344 125 mm ø EC centrifugal in-line fans Acoustic Line SilentBox ® SB and SlimVent SVS 400 367 246 135 124 125 266* 460* 438* 144* 136* Virtually noise-free with high air flow volumes against high resistances. Ideal for maintenance and cleaning. SilentBox ® SB EC Dim. in mm SB EC 125 A, * SB EC 125 B Similarities SilentBox ® SB EC and SlimVent SVS EC Installation Installation in any position with- out restriction – horizontally, ver- tically or pitched – suitable for intake or extract. Mounting bracket included in delivery. Motor Energy saving, speed control- lable EC-external rotor motors with highest efficiency, protection to IP 44 (SB EC 125 A IP 54). With ball bearings, maintenance- free and interference-free. Dynamically balanced for low noise operation. Speed control Stepless speed control with po- tentiometer or stepless speed control with universal control system (see table). Duties at different speeds are exemplarily given in the performance curve. Motor protection Integrated electronic tempera- ture monitoring for EC-motor and electronics. Sound levels See page 351. Specification SilentBox ® EC Casing Like an internal attenuator. Acoustically lined with abrasive resistant 50 mm thick mineral fibreboard. Four quick release clamps permit easy access to the impeller set. Motor-impeller unit can be pulled out, the pull- out range must be considered. Spigots on intake and exhaust twin-seal rubber gaskets fit standard ducts. All parts manu- factured from galvanised sheet steel. Impeller With backward curved impeller. Inflow via inlet cone. SB EC 125 A forward curved impeller in aerodynamically opti- mised volute casing, galvanised sheet steel. Electrical connection Terminal box (IP 54) mounted on running cable. Protection class With a connected pipe system IP 44 (SB EC 125 A IP 54). Specification SlimVent SVS EC Casing Extremely flat casing in longer design with more than 50 mm thick sound-absorbing mineral wool lining and glass fibre sur- face. The acoustic box which is placed in front of the fan reduces the sound level for the intake significantly. The sound level of the case breakout is reduced to a smaller extent (see sound lev- els in the tables above the per- formance curves). The swing out motor and im- peller unit permits maintenance and cleaning without disassem- bly of system components. The swing-out range of the motor- impeller unit must be consid- ered. Impeller Energy-saving centrifugal im- peller with backward curved blades from high quality poly- mer. Electrical connection Terminal box (IP 54) mounted on running cable. Protection class With a connected pipe system IP 44. SlimVent SVS EC 213 314 73 190 330 48 ø 125 310 Ultra low profile. Ideal for applications with limited installation space. With sound-insulating mineral wool lining for particularly noise-free operation. Dim. in mm SB EC 125 B 9624 125 600 3680 45 979 12.0 0.12 0.93 60 EUR EC 1) 2) 1347 PU 10 1) 1734 Type Ref. no. Connection Ø Air flow volume (FID) R.P.M. Sound press. case breakout Wiring diagram Weight net approx. mm . V m 3 /h min -1 dB(A) in 1 m No. kg Motor power kW Current A max. air flow temperature + °C Universal control system Speed-potentiometer flush surface Type Ref. no. Type Ref. no. PA 10 1) 1735 SB EC 125 A 6132 125 530 2790 43 979 10.0 0.12 1.00 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735 SVS EC 125 0016 125 590 3670 54 979 5.8 0.12 0.93 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735 Type Ref. no. Type SilentBox ® SB EC, 1 ph. motor, 230 V, 50/60 Hz, EC motor, IP 54 (A), IP 44 (B) Type SVS EC, 1 ph. motor, 230 V, 50/60 Hz, EC motor, IP 44 1) Several EC fans can normally be connected. 2) alternative electronic differential pressure/temp. controller (EDR/ETR, No. 1437/1438) or three step speed controller (SU/SA, No. 4266/4267), see accessories. Saving * * with speed control
Transcript
Page 1: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

344

125 mm ø EC centrifugal in-line fans Acoustic LineSilentBox® SB and SlimVent SVS

400 367

246

135

124

125

266*

460*438*

144*

136*

Virtually noise-free with high air flow volumes againsthigh resistances. Ideal for maintenance and cleaning.

SilentBox® SB EC

Dim. in mm SB EC 125 A, *SB EC 125 B

� SimilaritiesSilentBox® SB ECand SlimVent SVS EC

� InstallationInstallation in any position with-out restriction – horizontally, ver-tically or pitched – suitable forintake or extract. Mountingbracket included in delivery.

� MotorEnergy saving, speed control-lable EC-external rotor motorswith highest efficiency, protectionto IP 44 (SB EC 125 A IP 54).With ball bearings, maintenance-free and interference-free.Dynamically balanced for lownoise operation.

� Speed controlStepless speed control with po-tentiometer or stepless speedcontrol with universal controlsystem (see table). Duties atdifferent speeds are exemplarilygiven in the performance curve.

� Motor protectionIntegrated electronic tempera-ture monitoring for EC-motorand electronics.

� Sound levelsSee page 351.

� Specification SilentBox® EC� CasingLike an internal attenuator.Acoustically lined with abrasiveresistant 50 mm thick mineralfibreboard. Four quick releaseclamps permit easy access tothe impeller set. Motor-impellerunit can be pulled out, the pull-out range must be considered.Spigots on intake and exhausttwin-seal rubber gaskets fitstandard ducts. All parts manu-factured from galvanised sheetsteel.

� ImpellerWith backward curved impeller.Inflow via inlet cone.SB EC 125 A forward curved

impeller in aerodynamically opti-mised volute casing, galvanisedsheet steel.

� Electrical connectionTerminal box (IP 54) mounted onrunning cable.

� Protection classWith a connected pipe systemIP 44 (SB EC 125 A IP 54).

� Specification SlimVent SVS EC� CasingExtremely flat casing in longerdesign with more than 50 mmthick sound-absorbing mineralwool lining and glass fibre sur-face. The acoustic box which isplaced in front of the fan reducesthe sound level for the intakesignificantly. The sound level ofthe case breakout is reduced toa smaller extent (see sound lev-els in the tables above the per-formance curves).

� The swing out motor and im-peller unit permits maintenance

and cleaning without disassem-bly of system components. Theswing-out range of the motor-impeller unit must be consid-ered.

� ImpellerEnergy-saving centrifugal im-peller with backward curvedblades from high quality poly-mer.

� Electrical connectionTerminal box (IP 54) mounted onrunning cable.

� Protection classWith a connected pipe systemIP 44.

SlimVent SVS EC

213

314

73

190

330

48

ø 125

310

Ultra low profile. Ideal for applications withlimited installation space. With sound-insulatingmineral wool lining for particularly noise-free operation.

Dim. in mm

SB EC 125 B 9624 125 600 3680 45 979 12.00.12 0.93 60 EUR EC 1) 2) 1347 PU 10 1) 1734

Type Ref. no. ConnectionØ

Air flowvolume(FID)

R.P.M. Sound press.case

breakout

Wiringdiagram

Weightnet

approx.

mm.V m3/h min-1 dB(A) in 1m No. kg

Motorpower

kW

Current

A

max. air flowtemperature

+ °C

Universalcontrol system

Speed-potentiometer flush surface

Type Ref. no. Type Ref. no.

PA 10 1) 1735

SB EC 125 A 6132 125 530 2790 43 979 10.00.12 1.00 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

SVS EC 125 0016 125 590 3670 54 979 5.80.12 0.93 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

Type Ref. no.

Type SilentBox® SB EC, 1 ph. motor, 230 V, 50/60 Hz, EC motor, IP 54 (A), IP 44 (B)

Type SVS EC, 1 ph. motor, 230 V, 50/60 Hz, EC motor, IP 44

1) Several EC fans can normally be connected. 2) alternative electronic differential pressure/temp. controller (EDR/ETR, No. 1437/1438) or three step speed controller (SU/SA, No. 4266/4267), see accessories.

Saving ** with speed control

Page 2: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

345

EC centrifugal in-line fans Acoustic Line 125 mm øSilentBox® SB and SlimVent SVS

� Accessories

Flexible sleeveType FM 125 Ref. no. 1682Supplied with two hose clips asstandard; for installation betweenfan and duct system. Preventssound and vibration transmissionto ducting and corrects small site misalignments. For intake or ex-tract two sleeves are needed forcomplete isolation.

Gravity shutterType VK 125 Ref. no. 0857Automatic made from polymer,white.

Fixed grilleType G 160 Ref. no. 0893Made from polymer, white.

GuardType SGR 125 Ref. no. 5064For intake and extract installation.Made from powder-coated steelwire.

Backdraught shutterType RSKK 125 Ref. no. 5107Automatic, made from polymer.

Flexible circular attenuatorType FSD 125 Ref. no. 0677Spigotted aluminium attenuatorwith 50 mm insulation. Length 1 m.

Air filter boxLFBR 125 G4 Ref. no. 8577LFBR 125 F7 Ref. no. 8531Air filter with large surface area, forinstallation in ducting.

Electric heater batteryEHR-R 0,8/125 0,8 kW No. 8709EHR-R 1,2/125 1,2 kW No. 9433– with integrated temp. controlEHR-R 0,8/125 TR 0,8 kW No. 5293Room or duct sensor (TFK/TFR,accessories) required.

Temperature control system for electric heater battery EHR-RType EHS Ref. no. 5002

Warm water heater batteryType WHR 125 Ref. no. 9480Compact heat exchanger for in-line installation.

Temperature control system for warm water heater batteryType WHST 300 T38 No. 8817

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 53 44 47 49 44 37 33 30 LWA Intake dB(A) 61 58 55 53 47 48 44 36 LWA Exhaust dB(A) 81 67 71 77 74 74 69 63

V· m3/h

DpfaPa

r = 1,20 kg/m3

SB EC 125 B

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 3720 600 115 0,91 45 0,68 8 3140 520 70 0,57 42 0,48 6 2500 390 40 0,32 38 0,37

4 1850 280 20 0,15 32 0,26

� 10 V� 8 V� 6 V� 4 V� 2 V

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 62 47 51 60 54 52 46 39 LWA Intake dB(A) 69 64 65 62 55 55 55 45 LWA Exhaust dB(A) 81 68 70 76 75 73 71 61

V· m3/h

DpfaPa

r = 1,20 kg/m3

SVS EC 125

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 3680 590 115 0,92 54 0,71 8 3250 520 80 0,61 51 0,55 6 2500 370 40 0,31 46 0,39

4 2000 300 22 0,19 41 0,25

� 10 V� 8 V� 6 V� 4 V� 2 V

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 51 47 43 45 35 36 35 31 LWA Intake dB(A) 66 63 58 50 47 54 53 49 LWA Exhaust dB(A) 79 68 69 71 71 74 70 69

��

V· m3/h

DpfaPa

r = 1,20 kg/m3

SB EC 125 A

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 2380 530 110 0,95 43 0,75 8 2070 460 75 0,66 41 0,59 6 1890 410 55 0,48 39 0,48

4 1560 330 35 0,31 35 0,38

� 10 V� 8 V� 6 V � 4 V � 2 V

EC in

-line

fans

Page 3: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

346

160 mm ø EC centrifugal in-line fans Acoustic LineSilentBox® SB and SlimVent SVS

SlimVent SVS EC

248

362

390 220

91 48

ø 160

368

Dim. in mm

400 367

266

136

152

160

460* 438*

Virtually noise-free with high air flow volumes againsthigh resistances. Ideal for maintenance and cleaning.

SilentBox® SB ECUltra low profile. Ideal for applications withlimited installation space. With sound-insulatingmineral wool lining for particularly noise-free operation.

SB EC 160 B 9625 160 670 3630 45 979 12.00.11 0.89 60 EUR EC 1) 2) 1347 PU 10 1) 1734

Type Ref. no. ConnectionØ

Air flowvolume(FID)

R.P.M. Sound press.case

breakout

Wiringdiagram

Weightnet

approx.

mm.V m3/h min-1 dB(A) in 1m No. kg

Motorpower

kW

Current

A

max. air flowtemperature

+ °C

Universalcontrol system

Speed-potentiometer flush surface

Type Ref. no. Type Ref. no.

PA 10 1) 1735

SB EC 160 A 6136 160 540 2640 41 979 10.00.12 0.98 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

SVS EC 160 A 3) 0017 160 620 3650 55 979 8.00.12 0.93 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

SVS EC 160 B 0018 160 800 3100 55 979 7.60.13 1.04 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

Type Ref. no.

Type SilentBox® SB EC, 1 ph. motor, 230 V, 50/60 Hz, EC motor, IP 54 (A), IP 44 (B)

Type SVS EC, 1 ph. motor, 230 V, 50/60 Hz, EC motor, IP 44

� SimilaritiesSilentBox® SB ECand SlimVent SVS EC

� InstallationInstallation in any position with-out restriction – horizontally, ver-tically or pitched – suitable forintake or extract. Mountingbracket included in delivery.

� MotorEnergy saving, speed control-lable EC-external rotor motorswith highest efficiency, protectionto IP 44 (SB EC 160 A IP 54).With ball bearings, maintenance-free and interference-free.Dynamically balanced for lownoise operation.

� Speed controlStepless speed control with po-tentiometer or stepless speedcontrol with universal controlsystem (see table). Duties atdifferent speeds are exemplarilygiven in the performance curve.

� Motor protectionIntegrated electronic tempera-ture monitoring for EC-motorand electronics.

� Sound levelsSee page 351.

� Specification SilentBox® EC� CasingLike an internal attenuator.Acoustically lined with abrasiveresistant 50 mm thick mineralfibreboard. Four quick releaseclamps permit easy access tothe impeller set. Motor-impellerunit can be pulled out, the pull-out range must be considered.Spigots on intake and exhausttwin-seal rubber gaskets fitstandard ducts. All parts manu-factured from galvanised sheetsteel.

� ImpellerWith backward curved impeller.Inflow via inlet cone.SB EC 160 A forward curved

impeller in aerodynamically opti-mised volute casing, galvanisedsheet steel.

� Electrical connectionTerminal box (IP 54) mounted onrunning cable.

� Protection classWith a connected pipe systemIP 44 (SB EC 160 A IP 54).

� Specification SlimVent SVS EC� CasingExtremely flat casing in longerdesign with more than 50 mmthick sound-absorbing mineralwool lining and glass fibre sur-face. The acoustic box which isplaced in front of the fan reducesthe sound level for the intakesignificantly. The sound level ofthe case breakout is reduced toa smaller extent (see sound lev-els in the tables above the per-formance curves).

� The swing out motor and im-peller unit permits maintenance

and cleaning without disassem-bly of system components. Theswing-out range of the motor-impeller unit must be consid-ered.

� ImpellerEnergy-saving centrifugal im-peller with backward curvedblades from high quality poly-mer.

� Electrical connectionTerminal box (IP 54) mounted onrunning cable.

� Protection classWith a connected pipe systemIP 44.

1) Several EC fans can normally be connected. 2) alternative electronic differential pressure/temp. controller (EDR/ETR, No. 1437/1438) or three step speed controller (SU/SA, No. 4266/4267), see accessories.3) Characteristic curve on www.HeliosSelect.de

Dim. in mm SB EC 160 A, *SB EC 160 B

Saving ** with speed control

Page 4: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

347

EC centrifugal in-line fans Acoustic Line 160 mm øSilentBox® SB and SlimVent SVS

� Accessories

Flexible sleeveType FM 160 Ref. no. 1684Supplied with two hose clips asstandard; for installation betweenfan and duct system. Preventssound and vibration transmissionto ducting and corrects small site misalignments. For intake or ex-tract two sleeves are needed forcomplete isolation.

Gravity shutterType VK 160 Ref. no. 0892Automatic made from polymer,white.

Fixed grilleType G 160 Ref. no. 0893Made from polymer, white.

GuardType SGR 160 Ref. no. 5069For intake and extract installation.Made from galvanised steel.

Backdraught shutterType RSK 160 Ref. no. 5669Automatic, made from metal.

Flexible circular attenuatorType FSD 160 Ref. no. 0678Spigotted aluminium attenuatorwith 50 mm insulation. Length 1 m.

Air filter boxLFBR 160 G4 Ref. no. 8578LFBR 160 F7 Ref. no. 8532Air filter with large surface area, forinstallation in ducting.

Electric heater batteryEHR-R 1,2/160 1,2 kW No. 9434EHR-R 2,4/160 2,4 kW No. 9435EHR-R 5/160 5,0 kW No. 8710– with integrated temp. controlEHR-R 2,4/160 TR 2,4 kW No. 5294Room or duct sensor (TFK/TFR,accessories) required.

Temperature control system for electric heater battery EHR-RType EHS Ref. no. 5002

Warm water heater batteryType WHR 160 Ref. no. 9481Compact heat exchanger for in-line installation.

Temperature control system for warm water heater batteryType WHST 300 T38 No. 8817

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 53 46 48 48 45 37 34 30 LWA Intake dB(A) 64 62 57 53 47 47 45 37 LWA Exhaust dB(A) 82 67 72 78 74 73 70 64

V· m3/h

DpfaPa

r = 1,20 kg/m3

SB EC 160 B

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 3630 670 115 0,89 45 0,62 8 3120 560 70 0,56 43 0,45 6 2500 440 35 0,30 39 0,28 4 1850 320 20 0,15 33 0,23

� 10 V� 8 V� 6 V � 4 V � 2 V

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 63 50 56 60 52 50 44 37 LWA Intake dB(A) 72 66 69 62 55 57 54 43 LWA Exhaust dB(A) 80 69 73 76 71 71 68 58

��

V· m3/h

DpfaPa

r = 1,20 kg/m3

SVS EC 160 B

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 3100 800 130 1,04 55 0,59 8 2640 700 85 0,65 52 0,44 6 2000 520 40 0,32 46 0,28 4 1550 400 20 0,17 40 0,18

� 10 V� 8 V� 6 V � 4 V � 2 V

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 49 45 42 40 35 36 35 31 LWA Intake dB(A) 65 62 59 52 46 50 46 44 LWA Exhaust dB(A) 77 66 68 70 68 69 68 67

��

V· m3/h

DpfaPa

r = 1,20 kg/m3

SB EC 160 A

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 2060 540 100 0,86 41 0,80 8 1900 470 70 0,61 40 0,54 6 1640 420 50 0,44 37 0,43 4 1360 340 30 0,27 33 0,32

� 10 V� 8 V� 6 V � 4 V � 2 V

EC in

-line

fans

Page 5: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

348

200 mm ø EC centrifugal in-line fans Acoustic LineSilentBox® SB and SlimVent SVS

SlimVent SVS EC

288

372 220

390

111 48

ø 200

368

Dim. in mm

Ultra low profile. Ideal for applications withlimited installation space. With sound-insulatingmineral wool lining for particularly noise-free operation.

616 507

308

200

160

177

Virtually noise-free with high air flow volumes againsthigh resistances. Ideal for maintenance and cleaning.

SilentBox® SB EC

SB EC 200 B 9626 200 1160 2890 50 979 19.00.16 1.24 60 EUR EC 1) 2) 1347 PU 10 1) 1734

Type Ref. no. ConnectionØ

Air flowvolume(FID)

R.P.M. Sound press.case

breakout

Wiringdiagram

Weightnet

approx.

mm.V m3/h min-1 dB(A) in 1m No. kg

Motorpower

kW

Current

A

max. air flowtemperature

+ °C

Universalcontrol system

Speed-potentiometer flush surface

Type Ref. no. Type Ref. no.

PA 10 1) 1735

SB EC 200 A 6138 200 910 2900 45 979 19.00.12 0.99 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

SVS EC 200 0019 200 1030 2820 55 979 8.30.16 1.25 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

Type Ref. no.

Type SilentBox® SB EC, 1 ph. motor, 230 V, 50/60 Hz, EC motor, IP 54 (A), IP 44 (B)

Type SVS EC, 1 ph. motor, 230 V, 50/60 Hz, EC motor, IP 44

Dim. in mm

� SimilaritiesSilentBox® SB ECand SlimVent SVS EC

� InstallationInstallation in any position with-out restriction – horizontally, ver-tically or pitched – suitable forintake or extract. Mountingbracket included in delivery.

� MotorEnergy saving, speed control-lable EC-external rotor motorswith highest efficiency, protectionto IP 44 (SB EC 200 A IP 54).With ball bearings, maintenance-free and interference-free.Dynamically balanced for lownoise operation.

� Speed controlStepless speed control with po-tentiometer or stepless speedcontrol with universal controlsystem (see table). Duties atdifferent speeds are exemplarilygiven in the performance curve.

� Motor protectionIntegrated electronic tempera-ture monitoring for EC-motorand electronics.

� Sound levelsSee page 351.

� Specification SilentBox® EC� CasingLike an internal attenuator.Acoustically lined with abrasiveresistant 50 mm thick mineralfibreboard. Four quick releaseclamps permit easy access tothe impeller set. Motor-impellerunit can swing-out, the swing-out range of the motor-impellerunit must be considered. Spig-ots on intake and exhaust twin-seal rubber gaskets fit standardducts. All parts manufacturedfrom galvanised sheet steel.

� ImpellerWith backward curved impeller.Inflow via inlet cone.

� Electrical connectionTerminal box (IP 54) mounted onrunning cable.

� Protection classWith a connected pipe systemIP 44 (SB EC 200 A IP 54).

� Specification SlimVent SVS EC� CasingExtremely flat casing in longerdesign with more than 50 mmthick sound-absorbing mineralwool lining and glass fibre sur-face. The acoustic box which isplaced in front of the fan reducesthe sound level for the intakesignificantly. The sound level ofthe case breakout is reduced toa smaller extent (see sound lev-els in the tables above the per-formance curves).

� The swing out motor and im-peller unit permits maintenanceand cleaning without disassem-bly of system components.The swing-out range of the

motor-impeller unit must beconsidered.

� ImpellerEnergy-saving centrifugal im-peller with backward curvedblades from high quality poly-mer.

� Electrical connectionTerminal box (IP 54) mounted onrunning cable.

� Protection classWith a connected pipe systemIP 44.

1) Several EC fans can normally be connected. 2) alternative electronic differential pressure/temp. controller (EDR/ETR, No. 1437/1438) or three step speed controller (SU/SA, No. 4266/4267), see accessories.

Saving ** with speed control

Page 6: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

349

EC centrifugal in-line fans Acoustic Line 200 mm øSilentBox® SB and SlimVent SVS

� Accessories

Flexible sleeveType FM 200 Ref. no. 1670Supplied with two hose clips asstandard; for installation betweenfan and duct system. Preventssound and vibration transmissionto ducting and corrects small site misalignments. For intake or ex-tract two sleeves are needed forcomplete isolation.

Gravity shutterType VK 200 Ref. no. 0758Made from polymer, light grey.

Fixed grilleType RAG 200 Ref. no. 0750For covering air inlets and outletson facades. Made from polymer,light grey.

GuardType SGR 200 Ref. no. 5066For intake and extract installation.Made from galvanised steel.

Backdraught shutterType RSK 200 Ref. no. 5074Automatic, made from metal.

Flexible circular attenuatorType FSD 200 Ref. no. 0679Spigotted aluminium attenuatorwith 50 mm insulation. Length 1 m.

Air filter boxLFBR 200 G4 Ref. no. 8579LFBR 200 F7 Ref. no. 8533Air filter with large surface area, forinstallation in ducting.

Electric heater batteryEHR-R 1,2/200 1,2 kW No. 9436EHR-R 2/200 2,0 kW No. 9437EHR-R 5/200 5,0 kW No. 8711– with integrated temp. controlEHR-R 5/200 TR 5,0 kW No. 5295Room or duct sensor (TFK/TFR,accessories) required.

Temperature control system for electric heater battery EHR-RType EHS Ref. no. 5002

Warm water heater batteryType WHR 200 Ref. no. 9482Compact heat exchanger for in-line installation.

Temperature control system for warm water heater batteryType WHST 300 T38 No. 8817

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 58 51 56 49 41 37 33 30 LWA Intake dB(A) 69 66 65 58 49 44 44 36 LWA Exhaust dB(A) 76 69 72 68 64 65 60 52

��

V· m3/h

DpfaPa

r = 1,20 kg/m3

SB EC 200 B

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 2900 1160 160 1,24 50 0,49 8 2450 1040 105 0,85 47 0,36 6 1740 750 40 0,35 41 0,19 4 1250 540 15 0,14 35 0,10

� 10 V� 8 V� 6 V � 4 V � 2 V

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 63 47 57 60 52 48 41 34 LWA Intake dB(A) 72 66 68 62 54 51 50 41 LWA Exhaust dB(A) 81 69 76 78 71 71 66 56

��

V· m3/h

DpfaPa r = 1,20 kg/m3

SVS EC 200

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 2850 1030 160 1,27 55 0,56 8 2500 900 110 0,86 52 0,44 6 1850 670 45 0,36 46 0,23 4 1300 470 20 0,14 38 0,15

� 10 V� 8 V� 6 V � 4 V � 2 V

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 53 42 51 44 39 40 39 34 LWA Intake dB(A) 66 60 63 54 50 49 47 41 LWA Exhaust dB(A) 72 63 67 64 59 65 59 51

��

V· m3/h

DpfaPa

r = 1,20 kg/m3

SB EC 200 A

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 2930 910 104 0,85 45 0,41 8 2500 780 63 0,5 43 0,29 6 1950 610 32 0,27 38 0,19 4 1400 440 12 0,11 31 0,10

� 10 V� 8 V� 6 V � 4 V � 2 V

EC in

-line

fans

Page 7: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

SVS EC 250 6125 250 1250 2700 51 979 9.10.15 1.27 50 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

350

250 mm ø EC centrifugal in-line fans Acoustic LineSilentBox® SB and SlimVent SVS

580 527

250

184

179

342

Virtually noise-free with high air flow volumes againsthigh resistances. Ideal for maintenance and cleaning.

SilentBox® SB EC

Dim. in mm

SB EC 250 9627 250 1250 2760 50 979 17.50.16 1.27 60 EUR EC 1) 2) 1347 PU 10 1) 1734

Type Ref. no. ConnectionØ

Air flowvolume(FID)

R.P.M. Sound press.case

breakout

Wiringdiagram

Weightnet

approx.

mm.V m3/h min-1 dB(A) in 1m No. kg

Motorpower

kW

Current

A

max. air flowtemperature

+ °C

Universalcontrol system

Speed-potentiometer flush surface

Type Ref. no. Type Ref. no.

PA 10 1) 1735

Type Ref. no.

Type SilentBox® SB EC, 1 ph. motor, 230 V, 50/60 Hz, EC motor, IP 44

1) Several EC fans can normally be connected. 2) alternative electronic differential pressure/temp. controller (EDR/ETR, No. 1437/1438) or three step speed controller (SU/SA, No. 4266/4267), see accessories.

SlimVent SVS EC

339

392 196

391

136

48

ø 25072

8

Dim. in mm

Ultra low profile. Ideal for applications withlimited installation space. With sound-insulatingmineral wool lining for particularly noise-free operation.

� SimilaritiesSilentBox® SB ECand SlimVent SVS EC

� InstallationInstallation in any position with-out restriction – horizontally, ver-tically or pitched – suitable forintake or extract. Mountingbracket included in delivery.

� MotorEnergy saving, speed control-lable EC-external rotor motorswith highest efficiency, protectionto IP 44. With ball bearings,maintenance-free and interfer-ence-free. Dynamically balancedfor low noise operation.

� Speed controlStepless speed control with po-tentiometer or stepless speedcontrol with universal controlsystem (see table). Duties atdifferent speeds are exemplarilygiven in the performance curve.

� Motor protectionIntegrated electronic tempera-ture monitoring for EC-motorand electronics.

� Specification SilentBox® EC� CasingLike an internal attenuator.Acoustically lined with abrasiveresistant 50 mm thick mineralfibreboard. Four quick releaseclamps permit easy access tothe impeller set. Motor-impellerunit can swing-out, the swing-out range of the motor-impellerunit must be considered. Spig-ots on intake and exhaust twin-seal rubber gaskets fit standardducts. All parts manufacturedfrom galvanised sheet steel.

� ImpellerWith backward curved impeller.Inflow via inlet cone.

� Electrical connectionTerminal box (IP 54) mounted onrunning cable.

� Protection classWith a connected pipe systemIP 44.

� Specification SlimVent SVS EC� CasingExtremely flat casing in longerdesign with more than 50 mmthick sound-absorbing mineralwool lining and glass fibre sur-face. The acoustic box which isplaced in front of the fan reducesthe sound level for the intakesignificantly. The sound level ofthe case breakout is reduced toa smaller extent (see sound lev-els in the tables above the per-formance curves).

� The swing out motor and im-peller unit permits maintenanceand cleaning without disassem-bly of system components.The swing-out range of the

motor-impeller unit must beconsidered.

� ImpellerEnergy-saving centrifugal im-peller with backward curvedblades from high quality poly-mer.

� Electrical connectionTerminal box (IP 54) mounted onrunning cable.

� Protection classWith a connected pipe systemIP 44.

Type SVS EC, 1 ph. motor, 230 V, 50/60 Hz, EC motor, IP 44

Saving ** with speed control

Page 8: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

351

EC centrifugal in-line fans Acoustic Line 250 mm øSilentBox® SB and SlimVent SVS

� Accessories

Flexible sleeveType FM 250 Ref. no. 1672Supplied with two hose clips asstandard; for installation betweenfan and duct system. Preventssound and vibration transmissionto ducting and corrects small site misalignments. For intake or ex-tract two sleeves are needed forcomplete isolation.

Gravity shutterType VK 250 Ref. no. 0759Automatic made from polymer,light grey.

Fixed grilleType RAG 250 Ref. no. 0751For covering air inlets and outletson facades. Made from polymer,light grey.

GuardType SGR 250 Ref. no. 5067For intake and extract installation.Made from galvanised steel.

Backdraught shutterType RSK 250 Ref. no. 5673Automatic, made from metal.

Flexible circular attenuatorType FSD 250 Ref. no. 0680Spigotted aluminium attenuatorwith 50 mm insulation. Length 1 m.

Air filter boxLFBR 250 G4 Ref. no. 8580LFBR 250 F7 Ref. no. 8534Air filter with large surface area, forinstallation in ducting.

Electric heater batteryEHR-R 6/250 6,0 kW No. 8712– with integrated temp. controlEHR-R 6/250 TR 6,0 kW No. 5296Room or duct sensor (TFK/TFR,accessories) required.

Temperature control system for electric heater battery EHR-RType EHS Ref. no. 5002

Warm water heater batteryType WHR 250 Ref. no. 9483Compact heat exchanger for in-line installation.

