.It is unreasonable to assume both will fail to

    response. Hence, this scenario cuts off the

    feed to vessel and no relief is needed.

    2. Oil Blocked Discharge.

    This scenario relates to only oil trip, while

    interface level is already healthy. No credit

    can be taken that this trip will work. Hence

    PSV needs oil relief.

    Yes

    Assess Relief Scenarios

    6 Thermal Relief This case is not applicable. No

  • 5/20/2018 124479095 PSV Calculation Ppt

    64/79

    OIL & GAS

    EXAMPLE

    Possible Relief Scenarios

    There are three different possible relief scenarios :

    Fire Case.

    Gas Blow-by Case.Blocked Outlet Case.

  • 5/20/2018 124479095 PSV Calculation Ppt

    65/79

    OIL & GAS

    EXAMPLE

    Fire Case

    Scenario

    An external fire could cause the pressure in V-2 to rise to the relief valve

    setting through vaporization of liquids. Equipment layout shown no potential

    that jet fire will happen on located area thus pool fire will be determinedas a basis for calculation.

    Relief Condition

    PSV-2 set pressure = 250 psig

    Allowable Accumulation = 21%

    Maximum allowable accumulated pressure = 250x1.21 = 302.5 psig.Relieving temperature = ????

  • 5/20/2018 124479095 PSV Calculation Ppt

    66/79

    OIL & GAS

    EXAMPLE

    Fire Case

    250 psig@61 min ,relief temperature = 191.5 oF

    Since relief can beinitiated after 61 min

    fired but API RP 520

    allow 15 min to handle

    fire hence

    this case will rarely

    happen in real operation.

  • 5/20/2018 124479095 PSV Calculation Ppt

    67/79

    OIL & GAS

    EXAMPLE

    Fire Case

    By input all required parameters (eg. Vessel dimensions, fluid relieving

    properties), in to calculation sheet (WS-CA-PR-025, Rev 0)

    Required relief area = 0.183 in2

    Relief Load = 4,066 lb/hr

    Therefore

    Select 1xEx2 orifice with discharge area of 0.196 in2

  • 5/20/2018 124479095 PSV Calculation Ppt

    68/79

    OIL & GAS

    EXAMPLE

    Gas Blow-by

    Scenario

    Liquid in a V-1 drop so low that gas exits via the liquid outlet nozzle due to

    level control failure. Loss of liquid level will result

    in gas from V-1 passing into V-2 via F-1 and/or F-2.

    Gas blow-by is based on follow assumption

    Control valve upstream fails 100 % open.

    The upstream pressure is at the high pressure alarm.

    The downstream pressure is 110 % of the set point of the relief valve on the

    downstream vessel.

    No possibility that the bypass valve around the control valve is openedas locked close.

    (Note : This may need to be considered in some cases).

    Relief Condition

    PSV-2 set pressure = 250 psig

    Allowable Accumulation = 10%

    Maximum allowable accumulated pressure = 250x1.1 = 275 psig.

  • 5/20/2018 124479095 PSV Calculation Ppt

    69/79

    OIL & GAS

    EXAMPLE

    Gas Blow-by

    Assume

    F-1 and F-2 are same maximum Cv of 433.

    C1 assumed 26.5 (C1 is normally obtained from valve vendor)

    Assume only one control valve is fail.

    Therefore Cg = C1 x Cv = 433 x 26.5 = 11,474.5V-1 hold pressure at PAH = 350 psig

    V-2 operating pressure = 275 psig ( 250 psig x 1.1 = 275 psig)

    Differential pressure = 350-275 = 75 psi

    Reliving temperature = 80 deg F

    How to find the maximum relief rate via F-1 and/or F-2 ?????

  • 5/20/2018 124479095 PSV Calculation Ppt

    70/79

    OIL & GAS

    EXAMPLE

    Gas Blow-by

    Maximum relief rate = 245,703.5 lb/hr

    Maximum relief rate

    can be evaluated from

    control valve sizing

    Programs (eg. Fisher,

    Masoneilan etc.) or sizing

    equations eg.in GPSA.

  • 5/20/2018 124479095 PSV Calculation Ppt

    71/79

    OIL & GAS

    EXAMPLE

    Gas Blow-by

    By input all required parameters (eg. fluid relieving

    properties), in to calculation sheet (WS-CA-PR-025, Rev 0) for generally

    vapor relief.

