Date post: | 09-Oct-2015 |
Category: |
Documents |
Upload: | raghavan0189 |
View: | 331 times |
Download: | 51 times |
5/20/2018 124479095 PSV Calculation Ppt
1/79
OIL & GAS
WorleyParsons
OIL&GAS
PSV Sizing Calculation
23-June-05
5/20/2018 124479095 PSV Calculation Ppt
2/79
OIL & GAS
CONTENT
INTRODUCTION
PSV TYPES
CHATTERING PROBLEM
SIZING CALCULATION
EXAMPLE
5/20/2018 124479095 PSV Calculation Ppt
3/79
OIL & GAS
INTRODUCTION
Relief systems are provided on a platform in order toensure the safe operation of the facilities.
In accordance with API RP 14C, all hydrocarbons handling
equipment and pressure vessels will be provided with two
levels of over protection, high pressure trip (PSHH) withshutdown action, and protection by mechanical devices,
Pressure Safety Valve (PSV) or Rupture Disc.
PSVs are installed at every point identified as potentially
hazardous, that is, at points where upset conditions
create pressure which may exceed the maximum
allowable working pressure.
5/20/2018 124479095 PSV Calculation Ppt
4/79
OIL & GAS
INTRODUCTION
How High Pressure Develop
Over heating
High head ( from pumping or compression)
Over Filling
Failure of Regulator / Control valve.External Fire
Runaway Reaction
Combustion of gas/dust
Freezing
Thermal Expansion
Loss of Mixing
Others
5/20/2018 124479095 PSV Calculation Ppt
5/79
OIL & GAS
INTRODUCTION
Definitions
Operating pressure: The gauge pressure during normal
service.
Set Pressure: The pressure at which the relief device
begins to activate or open.
Maximum Allowable Working Pressure (MAWP): The
maximum guage pressure permissible at the top of a vessel
for a designated temperature.
Vessel fails at 4 to 5 times of MAWP!!!! . But onlyhydrostatically tested to 1.5 times.
Accumulation: The pressure increase over the maximum
allowable working pressure of a vessel during the relief
process. Expressed as % of MAWP.
5/20/2018 124479095 PSV Calculation Ppt
6/79
OIL & GAS
INTRODUCTION
Set Pressure
Relief begin to open
Accumulation
Pressure
Time
5/20/2018 124479095 PSV Calculation Ppt
7/79
OIL & GAS
Definitions
Over Pressure: The pressure increase in vessel over the set
pressure during the relieving process. Overpressure is
equivalent to the accumulation when the set pressure is at the
MAWP. Expressed as % of set pressure. Must be specified prior
relief design. Typically 10 % ( or for fire 21%) will be used.
Pressure
Time
Relief begin to open
Set Pressure
Over Pressure
INTRODUCTION
5/20/2018 124479095 PSV Calculation Ppt
8/79
OIL & GAS
Definitions
Blow-down: The pressure difference between the relief
set pressure and the relief reseating pressure.
Maximum Allowable Accumulated Pressure: The sum of
the maximum allowable working pressure plus the allowable
accumulation.
INTRODUCTION
5/20/2018 124479095 PSV Calculation Ppt
9/79
OIL & GAS
INTRODUCTION
Guideline for relief pressures
(Adapted from API RP 520 : Sizing, Selection, and Installation of Pressure-RelievingDevices in Refineries., page 3)
5/20/2018 124479095 PSV Calculation Ppt
10/79
OIL & GAS
Definitions
Back Pressure: The pressure at the outlet of the relief
device during the relief process due to pressure in the
discharge system.
1. Superimposed Back Pressure.
2. Built-up Back Pressure.
Total Back Pressure = Superimposed Back Pressure + Built-up Back Pressure
INTRODUCTION
5/20/2018 124479095 PSV Calculation Ppt
11/79
OIL & GAS
INTRODUCTION
Definitions
1. Superimposed Back Pressure is the back pressure which
may exist at the outlet of a particular relief valve when connected
to a closed system. The pressure can be constant or variable. The
Superimposed back pressure always exists even when the relief
valve is closed.
2. Built-up Back Pressure is the pressure at the discharge of a
relief device which develops due to the relief flow through the
device when the relief valve opens. The built-up back pressure
depends on the valve itself but also on the design of the relief
piping. It can reach excessive values in the case of vary highset pressures and/or poorly designed piping with too much pressure
Loss. The built-up back pressure is variable.
5/20/2018 124479095 PSV Calculation Ppt
12/79
OIL & GAS
PSV TYPES
General Design of PSV
1. Direct acting type
Oldest and most common.
Kept closed by a spring or weight to oppose
lifting force of process pressure.