Temperature control system for warm water heater batteryType WHS HE Ref. no. 8319

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 58 49 57 48 41 37 33 30 LWA Intake dB(A) 69 63 66 55 50 50 47 38 LWA Exhaust dB(A) 77 67 72 67 67 69 63 52

��

V· m3/h

DpfaPa r = 1,20 kg/m3

SB EC 250

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 2760 1250 163 1,27 50 0,47 8 2480 1110 110 0,90 49 0,36 6 1850 830 50 0,42 44 0,22

4 1250 580 15 0,14 37 0,09

� 10 V� 8 V� 6 V� 4 V� 2 V

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 59 47 56 56 48 44 37 32 LWA Intake dB(A) 72 65 70 57 55 56 54 45 LWA Exhaust dB(A) 82 68 78 77 72 73 69 61

��

��

V· m3/h

DpfaPa

r = 1,20 kg/m3

SVS EC 250

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 2700 1250 150 1,2 51 0,43 8 2450 1160 120 0,98 49 0,37 6 1720 820 45 0,35 42 0,20

4 1050 500 12 0,10 32 0,09

� 10 V� 8 V� 6 V� 4 V� 2 V

� Sound levelsTotal sound power levels andthe spectrum figures in dB(A)are given for:

– Sound level case breakout– Sound level intake– Sound level exhaustIn the table below as well as un-derneath the performance curveyou can find additionally thesound pressure level at 1 m(free field conditions).

� Accessory details Page

Filters, heater batteries and attenuators 421 onTemperature control systemsfor heater batteries 427, 431 onFlexible ventilation ducting,Grilles, adaptors,roof terminations 487 onValves 508 onUniversal control system,electronic controller,speed-potentiometer 539 on

EC in

-line

fans

Page 9: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

SVS EC 315 6126 315 1630 2400 51 979 14.50.23 0.99 45 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

352

315 mm ø EC centrifugal in-line fans Acoustic LineSilentBox® SB and SlimVent SVS

410

658 608

315

246

226

763* 708*

463*

251*

218*

Virtually noise-free with high air flow volumes againsthigh resistances. Ideal for maintenance and cleaning.

SilentBox® SB EC

SB EC 315 A 6157 315 2160 2020 55 1066 34.00.33 1.50 60 EUR EC 1) 2) 1347 PU 10 1) 1734

Type Ref. no. ConnectionØ

Air flowvolume(FID)

R.P.M. Sound press.case

breakout

Wiringdiagram

Weightnet

approx.

mm.V m3/h min-1 dB(A) in 1m No. kg

Motorpower

kW

Current

A

max. air flowtemperature

+ °C

Universalcontrol system

Speed-potentiometer flush surface

Type Ref. no. Type Ref. no.

PA 10 1) 1735

SB EC 315 B 9628 315 2640 1650 51 1066 49.00.31 1,36 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

Type Ref. no.

Type SilentBox® SB EC, 1 ph. motor, 230 V, 50/60 Hz, EC motor, IP 54

1) Several EC fans can normally be connected. 2) alternative electronic differential pressure/temp. controller (EDR/ETR, No. 1437/1438) or three step speed controller (SU/SA, No. 4266/4267), see accessories.

Type SVS EC, 1 ph. motor, 230 V, 50/60 Hz, EC motor, IP 44

� SimilaritiesSilentBox® SB ECand SlimVent SVS EC

� InstallationInstallation in any position with-out restriction – horizontally, ver-tically or pitched – suitable forintake or extract. Mountingbracket included in delivery.

� MotorEnergy saving, speed control-lable EC-external rotor motorswith highest efficiency, protectionto IP 54 (SB EC) or IP 44 (SVSEC). With ball bearings, mainte-nance-free and interference-free.Dynamically balanced for lownoise operation.

� Speed controlStepless speed control with po-tentiometer or stepless speedcontrol with universal controlsystem (see table). Duties atdifferent speeds are exemplarilygiven in the performance curve.

� Motor protectionIntegrated electronic tempera-ture monitoring for EC-motorand electronics.

� Sound levelsSee page 351.

� Specification SilentBox® EC� CasingLike an internal attenuator.Acoustically lined with abrasiveresistant 50 mm thick mineralfibreboard. Four quick releaseclamps permit easy access tothe impeller set. Motor-impellerunit can swing-out, the swing-out range of the motor-impellerunit must be considered. Spig-ots on intake and exhaust twin-seal rubber gaskets fit standardducts. All parts manufacturedfrom galvanised sheet steel.

� ImpellerWith backward curved impeller.Inflow via inlet cone.

� Electrical connectionTerminal box (IP 54) mounted onrunning cable (approx. 60 cmlong).

� Protection classWith a connected pipe systemIP 54.

� Specification SlimVent SVS EC� CasingExtremely flat casing in longerdesign with more than 50 mmthick sound-absorbing mineralwool lining and glass fibre sur-face. The acoustic box which isplaced in front of the fan reducesthe sound level for the intakesignificantly. The sound level ofthe case breakout is reduced toa smaller extent (see sound lev-els in the tables above the per-formance curves).

� The swing out motor and im-peller unit permits maintenanceand cleaning without disassem-bly of system components.

The swing-out range of the mo-tor-impeller unit must be consid-ered.

� ImpellerEnergy-saving centrifugal im-peller with backward curvedblades from high quality poly-mer.

� Electrical connectionTerminal box (IP 54) mounted onrunning cable.

� Protection classWith a connected pipe systemIP 44.

SlimVent SVS EC

426

427 223

446

169 48

ø 31584

0

Dim. in mm

Ultra low profile. Ideal for applications withlimited installation space. With sound-insulatingmineral wool lining for particularly noise-free operation.

Dim. in mm SB EC 315 A, *SB EC 315 B

Saving ** with speed control

Page 10: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

353

EC centrifugal in-line fans Acoustic Line 315 mm øSilentBox® SB and SlimVent SVS

� Accessories

Flexible sleeveType FM 315 Ref. no. 1674Supplied with two hose clips asstandard; for installation betweenfan and duct system. Preventssound and vibration transmissionto ducting and corrects small site misalignments. For intake or ex-tract two sleeves are needed forcomplete isolation.

Gravity shutterType VK 315 Ref. no. 0760Automatic made from polymer,light grey.

Fixed grilleType RAG 315 Ref. no. 0752For covering air inlets and outletson facades. Made from polymer,light grey.

GuardType SGR 315 Ref. no. 5068For intake and extract installation.Made from galvanised steel.

Backdraught shutterType RSK 315 Ref. no. 5674Automatic, made from metal.

Flexible circular attenuatorType FSD 315 Ref. no. 0681Spigotted aluminium attenuatorwith 50 mm insulation. Length 1 m.

Air filter boxLFBR 315 G4 Ref. no. 8581LFBR 315 F7 Ref. no. 8535Air filter with large surface area, forinstallation in ducting.

Electric heater batteryEHR-R 6/315 6,0 kW No. 8713– with integrated temp. controlEHR-R 6/315 TR 6,0 kW No. 5301Room or duct sensor (TFK/TFR,accessories) required.

Temperature control system for electric heater battery EHR-RType EHS Ref. no. 5002

Warm water heater batteryType WHR 315 Ref. no. 9484Compact heat exchanger for in-line installation.

Temperature control system for warm water heater batteryType WHS HE Ref. no. 8319

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 63 52 62 51 41 39 39 35 LWA Intake dB(A) 73 68 70 54 48 50 46 44 LWA Exhaust dB(A) 79 70 78 67 65 61 57 55

��

V· m3/h

DpfaPa r = 1,20 kg/m3

SB EC 315 A

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 2020 2160 330 1,44 55 0,55 8 1620 1700 170 0,76 51 0,36 6 1210 1260 75 0,34 45 0,21

4 770 740 25 0,15 36 0,12

� 10 V� 8 V� 6 V � 4 V � 2 V

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 59 56 57 43 34 30 27 27 LWA Intake dB(A) 69 67 64 50 41 40 39 37 LWA Exhaust dB(A) 77 75 72 62 61 57 55 53

V· m3/h

DpfaPa r = 1,20 kg/m3

SB EC 315 B

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 1650 2640 280 1,23 51 0,38 8 1350 2200 155 0,68 47 0,25 6 1000 1580 70 0,31 42 0,16

4 700 1100 26 0,13 37 0,09

� 10 V� 8 V� 6 V � 4 V � 2 V

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 59 45 53 56 49 47 42 38 LWA Intake dB(A) 73 67 66 57 60 64 60 56 LWA Exhaust dB(A) 82 67 70 79 72 76 71 67

��

��

V· m3/h

DpfaPa

r = 1,20 kg/m3

SVS EC 315

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 2700 1630 220 0,96 51 0,49 8 2240 1330 130 0,57 47 0,35 6 1680 1000 60 0,25 41 0,22

4 1200 720 25 0,13 34 0,13

� 10 V� 8 V� 6 V� 4 V� 2 V

EC in

-line

fans

Page 11: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

354

355 mm ø EC centrifugal in-line fans Acoustic LineSilentBox® SB

� Specification

� CasingLike an internal attenuator.Acoustically lined with abrasiveresistant 50 mm thick mineralfibreboard. Four quick releaseclamps permit easy access tothe impeller set. Motor-impellerunit can swing-out, the swing-out range of the motor-impellerunit must be considered. Spig-ots on intake and exhaust twin-seal rubber gaskets fit standardducts. All parts manufacturedfrom galvanised sheet steel.

� ImpellerWith backward curved impeller.Inflow via inlet cone.

� MotorEnergy saving, speed control-lable EC-external rotor motorswith highest efficiency, protectionto IP 54. With ball bearings,maintenance-free and interfer-ence-free. Dynamically balancedfor low noise operation.

� Motor protectionIntegrated electronic tempera-ture monitoring for EC-motorand electronics.

� Speed controlStepless speed control with po-tentiometer or stepless speedcontrol with universal controlsystem (see table). Duties atdifferent speeds are exemplarilygiven in the performance curve.

� Electrical connectionTerminal box (IP 54) mounted onrunning cable (approx. 60 cmlong).

� Protection classWith a connected pipe systemIP 54.

� InstallationInstallation in any position with-out restriction – horizontally, ver-tically or pitched – suitable forintake or extract. Mountingbracket included in delivery.

� Sound levelsTotal sound power levels andthe spectrum figures in dB(A)are given for:

– Sound level case breakout– Sound level intake– Sound level exhaustIn the table below as well as un-derneath the performance curveyou can find additionally thesound pressure level at 1 m(free field conditions).

763 708

355

463

231

251

Virtually noise-free with high air flow volumes againsthigh resistances. Ideal for maintenance and cleaning.

SilentBox® SB EC

Dim. in mm

SB EC 355 6139 355 2670 1650 51 1066 37.00.32 1.40 60 EUR EC 1) 2) 1347 PU 10 1) 1734

Type Ref. no. ConnectionØ

Air flowvolume(FID)

R.P.M. Sound press.case

breakout

Wiringdiagram

Weightnet

approx.

mm.V m3/h min-1 dB(A) in 1m No. kg

Motorpower

kW

Current

A

max. air flowtemperature

+ °C

Universalcontrol system

Speed-potentiometer flush surface

Type Ref. no. Type Ref. no.

PA 10 1) 1735

Type Ref. no.

Type SilentBox® SB EC, 1 ph. motor 230 V, 50/60 Hz, EC motor, IP 54

1) Several EC fans can normally be connected. 2) alternative electronic differential pressure/temp. controller (EDR/ETR, No. 1437/1438) or three step speed controller (SU/SA, No. 4266/4267), see accessories.

Saving ** with speed control

Page 12: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

355

EC centrifugal in-line fans Acoustic Line 355 mm øSilentBox® SB

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 59 52 58 44 38 37 36 32 LWA Intake dB(A) 70 68 63 49 44 46 41 41 LWA Exhaust dB(A) 74 71 70 61 59 57 53 50

��

V· m3/h

DpfaPa r = 1,20 kg/m3

SB EC 355

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 1650 2670 280 1,26 51 0,38 8 1320 2170 150 0,66 47 0,25 6 1000 1630 70 0,31 41 0,15

4 600 980 20 0,12 30 0,07

� 10 V� 8 V� 6 V� 4 V� 2 V

� Accessories

Flexible sleeveType FM 355 Ref. no. 1675Supplied with two hose clips asstandard; for installation betweenfan and duct system. Preventssound and vibration transmissionto ducting and corrects small site misalignments. For intake or ex-tract two sleeves are needed forcomplete isolation.

Gravity shutterType VK 355 Ref. no. 0761Automatic made from polymer,light grey.

Fixed grilleType RAG 355 Ref. no. 0753For covering air inlets and outletson facades. Made from polymer,light grey.

Backdraught shutterType RSK 355 Ref. no. 5650Automatic, made from metal.

Flexible circular attenuatorType FSD 355 Ref. no. 0682Spigotted aluminium attenuatorwith 50 mm insulation. Length 1 m.

Air filter boxLFBR 355 G4 Ref. no. 8583LFBR 355 F7 Ref. no. 8536Air filter with large surface area andcapacity for installation in ducting.Connections with double lip seals,adapted to standard Ø.

Electric heater batteryEHR-R 355 9,0 kW No. 8656– with integrated temp. controlEHR-R 9/355 TR 9,0 kW No. 5297Room or duct sensor (TFK/TFR,accessories) required.

Temperature control system for electric heater battery EHR-RType EHSD 16 Ref. no. 5003

Warm water heater batteryType WHR 355 Ref. no. 8790Compact heat exchanger for in-line installation.

Temperature control system for warm water heater batteryType WHS HE Ref. no. 8319

� Accessory details Page

Filters, heater batteries and attenuators 421 onTemperature control systemsfor heater batteries 427, 431 onFlexible ventilation ducting,Grilles, adaptors,roof terminations 487 onValves 508 onUniversal control system,electronic controller,speed-potentiometer 539 on

EC in

-line

fans

Page 13: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

356

400 mm ø EC centrifugal in-line fans Acoustic LineSilentBox® SB

� Specification

� CasingLike an internal attenuator.Acoustically lined with abrasiveresistant 50 mm thick mineralfibreboard. Four quick releaseclamps permit easy access tothe impeller set. Motor-impellerunit can swing-out, the swing-out range of the motor-impellerunit must be considered. Spig-ots on intake and exhaust twin-seal rubber gaskets fit standardducts. All parts manufacturedfrom galvanised sheet steel.

� ImpellerWith backward curved impeller.Inflow via inlet cone.

� MotorEnergy saving, speed control-lable EC-external rotor motorswith highest efficiency, protectionto IP 54. With ball bearings,maintenance-free and interfer-ence-free. Dynamically balancedfor low noise operation.

� Motor protectionIntegrated electronic tempera-ture monitoring for EC-motorand electronics.

� Speed controlStepless speed control with po-tentiometer or stepless speedcontrol with universal controlsystem (see table). Duties atdifferent speeds are exemplarilygiven in the performance curve.

� Electrical connectionTerminal box (IP 54) mounted onrunning cable (approx. 60 cmlong).

� Protection classWith a connected pipe systemIP 54.

� InstallationInstallation in any position with-out restriction – horizontally, ver-tically or pitched – suitable forintake or extract. Mountingbracket included in delivery.

� Sound levelsTotal sound power levels andthe spectrum figures in dB(A)are given for:

– Sound level case breakout– Sound level intake– Sound level exhaustIn the table below as well as un-derneath the performance curveyou can find additionally thesound pressure level at 1 m(free field conditions).

763 708

400

513

256

265

567*

304*

261*

908* 808*

Virtually noise-free with high air flow volumes againsthigh resistances. Ideal for maintenance and cleaning.

SilentBox® SB EC

SB EC 400 B 9629 400 4760 1420 56 982 60.80.65 2.98 60 EUR EC 1) 2) 1347 PU 10 1) 1734

Type Ref. no. ConnectionØ

Air flowvolume(FID)

R.P.M. Sound press.case

breakout

Wiringdiagram

Weightnet

approx.

mm.V m3/h min-1 dB(A) in 1m No. kg

Motorpower

kW

Current

A

max. air flowtemperature

+ °C

Universalcontrol system

Speed-potentiometer flush surface

Type Ref. no. Type Ref. no.

PA 10 1) 1735

SB EC 400 A 6140 400 3000 1650 53 1066 45.00.34 1.50 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

Type Ref. no.

Type SilentBox® SB EC, 1 ph. motor, 230 V, 50/60 Hz, EC motor, IP 54

1) Several EC fans can normally be connected. 2) alternative electronic differential pressure/temp. controller (EDR/ETR, No. 1437/1438) or three step speed controller (SU/SA, No. 4266/4267), see accessories.

Dim. in mm SB EC 400 A, *SB EC 400 B

Saving ** with speed control

Page 14: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

357

EC centrifugal in-line fans Acoustic Line 400 mm øSilentBox® SB

� Accessories

Flexible sleeveType FM 400 Ref. no. 1676Supplied with two hose clips asstandard; for installation betweenfan and duct system. Preventssound and vibration transmissionto ducting and corrects small site misalignments. For intake or ex-tract two sleeves are needed forcomplete isolation.

Gravity shutterType VK 400 Ref. no. 0762Automatic made from polymer,light grey.

Fixed grilleType RAG 400 Ref. no. 0754For covering air inlets and outletson facades. Made from polymer,light grey.

Backdraught shutterType RSK 400 Ref. no. 5651Automatic, made from metal.

Flexible circular attenuatorType FSD 400 Ref. no. 0683Spigotted aluminium attenuatorwith 50 mm insulation. Length 1 m.

Air filter boxLFBR 400 G4 Ref. no. 8582LFBR 400 F7 Ref. no. 8537Air filter with large surface area andcapacity for installation in ducting.Connections with double lip seals,adapted to standard Ø.

Electric heater batteryEHR-R 9/400 9,0 kW No. 8657– with integrated temp. controlEHR-R 9/400 TR 9,0 kW No. 5299Room or duct sensor (TFK/TFR,accessories) required.

Temperature control system for electric heater battery EHR-RType EHSD 16 Ref. no. 5003

Warm water heater batteryType WHR 400 Ref. no. 9524Compact heat exchanger for in-line installation.

Temperature control system for warm water heater batteryType WHS HE Ref. no. 8319

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 61 52 60 45 38 37 36 33 LWA Intake dB(A) 73 71 69 53 48 48 45 45 LWA Exhaust dB(A) 77 73 72 63 64 60 57 57

��

V· m3/h

DpfaPa

r = 1,20 kg/m3

SB EC 400 A

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 1650 3000 300 1,30 53 0,36 8 1330 2430 160 0,71 49 0,24 6 1000 1820 75 0,33 44 0,15

4 610 1100 20 0,11 34 0,07

� 10 V� 8 V� 6 V� 4 V� 2 V

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 64 62 58 46 37 34 31 28 LWA Intake dB(A) 73 71 64 60 58 45 41 39 LWA Exhaust dB(A) 80 78 73 67 65 61 59 54

V· m3/h

DpfaPa

r = 1,20 kg/m3

SB EC 400 B

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 1420 4760 590 2,73 56 0,45 8 1150 3840 310 1,48 52 0,29 6 900 3000 160 0,75 47 0,19

4 700 2290 80 0,41 41 0,13

� 10 V� 8 V� 6 V � 4 V � 2 V

� Accessory details Page

Filters, heater batteries and attenuators 421 onTemperature control systemsfor heater batteries 427, 431 onFlexible ventilation ducting,Grilles, adaptors,roof terminations 487 onValves 508 onUniversal control system,electronic controller,speed-potentiometer 539 on

EC in

-line

fans

Page 15: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

358

125 mm ø Centrifugal in-line fans Acoustic LineSilentBox® SB and SlimVent SVS

Virtually noise-free with high air flow volumes againsthigh resistances. Ideal for maintenance and cleaning.

SilentBox® SB

Dim. in mm

� Similarities SB and SVS� InstallationInstallation in any position with-out restriction – horizontally, ver-tically or pitched – suitable forintake or extract (Exception:SVS must not be installed withthe swing-out motor-impellerunit facing upward).

� MotorTotally enclosed external rotormotor with ball bearings, im-pregnated windings insulationclass F, designed for continuousoperation, maintenance free andinterference-free.

� Specification SilentBox®� CasingLike an internal attenuator.Acoustically lined with abrasiveresistant 50 mm thick mineralfibreboard. Four quick releaseclamps permit easy access tomotor scroll and impeller set.

Swing out motor and impeller.Spigots on intake and exhausttwin-seal rubber gaskets fitstandard ducts. All parts manu-factured from galvanised sheetsteel.

� ImpellerLow noise forward curved cen-trifugal impeller, housed withinan aerodynamically shapedscroll from galvanised steel.Bell mouth shaped inlet ring toachieve optimum air flow.

� Electrical connectionTerminal box (IP 54) is suppliedwith a 60 cm long electric cable.

� Motor protectionWith thermal contacts wired inseries with the windings. To re-set the thermal contacts themain supply must be switchedoff and on.

� Speed controlStepless 0 – 100 % using elec-tronic controller or 5 step trans-former controller (see table).

� Protection classIP 44

� Specification SlimVent SVS� CasingExtremely flat casing in longerdesign with more than 50 mmthick sound-absorbing mineralwool lining and glass fibre sur-face. The acoustic box which isplaced in front of the fan reducesthe sound level for the intakesignificantly. The sound pressurelevel is reduced to a smaller ex-tent (see sound levels in the ta-bles above the performancecurves).

� The swing out motor and im-peller unit permits maintenanceand cleaning without disassem-bly of system components.The swing-out range must beconsidered for the inspectionflap.

� ImpellerEnergy-saving centrifugal im-peller with backward curvedblades from high quality poly-mer. Dynamically balanced forlow noise operation.

� Electrical connectionTerminal box (IP 54) mounted onrunning cable.

� Motor protectionWith thermal contacts wired inseries with the windings whichautomatically reset after cooling.

� Speed controlStepless 0 – 100 % by use ofelectronic controller or 5 steptransformer controller (see table)or 2 speed operation withDS 2/2 (accessories).Type DS 2/2 Ref. no. 1267

� Protection classWhen installed in ducting the fanis rated IP 44.

SlimVent SVS

210

314

73

190

330

48

ø 125

310

Ultra low profile. Ideal for applications withlimited installation space. With sound-insulatingmineral wool lining for particularly noise-free operation.

Dim. in mm

1) Values refer to the two speed stages (see characteristic curve).* In noise relevant cases, transformer controllers must be provided. An electronic controller can trigger a distracting magnetisation noise.

Type Ref. no. Air flow R.P.M. Sound press. Motor Current Wiring max. air flow temp. Weight Transformer- Electronic*volume case power full diagram full net speed controller speed controller, stepless(FID) breakout load control load control approx. 5-step flush / surface

.V m3/h min-1 db(A) in 1m W A A No. +°C +°C kg Type Ref. no. Type Ref. no.

Type SilentBox® SB, 1 ph. motor, 230 V, 50 Hz, capacitor motor, IP 44

SB 125 A 9506 230 1130 28 61 0.27 0.27 508 80 80 12.0 TSW 0,3 3608 ESU 1 / ESA 1 0236 / 0238

SB 125 C 9562 440 1850 37 122 0.53 0.53 508 65 65 12.0 TSW 1,5 1495 ESU 1 / ESA 1 0236 / 0238

Type SVS, 1 ph. motor, 230 V, 50 Hz, capacitor motor, IP 33

SVS 125 B 0130 400/2701) 2570/17101) 45/361) 61/451) 0.27/0.201) 0.261) 934.1 60 60 5.9 TSW 1,5 1495 ESU 1 / ESA 1 0236 / 0238

FEfficiency class

Page 16: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

359

In-li

nefa

ns

Centrifugal in-line fans Acoustic Line 125 mm øSilentBox® SB and SlimVent SVS

� Accessories

Flexible sleeveType FM 125 Ref. no. 1682Supplied with two hose clips asstandard; for installation betweenfan and duct system. Preventssound and vibration transmissionto ducting and corrects small site misalignments. For intake or ex-tract two sleeves are needed forcomplete isolation.

Gravity shutterType VK 125 Ref. no. 0857Automatic made from polymer,white.

Fixed grilleType G 160 Ref. no. 0893Made from polymer, white.

GuardType SGR 125 Ref. no. 5064For intake and extract installation.Made from powder-coated steelwire.

Backdraught shutterType RSKK 125 Ref. no. 5107Automatic, made from polymer.

Flexible circular attenuatorType FSD 125 Ref. no. 0677Spigotted aluminium attenuatorwith 50 mm insulation. Length 1 m.

Air filter boxLFBR 125 G4 Ref. no. 8577LFBR 125 F7 Ref. no. 8531Air filter with large surface area forinstallation in ducting.

Electric heater batteryEHR-R 0,8/125 0,8 kW No. 8709EHR-R 1,2/125 1,2 kW No. 9433– with integrated temp. controlEHR-R 0,8/125 TR 0,8 kW No. 5293Room or duct sensor (TFK/TFR,accessories) required.

Temperature control system for electric heater battery EHR-RType EHS Ref. no. 5002

Warm water heater batteryType WHR 125 Ref. no. 9480Compact heat exchanger for in-line installation.

Temperature control system for warm water heater batteryType WHST 300 T38 No. 8817

DpfaPa

V· m3/h

r = 1,20 kg/m3

V· m3/h

r = 1,20 kg/m3

SB 125 A

SVS 125 B

DpfaPa

� High speed� Low speed

� Sound levelsTotal sound power levels andthe spectrum figures in dB(A)are given for

– Sound level case breakout– Sound level intake/exhaustThe type table also shows

– Sound pressure case breakoutand intake air noise specified assound pressure in 1 m (free fieldconditions).For the SB types, it should benoted that the intake sound levelis less than the exhaust soundlevel.

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 35 28 28 27 27 25 26 27 LWA Intake dB(A) 53 51 48 43 38 33 29 17 LWA Exhaust dB(A) 61 53 54 55 56 50 43 30

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 54 38 48 51 43 39 33 30 LWA Intake dB(A) 63 58 60 53 44 44 43 36 LWA Exhaust dB(A) 72 61 65 68 64 61 57 49

� Accessory details Page

Filters, heater batteries and attenuators 421 onTemperature control systemsfor heater batteries 427, 431 onFlexible ventilation ducting,Grilles, adaptors,roof terminations 487 onValves 508 onSpeed controllers,switches 525 on

� 230 V� 170 V� 130 V� 100 V� 80 V

��

DpfaPa

V· m3/h

r = 1,20 kg/m3

SB 125 C

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 44 35 42 36 33 29 28 28 LWA Intake dB(A) 62 59 57 54 46 44 40 30 LWA Exhaust dB(A) 70 62 63 65 64 62 55 46

� 230 V� 170 V� 130 V� 100 V� 80 V

Page 17: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

360

160 mm ø Centrifugal in-line fans Acoustic LineSilentBox® SB and SlimVent SVS

SlimVent SVS

246

362

390 220

91 48

ø 160

368

Dim. in mm

Virtually noise-free with high air flow volumes againsthigh resistances. Ideal for maintenance and cleaning.

SilentBox® SB

Dim. in mm

� Similarities SB and SVS� InstallationInstallation in any position with-out restriction – horizontally, ver-tically or pitched – suitable forintake or extract (Exception:SVS must not be installed withthe swing-out motor-impellerunit facing upward).

� MotorTotally enclosed external rotormotor with ball bearings, im-pregnated windings insulationclass F, designed for continuousoperation, maintenance free andinterference-free.

� Sound levels See page 359.

� Specification SilentBox®� CasingLike an internal attenuator.Acoustically lined with abrasiveresistant 50 mm thick mineralfibreboard. Four quick releaseclamps permit easy access to

motor scroll and impeller set.Swing out motor and impeller.Spigots on intake and exhausttwin-seal rubber gaskets fitstandard ducts. All parts manu-factured from galvanised sheetsteel.

� ImpellerLow noise forward curved cen-trifugal impeller, housed withinan aerodynamically shapedscroll from galvanised steel.Bell mouth shaped inlet ring toachieve optimum air flow.

� Electrical connectionTerminal box (IP 54) is suppliedwith a 60 cm long electric cable.

� Motor protectionWith thermal contacts wired inseries with the windings. To re-set the thermal contacts themain supply must be switchedoff and on.

� Speed controlStepless 0 – 100 % using elec-tronic controller or 5 step trans-former controller (see table).

� Protection classIP 44

� Specification SlimVent SVS� CasingExtremely flat casing in longerdesign with more than 50 mmthick sound-absorbing mineralwool lining and glass fibre sur-face. The acoustic box which isplaced in front of the fan reducesthe sound level for the intakesignificantly. The sound pressurelevel is reduced to a smaller ex-tent (see sound levels in the ta-bles above the performancecurves).

� The swing out motor and im-peller unit permits maintenanceand cleaning without disassem-bly of system components. The

swing-out range must be con-sidered for the inspection flap.

� ImpellerEnergy-saving centrifugal im-peller with backward curvedblades from high quality poly-mer. Dynamically balanced forlow noise operation.

� Electrical connectionTerminal box (IP 54) mounted onrunning cable.

� Motor protectionWith thermal contacts wired inseries with the windings whichautomatically reset after cooling.

� Speed controlStepless 0 – 100 % by use ofelectronic controller or 5 steptransformer controller (see table)or 2 speed operation withDS 2/2 (accessories).Type DS 2/2 Ref. no. 1267

� Protection classWhen installed in ducting the fanis rated IP 44.

Ultra low profile. Ideal for applications withlimited installation space. With sound-insulatingmineral wool lining for particularly noise-free operation.

1) Values refer to the two speed stages (see characteristic curve).* In noise relevant cases, transformer controllers must be provided. An electronic controller can trigger a distracting magnetisation noise.

Type Ref. no. Air flow R.P.M. Sound press. Motor Current Wiring max. air flow temp. Weight Transformer- Electronic*volume case power full diagram full net speed controller speed controller, stepless(FID) breakout load control load control approx. 5-step flush / surface

.V m3/h min-1 db(A) in 1m W A A No. +°C +°C kg Type Ref. no. Type Ref. no.

