Date post: | 14-Dec-2015 |
Category: |
Documents |
Upload: | rajendra-kamble |
View: | 10 times |
Download: | 1 times |
Team 13 – All for Angkor Final Report
Team 13: All for Angkor
Final Design Report
ENGR 339/340
5/12/06
Katie Anderson Brad Jansen Jon Larsen Andy Lynch Kirk Starnes
Team 13 – All for Angkor Final Report
© 2006 Calvin College & Katie Anderson, Brad Jansen, Jon Larsen, Andy Lynch, Kirk Starnes
Table of Contents
1. Executive Summary ............................................................................................................................. 1 2. Introduction .......................................................................................................................................... 2
2.1. Purpose ........................................................................................................................................ 2 2.2. Description .................................................................................................................................. 2 2.3. Background.................................................................................................................................. 2
3. Challenge.............................................................................................................................................. 5 3.1. Design Norms.............................................................................................................................. 5
3.1.1. Cultural Appropriateness .................................................................................................... 5 3.1.2. Stewardship......................................................................................................................... 6 3.1.3. Justice ................................................................................................................................. 6 3.1.4. Integrity............................................................................................................................... 7 3.1.5. Trust .................................................................................................................................... 7 3.1.6. Caring ................................................................................................................................. 7
3.2. Meteorology and Geology ........................................................................................................... 8 3.2.1. Geography........................................................................................................................... 8 3.2.2. Climate................................................................................................................................ 9 3.2.3. Soil Types ......................................................................................................................... 11 3.2.4. Building Use ..................................................................................................................... 12
3.3. External Dependency................................................................................................................. 13 3.4. Design Considerations............................................................................................................... 13
3.4.1. Team Knowledge.............................................................................................................. 13 3.4.2. Building Practices ............................................................................................................. 14
3.4.2.1. Building Materials.................................................................................................... 14 3.4.2.2. Building Methods..................................................................................................... 15
3.4.3. Units and Codes ................................................................................................................ 16 3.4.4. Economics......................................................................................................................... 17
4. Solution .............................................................................................................................................. 17 4.1. Schedule .................................................................................................................................... 17 4.2. Loads and Codes........................................................................................................................ 18 4.3. STAAD.Pro ............................................................................................................................... 18 4.4. Floor Slab Design ...................................................................................................................... 22 4.5. Beam and Girder Design ........................................................................................................... 24 4.6. Column Design.......................................................................................................................... 27 4.7. Foundation Design..................................................................................................................... 32 4.8. Land Development .................................................................................................................... 34 4.9. Plan Set...................................................................................................................................... 36 4.10. Promotional Material ............................................................................................................ 36
5. Cost Analysis ..................................................................................................................................... 36 5.1. Project Budget ........................................................................................................................... 37 5.2. Construction Budget .................................................................................................................. 37 5.3. Engineering Fees ....................................................................................................................... 40
6. Discussion .......................................................................................................................................... 40 7. Conclusion.......................................................................................................................................... 41 8. Recommendations .............................................................................................................................. 41 9. Acknowledgements ............................................................................................................................ 43 10. Resources ....................................................................................................................................... 44 11. Appendices..................................................................................................................................... 45
i Team 13 – All for Angkor Final Report
Table of Figures
Figure 2.3.1 The Angkor Wat temple ........................................................................................................... 4 Figure 3.2.1 Map of Cambodia showing Siem Reap location ...................................................................... 8 Figure 3.1.2 Topographical map of Siem Reap area showing AGU site ...................................................... 9 Figure 3.2.3 Monthly temperature ranges for Phnom Penh, Cambodia...................................................... 10 Figure 3.2.4 Average monthly precipitation for Siem Reap, Cambodia..................................................... 10 Figure 3.4.1 Picture of a Cambodian building under construction ............................................................. 16 Figure 3.4.2 Picture of clay bricks used in construction of concrete frame buildings ................................ 16 Figure 4.3.1 Model of structural members within STAAD.Pro.................................................................. 19 Figure 4.3.2 STAAD.Pro rendering showing the relative sizes of each structural member ....................... 20 Figure 4.3.3 Visualization of linearized loads applied to the roof structure ............................................... 21 Figure 4.5.1 Beam and girder floor system................................................................................................. 24 Figure 4.5.2 T-beam as part of a floor system ............................................................................................ 25 Figure 4.5.3 Moment graph of beam........................................................................................................... 26 Figure 4.5.4 Shear graph of beam............................................................................................................... 27 Figure 4.6.1 Interaction diagram for the 2nd floor exterior column............................................................. 29 Figure 4.6.2 Typical column detail ............................................................................................................. 31 Figure 4.7.1 Standard footing detail............................................................................................................ 33
Table of Tables
Table 3.2.1 Load table for proposed building in Siem Reap, Cambodia .................................................... 11 Table 3.2.2 Soil properties for local soil types ........................................................................................... 12 Table 3.4.1 Material costs according to U.S. Standards ............................................................................ 14 Table 3.4.2 Building material decision table .............................................................................................. 15 Table 4.4.1 General slab design choices ..................................................................................................... 23 Table 4.6.1 Summary table of column dimensions and reinforcing sizes for AGU building ..................... 32 Table 4.7.1 Summary table of footing dimensions ..................................................................................... 33 Table 5.1.1 Project budget .......................................................................................................................... 37 Table 5.2.1 Project construction cost estimate............................................................................................ 39 Table 5.3.1 Professional engineering fees .................................................................................................. 40
ii Team 13 – All for Angkor Final Report
1. Executive Summary
Team 13, comprised of Katie Anderson, Brad Jansen, Jon Larsen, Andy Lynch, and Kirk Starnes,
has been working in conjunction with architectural students from Handong Global University
(HGU) in South Korea to design the first academic building for Angkor Global University (AGU)
in the Siem Reap region of Cambodia.
The design for this building consists of two parts: the structural design of the building and the
design of the site on which the building will be located. The structural design consists of a
concrete frame including concrete slabs, columns, beams, girders, and spread footings. The site
design that fell within the scope of the project included designing a stormwater retention system,
a grading layout, and a layout for future and present utilities.
The final products of this project include a set of construction documents for the building, a cost
estimate for engineering fees as well as construction costs, a physical 3-D model, and computer
renderings including a walkthrough video of the building and still-shots of both the interior and
exterior of the building.
1 Team 13 – All for Angkor Final Report
2. Introduction
2.1. Purpose
“Angkor Global University will be the ‘Global Christian University’, educating twenty-first
century leaders for Cambodia and the world who embody excellence in both academics and
Christian moral character”. This is the vision statement that is driving the design of a Christian
university in Siem Reap, Cambodia. For senior design, team All for Angkor has been be working
in conjunction with graduate architecture students from Handong Global University (HGU) in
South Korea to complete the basic land development and structural design for the first building of
the new university. The first structure will be a building for the agricultural school and will be the
first step in making the vision of Angkor Global University into a reality.
2.2. Description
This design project includes two aspects: the structural design of the building and the design of
the site on which the building will be located. The structural design consists of a concrete frame
including concrete slabs, columns, beams, girders, and spread footings. Also, the preliminary site
design which fell within the scope of this project includes the design of a stormwater retention
system, a grading layout, and a layout for future and present utilities.
The main goal of this project has been to provide a culturally appropriate building that will fulfill
the needs of the university for years to come. It is the belief of Team 13 that this goal has been
achieved through the chosen design.
2.3. Background
On April 17, 1975, the Khmer Rouge, led by Pol Pot, invaded Cambodia and took power in the
capital of Phnom Penh. During Pol Pot’s rule, all institutions were prohibited including schools,
religion, and family. All of the people living in the cities were required to move to the
countryside and were forced into labor camps. Children were separated from their parents and
were made into soldiers or forced laborers. According to Yale University’s Cambodia Genocide
2 Team 13 – All for Angkor Final Report
Program, an estimated 1.7 million people died from torture, execution, and starvation. This was
approximately 21% of the population of Cambodia at the time.
One of the main reasons that people were killed was if they were educated. The Khmer Rouge
saw educated persons as a threat to their rule. Children, as well as adults, were questioned by
soldiers and if they appeared to be educated, they were killed immediately. As a result of the
mass killings in Cambodia during the late 1970s, as well as other social economic reasons, nearly
30% of Cambodians are illiterate.
Not only did the Khmer Rouge have implications as far as education, it also had repercussions on
family and community life. Families were split apart and communities were basically
demolished. Many children grew up as orphans and thus did not learn basic family values. This
affects the way Cambodians relate within a village. Furthermore, they do not know how to create
healthy communities. It is the belief of Professor Hakchul Kim of Handong Global University
and Team 13 that education will help with the solution of all of these problems. Through
education, the Cambodians will learn how to sustain themselves through physical means and
create stronger family and communal attachments.
Since the early 1990’s, Cambodia has gone through a series of changes that will forever transform
the country of Cambodia. In 1993, Cambodia for the first time became a constitutional
monarchy. Not only did this transformation have political implications, but it had influences in
the economy and tourism. For the first time in many years, the temple of Angkor Wat, seen in
Figure 2.3.1, opened its doors to the public.
3 Team 13 – All for Angkor Final Report
Figure 2.3.1 The Angkor Wat temple
This temple is known as one of the great mysteries of the ancient world. As a result of this,
tourism to the Siem Reap area has drastically increased. Hundreds of hotels, restaurants, and
shops have been built around the Angkor Wat temples.
With this new wave of tourism, there is a great opportunity for the local Cambodians to prosper.
Currently, 40% of the country lives below the poverty line. For this project, the goal is to disrupt
the current Cambodian culture as little as possible while still increasing the quality of living by
giving Cambodians the means to support themselves. The goal of Angkor Global University is to
meet this need. Initially, Angkor Global University will be an agricultural school where it will
meet the immediate needs of the Cambodian people by supplying them with the knowledge of
how to support themselves through agriculture. Currently, the majority of Cambodians are
subsistent farmers. Since Cambodia has a wet season and a dry season, this poses a problem for
farmers who must grow food year round. AGU’s first mission is to solve this problem. Later,
Angkor Global University plans to open a School of Business and Tourism Management. This
will allow Cambodians to profit from the growing tourism and keep the wealth in the country.
The land that Angkor Global University will be built on was donated by Governor Oung Oeun of
Siem Reap. Governor Oung Oeun visited Handong Global University in South Korea and was
pleased with the community and educational system he witnessed. Even though Governor Oung
Oeun is Buddhist, he decided he wanted a Christian University in his province.
4 Team 13 – All for Angkor Final Report
The design and construction of Angkor Global University will be completed with a number of
different participating parties. As previously stated, Calvin College will be working in
cooperation with Handong Global University in South Korea. In January 2005, the NIBC (New
International Builder’s Community) was established. Currently the NIBC, also known as “Not I
But Christ”, is working to establish kindergarten schools throughout the country, as well as
Angkor Global University in Siem Reap.
3. Challenge
As with any project, obstacles and challenges are expected. While completing the design for this
project some of the challenges that were encountered and overcome include designing with the
design norms in mind, geographical constraints, and limited structural design knowledge among
team members. These challenges and how they were overcome are discussed in the following
sections.
3.1. Design Norms
Design norms are moral principles that should be considered in the design process in order to
ensure an appropriate balance between technical and ethical concerns. When working on a
design project, it is easy to focus too heavily on the functional aspect of the project. The design
norms are important for remembering the project’s relation to people, society, and Christian
calling. The chief design norms that were considered in this project are cultural appropriateness
and stewardship.
3.1.1. Cultural Appropriateness
A culturally appropriate design is one that focuses on how the design fits into the society in which
it is placed. This includes materials used, project scale, social impact, and aesthetics. As
mentioned above, this is especially important for this project. As American engineering students
working with South Korean architecture students building a structure in Cambodia, it was
difficult to ensure that the structure fits with the Cambodian culture. One way that cultural
appropriateness is taken into account in the design is that the building has been designed as an
5 Team 13 – All for Angkor Final Report
open structure. Because of the warm temperatures and the lack of climate controls systems, an
open structure will provide additional ventilation for the building.
Not only must the actual structure be considered but the construction methods and materials used
to build the structure. The methods used in the United States for construction projects of a similar
scale are likely to be different than those implemented in Cambodia. The construction methods
that will be implemented in the future construction of the building are likely to involve more
manual labor and less machinery. The materials used to construct the building may also be
different than those used in the United States. In order to appear similar to Cambodian
architecture, the building will be constructed using a concrete frame with clay brick walls. These
materials are readily available and similar to materials currently used.
3.1.2. Stewardship
Stewardship includes not only careful use of environmental resources but also appropriate use of
human and economic resources. This is important for this senior design project primarily for two
reasons. First of all, there is a classroom budget that must be considered. This covers any costs
that may be incurred by Team 13 throughout the course of the year, including software license
costs and the cost of presentation materials. The second reason that stewardship must be
incorporated into the design is the actual construction of the building. In order to make the design
a viable option for Siem Reap, the building must be economically feasible. In Cambodia, labor is
cheap while materials are very expensive. As a result of the above factors, material usage will be
minimized in both the classroom modeling and the design for the actual construction.
One specific example of how stewardship was considered in the project was in the design of the
university parking lot. The original design for the parking lot included an asphalt paved parking
lot. This design however has been improved to be a gravel parking lot. This design is not only
more culturally appropriate but it also greatly reduces the cost of the project. Furthermore, this
will increase infiltration of stormwater, in turn decreasing the stormwater runoff. Thus the
change proved to be stewardly in relation to both finances and the environment.
3.1.3. Justice
6 Team 13 – All for Angkor Final Report
Justice is considering the rights of those that are affected by the design. For the project, this
includes students and professors at Handong Global University, NIBC, future students of Angkor
Global University, and those who live in the area around the future university. In order to make a
just design, the design must have limited negative repercussions on those surrounded by it. In
order to limit the negative effects that Angkor Global University has on its surroundings, studies
were completed to determine site runoff volumes. Adequate detention methods were then
designed to eliminate the negative impact of this runoff.