2. Balanced Bellows.
3. Pilot operated type
Kept closed by process pressure
4. Modulating Pilot.
5/20/2018 124479095 PSV Calculation Ppt
13/79
OIL & GAS
PSV TYPES
The following types of PSV are generally used.
1. Conventional PSV
2. Balanced Type PSV (Balanced Bellow)
3. Pilot Operated PSV
4. Modulating Pilot Operated PSV5. Thermal PSV
5/20/2018 124479095 PSV Calculation Ppt
14/79
OIL & GAS
PSV TYPES
Conventional PSV
AdvantagesMost reliable type if properly sized
and operated
Versatile -- can be used in many services
Compatible with fouling or dirty service.
Disadvantages
Relieving pressure affected byback pressure
Susceptible to chatter if built-up
back pressure is too high
5/20/2018 124479095 PSV Calculation Ppt
15/79
OIL & GAS
Balanced Bellow PSV
PSV TYPES
AdvantagesRelieving pressure not affected by back
pressure.
Can handle higher built-up back pressure.
Protects spring from corrosion.
Wide range of materials available &
chemical compatibility.
Disadvantages
Bellows susceptible to fatigue/rupture.
May release flammables/toxics to
atmosphere.
High maintenance costs.
5/20/2018 124479095 PSV Calculation Ppt
16/79
OIL & GAS
Pilot Operated PSV
Advantages
Relieving pressure not affected by
backpressure
Can operate at up to 98% of set pressure
Less susceptible to chatter (some models)
Disadvantages
Pilot is susceptible to plugging (thereforenot recommended for fouling service,
eg. Wax).
Limited chemical and high temperature
use by O-ring seals
Vapor condensation and liquid
accumulation above the piston may
cause problems
Potential for back flow
PSV TYPES
5/20/2018 124479095 PSV Calculation Ppt
17/79
OIL & GAS
CHATTERING PROBLEM
Modulating Pilot Operated
There are two main types of pilot control operation
Pop action Main valve fully open at set pressure
Modulating : Main valve opens according to relief demand.
Modulating pilots have additional advantages:
They only open the main valve enough to keep the system at set
pressure which leads to less wasted product being relieved
through the valve.
Less noise generated by the valve when it is required to relieve.
Recommended for Wellhead platform PSV.
5/20/2018 124479095 PSV Calculation Ppt
18/79
OIL & GAS
CHATTERING PROBLEM
Main valve
piston lift
Pressure
Opening
Closing
100 % Lift POP Action
5/20/2018 124479095 PSV Calculation Ppt
19/79
OIL & GAS
CHATTERING PROBLEM
Main valve
piston lift
Pressure
Opening
Closing
100 % LiftModulating
5/20/2018 124479095 PSV Calculation Ppt
20/79
OIL & GAS
Chattering Problem
Chattering is the rapid, alternating opening and closing
of a PSV.
Resulting vibration may cause misalignment, valve seatdamage and, if prolonged, can cause mechanical failure
of valve internals and associated piping.
Chatter may occur in either liquid or vapor services
CHATTERING PROBLEM
5/20/2018 124479095 PSV Calculation Ppt
21/79
OIL & GAS
Cause of Chattering
Excessive inlet pressure drop
Excessive built-up back pressure
Oversized valve
Valve handling widely differing rates
CHATTERING PROBLEM
5/20/2018 124479095 PSV Calculation Ppt
22/79
OIL & GAS
Excessive inlet pressure drop
Normal PSV has definite pop
and reseat pressures.
CHATTERING PROBLEM
Reseat orclose pressure
Pop or opening pressure
Blow-down = Different between pop and reseat pressure
5/20/2018 124479095 PSV Calculation Ppt
23/79
OIL & GAS
CHATTERING PROBLEM
Excessive inlet pressure drop : Solution
If you cant change the
piping
Install smaller PSV
Install different type of
PSV
5/20/2018 124479095 PSV Calculation Ppt
24/79
OIL & GAS
CHATTERING PROBLEM
Excessive Built-up Back Pressure
Excessive outlet pressure will also cause chatter.
Avoid
Long outlet piping runs. Elbows and turns.
Sharp edge reductions.
But if you must
Make outlet piping large!
5/20/2018 124479095 PSV Calculation Ppt
25/79
OIL & GAS
CHATTERING PROBLEM
Improper Valve Size
Oversized valve
Must flow at least 25% of capacity to keep valve open.
Especially bad in larger sizes.
Valve handling widely differing rates
Leads to oversized valve case.