Type SilentBox® SB, 1 ph. motor, 230 V, 50 Hz, capacitor motor, IP 44 (B), IP 33 (D)

SB 160 B 9508 360 1650 36 105 0.46 0.46 508 65 65 13.0 TSW 1,5 1495 ESU 1 / ESA 1 0236 / 0238

SB 160 D 9563 580 2220 43 164 0.72 0.72 508 60 60 10.3 TSW 1,5 1495 ESU 1 / ESA 1 0236 / 0238

Type SVS, 1 ph. motor, 230 V, 50 Hz, capacitor motor, IP 33

SVS 160 K 0131 440/3001) 2560/17301) 44/351) 61/451) 0.26/0.201) 0.261) 934.1 60 60 7.6 TSW 1,5 1495 ESU 1 / ESA 1 0236 / 0238

SVS 160 L 2653 670/3901) 2520/15301) 50/391) 108/691) 0.47/0.301) 0.451) 934.1 60 60 7.8 TSW 1,5 1495 ESU 1 / ESA 1 0236 / 0238

Page 18: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

361

In-li

nefa

ns

Centrifugal in-line fans Acoustic Line 160 mm øSilentBox® SB and SlimVent SVS

� Accessories

Flexible sleeveType FM 160 Ref. no. 1684Supplied with two hose clips asstandard; for installation betweenfan and duct system. Preventssound and vibration transmissionto ducting and corrects small site misalignments. For intake or ex-tract two sleeves are needed forcomplete isolation.

Gravity shutterType VK 160 Ref. no. 0892Automatic made from polymer,white.

Fixed grilleType G 160 Ref. no. 0893Made from polymer, white.

GuardType SGR 160 Ref. no. 5069For intake and extract installation.Made from galvanised steel.

Backdraught shutterType RSK 160 Ref. no. 5669Automatic, made from metal.

Flexible circular attenuatorType FSD 160 Ref. no. 0678Spigotted aluminium attenuatorwith 50 mm insulation. Length 1 m.

Air filter boxLFBR 160 G4 Ref. no. 8578LFBR 160 F7 Ref. no. 8532Air filter with large surface area forinstallation in ducting.

Electric heater batteryEHR-R 1,2/160 1,2 kW No. 9434EHR-R 2,4/160 2,4 kW No. 9435EHR-R 5/160 5,0 kW No. 8710– with integrated temp. controlEHR-R 2,4/160 TR 2,4 kW No. 5294Room or duct sensor (TFK/TFR,accessories) required.

Temperature control system for electric heater battery EHR-RType EHS Ref. no. 5002

Warm water heater batteryType WHR 160 Ref. no. 9481Compact heat exchanger for in-line installation.

Temperature control system for warm water heater batteryType WHST 300 T38 No. 8817

DpfaPa

V· m3/h

r = 1,20 kg/m3

V· m3/h

r = 1,20 kg/m3

SB 160 B

SVS 160 K

DpfaPa

� High speed� Low speed

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 43 40 39 34 32 28 27 27 LWA Intake dB(A) 61 59 56 50 44 39 35 26 LWA Exhaust dB(A) 68 61 61 62 61 58 53 44

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 52 38 47 50 40 37 32 31 LWA Intake dB(A) 63 58 61 50 40 45 44 38 LWA Exhaust dB(A) 70 60 66 65 59 56 56 48

� 230 V� 170 V� 130 V � 100 V � 80 V

��

DpfaPa

V· m3/h

r = 1,20 kg/m3

SB 160 D

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 50 47 44 41 34 32 30 28 LWA Intake dB(A) 67 65 60 53 44 48 46 45 LWA Exhaust dB(A) 79 68 71 72 69 71 69 69

� 230 V� 170 V� 130 V� 100 V� 80 V

* Note the necessary minimum unit resistance.

* * ** *

V· m3/h

r = 1,20 kg/m3

SVS 160 L

DpfaPa

� High speed� Low speed

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 58 40 53 55 46 44 38 31 LWA Intake dB(A) 66 60 64 58 50 47 48 35 LWA Exhaust dB(A) 75 62 67 73 66 63 63 51

Page 19: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

362

200 mm ø Centrifugal in-line fans Acoustic LineSilentBox® SB and SlimVent SVS

SlimVent SVS

286

372 220

390

111 48

ø 200

368

Dim. in mm

Ultra low profile. Ideal for applications withlimited installation space. With sound-insulatingmineral wool lining for particularly noise-free operation.

Virtually noise-free with high air flow volumes againsthigh resistances. Ideal for maintenance and cleaning.

SilentBox® SB

Dim. in mm

� Similarities SB and SVS� InstallationInstallation in any position with-out restriction – horizontally, ver-tically or pitched – suitable forintake or extract (Exception:SVS must not be installed withthe swing-out motor-impellerunit facing upward).

� MotorTotally enclosed external rotormotor with ball bearings, im-pregnated windings insulationclass F, designed for continuousoperation, maintenance free andinterference-free.

� Specification SilentBox®� Casing Like an internal attenuator.Acoustically lined with abrasiveresistant 50 mm thick mineralfibreboard. Four quick releaseclamps permit easy access tomotor scroll and impeller set.Swing out motor and impeller.

Spigots on intake and exhausttwin-seal rubber gaskets fitstandard ducts. All parts manu-factured from galvanised sheetsteel.

� ImpellerWith backward curved high-quality polymer blades. Inflowvia inlet cone.

� Electrical connectionTerminal box (IP 54) is suppliedwith a 60 cm long electric cable.

� Motor protectionWith thermal contacts wired inseries with the windings. To re-set the thermal contacts themain supply must be switchedoff and on.

� Speed control Stepless 0 – 100 % using elec-tronic controller or 5 step trans-former controller (see table).

� Protection classIP 44

� Specification SlimVent SVS � CasingExtremely flat casing in longerdesign with more than 50 mmthick sound-absorbing mineralwool lining and glass fibre sur-face. The acoustic box which isplaced in front of the fan reducesthe sound level for the intakesignificantly. The sound pressurelevel is reduced to a smaller ex-tent (see sound levels in the ta-bles above the performancecurves).

� The swing out motor and im-peller unit permits maintenanceand cleaning without disassem-bly of system components. Theswing-out range must be con-sidered for the inspection flap.

� Impeller Energy-saving centrifugal im-peller with backward curvedblades from high quality poly-mer. Dynamically balanced forlow noise operation.

� Electrical connection Terminal box (IP 54) mounted onrunning cable.

� Motor protection With thermal contacts wired inseries with the windings whichautomatically reset after cooling.

� Speed controlStepless 0 – 100 % by use ofelectronic controller or 5 steptransformer controller (seetable).

� Protection class When installed in ducting the fanis rated IP 44.

* In noise relevant cases, transformer controllers must be provided. An electronic controller can trigger a distracting magnetisation noise.

Type Ref. no. Air flow R.P.M. Sound press. Motor Current Wiring max. air flow temp. Weight Transformer- Electronic* volume case power full diagram full net speed controller speed controller, stepless (FID) breakout load control load control approx. 5-step flush / surface

.V m3/h min-1 db(A) in 1m W A A No. +°C +°C kg Type Ref. no. Type Ref. no.

Type SilentBox® SB, 1 ph. motor, 230 V, 50 Hz, capacitor motor, IP 33

SB 200 C 9510 810 2520 44 105 0.46 0.46 508 70 70 19.0 TSW 1,5 1495 ESU 1 / ESA 1 0236 / 0238

SB 200 D 9564 1030 2700 48 160 0.69 0.83 508 70 50 19.7 TSW 1,5 1495 ESU 1 / ESA 1 0236 / 0238

Type SVS, 1 ph. motor, 230 V, 50 Hz, capacitor motor, IP 33

SVS 200 K 0132 940 2710 55 163 0.71 0.83 508 70 50 9.2 TSW 1,5 1495 ESU 1 / ESA 1 0236 / 0238

� Information PageTechn. description 296Selection chart 297Information for planning 10 onModular system 294

Page 20: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

363

In-li

nefa

ns

Centrifugal in-line fans Acoustic Line 200 mm øSilentBox® SB and SlimVent SVS

� Accessories

Flexible sleeveType FM 200 Ref. no. 1670Supplied with two hose clips asstandard; for installation betweenfan and duct system. Preventssound and vibration transmissionto ducting and corrects small site misalignments. For intake or ex-tract two sleeves are needed forcomplete isolation.

Gravity shutterType VK 200 Ref. no. 0758Automatic made from polymer,light grey.

Fixed grilleType RAG 200 Ref. no. 0750For covering air inlets and outletson facades. Made from polymer,light grey.

GuardType SGR 200 Ref. no. 5066For intake and extract installation.Made from galvanised steel.

Backdraught shutterType RSK 200 Ref. no. 5074Automatic, made from metal.

Flexible circular attenuatorType FSD 200 Ref. no. 0679Spigotted aluminium attenuatorwith 50 mm insulation. Length 1 m.

Air filter boxLFBR 200 G4 Ref. no. 8579LFBR 200 F7 Ref. no. 8533Air filter with large surface area forinstallation in ducting.

Electric heater batteryEHR-R 1,2/200 1,2 kW No. 9436EHR-R 2/200 2,0 kW No. 9437EHR-R 5/200 5,0 kW No. 8711– with integrated temp. controlEHR-R 5/200 TR 5,0 kW No. 5295Room or duct sensor (TFK/TFR,accessories) required.

Temperature control system for electric heater battery EHR-RType EHS Ref. no. 5002

Warm water heater batteryType WHR 200 Ref. no. 9482Compact heat exchanger for in-line installation.

Temperature control system for warm water heater batteryType WHST 300 T38 No. 8817

� Sound levelsTotal sound power levels andthe spectrum figures in dB(A)are given for

– Sound level case breakout– Sound level intake/exhaustThe type table also shows

– Sound pressure case breakoutand intake air noise specified assound pressure in 1 m (free fieldconditions).For the SB types, it should benoted that the intake sound levelis less than the exhaust soundlevel.

V· m3/h

r = 1,20 kg/m3

SVS 200 K

DpfaPa

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 63 45 55 61 50 45 38 35 LWA Intake dB(A) 71 65 67 61 54 49 49 46 LWA Exhaust dB(A) 81 67 74 78 72 70 66 61

DpfaPa

V· m3/h

r = 1,20 kg/m3

SB 200 D

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 55 42 53 48 40 37 32 29 LWA Intake dB(A) 65 60 62 57 48 41 40 39 LWA Exhaust dB(A) 73 62 68 66 63 62 58 60

� 230 V� 170 V� 130 V � 100 V � 80 V

��

DpfaPa

V· m3/h

r = 1,20 kg/m3

SB 200 C

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 51 37 51 40 36 36 29 28 LWA Intake dB(A) 62 58 58 49 42 41 38 33 LWA Exhaust dB(A) 69 59 65 61 57 60 56 49

� 230 V� 170 V� 130 V � 100 V � 80 V

��

� Accessory details Page

Filters, heater batteries and attenuators 421 onTemperature control systemsfor heater batteries 427, 431 onFlexible ventilation ducting,Grilles, adaptors,roof terminations 487 onValves 508 onSpeed controllers,switches 525 on

Page 21: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

364

250 mm ø Centrifugal in-line fans Acoustic LineSilentBox® SB

Virtually noise-free with high air flow volumes againsthigh resistances. Ideal for maintenance and cleaning.

SilentBox® SB 250 E

Dim. in mm

� SimilaritiesSB 250 C and E

� InstallationInstallation in any position with-out restriction – horizontally, ver-tically or pitched – suitable forintake or extract.

� MotorTotally enclosed external rotormotor with ball bearings, im-pregnated windings insulationclass F, designed for continuousoperation, maintenance free andinterference-free.

� Motor protectionWith thermal contacts wired inseries with the windings. To re-set the thermal contacts themain supply must be switchedoff and on.

� Speed controlStepless 0 – 100 % by use ofelectronic controller or 5 steptransformer controller (seetable).

� Electrical connectionTerminal box (IP 54) is suppliedwith a 60 cm long electric cable.

� Protection classIP 44.

� Specification SB 250 C� CasingLike an internal attenuator.Acoustically lined with abrasiveresistant 50 mm thick mineralfibreboard. For quick releaseclamps permit easy access tomotor scroll and impeller set.Extractable motor and impellerunit. Spigots on intake and ex-haust twin-seal rubber gasketsfit standard ducts. All partsmanufactured from galvanisedsheet steel.

� ImpellerLow noise forward curved cen-trifugal impeller, housed withinan aero dynamically shapedscroll from galvanised steel.Bell mouth shaped inlet ring toachieve optimum air flow.

� Specification SB 250 E� CasingAcoustically lined with abrasiveresistant 50 mm thick mineralfibreboard. Four quick releaseclamps permit easy access tomotor scroll and impeller set.Swing out motor and impellerunit. Spigots on intake and ex-haust twin-seal rubber gasketsfit standard ducts. All partsmanufactured from galvanisedsheet steel.

� ImpellerLow noise forward curved cen-trifugal impeller, housed withinan aerodynamically shapedscroll from galvanised steel.Bell mouth shaped inlet ring toachieve optimum air flow.

* In noise relevant cases, transformer controllers must be provided. An electronic controller can trigger a distracting magnetisation noise.

Type Ref. no. Air flow R.P.M. Sound press. Motor Current Wiring max. air flow temp. Weight Transformer- Electronic*volume case power full diagram full net speed controller speed controller, stepless(FID) breakout load control load control approx. 5-step flush / surface

.V m3/h min-1 db(A) in 1m W A A No. +°C +°C kg Type Ref. no. Type Ref. no.

Type SilentBox® SB, 1 ph. motor, 230 V, 50 Hz, capacitor motor, IP 44 (C), IP 33 (E)

SB 250 C 9512 960 2120 43 255 1.13 1.13 508 50 50 18.0 TSW 1,5 1495 ESU 3 / ESA 3 0237 / 0239

SB 250 E 9565 1080 2690 45 165 0.71 0.86 508 70 50 33.4 TSW 1,5 1495 ESU 1 / ESA 1 0236 / 0238

� Information PageTechn. description 296Selection chart 297Information for planning 10 onModular system 294

Virtually noise-free with high air flow volumes againsthigh resistances. Ideal for maintenance and cleaning.

SilentBox® SB 250 C

Dim. in mm

Page 22: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

365

In-li

nefa

ns

Centrifugal in-line fans Acoustic Line 250 mm øSilentBox® SB

� Accessories

Flexible sleeveType FM 250 Ref. no. 1672Supplied with two hose clips asstandard; for installation betweenfan and duct system. Preventssound and vibration transmissionto ducting and corrects small site misalignments. For intake or ex-tract two sleeves are needed forcomplete isolation.

Gravity shutterType VK 250 Ref. no. 0759Automatic made from polymer,light grey.

Fixed grilleType RAG 250 Ref. no. 0751For covering air inlets and outletson facades. Made from polymer,light grey.

GuardType SGR 250 Ref. no. 5067For intake and extract installation.Made from galvanised steel.

Backdraught shutterType RSK 250 Ref. no. 5673Automatic, made from metal.

Flexible circular attenuatorType FSD 250 Ref. no. 0680Spigotted aluminium attenuatorwith 50 mm insulation. Length 1 m.

Air filter boxLFBR 250 G4 Ref. no. 8580LFBR 250 F7 Ref. no. 8534Air filter with large surface area forinstallation in ducting.

Electric heater batteryEHR-R 6/250 6,0 kW No. 8712– with integrated temp. controlEHR-R 6/250 TR 6,0 kW No. 5296Room or duct sensor (TFK/TFR,accessories) required.

Temperature control system for electric heater battery EHR-RType EHS Ref. no. 5002

Warm water heater batteryType WHR 250 Ref. no. 9483Compact heat exchanger for in-line installation.

Temperature control system for warm water heater batteryType WHS HE Ref. no. 8319

� Sound levelsTotal sound power levels andthe spectrum figures in dB(A)are given for

– Sound level case breakout– Sound level intake/exhaustThe type table also shows

– Sound pressure case breakoutand intake air noise specified assound pressure in 1 m (free fieldconditions).It should be noted that the in-take sound level is less than theexhaust sound level.

DpfaPa

V· m3/h

r = 1,20 kg/m3

SB 250 E

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 52 38 51 44 38 33 30 28 LWA Intake dB(A) 62 55 57 47 50 46 44 46 LWA Exhaust dB(A) 73 57 69 63 65 66 61 62

� 230 V� 170 V� 130 V � 100 V � 80 V

��

� Accessory details Page

Filters, heater batteries and attenuators 421 onTemperature control systemsfor heater batteries 427, 431 onFlexible ventilation ducting,Grilles, adaptors,roof terminations 487 onValves 508 onSpeed controllers,switches 525 on

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 47 38 45 39 34 36 35 36 LWA Intake dB(A) 63 59 58 55 50 47 46 44 LWA Exhaust dB(A) 70 61 60 63 62 63 61 58

DpfaPa

V· m3/h

r = 1,20 kg/m3

SB 250 C

cm/s

* Note the necessary minimum unit resistance.

*

Page 23: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

366

315 mm ø Centrifugal in-line fans Acoustic LineSilentBox® SB and SBD

Virtually noise-free with high air flow volumes againsthigh resistances. Ideal for maintenance and cleaning.

SilentBox® SBD 315 B

Dim. in mm

Virtually noise-free with high air flow volumes againsthigh resistances. Ideal for maintenance and cleaning.

SilentBox® SB 315 and SBD 315 A

Dim. in mm

� SimilaritiesSB 315, SBD 315 A and B

� InstallationInstallation in any position with-out restriction – horizontally, ver-tically or pitched – suitable forintake or extract.

� ImpellerSB 315 and SBD 315 A withbackward curved high-qualitypolymer blades. Inflow via inletcone.SBD 315 B as described on theright.

� MotorTotally enclosed external rotormotor with ball bearings, im-pregnated windings insulationclass F, designed for continuousoperation, maintenance free andinterference-free.

� Motor protectionWith thermal contacts wired tothe terminal block and must beconnected to a motor protectionunit (see type table).

� Speed controlThrough voltage reduction bymeans of 5 step transformer orelectronic controller (stepless).

� Electrical connectionTerminal box (IP 54) is suppliedwith a 60 cm long electric cable.

� Protection classIP 54.

� SpecificationSB 315 and SBD 315 A

� CasingLike an internal attenuator.Acoustically lined with abrasiveresistant 50 mm thick mineralfibreboard. Four quick releaseclamps permit easy access tomotor scroll and impeller set.Swing out motor and impellerunit. Spigots on intake and ex-haust twin-seal rubber gasketsfit standard ducts. All partsmanufactured from galvanisedsheet steel.

� Specification SBD 315 B

� CasingLike an internal attenuator.Acoustically lined with abrasiveresistant 50 mm thick mineralfibreboard. Four quick releaseclamps permit easy access tomotor scroll and impeller set.Fan and spiral casing freely ac-cessible. Swing out motor andimpeller unit. Spigots on intakeand exhaust twin-seal rubbergaskets fit standard ducts. Allparts manufactured from gal-vanised sheet steel.

� ImpellerLow noise forward curved cen-trifugal impeller, housed withinan aerodynamically shapedscroll from galvanised steel.Bell mouth shaped inlet ring toachieve optimum air flow.

Type Ref. no. Air flow R.P.M. Sound press. Motor Current Wiring max. air flow temp. Weight Speed controller 5-stepvolume case power full diagram full net without with(FID) breakout load control load control approx. motor protection unit motor protection unit

.V m3/h min-1 db(A) in 1m W A A No. +°C +°C kg Type Ref. no. Type Ref. no.

Type SilentBox® SB, 1 ph. motor, 230 V, 50 Hz, capacitor motor, IP 54

SB 315 9515 2420 1420 51 310 1.70 1,80 536.1 60 60 45 TSW 3,0 1) 1496 — —

Type SilentBox® SBD, 3 ph. motor, 230/400 V, 50 Hz, IP 54

SBD 315 A 9718 2200 1350 47 215 0.73/0.42 0.44 860 60 60 46.0 TSD 0,8 2) 1500 RDS 1 1314

SBD 315 B 9583 2250 1290 50 640 2.40/1.40 1.40 860 60 60 43.4 TSD 3,0 2) 1502 RDS 2 13151) required full motor protection device, Type MW, No. 1579, see accessories. 2) required full motor protection device, Type MD, No. 5849, see accessories.

Page 24: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

367

In-li

nefa

ns

Centrifugal in-line fans Acoustic Line 315 mm øSilentBox® SB and SBD

� Accessories

Flexible sleeveType FM 315 Ref. no. 1674Supplied with two hose clips asstandard; for installation betweenfan and duct system. Preventssound and vibration transmissionto ducting and corrects small site misalignments. For intake or ex-tract two sleeves are needed forcomplete isolation.

Gravity shutterType VK 315 Ref. no. 0760Automatic made from polymer,light grey.

Fixed grilleType RAG 315 Ref. no. 0752For covering air inlets and outletson facades. Made from polymer,light grey.

GuardType SGR 315 Ref. no. 5068For intake and extract installation.Made from galvanised steel.

Backdraught shutterType RSK 315 Ref. no. 5674Automatic, made from metal.

Flexible circular attenuatorType FSD 315 Ref. no. 0681Spigotted aluminium attenuatorwith 50 mm insulation. Length 1 m.

Air filter boxLFBR 315 G4 Ref. no. 8581LFBR 315 F7 Ref. no. 8535Air filter with large surface area forinstallation in ducting.

Electric heater batteryEHR-R 6/315 6,0 kW No. 8713– with integrated temp. controlEHR-R 6/315 TR 6,0 kW No. 5301Room or duct sensor (TFK/TFR,accessories) required.

Temperature control system for electric heater battery EHR-RType EHS Ref. no. 5002

Warm water heater batteryType WHR 315 Ref. no. 9484Compact heat exchanger for in-line installation.

Temperature control system for warm water heater batteryType WHS HE Ref. no. 8319

� Sound levelsTotal sound power levels andthe spectrum figures in dB(A)are given for

– Sound level case breakout– Sound level intake/exhaustThe type table also shows

– Sound pressure case breakoutand intake air noise specified assound pressure in 1 m (free fieldconditions).It should be noted that the in-take sound level is less than theexhaust sound level.

DpfaPa

V· m3/h

r = 1,20 kg/m3

SBD 315 B

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 57 54 52 46 44 41 38 31 LWA Intake dB(A) 69 66 63 50 53 54 50 46 LWA Exhaust dB(A) 85 70 73 77 79 79 77 71

� 400 V� 280 V� 200 V� 140 V� 80 V

DpfaPa

V· m3/h

r = 1,20 kg/m3

SBD 315 A

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 54 51 51 37 36 31 29 28 LWA Intake dB(A) 64 62 57 41 35 35 32 29 LWA Exhaust dB(A) 70 68 64 53 53 51 50 38

� 400 V� 280 V� 200 V� 140 V� 80 V

V· m3/h

r = 1,20 kg/m3

SB 315

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 58 52 56 42 38 33 31 27 LWA Intake dB(A) 66 63 62 47 40 40 36 33 LWA Exhaust dB(A) 74 69 69 60 64 58 53 45

� 230 V� 170 V� 130 V� 100 V� 80 V

��

DpfaPa

� Accessory details Page

Filters, heater batteries and attenuators 421 onTemperature control systemsfor heater batteries 427, 431 onFlexible ventilation ducting,Grilles, adaptors,roof terminations 487 onValves 508 onSpeed controllers,switches 525 on

Page 25: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

368

355 mm and 400 mm ø centrifugal in-line fans Acoustic LineSilentBox® SB and SBD

Virtually noise-free with high air flow volumes againsthigh resistances. Ideal for maintenance and cleaning.

SilentBox® SBD 355 and SBD 400

Dim. in mm *SBD 355, SBD 400

Virtually noise-free with high air flow volumes againsthigh resistances. Ideal for maintenance and cleaning.

SilentBox® SB 355 and SB 400

Type Ref. no. Air flow R.P.M. Sound press. Motor Current Wiring max. air flow temp. Weight Speed controller 5-stepvolume case power full diagram full net without with(FID) breakout load control load control approx. motor protection unit motor protection unit

.V m3/h min-1 db(A) in 1m W A A No. +°C +°C kg Type Ref. no. Type Ref. no.

Type SilentBox® SB, 1 ph. motor, 230 V, 50 Hz, capacitor motor, IP 54

SB 355 6158 2960 1400 52 345 1.8 1.9 536.1 60 60 47.0 TSW 3,0 1) 1496 — —

SB 400 6159 3930 1320 51 500 2.3 2.5 536.1 60 60 61.0 TSW 3,0 1) 1496 — —

Type SilentBox® SBD, 3 ph. motor, 230/400 V, 50 Hz, IP 54

SBD 355 9969 3330 1310 51 1470 4.6/2.6 2.8 860 45 45 47.0 TSD 5,5 2) 1503 RDS 7 1578

SBD 400 9623 3450 1310 50 1470 4.6/2.6 2.7 860 45 45 47.0 TSD 5,5 2) 1503 RDS 7 1578

� SimilaritiesSB 355 and SB 400,SBD 355 and SBD 400

� InstallationInstallation in any position with-out restriction – horizontally, ver-tically or pitched – suitable forintake or extract.Make sure that there is free ac-cessibility to the cover. To keepsound levels inside the ventilat-ed rooms as low as possible werecommend the fan is installedas remote as possible.

� MotorTotally enclosed external rotormotor with ball bearings, im-pregnated windings insulationclass F, designed for continuousoperation, maintenance free andinterference-free.

� Motor protectionWith thermal contacts wired tothe terminal block and must beconnected to a motor protectionunit (see type table).

� Speed controlThrough voltage reduction bymeans of 5 step transformer orelectronic controller (stepless).

� Electrical connectionTerminal box (IP 54) is suppliedwith a 60 cm long electric cable.

� Protection classIP 54.

� Sound levelsSee page 367.

� SpecificationSB 355 and SB 400

� CasingLike an internal attenuator.Acoustically lined with abrasiveresistant 50 mm thick mineralfibreboard. Four quick releaseclamps permit easy access tomotor scroll and impeller set.Swing out motor and impellerunit. Spigots on intake and ex-haust twin-seal rubber gasketsfit standard ducts. All partsmanufactured from galvanisedsheet steel.

� ImpellerBackward curved high-qualitypolymer impeller. Inflow via inletcone.

� SpecificationSBD 355 and SBD 400

� CasingLike an internal attenuator.Acoustically lined with abrasiveresistant 50 mm thick mineralfibreboard. Four quick releaseclamps permit easy access tomotor scroll and impeller set.Fan and spiral casing freely ac-cessible. Swing out motor andimpeller unit. Spigots on intakeand exhaust twin-seal rubbergaskets fit standard ducts. Allparts manufactured from gal-vanised sheet steel.

� ImpellerLow noise forward curved cen-trifugal impeller, housed withinan aerodynamically shapedscroll from galvanised steel.Bell mouth shaped inlet ring toachieve optimum air flow.

Dim. in mm *SB 355, SB 400

1) required full motor protection device, Type MW, No. 1579, see accessories. 2) required full motor protection device, Type MD, No. 5849, see accessories.

Page 26: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

369

In-li

nefa

ns

Centrifugal in-line fans Acoustic Line 355 and 400 mm øSilentBox® SB and SBD

� Accessories

Flexible sleeveType FM 355 Ref. no. 1675Type FM 400 Ref. no. 1676Supplied with two hose clips asstandard; for installation betweenfan and duct system. Preventssound and vibration transmissionto ducting and corrects small site misalignments. For intake or ex-tract two sleeves are needed forcomplete isolation.

Gravity shutterType VK 355 Ref. no. 0761Type VK 400 Ref. no. 0762Automatic made from polymer,light grey.

Fixed grilleType RAG 355 Ref. no. 0753Type RAG 400 Ref. no. 0754For covering air inlets and outletson facades. Made from polymer,light grey.

Backdraught shutterType RSK 355 Ref. no. 5650Type RSK 400 Ref. no. 5651Automatic, made from metal.

Flexible circular attenuatorType FSD 355 Ref. no. 0682Type FSD 400 Ref. no. 0683Spigotted aluminium attenuatorwith 50 mm insulation. Length 1 m.

Air filter boxLFBR 355 G4 Ref. no. 8583LFBR 355 F7 Ref. no. 8536LFBR 400 G4 Ref. no. 8582LFBR 400 F7 Ref. no. 8537Air filter with large surface area andcapacity for installation in ducting.Connections with double lip seals,adapted to standard Ø.

Electric heater batteryEHR-R 9/355 9,0 kW No. 8656EHR-R 9/400 9,0 kW No. 8657– with integrated temp. controlEHR-R 9/355 TR 9,0 kW No. 5297EHR-R 9/400 TR 9,0 kW No. 5299Room or duct sensor (TFK/TFR,accessories) required.