Another way that the design incorporates justice is by providing a means for food production. As
stated previously, a large portion of Cambodians are farmers and are unable to farm during the
dry season. By building an agricultural school, the design will further justice by decreasing the
number of starving citizens of Cambodia.
3.1.4. Integrity
Integrity refers to the project as a whole and its complete implementation. This includes how
different aspects of the design affect the others as well as how the design as a whole affects the
surrounding. Integrity of a design should be considered before the design is completed. In the
design, this included how the building will impact the proposed university site. As a result of
this, future expansion was incorporated into the design. The site grading and utilities were
designed in order to eliminate interference in future construction. This includes grading the site
in such a manner as to not have large amounts of stormwater runoff ponding on other parts of the
university site.
3.1.5. Trust
Trust is important in every aspect of life but it is especially important when working on a design
project. It is important that project stakeholders know that project updates and the final design
are trustworthy. This includes being truthful about the progress of the design as well as what the
final outcome will be. To exercise the design norm of trust, team All for Angkor has periodically
updated project participants as to the project status.
3.1.6. Caring
7 Team 13 – All for Angkor Final Report
Through the design of the structure, it is important to show caring to those affected here, as well
as overseas. Particularly in the design of a university, it is necessary to consider how the design
will affect those living in the area of Siem Reap. The future Angkor Global University will have
several positive impacts on the Siem Reap inhabitants including an increased food supply,
increased economic prosperity, and education.
3.2. Meteorology and Geology
3.2.1. Geography
Siem Reap is a province located by the Tonle Sap Lake in the northwest region of Cambodia (see
Figure 3.2.1).
Figure 3.2.1 Map of Cambodia showing Siem Reap location
The total area of Siem Reap covers approximately 10,300 km2 with nearly 700,000 inhabitants (as
of 1998). As seen in Figure 3.2.2 below, the area of Siem Reap, including the site of Angkor
8 Team 13 – All for Angkor Final Report
Global University, AGU, is mostly low, flat plains. The elevation contour lines on the below map
are at 10 meter intervals. The location of AGU is designated by a red rectangle.
Figure 3.1.2 Topographical map of Siem Reap area showing AGU site
As of 2005, only 3.1% of the population is 65 years of age or older. The median age of
Cambodia is approximately 20 years old. 95% of Cambodians are Buddhist while 5% claim other
religious beliefs. Currently the educational system is centered around the Buddhist temples
located throughout Cambodia.
3.2.2. Climate
The climate in Siem Reap, Cambodia is drastically different from any in the United States.
Cambodia is located a mere 11° north of the equator, which has implications on many aspects of
the design.
First, Cambodia experiences very little seasonal temperature variation. Because of this, the
building could be designed to passively maintain a comfortable temperature without furnaces and
air conditioners. The yearly temperature in Cambodia ranges from 21°C to 35°C as can be seen
in Figure 3.2.3. This meant that the building had to be designed with ventilation in mind in order
to keep the ambient temperatures within a comfortable range.
9 Team 13 – All for Angkor Final Report
0
5
10
15
20
25
30
35
40
Janu
ary
Februa
ryMarc
hApri
lMay
June Ju
ly
Augus
t
Septem
ber
Octobe
r
Novem
ber
Decem
ber
Tem
pera
ture
(o C
)
Min Temperature
Max Temperature
Figure 3.2.3 Monthly temperature ranges for Phnom Penh, Cambodia
Second, Cambodia primarily has two seasons: a wet season and a dry season. The wet, monsoon
season is typically from May to November while the dry, arid season is from December to April.
According to the research of Matti Kumma from the Helsinki University of Technology, Figure
3.2.4 shows the average monthly rainfall in Siem Reap. A typical year in Cambodia brings with
it between 900 mm and 1800 mm of precipitation, with a mere 12% taking place during the five
month long dry season.
0
50
100
150
200
250
300
Janu
ary
Februa
ryMarc
hApri
lMay
June Ju
ly
Augus
t
Septem
ber
Octobe
r
Novem
ber
Decem
ber
Ave
rage
Mon
thly
Rai
nfal
l (m
m)
Wet SeasonDry Season Dry
Figure 3.2.4 Average monthly precipitation for Siem Reap, Cambodia
10 Team 13 – All for Angkor Final Report
These issues brought to light the need to consider the loads that precipitation and winds will exert
on the building. According to the Siem Reap Weather Station, the average monthly wind speed
varies from the wet to the dry season. Average wind speeds range from 1.93 m/s to 2.58 m/s with
a yearly average speed of 2.52 m/s in the Angkor area. However, in order to ensure a structurally
sound building, a wind speed of 16 m/s was used for the wind calculations. This value is the
maximum wind speed seen in the nearby capital of Phnom Penh while the maximum wind speed
seen in Siem Reap is less than 10 m/s. This should guarantee more than adequate wind
consideration in the design of the building. As seen in Table 3.2.1, these rainfall and wind values
were used to approximate the natural exterior loads that will be exerted on the building. Rain
loads are calculated based on the maximum values seen over the past 35 years. While
consideration of rain loads was not necessary for the structural design, the calculations were
completed for the case of a future roof gutter system.
Table 3.2.1 Load table for proposed building in Siem Reap, Cambodia
Load Type Load Value (kN/m2)
Wind 1.325
Rain 0.7448
3.2.3. Soil Types
The soil types in Cambodia had to be considered in order to determine many aspects of the
design. Everything from foundation design to drainage considerations were affected by the type
of soil found on site. Without soil borings it was impossible to determine the exact bearing
strength of the soil, and therefore required that assumptions be made. As a result of this, a
bearing capacity of 2000 lb/ft2 was employed for the design, which is in accordance with
international building codes.
The soil on site is comprised primarily of either red-yellow podzol or alluvial lithosol, depending
on the exact site location. Currently the land is being used to grow southwest wet season rice,
which will prove beneficial since the building is intended to be an agricultural building and the
surrounding land is fertile.
Red-yellow podzol is a type of soil which is made up of numerous layers of varying properties. It
gets its name from the mixing of yellow, bleached soil and red, “rusty” soils. Podzol is formed
11 Team 13 – All for Angkor Final Report
by the leaching of nutrients from the upper layer to the lower layers, leaving only quartz grains on
the surface. This type of soil is commonly found in wet climates, which explains the nutrient
leaching.
Alluvial lithosol is a soil type which is high in alluvium, or soils deposited by flowing water such
as rivers. Alluvial lithosol is often clayey, rich in nutrients, and has much more structural
stability than red-yellow podzol. As can be seen in Table 3.2.2, it is desired for the building site
to be located on this type of soil due to the structural and consistency properties of the two soils.
Table 3.2.2 Soil properties for local soil types
© 1997 Cambodia-IRRI-Australia Project
Surface Red-Yellow Podzol Alluvial Lithosol
Depth 15 - 40 cm 10 - 30 cm
Texture Sandy Clay
Color Dry: pale brown or grey with pinkish tinge
Moist: light brown to light grey
Dry: dark grey or black
Moist: black
Consistency Dry: hard but loose
Moist: loose
Dry: very hard
Moist: firm
Structure None Crumb or blocky
Subsoil
Texture Loamy or Clay Clay
Color Dry: light brown to light grey
Moist: light brown to grey
Dry: grey to light grey
Moist: grey
Consistency Dry: firm to very hard
Moist: firm to hard
Dry: very hard
Moist: firm
Structure A hard ironstone layer may occur Crumb or blocky
3.2.4. Building Use
The first building of Angkor Global University will be used as an administrative and educational
building. Because of this mixed usage, it was important to consider how to best integrate both of
the building’s uses. When determining building usage, the number of occupants, number of
rooms, air flow, and any other requirements (considerations for agricultural education, etc.) were
12 Team 13 – All for Angkor Final Report
considered. The building will consist of many offices, lecture rooms, and a few laboratories, all
of which have different applied loads according to the ASCE 7.
The first floor of the building will be comprised mainly of laboratories, offices, and research
resource rooms. The second floor of the building consists primarily of classrooms and meeting
rooms. The third floor has a reduced floor area and will be used primarily for storage. To see the
architectural floor layouts for each floor, see drawings A1.1-A1.3 in Appendix B.
The standard hallways in the building are proposed to be 2.6 meters wide, which should provide
for comfortable flow of air and will be wide enough for numerous people to comfortably
navigate. Most rooms have two windows and two doors. This abundance of windows and doors
will create a very comfortable and relaxing atmosphere.
3.3. External Dependency
The external interdependancy of this project also proved to be a challenge. In order to proceed
with the structural design of the building, it was necessary to first receive preliminary
architectural information and plans. As a result of this, progress was initially slow. After
architectural plans were received, maintaining frequent communication with the architecture
students also proved difficult. This seemed to result from varying academic calendars and the
twelve hour time difference between Grand Rapids and South Korea. Consequently, while many
decisions were made by collaboration between the engineering and architectural students, some
assumptions had to be made without the input of the architectural students in South Korea.
3.4. Design Considerations
3.4.1. Team Knowledge
The engineering course work at Calvin College only includes two structural related courses:
Structural Analysis and Structural Design. Consequently, all members of Team All for Angkor
had limited experience in structural design, specifically reinforced concrete design. This resulted
in a large opportunity for the growth of engineering knowledge. The level of knowledge proved
to be sufficient for completing the prelimary structural design. It did however require
13 Team 13 – All for Angkor Final Report
assumptions to be made in areas where the necessary information was not readily available.
Nevertheless, it is the belief of Team 13 that the design will result in a structurally sound
building.
3.4.2. Building Practices
3.4.2.1. Building Materials
There are multiple types of building materials that would be possible for use in this project. The
primary building materials that are used in global commercial construction are concrete, steel,
and wood. In order to determine the most appropriate material to use for this project two
elements were considered: cost and availability of the material.
The cost of the materials was a primary driving consideration because one of the goals of the
project was to keep the final project budget to a minimum in order to keep it financially feasible.
Since cost information from Cambodia is limited, the United States cost information was used to
make a preliminary decision. Table 3.4.1 shows the three building materials mentioned as well as
the cost of each.
Table 3.4.1 Material costs according to U.S. Standards Building Material Material Cost
Concrete Block Foundation Wall $1,810 / Ton
Steel $1,975 / Ton
Wood $811 / M.S.F.
The availability of materials in the Siem Reap area is limited in many ways. On the other hand, it
is known that many large international companies have moved to the country because of the
growing tourism as a result of the opening of the Angkor Wat temples. Based upon this growth it
was apparent that steel and concrete are readily available in the area. It is also known that lumber
is available because of its use in the construction of the kindergarten buildings. However, due to
the large amount needed and the limitations in structural stability for a building this large, it was
safe to assume that lumber would not be the optimum choice. Furthermore, the use of lumber is
frowned upon because of the large amounts of recent deforestation.
14 Team 13 – All for Angkor Final Report
Based on the above information, the best choice for building material is concrete. This decision
was made by analyzing the three materials in a decision table similar to Table 3.4.2. As is seen in
the table, three questions were asked for each material and a conclusion was determined. Based
on the table, the optimum material that should be used is concrete. This is the least expensive
material, is readily available, and it fulfills all of the structural requirements. Furthermore,
concrete is a culturally appropriate material for the region in which the building will be
constructed. Thus a concrete frame was chosen for the final building design.
Table 3.4.2 Building material decision table Building Material Is it the least
expensive?
Is it available? Does it fulfill the
requirements?
Concrete Yes Yes Yes
Steel No Yes Yes
Lumber No Yes No
3.4.2.2. Building Methods
The standard Cambodian building method for a structure of the size that is required for this
project is a concrete frame and brick wall building. The first task that is performed in this process
is placing the footings for the building foundation. After the foundation has been laid, reinforced
concrete columns are poured to support the floor of the first level. With the columns in place, the
first floor is poured into a form which is support by numerous bamboo shoots. This can be seen
in Figure 3.4.1 which shows typical Cambodian construction.
15 Team 13 – All for Angkor Final Report
Figure 3.4.1 Picture of a Cambodian building under construction
This illustrates the concrete frame design being supported by bamboo network
Once the concrete frame is in place, clay bricks are laid to form the walls of the building. A
picture of these clay bricks can be seen in Figure 3.4.2. From this image it is observed that the
bricks are similar to those used in the United States.
Figure 3.4.2 Picture of clay bricks used in construction of concrete frame buildings
3.4.3. Units and Codes
In the United States of America, standard English units are very typical for civil engineering
design purposes. However, since the agricultural building will be located in Cambodia, metric
16 Team 13 – All for Angkor Final Report
units were used for all construction documents. As a result of this, while many of the structural
calculation were orginally computed using English units, the final dimensions and bar sizes were
converted to their metric equivalent. This will allow for easy use of the structural plans during
building construction.
Standardized building codes for Cambodia do not currently exist. Because of this, international
building codes were used for the design and analysis of this project. The codes which were used
are the ACI 318-05 metric and English versions. While regional building codes would allow a
more efficient design of the building, the ACI 318-05 will provide the necessary information to
design a more than adequately safe building. The international building code was also
supplemented by the ASCE Bulletin 7-98 for load calculations.
3.4.4. Economics
As with any project, finances always must be considered. In order to make the building
financially feasible for AGU, efforts had to be made to reduce all possible costs. In Cambodia,
labor is relatively inexpensive in comparison with material costs. In the United States, the
opposite is true. Thus in the United States, efforts are made to reduce labor costs by simplifying
design while possibly at the expense of additional material. On the contrary, material useage for
the agricultural building has been reduced where possible in order to most effectively keep the
cost of the building to a minimum.
For additional information related to the project and construction budgets, refer to section 5 –
Cost Analysis.
4. Solution
4.1. Schedule
In order to ensure the timely completion of the design project, a project schedule was created and
maintained throughout the course of the project. This schedule tracked the progress and
completion of tasks such as project research, structural design, and creation of a 3-D computer
model. Throughout the year, the schedule was updated to reflect significant changes in the
timeline of the project. To see the final project schedule, reference Appendix C. This schedule,
as well as weekly status reports, helped to keep the project on track all the way to completion. In
17 Team 13 – All for Angkor Final Report
fact, according to the final schedule, the project should be completed by the 12th of May. With
proper task management, Team 13 completed the design and all deliverables one week ahead of
schedule.