5/20/2018 124479095 PSV Calculation Ppt
26/79
OIL & GAS
SIZING CALCULATION
Step Of Sizing CalculationDevelop Process Safety Diagram (PSD)
Develop relief scenarios by using general possible cause and PSD
Determine required relief area for each cases (Gas, Liquid, 2-Phases)
Choose the worst case scenario to be a governing case
Select proper orifice and valve body size based on STD
Calculate inlet line size (Line P < 3%of RP)
Perform preliminary estimate of tail pipe
Perform Flare system modeling to indicate total back pressureand most suitable tail pipe size.
Select PSV type (Conventional, Balanced Bellow, Pilot Operated
5/20/2018 124479095 PSV Calculation Ppt
27/79
OIL & GAS
SIZING CALCULATION
Develop Process Safety Diagram (PSD)
Process safety diagram is the diagram which show
all installation of all process safety equipments (PSHH,
TSHH, PSV, BDV, Rupture disc, etc.) intend to be used in
evaluation of all possible relieving scenarios in process
facilities. Process safety diagram must be developed beforeperforming any PSV calculation.
5/20/2018 124479095 PSV Calculation Ppt
28/79
OIL & GAS
SIZING CALCULATION
Develop Process Safety Diagram (PSD)
5/20/2018 124479095 PSV Calculation Ppt
29/79
OIL & GAS
SIZING CALCULATION
Develop relief scenarios by using general possible cause and PSD
EquipmentPossible Scenarios
PumpHEX LineVessel /Column
Compressor
Blocked Outlet
Thermal Expansion
Tube Rupture
Gas Blow-by
Inlet Control Valve Failure
Exterior Fire
Note : Exterior Fire is not applicable for PHEX!!
5/20/2018 124479095 PSV Calculation Ppt
30/79
OIL & GAS
SIZING CALCULATION
Blocked Outlet/ Blocked Discharge
CLOSED
CLOSED
CLOSED
CLOSED
CLOSED
Process Vessel
Compressor Pump
This situation arises from the inadvertent closure of a block valve or failure
of a control valve in the closed position on an outlet line. Typical
overpressure application where this form of protection is required includes
production separators, compressor discharge piping or pump discharge
piping. The safety relief valves are sized to handle 100% of the anticipated
upstream flow. If the feed stream(s) is multi-phase, the relief rate is the totalinlet flow (gas plus liquids).
5/20/2018 124479095 PSV Calculation Ppt
31/79
OIL & GAS
SIZING CALCULATION
Thermal Expansion/ Thermal Relief
Heat Exchanger
Line
Hot Side
Cold Side
CLOSED CLOSED CLOSED
Thermal expansion relief valves (TERVs) are required in liquid-full systemsif the system can be blocked in and/or subjected to heat input from theatmosphere or process that results in overpressure.
5/20/2018 124479095 PSV Calculation Ppt
32/79
OIL & GAS
SIZING CALCULATION
Tube Rupture
Heat Exchanger
Hot Side
Cold SideOR
Heat Exchanger
Hot Side
Cold Side
Tube rupture causing vapour to enter either the tubeside or shellside
of a heat exchanger will cause a pressure spike to travel through the
fluid at sonic velocity. Generally, a PSV will not lift fast enough to protect
the system. Protection against tube rupture is typically by the useof bursting discs.
5/20/2018 124479095 PSV Calculation Ppt
33/79
OIL & GAS
SIZING CALCULATION
Suddenly OpeningPressure at PSHH
Liquid at LSLL
Gas blow-by occurs when liquid level in a partially filled vessel drops solow that gas exits via the liquid outlet nozzle due to level control failure.
Loss of liquid level will result in gas from the high pressure vessel passinginto the low pressure system downstream of the liquid level control valve.
Gas Blow-by
5/20/2018 124479095 PSV Calculation Ppt
34/79
OIL & GAS
SIZING CALCULATION
Fail to openPressure at normalLiquid at normal
Inlet Control Valve Failure
The relief rate is equal to the difference between the maximum inlet
flow and the flow, at relief conditions, from the outlet valves that
remain open. No credit for outlet valves response will be taken i.e.
they will be assumed to remain at their normal operating point
(% open).
5/20/2018 124479095 PSV Calculation Ppt
35/79
OIL & GAS
SIZING CALCULATION
Exterior Fire
Generally, the production & processing facilities will be segregated into fire
areas, by means of plated decks, fire walls, or edge of the platform. During
a fire in one of the fire areas, all equipment within that area is assumed to be
fully exposed to the fire.
It is assumed that during a fire there is no feed to or product from an
affected system, and all normal heat inputs have ceased.
No credit will be taken for the presence of any water spray systems.No credit will be taken for thermal insulation on vessels.