Temperature control system for electric heater battery EHR-RType EHSD 16 Ref. no. 5003

Warm water heater batteryType WHR 355 Ref. no. 8790Type WHR 400 Ref. no. 9524

Temperature control system for warm water heater batteryType WHS HE Ref. no. 8319

DpfaPa

V· m3/h

r = 1,20 kg/m3

SB 355

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 59 53 58 44 38 33 30 27 LWA Intake dB(A) 70 69 63 48 43 42 38 34 LWA Exhaust dB(A) 75 71 71 62 65 61 55 48

� 230 V� 170 V� 130 V� 100 V� 80 V

��

DpfaPa

V· m3/h

r = 1,20 kg/m3

SBD 400

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 57 50 54 48 47 44 41 34 LWA Intake dB(A) 72 68 65 53 58 59 55 50 LWA Exhaust dB(A) 91 77 80 79 86 86 84 77

� 400 V� 280 V� 200 V � 140 V � 80 V

��

DpfaPa

V· m3/h

r = 1,20 kg/m3

SBD 355

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 58 51 55 46 46 44 42 35 LWA Intake dB(A) 72 68 64 53 58 61 59 57 LWA Exhaust dB(A) 87 71 75 77 80 82 80 74

� 400 V� 280 V� 200 V� 140 V� 80 V

��

DpfaPa

V· m3/h

r = 1,20 kg/m3

SB 400

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 58 54 55 45 39 36 33 29 LWA Intake dB(A) 69 66 62 54 47 44 39 37 LWA Exhaust dB(A) 75 70 70 62 67 61 57 49

� 230 V� 170 V� 130 V� 100 V� 80 V

Page 27: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

372

Rectangular centrifugal fansSelection chart

Sound press. Sound press. Air flow volumes V m3/h against static pressurebreakout intake

Type LPA dB(A) LPA dB(A) (DPfa) in Pa

in 4 m in 4 m 0 50 100 150 200 250 300 350 400 500 600 700 800

KV – with forward curved impellers KVW 200/4/40/20 37 49 920 890 850 800 750 40

KVD 200/4/40/20 36 50 1130 1030 930 830 710

KVD 225/4/50/25 43 52 1920 1820 1710 1590 1460 1290 1040

KVD 250/4/50/30 42 56 2110 1970 1810 1610 1320

KVD 280/4/60/30 45 59 3930 3780 3620 3470 3310 3150 2990 2820 2620 2000

KVD 315/4/60/35 48 61 4400 4230 4060 3870 3430 2700

KVD 355/4/70/40 54 67 5580 5440 5300 4960 4540 3920

KVD 355/6/70/40 42 53 4970 4680 4380 4060 3680 3190

KVD 355/8/70/40 35 47 4790 4410 4000 3520 2850

KVD 400/6/80/50 45 60 7620 7320 7020 6710 6390 6060 5690 5290 4800 1460

KVD 400/8/80/50 38 51 5140 4670 4150 3420

KVD 450/6/100/50 50 60 8170 7850 7500 6630 5220

KVD 450/8/100/50 46 56 7290 6880 6420 5860 5120 3980

KR EC – with backward curved impellers / SKR EC – with sound isolated casing KRW EC 180/30/15 44 58 660 620 590 550 520 480 440 410 360 240 70

KRW EC 225/40/20 46 60 1430 1280 1130 1010 920 830 750 660 590 440 290 120

KRW EC 315/50/25 44 56 1410 1320 1190 1060 970 870 780 700 630 480 340 190

KRW EC 355/60/30 46 58 3110 3000 2870 2730 2590 2430 2260 2020 1750

KRW EC 400/60/35 56 66 4460 4360 4250 4140 4020 3890 3760 3630 3500 3230 2890 2500 1950

KRW EC 450/70/40 46 59 5450 5210 4970 4740 4480 4210 3960 3670 3380 2580 1570

KRD EC 450/70/40 54 67 7480 7310 7080 6860 6650 6450 6200 5970 5750 5300 4820

KRD EC 500/80/50 A 51 62 8810 8520 8230 7940 7630 7260 6890 6560 6120 5300 4170 2590

KRD EC 500/80/50 B 60 69 10400 10210 10010 9810 9600 9390 9180 8970 8760 8260 7720 7170 6570

KRD EC 560/100/50 A 54 62 11270 10840 10410 10000 9630 9270 8890 8480 8010 6990 5340 1190

KRD EC 560/100/50 B 60 69 14410 14120 13830 13530 13230 12950 12670 12410 12130 11550 10970 10360 9620

SKRW EC 315/50/25 47 54 2600 2500 2400 2270 2140 2020 1860 1720 1500 1040

SKRW EC 355/60/30 51 58 3950 3840 3720 3590 3480 3370 3250 3120 3000 2750 2460 2070 580

SKRW EC 400/60/35 51 56 4200 4100 4000 3890 3760 3620 3480 3330 3170 2880 2560 1990

SKRW EC 450/70/40 45 54 5420 5130 4900 4620 4330 4050 3770 3420 3060 2280 1010

SKRD EC 355/60/30 52 60 4550 4450 4360 4230 4125 4030 3920 3830 3710 3500 3280 3030 2695

SKRD EC 400/60/35 51 58 5000 4880 4760 4630 4510 4380 4250 4160 3940 3630 3340 3060 2750

SKRD EC 450/70/40 A 51 59 7500 7290 7120 6820 6590 6360 6110 5930 5620 5200 4710 4200 3320

SKRD EC 500/80/50 A 48 56 8600 8250 7910 7540 7190 6830 6450 6070 5660 4770 3270

SKRD EC 500/80/50 B 55 61 10650 10400 10160 9920 9710 9440 9210 8980 8720 8240 7670 7000 6280

SKRD EC 560/100/50 A 48 56 10070 9740 9410 9080 8720 8310 7870 7420 6890 5700 3990

SKRD EC 560/100/50 B 56 60 13700 13450 13190 12920 12650 12370 12090 11810 11540 10980 10410 9750 8990

KR – with backward curved impellers / SKR – with sound isolated casing KRW 180/2/30/15 37 51 540 480 420 360 280 210 110

KRW 225/2/40/20 40 52 1020 920 820 700 590 490 380 260 100

KRW 225/2/50/25 45 52 1160 1100 1040 990 910 850 780 690 610 340 60

KRW 315/4/50/25 39 51 1760 1580 1390 1110 840 370

KRW 355/4/60/35 42 55 3600 3370 3130 2900 2590 2090 1330 570

KRW 400/4/70/40 44 54 4970 4710 4400 4110 3730 3320 2750 2090 1160

KRW 450/4/70/40 51 59 6650 6360 6010 5710 5430 5120 4730 4280 3850 2290

KRW 500/4/80/50 52 62 9700 9380 9040 8670 8310 7920 7460 6890 6260 4590 2290

KRD 355/4/60/35 37 50 2840 2640 2410 2110 1860 1510 1050 450

KRD 450/4/70/40 47 57 5830 5570 5320 5060 4810 4550 4230 3930 3610 2840 1840

KRD 500/4/80/50 A 52 58 8430 8120 7810 7490 7110 6670 6300 5870 5420 4530 3560 1330

KRD 560/6/80/50 41 53 7460 6940 6300 5630 5110 4290 3490 2410 400

KRD 560/4/80/50 55 66 11970 11630 11260 10870 10480 10080 9640 9140 8620 7230 5470 2920 840

KRD 630/6/100/50 44 55 8740 8280 7700 7140 6440 5750 5060 4310 3370 920

KRD 630/4/100/50 55 66 12100 11800 11510 11230 10940 10640 10320 9980 9620 8810 7760 6210 4620

SKRW 315/4/50/25 34 43 1770 1620 1400 1170 650

SKRW 355/4/60/35 39 49 3580 3350 3070 2830 2450 1880 110

SKRW 400/4/70/40 42 49 4940 4540 4230 3830 3470 3040 2460 1670 780

SKRW 500/4/80/50 48 52 9540 9130 8640 8130 7630 7130 6640 6020 5520 4020

SKRD 355/4/60/35 34 43 2800 2510 2270 2030 1670 1300 650 140

SKRD 450/4/70/40 46 52 5430 5230 5000 4770 4520 4240 4000 3640 3290 2380 860

SKRD 500/6/70/40 36 48 4620 4230 3800 3480 2980 2490 1490

SKRD 500/4/80/50 48 54 8050 7830 7520 7060 6650 6210 5820 5450 5040 4150 2560 690

SKRD 560/6/80/50 36 46 7600 6990 6220 5630 5040 4280 3220 1810 400

SKRD 630/6/100/50 43 52 8450 8010 7450 6900 6230 5490 4750 3780 2670

This chart is enables the easy selection of rectangular fans by combiningthe parameters of static pressure increase Dpfa, case breakout and intake

air sound levels as sound pressure levels at 4 m (free field conditions).

Page 28: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

373

Rect

angu

lar

fans

Rectangular centrifugal fansProduct specific information

For complete information seethe “general technical infor-mation” and descriptions onthe product pages.

� Position, installation anddrainage holesModels can be installed in anyposition, however types KRmust be installed with the in-spection flap facing downwardsor to the side. The swing-outareas need to be cleared andaccessed easily for service andmaintenance.If condensation occurs (e.g.ntermittent operation, high hu-midity or varying temperatures)the fan must be installed in away that the condensation candrain off unhindered.Additional holes may have to bedrilled into the casing at the ap-propriate positions. Alternatively,the duct system may have to beinsulated to avoid condensation.

� Noise/vibration transmissionTo be prevented from ductingand building. Therefore, the fanshould be secured with soundinsulation and connected flexiblyto the ducting.For this, see VS accessories.

� Explosion proof modelsWith regards to operating condi-tions and norms please refer tochapter “Information for planning– explosion proof”. The ex-pro-tected types correspond to unitgroup II, category 2G for opera-tion in zone 1 and 2 pursuant toDirective 2014/34/EU (ATEX).The motors of the KVD Ex rangeare equipped with positive tem-perature coefficient (PTC) ther-mistors (to monitor the tempera-ture of windings) as standard.They are prewired to the termi-nal board and must be connect-ed to the motor protection trip-ping unit MSA.This makes the KVD Ex fanssuitable for speed control thatcan be carried out via TSD orTSSD transformer controllers.The minimum voltage should notdrop below 100 V.Electronic speed control or reg-ulation by means of a frequencyinverter are not permitted.

� Motor - ImpellerAll AC types incorporate a motorwith external rotor motor pro-tected to IP 44 or IP 54 withinthe air flow. They conform toDIN EN 60034 / VDE 0530 andDIN EN 60335-1 / VDE 0700-1with an insulation class F, plusmoisture protection.The EC types are equipped withenergy-saving, speed-control-lable EC external rotor motorsprotected to IP 44 or IP 54 forthe lowest operating costs.

All motors are maintenance free,interference-free, speed control-lable and suitable for continuousoperation.The ball bearings are greasedfor life.The centrifugal impellers arepressed onto the rotating part ofthe motor body and dynamicallybalanced to DIN ISO 1940 T.1 –class 6.3 as one unit.

� Speed controlAll InlineVent® AC rectangularfans are speed controllable viavoltage reduction of 0 – 100 %.Thereby the operating level canbe adapted to the required airflow volume. Our speed con-trollers are suitable to controlvarious fans (one or more) up totheir maximum nominal output.When selecting a controller notshown on the chart, allow for a10 % safety margin.It is possible to control 3 ph.-fansthrough frequency inverter by on-site installation of sine filters be-tween inverter and motor.All EC types are steplessly con-trollable via speed-potentiome-ter. Regulation is also possiblevia three-step switch or step-lessly via universal control sys-tem or electronic differentialpressure/temperature controller.For example, the performancelevels are shown on the charac-teristic curve.

� Air flow directionThe air flow direction of centrifu-gal fans is fixed and cannot bereversed; but it can be specifiedin all units through the installa-tion method. The rotational di-rection and the direction of airflow are marked with arrows onthe units and must be checkedwhen installing.

� Incorrect direction of rotationIf the fan is operated in the in-correct direction of rotation theAC motor will be overloadedand the thermal contacts willtrip. Typical indication of this is avirtually low fan efficiency com-bined with high noise levels andvibration.

� Air flow temperatureAll models are applicable in therange of – 40 °C to at least+ 60 °C, types KV Ex from– 20 °C to +40 °C.The upper temp. threshold valuevaries between the models andcan be found at the relatedcharts on the individual productpage.

� KVCentrifugal rectangular fans withforward curved impeller paddlesand swing-out motor impellerunit. Low-noise centrifugal im-pellers in volute casing for highpressure levels.

V.

= 920 – 8500 m3/h.Compact and flat design for ver-satile usage in exhaust and freshair systems in commercial andindustrial applications.

The models and their specifications

� KR and KR ECRectangular fans with backwardcurved impeller paddles, withoptional energy-saving EC motortechnology. High performancecentrifugal impellers with highefficiency. Swing-out motor im-peller unit.

V.

= 540 – 14 410 m3/h.For conveying higher volume flowrates in extract and fresh air sys-tems.Uncritical in extraction of pollutedair.

� SKR and SKR ECHigh performance centrifugalimpellers (backward curved) insound insulated casing withgood damping characteristicsfor noise-critical applications,with optional energy-saving ECmotor technology. Performancefigures similar to KR.

V.

= 1770 – 13 700 m³/h.For further reduction of intakeand exhaust air noise levels,rectangular attenuators (KLF,accessory) are recommended.Exhaust and fresh air fans forapplications with specific noiselevel requirements.

Page 29: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

374

200 mm ø InlineVent® Rectangular fansforward curved, for rectangular duct size 40 x 20 cm

70 70

KVW 200/4/40/20 5675 925 810 37 0.21 0,95 508 60 50 11 TSW 1,5 1495 — — — —

Speed controller 5-step without with motor protect. unit motor protect. unit

Motor full protectiondevice to connect

built-in thermal contacts

Type Ref. no. Air flowvolume, freedischarge

NominalR.P.M.

Sound press.case

breakout

Power consumption Wiringdiagram

Max. air flowtemperature at

Nom. vol. Control

Weightnet

approx.

Type Ref. no. Type Ref. no.V· m3/h min-1 dB(A) in 4 m kW A No. +°C +°C kg Type Ref. no.

KVD 200/4/40/20 5676 1130 1260 36 0.25 0,82/0,47 860 8,6 TSD 0,8 1500 RDS 1 1314 MD 5849

1-phase motor, 230 V, 50 Hz, capacitor motor, protection to IP 44

3-phase motor, 230/400 V, 50 Hz, protected to IP 44

Rectangular centrifugal fan withforward curved impeller bladesand swing-out motor impellerunit.

� Low-noise centrifugal impellersin aerodynamic galvanised steelcasing for high pressure levels.

� Compact and flat design for usein extract and fresh air systemsin commercial and industrial ap-plications.

� Specification� Casing

Made of galvanised steel andflanged on both ends. Spacesaving, compact design.

� Easy to clean and servicethanks to the swing-out motorimpeller unit.

� ImpellerForward curved centrifugal im-peller made of galvanised steel,highly efficient with low noiselevels. Aerodynamically opti-mised casing; intake air flow bymeans of an inlet nozzle.

� MotorTotally enclosed, maintenance-free external rotor motor with di-rectly fitted impeller, protected toIP 44.Windings with protection againstmoisture. Ball bearing mountedand interference-free.Dynamically balanced with

resilient motor mounting bracketfor low vibration and low noiseoperation.

� Electrical connectionTerminal box (IP 55 for 3 ph.- orIP 44 for 1 ph.-types) is mount-ed with a permanently attachedcable.

� Motor protectionModel KVW through thermalcontacts which are connected inseries with winding and auto-matically resets. Model KVDthrough built-in thermal contactswhich must be connected to amotor full protection device.

� Speed controlBy voltage reduction using a5 speed transformer controller(recommended) or an electroniccontroller (stepless). The perfor-mance figures at correspondingvoltages are given in the perfor-mance curve.

� Sound LevelsAbove the performance curve,total values and spectrum aregiven for:

– Sound level case breakout– Sound level intake– Sound level exhaust

The sound power level (on in-take) is additionally shown withinthe performance curve for corre-sponding control voltages.In the table below you can alsofind:

– Case breakout sound level at4 m (free field conditions).

� InstallationPossible in any position.Attention should be paid toaccessibility/swing out.

KV

� Note PageSelection chart 372Technical description 373Design guidelines 10 onModul. system components 370Dim. in mm

Swing-out area

Page 30: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

375

Rect

angu

lar

fans

InlineVent® Rectangular fans 200 mm ø forward curved, for rectangular duct size 40 x 20 cm

� Accessories

Gravity shutterType VK 40/20 Ref. no. 0874External airflow operated gravityshutter made of polymer, light grey.

External louvresType WSG 40/20 Ref. no. 0109Robust construction made ofaluminium extrusion profile, naturalcolour anodised.

Volume control damper forductingType JVK 40/20 Ref. no. 6910Casing made with flanges on bothsides. The control mechanism isoutside the airstream. For electricaldrive, see STM, accessory.

Circular spigotType FSK 40/20 Ref. no. 0832For cost effective adaption ofrectangular fans into circularducting systems with Ø 200 mm.

Flexible connectorsType VS 40/20 Ref. no. 5694Flexible in-duct connector withflanges on both sides.

CounterflangeType GF 40/20 Ref. no. 6919Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 40/20 Ref. no. 8728For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 40/20 G4 No. 8720Type KLF 40/20 F7 No. 8644Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Electric heater batteryType EHR-K 6/40/20 No. 8702Type EHR-K 15/40/20 No. 8703Heating elements enclosed in agalvanised steel casing withconnecting flanges on both sides.

Temperature control system forelectric heater batteryType EHSD 16 Ref. no. 5003

Warm water heater batteryType WHR 2/40/20 No. 8782Type WHR 4/40/20 No. 8783For in-duct installation.

Temperature control system forwarm water heater batteryType WHS HE Ref. no. 8319

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 56 45 52 51 48 45 43 37 LWA Intake dB(A) 70 65 65 62 58 58 59 54 LWA Exhaust dB(A) 77 68 70 68 68 70 68 64

V· m3/h

DpfaPa

r = 1,20 kg/m3

� 400 V� 280 V� 200 V � 140 V � 80 V

DpfaPa

V· m3/h

r = 1,20 kg/m3

��

� 230 V� 170 V� 130 V � 100 V � 80 V

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 57 46 52 50 52 45 40 32 LWA Intake dB(A) 69 64 64 61 55 56 54 47 LWA Exhaust dB(A) 72 63 65 65 64 63 62 55

KVW 200/4/40/20

KVD 200/4/40/20

� Accessory details PageShutters, grilles andlouvres 420, 487 onFilters, heaters andattenuators 421 onTemperature controlsystems for heaters 427, 432 onSpeed controllers and motorfull protection devices 525 on

69

64

6260

53

70

63

67

59

49

Page 31: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

376

225 mm ø InlineVent® Rectangular fansforward curved, for rectangular duct size 50 x 25 cm

65 60

KVD 225/4/50/25 Ex 6810 1900 1280 43 0.53 0.92 899 40 40 17 TSD 1,5 1501 — — MSA 1289

Dim. in mm

Speed controller 5-step without with motor protect. unit motor protect. unit

Motor full protectiondevice to connect

built-in thermal contacts

Type Ref. no. Air flowvolume, freedischarge

NominalR.P.M.

Sound press.case

breakout

Power consumption Wiringdiagram

Max. air flowtemperature at

Nom. vol. Control

Weightnet

approx.

Type Ref. no. Type Ref. no.V· m3/h min-1 dB(A) in 4 m kW A No. +°C +°C kg Type Ref. no.

KVD 225/4/50/25 5679 1950 1270 43 0.54 1.6/0.93 860 17 TSD 1,5 1501 RDS 2 1315 MD 5849

3 ph. motor, 230/400 V, 50 Hz, protection to IP 44

Explosion-proof Ex e II, temperature class T1 – T3, 3-phase 400 V, 50 Hz, protection to IP 44

Rectangular centrifugal fan withforward curved impeller bladesand swing-out motor impellerunit.

� Low-noise centrifugal impellersin aerodynamic galvanised steelcasing for high pressure levels.

� Compact and flat design for usein extract and fresh air systemsin commercial and industrial ap-plications.

� Specification� Casing Made of galvanised steel and

flanged on both ends. Spacesaving, compact design.

� Easy to clean and servicethanks to the swing-out motorimpeller unit.

� Impeller Forward curved centrifugal im-

peller made of galvanised steel,highly efficient with low noiselevels. Aerodynamically opti-mised casing; intake air flow bymeans of an inlet nozzle.

� Motor Totally enclosed, maintenance-

free external rotor motor with di-rectly fitted impeller, protected toIP 44.

Windings with protection againstmoisture. Ball bearing mountedand interference-free.

Dynamically balanced with re-silient motor mounting bracketfor low vibration and low noiseoperation.

� Electrical connection Terminal box (IP 55 for 3 ph., IP 65 for explosion-proof types)

is mounted with permanently at-tached cable.

� Motor protection Through built-in thermal con-

tacts which must be connectedto a motor full protection device.

� Speed control By voltage reduction using a 5 speed transformer controller

(recommended) or an electroniccontroller (stepless). The perfor-mance figures at correspondingvoltages are given in the perfor-mance curve.

� Sound Levels Above the performance curve,

total values and spectrum aregiven for:

– Sound level case breakout– Sound level intake– Sound level exhaust The sound power level (on in-

take) is additionally shown withinthe performance curve for corre-sponding control voltages.

In the table below you can alsofind:

– Case breakout sound level at 4 m (free field conditions).

� Installation Possible in any position. Attention should be paid to accessibility/swing out.

� Explosion-proof modelsThermal motor protectionthrough built-in PTC (positivetemperature coefficient) thermis-tors which must be connectedto a tripping unit MSA. Usingthis motor protection enablesthe speed control where a mini-mum voltage of 100 V must bemaintained.

KV

� Note PageSelection chart 372Technical description 373Design guidelines 10 onModul. system components 370

Page 32: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

377

Rect

angu

lar

fans

InlineVent® Rectangular fans 225 mm ø forward curved, for rectangular duct size 50 x 25 cm

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 63 47 56 56 57 55 51 44 LWA Intake dB(A) 72 64 66 62 63 65 64 58 LWA Exhaust dB(A) 78 63 66 69 73 72 71 65

V· m3/h

DpfaPa r = 1,20 kg/m3

��

� 400 V� 280 V� 200 V � 140 V � 80 V

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 63 43 56 57 58 54 49 43 LWA Intake dB(A) 73 65 66 62 63 65 65 60 LWA Exhaust dB(A) 79 63 67 70 73 73 72 67

V.

m3/h

DpfaPa r = 1,20 kg/m3

��

� 400 V� 280 V� 200 V� 140 V� 100 V

KVD 225/4/50/25

KVD 225/4/50/25 Ex

72

67

69

64

58

72

67

69

64

60

� Accessories

Gravity shutterType VK 50/25 Ref. no. 0875External airflow operated gravityshutter made of polymer, light grey.

External louvresType WSG 50/25 Ref. no. 0110Robust construction made ofaluminium extrusion profile, naturalcolour anodised.

Volume control damper forductingType JVK 50/25 Ref. no. 6911Casing made with flanges on bothsides. The control mechanism isoutside the airstream. For electricaldrive, see STM, accessory.

Circular spigotType FSK 50/25 Ref. no. 0833For cost effective adaption ofrectangular fans into circularducting systems with Ø 250 mm.

Flexible connectorsType VS 50/25 Ref. no. 5695Flexible in-duct connector withflanges on both sides.– for Ex-fansType VS 50/25 Ex Ref. no. 0265

CounterflangeType GF 50/25 Ref. no. 6920Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 50/25-30 No. 8729For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 50/25-30 G4 No. 8721Type KLF 50/25-30 F7 No. 8645Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Electric heater batteryType EHR-K 8/50/25-30 No. 8704Type EHR-K 24/50/25-30 No. 8705Heating elements enclosed in agalvanised steel casing withconnecting flanges on both sides.

Temperature control system forelectric heater batteryType EHSD 16 Ref. no. 5003

Warm water heater batteryType WHR 2/50/25-30 No. 8784Type WHR 4/50/25-30 No. 8785For in-duct installation.

Temperature control system forwarm water heater batteryType WHS HE Ref. no. 8319

� Accessory details PageShutters, grilles andlouvres 420, 487 onFilters, heaters andattenuators 421 onTemperature controlsystems for heaters 427, 432 onSpeed controllers and motorfull protection devices 525 on

Page 33: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

378

250 mm ø InlineVent® Rectangular fansforward curved, for rectangular duct size 50 x 30 cm

Speed controller 5-step without with motor protect. unit motor protect. unit

Motor full protectiondevice to connect

built-in thermal contacts

Type Ref. no. Air flowvolume, freedischarge

NominalR.P.M.

Sound press.case

breakout

Power consumption Wiringdiagram

Max. air flowtemperature at

Nom. vol. Control

Weightnet

approx.

KVD 250/4/50/30 Ex 6811 2300 1240 42 0.74 1.5 899 40 40 21 TSD 1,5 1501 — — MSA 1289

Dim. in mm

Type Ref. no. Type Ref. no.V· m3/h min-1 dB(A) in 4 m kW A No. +°C +°C kg Type Ref. no.

KVD 250/4/50/30 5682 2200 1260 42 0.72 2.5/1.5 860 60 60 21 TSD 1,5 1501 RDS 2 1315 MD 5849

3-phase motor, 230/400 V, 50 Hz, protected to IP 44

Explosion-proof Ex e II, temperature class T1 – T3, 3-phase 400 V, 50 Hz, protection to IP 44

Rectangular centrifugal fan withforward curved impeller bladesand swing-out motor impellerunit.

� Low-noise centrifugal impellersin aerodynamic galvanised steelcasing for high pressure levels.

� Compact and flat design for usein extract and fresh air systemsin commercial and industrial ap-plications.

� Specification� Casing Made of galvanised steel and

flanged on both ends. Spacesaving, compact design.

� Easy to clean and servicethanks to the swing-out motorimpeller unit.

� Impeller Forward curved centrifugal im-

peller made of galvanised steel,highly efficient with low noiselevels. Aerodynamically opti-mised casing; intake air flow bymeans of an inlet nozzle.

� Motor Totally enclosed, maintenance-

free external rotor motor with di-rectly fitted impeller, protected toIP 44.

Windings with protection againstmoisture. Ball bearing mountedand interference-free.

Dynamically balanced with re-silient motor mounting bracketfor low vibration and low noiseoperation.

� Electrical connection Terminal box (IP 55 for 3 ph., IP 65 for explosion-proof types)

is mounted with permanently at-tached cable.

� Motor protection Through built-in thermal con-

tacts which must be connectedto a motor full protection device.

� Speed control By voltage reduction using a 5 speed transformer controller

(recommended) or an electroniccontroller (stepless). The perfor-mance figures at correspondingvoltages are given in the perfor-mance curve.

� Sound Levels Above the performance curve,

total values and spectrum aregiven for:

– Sound level case breakout– Sound level intake– Sound level exhaust The sound power level (on in-

take) is additionally shown withinthe performance curve for corre-sponding control voltages.

In the table below you can alsofind:

– Case breakout sound level at 4 m (free field conditions).

� Installation Possible in any position. Attention should be paid to accessibility/swing out.

� Explosion-proof modelsThermal motor protectionthrough built-in PTC (positivetemperature coefficient) thermis-tors which must be connectedto a tripping unit MSA. Usingthis motor protection enablesthe speed control where a mini-mum voltage of 100 V must bemaintained.

KV

� Note PageSelection chart 372Technical description 373Design guidelines 10 onModul. system components 370

Page 34: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

379

Rect

angu

lar

fans

InlineVent® Rectangular fans 250 mm ø forward curved, for rectangular duct size 50 x 30 cm

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 62 48 56 54 57 54 52 45 LWA Intake dB(A) 76 69 68 63 67 70 68 63 LWA Exhaust dB(A) 81 68 71 72 76 74 74 69

V· m3/h

DpfaPa

r = 1,20 kg/m3

� 400 V� 280 V� 200 V � 140 V � 80 V

Inadmissible area

KVD 250/4/50/30

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 62 46 56 53 59 52 51 45 LWA Intake dB(A) 73 68 66 59 64 65 64 58 LWA Exhaust dB(A) 80 66 68 70 75 72 72 66

V· m3/h

DpfaPa r = 1,20 kg/m3

� 400 V� 280 V� 200 V � 140 V � 100 V

Inadmissible area

KVD 250/4/50/30 Ex

76

69

73

65

58

76

69

73

65

60

� Accessories

Gravity shutterType VK 50/30 Ref. no. 0876External airflow operated gravityshutter made of polymer, light grey.

External louvresType WSG 50/30 Ref. no. 0111Robust construction made ofaluminium extrusion profile, naturalcolour anodised.

Volume control damper forductingType JVK 50/30 Ref. no. 6912Casing made with flanges on bothsides. The control mechanism isoutside the airstream. For electricaldrive, see STM, accessory.

Circular spigotType FSK 50/30 Ref. no. 0837For cost effective adaption ofrectangular fans into circularducting systems with Ø 315 mm.

Flexible connectorsType VS 50/30 Ref. no. 5696Flexible in-duct connector withflanges on both sides.– for Ex-fansType VS 50/30 Ex Ref. no. 0266

CounterflangeType GF 50/30 Ref. no. 6921Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 50/25-30 No. 8729For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 50/25-30 G4 No. 8721Type KLF 50/25-30 F7 No. 8645Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Electric heater batteryType EHR-K 8/50/25-30 No. 8704Type EHR-K 24/50/25-30 No. 8705Heating elements enclosed in agalvanised steel casing withconnecting flanges on both sides.

Temperature control system forelectric heater batteryType EHSD 16 Ref. no. 5003

Warm water heater batteryType WHR 2/50/25-30 No. 8784Type WHR 4/50/25-30 No. 8785For in-duct installation.

Temperature control system forwarm water heater batteryType WHS HE Ref. no. 8319

� Accessory details PageShutters, grilles andlouvres 420, 487 onFilters, heaters andattenuators 421 onTemperature controlsystems for heaters 427, 432 onSpeed controllers and motorfull protection devices 525 on

Page 35: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

380

280 mm ø InlineVent® Rectangular fansforward curved, for rectangular duct size 60 x 30 cm

Speed controller 5-step without with motor protect. unit motor protect. unit

Motor full protectiondevice to connect

built-in thermal contacts

Type Ref. no. Air flowvolume, freedischarge

NominalR.P.M.

Sound press.case

breakout

Power consumption Wiringdiagram

Max. air flowtemperature at

Nom. vol. Control

Weightnet

approx.

65 60

KVD 280/4/60/30 Ex 6812 3450 1340 47 1.45 2.9 899 40 40 34 TSD 5,5 1503 — — MSA 1289

Dim. in mm

Type Ref. no. Type Ref. no.V· m3/h min-1 dB(A) in 4 m kW A No. +°C +°C kg Type Ref. no.

KVD 280/4/60/30 5684 3950 1300 45 1.67 5.4/3.1 860 35 TSD 5,5 1503 RDS 7 1578 MD 5849

3-phase motor, 230/400 V, 50 Hz, protected to IP 44

Explosion-proof Ex e II, temperature class T1 – T3, 3-phase 230/400 V, 50 Hz, protection to IP 44

Rectangular centrifugal fan withforward curved impeller bladesand swing-out motor impellerunit.

� Low-noise centrifugal impellersin aerodynamic galvanised steelcasing for high pressure levels.

� Compact and flat design for usein extract and fresh air systemsin commercial and industrial ap-plications.

� Specification� Casing Made of galvanised steel and

flanged on both ends. Spacesaving, compact design.

� Easy to clean and servicethanks to the swing-out motorimpeller unit.

� Impeller Forward curved centrifugal im-

peller made of galvanised steel,highly efficient with low noiselevels. Aerodynamically opti-mised casing; intake air flow bymeans of an inlet nozzle.

� Motor Totally enclosed, maintenance-

free external rotor motor with di-rectly fitted impeller, protected toIP 44.

Windings with protection againstmoisture. Ball bearing mountedand interference-free.

Dynamically balanced with re-silient motor mounting bracketfor low vibration and low noiseoperation.

� Electrical connection Terminal box (IP 55 for 3 ph., IP 65 for explosion-proof types)

is mounted with permanently at-tached cable.

� Motor protection Through built-in thermal con-

tacts which must be connectedto a motor full protection device.

� Speed control By voltage reduction using a 5 speed transformer controller

(recommended) or an electroniccontroller (stepless). The perfor-mance figures at correspondingvoltages are given in the perfor-mance curve.

� Sound Levels Above the performance curve,

total values and spectrum aregiven for:

– Sound level case breakout– Sound level intake– Sound level exhaust The sound power level (on in-

take) is additionally shown withinthe performance curve for corre-sponding control voltages.

In the table below you can alsofind:

– Case breakout sound level at 4 m (free field conditions).