4.2. Loads and Codes
When designing a building, the first calculations made have to do with “the loads and the code.”
As previously stated, the codes used for this design were the ASCE 7 and the ACI318-05. Load
calculations are of great importance for the design of a building. The material and thickness of
structural members is dependant on the loads they will need to withstand.
Because of the location of Angkor Global University, there were several environmental
considerations that had to be accounted for in the load calculations. First of all, because of the
warm climate with little variance in temperature, snow loads were not considered in the design.
Secondly, while a rain load was calculated, this will also not play a factor in design because all of
the rainfall on the roof is designated to simply run off the roof with no gutter system.
Accordingly, the roof was designed with a large overhang to avoid rainwater from falling into the
building. The third environmental consideration that played a large role in our design was wind.
The wind speed used in the design was 16 m/s which is the maximum wind speed observed in the
neighboring city of Phnom Penh.
For more details on load calculations, see Appendix A-1.
4.3. STAAD.Pro
In order to design the structural members of the building, moment, shear, and deflection values
needed to be calculated based on the anticipated loading seen in the building. Due to the
complexity of the structure, the program STAAD.Pro was used to calculate the necessary values
for each member. STAAD.Pro is a widely used structural analysis program capable of analyzing
hundreds of structural members under dozens of different loading scenarios. But before using
any of the STAAD.Pro results, hand calculations were made in order to verify the accuracy of
certain values and ensure that the program was working properly.
18 Team 13 – All for Angkor Final Report
Within STAAD.Pro, a set of nodes are defined, each node representing the intersection of two or
more structural members. Once each node has been defined in three-dimensional space, the
structural members are laid out between the nodes. Next, support conditions are applied where
necessary, which, in this design, are fixed supports at the base of each column. Figure 4.3.1
shows the STAAD.Pro model including all structural members and supports.
Figure 4.3.1 Model of structural members within STAAD.Pro
From this point, each member is given a material definition (concrete, aluminum, steel, etc.) and a
geometric shape, the sum total of which is shown in Figure 4.3.2.
19 Team 13 – All for Angkor Final Report
Figure 4.3.2 STAAD.Pro rendering showing the relative sizes of each structural member
Finally the loads are applied to each member. Included within this aspect of the model are
different loads representing the selfweight of the members, building dead loads, building live
loads, and wind loads. In order to calculate the load applied to each member, tributary widths for
each member were calculated and used to determine the force per unit length which would be
applied to each member. This approach was used for dead loads, live loads, and selfweight loads.
One hundred thirty different loads in all were applied to the building. From these loads, a half-
dozen load cases were defined based on ASCE load factoring, and the load case which generated
the highest moments and deflections was used as the design case. Figure 4.3.3 shows the dead
loads and selfweight loads applied to the roof structure of the building.
20 Team 13 – All for Angkor Final Report
Figure 4.3.3 Visualization of linearized loads applied to the roof structure
In addition to this first model, a ‘cracked’ model was generated within STAAD.Pro. This model
was created to simulate the effects of long-term loading on the concrete frame and the cracks
which would form as a result of creep and settling. In order to calculate the moment distribution
and deflections of the cracked structure, a new moment of inertia had to be calculated for each
structural member.
When a concrete structural member is under load, cracks will form in the areas of the member
which are in tension, as concrete has negligible tensile strength. Therefore the moment of inertia
of each member will be decreased by a certain amount. This reduction is a function of the
member’s initial geometry, the strength of the concrete, the strength of the reinforcing steel, and
the amount of reinforcing steel within the member. Once the ‘cracked’ moment of inertia had
been calculated, the new section properties were applied to the STAAD.Pro model and the
structure was reanalyzed. The resulting data showed that there would be negligible changes in
both the moment distribution and deflection of the structure, which verified the integrity of the
model. Once both models were complete, STAAD.Pro analyzed them and returned moment,
shear, deflection, and rotation values for each member within the structure.
In order to make use of this data, a spreadsheet was created in Excel which would parse the
thousands of lines of data from STAAD.Pro and display a graph showing the moment or shear
along any given continuous beam, girder, or column. This spreadsheet greatly expedited the
21 Team 13 – All for Angkor Final Report
process of retrieving the necessary data from STAAD.Pro, and allowed for quickly viewing
snapshots of the building in order to see how changes made to the model affected the final
moment and shear distribution.
For figures and details regarding the Excel spreadsheet, refer to section 4.5 – Beam and Girder
Design.
4.4. Floor Slab Design
The floors of the agricultural building were designed using a system of continuous one-way slabs.
When designing a slab, it is typical to assume that it will act as a series of strips of slab with a
standard width of 1-ft. The required depth of each floor slab was based on Table 9.5(a) from the
ACI 318-05 code. The table provides a minimum thickness based on the distance the slab is
required to span. According to the code, a slab with one end continuous should have a minimum
thickness of ( ), where l is the span of the slab. Once these minimum slab thicknesses were
calculated, the slab’s serviceability was evaluated based on the maximum moment and shear
forces the slab would have to withstand. For a more detailed account of slab design calculations,
see Appendix A-2. After it was determined that the depth of the slabs was adequate, the
reinforcement for the slab was designed.
24/l
The thickness of the slab is important not only to resist the necessary forces but also for
determining the fire rating of a structure. According to Reinforced Concrete: Mechanics and
Design, the fire rating of a floor slab is the number of hours necessary for the temperature of the
unexposed surface to rise by a given amount, generally 250oF (MacGregor, pg 383). According
to this, the slabs designed for the agricultural building have a fire rating of at least 3-hours.
A concrete slab has flexural reinforcement in both the positive and negative moment areas (the
top and bottom of the slab) in order to minimize deflection. The size and spacing of the
reinforcement is based on a minimum area of steel per foot of slab required by the ACI Code.
Concrete slab reinforcement differs from other structural concrete elements in that slabs require
shrinkage and temperature reinforcement perpendicular to the primary flexural reinforcement.
Because a slab’s depth is less than that of the supporting beams, the concrete in the slab will
22 Team 13 – All for Angkor Final Report
shrink at a greater rate than the concrete in the beams. This may lead to shrinkage cracks in the
slab. Shrinkage reinforcement will minimize cracking that would otherwise result.
Another aspect of slab design that was considered was the minimum concrete cover necessary
over the reinforcement. Cover is necessary to develop a bond between the steel reinforcement
and the concrete as well as to provide a wearing surface, corrosion resistance, and fire resistance
(MacGregor, pg 383). According to the ACI Building Code, a 40 mm cover is required for slabs
exposed to the weather and a 20 mm cover is required for slabs that are not exposed to the
weather. Thus, 40 mm of cover was used when designing the roof slab and 20 mm cover was
used to design the interior slabs.
Given the previous design requirements and considerations, Table 4.4.1 shows the general design
choices that were used for design. For more design details, see Appendix A-2 for slab
calculations and Appendix B for slab design schedules.
Table 4.4.1 General slab design choices 1st and 2nd Floor Slab
Thickness (mm): 165
Reinforcement:
Negative (top): Use No. 4 @ 270 mm
Positive (bottom): Use No. 4 @ 400 mm
Temp & Shrinkage: Use No. 4 @ 400 mm
3rd Floor Slab
Thickness (mm): 205
Reinforcement:
Negative (top): Use No. 4 @ 200 mm
Positive (bottom): Use No. 4 @ 300 mm
Temp & Shrinkage: Use No. 4 @ 330 mm
Upper and Lower Roof Slab
Thickness (mm): 195
Reinforcement:
Negative (top): Use No. 4 @ 330 mm
Positive (bottom): Use No. 4 @ 330 mm
23 Team 13 – All for Angkor Final Report
Temp & Shrinkage: Use No. 4 @ 330 mm
4.5. Beam and Girder Design
There are two options for beam and girder design in a building as large as the agricultural
building at AGU: steel and concrete. The agricultural building will be constructed entirely of
concrete and as such, the beams and girders were designed with that in mind. A reinforced
concrete design is the clear choice in this situation as it is culturally appropriate and was specified
by the architects. The design was accomplished using Building Code Requirements for Structural
Concrete and Commentary (ACI 318M-05) along with other reference materials.
Once reinforced concrete was chosen as the design material the next step was to decide if the slab
would be supported by a one-way or a two-way system. A one-way slab is supported on two
opposite sides so that bending occurs in only one direction. It has the advantages of being the
most basic design as well as the most common. A two-way system is supported along all four
edges and has bending in two directions perpendicular to each other. Since a one-way slab is
much easier to design and construct, the design initially proceeded with a one-way system and
was later confirmed as a legitimate design decision.
The specific one-way system designed for the agricultural building is called a beam and girder
system. The beams and girders are placed monolithically with the slab. An example of a beam
and girder systems can be seen in Figure 4.5.1.
Figure 4.5.1 Beam and girder floor system
In this system the slab is supported by beams and girders, which are in turn supported by
columns. Other systems do exist, but they often make use of precast concrete which would be
24 Team 13 – All for Angkor Final Report
much less economical in this situation. Continuous T-beams, as seen in Figure 4.5.2, are chosen
because of the monolithic nature of the floor slab and the multiple gaps along the line of nearly
every beam that must be spanned. There are three major stages in the design of a continuous
beam: design for flexure, design for shear, and design of bar details.
Figure 4.5.2 T-beam as part of a floor system
The first step in the design process is to choose a beam depth and width. For aesthetic and
convenience purposes, the depths of all beams and girders have been set at a standard depth. The
first, second, and third floors have been set at 600 mm and the roof beams and girders have been
set at 450 mm. The final sizes are available in the beam and girder schedules in the final plan set
and can also be seen in Appendix B.
Next the moments must be calculated to determine the effects of flexure on the beams and
girders. In order to greatly simplify the process as well as ideally eliminate human error in the
calculations, STAAD.Pro was used to compute the moments along every beam and girder in the
building. The data from STAAD.Pro was then put into a Microsoft Excel spreadsheet which
provides graphs such as the sample graph seen in Figure 4.5.3. Once provided with the moments,
the total area of reinforcing steel can be determined.
25 Team 13 – All for Angkor Final Report
-800
-600
-400
-200
0
200
400
6000 9.6 19.2 28.8 38.4 48Dist (m)
Figure 4.5.3 Moment graph of beam
Determining the necessary reinforcing steel was one part of the design where engineering
judgment proved crucial. The calculated required area of steel was only the minimum amount of
steel required. This area of steel does not indicate which size of bars to satisfy the required area,
nor the number of bars. The goal of the structural engineer is to meet the minimum reinforcing
requirements, thus creating a safe and sturdy building, while at the same time minimizing the
amount of required material to make the design as cost effective as possible. There were several
guidelines followed in the decision-making process. Bar sizes should be at least two sizes apart
so that the construction crew can visually tell them apart and not get them mixed up during the
building phase. The bars must be able to fit within the specified width of the beam so extremely
large bars cannot be used in every case. Finally, two bars must run continuously on both the top
and bottom of each beam in order to support the stirrups, so choosing too large of a bar is a waste
of materials. For the design of the agricultural building, only #19 and #29 bars were used to keep
the design as simple as possible. Using a combination of these two bars sizes, it was possible to
attain an area of steel close to the required minimum in nearly every case.
Looking again at Figure 4.5.3, each beam has negative and positive moments. The negative
moments occur at the supports of the beam and the positive moments occur over the mid-span of
each beam. Additional reinforcing steel may be necessary at points of tension, but unnecessary at
points of compression. The additional steel may be cutoff at flexural cutoff points. The practice
of cutting off extra reinforcing not only saves materials, but extending it into compression zones
can have a negative effect on the strength of the beam.
26 Team 13 – All for Angkor Final Report
Besides being designed for flexural forces, shear forces must also be taken into consideration in
the design of a beam. Like the moment values, STAAD.Pro, in combination with the Excel
spreadsheet mentioned earlier, provided a graph, as seen in Figure 4.5.4, of the values for shear
through the beams and girders.
-400
-300
-200
-100
0
100
200
300
4000 9.6 19.2 28.8 38.4 48Dist (m)
Figure 4.5.4 Shear graph of beam
The shear values were used to determine if stirrups were required, and if so at what spacing they
must be placed. The most commonly used stirrup size is a #10 which was chosen for this project.
The selected stirrup type is a single-loop stirrup which is generally satisfactory for beam widths
600 mm and under. Multiple stirrup spacings in a single beam can be used in cases where a very
small spacing is required for only a small section of the beam. By increasing the stirrup spacing
when the shear is sufficiently reduced, large quantities of materials can be saved.
This design process strictly follows the Building Code Requirements for Structural Concrete and
Commentary (ACI 318M-05). Appendices A-3 and A-4 have examples of the spreadsheet used
to design the beams and girders for the agricultural building. The spreadsheet was created using
an example from Reinforced Concrete: Mechanics and Design which incorporated relevant
sections of the structural concrete code.
4.6. Column Design
The primary variables used to design concrete columns are the axial loads going into the columns
as well as the moments at the top and bottom of the column. In order to find the loads being
27 Team 13 – All for Angkor Final Report
carried by the column, the loading on the beams and the girders first had to be determined. The
loads in the beams and girders represent the tributary area of floor space that is carried by an
individual column which consists of both the dead and live loads. Because this load is applied on
each floor, the columns are expected to increase in size as each floor is added. This being said,
the top floor will have the smallest column dimensions and then the floor below will increase
slightly due to the additional loads being applied as well as the loads from the floor above.
Since there are a large number of variables to be considered in determining the loading of the
columns, it was decided to use STAAD.Pro to analyze the reactions the columns were subjected
to, due to its simplicity and accuracy. This was also a benefit to the team because STAAD.Pro
performed the necessary moment and deflection calculations required to complete the necessary
column design calculations.