    Required relief area = 11.57 in2Relief Load = 245,703.5 lb/hr

    Therefore

    Select 6xRx8 orifice with discharge area of 16 in2

  • 5/20/2018 124479095 PSV Calculation Ppt

    72/79

    OIL & GAS

    EXAMPLE

    Blocked Outlet

    1. Water Blocked Discharge.

    This scenario will relates to two trips; first LIAHH and secondly LAHH.

    Credit can be taken that either of these two will actuate. It is unreasonable

    to assume both will fail to response. Hence, this scenario cuts off the feed to

    vessel and no relief is needed.

    2. Oil Blocked Discharge.

    This scenario relates to only oil trip, while interface level is already healthy.No credit can be taken that this trip will work. Hence PSV needs oil relief.

    Relief condition

    PSV-2 set pressure = 250 psig

    Allowable Accumulation = 10%Maximum allowable accumulated pressure = 250x1.1 = 275 psig.Relieving temperature = 130 oF

  • 5/20/2018 124479095 PSV Calculation Ppt

    73/79

    OIL & GAS

    EXAMPLE

    Blocked Outlet

    From simulation

    Oil flow rate = 508,100 lb/hr (25,000 bpd)

    Oil density = 55.21 lb/ft3

    By input all required parameters (eg. fluid relieving properties), in to

    calculation sheet (WS-CA-PR-025, Rev 0) for generally liquid relief.

    Required relief area = 2.76 in2

    Therefore select a 3xLx4 orifice with discharge area of 2.853 in2

  • 5/20/2018 124479095 PSV Calculation Ppt

    74/79

    OIL & GAS

    EXAMPLE

    Relief Case

    Design Orifice Size

    Relief Phase

    Fire Case 1xEx2 Vapor

    Gas Blow-by 6xRx8 Vapor

    Blocked Outlet 3xLx4 Liquid

    Selection of Governing Relief Scenarios

  • 5/20/2018 124479095 PSV Calculation Ppt

    75/79

    OIL & GAS

    EXAMPLE

    Therefore the governing case is Gas Blow-by case

    Required relief rate = 287,530 lb/hr

    Required relief area = 11.57 in2

    Selected relief area = 16 in2

    Rated flow = 16 x 287,530 lb/hr = 397,621 lb/hr

    11.57

    Selection of Governing Relief Scenarios

  • 5/20/2018 124479095 PSV Calculation Ppt

    76/79

    OIL & GAS

    EXAMPLE

    Inlet line sizing calculation

    Inlet line sizing calculation is based on pressure drop less

    than 3 % of set pressure

    PSV set pressure = 250 psig

    Allowable pressure drop = 0.03x250 = 7.5 psi

    Mass rated flow = 397,621 lb/hr

    Based on maximum rated flow and its relief properties

    For 8 inlet line, single phase pressure drop is 5.3 psi therefore

    suitable for inlet line sizing criteria.

  • 5/20/2018 124479095 PSV Calculation Ppt

    77/79

    OIL & GAS

    EXAMPLE

    Outlet line sizing calculation

    Outlet line sizing calculation is based on the maximum Mach No. of 0.75

    From preliminary estimation 12 line give Mach No. of 0.71 hence suitable

    for outlet line sizing criteria.

    Result from FlareNet modeling show 10 give Mach No. of 0.45 ?????

    EXAMPLE

  • 5/20/2018 124479095 PSV Calculation Ppt

    78/79

    OIL & GAS

    Selection of Relief Valve Type

    Result from FlareNet simulation give total back pressure of 70 psig

    PSV set pressure = 250 psig

    PSV type

    Conventional

    Balanced Bellow

    Pilot Operated

    % of Maximum Back

    Pressure Allowable

    10% of SP

    30% of SP

    N/A

    Maximum Back

    Pressure Allowable(psig)

    25 psig

    75 psig

    N/A

    EXAMPLE

  • 5/20/2018 124479095 PSV Calculation Ppt

    79/79

    Summary

    6xRx8 Balanced Bellow PSV

    Inlet line size is 8

    Outlet line size is 10

    108x10

    8x6

    8

    Gas Blow-by

    Set@250 psigBalanced Bellow


Recommended