� Installation Possible in any position. Attention should be paid to accessibility/swing out.

� Explosion-proof modelsThermal motor protectionthrough built-in PTC (positivetemperature coefficient) thermis-tors which must be connectedto a tripping unit MSA. Usingthis motor protection enablesthe speed control where a mini-mum voltage of 100 V must bemaintained.

KV

� Note PageSelection chart 372Technical description 373Design guidelines 10 onModul. system components 370

Page 36: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

381

Rect

angu

lar

fans

InlineVent® Rectangular fans 280 mm ø forward curved, for rectangular duct size 60 x 30 cm

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 65 56 58 57 60 57 55 50 LWA Intake dB(A) 80 70 72 67 73 74 72 67 LWA Exhaust dB(A) 85 69 73 75 79 78 78 73

V· m3/h

DpfaPa

r = 1,20 kg/m3

��

� 400 V� 280 V� 200 V � 140 V � 80 V

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 67 54 59 58 63 60 57 52 LWA Intake dB(A) 78 71 70 65 72 70 69 64 LWA Exhaust dB(A) 86 70 75 75 80 80 79 74

V· m3/h

DpfaPa

r = 1,20 kg/m3

� 400 V� 280 V� 200 V � 140 V � 100 V

KVD 280/4/60/30

KVD 280/4/60/30 Ex

Inadmissible area

80

76

78

73

66

80

76

78

73

68

� Accessories

Gravity shutterType VK 60/30 Ref. no. 0877External airflow operated gravityshutter made of polymer, light grey.

External louvresType WSG 60/30 Ref. no. 0112Robust construction made ofaluminium extrusion profile, naturalcolour anodised.

Volume control damper forductingType JVK 60/30 Ref. no. 6913Casing made with flanges on bothsides. The control mechanism isoutside the airstream. For electricaldrive, see STM, accessory.

Circular spigotType FSK 60/30 Ref. no. 0834For cost effective adaption ofrectangular fans into circularducting systems with Ø 315 mm.

Flexible connectorsType VS 60/30 Ref. no. 5697Flexible in-duct connector withflanges on both sides.– for Ex-fansType VS 60/30 Ex Ref. no. 0267

CounterflangeType GF 60/30 Ref. no. 6922Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 60/30-35 No. 8730For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 60/30-35 G4 No. 8722Type KLF 60/30-35 F7 No. 8646Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Electric heater batteryType EHR-K 15/60/30-35 No. 8706Type EHR-K 30/60/30-35 No. 8707Heating elements enclosed in agalvanised steel casing withconnecting flanges on both sides.

Temperature control system forelectric heater batteryType EHSD 16 Ref. no. 5003

Warm water heater batteryType WHR 2/60/30-35 No. 8786Type WHR 4/60/30-35 No. 8787For in-duct installation.

Temperature control system forwarm water heater batteryType WHS HE 1) Ref. no. 83191) In model WHR 4/60/30-35 the heat output is reduced to 2200 l/h.

� Accessory details PageShutters, grilles andlouvres 420, 487 onFilters, heaters andattenuators 421 onTemperature controlsystems for heaters 427, 432 onSpeed controllers and motorfull protection devices 525 on

Page 37: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

382

315 mm ø InlineVent® Rectangular fansforward curved, for rectangular duct size 60 x 35 cm

Speed controller 5-step without with motor protect. unit motor protect. unit

Motor full protectiondevice to connect

built-in thermal contacts

Type Ref. no. Air flowvolume, freedischarge

NominalR.P.M.

Sound press.case

breakout

Power consumption Wiringdiagram

Max. air flowtemperature at

Nom. vol. Control

Weightnet

approx.

40 40

Dynamically balanced with re-silient motor mounting bracketfor low vibration and low noiseoperation.

� Electrical connectionTerminal box (IP 55 for 3 ph.,IP 65 for explosion-proof types)is mounted with permanently at-tached cable.

� Motor protectionThrough built-in thermal con-tacts which must be connectedto a motor full protection device.

� Speed controlBy voltage reduction using a5 speed transformer controller(recommended) or an electroniccontroller (stepless). The perfor-mance figures at correspondingvoltages are given in the perfor-mance curve.

� Sound LevelsAbove the performance curve,total values and spectrum aregiven for:

– Sound level case breakout– Sound level intake– Sound level exhaust

The sound power level (on in-take) is additionally shown withinthe performance curve for corre-sponding control voltages.In the table below you can alsofind:

– Case breakout sound level at4 m (free field conditions).

� InstallationPossible in any position.Attention should be paid toaccessibility/swing out.

� Explosion-proof modelsThermal motor protectionthrough built-in PTC (positivetemperature coefficient) thermis-tors which must be connectedto a tripping unit MSA. Usingthis motor protection enablesthe speed control where a mini-mum voltage of 100 V must bemaintained.

KVD 315/4/60/35 5686 4500 1350 48 2.06 6.8/3.9 860 60 55 42 TSD 5,5 1503 RDS 7 1578 MD 5849

Type Ref. no. Type Ref. no.V· m3/h min-1 dB(A) in 4 m kW A No. +°C +°C kg Type Ref. no.

KVD 315/4/60/35 Ex 6813 4200 1370 48 2.0 4.0 899 42 TSD 5,5 1503 — — MSA 1289

3-phase motor, 230/400 V, 50 Hz, protected to IP 44

Explosion-proof Ex e II, temperature class T1 – T3, 3-phase 230/400 V, 50 Hz, protection to IP 44

Dim. in mm

Rectangular centrifugal fan withforward curved impeller bladesand swing-out motor impellerunit.

� Low-noise centrifugal impellersin aerodynamic galvanised steelcasing for high pressure levels.

� Compact and flat design for usein extract and fresh air systemsin commercial and industrial ap-plications.

� Specification� Casing

Made of galvanised steel andflanged on both ends. Spacesaving, compact design.

� Easy to clean and servicethanks to the swing-out motorimpeller unit.

� ImpellerForward curved centrifugal im-peller made of galvanised steel,highly efficient with low noiselevels. Aerodynamically opti-mised casing; intake air flow bymeans of an inlet nozzle.

� MotorTotally enclosed, maintenance-free external rotor motor with di-rectly fitted impeller, protected toIP 44.Windings with protection againstmoisture. Ball bearing mountedand interference-free.

KV

� Note PageSelection chart 372Technical description 373Design guidelines 10 onModul. system components 370

Page 38: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

383

Rect

angu

lar

fans

InlineVent® Rectangular fans 315 mm ø forward curved, for rectangular duct size 60 x 35 cm

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 68 55 60 60 63 62 58 54 LWA Intake dB(A) 81 73 70 68 74 73 72 68 LWA Exhaust dB(A) 87 73 74 78 82 81 80 75

V· m3/h

DpfaPa r = 1,20 kg/m3

��

� 400 V� 280 V� 200 V � 140 V � 80 V

Inadmissible area

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 68 56 60 58 64 61 60 56 LWA Intake dB(A) 79 71 70 67 72 72 71 67 LWA Exhaust dB(A) 87 73 75 78 82 81 80 76

V· m3/h

DpfaPa

r = 1,20 kg/m3

��

� 400 V� 280 V� 200 V � 140 V � 100 V

KVD 315/4/60/35

KVD 315/4/60/35 Ex

Inadmissible area

81

77

79

75

70

81

77

79

75

70

� Accessories

Gravity shutterType VK 60/35 Ref. no. 0878External airflow operated gravityshutter made of polymer, light grey.

External louvresType WSG 60/35 Ref. no. 0113Robust construction made ofaluminium extrusion profile, naturalcolour anodised.

Volume control damper forductingType JVK 60/35 Ref. no. 6914Casing made with flanges on bothsides. The control mechanism isoutside the airstream. For electricaldrive, see STM, accessory.

Circular spigotType FSK 60/35 Ref. no. 0835For cost effective adaption ofrectangular fans into circularducting systems with Ø 355 mm.

Flexible connectorsType VS 60/35 Ref. no. 5698Flexible in-duct connector withflanges on both sides.– for Ex-fansType VS 60/35 Ex Ref. no. 0268

CounterflangeType GF 60/35 Ref. no. 6923Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 60/30-35 No. 8730For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 60/30-35 G4 No. 8722Type KLF 60/30-35 F7 No. 8646Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Electric heater batteryType EHR-K 15/60/30-35 No. 8706Type EHR-K 30/60/30-35 No. 8707Heating elements enclosed in agalvanised steel casing withconnecting flanges on both sides.

Temperature control system forelectric heater batteryType EHSD 16 Ref. no. 5003

Warm water heater batteryType WHR 2/60/30-35 No. 8786Type WHR 4/60/30-35 No. 8787For in-duct installation.

Temperature control system forwarm water heater batteryType WHS HE 1) Ref. no. 83191) In model WHR 4/60/30-35 the heat output is reduced to 2200 l/h.

� Accessory details PageShutters, grilles andlouvres 420, 487 onFilters, heaters andattenuators 421 onTemperature controlsystems for heaters 427, 432 onSpeed controllers and motorfull protection devices 525 on

Page 39: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

384

355 mm ø InlineVent® Rectangular fansforward curved, for rectangular duct size 70 x 40 cm

Speed controller 5-step without with motor protect. unit motor protect. unit

Motor full protectiondevice to connect

built-in thermal contacts

Type Ref. no. Air flowvolume, freedischarge

NominalR.P.M.

Sound press.case

breakout

Power consumption Wiringdiagram

Max. air flowtemperature at

Nom. vol. Control

Weightnet

approx.

70 50

60 60

70 70

KVD 355/6/70/40 Ex 6814 4800 800 48 1.40 2.4 899 40 40 49 TSD 3,0 1502 — — MSA 1289

Dim. in mm

Type Ref. no. Type Ref. no.V· m3/h min-1 dB(A) in 4 m kW A No. +°C +°C kg Type Ref. no.

KVD 355/8/70/40 5687 4850 680 35 1.02 3.9/2.3 860 49 TSD 5,5 1503 RDS 4 1316 MD 5849

KVD 355/6/70/40 5688 5000 830 42 1.53 5.5/3.2 860 54 TSD 5,5 1503 RDS 4 1316 MD 5849

KVD 355/4/70/40 5689 5800 1400 54 3.48 10.4/6.0 860 60 TSD 11 1513 RDS 11 1332 MD 5849

3-phase motor, 230/400 V, 50 Hz, protected to IP 44

Explosion-proof Ex e II, temperature class T1 – T3, 3-phase 230/400 V, 50 Hz, protection to IP 44

and interference-free. Dynami-cally balanced with resilient mo-tor mounting bracket for low vi-bration and low noise operation.

� Electrical connectionTerminal box (IP 55 for 3 ph.,IP 65 for explosion-proof types)is mounted with permanently at-tached cable.

� Motor protectionThrough built-in thermal con-tacts which must be connectedto a motor full protection device.

� Speed controlBy voltage reduction using a5 speed transformer controller(recommended) or an electroniccontroller (stepless). The perfor-mance figures at correspondingvoltages are given in the perfor-mance curve.

� Sound LevelsAbove the performance curve,total values and spectrum aregiven for:

– Sound level case breakout– Sound level intake– Sound level exhaust

The sound power level (on in-take) is additionally shown withinthe performance curve for corre-sponding control voltages.In the table below you can alsofind:

– Case breakout sound level at4 m (free field conditions).

� InstallationPossible in any position.Attention should be paid toaccessibility/swing out.

Rectangular centrifugal fan withforward curved impeller bladesand swing-out motor impellerunit.

� Low-noise centrifugal impellersin aerodynamic galvanised steelcasing for high pressure levels.

� Compact and flat design for usein extract and fresh air systemsin commercial and industrial ap-plications.

� Specification� Casing

Made of galvanised steel andflanged on both ends. Spacesaving, compact design.

� Easy to clean and servicethanks to the swing-out motorimpeller unit.

� ImpellerForward curved centrifugal im-peller made of galvanised steel,highly efficient with low noiselevels. Aerodynamically opti-mised casing; intake air flow bymeans of an inlet nozzle.

� MotorTotally enclosed, maintenance-free external rotor motor with di-rectly fitted impeller, protected toIP 44.Windings with protection againstmoisture. Ball bearing mounted

� Explosion-proof modelsThermal motor protectionthrough built-in PTC (positivetemperature coefficient) thermis-tors which must be connectedto a tripping unit MSA. Usingthis motor protection enablesthe speed control where a mini-mum voltage of 100 V must bemaintained.

KV

� Note PageSelection chart 372Technical description 373Design guidelines 10 onModul. system components 370

Page 40: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

385

Rect

angu

lar

fans

InlineVent® Rectangular fans 355 mm ø forward curved, for rectangular duct size 70 x 40 cm

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 55 46 50 50 48 45 40 32 LWA Intake dB(A) 67 58 59 57 62 60 57 48 LWA Exhaust dB(A) 77 64 69 69 69 69 68 61

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 62 52 52 55 56 53 51 46 LWA Intake dB(A) 73 65 64 61 67 65 64 58 LWA Exhaust dB(A) 81 69 72 73 74 74 73 67

DpfaPa

V· m3/h

V· m3/h

r = 1,20 kg/m3

��

� 400 V� 280 V� 200 V � 140 V � 80 V

DpfaPa

r = 1,20 kg/m3

� 400 V� 280 V� 200 V � 140 V � 80 V

Inadmissible area

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 68 51 56 57 62 64 61 52 LWA Intake dB(A) 75 65 65 63 68 68 66 60 LWA Exhaust dB(A) 79 66 69 70 73 72 72 65

V· m3/h

DpfaPa

r = 1,20 kg/m3

� 400 V� 280 V� 200 V � 140 V � 100 V

KVD 355/8/70/40

KVD 355/6/70/40

KVD 355/6/70/40 Ex

Inadmissible area

67

66

66

64

55

73

69

72

66

59

V· m3/h

DpfaPa

r = 1,20 kg/m3

��

� 400 V� 280 V� 200 V � 140 V � 80 V

Inadmissible area

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 74 63 66 67 68 67 65 59 LWA Intake dB(A) 87 76 76 72 83 81 79 75 LWA Exhaust dB(A) 90 76 79 78 84 84 83 78

KVD 355/4/70/40

87

84

88

81

73

75

69

72

66

61

� Accessories

Gravity shutterType VK 70/40 Ref. no. 0879External airflow operated gravityshutter made of polymer, light grey.

External louvresType WSG 70/40 Ref. no. 0114Robust construction made ofaluminium extrusion profile, naturalcolour anodised.

Volume control damper forductingType JVK 70/40 Ref. no. 6915Casing made with flanges on bothsides. The control mechanism isoutside the airstream. For electricaldrive, see STM, accessory.

Circular spigotType FSK 70/40 Ref. no. 0840For cost effective adaption ofrectangular fans into circularducting systems with Ø 400 mm.

Flexible connectorsType VS 70/40 Ref. no. 5699Flexible in-duct connector withflanges on both sides.– for Ex-fansType VS 70/40 Ex Ref. no. 0269

CounterflangeType GF 70/40 Ref. no. 6924Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 70/40 Ref. no. 8731For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 70/40 G4 No. 8723Type KLF 70/40 F7 No. 8647Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Warm water heater batteryType WHR 2/70/40 No. 8788Type WHR 4/70/40 No. 8789For in-duct installation.

Temperature control system forwarm water heater batteryType WHS HE 1) Ref. no. 83191) In model WHR 4/70/40 the heat output is reduced to 2200 l/h.

� Accessory details PageShutters, grilles andlouvres 420, 487 onFilters, heaters andattenuators 421 onTemperature controlsystems for heaters 427, 432 onSpeed controllers and motorfull protection devices 525 on

Page 41: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

386

400 mm ø InlineVent® Rectangular fansforward curved, for rectangular duct size 80 x 50 cm

Speed controller 5-step without with motor protect. unit motor protect. unit

Motor full protectiondevice to connect

built-in thermal contacts

Type Ref. no. Air flowvolume, freedischarge

NominalR.P.M.

Sound press.case

breakout

Power consumption Wiringdiagram

Max. air flowtemperature at

Nom. vol. Control

Weightnet

approx.

and interference-free. Dynami-cally balanced with resilient mo-tor mounting bracket for low vi-bration and low noise operation.

� Electrical connectionTerminal box (IP 55) is mountedwith a permanently attached ca-ble.

� Motor protectionThrough built-in thermal con-tacts which must be connectedto a motor full protection device.

� Speed controlBy voltage reduction using a5 speed transformer controller(recommended) or an electroniccontroller (stepless). The perfor-mance figures at correspondingvoltages are given in the perfor-mance curve.

� Sound LevelsAbove the performance curve,total values and spectrum aregiven for:

– Sound level case breakout– Sound level intake– Sound level exhaust

The sound power level (on in-take) is additionally shown withinthe performance curve for corre-sponding control voltages.In the table below you can alsofind:

– Case breakout sound level at4 m (free field conditions).

� InstallationPossible in any position.Attention should be paid toaccessibility/swing out.

Rectangular centrifugal fan withforward curved impeller bladesand swing-out motor impellerunit.

� Low-noise centrifugal impellersin aerodynamic galvanised steelcasing for high pressure levels.

� Compact and flat design for usein extract and fresh air systemsin commercial and industrial ap-plications.

� Specification� Casing

Made of galvanised steel andflanged on both ends. Spacesaving, compact design.

� Easy to clean and servicethanks to the swing-out motorimpeller unit.

� ImpellerForward curved centrifugal im-peller made of galvanised steel,highly efficient with low noiselevels. Aerodynamically opti-mised casing; intake air flow bymeans of an inlet nozzle.

� MotorTotally enclosed, maintenance-free external rotor motor with di-rectly fitted impeller, protected toIP 44.Windings with protection againstmoisture. Ball bearing mounted

KVD 400/6/80/50 5691 7600 860 45 2.81 9.1/5.3 860 70 50 70 TSD 7,0 1504 RDS 7 1578 MD 5849

KVD 400/8/80/50 5690 5400 640 38 1.29 5.1/2.9 860 70 70 66 TSD 5,5 1503 RDS 4 1316 MD 5849

Type Ref. no. Type Ref. no.V· m3/h min-1 dB(A) in 4 m kW A No. +°C +°C kg Type Ref. no.

3-phase motor, 230/400 V, 50 Hz, protected to IP 44

Dim. in mm

KV

� Note PageSelection chart 372Technical description 373Design guidelines 10 onModul. system components 370

Page 42: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

387

Rect

angu

lar

fans

InlineVent® Rectangular fans 400 mm ø forward curved, for rectangular duct size 80 x 50 cm

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 58 46 50 54 53 47 42 34 LWA Intake dB(A) 71 62 59 62 66 65 63 54 LWA Exhaust dB(A) 77 62 63 70 71 70 69 60

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 65 53 57 60 61 56 51 44 LWA Intake dB(A) 80 67 65 70 75 73 71 65 LWA Exhaust dB(A) 85 67 68 78 80 78 77 71

DpfaPa

V· m3/h

V· m3/h

r = 1,20 kg/m3

� 400 V� 280 V� 200 V � 140 V � 80 V

DpfaPa

r = 1,20 kg/m3

� 400 V� 280 V� 200 V � 140 V � 80 V

KVD 400/8/80/50

KVD 400/6/80/50

Inadmissible area

71

67

70

63

53

80

76

78

72

64

� Accessories

Gravity shutterType VK 80/50 Ref. no. 0880External airflow operated gravityshutter made of polymer, light grey.

External louvresType WSG 80/50 Ref. no. 0115Robust construction made ofaluminium extrusion profile, naturalcolour anodised.

Volume control damper forductingType JVK 80/50 Ref. no. 6916Casing made with flanges on bothsides. The control mechanism isoutside the airstream. For electricaldrive, see STM, accessory.

Circular spigotType FSK 80/50 Ref. no. 0842For cost effective adaption ofrectangular fans into circularducting systems with Ø 500 mm.

Flexible connectorsType VS 80/50 Ref. no. 5700Flexible in-duct connector withflanges on both sides.

CounterflangeType GF 80/50 Ref. no. 6925Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 80/50 Ref. no. 8732For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 80/50 G4 No. 8670Type KLF 80/50 F7 No. 8654Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Warm water heater batteryType WHR 2/80/50 No. 8795Type WHR 4/80/50 No. 8796For in-duct installation.

� Accessory details PageShutters, grilles andlouvres 420, 487 onFilters, heaters andattenuators 421 onSpeed controllers and motorfull protection devices 525 on

Page 43: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

388

450 mm ø InlineVent® Rectangular fansforward curved, for rectangular duct size 100 x 50 cm

Speed controller 5-step without with motor protect. unit motor protect. unit

Motor full protectiondevice to connect

built-in thermal contacts

Type Ref. no. Air flowvolume, freedischarge

NominalR.P.M.

Sound press.case

breakout

Power consumption Wiringdiagram

Max. air flowtemperature at

Nom. vol. Control

Weightnet

approx.

Dim. in mm

Dynamically balanced with re-silient motor mounting bracketfor low vibration and low noiseoperation.

� Electrical connection Terminal box (IP 55) is mounted

with a permanently attached ca-ble.

� Motor protection Through built-in thermal con-

tacts which must be connectedto a motor full protection device.

� Speed control By voltage reduction using a 5 speed transformer controller

(recommended) or an electroniccontroller (stepless). The perfor-mance figures at correspondingvoltages are given in the perfor-mance curve.

� Sound Levels Above the performance curve,

total values and spectrum aregiven for:

– Sound level case breakout– Sound level intake– Sound level exhaust The sound power level (on in-

take) is additionally shown withinthe performance curve for corre-sponding control voltages.

In the table below you can alsofind:

– Case breakout sound level at 4 m (free field conditions).

� Installation Possible in any position. Attention should be paid to accessibility/swing out.

Rectangular centrifugal fan withforward curved impeller bladesand swing-out motor impellerunit.

� Low-noise centrifugal impellersin aerodynamic galvanised steelcasing for high pressure levels.

� Compact and flat design for usein extract and fresh air systemsin commercial and industrial ap-plications.

� Specification� Casing Made of galvanised steel and

flanged on both ends. Spacesaving, compact design.

� Easy to clean and servicethanks to the swing-out motorimpeller unit.

� Impeller Forward curved centrifugal im-

peller made of galvanised steel,highly efficient with low noiselevels. Aerodynamically opti-mised casing; intake air flow bymeans of an inlet nozzle.

� Motor Totally enclosed, maintenance-

free external rotor motor with di-rectly fitted impeller, protected toIP 44.

Windings with protection againstmoisture. Ball bearing mountedand interference-free.

KVD 450/8/100/50 5692 7600 690 46 2.26 8.6/5.0 860 60 50 90 TSD 7,0 1504 RDS 7 1578 MD 5849

KVD 450/6/100/50 5693 8500 870 50 3.65 11.6/6.7 860 70 50 90 TSD 11 1513 RDS 11 1332 MD 5849

Type Ref. no. Type Ref. no.V· m3/h min-1 dB(A) in 4 m kW A No. +°C +°C kg Type Ref. no.

3-phase motor, 230/400 V, 50 Hz, protected to IP 44

KV

� Note PageSelection chart 372Technical description 373Design guidelines 10 onModul. system components 370

Page 44: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

389

Rect

angu

lar

fans

InlineVent® Rectangular fans 450 mm ø forward curved, for rectangular duct size 100 x 50 cm

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 66 56 56 62 58 57 54 47 LWA Intake dB(A) 76 63 62 70 70 70 68 59 LWA Exhaust dB(A) 82 65 67 76 78 76 74 65

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 70 62 61 65 63 61 56 50 LWA Intake dB(A) 80 67 65 74 75 74 73 66 LWA Exhaust dB(A) 86 69 69 78 82 80 78 71

DpfaPa

V· m3/h

V· m3/h

r = 1,20 kg/m3

���

� 400 V� 280 V� 200 V� 140 V� 80 V

DpfaPa r = 1,20 kg/m3

� 400 V� 280 V� 200 V� 140 V� 80 V

KVD 450/8/100/50

KVD 450/6/100/50

Inadmissible area

Inadmissible area

76

76

78

73

66

80

72

74

69

62

� Accessories

Gravity shutterType VK 100/50 Ref. no. 0881External airflow operated gravityshutter made of polymer, light grey.

External louvresType WSG 100/50 Ref. no. 0116Robust construction made ofaluminium extrusion profile, naturalcolour anodised.

Volume control damper forductingType JVK 100/50 Ref. no. 6917Casing made with flanges on bothsides. The control mechanism isoutside the airstream. For electricaldrive, see STM, accessory.

Circular spigotType FSK 100/50 Ref. no. 0843For cost effective adaption ofrectangular fans into circularducting systems with Ø 500 mm.

Flexible connectorsType VS 100/50 Ref. no. 5701Flexible in-duct connector withflanges on both sides.

CounterflangeType GF 100/50 Ref. no. 6926Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 100/50 Ref. no. 8733For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 100/50 G4 No. 8671Type KLF 100/50 F7 No. 8655Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Warm water heater batteryType WHR 2/100/50 No. 8797Type WHR 4/100/50 No. 8798For in-duct installation.

� Accessory details PageShutters, grilles andlouvres 420, 487 onFilters, heaters andattenuators 421 onSpeed controllers and motorfull protection devices 525 on

Page 45: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

390

180 mm ø InlineVent® EC rectangular fansbackward curved, for rectangular duct size 30 x 15 cm

Rectangular EC centrifugal fanwith backward curved impellerand swing-out motor impellerunit.

� Highly efficient EC-motor forlowest operating costs.

� High performance with highefficiency impellers.

� Use in extract and fresh airsystems for conveying higherair flow volume.

� Suitable for extraction ofpolluted air.

� Special features� High pressure and high volumespecific centrifugal fan with highefficiency.

� Particularly easy to service(cleaning) thanks to the swing-out motor impeller unit.

� For cleaning, easy access andtherefore suitable for extractionof polluted air.

� Compact design, less space re-quirement and straight through-flow.

� Specification� CasingMade of galvanised steel.Flanged (20 mm) on both endsfor in-duct installation.

� ImpellerCentrifugal, backward curvedimpeller made of polymer.Aerodynamically optimised,intake air flow by means of aninlet nozzle.

� MotorEnergy saving, speed control-lable EC-external rotor motorswith highest efficiency, protec-tion to IP 44. With ball bearings,maintenance-free and interfer-ence-free. Motor and impellerare dynamically balanced.

� Motor protectionIntegrated electronic tempera-ture monitoring for EC-motorand electronics.

� Speed controlStepless speed control with po-tentiometer or stepless speedcontrol with universal controlsystem (see table). Duties atdifferent speeds are exemplarilygiven in the performance curve.

� Electrical connectionTerminal box (IP 54) fitted toflying lead.

� InstallationInstallation in any position.Allowance must be made for themotor swing out access.

� Sound levelsTotal sound power levels andthe spectrum figures in dB(A)are given for:

– Sound level case breakout– Sound level intake– Sound level exhaustIn the table below as well as un-derneath the performance curveyou can find additionally thesound pressure level at 4 m(free field conditions).

Suitable for polluted air.

KR EC

Dim. in mm

(fig. similar)

� Note PageSelection chart 372Technical description 373Design guidelines 10 onModul. system components 370

KRW EC 180/30/15 8168 660 3700 44 979 6.20.11 0.90 60 EUR EC 1) 2) 1347 PU 10 1) 1734

Type Ref no. Air flowvolume(FID)

NominalR.P.M.

Sound press.case

breakout

Wiringdiagram

Weightnet

approx. .V m3/h min-1 dB(A) in 4m No. kg

Motorpower

kW

Current

A

max. air flowtemperature

+ °C

Universalcontrol system

Speed-potentiometer flush surface

Type Ref. no. Type Ref. no.

PA 10 1) 1735

Type Ref. no.

Single Phase, 230 V, 50/60 Hz, EC motor, protection to IP 44

1) Multiple EC fans can normally be connected 2) alternative electronic differential pressure/temp. controller (EDR/ETR, No. 1437/1438) or three-step speed controller (SU/SA, No. 4266/4267), s. accessories

Saving ** with speed control

Page 46: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

391

InlineVent® EC rectangular fans 180 mm ø backward curved, for rectangular duct size 30 x 15 cm

� Accessories

Gravity shutterType VK 30/15 Ref. no. 0735Air stream operated louvres, lightgrey polymer.

External louvreType WSG 30/15 Ref. no. 0108Heavy duty construction madefrom profile anodised aluminiumextrusion.

Vol. control damper for ductingType JVK 30/15 Ref. no. 6927Casing with flanges on both sides.The control mechanism is outsidethe airstream. For electrical drive,see STM, accessory.

Circular spigotType FSK 30/15 Ref. no. 0831For cost effective adaption ofrectangular fans into circularducting systems with Ø 160 mm.

Flexible connectorsType VS 30/15 Ref. no. 6928Flexible in-duct connector withflanges on both sides.

CounterflangeType GF 30/15 Ref. no. 6918Flange frames made of galvanisedsteel for connection to ducting.

� Accessory details PageShutters, grilles and louvres 420, 487 onFilters, heater batteriesand attenuators 421 onUniversal control system,electronic controller,speed-potentiometer 539 on

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 64 50 52 61 57 55 49 42 LWA Intake dB(A) 78 63 72 74 67 66 67 60 LWA Exhaust dB(A) 84 66 76 79 75 78 74 66

��

V· m3/h

DpfaPa r = 1,20 kg/m3

KRW EC 180/30/15

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 3700 660 113 0,89 44 0,62 8 3120 560 70 0,58 40 0,45 6 2300 400 30 0,25 34 0,27 4 1500 260 10 0,10 26 0,14

� 10 V� 8 V� 6 V� 4 V� 2 V

EC re

ctan

gula

rfa

ns

Page 47: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

392

225 mm ø InlineVent® EC rectangular fansbackward curved, for rectangular duct size 40 x 20 cm

Rectangular EC centrifugal fanwith backward curved impellerand swing-out motor impellerunit.

� Highly efficient EC-motor forlowest operating costs.

� High performance with high efficiency impellers. � Use in extract and fresh air systems for conveying higher air flow volume.� Suitable for extraction of polluted air.

� Special features� High pressure and high volumespecific centrifugal fan with highefficiency.

� Particularly easy to service(cleaning) thanks to the swing-out motor impeller unit.

� For cleaning, easy access andtherefore suitable for extractionof polluted air.

� Compact design, less space re-quirement and straight through-flow.

� Specification� CasingMade of galvanised steel.Flanged (20 mm) on both endsfor in-duct installation.

� ImpellerCentrifugal, backward curvedimpeller made of polymer. Aerodynamically optimised,intake air flow by means of aninlet nozzle.