5/20/2018 124479095 PSV Calculation Ppt
36/79
OIL & GAS
SIZING CALCULATION
Pool Fire
Jet Fire
Fire Type
Systems with significant liquid
hydrocarbon inventory will be
considered for pool fire case.
Heat flux will be calculated as
per API RP521. Credit for a 40%
reduction in heat flux may be
taken for good drainage and
the presence of prompt fire
fighting efforts as specified inAPI RP 521.
Where potential for jet fire exists, relief
load will be calculated for higher heat flux
from heat fire. The heat flux generated by
jet fire ranges from 50 kW/m2 to 300 kW /m2.
However, the net heat flux into the fluid will
depend on many factors such as fuel type,
vessel temperature, the surface emissivity,
the fire environment, the radiative andconvective components of the fire.
5/20/2018 124479095 PSV Calculation Ppt
37/79
OIL & GAS
SIZING CALCULATION
Vessel Type & Fluid relief type
Vessel type could be :
Dry or empty vessel
Vessels containing liquid -> Need to consider effect ofwetted area of vessel
Fluid relief type could be :
Fluid is sub-critical: P 1.1*Pc
Pc = Critical PressureP = Relieving Pressure
5/20/2018 124479095 PSV Calculation Ppt
38/79
OIL & GAS
SIZING CALCULATION
Fire case
Jet Fire
Dry Vessel Wetted vessel
Sub Critical FlowNear Critical FlowSuper Critical Flow
Pool Fire2 CASES
2 CASES
3 CASES
Totally = 2x2x3 = 12 cases possibleHence 12 methods of calculation for Fire case
5/20/2018 124479095 PSV Calculation Ppt
39/79
OIL & GAS
SIZING CALCULATION
Determine required relief area for each case (Gas, Liquid, 2-Phases)
Target of sizing relief valve
1. Determine the relief rate.
2. Determine the required relief area.
3. Select the standard relief area.
Code and standard required
API RP 520 : Sizing, Selection, and Installation of Pressure-Relieving
Devices in Refineries.
API RP 521 : Guide for Pressure Relieving and Depressuring Systems.
5/20/2018 124479095 PSV Calculation Ppt
40/79
OIL & GAS
SIZING CALCULATION
Relief Phase
Single Phase Relief
Two Phase Relief
Vapor Phase Relief
Liquid Phase Relief
Relief Type
Continuous Relief
Transient Relief Thermal Relief
Generally
Gas/Vapor
Steam
Relief fluid category
Determine required relief area for each case (Gas, Liquid, 2-Phases)
5/20/2018 124479095 PSV Calculation Ppt
41/79
OIL & GAS
SIZING CALCULATION
Determine relief rate, some cases (eg. Gas blow-by, tube rupture,
fire case etc.) are very complicated and contain many steps of calculation
especially fire case.
API RP520/ 521 shows the simple method of calculation in order todetermine the relief rate. This does not govern all relief scenarios. Hence
some companies have developed their own procedure to determine the
relief rate.
Determine required relief area for each case (Gas, Liquid, 2-Phases)
5/20/2018 124479095 PSV Calculation Ppt
42/79
OIL & GAS
SIZING CALCULATION
Vapor Phase Relief
Relief valves for single phase vapour flow will be sized according
to the methodology presented in API RP 520, Section 3 (reference 4).
The sizing equations fall into 2 categories, depending on whether
flow is critical or subcritical.
The critical pressure must be checked using the equation below:
)1(
1
1
2.
k
k
cf
k
PP
where
Pcf= critical flow throat pressure (psia)
P1= upstream relieving pressure (psia)k= ratio of specific heats
Ref. API 520 section 3.6.1.4
5/20/2018 124479095 PSV Calculation Ppt
43/79
OIL & GAS
SIZING CALCULATION
Vapor Phase Relief
If flow is critical (Pcf > downstream pressure P2), the criticalsizing equation is used:
A W
C K P K
TZ
Md b
1
Ref. API 520 section 3.6.2.1
WhereA = required effective discharge area of the valve ( in2).
W = required flow through the valve (lb/hr).
C = coefficient determined from an expression of the ratio of the specific heats of the gas
or vapour at standard conditions. This can be obtained from Figure 26 or Table 9 in
API 520.
Kd = effective coefficient of discharge = 0.975
P1 = upstream relieving pressure, in psia.Kb = capacity correction factor due to back-pressure. This can be obtained from the
manufacturers literature or estimated from Figure 27 in API 520. The back-pressure
correction factor applies to balanced-bellows valves only.
T = relieving temperature of the inlet gas or vapour, in R.
Z = compressibility factor for the deviation of the actual gas from a perfect gas, a ratio
evaluated at inlet conditions.M = molecular weight of the gas or vapour.