The calculation of a concrete column consists of two primary parts, the column dimensions and
the required reinforcing. In order to calculate the column design, example 11-1 in Reinforced
Concrete: Mechanics and Materials was used in supplement to the ACI code. This example
analyzes column dimensions and reinforcing information under different strain conditions to
create points on an interaction diagram, which graphically shows the relationship of axial loading
and moments on the specified column. These five points form an “envelope” curve on the
interaction diagram that illustrates the structural limits of the specified column. The five points
represent the load for the axial loaded, for the balanced failure condition (εs1 = -εy), for z equal to
-2, for z equal to -4, and for the axial tension condition. An example of an interaction diagram
produced from these five points can be seen in Figure 4.6.1.
28 Team 13 – All for Angkor Final Report
2nd Floor Exterior Column Interaction Diagram
0
1000
2000
3000
4000
5000
6000
0 100 200 300 400 500 600
Moment, Mn and φMn [ft*kips]
Axi
al L
oad,
Pn
and φ
Pn [k
ips]
φPn, φMnPn, MnφPn (max)Design Points
Figure 4.6.1 Interaction diagram for the 2nd floor exterior column
From the figure it is noted that there are in fact two curves and one straight line. The green curve,
or the curve labeled “Pn, Mn”, represents the maximum limits of the specified column. The blue
line shows similar characteristics to the green line and that is because it represents 70% of the
capacity for the column. The 30% reduction from the maximum column capacity is an industrial
standard for a factor of safety and is specified in the ACI codebook. This factored curve is the
curve that the column must be designed for. The final line on the interaction diagram is the
maximum allowable axial load that can be carried by the column. This is calculated by applying
the same 30% reduction factor to the maximum load on the blue line.
The actual design of the columns is based solely on the interaction diagram. For the agricultural
building, the columns on every floor were arranged into two groups based on similar loading
conditions. It turned out that these two groups were the interior columns and the exterior
columns. This can be explained by the fact that the interior columns had to carry dead loads and
live loads that came from all four sides of the column, whereas the exterior columns primarily
carried loads from the interior face. Once the columns were grouped together, the loads into each
29 Team 13 – All for Angkor Final Report
column were obtained from STAAD.Pro, and the moment used in each column was the maximum
moment between the top and bottom of the column. The column’s individual loading conditions
were then graphed on the respective group interaction diagram (for Figure 4.6.1 the column group
is the 2nd story exterior columns). The final part of the column design was to change the column
dimensions and reinforcing in Excel until all of the column information fell within the factored
loading capacity curve (the blue curve).
Once the dimensions of the column and the reinforcing size and quantity are determined, the ACI
code requires that some additional factors be determined. One such variable is to determine if the
building represents a sway or non-sway frame. This factor is determined by finding out if the
columns are “slender” or not. The slenderness test can be found in the ACI 10.12.2. The
slenderness test compares the length of the beam and the radius of gyration against the ratio of the
moments acting at the top and bottom of the column. This test can be found in the accompanying
Calculation Notebook under the column section. The results of the test proved that every column
group was slender except for the third floor exterior group. In order to keep calculations uniform
the building was calculated as a sway building which only applies an additional factor of safety to
the group of non-slender columns.
Since the building was determined to be a sway frame, an additional calculation was required by
the code. This calculation is called a P-Delta analysis and was performed by STAAD.Pro. What
this additional condition does in the STAAD.Pro model is that it applies the moments from
loading variations to the columns which cause a slight deflection at the top of the columns. Next
STAAD.Pro applies the loads to the already deflected columns which increases the moment
slightly since the column is offset from its center of gravity. In order to get an accurate result,
STAAD.Pro was instructed to perform this process ten times which increased moments in many
columns, therefore increasing the column dimensions and reinforcing size.
With the final column sizes determined, the last two variables required by the ACI code are the
lap splice length and the tie spacing. The lap splice is the height that the reinforcing from the
floor below must continue into the column of the floor above. The tie spacing is the required
spacing that stirrups must be placed around the reinforcing in each column. Both of these
variables are pictured in Figure 4.6.2 where the lap splice is called out and the tie spacing is
shown as the variable P. The lap splice length conditions are found in ACI 12.17 and are based
on the diameter of the reinforcing and the loading properties of the steel and concrete. The tie
30 Team 13 – All for Angkor Final Report
spacing conditions are found in ACI 7.10.5.2 and are determined by finding the smallest spacing
from three conditions. The results of the lap splice and tie spacing for each column group can be
found in the Calculation Notebook under the column section.
Figure 4.6.2 Typical column detail
Rather than designing each individual column with its own unique dimensions and reinforcement,
columns were grouped together to maintain a certain degree of simplicity for construction. This
was done in order to help ensure that the correct rebar sizes and concrete forms will be used in the
column construction since it will reduce the complexity of the building. A summary table that
displays the resulting column sizes and reinforcing size from the Calculation Notebook can be
seen in Table 4.6.1.
31 Team 13 – All for Angkor Final Report
Table 4.6.1 Summary table of column dimensions and reinforcing sizes for AGU building Column Group
Exterior Interior
Support Columns
Dimension [mm] 460 540
Bar Sizing #25 #25
Number of bars 8 8
First Floor Columns
Dimension [mm] 450 440
Bar Sizing #25 #25
Number of bars 8 8
Second Floor Columns
Dimension [mm] 400 410
Bar Sizing #29 #19
Number of bars 8 4
Third Floor Columns
Dimension [mm] 410 350
Bar Sizing #25 #19
Number of bars 8 4
4.7. Foundation Design
Because the building is going to essentially be built upon concrete pilings, a spread footing
needed to be designed for the base of each column. The vertical support reaction at the base of
each column was calculated with STAAD.Pro, and was used as the design load for the spread
footing. Due to the symmetry of the building about both ground axes, there were essentially only
four different magnitudes of loads being applied by the columns, and therefore required the
design of only four footings. For simplicity, square footings were designed in every instance.
Figure 4.7.1 shows the standard footing detail, with the applicable dimensions being found in
Table 4.7.1. For sample calculations and complete footing specifications, see Appendix A-6.
32 Team 13 – All for Angkor Final Report
Figure 4.7.1 Standard footing detail
Table 4.7.1 Summary table of footing dimensions Footing Dimension (mm)
A B C D E F G H
F0.1 5000 340 76 600 485 510 390 230
F0.2 6000 650 76 700 560 600 390 230
F0.3 6600 530 76 750 610 650 390 230
F0.4 7250 470 76 850 710 750 390 230
In accordance with international building codes, a soil bearing pressure of 2000 psf was used for
the design due to lack of specific site information from Cambodia. Also, a concrete strength of
3500 psi was used for calculations, which is significantly lower than the 5000+ psi used in
commercial concrete buildings in the United States. Aside from these two educated assumptions,
the design of the spread footings is based on calculated data. All footings were designed
following the ACI code along with example calculations.
Determining the size of the spread footing is a very simple calculation of dividing the loads
applied to the footing by the soil bearing pressure. This yields an area, which is used to calculate
the length of a side of the square footing. Next, the magnitude of punching shear from the
column needed to be calculated and compared to the strength of the footing in order to determine
whether the footing would be strong enough to support the column. In one instance, the size of
the column needed to be increased in order to prevent excessive punching shear being applied to
the foundation. Next, the reinforcing steel needed to be calculated and defined. Calculations
from the ACI code yielded a minimum required area of steel which needed to be present along
33 Team 13 – All for Angkor Final Report
the bottom of the footing in each direction. This area was used to determine a size and number of
reinforcing rods which would satisfy this requirement. Throughout the design of the spread
footings, only bar sizes 19, 29, and 43 were used in order to make for a more efficient and simple
construction. Finally, the reinforcement between the column and the footing was calculated,
including minimum development lengths with calculations to verify that the footing was large
enough to be able to have the specified development length.
4.8. Land Development
For this portion of the design project, it was Team 13’s goal to produce a general site plan for the
location of the proposed agricultural facility that clearly conveys the design of necessary sanitary
sewer and watermain systems, as well as necessary stormwater management. In general, this
process requires both the knowledge of regional design guidelines and detailed topographic
information. However, since this building is to be constructed in an area of the country where
such information has not previously been in great demand, it is in turn not readily available for
the purpose of such design. Due to this lack of site-specific information, some significant
assumptions were required for the completion of the site development.
The first assumption that was made dealt with grading the proposed site in order to effectively
handle surface runoff and protect the proposed building from the dangers of flooding. Since there
was no detailed, site specific topographic information with which to complete the design, it was
assumed that the surrounding terrain was essentially flat, and any grading was completed using
the elevation of the building corners as a datum. This assumption was made with some measure
of confidence given the evidence that was observed from regional topographic information, as
well as the account of Professor De Rooy, who has personally visited the site of the proposed
building and provided testimony to its flat nature.
Some other design features relating to site grading include a proposed gravel parking facility
located along the northwest and northeast faces of the building, a two-meter wide concrete
walkway around the entirety of the building with an adjacent gravel infiltration area designed to
handle runoff from the roof of the building, and a vegetated swale to the northeast and northwest
of the parking lot to handle any parking lot runoff. The gravel parking lot was designed with a
capacity of approximately one hundred cars to provide for the parking needs of the faculty and
any prospective students. Both the parking lot and sidewalk were designed with a two percent
34 Team 13 – All for Angkor Final Report
slope away from the building to provide for the necessary conveyance of stormwater runoff. Also
of note is the fact that a gravel parking lot was chosen over the previous idea of an asphalt
parking area. A gravel surface will allow for greater infiltration rates than asphalt, and does away
with the need for stormwater collection features including curb and gutter, catchbasins, manholes,
storm sewer piping, and detention storage. Gravel is also a more economically feasible choice for
the proposed project. A five percent slope on the sides of the building opposite the parking lot
also provide for necessary stormwater conveyance away from the base of the building. The
relatively sandy soil in the area of the proposed building will aid a great deal in the handling of
excess runoff produced by the proposed building.
Another important design decision that was made was to assume that it would be unreasonable to
have sanitary sewer extended to the site, and to rather design a sanitary system for the building
that includes the installation of two septic tanks and the necessary piping for a leach field. The
volume requirements of the proposed septic system were calculated given figures for water
consumption provided in Wastewater Engineering: Treatment, Disposal, and Reuse, Third
Edition, by Metcalf and Eddy, Inc. Based on a capacity of one hundred individuals, using
approximately ten gallons per day each, and an average retention time of five days the septic
tanks were sized to hold a volume of five thousand gallons. For purposes of redundancy and
contingency storage, two septic tanks, each with a volume of three thousand gallons were called
for in the design. The associated sanitary sewage disposal field was also designed following an
example laid out in Wastewater Engineering: Treatment, Disposal, and Reuse. Based on a
conservative assumption for the soil’s percolation rate, these calculations resulted in the need for
four thirty-five meter trenches to be placed perpendicular to the assumed groundwater flow
direction, which was to the south toward the Tonle Sap Lake. (Please refer to Appendix A-7 for
septic system calculations) Team 13 is confident that this design is sufficient to meet the sanitary
sewage needs of the proposed building.
With regard to other utilities such as water, electricity, phone, and internet, there is little
information available as to the existing infrastructure in the area of the proposed building.
Research has shown that a power grid does exist within somewhat close proximity the site with
the capacity to extend to the site, but it is unknown if there are plans to extend service to the site
in the near future. It is also unknown whether the same can be said regarding any sort of
watermain within reach of the site. The use of a well would be necessary in the event that such
35 Team 13 – All for Angkor Final Report
access is unavailable. Whatever the specific case may be, approximate water, electric, phone, and
internet connections have been shown as a part of our site plan.
4.9. Plan Set
In order to clearly display the structural design as well as the land development for Angkor
Global University, Team 13 developed a set of drawings of the building and the surrounding area.
This set includes four different drawing categories. The first section of the plan set includes the
civil drawings. This consists of a site layout, a grading plan, and a layout for proposed utilities.
Following the civil drawings are the architectural drawings. These drawings show floor plans
that dictate room usage. Along with the the floor layouts, the architectural drawings include
section cuts through the building with elevations shown for each floor level. The next drawing
category is foundation drawing. This includes the foundation plan as well as the foundation
schedule. The final drawings are the structural plans. This includes the framing plans, structural
schedules, and details. Structural schedules were utilized for clear communication of structural
members.
4.10. Promotional Material
As the design of a building consists nearly entirely of a set of drawings supported by calculations,
it was apparent that something needed to be created for presentation purposes. A physical 3-D
model was created with the help of Pete VanDyk in order to give a scale representation of the
building, and a virtual walkthrough was generated using SketchUp to give a feel to how the
building will look when finally constructed. In addition to these two models, posters and
pamphlets were created to tell the general public more about this team and what it is that has been
created, as well as how it ties into the future of Siem Reap and Cambodia in general. Materials
such as these will help to give the general public an idea of what exactly has been designed,
without making any sort of assumptions as to their understanding of structural drawings and
schedules.
5. Cost Analysis
36 Team 13 – All for Angkor Final Report
This project consisted of two separate budgets. The first was the budget of the team, and the
second was that of the actual proposed agricultural building. The classroom budget was set at
approximately $300.00 and could be used for items that were necessary to complete the project.
The total construction budget will be an estimate of the cost to construct the building as designed
by Team 13.
5.1. Project Budget
The material cost to complete the design of the building was well below the $300 limit. Nearly
all the design work was accomplished with software licensed to Calvin College. SketchUp was
the only software used during the project for which a license had to be purchased, for a cost of
only $39 for single computer usage. Materials purchased for the physical scale model of the
agricultural building totaled $64.58. A three-hole punch and binder were purchased for $10.23
and the binding of the final report and calculation notebook only cost $2. A summary table of the
project budget can be seen in Table 5.1.1.
Table 5.1.1 Project budget Item Description Item Cost
Three-hole Punch / Binder $ 10.23
Binding $ 2.00
SketchUp $ 39.00
Model Materials $ 64.58
Dividers for Calc. Notebook $ 23.31
Total Cost $ 139.12
5.2. Construction Budget
A final estimate of the construction costs has been determined for the new agricultural building
for AGU. It is based on construction labor and material prices in the United States. In order to
give AGU a sense of the cost, the final cost will be converted to the Cambodian Riel (KHR),
which is the currency used in Cambodia. To give the reader a point of reference, the national
average household income for a Cambodian was $106 United States Dollars (USD) per month in
1999.