� Motor Energy saving, speed control-lable EC-external rotor motorswith highest efficiency, protec-tion to IP 44. With ball bearings,maintenance-free and interfer-ence-free. Motor and impellerare dynamically balanced.

� Motor protectionIntegrated electronic tempera-ture monitoring for EC-motorand electronics.

� Speed control Stepless speed control with po-tentiometer or stepless speedcontrol with universal controlsystem (see table). Duties at

different speeds are exemplarilygiven in the performance curve.

� Electrical connectionTerminal box (IP 54) fitted toflying lead.

� InstallationInstallation in any position.Allowance must be made for themotor swing out access.

� Sound levels Total sound power levels andthe spectrum figures in dB(A)are given for:

– Sound level case breakout– Sound level intake– Sound level exhaust In the table below as well as un-derneath the performance curveyou can find additionally thesound pressure level at 4 m(free field conditions).

� Note PageSelection chart 372Technical description 373Design guidelines 10 onModul. system components 370

Suitable for polluted air.

KR EC

Dim. in mm

KRW EC 225/40/20 8169 1430 2650 46 979 9,80,16 1,26 60 EUR EC 1) 2) 1347 PU 10 1) 1734

Type Ref. no. Air flowvolume(FID)

NominalR.P.M.

Sound press.case

breakout

Wiringdiagram

Weightnet

approx. .V m3/h min-1 dB(A) in 4m No. kg

Motorpower

kW

Current

A

max. air flowtemperature

+ °C

Universalcontrol system

Speed-potentiometer flush surface

Type Ref. no. Type Ref. no.

PA 10 1) 1735

Type Ref. no.

Single Phase, 230 V, 50/60 Hz, EC motor, protection to IP 44

1) Multiple EC fans can normally be connected 2) alternative electronic differential pressure/temp. controller (EDR/ETR, No. 1437/1438) or three-step speed controller (SU/SA, No. 4266/4267), s. accessories

(Fig. similar)

Saving ** with speed control

Page 48: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

393

InlineVent® EC rectangular fans 225 mm ø backward curved, for rectangular duct size 40 x 20 cm

� Accessories

Gravity shutterType VK 40/20 Ref. no. 0874Air stream operated louvres, lightgrey polymer.

External louvreType WSG 40/20 Ref. no. 0109Heavy duty construction madefrom profile anodised aluminiumextrusion.

Vol. control damper for ductingType JVK 40/20 Ref. no. 6910Casing with flanges on both sides.The control mechanism is outsidethe airstream. For electrical drive,see STM, accessory.

Circular spigotType FSK 40/20 Ref. no. 0832For cost effective adaption ofrectangular fans into circularducting systems with Ø 200mm.

Flexible connectorsType VS 40/20 Ref. no. 5694Flexible in-duct connector withflanges on both sides.

CounterflangeType GF 40/20 Ref. no. 6919Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 40/20 Ref. no. 8728For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 40/20 G4 No. 8720Type KLF 40/20 F7 No. 8644Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Electric heater batteryType EHR-K 6/40/20 No 8702Type EHR-K 15/40/20 No. 8703Heating elements enclosed in agalvanised steel casing withconnecting flanges on both sides.

Temperature control system forelectric heater batteryType EHSD 16 Ref. no. 5003

Warm water heater batteryType WHR 2/40/20 No. 8782Type WHR 4/40/20 No. 8783For in-duct installation.

Temperature control system forwarm water heater batteryType WHS HE Ref. no. 8319

� Accessory details PageShutters, grilles and louvres 420, 487 onFilters, heater batteriesand attenuators 421 onTemperature control systemsfor heater batteries 427, 432 onUniversal control system,electronic controller,speed-potentiometer 539 on

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 66 50 62 63 54 50 45 37 LWA Intake dB(A) 80 72 78 73 67 64 64 54 LWA Exhaust dB(A) 83 71 78 78 74 72 68 59

��

V· m3/h

DpfaPa

r = 1,20 kg/m3

KRW EC 225/40/20

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 2650 1430 160 1,26 46 0,40 8 2490 1300 118 0,95 45 0,33 6 2000 1060 60 0,50 40 0,20 4 1350 710 20 0,18 32 0,10

� 10 V� 8 V� 6 V � 4 V � 2 V

EC re

ctan

gula

rfa

ns

Page 49: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

394

315 mm ø InlineVent® EC rectangular fansbackward curved, for rectangular duct size 50 x 25 cm

� Features ofKR EC and SKR EC

� Highly efficient EC-motor forlowest operating costs.

� High pressure and high volumewith high efficiency centrifugalfan.

� Particularly easy to service(cleaning) thanks to the swing-out motor impeller unit.

� For cleaning, easy access andtherefore suitable for extractionof polluted air.

� Straight through-flow.� Compact design, convenientinstallation.

� Special features of SKR EC� Lowest sound levels for intakeand case breakout at higherpower density.

� Specification� Casing KR ECMade of galvanised steel.Flanged (20 mm) on both endsfor in-duct installation.

� Casing SKR ECAs above, but with additionalsound insulation with 50 mmthick mineral fibre board, insidelined with a sound deadeningperforated plate.

� Common features ofKR EC and SKR EC

� ImpellerCentrifugal, backward curvedimpeller made of polymer. Aero-dynamically optimised, intake airflow by means of an inlet nozzle.

� MotorEnergy-saving, speed control-lable EC-external rotor motorswith highest efficiency, protec-tion to IP 44 (SKR EC IP 54).With ball bearings, mainte-nance-free and interference-free.Motor and impeller are dynami-cally balanced.

� Motor protectionIntegrated electronic tempera-ture monitoring for EC-motorand electronics.

� Speed controlStepless speed control with po-tentiometer or stepless speedcontrol with universal controlsystem (see table). Duties atdifferent speeds are exemplarilygiven in the performance curve.

� Electrical connectionTerminal box (IP 54) fitted toflying lead.

� InstallationInstallation in any position.Allowance must be made for themotor swing out access.

� Sound levelsTotal sound power levels andthe spectrum figures in dB(A)are given for:

– Sound level case breakout– Sound level intake– Sound level exhaustIn the table below as well as un-derneath the performance curveyou can find additionally thesound pressure level at 4 m(free field conditions).

Suitable for polluted air.

KR EC

Dim. in mm

KRW EC 315/50/25 8170 1410 3080 44 979 13.80.16 1.24 60 EUR EC 1) 2) 1347 PU 10 1) 1734

Type Ref. no. Air flowvolume(FID)

NominalR.P.M.

Sound press.case

breakout

Wiringdiagram

Weightnet

approx. .V m3/h min-1 dB(A) in 4m No. kg

Motorpower

kW

Current

A

max. air flowtemperature

+ °C

Universalcontrol system

Speed-potentiometer flush surface

Type Ref. no. Type Ref. no.

PA 10 1) 1735

Type Ref. no.

(Fig. similar)

SKR EC – Sound insulated

Dim. in mm

Lowest sound levels for intake and casebreakout at higher power density.Use in extract and fresh air systems with specific requirements for low noise levels.

SKRW EC 315/50/25 8182 2600 2020 47 1066 34.00.36 1.57 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

Sound insulated model SKR EC – single phase, 230 V, 50/60 Hz, EC motor, protection to IP 54

Single Phase, 230 V, 50/60 Hz, EC motor, protection to IP 44

1) Multiple EC fans can normally be connected 2) alternative electronic differential pressure/temp. controller (EDR/ETR, No. 1437/1438) or three-step speed controller (SU/SA, No. 4266/4267), s. accessories

Swing-out area Swing-out area

Page 50: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

395

InlineVent® EC rectangular fans 315 mm ø backward curved, for rectangular duct size 50 x 25 cm

� Accessories

Gravity shutterType VK 50/25 Ref. no. 0875Air stream operated louvres, lightgrey polymer.

External louvreType WSG 50/25 Ref. no. 0110Heavy duty construction madefrom profile anodised aluminiumextrusion.

Vol. control damper for ductingType JVK 50/25 Ref. no. 6911Casing with flanges on both sides.The control mechanism is outsidethe airstream. For electrical drive,see STM, accessory.

Circular spigotType FSK 50/25 Ref. no. 0833For cost effective adaption ofrectangular fans into circularducting systems with Ø 250mm.

Flexible connectorsType VS 50/25 Ref. no. 5695Flexible in-duct connector withflanges on both sides.

CounterflangeType GF 50/25 Ref. no. 6920Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 50/25-30 No. 8729For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 50/25-30 G4 No. 8721Type KLF 50/25-30 F7 Nor. 8645Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Electric heater batteryType EHR-K 8/50/25-30 No. 8704Type EHR-K 24/50/25-30 No. 8705Heating elements enclosed in agalvanised steel casing withconnecting flanges on both sides.

Temperature control system forelectric heater batteryType EHSD 16 Ref. no. 5003

Warm water heater batteryType WHR 2/50/25-30 No. 8784Type WHR 4/50/25-30 No. 8785For in-duct installation.

Temperature control system forwarm water heater batteryType WHS HE Ref. no. 8319

� Accessory details PageShutters, grilles and louvres 420, 487 onFilters, heater batteriesand attenuators 421 onTemperature control systemsfor heater batteries 427, 432 onUniversal control system,electronic controller,speed-potentiometer 539 on

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 64 49 61 58 50 48 42 35 LWA Intake dB(A) 76 67 72 63 65 66 64 52 LWA Exhaust dB(A) 80 67 74 72 70 73 68 57

��

V· m3/h

DpfaPa r = 1,20 kg/m3

KRW EC 315/50/25

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 3080 1410 160 1,24 44 0,41 8 2500 1230 105 0,82 42 0,31 6 2000 980 55 0,45 39 0,20 4 1350 690 20 0,18 32 0,11

� 10 V� 8 V� 6 V � 4 V � 2 V

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 67 58 66 52 47 43 37 32 LWA Intake dB(A) 74 68 72 57 50 49 48 46 LWA Exhaust dB(A) 81 71 80 69 66 63 59 56

V· m3/h

DpfaPa

r = 1,20 kg/m3

SKRW EC 315/50/25

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 2020 2600 310 1,30 47 0,43 8 1650 2140 170 0,74 43 0,29 6 1350 1730 100 0,45 40 0,21 4 900 1130 35 0,20 32 0,11

� 10 V� 8 V� 6 V � 4 V � 2 V

��

EC re

ctan

gula

rfa

nsSaving ** with speed control

Page 51: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

396

355 mm ø InlineVent® EC rectangular fansbackward curved, for rectangular duct size 60 x 30 cm

� Features ofKR EC and SKR EC

� Highly efficient EC-motor forlowest operating costs.

� High pressure and high volumewith high efficiency centrifugalfan.

� Particularly easy to service(cleaning) thanks to the swing-out motor impeller unit.

� For cleaning, easy access andtherefore suitable for extractionof polluted air.

� Straight through-flow.� Compact design, convenientinstallation.

� Special features of SKR EC� Lowest sound levels for intakeand case breakout at higherpower density.

� Specification� Casing KR ECMade of galvanised steel.Flanged (20 mm) on both endsfor in-duct installation.

� Casing SKR ECAs above, but with additionalsound insulation with 50 mmthick mineral fibre board, insidelined with a sound deadeningperforated plate.

� Common features ofKR EC and SKR EC

� ImpellerCentrifugal, backward curvedimpeller made of polymer. Aero-dynamically optimised, intake airflow by means of an inlet nozzle.

� MotorEnergy-saving, speed control-lable EC-external rotor motorswith highest efficiency, protec-tion to IP 44. With ball bearings,maintenance-free and interfer-ence-free. Motor and impellerare dynamically balanced.

� Motor protectionIntegrated electronic tempera-ture monitoring for EC-motorand electronics.

� Speed controlStepless speed control with po-tentiometer or stepless speedcontrol with universal controlsystem (see table). Duties atdifferent speeds are exemplarilygiven in the performance curve.

� Electrical connectionTerminal box (IP 54) fitted toflying lead.

� InstallationInstallation in any position.Allowance must be made for themotor swing out access.

� Sound levelsTotal sound power levels andthe spectrum figures in dB(A)are given for:

– Sound level case breakout– Sound level intake– Sound level exhaustIn the table below as well as un-derneath the performance curveyou can find additionally thesound pressure level at 4 m(free field conditions).

SKR EC – Sound insulatedSuitable for polluted air.KR EC

Dim. in mm Dim. in mm

Lowest sound levels for intake and casebreakout at higher power density.Use in extract and fresh air systems with specific requirements for low noise levels.

SKRD EC 355/60/30 8296 4550 2500 52 1005 44.51.16 1.81 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

KRW EC 355/60/30 8171 3110 1650 46 1066 25.00.37 1.59 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

SKRW EC 355/60/30 8176 3950 2200 51 982 44.50.84 3.94 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

Type Ref. no. Air flowvolume(FID)

NominalR.P.M.

Sound press.case

breakout

Wiringdiagram

Weightnet

approx. .V m3/h min-1 dB(A) in 4m No. kg

Motorpower

kW

Current

A

max. air flowtemperature

+ °C

Universalcontrol system

Speed-potentiometer flush surface

Type Ref. no. Type Ref. no. Type Ref. no.

Single Phase, 230 V, 50/60 Hz, EC motor, protection to IP 54

Sound insulated model SKR EC – single phase, 230 V, 50/60 Hz, EC motor, protection to IP 54

Sound insulated model SKR EC – three phase, 400 V, 50/60 Hz, EC motor, protection to IP 54

1) Multiple EC fans can normally be connected 2) alternative electronic differential pressure/temp. controller (EDR/ETR, No. 1437/1438) or three-step speed controller (SU/SA, No. 4266/4267), s. accessories

(Fig. similar)

Swing-out area Swing-out area

Page 52: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

397

InlineVent® EC rectangular fans 355 mm ø backward curved, for rectangular duct size 60 x 30 cm

� Accessories

Gravity shutterType VK 60/30 Ref. no. 0877Air stream operated louvres, lightgrey polymer.

External louvreType WSG 60/30 Ref. no. 0112Heavy duty construction madefrom profile anodised aluminiumextrusion.

Vol. control damper for ductingType JVK 60/30 Ref. no. 6913Casing with flanges on both sides.The control mechanism is outsidethe airstream. For electrical drive,see STM, accessory.

Circular spigotType FSK 60/30 Ref. no. 0834For cost effective adaption ofrectangular fans into circularducting systems with Ø 315mm.

Flexible connectorsType VS 60/30 Ref. no. 5697Flexible in-duct connector withflanges on both sides.

CounterflangeType GF 60/30 Ref. no. 6922Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 60/30-35 No. 8730For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 60/30-35 G4 No. 8722Type KLF 60/30-35 F7 No. 8646Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Electric heater batteryType EHR-K 15/60/30-35 No. 8706Type EHR-K 30/60/30-35 No. 8707Heating elements enclosed in agalvanised steel casing withconnecting flanges on both sides.

Temperature control system forelectric heater batteryType EHSD 16 Ref. no. 5003

Warm water heater batteryType WHR 2/60/30-35 No. 8786Type WHR 4/60/30-35 No. 8787For in-duct installation.

Temperature control system forwarm water heater batteryType WHS HE 1) Ref. no. 83191) In model WHR 4/60/30-35 the heat output is reduced

to 2200 l/h.

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 71 58 71 55 52 49 44 39 LWA Intake dB(A) 78 72 75 64 58 56 52 50 LWA Exhaust dB(A) 84 74 83 73 72 69 65 61

V· m3/h

DpfaPa

r = 1,20 kg/m3

SKRW EC 355/60/30

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 2200 3950 670 3,10 51 0,61 8 1750 3200 360 1,70 46 0,41 6 1300 2400 160 0,74 40 0,24 4 850 1550 60 0,36 32 0,14

� 10 V� 8 V� 6 V � 4 V � 2 V

��

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 72 61 71 61 57 53 48 42 LWA Intake dB(A) 80 74 76 68 62 60 56 53 LWA Exhaust dB(A) 86 76 84 77 76 74 69 64

V· m3/h

DpfaPa

r = 1,20 kg/m3

SKRD EC 355/60/30

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 2500 4550 930 1,50 52 0,74 8 2000 3600 500 0,82 47 0,50 6 1450 2750 220 0,45 42 0,29 4 950 1700 80 0,26 33 0,17

� 10 V� 8 V� 6 V � 4 V � 2 V

��

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 66 59 63 58 54 48 42 40 LWA Intake dB(A) 78 73 76 66 61 61 58 58 LWA Exhaust dB(A) 81 70 78 74 69 67 63 62

V· m3/h

DpfaPa

r = 1,20 kg/m3

KRW EC 355/60/30

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 1650 3110 275 1,20 46 0,32 8 1350 2580 150 0,65 42 0,21 6 1050 2000 75 0,35 37 0,14 4 750 1400 35 0,20 28 0,09

� 10 V� 8 V� 6 V � 4 V � 2 V

EC re

ctan

gula

rfa

ns

Page 53: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

398

400 mm ø InlineVent® EC rectangular fansbackward curved, for rectangular duct size 60 x 35 cm

� Features ofKR EC and SKR EC

� Highly efficient EC-motor forlowest operating costs.

� High pressure and high volumewith high efficiency centrifugalfan.

� Particularly easy to service(cleaning) thanks to the swing-out motor impeller unit.

� For cleaning, easy access andtherefore suitable for extractionof polluted air.

� Straight through-flow.� Compact design, convenientinstallation.

� Special features of SKR EC� Lowest sound levels for intakeand case breakout at higherpower density.

� Specification� Casing KR ECMade of galvanised steel.Flanged (20 mm) on both endsfor in-duct installation.

� Casing SKR ECAs above, but with additionalsound insulation with 50 mmthick mineral fibre board, insidelined with a sound deadeningperforated plate.

� Common features ofKR EC and SKR EC

� ImpellerCentrifugal, backward curvedimpeller made of polymer. Aero-dynamically optimised, intake airflow by means of an inlet nozzle.

� MotorEnergy-saving, speed control-lable EC-external rotor motorswith highest efficiency, protec-tion to IP 44 (SKR EC IP 54).With ball bearings, mainte-nance-free and interference-free.Motor and impeller are dynami-cally balanced.

� Motor protectionIntegrated electronic tempera-ture monitoring for EC-motorand electronics.

� Speed controlStepless speed control with po-tentiometer or stepless speedcontrol with universal controlsystem (see table). Duties atdifferent speeds are exemplarilygiven in the performance curve.

� Electrical connectionTerminal box (IP 54) fitted toflying lead.

� InstallationInstallation in any position.Allowance must be made for themotor swing out access.

� Sound levelsTotal sound power levels andthe spectrum figures in dB(A)are given for:

– Sound level case breakout– Sound level intake– Sound level exhaustIn the table below as well as un-derneath the performance curveyou can find additionally thesound pressure level at 4 m(free field conditions).

SKR EC – Sound insulated

Dim. in mm

Lowest sound levels for intake and casebreakout at higher power density.Use in extract and fresh air systems with specific requirements for low noise levels.

KRW EC 400/60/35 8172 4460 2200 56 982 30.40.88 4.04 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

SKRW EC 400/60/35 8177 4200 2200 51 982 46.00.84 3.92 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

Type Ref. no. Air flowvolume(FID)

NominalR.P.M.

Sound press.case

breakout

Wiringdiagram

Weightnet

approx. .V m3/h min-1 dB(A) in 4m No. kg

Motorpower

kW

Current

A

max. air flowtemperature

+ °C

Universalcontrol system

Speed-potentiometer flush surface

Type Ref. no. Type Ref. no. Type Ref. no.

Suitable for polluted air.KR EC

Dim. in mm

SKRD EC 400/60/35 8297 5000 2500 51 1005 46.01.17 1.81 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

Single Phase, 230 V, 50/60 Hz, EC motor, protection to IP 54

Sound insulated model SKR EC – 1-phase, 1~, 230 V, 50/60 Hz, EC motor, protection to IP 54

Sound insulated model SKR EC – 3-phase, 3~, 400 V, 50/60 Hz, EC motor, protection to IP 54

1) Multiple EC fans can normally be connected 2) alternative electronic differential pressure/temp. controller (EDR/ETR, No. 1437/1438) or three-step speed controller (SU/SA, No. 4266/4267), s. accessories

(Fig. similar)

Swing-out area Swing-out area

Page 54: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

399

InlineVent® EC rectangular fans 400 mm ø backward curved, for rectangular duct size 60 x 35 cm

� Accessories

Gravity shutterType VK 60/35 Ref. no. 0878Air stream operated louvres, lightgrey polymer.

External louvreType WSG 60/35 Ref. no. 0113Heavy duty construction madefrom profile anodised aluminiumextrusion.

Vol. control damper for ductingType JVK 60/35 Ref. no. 6914Casing with flanges on both sides.The control mechanism is outsidethe airstream. For electrical drive,see STM, accessory.

Circular spigotType FSK 60/35 Ref. no. 0835For cost effective adaption ofrectangular fans into circularducting systems with Ø 355mm.

Flexible connectorsType VS 60/35 Ref. no. 5698Flexible in-duct connector withflanges on both sides.

CounterflangeType GF 60/35 Ref. no. 6923Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 60/30-35 No. 8730For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 60/30-35 G4 No. 8722Type KLF 60/30-35 F7 No. 8646Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Electric heater batteryType EHR-K 15/60/30-35 No. 8706Type EHR-K 30/60/30-35 No. 8707Heating elements enclosed in agalvanised steel casing withconnecting flanges on both sides.

Temperature control system forelectric heater batteryType EHSD 16 Ref. no. 5003

Warm water heater batteryType WHR 2/60/30-35 No. 8786Type WHR 4/60/30-35 No. 8787For in-duct installation.

Temperature control system forwarm water heater batteryType WHS HE 1) Ref. no. 83191) In model WHR 4/60/30-35 the heat output is reduced

to 2200 l/h.

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 71 55 70 53 49 49 46 44 LWA Intake dB(A) 76 69 74 63 56 53 50 48 LWA Exhaust dB(A) 83 71 82 70 71 69 63 60

V· m3/h

DpfaPa

r = 1,20 kg/m3

SKRW EC 400/60/35

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 2200 4200 600 2,90 51 0,51 8 1800 3400 350 1,70 46 0,37 6 1300 2500 150 0,71 40 0,22 4 850 1600 60 0,34 33 0,14

� 10 V� 8 V� 6 V� 4 V� 2 V

��

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 71 59 70 62 53 48 44 41 LWA Intake dB(A) 78 73 75 69 63 58 55 52 LWA Exhaust dB(A) 86 75 84 76 77 73 68 66

V· m3/h

DpfaPa

r = 1,20 kg/m3

SKRD EC 400/60/35

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 2500 5000 830 1,30 51 0,60 8 2000 3900 450 0,77 46 0,42 6 1450 2850 200 0,43 40 0,25 4 950 1850 70 0,25 33 0,14

� 10 V� 8 V� 6 V � 4 V � 2 V

��

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 76 57 76 62 61 57 50 45 LWA Intake dB(A) 86 72 85 72 71 69 66 61 LWA Exhaust dB(A) 90 74 88 81 80 77 72 66

V· m3/h

DpfaPa

r = 1,20 kg/m3

KRW EC 400/60/35

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 2200 4460 635 3,00 56 0,51 8 1750 3500 340 1,60 50 0,35 6 1350 2720 160 0,73 43 0,21 4 1000 2040 75 0,37 37 0,13

� 10 V� 8 V� 6 V � 4 V � 2 V

EC re

ctan

gula

rfa

ns

Page 55: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

SKRW EC 450/70/40 3) 6129 5420 1410 45 982 60.00.71 3.24 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

400

450 mm ø InlineVent® EC rectangular fansbackward curved, for rectangular duct size 70 x 40 cm

SKR EC – Sound insulated

� Features ofKR EC and SKR EC

� Highly efficient EC-motor forlowest operating costs.

� High pressure and high volumewith high efficiency centrifugalfan.

� Particularly easy to service(cleaning) thanks to the swing-out motor impeller unit.

� For cleaning, easy access andtherefore suitable for extractionof polluted air.

� Straight through-flow.� Compact design, convenientinstallation.

� Special features of SKR EC� Lowest sound levels for intakeand case breakout at higherpower density.

� Specification� Casing KR ECMade of galvanised steel.Flanged (20 mm) on both endsfor in-duct installation.

� Casing SKR ECAs above, but with additionalsound insulation with 50 mmthick mineral fibre board, insidelined with a sound deadeningperforated plate.

� Common features ofKR EC and SKR EC

� ImpellerCentrifugal, backward curvedimpeller made of polymer. Aero-dynamically optimised, intake airflow by means of an inlet nozzle.

� MotorEnergy-saving, speed control-lable EC-external rotor motorswith highest efficiency, protec-tion to IP 44 (SKR EC IP 54).With ball bearings, mainte-nance-free and interference-free.Motor and impeller are dynami-cally balanced.

� Motor protectionIntegrated electronic tempera-ture monitoring for EC-motorand electronics.

� Speed controlStepless speed control with po-tentiometer or stepless speedcontrol with universal controlsystem (see table). Duties at dif-ferent speeds are exemplarilygiven in the performance curve.

� Electrical connectionTerminal box (IP 54) fitted toflying lead.

� InstallationInstallation in any position.Allowance must be made for themotor swing out access.

� Sound levelsTotal sound power levels andthe spectrum figures in dB(A)are given for:

– Sound level case breakout– Sound level intake– Sound level exhaustIn the table below as well as un-derneath the performance curveyou can find additionally thesound pressure level at 4 m(free field conditions).

Lowest sound levels for intake and casebreakout at higher power density.Use in extract and fresh air systems with specific requirements for low noise levels.

Dim. in mm

Suitable for polluted air.KR EC

Dim. in mm

KRD EC 450/70/40 8173 7480 2300 54 1005 40.01.50 2.30 60 EUR EC 1) 2) 1347 PU 10 1) 1734

Type Ref. no. Air flowvolume(FID)

NominalR.P.M.

Sound press.case

breakout

Wiringdiagram

Weightnet

approx. .V m3/h min-1 dB(A) in 4m No. kg

Motorpower

kW

Current

A

max. air flowtemperature

+ °C

Universalcontrol system

Speed-potentiometer flush surface

Type Ref. no. Type Ref. no.

PA 10 1) 1735

Type Ref. no.

SKRD EC 450/70/40 A 8178 7500 1800 51 1005 60.01.44 2.24 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

KRW EC 450/70/40 6127 5450 1420 46 982 40.00.72 3.29 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

1) Multiple EC fans can normally be connected 2) alternative electronic differential pressure/temp. controller (EDR/ETR, No. 1437/1438) or three-step speed controller (SU/SA, No. 4266/4267), s. accessories3) Characteristic curve diagram on www.HeliosSelect.de

Single Phase, 230 V, 50/60 Hz, EC motor, protection to IP 54

Sound insulated model SKR EC – 3-phase, 400 V, 50/60 Hz, EC motor, protection to IP 54

Sound insulated model SKR EC – 1-phase, 230 V, 50/60 Hz, EC motor, protection to IP 54

Three Phase, 400 V, 50/60 Hz, EC motor, protection to IP 54

(Fig. similar)

Swing-out area Swing-out area

Page 56: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

401

InlineVent® EC rectangular fans 450 mm ø backward curved, for rectangular duct size 70 x 40 cm

� Accessories

Gravity shutterType VK 70/40 Ref. no. 0879Air stream operated louvres, lightgrey polymer.

External louvreType WSG 70/40 Ref. no. 0114Heavy duty construction madefrom profile anodised aluminiumextrusion.

Vol. control damper for ductingType JVK 70/40 Ref. no. 6915Casing with flanges on both sides.The control mechanism is outsidethe airstream. For electrical drive,see STM, accessory.

Circular spigotType FSK 70/40 Ref. no. 0840For cost effective adaption ofrectangular fans into circularducting systems with Ø 400mm.

Flexible connectorsType VS 70/40 Ref. no. 5699Flexible in-duct connector withflanges on both sides.

CounterflangeType GF 70/40 Ref. no. 6924Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 70/40 Ref. no. 8731For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 70/40 G4 No. 8723Type KLF 70/40 F7 No. 8647Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Warm water heater batteryType WHR 2/70/40 No. 8788Type WHR 4/70/40 No. 8789For in-duct installation.

Temperature control system forwarm water heater batteryType WHS HE 1) Ref. no. 83191) In model WHR 4/70/40 the heat output is reduced

to 2200 l/h.

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 71 64 69 54 51 48 47 44 LWA Intake dB(A) 79 74 75 71 67 57 51 47 LWA Exhaust dB(A) 88 79 86 76 75 69 65 62

V· m3/h

DpfaPa r = 1,20 kg/m3

SKRD EC 450/70/40 A

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 1800 7500 1050 1,70 51 0,50 8 1450 6100 550 0,92 47 0,32 6 1050 4350 230 0,48 40 0,19 4 700 2800 80 0,27 32 0,11

� 10 V� 8 V� 6 V� 4 V� 2 V

��

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 66 60 64 59 53 46 43 40 LWA Intake dB(A) 79 76 73 69 66 63 60 58 LWA Exhaust dB(A) 84 77 80 75 74 68 64 62

��

V· m3/h

DpfaPa r = 1,20 kg/m3

KRW EC 450/70/40

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 1440 5450 600 2,8 46 0,40 8 1130 4290 290 1,4 41 0,24 6 850 3240 120 0,60 35 0,13 4 600 2320 50 0,25 28 0,08

� 10 V� 8 V� 6 V � 4 V � 2 V

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 74 63 72 68 61 53 47 43 LWA Intake dB(A) 87 79 85 77 76 71 66 61 LWA Exhaust dB(A) 91 80 89 82 83 75 70 66

��

V· m3/h

DpfaPa

r = 1,20 kg/m3

KRD EC 450/70/40

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 2300 7480 1060 1,66 54 0,51 8 1550 6175 605 0,97 46 0,35 6 1080 4540 250 0,44 40 0,20 4 720 3130 85 0,20 32 0,10

� 10 V� 8 V� 6 V� 4 V� 2 V

� Accessory details PageShutters, grilles and louvres 420, 487 onFilters, heater batteriesand attenuators 421 onTemperature control systemsfor heater batteries 427, 432 onUniversal control system,electronic controller,speed-potentiometer 539 on

EC re

ctan

gula

rfa

ns

Saving ** with speed control

Page 57: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

402

500 mm ø InlineVent® EC rectangular fansbackward curved, for rectangular duct size 80 x 50 cm

SKR EC – Sound insulatedLowest sound levels for intake and casebreakout at higher power density.Use in extract and fresh air systems with specific requirements for low noise levels.

Dim. in mm

� Features ofKR EC and SKR EC

� Highly efficient EC-motor forlowest operating costs.