5/20/2018 124479095 PSV Calculation Ppt
44/79
OIL & GAS
SIZING CALCULATION
Vapor Phase Relief
If flow is subcritical, the following equation will be used:
)(..735 2112 PPPM
ZT
KF
WA
d Ref. API 520 section 4.3.3.1
Where A = required effective discharge area of the valve, in square inches.
W = required flow through the valve, in pounds per hour.F2 = coefficient of subcritical flow
=
r
rr
k
k kk
k
1
1)(
)1(
12
Ref. API 520 section 4.3.3.1
5/20/2018 124479095 PSV Calculation Ppt
45/79
OIL & GAS
SIZING CALCULATION
k = ratio of the specific heats.
r = ratio of back pressure to upstream relieving pressure, P2/P1.
Kd = effective coefficient of discharge = 0.975
Z = compressibility at relieving inlet conditions.
T = relieving temperature of the inlet gas or vapour (R)
M = molecular weight of the gas or vapour.P1& P2 = upstream relieving pressure and back-pressure pressure respectively (psia)
Vapor Phase Relief
5/20/2018 124479095 PSV Calculation Ppt
46/79
OIL & GAS
SIZING CALCULATION
Vapor Phase Relief
Relief valves in steam servicewill be sized as follows:
A W
P K K Kd N SH
51 5 1.Ref API 520 Section 3.7.1
Where
A = required effective discharge area of the valve ( in2).
W = required flow through the valve (lb/hr).
P1 = upstream relieving pressure (psia)
Kd = effective coefficient of discharge = 0.975
KN = correction factor for Napier equation.= 1 where P11515 psia.
= (0.1906P11000)/(0.2292P11061) where P11515 psia and 3215 psia
KSH = superheat steam correction factor. This can be obtained from Table 9 in API RP520.For saturated steam at any pressure, KSH-= 1.0.
5/20/2018 124479095 PSV Calculation Ppt
47/79
OIL & GAS
SIZING CALCULATION
Liquid Phase Relief
For single phase liquid flow, the sizing method specified for
certified relief valves will be used.
The following equation only applies to non-flashing liquids.
A Q
K K K
G
P Pd w v
38 1 2Ref. API 520 section 4.5.1
Where
A = required effective discharge area of the valve ( in2).
Q = flow rate, in U.S. gallons per minute.
Kd = effective coefficient of discharge that should be obtained from the valve manufacturer.For a preliminary sizing estimation, a discharge coefficient of 0.65 can be used.
Kw = correction factor due to back-pressure. If the back-pressure is atmospheric, KW= 1.
Balanced-bellows valves in back-pressure service will require the correction factor
determined in Figure 31 in API RP520. Conventional valves require no special correction.
K-V = correction factor due to viscosity as determined from Figure 32 in API RP520.G = specific gravity of the liquid at the flowing temperature referred to water = 1.0 at 70F.
P1 = upstream relieving pressure, set pressure plus allowable overpressure (psia).P2 = back-pressure (psia).
5/20/2018 124479095 PSV Calculation Ppt
48/79
OIL & GAS
SIZING CALCULATION
Two Phase Relief
For 2-phase relief, the methodology in the newly released API 520Part 1 Appendix D Sizing for Two-Phase Liquid/Vapour Relief shall
be used (see Appendix 1).
This method has superseded the previous API methods because, in
certain circumstances, it has been found that the previous APImethods for 2-phase flow can undersize PSVs significantly.
This sizing method is based on the Leung Omega method, which
assumes thermal and mechanical equilibrium; these assumptionscorrespond to the Homogeneous Equilibrium Model (HEM).
5/20/2018 124479095 PSV Calculation Ppt
49/79
OIL & GAS
SIZING CALCULATION
Required relief area is calculated from relief rate. Hence
relief rate calculation is very important step
The case which giving the maximum relief area will be a
governing case.
Choose the worst case scenario to be a governing case
Determine required relief area for each case (Gas, Liquid, 2-Phases)
5/20/2018 124479095 PSV Calculation Ppt
50/79
OIL & GAS
SIZING CALCULATION
Selected standard relief area follows API RP526 or
GPSA chapter 5 Figure 5-7
Valve body size ( Inlet diameter x Outlet diameter) follows
API STD 526 Flanged Steel Pressure Relief Valve 4th Ed June 1995
Rated flow = (STD relief area) x Relief rate
(Required relief area)
Select proper orifice and valve body size based on STD
5/20/2018 124479095 PSV Calculation Ppt
51/79
OIL & GAS
SIZING CALCULATION
Calculate inlet line size (Line P < 3%of RP)
Inlet line sizing is based on pressure drop less than 3 % of
relieving pressure
Inlet Line design Consideration
Inlet line size must be at least equal to PSV inlet flange size.