37 Team 13 – All for Angkor Final Report
The items in the estimate are based on the architectural, structural, and site drawings as well as
known construction techniques in the Siem Reap region of Cambodia. The estimate assumes that
the entire footprint area of the building will be excavated to a depth of 3.5 meters. The values for
the necessary volume of concrete were quite accurately determined based on the structural
drawings. The reinforcing steel was included in the overall cost of reinforced concrete. With
only limited architectural drawings, it is difficult to accurately estimate the interior construction
costs. Only large cost items were estimated for the interior construction costs, which still gives a
fairly accurate picture of the total cost. Mechanical and electrical costs were also difficult to
estimate since the design of both were not parts of the project. Only items that are necessary to
the function of the building were included in the estimate. A 20% contingency has been applied
to the final project budget because of the uncertainty associated with electrical and mechanical
portions of the building. The estimated unit costs were taken from Building Construction Cost
Data from 2002. Since cement is a known industry in Cambodia, it was assumed that the cost of
concrete would be comparable to that of the United States. A 15% material cost increase was
assessed to other materials such as glass that would be more difficult to obtain. The total
estimated cost of construction for the project is about $2.01 million USD or $8.05 billion KHR
(see Table 5.2.1 for detailed budget).
38 Team 13 – All for Angkor Final Report
Table 5.2.1 Project construction cost estimate
Category Description Unit Quantity Unit Cost Cost Foundation Footing and Foundation Poured Concrete and Footings C.M. 815 $ 214.50 $ 110,135.03
Excavation and Backfill Site Preparation for Concrete and Footings C.M. 7100 $ 4.16 $ 1,476.80
Structure
First and Second Floor Reinforced Concrete - One-way Beam and Slab C.M. 955 $ 843.63 $ 507,569.99
Third Floor Reinforced Concrete - One-way Beam and Slab C.M. 165 $ 843.63 $ 87,695.34
Roof Reinforced Concrete - One-way Beam and Slab C.M. 460 $ 844.63 $ 244,773.77
Super Structure Foundation Column - Minimum Reinforcement C.M. 30 $ 810.93 $ 15,326.58 First Floor Column - Minimum Reinforcement C.M. 35 $ 810.93 $ 17,881.01 Second Floor Column - Minimum Reinforcement C.M. 30 $ 810.93 $ 15,326.58 Third Floor Column - Minimum Reinforcement C.M. 25 $ 810.93 $ 12,772.15 Exterior Closure Walls Clay Brick S.M. 2250 $ 12.00 $ 18,711.00 Doors Glass Entry Door EA 6 $4,100.00 $ 17,047.80 Doors Second Floor Balcony Door EA 8 $ 375.00 $ 2,079.00 Windows Glass EA 64 $ 300.00 $ 13,305.60 Large Entryway Window Glass S.M. 135 $ 121.09 $ 11,328.57 Roofing Roof Coverings Red Clay Tile S.M. 1800 $ 81.80 $ 102,037.32 Wood Sheathing Plywood S.M. 1800 $ 11.52 $ 14,370.05 Roofing Felt Asphalt Felt S.M. 1800 $ 0.93 $ 1,160.08 Interior Construction Partitions Clay Brick S.M. 2560 $ 12.00 $ 21,288.96 Partitions Toilet Compartments EA 32 $ 286.00 $ 6,342.34 Wall Finishes Paint S.M. 7370 $ 4.41 $ 22,523.68 Wall Finishes Mortar S.M. 7370 $ 38.97 $ 199,035.77 Interior Doors Wood EA 70 $ 73.00 $ 3,541.23 Floor Carpet S.M. 3400 $ 47.84 $ 112,720.61 Stairs Concrete L.M. 25 $ 113.19 $ 1,961.02 Ceiling Tile S.M. 3400 $ 10.76 $ 25,352.71 Mechanical Plumbing Urinal EA 20 $ 500.00 $ 11,500.00 Plumbing Toilet EA 32 $ 430.00 $ 15,824.00 Plumbing Sink EA 16 $ 200.00 $ 3,680.00 Fire Protection 4 Section Alarm EA 1 $1,200.00 $ 1,380.00 Electrical Lighting Fluorescent EA 280 $ 136.00 $ 43,792.00 Site Work Utilities Septic Tank - 5750 L EA 4 $4,000.00 $ 18,400.00 Overhead Contingency 20% $ 336,067.79
Total $2,016,406.76
39 Team 13 – All for Angkor Final Report
5.3. Engineering Fees
The engineering fees are presented in Table 5.3.1. Engineering wages of $30 per hour were
assumed, as was an indirect labor multiplier of 1.8 that was used to calculate the indirect labor
overhead cost. A total cost of $140,355.60 was calculated for the design of this project.
Table 5.3.1 Professional engineering fees
Task Time Raw Labor Indirect Labor Overhead
Professional Fees Total
Meeting 266.75 $ 8,002.50 $ 14,404.50 $ 2,240.70 $ 24,647.70 Research 95.00 $ 2,850.00 $ 5,130.00 $ 798.00 $ 8,778.00
Budget/Business Plan 29.75 $ 892.50 $ 1,606.50 $ 249.90 $ 2,748.90 PPFS 153.50 $ 4,605.00 $ 8,289.00 $ 1,289.40 $ 14,183.40
Promotional Materials 52.25 $ 1,567.50 $ 2,821.50 $ 438.90 $ 4,827.90 Presentations 58.00 $ 1,740.00 $ 3,132.00 $ 487.20 $ 5,359.20
Land Development 46.50 $ 1,395.00 $ 2,511.00 $ 390.60 $ 4,296.60 Calculations 325.50 $ 9,765.00 $ 17,577.00 $ 2,734.20 $ 30,076.20
3D Walkthrough 135.50 $ 4,065.00 $ 7,317.00 $ 1,138.20 $ 12,520.20 AutoCAD 202.50 $ 6,075.00 $ 10,935.00 $ 1,701.00 $ 18,711.00 STAAD 86.25 $ 2,587.50 $ 4,657.50 $ 724.50 $ 7,969.50
Final Report 67.50 $ 2,025.00 $ 3,645.00 $ 567.00 $ 6,237.00
Total (hr): 1519.00 $45,570.00 $ 82,026.00 $ 12,759.60 $140,355.60
6. Discussion
As is seen in the above final design, the structural design and land development for this project
have been completed. The final structural design consists of a three-story concrete frame
building. Because of this design, none of the walls have been designed to be load bearing.
Structural member dimensions and reinforcement have been standardized wherever possible to
help ensure a smooth construction process. The final deliverables for this project include a
calculation notebook with the final calculations, a design report offering explanations of the
design, a set of structural drawings, a physical 3-D model, and a 3-D video model which shows a
complete walkthrough of the building. These components are useful not only for the actual
design process but also for presentation purposes.
Sample calculations for all structural members can by found in Appendix A. For a complete set
of structural calculations, reference the supplemental Calculation Notebook.
40 Team 13 – All for Angkor Final Report
7. Conclusion
The final construction drawings for the agricultural building can be found in Appendix B. The
objectives of this project included completing the structural design and basic land development
for the first building of Angkor Global University. Team 13 was able to accomplish these tasks
in a culturally appropriate manner. This was done by taking into account local building
architecture and common local construction materials. The estimated construction budget for the
agricultural building is roughly $2.02 milllion USD. This design will provide a building which
will fulfill all of the needs of the university, while remaining within the design norms discussed
earlier.
Due to the turbulent past of Cambodia, the country is currently in need of the education that was
purged from the people during the Pol Pot massacres. This building design is one of many
attempts currently underway to aid in the restoration and education of the country of Cambodia.
This building will also serve to glorify God while promoting His good word into a region of the
world where Christianity is scarce. This project has tremendous potential to do a lot of good for
many people.
8. Recommendations
There were many challenges that resulted from completing a design for a country several
thousand miles away. Many of the issues that arose as a result of the distance could have been
reduced or possibly eliminated by a site visit. Much of the site information such as soil bearing
capacity and exact elevation of the site had to be assumed because of the lack of specific
information. Thus, a site visit would have been very profitable to the project. Not only would it
make the design of the building more accurate but it would also reduce the final cost of the
building.
Another challenge that resulted from the distance was inconsistent communication with the
architechture students from HGU. The main form of communication for this project was email.
While attempts were made to use a internet phone service, such as Gizmo, this type of
communication was never utilized. Thus, in hindsight, this would have been very valuable to the
timely completion of our project.
41 Team 13 – All for Angkor Final Report
One recommendation that Team 13 would make for the future construction of the building is to
make the building handicap-accessible. Currently, the architectural layout of the building
includes stairs at all entrances. As a result of this, it is not possible for those with physical
impairments to access the building. Since the architectural design was not within the scope of our
project, this issue was not addressed within our design. However, it is the recommendation of
Team 13 that this problem be addressed before the actual construction of the building.
42 Team 13 – All for Angkor Final Report
9. Acknowledgements
As a team, we would like to acknowledge those who have helped us along the way. Your
expertise and assistance were invaluable to our project.
Handong Architecture Students (Netty and Billy) Professor Sang Ki Lee, Handong Global University Professor Hakchul Ezra Kim, Handong Global University Professor David Wunder, P.E., Team Advisor Professor Leonard P. De Rooy P.E., Project Consultant Roger Lamer, P.E., Industrial Consultant Pete VanDyk – for his help on the physical model JD Schaumberg – for landscape design assistance The members of Team 15 – for sharing valuable information
43 Team 13 – All for Angkor Final Report
10. Resources
ACI Committee 318. Building Code Requirements for Structural Concrete (ACI318-02) and Commentary (ACI 318R-02). : , 2002.
ACI Committee 318. Building Code Requirements for Structural Concrete and Commentary
(ACI318M-05): , 2005. "Cambodia." The World Factbook. 1 Nov. 2005. CIA. 21 Nov. 2005 <www.cia.gov>. Concrete Reinforcing Steel Institute. CRSI Handbok 1992. 7 ed. Schaumburg: CRSI, 1992. Coutsoukis, Photius. "Cambodia Geography 2000." Cambodia. 2000. 21 Nov. 2005
<www.photius.com>. Fanella, David A., and Basile G. Rabbat, ed. Notes on ACI 318-02 Building Code Requirements For
Structural Concrete. 8 ed. Skokie: PCA, 2002. Kummu, Matti. "The Natural Environment and Historical Water Management of Angkor, Cambodia."
Department of Water Resources, Helsinki University of Technology, Espoo, Finland. 08 Dec. 2005 http://users.tkk.fi/~mkummu/publications/WAC5_paper_kummu.pdf.
Metcalf & Eddy, Inc.. Wastewater Engineering. 3rd ed. New York: McGraw-Hill, Inc., 1991. MacGregor, James G. Reinforced Concrete Mechanics and Design. 3 ed. Upper Saddle River: Prentice
Hall, 1997. Packard, Robert T., ed. Architectural Graphic Standards. 7 ed. New York: John Wiley & Sons, 1981. "Septic Tank - Soil Absorbtion Systems." Decentralized Systems Technology Fact Sheet. Sept 1999.
EPA. 7 Dec. 2005 <http://epa.gov>. "Siem Reap." Wikipedia. 21 Nov. 2005 <http://en.widipedia.org>. Spiegel, Leonard, and George F. Limbrunner. Reinforced Concrete Design. 5 ed. Upper Saddle River:
Prentice Hall, Inc., 2003. Takahashi, Yukio. "Country Study for Japan's ODA to the Kingdom of Cambodia." Section 7. The
Environment. 08 Dec. 2005 http://www.jica.go.jp/english/resources/publications/study/country/pdf/cambodia_15.pdf.
Wang, Chu-Kia, and Charles G. Salmon. Reinforced Concrete Design. 6 ed. New York: Addison
Wesley, 1998. White, P.F. . "The Soils Used for Rice Production in Cambodia." 1997. Cambodia-IRRI-Australia
Project. 08 Dec. 2005 http://www.knowledgebank.irri.org/regionalSites/cambodia/docs/Soils%20Used%20In%20Cambodia.pdf.
44 Team 13 – All for Angkor Final Report
11. Appendices
A. Sample Calculations (For complete design calculations, please reference the Calculation Notebook)
A-1. Load Calculations
A-2. Slab Calculations
A-3. Beam Calculations
A-4. Girder Calculations
A-5. Column Calculations
A-6. Foundation Calculations
A-7. Land Development Calculations
B. Drawing Set
C. Project Schedule
45 Team 13 – All for Angkor Final Report
A-1. Load Calculations
46
A-1. LOAD CALCULATIONS
1. Classification of Buildings and Other Structures for Flood, Wind, Snow, and Earthquake Loads
Classified as a Type III building:
Buildings and other structures that represent a substantial hazard to human life in the event of
failure inclusing, but not limited to:
> Buildings and other structures where more than 300 people congregate in one area
> Buildings and other structures with a capacity greater than 500 for colleges or adult education
facilities
While these standards are most likely higher than the actual requirements, because of limited information,
currently, we will design to meet this building type.
Tributary Length [m] = 10
2. Combinations of Loads
Load Values [kN/m2] Lower Roof [kN/m] Upper Roof [kN/m]
Dead Loads, D: 5.279 0.5279 0.5279
Earthquake Load, E: 0 0 0
0 0
0 0
Flood Load, Fa: 0 0 0
0 0
0 0
Live Load, L: 4.79 0.479 0.479
Roof Live Load, Lr: 0.576 0.0576 0.0576
Rain Load, R: 0.7448 0.07448 0.07448
Snow Load, S: 0 0 0
Self-straining force, T: 0 0 0
Wind load, W: 0.100 0.010015347 0.010015347
Basic Load Combinations:
1. 1.4(D+F) 7.3906 0.73906 0.73906
2. 1.2(D+F+T)+1.6(L+H)+0.5(Lr or S or R) 14.3712 1.43712 1.43712
3. 1.2D+1.6(Lr or S of R)+(0.5L or 0.8W) 7.60660278 0.760660278 0.760660278
4. 1.2D+1.6W +0.5L +0.5(Lr or S or R) 9.262445559 0.926244556 0.926244556
5. 1.2D+1.0E+0.5L+0.2S 8.7298 0.87298 0.87298
6. 0.9D+1.6W+1.6H 4.911345559 0.491134556 0.491134556
7. 0.9D+1.0E+1.6H 4.7511 0.47511 0.47511
Greatest Load Combination:
See following pages for calculations of above mentioned loads.