� High pressure and high volumewith high efficiency centrifugalfan.

� Particularly easy to service(cleaning) thanks to the swing-out motor impeller unit.

� For cleaning, easy access andtherefore suitable for extractionof polluted air.

� Straight through-flow.� Compact design, convenientinstallation.

� Special features of SKR EC� Lowest sound levels for intakeand case breakout at higherpower density.

� Specification� Casing KR ECMade of galvanised steel.Flanged (20 mm) on both endsfor in-duct installation.

� Casing SKR ECAs above, but with additionalsound insulation with 50 mmthick mineral fibre board, insidelined with a sound deadeningperforated plate.

� Common features ofKR EC and SKR EC

� ImpellerCentrifugal, backward curvedimpeller made of polymer. Aero-dynamically optimised, intake airflow by means of an inlet nozzle.

� MotorEnergy-saving, speed control-lable EC-external rotor motorswith highest efficiency, protec-tion to IP 44 (SKR EC IP 54).With ball bearings, mainte-nance-free and interference-free.Motor and impeller are dynami-cally balanced.

� Motor protectionIntegrated electronic tempera-ture monitoring for EC-motorand electronics.

� Speed controlStepless speed control with po-tentiometer or stepless speedcontrol with universal controlsystem (see table). Duties atdifferent speeds are exemplarilygiven in the performance curve.

� Electrical connectionTerminal box (IP 54) fitted toflying lead.

� InstallationInstallation in any position.Allowance must be made for themotor swing out access.

� Sound levelsTotal sound power levels andthe spectrum figures in dB(A)are given for:

– Sound level case breakout– Sound level intake– Sound level exhaustIn the table below as well as un-derneath the performance curveyou can find additionally thesound pressure level at 4 m(free field conditions).

Suitable for polluted air.KR EC

KRD EC 500/80/50 A 8174 8810 1400 51 1005 55.61.26 1.96 60 EUR EC 1) 2) 1347 PU 10 1) 1734

Type Ref. no. Air flowvolume(FID)

NominalR.P.M.

Sound press.case

breakout

Wiringdiagram

Weightnet

approx. .V m3/h min-1 dB(A) in 4m No. kg

Motorpower

kW

Current

A

max. air flowtemperature

+ °C

Universalcontrol system

Speed-potentiometer flush surface

Type Ref. no. Type Ref. no.

PA 10 1) 1735

KRD EC 500/80/50 B 3) 6128 10400 1800 60 1005 55.02.57 3.92 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

Type Ref. no.

SKRD EC 500/80/50 A 8299 8600 1400 48 1005 67.51.20 1.87 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

SKRD EC 500/80/50 B 8179 10650 1800 55 1005 79.52.42 3.68 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

Three phase, 400 V, 50/60 Hz, EC motor, protection to IP 54

Sound insulated model SKR EC – 3-phase, 400 V, 50/60 Hz, EC motor, protection to IP 54

1) Multiple EC fans can normally be connected 2) alternative electronic differential pressure/temp. controller (EDR/ETR, No. 1437/1438) or three-step speed controller (SU/SA, No. 4266/4267), s. accessories3) Characteristic curve diagram on www.HeliosSelect.de

Dim. in mm

KR EC 500 A, *KR EC 500 B

(Fig. similar)

Swing-out area Swing-out area

Page 58: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

403

InlineVent® EC rectangular fans 500 mm ø backward curved, for rectangular duct size 80 x 50 cm

� Accessories

Gravity shutterType VK 80/50 Ref. no. 0880Air stream operated louvres, lightgrey polymer.

External louvreType WSG 80/50 Ref. no. 0115Heavy duty construction madefrom profile anodised aluminiumextrusion.

Vol. control damper for ductingType JVK 80/50 Ref. no. 6916Casing with flanges on both sides.The control mechanism is outsidethe airstream. For electrical drive,see STM, accessory.

Circular spigotType FSK 80/50 Ref. no. 0842For cost effective adaption ofrectangular fans into circularducting systems with Ø 500mm.

Flexible connectorsType VS 80/50 Ref. no. 5700Flexible in-duct connector withflanges on both sides.

CounterflangeType GF 80/50 Ref. no. 6925Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 80/50 Ref. no. 8732For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 80/50 G4 No. 8670Type KLF 80/50 F7 No. 8654Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Warm water heater batteryType WHR 2/80/50 No. 8795Type WHR 4/80/50 No. 8796For in-duct installation.

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 68 67 60 52 52 48 43 38 LWA Intake dB(A) 76 76 64 58 56 54 50 51 LWA Exhaust dB(A) 83 79 76 72 73 67 66 66

V· m3/h

DpfaPa

r = 1,20 kg/m3

SKRD EC 500/80/50 A

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 1400 8600 780 1,30 48 0,33 8 1150 7000 400 0,72 44 0,21 6 850 4900 180 0,41 38 0,13 4 530 3200 60 0,26 32 0,10

� 10 V� 8 V� 6 V � 4 V � 2 V

��

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 75 69 73 59 58 57 54 51 LWA Intake dB(A) 81 75 78 68 65 62 57 59 LWA Exhaust dB(A) 90 82 87 81 82 75 73 73

V· m3/h

DpfaPa r = 1,20 kg/m3

SKRD EC 500/80/50 B

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 1800 10650 1750 2,70 55 0,59 8 1450 8650 950 1,50 50 0,40 6 1050 6060 400 0,68 43 0,24 4 700 3750 130 0,34 35 0,13

� 10 V� 8 V� 6 V� 4 V� 2 V

��

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 71 68 66 62 56 48 42 45 LWA Intake dB(A) 82 79 73 70 72 70 67 67 LWA Exhaust dB(A) 86 81 81 78 78 74 71 70

V· m3/h

DpfaPa r = 1,20 kg/m3

KRD EC 500/80/50 A

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 1400 8810 800 1,3 51 0,33 8 1150 7080 455 0,76 47 0,23 6 900 5400 230 0,44 41 0,15 4 700 4200 120 0,31 34 0,10

� 10 V� 8 V� 6 V� 4 V� 2 V

� Accessory details PageShutters, grilles and louvres 420, 487 onFilters, heater batteriesand attenuators 421 onUniversal control system,electronic controller,speed-potentiometer 539 on

EC re

ctan

gula

rfa

ns

Saving ** with speed control

Page 59: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

404

560 mm ø InlineVent® EC rectangular fansbackward curved, for rectangular duct size 100 x 50 cm

SKR EC – Sound insulatedLowest sound levels for intake and casebreakout at higher power density.Use in extract and fresh air systems with specific requirements for low noise levels.

Dim. in mm

� Features ofKR EC and SKR EC

� Highly efficient EC-motor forlowest operating costs.

� High pressure and high volumewith high efficiency centrifugalfan.

� Particularly easy to service(cleaning) thanks to the swing-out motor impeller unit.

� For cleaning, easy access andtherefore suitable for extractionof polluted air.

� Straight through-flow.� Compact design, convenientinstallation.

� Special features of SKR EC� Lowest sound levels for intakeand case breakout at higherpower density.

� Specification� Casing KR ECMade of galvanised steel.Flanged (20 mm) on both endsfor in-duct installation.

� Casing SKR ECAs above, but with additionalsound insulation with 50 mmthick mineral fibre board, insidelined with a sound deadeningperforated plate.

� Common features ofKR EC and SKR EC

� ImpellerCentrifugal, backward curvedimpeller made of polymer. Aero-dynamically optimised, intake airflow by means of an inlet nozzle.

� MotorEnergy-saving, speed control-lable EC-external rotor motorswith highest efficiency, protec-tion to IP 44 (SKR EC IP 54).With ball bearings, mainte-nance-free and interference-free.Motor and impeller are dynami-cally balanced.

� Motor protectionIntegrated electronic tempera-ture monitoring for EC-motorand electronics.

� Speed controlStepless speed control with po-tentiometer or stepless speedcontrol with universal controlsystem (see table). Duties atdifferent speeds are exemplarilygiven in the performance curve.

� Electrical connectionTerminal box (IP 54) fitted toflying lead.

� InstallationInstallation in any position.Allowance must be made for themotor swing out access.

� Sound levelsTotal sound power levels andthe spectrum figures in dB(A)are given for:

– Sound level case breakout– Sound level intake– Sound level exhaustIn the table below as well as un-derneath the performance curveyou can find additionally thesound pressure level at 4 m(free field conditions).

KRD EC 560/100/50 B 8175 14410 1630 60 1005 83.03.45 5.20 60 EUR EC 1) 2) 1347 PU 10 1) 1734

Type Ref. no. Air flowvolume(FID)

NominalR.P.M.

Sound press.case

breakout

Wiringdiagram

Weightnet

approx. .V m3/h min-1 dB(A) in 4m No. kg

Motorpower

kW

Current

A

max. air flowtemperature

+ °C

Universalcontrol system

Speed-potentiometer flush surface

Type Ref. no. Type Ref. no.

PA 10 1) 1735

KRD EC 560/100/50 A 8167 11270 1230 54 1005 70.81.57 2.45 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

Type Ref. no.

SKRD EC 560/100/50 B 8180 13700 1630 56 1005 100.03.26 4.98 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

SKRD EC 560/100/50 A3) 6130 10070 1230 48 1005 98.01.48 2.30 60 EUR EC 1) 2) 1347 PU 10 1) 1734 PA 10 1) 1735

Three phase, 400 V, 50/60 Hz, EC motor, protection to IP 54

Sound insulated model SKR EC – 3-phase, 400 V, 50/60 Hz, EC motor, protection to IP 54

1) Multiple EC fans can normally be connected 2) alternative electronic differential pressure/temp. controller (EDR/ETR, No. 1437/1438) or three-step speed controller (SU/SA, No. 4266/4267), s. accessories3) Characteristic curve diagram on www.HeliosSelect.de

Suitable for polluted air.KR EC

Dim. in mm

KR EC 560 A, *KR EC 560 B

(Fig. similar)

Swing-out area Swing-out area

Page 60: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

405

InlineVent® EC rectangular fans 560 mm ø backward curved, for rectangular duct size 100 x 50 cm

� Accessories

Gravity shutterType VK 100/50 Ref. no. 0881Air stream operated louvres, lightgrey polymer.

External louvreType WSG 100/50 Ref. no. 0116Heavy duty construction madefrom profile anodised aluminiumextrusion.

Vol. control damper for ductingType JVK 100/50 Ref. no. 6917Casing with flanges on both sides.The control mechanism is outsidethe airstream. For electrical drive,see STM, accessory.

Circular spigotType FSK 100/50 Ref. no. 0843For cost effective adaption ofrectangular fans into circularducting systems with Ø 500mm.

Flexible connectorsType VS 100/50 Ref. no. 5701Flexible in-duct connector withflanges on both sides.

CounterflangeType GF 100/50 Ref. no. 6926Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 100/50 Ref. no. 8733For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 100/50 G4 No. 8671Type KLF 100/50 F7 No. 8655Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Warm water heater batteryType WHR 2/100/50 No. 8797Type WHR 4/100/50 No. 8798For in-duct installation.

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 80 74 77 73 68 60 56 50 LWA Intake dB(A) 89 84 82 81 81 78 74 69 LWA Exhaust dB(A) 96 89 91 87 88 84 80 74

��

V· m3/h

DpfaPa

r = 1,20 kg/m3

KRD EC 560/100/50 B

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 1630 14410 2270 3,45 60 0,57 8 1350 11950 1300 2,00 56 0,39 6 1000 8750 580 0,91 50 0,24 4 650 5780 170 0,30 41 0,11

� 10 V� 8 V� 6 V� 4 V� 2 V

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 76 73 71 62 57 56 54 48 LWA Intake dB(A) 80 77 73 70 67 63 60 56 LWA Exhaust dB(A) 90 85 84 81 82 75 72 68

V· m3/h

DpfaPa r = 1,20 kg/m3

SKRD EC 560/100/50 B

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 1630 13700 2370 3,60 56 0,62 8 1300 11300 1250 1,90 51 0,40 6 1050 9050 680 1,10 47 0,27 4 700 5900 250 0,51 39 0,15

� 10 V� 8 V� 6 V� 4 V� 2 V

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 74 71 69 63 57 51 47 48 LWA Intake dB(A) 82 79 73 71 73 70 66 66 LWA Exhaust dB(A) 88 82 82 79 79 75 71 72

��

V· m3/h

DpfaPa

r = 1,20 kg/m3

KRD EC 560/100/50 A

Free discharge Voltage V n min-1 V· m3/h P W I A Lp dB(A) SFP kW/m3/s 10 1230 11270 950 1,50 54 0,30 8 1000 9150 500 0,85 50 0,20 6 730 6710 210 0,40 43 0,12 4 550 4720 100 0,24 37 0,08

� 10 V� 8 V� 6 V� 4 V� 2 V

� Accessory details PageShutters, grilles and louvres 420, 487 onFilters, heater batteriesand attenuators 421 onUniversal control system,electronic controller,speed-potentiometer 539 on

EC re

ctan

gula

rfa

ns

Saving ** with speed control

Page 61: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

406

180 and 225 mm ø InlineVent® rectangular fansbackward curved, for rectangular duct sizes 30 x 15 and 40 x 20 cm

Rectangular EC centrifugal fanwith backward curved impellerand swing-out motor impellerunit.

� Highly efficient high performanceimpellers.

� Use in extract and fresh airsystems for conveying higherair flow volume.

� Suitable for extraction ofpolluted air.

� Special features� High pressure and high volumespecific centrifugal fan with highefficiency.

� Particularly easy to service(cleaning) thanks to the swing-out motor impeller unit.

� For cleaning, easy access andtherefore suitable for extractionof polluted air.

� For cleaning, easy access andtherefore suitable for extractionof polluted air.

� Specification� CasingMade of galvanised steel.Flanged (20 mm) on both endsfor in-duct installation.

� ImpellerCentrifugal, backward curvedimpeller made of polymer. Aero-dynamically optimised, intake airflow by means of an inlet nozzle.

� MotorEnergy saving, speed control-lable EC-external rotor motorswith highest efficiency, protec-tion to IP 44. With ball bearings,maintenance-free and interfer-ence-free. Motor and impellerare dynamically balanced.

� Motor protectionAutomatic resetting throughbuilt-in thermal contacts withwinding connected in series.

� Speed controlStepless speed control with po-tentiometer or stepless speedcontrol with universal controlsystem (see table). Duties atdifferent speeds are exemplarilygiven in the performance curve.

� Electrical connectionTerminal box (IP 54) fitted toflying lead.

� InstallationInstallation in any position.Allowance must be made for themotor swing out access.

� Sound LevelsAbove the performance curve,total values and spectrum aregiven for:

– Sound level case breakout– Sound level intake– Sound level exhaustThe sound power level (on in-take) is additionally shown withinthe performance curve for corre-sponding control voltages.In the table below you can alsofind:

– Case breakout sound level at4 m (free field conditions).

TSW 1,5 1495 ESA 1 0238 ESU 1 0236

Speed controller

5-step transformer surface, electronic flush, electronic

Ref. no.Type Air flowvolume(FID)

NominalR.P.M.

Sound press.case

breakout

Motor power Wiringdiagram

max. air flowtemperature at

full load control

Weightnet

approx.

Type Ref. no.V· m3/h min-1 dB(A) in 4 m kW A No. +°C +°C kg

8885 KRW 180/2/30/15 540 2460 37 0.06 0.35 508 70 70 5.5

TSW 1,5 1495 ESA 1 0238 ESU 1 02368886 KRW 225/2/40/20 1020 2530 40 0.12 0.46 508 70 70 9.8

Type Ref. no. Type Ref. no.

Single phase, capacitor motor, 230 V, 50 Hz, protection to IP 44

Suitable for polluted air.

KR 180

Dim. in mm

Suitable for polluted air.

KR 225

Dim. in mm

� Note PageSelection chart 372Technical description 373Design guidelines 10 onModul. system components 370

Page 62: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

407

Rect

angu

lar

fans

InlineVent® rectangular fans 180 and 225 mm ø backward curved, for rectangular duct sizes 30 x 15 cm and 40 x 20 cm

DpfaPa

V· m3/h

r = 1,20 kg/m3

� 230 V� 170 V� 130 V � 100 V � 80 V

KRW 180/2/30/15

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 57 36 52 56 47 44 38 34 LWA Intake dB(A) 71 56 65 69 59 55 50 45 LWA Exhaust dB(A) 72 55 65 68 66 61 56 47

71

67

61

52

42

� Accessories

Gravity shutterType VK 30/15 Ref. no. 0735Type VK 40/20 Ref. no. 0874Air stream operated louvres, lightgrey polymer.

External louvreType WSG 30/15 Ref. no. 0108Type WSG 40/20 Ref. no. 0109Heavy duty construction madefrom profile aluminium extrusion.

Vol. control damper for ductingType JVK 30/15 Ref. no. 6927Type JVK 40/20 Ref. no. 6910Casing with flanges on both sides.For electrical drive, see STM,accessory.

Circular spigotType FSK 30/15 Ref. no. 0831Type FSK 40/20 Ref. no. 0832For adaption of rectangular fansinto circular ducting systems withØ 160 or 200mm.

Flexible connectorsType VS 30/15 Ref. no. 6928Type VS 40/20 Ref. no. 5694Flexible in-duct connector withflanges on both sides.

CounterflangeType GF 30/15 Ref. no. 6918Type GF 40/20 Ref. no. 6919Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 40/20 Ref. no. 8728For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 40/20 G4 No. 8720Type KLF 40/20 F7 No. 8644Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Electric heater batteryType EHR-K 6/40/20 No. 8702Type EHR-K 15/40/20 No. 8703Heating elements enclosed in agalvanised steel casing withconnecting flanges on both sides.

Temperature control system forelectric heater batteryType EHSD 16 Ref. no. 5003

Warm water heater batteryType WHR 2/40/20 No. 8782Type WHR 4/40/20 No. 8783For in-duct installation.

Temperature control system forwarm water heater batteryType WHS HE Ref. no. 8319

DpfaPa

V· m3/h

r = 1,20 kg/m3

� 230 V� 170 V� 130 V � 100 V � 80 V

KRW 225/2/40/20

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 60 42 54 58 53 52 46 32 LWA Intake dB(A) 72 60 68 68 65 60 60 49 LWA Exhaust dB(A) 75 61 70 71 66 69 65 53

72

69

6357

47

� Accessory details PageShutters, grilles and louvres 420, 487 onFilters, heater batteriesand attenuators 421 onTemperature control systemsfor heater batteries 427, 432 onSpeed controller and full motorprotection devices 525 on

��

���

Page 63: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

408

225 and 315 mm ø InlineVent® rectangular fansbackward curved, for rectangular duct size 50 x 25 cm

Speed controller

5-step transformer surface, electronic flush, electronic

Ref. no.Type Air flowvolume(FID)

NominalR.P.M.

Sound press.case

breakout

Motor power Wiringdiagram

max. air flowtemperature at

full load control

Weightnet

approx.

Type Ref. no.V· m3/h min-1 dB(A) in 4 m kW A No. +°C +°C kg Type Ref. no. Type Ref. no.

TSW 1,5 1) 1495 ESA 11) 0238 ESU 11) 02368873 KRW 225/2/50/25 1160 2680 45 0.17 0.73 508 70 60 15.0

TSW 1,5 1) 1495 ESA 3 1) 0239 ESU 3 1) 02376149 KRW 315/4/50/25 1760 1390 39 0.18 0.95 536.1 60 60 16.8

Single phase, capacitor motor, 230 V, 50 Hz, protection to IP 33 (225), IP 54 (315)

Suitable for polluted air.

KR

Dim. in mm

Lowest sound levels for intake and casebreakout at higher power density.Use in extract and fresh air systems with specific requirements for low noise levels.

SKR – Sound insulated

Dim. in mm

� Features ofKR and SKR

� High pressure and high volumewith high efficiency centrifugalfan.

� Particularly easy to service(cleaning) thanks to the swing-out motor impeller unit.

� For cleaning, easy access andtherefore suitable for extractionof polluted air.

� Straight through-flow.

� Compact design, convenientinstallation.

� Special features of SKR� Lowest sound levels for intakeand case breakout at higherpower density.

� Specification� Casing KRMade of galvanised steel.Flanged (20 mm) on both endsfor in-duct installation.

� Casing SKRAs above, but with additionalsound insulation with 50 mmthick mineral fibre board, insidelined with a sound deadeningperforated plate.

� Common features ofKR and SKR

� ImpellerCentrifugal, backward curvedimpeller made of polymer. Aero-dynamically optimised, intake airflow by means of an inlet nozzle.

� MotorThrough maintenance-free exter-nal-rotor motor, on which theimpeller is mounted. Closeddesign. Protection to IP 54(KR 225 IP 33).Winding with moisture impreg-nation. Ball bearing mounted, in-terference-free. Motor and im-peller are dynamically balanced.

� Motor protectionThrough built-in thermal con-tacts via a tripping unit (acces-sories). In case of KRW 225through built-in therm. contacts,with winding connected in se-ries, automatic resetting.

� Speed controlpossible through voltage reduc-tion by means of 5-step trans-former or electronic (stepless).Duties at different speeds areexemplarily given in the perfor-mance curve.

� Electrical connectionTerminal box (IP 54) fitted toflying lead.

� InstallationInstallation in any position.Allowance must be made for themotor swing out access. (Excep-tion: KRW 225 may only be in-stalled with inspection flap fac-ing downwards or to the side.)

6142 1770 1390 34 0.19 0.97 536.1 60 60 33.1 MWS 1,5 1947 MW 1579

Sound insulated model SKR – Single phase, 230 V, 50 Hz, capacitor motor, protection to IP 54 Transformer speed controller Full motor protection

SKRW 315/4/50/25

� Note PageSelection chart 372Technical description 373Design guidelines 10 onModul. system components 370

KR 225, *KR 315

1) Full motor protection device required, Type MW, No. 1579, see accessories.

Swing-out area Swing-out area

Page 64: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

409

Rect

angu

lar

fans

InlineVent® rectangular fans 225 and 315 mm ø backward curved, for rectangular duct size 50 x 25 cm

� Accessories

Gravity shutterType VK 50/25 Ref. no. 0875Air stream operated louvres, lightgrey polymer.

External louvreType WSG 50/25 Ref. no. 0110Heavy duty construction madefrom profile anodised aluminiumextrusion.

Vol. control damper for ductingType JVK 50/25 Ref. no. 6911Casing with flanges on both sides.The control mechanism is outsidethe airstream. For electrical drive,see STM, accessory.

Circular spigotType FSK 50/25 Ref. no. 0833For adaption of rectangular fansinto circular ducting systems withØ 250 mm.

Flexible connectorsType VS 50/25 Ref. no. 5695Flexible in-duct connector withflanges on both sides.

CounterflangeType GF 50/25 Ref. no. 6920Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 50/25-30 No. 8729For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 50/25-30 G4 No. 8721Type KLF 50/25-30 F7 No. 8645Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Electric heater batteryType EHR-K 8/50/25-30 No. 8704Type EHR-K 24/50/25-30No. 8705Heating elements enclosed in agalvanised steel casing withconnecting flanges on both sides.

Temperature control system forelectric heater batteryType EHSD 16 Ref. no. 5003

Warm water heater batteryType WHR 2/50/25-30 No. 8784Type WHR 4/50/25-30 No. 8785For in-duct installation.

Temperature control system forwarm water heater batteryType WHS HE Ref. no. 8319

� Sound LevelsAbove the performance curve,total values and spectrum aregiven for:

– Sound level case breakout– Sound level intake– Sound level exhaustThe sound power level (on in-take) is additionally shown withinthe performance curve for corre-sponding control voltages.In the table below you can alsofind:

– Case breakout sound level at4 m (free field conditions).

DpfaPa

V· m3/h

r = 1,20 kg/m3

� 230 V� 170 V� 130 V� 100 V� 80 V

KRW 225/2/50/25

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 65 44 63 59 52 51 47 43 LWA Intake dB(A) 72 57 68 60 64 64 63 60 LWA Exhaust dB(A) 78 61 74 71 70 71 67 63

DpfaPa

V· m3/h

r = 1,20 kg/m3

��

� 230 V� 170 V� 130 V� 100 V� 80 V

KRW 315/4/50/25

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 59 47 55 52 51 49 44 34 LWA Intake dB(A) 71 64 65 62 62 60 56 48 LWA Exhaust dB(A) 74 63 69 69 66 66 59 52

71

6966

60

51

DpfaPa

V· m3/h

r = 1,20 kg/m3

��

� 230 V� 170 V� 130 V � 100 V � 80 V

SKRW 315/4/50/25

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 54 45 53 39 38 35 30 29 LWA Intake dB(A) 63 61 56 49 49 46 42 35 LWA Exhaust dB(A) 70 64 65 61 63 60 54 47

6361

59

54

48

72

68

64

5756

� Accessory details PageShutters, grilles and louvres 420, 487 onFilters, heater batteriesand attenuators 421 onTemperature control systemsfor heater batteries 427, 432 onSpeed controller and full motorprotection devices 525 on

Page 65: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

8681

8181 SKRD 355/4/60/35 2800 1330 34 0.24 0.78/0.45 860 60 60 49.0 RDS 1 1314 MD 5849

410

355 mm ø InlineVent® rectangular fansbackward curved, for rectangular duct size 60 x 35 cm

� Features of KR and SKR� High pressure and high volumewith high efficiency centrifugalfan.

� Particularly easy to service(cleaning) thanks to the swing-out motor impeller unit.

� For cleaning, easy access andtherefore suitable for extractionof polluted air.

� Straight through-flow.� Compact design, convenient installation.

� Special features of SKR� Lowest sound levels for intakeand case breakout at higherpower density.

� Specification� Casing KR Made of galvanised steel.Flanged (20 mm) on both endsfor in-duct installation.

� Casing SKR As above, but with additionalsound insulation with 50 mmthick mineral fibre board, insidelined with a sound deadeningperforated plate.

� Common features ofKR and SKR

� Impeller Centrifugal, backward curvedimpeller made of polymer. Aero-dynamically optimised, intake airflow by means of an inlet nozzle.

� Motor Through maintenance-free exter-nal-rotor motor, on which theimpeller is mounted. Closed de-sign. Protection to IP 54. Wind-ing with moisture impregnation.Ball bearing mounted, interfer-ence-free. Motor and impellerare dynamically balanced.

� Motor protection Through built-in thermal

contacts via a tripping unit(accessories).

� Speed control possible through voltage reduc-tion by means of 5-step trans-former or electronic (stepless).Duties at different speeds are

exemplarily given in the perfor-mance curve.

� Electrical connection Terminal box (IP 54) fitted to flying lead.

Speed controller 5-stepwith full motor protection

Full motor protection device forconnection of built-in

thermal contacts

Ref. no.Type Air flowvolume(FID)

NominalR.P.M.

Sound press.case

breakout

Motor power Wiringdiagram

max. air flowtemperature at

full load control

Weightnet

approx.

Type Ref. no. Type Ref. no.

8692 KRW 355/4/60/35 3600 1390 42 0.37 1.90 536.1 60 60 28.4 MWS 3 1948 MW 1579

3580 1400 39 0.35 1.82 536.1 60 60 48.8 MWS 3 1948 MW 1579

8584 KRD 355/4/60/35 2840 1330 37 0.25 0.80/0.46 860 60 60 27.2 RDS 1 1314 MD 5849

V· m3/h min-1 dB(A) in 4 m kW A No. +°C +°C kg

Three phase, 230/400 V, 50 Hz, protection to IP 54

Sound insulated model SKR – Single phase motor, 230 V, 50 Hz, capacitor motor, protection to IP 54

Lowest sound levels for intake and casebreakout at higher power density.Use in extract and fresh air systems with specific requirements for low noise levels.

SKR – Sound insulatedSuitable for polluted air.KR

Dim. in mm

Single phase, 230 V, 50 Hz, capacitor motor, protection to IP 54

Sound insulated model SKR – Three phase motor, 230/400 V, 50 Hz, protection to IP 54

SKRW 355/4/60/35

� Installation Installation in any position.

Allowance must be made for themotor swing out access.

� Sound Levels Above the performance curve,total values and spectrum aregiven for:

– Sound level case breakout– Sound level intake– Sound level exhaust The sound power level (on in-take) is additionally shown withinthe performance curve for corre-sponding control voltages.

In the table below you can alsofind:

– Case breakout sound level at 4 m (free field conditions).

Dim. in mm

KRD, *KRWSwing-out area Swing-out area

Page 66: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

Kana

l-ve

ntila

tore

n

411

Rect

angu

lar

fans

InlineVent® rectangular fans 355 mm ø backward curved, for rectangular duct size 60 x 35 cm

DpfaPa

V· m3/h

� 400 V� 280 V� 200 V � 140 V � 80 V

KRD 355/4/60/35

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 57 53 53 46 46 40 37 32 LWA Intake dB(A) 70 68 63 54 55 56 55 47 LWA Exhaust dB(A) 74 68 69 64 65 61 59 56

DpfaPa

V· m3/h

� 400 V� 280 V� 200 V � 140 V � 80 V

SKRD 355/4/60/35

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 54 52 48 38 37 35 33 31 LWA Intake dB(A) 63 62 54 45 41 42 40 36 LWA Exhaust dB(A) 68 66 62 54 57 52 50 44

70

66

59

51

39

63

� Accessories

Gravity shutterType VK 60/35 Ref. no. 0878Air stream operated louvres, lightgrey polymer.

External louvreType WSG 60/35 Ref. no. 0113Heavy duty construction madefrom profile anodised aluminiumextrusion.

Vol. control damper for ductingType JVK 60/35 Ref. no. 6914Casing with flanges on both sides.The control mechanism is outsidethe airstream. For electrical drive,see STM, accessory.

Circular spigotType FSK 60/35 Ref. no. 0835For cost effective adaption ofrectangular fans into circularducting systems with Ø 355mm.

Flexible connectorsType VS 60/35 Ref. no. 5698Flexible in-duct connector withflanges on both sides.

CounterflangeType GF 60/35 Ref. no. 6923Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 60/30-35 No. 8730For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 60/30-35 G4 No. 8722Type KLF 60/30-35 F7 No. 8646Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Electric heater batteryType EHR-K 15/60/30-35No. 8706Type EHR-K 30/60/30-35No. 8707Heating elements enclosed in agalvanised steel casing withconnecting flanges on both sides.

Temperature control system forelectric heater batteryType EHSD 16 Ref. no. 5003

Warm water heater batteryType WHR 2/60/30-35 No. 8786Type WHR 4/60/30-35 No. 8787For in-duct installation.