Inlet piping should slope continuously upward from vessel
to avoid traps.
Inlet piping should be heat traced if freezing or congealing
of viscous liquids could occur.
5/20/2018 124479095 PSV Calculation Ppt
52/79
OIL & GAS
SIZING CALCULATION
Inlet Line design Consideration
A continual clean purge should be provided if coke/polymer
formation or solids deposition could occur
CSO valves should have the stem horizontal or vertically
downward
5/20/2018 124479095 PSV Calculation Ppt
53/79
OIL & GAS
SIZING CALCULATION
Perform preliminary estimate of tail pipe
Discharge line sizing is based on Mach No. less than 0.75
Tail Pipe Design Consideration
Discharge line diameter must be at least equal to PSV outletflange size.
Atmospheric risers should discharge at least 10 ft above
platforms within 50 ft horizontally
Radiant heat due to ignition of release should be considered.
5/20/2018 124479095 PSV Calculation Ppt
54/79
OIL & GAS
SIZING CALCULATION
Tail Pipe Design Consideration
No check valves, orifice plates or other restrictions
permitted.
Atmospheric discharge risers should have drain hole.
CSO valves should have the stem oriented horizontally or
vertically.
Piping design must consider thermal expansion due to
hot/cold release.
Autorefrigeration and need for brittle fracture resistant
materials.
5/20/2018 124479095 PSV Calculation Ppt
55/79
OIL & GAS
SIZING CALCULATION
Tail Pipe Design Consideration
Closed discharge piping should slope continuously downward
to header to avoid liquid traps
5/20/2018 124479095 PSV Calculation Ppt
56/79
OIL & GAS
SIZING CALCULATION
5/20/2018 124479095 PSV Calculation Ppt
57/79
OIL & GAS
SIZING CALCULATION
Perform Flare system modeling to indicate total back pressure and most
suitable tail pipe size.
5/20/2018 124479095 PSV Calculation Ppt
58/79
OIL & GAS
SIZING CALCULATION
Select PSV type (Conventional, Balanced Bellow, Pilot Operated
Type
Value(% if set)
Conventional
Balanced Bellow
Pilot Operated
Effects on Valves : Gas applications
Back Pressure
Constant
VariableSuperimposed
VariableBuilt-up
< 30%
30-50%
>50%
No effect
Lift/Capacity reducedNo effect
Set point increasedby back pressure
Set point increasedby back pressure
Flow become sonic
Generally unstableDo not use
Flow becomesubsonic
Set point varieswith back pressure
10-30%
< 10%
No effect
> 50%
30-50%
UnstableDo not use
Lift/Capacity reduced
Generally unstableDo not use
No effect
Flow becomesubsonic
< 10%
UnstableDo not use
Lift/Capacity reduced
No effect
No effect
No effect
Generally unstableDo not use
10-30%
> 50%
Flow becomesubsonic
5/20/2018 124479095 PSV Calculation Ppt
59/79
OIL & GAS
SIZING CALCULATION
Select PSV type (Conventional, Balanced Bellow, Pilot Operated
Type
Value(% if set)
Conventional
Balanced Bellow
Pilot Operated
Effects on Valves : Liquid applications
Back Pressure
Constant
VariableSuperimposed
VariableBuilt-up
< 20%
20-50%
>50%
No effect
Lift/Capacity reduced
No effect
Set point increasedby back pressure
Set point increasedby back pressure
Flow become sonic
Generally unstableDo not use
Set point varieswith back pressure
10-20%
< 10%
No effect
> 50%
20-50%
UnstableDo not use
Lift/Capacity reduced
Generally unstableDo not use
No effect
< 10%
UnstableDo not use
Lift/Capacity reduced
No effect
No effect
No effect
Generally unstableDo not use
10-20%
> 50%
5/20/2018 124479095 PSV Calculation Ppt
60/79
OIL & GAS
EXAMPLE
DP = 400 psig
PAH = 350 psig
OP = 275 psig
OT = 80 oF
DP = 250 psig
OT = 130 oF
CV= 433
SP = 250 psig
SP = 400 psig
CV= 433FC
FC
V-1
V-2
F-1
F-2
Process SchematicPSV-1
PSV-2
5/20/2018 124479095 PSV Calculation Ppt
61/79
OIL & GAS
EXAMPLE
Assess Relief Scenarios
Scenario Source ofOverpressure
JudementScenario to be
consideredseparately
1 Fire Case An external fire could cause the pressure
in V-6010 to rise to the relief valve setting
through vaporization of liquids. Equipment
layout shown no potential that jet firewill happen on located area thus pool firewill be determined as a basis for calculation.