Load Calculations Using ASCE 7
Load due to fluids with well-defined pres.
and max heights F:
Load due to lateral earth pres., ground
water pres., or pres. of bulk materials, H:
0
0
47
A-1. LOAD CALCULATIONS
DEAD LOADS:
Min Densities for Design LoadsMin Design Loads
[kN/m3] [kN/m
2]
Interior Walls
Wood Studs, 51 x 102, Plastered 2 Sides 0.96
Floor:
Concrete, reinforced (slag) 21.7
Thickness (m) 0.17 3.689
Misc:
Subflooring 0.14
Linoleum or Asphalt Tile 0.05
Drop Ceiling 0.1
Mechanical 0.24
Erroneous 0.1
TOTAL DEAD LOAD: 5.279
Roof: [kN/m2]
Asphalt shingles 0.3
1.5" metal deck (acoustical), 18 gage 0.14
2 layers 12 mm plywood 0.144
Mech/elect 0.2
Miscellaneous: 0.2
total roof: 0.984
Walls 3
Wall Thickness (m) 0.2
Linear DL from EXTERIOR Walls (kN/m) 0.6
48
A-1. LOAD CALCULATIONS
LIVE LOADS:
Roof Live Loads: Lr=0.96*R1*R2 0.576 kN/m2
for A>55.74 m2 R1=.6 0.6
for F<4 R2=1 1
F 3.22
First tier W 51
L 45
W1 28.3
L1 22.3
At 1663.91 m2
Second tier W 30.3
L 24.3
W1 14
L1 7.8
At 627.09 m2
Interior Live Loads: Load, [kN/m2]
Laboratories: 4.79
Libraries: 2.87
Classrooms: 1.92
Offices: 2.4
Courtyard: 4.79
Conference Room: 4.79
Computer Room: 2.87
First Floor Corridors: 4.79
Second Floor Corridors: 3.83
Exterior Balconies: 4.79
Rest Rooms: 2.87
Live Load Element Factor, K LL
(would be used for live load reduction factor)
L=Lo(0.25+4.57/(KLLAT).5)
49
A-1. LOAD CALCULATIONS
RAIN LOADS:
Design Storm: 180 mm/hr
A (largest drainage area, single drain): 232.815 [m2]
Q 0.023300 [m3/s]
dh (based on 152 mm drain): 76 [mm]
ds: 0 [mm]
R=0.0098*(ds+dh) 0.7448 [kN/m2]
WIND LOADS:Walls:
z Kz: qz [N/m2]:
0 0.85 153.40
6.1 0.9 162.42
7.6 0.94 169.64
9.1 0.98 176.86
12.2 1.04 187.69
13.1 1.06 191.30
h 10.6 m (mean roof height)
Kz: 1.009 Table 6.5
Kzt: 1 flat ground
V: 16 m/s
I: 1.15 Type III
windward, q=q z :
design wind pressure for windward wall, p: Exterior P (N/m2) Interior P1 (N/m
2) Interior P2 (N/m
2) Net P1 (N/m
2) Net P2 (N/m
2)
p0-4.6 104.310 100.153 -100.153 4.157 204.464
p6.1 110.446 100.153 -100.153 10.292 210.599
p7.6 115.355 100.153 -100.153 15.201 215.508
p9.1 120.263 100.153 -100.153 20.110 220.417
p12.2 127.626 100.153 -100.153 27.473 227.780
p13.1 130.081 100.153 -100.153 29.927 230.234
Exposure C
qh: 182.097 value at mean roof height
G: 0.85 for rigid structure
Cp: 0.8
GCpi for partially enclosed : 0.55 -0.55
Exterior P (N/m2) Interior P1 (N/m
2) Interior P2 (N/m
2) Net P1 (N/m
2) Net P2 (N/m
2)
design wind pressure for leeward wall, p: -77.391 100.153 -100.153 -177.545 22.762
Cp: -0.5
Exterior P (N/m2) Interior P1 (N/m
2) Interior P2 (N/m
2) Net P1 (N/m
2) Net P2 (N/m
2)
design wind pressure for side walls, p: -108.348 100.153 -100.153 -208.501 -8.194
Cp: -0.7
Roof: p, N/m2
p, N/m2
design wind pressure for windward roof, p: -177.545 22.762
h/L: 0.220833333
Cp: -0.5
q=qh
p, N/m2
p, N/m2
design wind pressure for leeward roof, p: -177.545 22.762
Cp: -0.5
q=qh
50
A-2. Slab Calculations
51
A-2. SLAB CALCULATIONS
1st and 2nd Floor Slab Design:
PSI kN/m2
CONVERSIONS:
fc'= 3500 24132 1 kN/m2= 0.145 psi
fy= 60000 413685 1 kN/m2= 20.886 psf
1 m= 3.280 ft
m ft
Span Length: 4.3 14.104
(1) Compute minimum h:
Clear Span: Ln= 12.854 ft
For 1 end continuous:
min h= L/24 6.427 in
For 2 end continuous:
min h= L/28 5.51 in
Assume:
h= 6.427 in
d= 5.427 in
(2) Calculate weight of slab & compute factored load
slab wght: 0.0803 kip/sq-ft
width: 12 inches
wD= 0.128 kpf
+ wL= 0.160 kpf (LL=4.79 kN/m2 or 100 psf)
= wU= 0.288 kpf unfact'd w: 0.207 kpf
unfact'd M: 4.2718
Since wL is less than three times wD, use the ACI moment coefficients to calculate moments:
(3) Compute Moment:
Check whether slab thickness chosen is adequate if ρ≤0.01
ω=ρ(fy/fc) = 0.171
φKn= 485.38
continuous over two or more spans:
pos. M Mu= wl2/14 discontinuous end integral with support.
3.401 ft-kips
neg. M Mu= wl2/10 at exterior face of first interior support
4.762 ft-kips
Max Moment: 4.76 ft-kips
52
A-2. SLAB CALCULATIONS
Solve for bd2 based on max moment:
bd2= 117.727 in
3
Solve for d using b=12 in
d= 3.132 in
Is slab OK for flexure? YES
Since d=5.4 in exceeds this value, the slab will be OK for flexure.
(4) Check if thickness is adequate for shear:
Shear Reinforcement is required if Vu>φVc. (ACI 11.5.5.1a)
typical support: Vu=1.15*wu*ln/2
2130.14 lb/ft
φVc=.85(2√fcbd)
6549.74 lb/ft
Is Vu<φVc? YES
Since Vu<φVc, the slab chosen is adequate for shear.
(5) Reinforcement Ratio:
Reinforcement Ratio:ρt= 0.015805 (from table 6-1, supplement to ACI code)
Set Rein. Ratio: ρ= 0.007903 (half ρt)
(6) Coeff. Of Resistance: k-bar
Rn= 436.37 psi
(7) Calculate effective depth d:
Req'd d= 3.48 in
(8) Calculate Required Area of Steel for Flexural Reinforcement (neg. moment):
Assuming no. 5 bars:
cover (in)= 0.75
req'd h= 4.54 in
USE h= 6.427 in (for fire code)
AND d= 5.36 in
Req'd negative moment reinforcement:
Rn= 183.86 psi
ρ~ 0.0033
-As (min) = 0.138823 in2/ft (ACI 7.12)
-As (req'd) = ρbd = 0.21 in2/ft
REQ'D AS= 0.21
Select main steel (neg. moment):
Use No. 4 @ 11 in (As=0.22 in2/ft)
53
A-2. SLAB CALCULATIONS
(9) Calculate Required Area of Steel for Flexural Reinforcement (pos. moment):
Req'd positive moment reinforcement:
Mu/φfcbd2= 0.0375
(use table 7-1)
ω~ 0.039
ρ= ωfc/fy = 0.002275
+As (req'd) = ρbd = 0.1465 in2/ft
Select main steel (pos. moment):
Use No. 4 @ 16 in (As=0.15 in2/ft)
(10) Shrink and Temperature Steel:
grade 60: As=.0018bh (ACI, 7.12.2.1, b)
0.139 in2
Select Shrink and Temperature Steel:
Use No. 4 @ 16 in (As=0.15 in2/ft)
(11) Main Steel > Temperature Steel
Is main steel greater than temperature steel?
YES
Slab design is adequate for all loadings
CALCULATED BY: KTA
CHECKED BY: BAJ
54
A-2. SLAB CALCULATIONS
3rd Floor Slab Design:
PSI kN/m2
CONVERSIONS:
fc'= 3500 24132 1 kN/m2= 0.145 psi
fy= 60000 413685 1 kN/m2= 20.886 psf
1 m= 3.280 ft
m ft
Span Length: 5.3 17.384
(1) Compute minimum h:
Clear Span: Ln= 16.134 ft
For 1 end continuous:
min h= L/24 8.067 in
For 2 end continuous:
min h= L/28 6.91 in
Assume:
h= 8.067 in
d= 7.067 in
(2) Calculate weight of slab & compute factored load
slab wght: 0.1008 kip/sq-ft
width: 12 inches
wD= 0.153 kpf
+ wL= 0.160 kpf (LL=4.79 kN/m2 or 100 psf)
= wU= 0.313 kpf unfact'd w: 0.227 kpf
unfact'd M: 7.3972
Since wL is less than three times wD, use the ACI moment coefficients to calculate moments:
(3) Compute Moment:
Check whether slab thickness chosen is adequate if ρ≤0.01
ω=ρ(fy/fc) = 0.171
φKn= 485.38
continuous over two or more spans:
pos. M Mu= wl2/14 discontinuous end integral with support.
5.816 ft-kips
neg. M Mu= wl2/10 at exterior face of first interior support
8.143 ft-kips
Max Moment: 8.14 ft-kips
55
A-2. SLAB CALCULATIONS
Solve for bd2 based on max moment:
bd2= 201.305 in
3
Solve for d using b=12 in
d= 4.096 in
Is slab OK for flexure? YES
Since d=7 in exceeds this value, the slab will be OK for flexure.
(4) Check if thickness is adequate for shear:
Shear Reinforcement is required if Vu>φVc. (ACI 11.5.5.1a)
typical support: Vu=1.15*wu*ln/2
2901.91 lb/ft
φVc=.85(2√fcbd)
8529.02 lb/ft
Is Vu<φVc? YES
Since Vu<φVc, the slab chosen is adequate for shear.
(5) Reinforcement Ratio:
Reinforcement Ratio:ρt= 0.015805 (from table 6-1, supplement to ACI code)
Set Rein. Ratio: ρ= 0.007903 (half ρt)
(6) Coeff. Of Resistance: k-bar
Rn= 436.37 psi
(7) Calculate effective depth d:
Req'd d= 4.55 in
(8) Calculate Required Area of Steel for Flexural Reinforcement (neg. moment):
Assuming no. 5 bars:
cover (in)= 0.75
req'd h= 5.62 in
USE h= 8.067 in
AND d= 7.00 in
Req'd negative moment reinforcement:
Rn= 184.40 psi
ρ~ 0.0033
-As (min) = 0.174247 in2/ft (ACI 7.12)
-As (req'd) = ρbd = 0.28 in2/ft
REQ'D AS= 0.28
Select main steel (neg. moment):
Use No. 4 @ 8 in (As=0.30 in2/ft)
56
A-2. SLAB CALCULATIONS
(9) Calculate Required Area of Steel for Flexural Reinforcement (pos. moment):
Req'd positive moment reinforcement:
Mu/φfcbd2= 0.0376
(use table 7-1)
ω~ 0.039
ρ= ωfc/fy = 0.002275
+As (req'd) = ρbd = 0.1912 in2/ft
Select main steel (pos. moment):
Use No. 4 @ 12 in (As=0.20 in2/ft)
(10) Shrink and Temperature Steel:
grade 60: As=.0018bh (ACI, 7.12.2.1, b)
0.174 in2
Select Shrink and Temperature Steel:
Use No. 4 @ 13 in (As=0.18 in2/ft)
(11) Main Steel > Temperature Steel
Is main steel greater than temperature steel?
YES
CALCULATED BY: KTA
CHECKED BY: BAJ
57
A-2. SLAB CALCULATIONS
Roof Slab Design:(See ACI Code and MacGregor Concrete, P 388)
PSI kN/m2
CONVERSIONS:
fc'= 3500 24132 1 kN/m2= 0.145 psi
fy= 60000 413685 1 kN/m2= 20.886 psf
1 m= 3.280 ft
m ft
Span Length: 5.057 16.6
(1) Compute minimum h:
Clear Span: Ln= 15.3 ft
For 1 end continuous:
min h= L/24 7.6685 in
For 2 end continuous:
min h= L/28 6.57 in
Assume:
h= 7.67 in
d= 5.92 in
(2) Calculate weight of slab & compute factored load
slab wght: 0.0959 kip/sq-ft WIND:
width: 12 inches kN/m2
psf kpf
0.3 6.266 0.006
wD= 0.123 kpf
+ wL= 0.010 kpf
= wU= 0.133 kpf unfact'd w: 0.109 kpf
unfact'd M: 3.1938
Since wL is not three times wD, use the ACI moment coefficients to calculate moments:
(3) Compute Moment:
Check whether slab thickness chosen is adequate if ρ≤0.01
ω=ρ(fy/fc) = 0.171
φKn= 485.38
continuous over two or more spans:
pos. M Mu= wl2/14 discontinuous end integral with support.