Temperature control system forwarm water heater batteryType WHS HE 1) Ref. no. 83191) In model WHR 4/60/30-35 the heat output is reduced to 2200 l/h.

DpfaPa

V· m3/h

��

� 230 V� 170 V� 130 V � 100 V � 80 V

KRW 355/4/60/35

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 62 54 59 51 51 47 44 36 LWA Intake dB(A) 75 73 68 58 61 64 58 52 LWA Exhaust dB(A) 78 72 72 67 72 69 65 58

r = 1,20 kg/m3

75

70

6762

61

r = 1,20 kg/m3

DpfaPa

V· m3/h

��

� 230 V� 170 V� 130 V � 100 V � 80 V

SKRW 355/4/60/35

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 59 54 56 46 44 39 35 30 LWA Intake dB(A) 69 67 62 54 50 49 45 39 LWA Exhaust dB(A) 74 68 68 62 69 64 59 53

6967

62

59

49

r = 1,20 kg/m3

��

r = 1,20 kg/m3

59

53

4633

Page 67: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

412

400, 450 and 500 mm ø InlineVent® rectangular fansbackward curved, for rectangular duct size 70 x 40 cm

SKR – Sound insulatedSuitable for polluted air.KR

Dim. in mm

� Features ofKR and SKR

� High pressure and high volumewith high efficiency centrifugalfan.

� Particularly easy to service(cleaning) thanks to the swing-out motor impeller unit.

� For cleaning, easy access andtherefore suitable for extractionof polluted air.

� Straight through-flow.� Compact design, convenientinstallation.

� Special features of SKR� Lowest sound levels for intakeand case breakout at higherpower density.

� Specification� Casing KRMade of galvanised steel.Flanged (20 mm) on both endsfor in-duct installation.

� Casing SKRAs above, but with additionalsound insulation with 50 mmthick mineral fibre board, insidelined with a sound deadeningperforated plate.

� Common features ofKR and SKR

� ImpellerCentrifugal, backward curvedimpeller made of polymer. Aero-dynamically optimised, intake airflow by means of an inlet nozzle.

� MotorThrough maintenance-free exter-nal-rotor motor, on which theimpeller is mounted. Closed de-sign. Protection to IP 54. Wind-ing with moisture impregnation.Ball bearing mounted, interfer-ence-free. Motor and impellerare dynamically balanced.

� Motor protectionThrough built-in thermalcontacts via a tripping unit(accessories).

� Speed controlpossible through voltage reduc-tion by means of 5-step trans-former or electronic (stepless).Duties at different speeds areexemplarily given in the perfor-mance curve.

Lowest sound levels for intake and casebreakout at higher power density.Use in extract and fresh air systems with specific requirements for low noise levels.

Dim. in mm

6143

8196 SKRD 450/4/70/40 5430 1430 46 0.82 2.70/1.60 860 60 40 69,3 RDS 4 1316 MD 5849

8197 SKRD 500/6/70/401) 4620 920 36 0.40 1.40/0.82 860 60 60 64,1 RDS 2 1315 MD 5849

Speed controller 5-stepwith full motor protection

Full motor protection device forconnection of built-in

thermal contacts

Ref. no.Type Air flowvolume(FID)

NominalR.P.M.

Sound press.case

breakout

Motor power Wiringdiagram

max. air flowtemperature at

full load control

Weightnet

approx.

Type Ref. no. Type Ref. no.

6150 KRW 400/4/70/40 4970 1320 44 0.57 2.60 536.1 60 60 39,0 MWS 5 1949 MW 1579

6151 KRW 450/4/70/40 6650 1390 51 1.04 4.80 536.1 60 60 38,7 MWS 7,5 1950 MW 1579

4940 1330 42 0.53 2.40 536.1 60 60 62,0 MWS 5 1949 MW 1579

8694 KRD 450/4/70/401) 2) 5830 1430 47 0.82 2.80/1.60 860 60 40 48,5 RDS 4 1316 MD 5849

V· m3/h min-1 dB(A) in 4 m kW A No. +°C +°C kg

Three phase, 230/400 V, 50 Hz, protection to IP 54

Sound insulated model SKR – Single phase motor, 230 V, 50 Hz, capacitor motor, protection to IP 54

Single phase, 230 V, 50 Hz, capacitor motor, protection to IP 54

Sound insulated model SKR – Three phase motor, 230/400 V, 50 Hz, protection to IP 54

SKRW 400/4/70/40

� Electrical connectionTerminal box (IP 54) fitted toflying lead.

� InstallationInstallation in any position.Allowance must be made for themotor swing out access.

� Sound LevelsAbove the performance curve,total values and spectrum aregiven for:

– Sound level case breakout– Sound level intake– Sound level exhaustThe sound power level (on in-take) is additionally shown withinthe performance curve for corre-sponding control voltages.In the table below you can alsofind:

– Case breakout sound level at4 m (free field conditions).

1) Characteristic curve diagram on www.HeliosSelect.de 2) Dimensional drawing on www.HeliosSelect.de

KRW 450, *KRW 400Swing-out area Swing-out area

Page 68: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

413

Rect

angu

lar

fans

InlineVent® rectangular fans 400, 450 and 500 mm ø backward curved, for rectangular duct size 70 x 40 cm

� Accessories

Gravity shutterType VK 70/40 Ref. no. 0879Air stream operated louvres, lightgrey polymer.

External louvreType WSG 70/40 Ref. no. 0114Heavy duty construction madefrom profile anodised aluminiumextrusion.

Vol. control damper for ductingType JVK 70/40 Ref. no. 6915Casing with flanges on both sides.The control mechanism is outsidethe airstream. For electrical drive,see STM, accessory.

Circular spigotType FSK 70/40 Ref. no. 0840For cost effective adaption ofrectangular fans into circularducting systems with Ø 400mm.

Flexible connectorsType VS 70/40 Ref. no. 5699Flexible in-duct connector withflanges on both sides.

CounterflangeType GF 70/40 Ref. no. 6924Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 70/40 Ref. no. 8731For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 70/40 G4 No. 8723Type KLF 70/40 F7 No. 8647Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Warm water heater batteryType WHR 2/70/40 No. 8788Type WHR 4/70/40 No. 8789For in-duct installation.

Temperature control system forwarm water heater batteryType WHS HE 1) Ref. no. 83191) In model WHR 4/70/40 the heat output is reduced

to 2200 l/h.

DpfaPa

V· m3/h

� 230 V� 170 V� 130 V� 100 V� 80 V

KRW 400/4/70/40

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 64 57 61 54 54 50 45 38 LWA Intake dB(A) 74 71 66 64 66 65 60 53 LWA Exhaust dB(A) 84 75 77 74 80 76 70 63

r = 1,20 kg/m3

74

72

66

6151

DpfaPa

V· m3/h

��

� 230 V� 170 V� 130 V� 100 V� 80 V

KRW 450/4/70/40

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 71 61 70 62 59 53 49 44 LWA Intake dB(A) 79 74 73 70 70 69 66 58 LWA Exhaust dB(A) 90 80 83 81 84 81 76 68

r = 1,20 kg/m3

7978

74

6862

DpfaPa

V· m3/h

��

� 230 V� 170 V� 130 V� 100 V� 80 V

SKRW 400/4/70/40

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 62 58 59 47 44 40 36 34 LWA Intake dB(A) 69 68 61 58 53 51 46 42 LWA Exhaust dB(A) 79 73 71 67 73 70 65 58

6968

62

5647

r = 1,20 kg/m3

DpfaPa

V· m3/h

� 400 V� 280 V� 200 V� 140 V� 80 V

SKRD 450/4/70/40

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 66 64 61 49 46 40 37 36 LWA Intake dB(A) 72 70 65 62 56 51 49 44 LWA Exhaust dB(A) 80 76 74 69 68 61 60 56

72

r = 1,20 kg/m3

69

66

57

46

� Accessory details PageShutters, grilles and louvres 420, 487 onFilters, heater batteriesand attenuators 421 onTemperature control systemsfor heater batteries 427, 432 onSpeed controller and full motorprotection devices 525 on

Page 69: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

414

500 mm ø InlineVent® rectangular fansbackward curved, for rectangular duct size 80 x 50 cm

SKR – Sound insulatedSuitable for polluted air.KR

Dim. in mm

� Features ofKR and SKR

� High pressure and high volumewith high efficiency centrifugalfan.

� Particularly easy to service(cleaning) thanks to the swing-out motor impeller unit.

� For cleaning, easy access andtherefore suitable for extractionof polluted air.

� Straight through-flow.� Compact design, convenientinstallation.

� Special features of SKR� Lowest sound levels for intakeand case breakout at higherpower density.

� Specification� Casing KRMade of galvanised steel.Flanged (20 mm) on both endsfor in-duct installation.

� Casing SKRAs above, but with additionalsound insulation with 50 mmthick mineral fibre board, insidelined with a sound deadeningperforated plate.

� Common features ofKR and SKR

� ImpellerCentrifugal, backward curvedimpeller made of polymer. Aero-dynamically optimised, intake airflow by means of an inlet nozzle.

� MotorThrough maintenance-free exter-nal-rotor motor, on which theimpeller is mounted. Closed de-sign. Protection to IP 54. Wind-ing with moisture impregnation.Ball bearing mounted, interfer-ence-free. Motor and impellerare dynamically balanced.

� Motor protectionThrough built-in thermalcontacts via a tripping unit(accessories).

� Speed controlpossible through voltage reduc-tion by means of 5-step trans-former or electronic (stepless).Duties at different speeds areexemplarily given in the perfor-mance curve.

� Electrical connectionTerminal box (IP 54) fitted toflying lead.

� InstallationInstallation in any position.Allowance must be made for themotor swing out access.

� Sound LevelsAbove the performance curve,total values and spectrum aregiven for:

– Sound level case breakout– Sound level intake– Sound level exhaustThe sound power level (on in-take) is additionally shown withinthe performance curve for corre-sponding control voltages.In the table below you can alsofind:

– Case breakout sound level at4 m (free field conditions).

Lowest sound levels for intake and casebreakout at higher power density.Use in extract and fresh air systems with specific requirements for low noise levels.

Dim. in mm

6144

8198 SKRD 500/4/80/50 8050 1360 48 1.19 4.60/2.70 860 60 60 89.2 RDS 7 1578 MD 5849

Speed controller 5-stepwith full motor protection

Full motor protection device forconnection of built-in

thermal contacts

Ref. no.Type Air flowvolume(FID)

NominalR.P.M.

Sound press.case

breakout

Motor power Wiringdiagram

max. air flowtemperature at

full load control

Weightnet

approx.

Type Ref. no. Type Ref. no.

6152 KRW 500/4/80/50 9700 1370 52 1.55 6.80 536.1 60 60 66.9 MWS 10 1946 MW 1579

9540 1360 48 1.49 6.60 536.1 60 60 93.3 MWS 10 1946 MW 1579

8643 KRD 500/4/80/50 A 8430 1360 52 1.21 4.70/2.70 860 60 60 64.2 RDS 7 1578 MD 5849

V· m3/h min-1 dB(A) in 4 m kW A No. +°C +°C kg

Three phase, 230/400 V, 50 Hz, protection to IP 54

Sound insulated model SKR – Single phase motor, 230 V, 50 Hz, capacitor motor, protection to IP 54

Single phase, 230 V, 50 Hz, capacitor motor, protection to IP 54

Sound insulated model SKR – Three phase motor, 230/400 V, 50 Hz, protection to IP 54

SKRW 500/4/80/50

KRW, *KRDSwing-out area Swing-out area

Page 70: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

415

Rect

angu

lar

fans

InlineVent® rectangular fans 500 mm ø backward curved, for rectangular duct size 80 x 50 cm

� Accessories

Gravity shutterType VK 80/50 Ref. no. 0880Air stream operated louvres, lightgrey polymer.

External louvreType WSG 80/50 Ref. no. 0115Heavy duty construction madefrom profile anodised aluminiumextrusion.

Vol. control damper for ductingType JVK 80/50 Ref. no. 6916Casing with flanges on both sides.The control mechanism is outsidethe airstream. For electrical drive,see STM, accessory.

Circular spigotType FSK 80/50 Ref. no. 0842For cost effective adaption ofrectangular fans into circularducting systems with Ø 500mm.

Flexible connectorsType VS 80/50 Ref. no. 5700Flexible in-duct connector withflanges on both sides.

CounterflangeType GF 80/50 Ref. no. 6925Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 80/50 Ref. no. 8732For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 80/50 G4 No. 8670Type KLF 80/50 F7 No. 8654Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Warm water heater batteryType WHR 2/80/50 No. 8795Type WHR 4/80/50 No. 8796For in-duct installation.

� Accessory details PageShutters, grilles and louvres 420, 487 onFilters, heater batteriesand attenuators 421 onSpeed controller and full motorprotection devices 525 on

DpfaPa

V· m3/h

��

� 230 V� 170 V� 130 V� 100 V� 80 V

KRW 500/4/80/50

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 72 65 69 64 61 57 51 45 LWA Intake dB(A) 82 75 73 75 76 73 69 62 LWA Exhaust dB(A) 91 79 83 81 88 84 79 71

r = 1,20 kg/m3

82

79

7570

62

DpfaPa

V· m3/h

� 400 V� 280 V� 200 V� 140 V� 80 V

KRD 500/4/80/50 A

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 72 71 65 61 55 47 44 45 LWA Intake dB(A) 78 74 72 69 68 65 64 63 LWA Exhaust dB(A) 85 78 80 78 77 72 69 69

78

74

72

65

57

r = 1,20 kg/m3

DpfaPa

V· m3/h

��

� 230 V� 170 V� 130 V� 100 V� 80 V

SKRW 500/4/80/50

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 68 65 63 54 53 46 43 36 LWA Intake dB(A) 72 69 65 60 62 60 55 51 LWA Exhaust dB(A) 84 74 76 74 80 74 69 61

7271

6966

63

r = 1,20 kg/m3

DpfaPa

V· m3/h

� 400 V� 280 V� 200 V� 140 V� 80 V

SKRD 500/4/80/50

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 68 68 60 52 45 40 40 35 LWA Intake dB(A) 74 74 62 58 53 51 51 49 LWA Exhaust dB(A) 80 76 73 70 69 64 62 60

74

r = 1,20 kg/m3

69

69

6250

Page 71: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

416

560 mm ø InlineVent® rectangular fansbackward curved, for rectangular duct size 80 x 50 cm

SKR – Sound insulatedSuitable for polluted air.KR

Dim. in mm

� Features ofKR and SKR

� High pressure and high volumewith high efficiency centrifugalfan.

� Particularly easy to service(cleaning) thanks to the swing-out motor impeller unit.

� For cleaning, easy access andtherefore suitable for extractionof polluted air.

� Straight through-flow.

� Compact design, convenientinstallation.

� Special features of SKR� Lowest sound levels for intakeand case breakout at higherpower density.

� Specification� Casing KRMade of galvanised steel.Flanged (20 mm) on both endsfor in-duct installation.

� Casing SKRAs above, but with additionalsound insulation with 50 mmthick mineral fibre board, insidelined with a sound deadeningperforated plate.

� Common features ofKR and SKR

� ImpellerCentrifugal, backward curvedimpeller made of polymer. Aero-dynamically optimised, intake airflow by means of an inlet nozzle.

� MotorThrough maintenance-free exter-nal-rotor motor, on which theimpeller is mounted. Closed de-sign. Protection to IP 54. Wind-ing with moisture impregnation.Ball bearing mounted, interfer-ence-free. Motor and impellerare dynamically balanced.

� Motor protectionThrough built-in thermalcontacts via a tripping unit(accessories).

� Speed controlpossible through voltage reduc-tion by means of 5-step trans-former or electronic (stepless).Duties at different speeds areexemplarily given in the perfor-mance curve.

� Electrical connectionTerminal box (IP 54) fitted toflying lead.

� InstallationInstallation in any position.Allowance must be made for themotor swing out access.

Lowest sound levels for intake and casebreakout at higher power density.Use in extract and fresh air systems with specific requirements for low noise levels.

Dim. in mm

8199 SKRD 560/6/80/50 7600 880 36 0.66 2.50/1.50 860 60 60 86.9 RDS 2 1315 MD 5849

Speed controller 5-stepwith full motor protection

Full motor protection device forconnection of built-in

thermal contacts

Ref. no.Type Air flowvolume(FID)

NominalR.P.M.

Sound press.case

breakout

Motor power Wiringdiagram

max. air flowtemperature at

full load control

Weightnet

approx.

Type Ref. no. Type Ref. no.

8842 KRD 560/6/80/50 7460 880 41 0.64 2.50/1.40 860 60 60 61.9 RDS 2 1315 MD 5849

6147 KRD 560/4/80/50 11970 1350 55 2.33 7.80/4.50 860 45 45 64.1 RDS 7 1578 MD 5849

V· m3/h min-1 dB(A) in 4 m kW A No. +°C +°C kg

Three phase, 230/400 V, 50 Hz, protection to IP 54

Sound insulated model SKR – Three phase motor, 230/400 V, 50 Hz, protection to IP 54

� Note PageSelection chart 372Technical description 373Design guidelines 10 onModul. system components 370

KR 560/4, *KR 560/6Swing-out area Swing-out area

Page 72: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

417

Rect

angu

lar

fans

InlineVent® rectangular fan 560 mm ø backward curved, for rectangular duct size 80 x 50 cm

DpfaPa

V· m3/h

� 400 V� 280 V� 200 V � 140 V � 80 V

KRD 560/6/80/50

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 61 56 57 52 47 40 36 37 LWA Intake dB(A) 73 70 64 57 60 58 54 53 LWA Exhaust dB(A) 78 75 70 66 66 61 58 57

73

65

61

55

43

r = 1,20 kg/m3

DpfaPa

V· m3/h

� 400 V� 280 V� 200 V � 140 V � 80 V

KRD 560/4/80/50

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 75 63 73 68 65 60 54 48 LWA Intake dB(A) 86 76 77 77 81 78 75 67 LWA Exhaust dB(A) 93 81 86 83 89 86 82 73

86

82

78

74

65

r = 1,20 kg/m3

DpfaPa

V· m3/h

� 400 V� 280 V� 200 V � 140 V � 80 V

SKRD 560/6/80/50

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 56 55 50 41 40 37 36 33 LWA Intake dB(A) 66 64 53 44 44 42 40 40 LWA Exhaust dB(A) 74 71 63 59 58 54 51 48

66�

r = 1,20 kg/m3

58

54

49

37

� Accessories

Gravity shutterType VK 80/50 Ref. no. 0880Air stream operated louvres, lightgrey polymer.

External louvreType WSG 80/50 Ref. no. 0115Heavy duty construction madefrom profile anodised aluminiumextrusion.

Vol. control damper for ductingType JVK 80/50 Ref. no. 6916Casing with flanges on both sides.The control mechanism is outsidethe airstream. For electrical drive,see STM, accessory.

Circular spigotType FSK 80/50 Ref. no. 0842For cost effective adaption ofrectangular fans into circularducting systems with Ø 500mm.

Flexible connectorsType VS 80/50 Ref. no. 5700Flexible in-duct connector withflanges on both sides.

CounterflangeType GF 80/50 Ref. no. 6925Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 80/50 Ref. no. 8732For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 80/50 G4 No. 8670Type KLF 80/50 F7 No. 8654Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Warm water heater batteryType WHR 2/80/50 No. 8795Type WHR 4/80/50 No. 8796For in-duct installation.

� Accessory details PageShutters, grilles and louvres 420, 487 onFilters, heater batteriesand attenuators 421 onSpeed controller and full motorprotection devices 525 on

� Sound Levels Above the performance curve,total values and spectrum aregiven for:

– Sound level case breakout– Sound level intake– Sound level exhaust The sound power level (on in-take) is additionally shown withinthe performance curve for corre-sponding control voltages.

In the table below you can alsofind:

– Case breakout sound level at 4 m (free field conditions).

Page 73: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

418

630 mm ø InlineVent® rectangular fansbackward curved, for rectangular duct size 100 x 50 cm

SKR – Sound insulatedSuitable for polluted air.KR

Dim. in mm

Lowest sound levels for intake and casebreakout at higher power density.Use in extract and fresh air systems with specific requirements for low noise levels.

Dim. in mm

� Features ofKR and SKR

� High pressure and high volumewith high efficiency centrifugalfan.

� Particularly easy to service(cleaning) thanks to the swing-out motor impeller unit.

� For cleaning, easy access andtherefore suitable for extractionof polluted air.

� Straight through-flow.

� Compact design, convenientinstallation.

� Special features of SKR� Lowest sound levels for intakeand case breakout at higherpower density.

� Specification� Casing KRMade of galvanised steel.Flanged (20 mm) on both endsfor in-duct installation.

� Casing SKRAs above, but with additionalsound insulation with 50 mmthick mineral fibre board, insidelined with a sound deadeningperforated plate.

� Common features ofKR and SKR

� ImpellerCentrifugal, backward curvedimpeller made of polymer. Aero-dynamically optimised, intake airflow by means of an inlet nozzle.

� MotorThrough maintenance-free exter-nal-rotor motor, on which theimpeller is mounted. Closed de-sign. Protection to IP 54. Wind-ing with moisture impregnation.Ball bearing mounted, interfer-ence-free. Motor and impellerare dynamically balanced.

� Motor protectionThrough built-in thermalcontacts via a tripping unit(accessories).

� Speed controlpossible through voltage reduc-tion by means of 5-step trans-former or electronic (stepless).Duties at different speeds areexemplarily given in the perfor-mance curve.

� Electrical connectionTerminal box (IP 54) fitted toflying lead.

� InstallationInstallation in any position.Allowance must be made for themotor swing out access.

8295 SKRD 630/6/100/50 8450 900 43 1.17 5.00/2.90 860 60 60 112.8 RDS 7 1578 MD 5849

Speed controller 5-stepwith full motor protection

Full motor protection device forconnection of built-in

thermal contacts

Ref. no.Type Air flowvolume(FID)

NominalR.P.M.

Sound press.case

breakout

Motor power Wiringdiagram

max. air flowtemperature at

full load control

Weightnet

approx.

Type Ref. no. Type Ref. no.

8846 KRD 630/6/100/50 8740 910 44 1.10 4.90/2.90 860 60 60 84.0 RDS 7 1578 MD 5849

6148 KRD 630/4/100/50 12100 1320 55 3.31 9.90/5.70 860 55 55 95.6 RDS 11 1332 MD 5849

V· m3/h min-1 dB(A) in 4 m kW A No. +°C +°C kg

Three phase, 230/400 V, 50 Hz, protection to IP 54

Sound insulated model SKR – Three phase motor, 230/400 V, 50 Hz, protection to IP 54

� Note PageSelection chart 372Technical description 373Design guidelines 10 onModul. system components 370

KR 630/4, *KR 630/6Swing-out area Swing-out area

Page 74: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

419

Rect

angu

lar

fans

InlineVent® rectangular fans 630 mm ø backward curved, for rectangular duct size 100 x 50 cm

� Accessories

Gravity shutterType VK 100/50 Ref. no. 0881Air stream operated louvres, lightgrey polymer.

External louvreType WSG 100/50 Ref. no. 0116Heavy duty construction madefrom profile anodised aluminiumextrusion.

Vol. control damper for ductingType JVK 100/50 Ref. no. 6917Casing with flanges on both sides.The control mechanism is outsidethe airstream. For electrical drive,see STM, accessory.

Circular spigotType FSK 100/50 Ref. no. 0843For cost effective adaption ofrectangular fans into circularducting systems with Ø 500mm.

Flexible connectorsType VS 100/50 Ref. no. 5701Flexible in-duct connector withflanges on both sides.

CounterflangeType GF 100/50 Ref. no. 6926Flange frames made of galvanisedsteel for connection to ducting.

Rectangular attenuatorType KSD 100/50 Ref. no. 8733For in-duct installation on intake orexhaust side.

Air-duct filterType KLF 100/50 G4 No. 8671Type KLF 100/50 F7 No. 8655Bag filter with a large cross sectionarea. Galvanised steel casing withflanges on both sides.

Warm water heater batteryType WHR 2/100/50 No. 8797Type WHR 4/100/50 No. 8798For in-duct installation.

� Accessory details PageShutters, grilles and louvres 420, 487 onFilters, heater batteriesand attenuators 421 onSpeed controller and full motorprotection devices 525 on

� Sound LevelsAbove the performance curve,total values and spectrum aregiven for:

– Sound level case breakout– Sound level intake– Sound level exhaustThe sound power level (on in-take) is additionally shown withinthe performance curve for corre-sponding control voltages.In the table below you can alsofind:

– Case breakout sound level at4 m (free field conditions).

DpfaPa

V· m3/h

� 400 V� 280 V� 200 V� 140 V� 80 V

KRD 630/6/100/50

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 64 58 61 56 51 45 40 37 LWA Intake dB(A) 75 72 67 63 67 63 60 55 LWA Exhaust dB(A) 83 78 76 73 74 70 66 60

7570

66

61

51

r = 1,20 kg/m3

��

DpfaPa

V· m3/h

� 400 V� 280 V� 200 V� 140 V� 80 V

KRD 630/4/100/50

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 75 67 71 70 68 61 56 50 LWA Intake dB(A) 86 77 74 79 81 78 74 66 LWA Exhaust dB(A) 94 82 86 84 89 86 81 72

86

82

77

74

63

r = 1,20 kg/m3

DpfaPa

V· m3/h

� 400 V� 280 V� 200 V� 140 V� 80 V

SKRD 630/6/100/50

Frequency Hz Total 125 250 500 1k 2k 4k 8k LWA Case breakout dB(A) 63 62 57 47 42 42 37 32 LWA Intake dB(A) 72 70 61 54 53 50 48 48 LWA Exhaust dB(A) 79 76 69 66 66 62 58 54

72

r = 1,20 kg/m3

65

61

57

45

Page 75: 125 mm ø EC centrifugal in-line fansAcoustic Line · PDF file · 2017-01-13345 EC centrifugal in-line fansAcoustic Line 125 mm ø SilentBox® SB and SlimVent SVS Accessories Flexible

420

Counterflange – Flexible connectorsVolume control dampers – Servo motor

� Counterflange GFDesigned for connecting rectan-gular fans and accessories toducting where the flange framesare made of galvanised sheetsteel.

� Connectors VSFlexible ducting connector withflange frames on both ends,made of galvanised sheet steel,with sealing lip all around; leakproof to VDI 3803, temperatureresistance from –10 °C to+80 °C. The elastic sleeve inthe middle section is made ofplastic fibre bonded material.Designed to fit into rectangularfans.In order to prevent the vibrationtransmission and compensatesmall misalignments on site, theflexible connectors are fitted be-tween the ducting and fan on in-take and exhaust side.For explosion proof rectangularfans use VS Ex (explosion-proof)types.

� Volume control dampers JVKFlanged casing on both sides,made of galvanised sheet steel,designed to fit into rectangularfans. The blades are hollow andtheir shafts run embedded inpolymer guides. The externalcontrol lever adjusts all bladesequally.The control mechanism is alsooutside the airstream and se-cured against operational inter-ruptions therefore unaffected byairborne contamination.The blades create an additionalpressure loss (shown in the ad-jacent diagram) which must beconsidered when designing.

� AccessoriesServo motorSTM 10 230 V Ref. no. 8791Electric drive for opening andclosing of volume control dampersJVK. Installation in any position byusing fixing clamp (for Ø 8–26 or

8 – 26 mm) and fixing with theattached anti-rotation lockingbracket.Adjustment of shutter position byusing the gear unlock button.Output signal available to indicate“open” or “close”. Visible indicationof shutter position (0 – 90°).

� Technical dataSupply voltage 100–240 VAC Frequency 50/60 HzTorque 10 NmRotation angle 0 to 95°Operation 2.5 WRunning time (open/close) 150 sLeft / right motor rotation reversibleAmbient temp. –30 to +50 °CProtection IP 54Protection class IIDim. mm W 80 x H 124 x D 62Weight approx. 0.75 kgWiring diagram no. 1087

Pressure loss

DPt (Pa)

Flow velocity m/s

Counterflange GF

Type Ref. no.

Connector VS Type Ref. no.

Fits fan ductnominal size

mm

Connectorfor Ex-proof fans

Type Ref. no.

Dimensionsin mm

A B C D

GF 30/15 6918 VS 30/15 6928 — — 300 x 150 320 170 340 190 0.7 1.8

GF 40/20 6919 VS 40/20 5694 — — 400 x 200 420 220 440 240 0.8 2.3

GF 50/25 6920 VS 50/25 5695 VS 50/25 Ex 0265 500 x 250 520 270 540 290 0.9 2.8

GF 50/30 6921 VS 50/30 5696 VS 50/30 Ex 0266 500 x 300 520 320 540 340 1.0 2.9

GF 60/30 6922 VS 60/30 5697 VS 60/30 Ex 0267 600 x 300 620 320 640 340 1.1 3.2

GF 60/35 6923 VS 60/35 5698 VS 60/35 Ex 0268 600 x 350 620 370 640 390 1.1 3.4

GF 70/40 6924 VS 70/40 5699 VS 70/40 Ex 0269 700 x 400 720 420 740 440 1.2 3.7

GF 80/50 6925 VS 80/50 5700 — — 800 x 500 820 520 840 540 1.5 4.5

GF 100/50 6926 VS 100/50 5701 — — 1000 x 500 1020 520 1040 540 1.7 5.0

Weightapprox. kg

GF VS

Type Ref. no. Duct-fanØ mm

Fits fan ductnominal size

mm

Dimensionsin mm

A B C D

JVK 30/15 6927 300 x 150 180 320 170 340 190 3.5

JVK 40/20 6910 400 x 200 200–250 420 220 440 240 4.0

JVK 50/25 6911 500 x 250 315 520 270 540 290 5.0

JVK 50/30 6912 500 x 300 250 520 320 540 340 6.0

JVK 60/30 6913 600 x 300 285 620 320 640 340 7.0

JVK 60/35 6914 600 x 350 315–400 620 370 640 390 7.2

JVK 70/40 6915 700 x 400 355–450 720 420 740 440 9.0

JVK 80/50 6916 800 x 500 400–500 820 520 840 540 11.7

JVK 100/50 6917 1000 x 500 450–630 1020 520 1040 540 13.5

Weight approx. kg

Dim. in mm see table

Dim. in mm see table JVK

GF and VS

Auxiliary switchSTM 2P Ref. no. 8794The servo motor STM 10 230 Vcan also be operated with anauxiliary switch component.Two adjustable micro-switchesindicate the control position.The adjustable angle settings canbe set. Position indication via ad-justment ring (mechanical, snap-on).

STM 10 / STM 2P

Blade position a

in degrees


Recommended