Yes
2 Tube Rupture This case is not applicable. No
3 Inlet controlvalve failure
CVs are fail to close type therefore this caseis not applicable for sizing PSV.
No
5/20/2018 124479095 PSV Calculation Ppt
62/79
OIL & GAS
EXAMPLE
Scenario Source ofOverpressure
JudementScenario to be
consideredseparately
4
Gas Blow-by Gas blow-by can occur by
Liquid in a V-1 drop so low that gas
exits via the liquid outlet nozzle due to level
control failure. Loss of liquid level will result
in gas from V-1 passing into V-2 via
F-1 and/or F-2.
Gas blow-by is based on follow assumption
Control valve upstream fails 100 % open
The upstream pressure is at the high
pressure alarm. The downstream pressure is 110 % of the
set point of the relief valve on the
downstream vessel.
No possibility that the bypass valve around
the control valve is opened.
Yes
Assess Relief Scenarios
5/20/2018 124479095 PSV Calculation Ppt
63/79
OIL & GAS
EXAMPLE
Scenario Source ofOverpressure
JudementScenario to be
consideredseparately
5
Blocked Outlet 1. Water Blocked Discharge.
This scenario will relates to two trips; first
LIAHH and secondly LAHH. Credit can be
taken that either of these two will actuate.It is unreasonable to assume both will fail to
response. Hence, this scenario cuts off the
feed to vessel and no relief is needed.
2. Oil Blocked Discharge.
This scenario relates to only oil trip, while
interface level is already healthy. No credit
can be taken that this trip will work. Hence
PSV needs oil relief.
Yes
Assess Relief Scenarios
6 Thermal Relief This case is not applicable. No
5/20/2018 124479095 PSV Calculation Ppt
64/79
OIL & GAS
EXAMPLE
Possible Relief Scenarios
There are three different possible relief scenarios :
Fire Case.
Gas Blow-by Case.Blocked Outlet Case.
5/20/2018 124479095 PSV Calculation Ppt
65/79
OIL & GAS
EXAMPLE
Fire Case
Scenario
An external fire could cause the pressure in V-2 to rise to the relief valve
setting through vaporization of liquids. Equipment layout shown no potential
that jet fire will happen on located area thus pool fire will be determinedas a basis for calculation.
Relief Condition
PSV-2 set pressure = 250 psig
Allowable Accumulation = 21%
Maximum allowable accumulated pressure = 250x1.21 = 302.5 psig.Relieving temperature = ????
5/20/2018 124479095 PSV Calculation Ppt
66/79
OIL & GAS
EXAMPLE
Fire Case
250 psig@61 min ,relief temperature = 191.5 oF
Since relief can beinitiated after 61 min
fired but API RP 520
allow 15 min to handle
fire hence
this case will rarely
happen in real operation.
5/20/2018 124479095 PSV Calculation Ppt
67/79
OIL & GAS
EXAMPLE
Fire Case
By input all required parameters (eg. Vessel dimensions, fluid relieving
properties), in to calculation sheet (WS-CA-PR-025, Rev 0)
Required relief area = 0.183 in2
Relief Load = 4,066 lb/hr
Therefore
Select 1xEx2 orifice with discharge area of 0.196 in2
5/20/2018 124479095 PSV Calculation Ppt
68/79
OIL & GAS
EXAMPLE
Gas Blow-by
Scenario
Liquid in a V-1 drop so low that gas exits via the liquid outlet nozzle due to
level control failure. Loss of liquid level will result
in gas from V-1 passing into V-2 via F-1 and/or F-2.
Gas blow-by is based on follow assumption
Control valve upstream fails 100 % open.
The upstream pressure is at the high pressure alarm.
The downstream pressure is 110 % of the set point of the relief valve on the
downstream vessel.
No possibility that the bypass valve around the control valve is openedas locked close.
(Note : This may need to be considered in some cases).
Relief Condition
PSV-2 set pressure = 250 psig
Allowable Accumulation = 10%
Maximum allowable accumulated pressure = 250x1.1 = 275 psig.
5/20/2018 124479095 PSV Calculation Ppt
69/79
OIL & GAS
EXAMPLE
Gas Blow-by
Assume
F-1 and F-2 are same maximum Cv of 433.
C1 assumed 26.5 (C1 is normally obtained from valve vendor)
Assume only one control valve is fail.
Therefore Cg = C1 x Cv = 433 x 26.5 = 11,474.5V-1 hold pressure at PAH = 350 psig
V-2 operating pressure = 275 psig ( 250 psig x 1.1 = 275 psig)
Differential pressure = 350-275 = 75 psi
Reliving temperature = 80 deg F
How to find the maximum relief rate via F-1 and/or F-2 ?????