2.232 ft-kips
neg. M Mu= wl2/10 at exterior face of first interior support
3.125 ft-kips
Max Moment: 3.125 ft-kips
58
A-2. SLAB CALCULATIONS
Solve for bd2 based on max moment:
bd2= 77.258 in
3
Solve for d using b=12 in
d= 2.537 in
Is slab OK for flexure? YES
Since d=5.92 in exceeds this value, the slab will be OK for flexure.
(4) Check if thickness is adequate for shear:
Shear Reinforcement is required if Vu>φVc. (ACI 11.5.5.1a)
typical support: Vu=1.15*wu*ln/2
1171.59 lb/ft
φVc=.85(2√fcbd)
7142.90 lb/ft
Is Vu<φVc? YES
Since Vu<φVc, the slab chosen is adequate for shear.
(5) Reinforcement Ratio:
Reinforcement Ratio:ρt= 0.015805 (from table 6-1, supplement to ACI code)
Set Rein. Ratio: ρ= 0.007903 (half ρt)
(6) Coeff. Of Resistance: k-bar
Rn= 436.37 psi
(7) Calculate effective depth d:
Req'd d= 2.82 in OK
(8) Calculate Required Area of Steel for Flexural Reinforcement (neg. moment):
Assuming no. 5 bars:
cover (in)= 1.5 ACI 7.7.1b for concrete exposed to earth or weather
req'd h= 4.63 in (No. 5 bar and smaller)
USE h= 7.668 in (for fire code)
AND d= 5.86 in
Req'd negative moment reinforcement:
Rn= 101.25 psi
ρ~ 0.0018
-As (min) = 0.166 in2/ft (ACI 7.12)
-As (req'd) = ρbd = 0.13 in2/ft
REQ'D= -As= 0.17 in2/ft
Select main steel (neg. moment):
Use No. 4 @ 13 in (As=0.18 in2/ft)
59
A-2. SLAB CALCULATIONS
(9) Calculate Required Area of Steel for Flexural Reinforcement (pos. moment):
Req'd positive moment reinforcement:
Mu/φfcbd2= 0.0207
(use table 7-1)
ω~ 0.021
ρ= ωfc/fy = 0.001225
+As (req'd) = ρbd = 0.0861 in2/ft
REQ'D= +As= 0.17 in2/ft
Select main steel (pos. moment):
Use No. 4 @ 13 in (As=0.18 in2/ft)
(10) Shrink and Temperature Steel:
grade 60: As=.0018bh (ACI, 7.12.2.1, b)
0.166 in2
Select Shrink and Temperature Steel:
Use No. 4 @ 13 in (As=0.18 in2/ft)
(11) Main Steel > Temperature Steel
Is main steel greater than temperature steel?
YES
CALCULATED BY: KTA
CHECKED BY: BAJ
60
A-3. Beam Calculations
61
A-3. BEAM CALCULATIONS
Design of a Continuous T Beam (1-1):Using Reinforced Concrete: Mechanics & Design, MacGregor: pgs:396-413
PSI kN/m2
Conversions:
fc'= 3500 24132 1 kN/m2= 0.145 psi
fy= 60000 413685 1 kN/m2= 20.886 psf
1 m= 3.280 ft
m ft
Clear Span: 8.7 28.536
Trib. Width: 9.6 31.488
(1) Compute the Trial Factored Loads on the Beam:
a) Area of Influence over positive moment:
4.8.1 in ASCE 7-98: Can reduce live loads in design of members with AI ≥ 400 ft2
Dimensions:
span: 28.54 ft
width: 28.21 ft
AI= 804.94 ft2
Since the Area is greater than 400 ft2, can use a reduced live load:
L=Lo(.25+15/√(AI))
Lo= 100 psf
L= 77.87 psf
b) Area of Influence over negative moment:
Dimensions:
span: 57.07 ft
width: 28.21 ft
AI= 1609.89 ft2
Since the Area is greater than 400 ft2, can use a reduced live load:
L=Lo(.25+15/√(AI))
Lo= 100 psf
L= 62.38 psf
Use moment with smallest influence area:
use L= 62.38 psf
c) Loads:
Without the portion of the beam stem below the slab:
DL: 6.5 psf (extra)
20 psf (walls)
16.5 psf (beams)
81 psf (slab)
124 psf
LL: 62.38 psf (reduced)
wu= 1.2*DL+1.6*LL
wu= 248.6155 psf
Factored Load per Foot:
7828.40 lb/ft = 7.83 kips/ft
Estimation of weight of beam stem:
(1) Factored Load of stem approx. 10-20% of other factored loads
10% 0.783 kips/ft
20% 1.566 kips/ft
62
A-3. BEAM CALCULATIONS
(2) Depth of beam: h ≈ 8-10% of ln and bw ≈ .5h
h= 28 - 34 in
bw= 18 - 17 in
0.525 kips/ft 0.611 kips/ft
ASSUME: 1.045 kips/ft
Total Trial Load Per Foot: 8.874 kips/ft
(2) Choose Actual Size of Beam:
a) ACI Table 9.5(a) (Table A-14)
min h ≈ l/18.5 18.510 in (one-end continuous)
b) Determine Minimum Depth:
(based on moment at first interior support)
Mom. ≈ wl2/10 274.30 ft-kips
ρ= 0.0169 (Table A-5)
From Table A-3:
φk= 609
Thus, bd2/12000=M/φk = 0.45
bd2= 5404.87
Possible Choices:
b= 13.51 in d= 20.0 in
b= 10.22 in d= 23.0 in
b= 12.13 in d= 21.1 in
Select last option:
h= 23.6 in
TRY a 12X24 with d=21.1 in
c) Check the Shear Capacity of the Stem:
Vu=φ(Vc+Vs)
From ACI 11.3.1.1, Vc=2√(fc)bwd, Vs=8√(fc)bwd
φ= 0.85
Vu=φ(2+8)*(√fcbwd)
Maximum Vu: 145.60 kips
Minimum bwd: 289.54 in
If bw = 12.12625 in
Then min d = 23.88 in
Shear governs.
(3) Compute the Dead Load of the Stem and Recompute the Total Load Per Foot:
Weight per ft of stem below slab = 0.204 kip/ft
Total factored load = 8.07 kips/ft
(4) Calculate the Flange Width for Positive Moment Region
(ACI 8.10.2)
The effective width of the flange is the smallest of:
63
A-3. BEAM CALCULATIONS
1) 0.25*Ln 85.61 in
2) bw+2*(8*slab thickness) 116.13 in
3) bw+1/2 the clear distance 183.3 in
Effective width of flange: 85.61 in
(5) Compute the Moments and (6) Design Reinforcement
EE1 1st Span IE1 IE2 2nd Span EE2
Line
1. Mu (from STAAD) -206.27 253.12 -274.30 234.49 -157.53
2. As coefficient 0.0121 0.0118 0.0121 0.0118 0.0121
3. As(req'd), in2
2.48 2.80 3.30 2.60 1.90
4. As(min), in2
0.76 0.76 0.76 0.76 0.76
4. As > As(min), in2
YES YES YES YES YES
5. Bars Selected 3 #9 3 #9 3 #9 3 #9 2 #9
1 #6
6. As provided, in2
3.00 3.00 3.44 3.00 2.00
7. bw OK - YES - YES -
(7) Check the Distribution of the Reinforcement
a) Positive Moment Region
(Must satisfy ACI 10.6.3 & 10.6.4)
Check at section with the smallest # of positive moment bars - 3 #9 Bars
Diameter of Selected Bar 1.0 in
Centriod of Bar d c = 2.375 in
Area Per Bar = 19.20 in2
z = fs(dcA)1/3
= 128.61 kips/in
For interior exposure, z cannot exceed 175 kips/in
Bar Spacing Adequate
b) Negative Moment Region
Using 3 #9 and 1 #6 Bars
Diameter of Selected Bar 1.128 in
Area of Selected Bar 1 in2
Centriod of Bar d c = 2.439 in
Equivalent No. #9 Bars 3.44
Max Area = 47.10 in2
s = A/(2d c ) = 9.66
Thus within 47.1 in we must place 4 bars and they must not be spaced farther apart than 9.66 in
According to ACI 10.6.6 "part" of longitudinal reinforcement must be distributed over the effective flange
width or over (1/10)span, which ever is smaller. These will be in the slab (arbitrarily 5 in outside beam).
ACI 10.6.6 also requires "some" reinforcement in the slab outside this band. We shall assume that the
shrinkage and temperature steel will satisfy this requirement.
(8) Design the Shear Reinforcement
EE-1 IE-1 IE-2 EE-2
64
A-3. BEAM CALCULATIONS
Line
1. Cv 1 0.15 1.15 1 0.089 1
2. Vu 35.64 5.35 -45.57 40.56 3.59 -32.09
3. Vn = Vu/φ, kip 39.60 5.94 50.64 45.07 3.99 35.66
a) Exterior End - 1
Vu/φ at d = 35.45 kips
ACI 11.5.5.1 requires stirrups if Vn ≥ Vc/2
Vc=2√fcbwd 30.29 kips
Vc/2= 15.15 kips
Is Vn>Vc/2? YES
Stirrups are Required
TRY - No. 3 Grade 40 double-leg stirrups with a 90o hook enclosing a No. 4 stirrup support bar.
fy= 40000 PSI
Maximum spacing is smaller of the following:
d/2= 10.56 in (ACI 11.5.4.1)
Av= 0.22
s=Avfy/(50bw) 14.51 in (ACI 11.5.5.3)
MAX spacing: 10.6 in
The spacing required to support the shear force is:
s= 36.0 in
Compute Vu/φ where s=36 in.
s= 36 in
Vu/φ = 35.45 kips
This occurs at: 21.11 in
Compute Vu/φ where s=10.6 in.
s= 10.6 in
Vu/φ = 47.82 kips
This occurs at: -41.78 in
At EE use No. 3 grade double-leg stirrups: 1 at 3 in. and 15 at 10.6 in. on centers.
b) Interior End - 1
Vu/φ = 45.12
The spacing required to support the shear force is:
s= 12.53 in
Compute Vu/φ where s=12.53 in.
s= 12.53 in
65
A-3. BEAM CALCULATIONS
Vu/φ = 45.12 kips
This occurs at: 21.13 in
Compute Vu/φ where s=10.6 in.
s= 10.6 in
Vu/φ = 47.82 kips
This occurs at: 10.79 in
At EE use No. 3 grade double-leg stirrups: 1 at 3 in. and 15 at 10.6 in. on centers.
c) Interior End - 2
Vu/φ = 40.00
The spacing required to support the shear force is:
s= 19.13 in
Compute Vu/φ where s=19.13 in.
s= 19.13 in
Vu/φ = 40.00 kips
This occurs at: 21.11 in
Compute Vu/φ where s=10.6 in.
s= 10.6 in
Vu/φ = 47.82 kips
This occurs at: -11.47 in
At EE use No. 3 grade double-leg stirrups: 1 at 3 in. and 15 at 10.6 in. on centers.
d) Exterior End - 2
Vu/φ = 31.75
The spacing required to support the shear force is:
s= 127.29 in
Compute Vu/φ where s=127.29 in.
s= 127.29 in
Vu/φ = 31.75 kips
This occurs at: 21.11 in
Compute Vu/φ where s=10.6 in.
s= 10.6 in
Vu/φ = 47.82 kips
This occurs at: -65.77 in
66
A-3. BEAM CALCULATIONS
At EE use No. 3 grade double-leg stirrups: 1 at 3 in. and 15 at 10.6 in. on centers.
(9) Check the Development Lengths and Design Bar Cutoff
a) Perform the Preliminary Calculations for Positive Moment
12d b (12 x bar diameter)
No. 6 = 0.75 in
12d b = 9 in
No. 9 = 1.128 in
12d b = 13.54 in
ln/16 = 21.40
Therefore, ln/16 always exceeds 12d b
b) Select Cutoffs for Positive Moment Steel in First Span
(end section)
Reinforcement for midspan is 3 #9
Flexural Cutoff 71.91 in. from exterior end (From Fig A-3 in MacGregor bk)
89.03 in. from interior end
ld/d = 50.7
ld for No. 6= 38.0
ld for No. 8= 57.2
Rule 1. Bar must extend 21.1 in. past flexural cutoff points
Exterior Cutoff 50.80 in. from exterior end
Interior Cutoff 67.92 in. from interior end
Rule 2. Distance from midspan on exterior end 120.42
Distance from midspan on interior end 103.30
Rule 3. One-fourth of bars must hook into support at A and lapped spliced at D
2 #9 will have 90o hooks and lap splices at supports (girders)
Rule 2. Bars must extend ld past the actual cutoff points of adjacent bars.
Are rule 1 numbers greater than ld?
YES
Rule 4. At positive moment points of inflection, the bars must satisfy the following:
ld≤Mn/Vu+la
Pos. Moment Inflection Points: 0.098ln = 33.56 in from exterior end
(from fig. A-3) 0.146ln = 50.00 in from interior end
At these pts, have 2 #9
Area of one Bar: 1.00 in
Mn = 2503.4 in-kips
Check at the exterior end.
Vu/φ = 33.01 kips
67
A-3. BEAM CALCULATIONS
la= smaller of actual extension, that exceeds 33.56 in, or d or 12 db
la= 21.11
Therefore,
Mn/Vu+la = 105.39 OK
c) Select Cutoffs for Positive Moment Steel in Second Span
Selected Bars for Span: 3 #9
Run 2 #9 Bars into the support and cutoff the remaining #9 bars
Area of 2 Bars: 2 in2
As, Remaining: 0.33 times the original
.215ln = 73.62 in from face of support
Rule 1. Bar must extend d past flexural cutoff point
Exterior Cutoff 52.51 in. from exterior end
Interior Cutoff 52.51 in. from interior end
Rule 2. Distance from midspan on exterior end 118.71 in
Distance from midspan on interior end 118.71 in
Rule 3. Must lap splice the bars a length of ld = 57.2
Rule 4. At positive moment points of inflection, the bars must satisfy the following:
ld≤Mn/Vu+la
Positive moment points for inflection are .146*ln from the supports
.146*ln = 50.00 in from exterior end
At these pts, have 2 #9
Area of one Bar: 1.00 in
Mn = 2503.4 in-kips
Check at the exterior end.