5/20/2018 124479095 PSV Calculation Ppt
70/79
OIL & GAS
EXAMPLE
Gas Blow-by
Maximum relief rate = 245,703.5 lb/hr
Maximum relief rate
can be evaluated from
control valve sizing
Programs (eg. Fisher,
Masoneilan etc.) or sizing
equations eg.in GPSA.
5/20/2018 124479095 PSV Calculation Ppt
71/79
OIL & GAS
EXAMPLE
Gas Blow-by
By input all required parameters (eg. fluid relieving
properties), in to calculation sheet (WS-CA-PR-025, Rev 0) for generally
vapor relief.
Required relief area = 11.57 in2Relief Load = 245,703.5 lb/hr
Therefore
Select 6xRx8 orifice with discharge area of 16 in2
5/20/2018 124479095 PSV Calculation Ppt
72/79
OIL & GAS
EXAMPLE
Blocked Outlet
1. Water Blocked Discharge.
This scenario will relates to two trips; first LIAHH and secondly LAHH.
Credit can be taken that either of these two will actuate. It is unreasonable
to assume both will fail to response. Hence, this scenario cuts off the feed to
vessel and no relief is needed.
2. Oil Blocked Discharge.
This scenario relates to only oil trip, while interface level is already healthy.No credit can be taken that this trip will work. Hence PSV needs oil relief.
Relief condition
PSV-2 set pressure = 250 psig
Allowable Accumulation = 10%Maximum allowable accumulated pressure = 250x1.1 = 275 psig.Relieving temperature = 130 oF
5/20/2018 124479095 PSV Calculation Ppt
73/79
OIL & GAS
EXAMPLE
Blocked Outlet
From simulation
Oil flow rate = 508,100 lb/hr (25,000 bpd)
Oil density = 55.21 lb/ft3
By input all required parameters (eg. fluid relieving properties), in to
calculation sheet (WS-CA-PR-025, Rev 0) for generally liquid relief.
Required relief area = 2.76 in2
Therefore select a 3xLx4 orifice with discharge area of 2.853 in2
5/20/2018 124479095 PSV Calculation Ppt
74/79
OIL & GAS
EXAMPLE
Relief Case
Design Orifice Size
Relief Phase
Fire Case 1xEx2 Vapor
Gas Blow-by 6xRx8 Vapor
Blocked Outlet 3xLx4 Liquid
Selection of Governing Relief Scenarios
5/20/2018 124479095 PSV Calculation Ppt
75/79
OIL & GAS
EXAMPLE
Therefore the governing case is Gas Blow-by case
Required relief rate = 287,530 lb/hr
Required relief area = 11.57 in2
Selected relief area = 16 in2
Rated flow = 16 x 287,530 lb/hr = 397,621 lb/hr
11.57
Selection of Governing Relief Scenarios
5/20/2018 124479095 PSV Calculation Ppt
76/79
OIL & GAS
EXAMPLE
Inlet line sizing calculation
Inlet line sizing calculation is based on pressure drop less
than 3 % of set pressure
PSV set pressure = 250 psig
Allowable pressure drop = 0.03x250 = 7.5 psi
Mass rated flow = 397,621 lb/hr
Based on maximum rated flow and its relief properties
For 8 inlet line, single phase pressure drop is 5.3 psi therefore
suitable for inlet line sizing criteria.
5/20/2018 124479095 PSV Calculation Ppt
77/79
OIL & GAS
EXAMPLE
Outlet line sizing calculation
Outlet line sizing calculation is based on the maximum Mach No. of 0.75
From preliminary estimation 12 line give Mach No. of 0.71 hence suitable
for outlet line sizing criteria.
Result from FlareNet modeling show 10 give Mach No. of 0.45 ?????
EXAMPLE
5/20/2018 124479095 PSV Calculation Ppt
78/79
OIL & GAS
Selection of Relief Valve Type
Result from FlareNet simulation give total back pressure of 70 psig
PSV set pressure = 250 psig
PSV type
Conventional
Balanced Bellow
Pilot Operated
% of Maximum Back
Pressure Allowable
10% of SP
30% of SP
N/A
Maximum Back
Pressure Allowable(psig)
25 psig
75 psig
N/A
EXAMPLE
5/20/2018 124479095 PSV Calculation Ppt
79/79
Summary
6xRx8 Balanced Bellow PSV
Inlet line size is 8
Outlet line size is 10
108x10
8x6
8
Gas Blow-by
Set@250 psigBalanced Bellow