Vu/φ = 33.07 kips
la= smaller of actual extension, that exceeds 50.00 in, or d or 12 db
21.1
Therefore,
Mn/Vu+la = 105.22 OK
d) Perform the Preliminary Calculations for Negative Moment
(ACI 12-5)
No. 6 = 0.75 in
12d b = 9 in
lbh = 15.21 x 0.7 = 10.65
No. 9 = 1.128 in
12d b = 13.536 in
lbh = 22.88 x 0.7 = 16.02
These can be multiplied by .7 since the side cover exceeds 25 in.
68
A-3. BEAM CALCULATIONS
e) Select Cutoffs the Negative Moment Steel at the Exterior End
Selected Bars for Span: 3 #9
Extend all bars past the negative moment point of inflection
.108ln = 36.98 in (Fig. A-3)
Rule 6. One-third of bars must extend the longer of d, 12db, or ln/16 past the point of inflection
Cutoff at 58.4 in. from the face of the support
Rule 2. Bars must extend ld from the face of the support
38.03 in. OK
f) Select Cutoffs for the Negative Moment Steel at Interior End - 1
Selected Bars for Span: 3 #9 1 #6
Cutoff 2 #9 and 1 #6 bars when no longer needed and extend 2 #9 bar .67As past the negative moment point of inflection
Extend all bars past the negative moment point of inflection
.065ln = 22.26 in (MacGregor Fig. A-3)
Rule 1. Bar must extend 43.4 in. from the face of the support
Rule 2. Bars must extend ld from the face of the support
57.20 in. OK
Cutoff 2 #9 bars 57.20 in. from exterior face of support
Extend remaining bars entire length of beam
.224ln = 76.70 in
Rule 6. One-third of bars must extend the longer of d, 12db, or ln/16 past the point of inflection
Cutoff at 97.8 in. from the face of the support OK
Rule 2. Bars must extend ld past actual cutoff
40.62 in. NO
Cutoff bars at 114.4 in. from exterior face of support
g) Select Cutoffs for the Negative Moment Steel at Interior End - 2
Selected Bars for Span: 3 #9 1 #6
Extend 2 #9 bars the entire length of the beam
.24ln = 82.18 in (MacGregor Fig. A-1)
Rule 6. Bars must extend the longer of d, 12db, or ln/16 past the point of inflection
Cutoff at 103.6 in. from the face of the support
Rule 2. Bars must extend ld from the face of the support
64.52 in. OK
Cutoff bars at 103.6 in. from the face of the support
CALCULATED BY: BAJ
CHECKED BY: KTA
69
A-4. Girder Calculations
70
A-4. GIRDER CALCULATIONS
Design of a Continuous T Beam (1-1):Using Reinforced Concrete: Mechanics & Design, MacGregor: pgs:396-413
PSI kN/m2
Conversions:
fc'= 3500 24132 1 kN/m2= 0.145 psi
fy= 60000 413685 1 kN/m2= 20.886 psf
1 m= 3.280 ft
m ft
Clear Span: 8.7 28.536
Trib. Width: 9.6 31.488
(1) Compute the Trial Factored Loads on the Beam:
a) Area of Influence over positive moment:
4.8.1 in ASCE 7-98: Can reduce live loads in design of members with AI ≥ 400 ft2
Dimensions:
span: 28.54 ft
width: 28.21 ft
AI= 804.94 ft2
Since the Area is greater than 400 ft2, can use a reduced live load:
L=Lo(.25+15/√(AI))
Lo= 100 psf
L= 77.87 psf
b) Area of Influence over negative moment:
Dimensions:
span: 57.07 ft
width: 28.21 ft
AI= 1609.89 ft2
Since the Area is greater than 400 ft2, can use a reduced live load:
L=Lo(.25+15/√(AI))
Lo= 100 psf
L= 62.38 psf
Use moment with smallest influence area:
use L= 62.38 psf
c) Loads:
Without the portion of the beam stem below the slab:
DL: 6.5 psf (extra)
20 psf (walls)
16.5 psf (beams)
81 psf (slab)
124 psf
LL: 62.38 psf (reduced)
wu= 1.2*DL+1.6*LL
wu= 248.6155 psf
Factored Load per Foot:
7828.40 lb/ft = 7.83 kips/ft
Estimation of weight of beam stem:
(1) Factored Load of stem approx. 10-20% of other factored loads
10% 0.783 kips/ft
20% 1.566 kips/ft
71
A-4. GIRDER CALCULATIONS
(2) Depth of beam: h ≈ 8-10% of ln and bw ≈ .5h
h= 28 - 34 in
bw= 18 - 17 in
0.525 kips/ft 0.611 kips/ft
ASSUME: 1.045 kips/ft
Total Trial Load Per Foot: 8.874 kips/ft
(2) Choose Actual Size of Beam:
a) ACI Table 9.5(a) (Table A-14)
min h ≈ l/18.5 18.510 in (one-end continuous)
b) Determine Minimum Depth:
(based on moment at first interior support)
Mom. ≈ wl2/10 274.30 ft-kips
ρ= 0.0169 (Table A-5)
From Table A-3:
φk= 609
Thus, bd2/12000=M/φk = 0.45
bd2= 5404.87
Possible Choices:
b= 13.51 in d= 20.0 in
b= 10.22 in d= 23.0 in
b= 12.13 in d= 21.1 in
Select last option:
h= 23.6 in
TRY a 12X24 with d=21.1 in
c) Check the Shear Capacity of the Stem:
Vu=φ(Vc+Vs)
From ACI 11.3.1.1, Vc=2√(fc)bwd, Vs=8√(fc)bwd
φ= 0.85
Vu=φ(2+8)*(√fcbwd)
Maximum Vu: 145.60 kips
Minimum bwd: 289.54 in
If bw = 12.12625 in
Then min d = 23.88 in
Shear governs.
(3) Compute the Dead Load of the Stem and Recompute the Total Load Per Foot:
Weight per ft of stem below slab = 0.204 kip/ft
Total factored load = 8.07 kips/ft
(4) Calculate the Flange Width for Positive Moment Region
(ACI 8.10.2)
The effective width of the flange is the smallest of:
72
A-4. GIRDER CALCULATIONS
1) 0.25*Ln 85.61 in
2) bw+2*(8*slab thickness) 116.13 in
3) bw+1/2 the clear distance 183.3 in
Effective width of flange: 85.61 in
(5) Compute the Moments and (6) Design Reinforcement
EE1 1st Span IE1 IE2 2nd Span EE2
Line
1. Mu (from STAAD) -206.27 253.12 -274.30 234.49 -157.53
2. As coefficient 0.0121 0.0118 0.0121 0.0118 0.0121
3. As(req'd), in2
2.48 2.80 3.30 2.60 1.90
4. As(min), in2
0.76 0.76 0.76 0.76 0.76
4. As > As(min), in2
YES YES YES YES YES
5. Bars Selected 3 #9 3 #9 3 #9 3 #9 2 #9
1 #6
6. As provided, in2
3.00 3.00 3.44 3.00 2.00
7. bw OK - YES - YES -
(7) Check the Distribution of the Reinforcement
a) Positive Moment Region
(Must satisfy ACI 10.6.3 & 10.6.4)
Check at section with the smallest # of positive moment bars - 3 #9 Bars
Diameter of Selected Bar 1.0 in
Centriod of Bar d c = 2.375 in
Area Per Bar = 19.20 in2
z = fs(dcA)1/3
= 128.61 kips/in
For interior exposure, z cannot exceed 175 kips/in
Bar Spacing Adequate
b) Negative Moment Region
Using 3 #9 and 1 #6 Bars
Diameter of Selected Bar 1.128 in
Area of Selected Bar 1 in2
Centriod of Bar d c = 2.439 in
Equivalent No. #9 Bars 3.44
Max Area = 47.10 in2
s = A/(2d c ) = 9.66
Thus within 47.1 in we must place 4 bars and they must not be spaced farther apart than 9.66 in
According to ACI 10.6.6 "part" of longitudinal reinforcement must be distributed over the effective flange
width or over (1/10)span, which ever is smaller. These will be in the slab (arbitrarily 5 in outside beam).
ACI 10.6.6 also requires "some" reinforcement in the slab outside this band. We shall assume that the
shrinkage and temperature steel will satisfy this requirement.
(8) Design the Shear Reinforcement
EE-1 IE-1 IE-2 EE-2
73
A-4. GIRDER CALCULATIONS
Line
1. Cv 1 0.15 1.15 1 0.089 1
2. Vu 35.64 5.35 -45.57 40.56 3.59 -32.09
3. Vn = Vu/φ, kip 39.60 5.94 50.64 45.07 3.99 35.66
a) Exterior End - 1
Vu/φ at d = 35.45 kips
ACI 11.5.5.1 requires stirrups if Vn ≥ Vc/2
Vc=2√fcbwd 30.29 kips
Vc/2= 15.15 kips
Is Vn>Vc/2? YES
Stirrups are Required
TRY - No. 3 Grade 40 double-leg stirrups with a 90o hook enclosing a No. 4 stirrup support bar.
fy= 40000 PSI
Maximum spacing is smaller of the following:
d/2= 10.56 in (ACI 11.5.4.1)
Av= 0.22
s=Avfy/(50bw) 14.51 in (ACI 11.5.5.3)
MAX spacing: 10.6 in
The spacing required to support the shear force is:
s= 36.0 in
Compute Vu/φ where s=36 in.
s= 36 in
Vu/φ = 35.45 kips
This occurs at: 21.11 in
Compute Vu/φ where s=10.6 in.
s= 10.6 in
Vu/φ = 47.82 kips
This occurs at: -41.78 in
At EE use No. 3 grade double-leg stirrups: 1 at 3 in. and 15 at 10.6 in. on centers.
b) Interior End - 1
Vu/φ = 45.12
The spacing required to support the shear force is:
s= 12.53 in
Compute Vu/φ where s=12.53 in.
s= 12.53 in
74
A-4. GIRDER CALCULATIONS
Vu/φ = 45.12 kips
This occurs at: 21.13 in
Compute Vu/φ where s=10.6 in.
s= 10.6 in
Vu/φ = 47.82 kips
This occurs at: 10.79 in
At EE use No. 3 grade double-leg stirrups: 1 at 3 in. and 15 at 10.6 in. on centers.
c) Interior End - 2
Vu/φ = 40.00
The spacing required to support the shear force is:
s= 19.13 in
Compute Vu/φ where s=19.13 in.
s= 19.13 in
Vu/φ = 40.00 kips
This occurs at: 21.11 in
Compute Vu/φ where s=10.6 in.
s= 10.6 in
Vu/φ = 47.82 kips
This occurs at: -11.47 in
At EE use No. 3 grade double-leg stirrups: 1 at 3 in. and 15 at 10.6 in. on centers.
d) Exterior End - 2
Vu/φ = 31.75
The spacing required to support the shear force is:
s= 127.29 in
Compute Vu/φ where s=127.29 in.
s= 127.29 in
Vu/φ = 31.75 kips
This occurs at: 21.11 in
Compute Vu/φ where s=10.6 in.
s= 10.6 in
Vu/φ = 47.82 kips
This occurs at: -65.77 in
75
A-4. GIRDER CALCULATIONS
At EE use No. 3 grade double-leg stirrups: 1 at 3 in. and 15 at 10.6 in. on centers.
(9) Check the Development Lengths and Design Bar Cutoff
a) Perform the Preliminary Calculations for Positive Moment
12d b (12 x bar diameter)
No. 6 = 0.75 in
12d b = 9 in
No. 9 = 1.128 in
12d b = 13.54 in
ln/16 = 21.40
Therefore, ln/16 always exceeds 12d b
b) Select Cutoffs for Positive Moment Steel in First Span
(end section)
Reinforcement for midspan is 3 #9
Flexural Cutoff 71.91 in. from exterior end (From Fig A-3 in MacGregor bk)
89.03 in. from interior end
ld/d = 50.7
ld for No. 6= 38.0
ld for No. 8= 57.2
Rule 1. Bar must extend 21.1 in. past flexural cutoff points
Exterior Cutoff 50.80 in. from exterior end
Interior Cutoff 67.92 in. from interior end
Rule 2. Distance from midspan on exterior end 120.42
Distance from midspan on interior end 103.30
Rule 3. One-fourth of bars must hook into support at A and lapped spliced at D
2 #9 will have 90o hooks and lap splices at supports (girders)
Rule 2. Bars must extend ld past the actual cutoff points of adjacent bars.
Are rule 1 numbers greater than ld?
YES
Rule 4. At positive moment points of inflection, the bars must satisfy the following:
ld≤Mn/Vu+la
Pos. Moment Inflection Points: 0.098ln = 33.56 in from exterior end
(from fig. A-3) 0.146ln = 50.00 in from interior end
At these pts, have 2 #9
Area of one Bar: 1.00 in
Mn = 2503.4 in-kips
Check at the exterior end.
Vu/φ = 33.01 kips
76
A-4. GIRDER CALCULATIONS
la= smaller of actual extension, that exceeds 33.56 in, or d or 12 db
la= 21.11
Therefore,
Mn/Vu+la = 105.39 OK
c) Select Cutoffs for Positive Moment Steel in Second Span
Selected Bars for Span: 3 #9
Run 2 #9 Bars into the support and cutoff the remaining #9 bars
Area of 2 Bars: 2 in2
As, Remaining: 0.33 times the original
.215ln = 73.62 in from face of support
Rule 1. Bar must extend d past flexural cutoff point
Exterior Cutoff 52.51 in. from exterior end
Interior Cutoff 52.51 in. from interior end
Rule 2. Distance from midspan on exterior end 118.71 in
Distance from midspan on interior end 118.71 in
Rule 3. Must lap splice the bars a length of ld = 57.2
Rule 4. At positive moment points of inflection, the bars must satisfy the following:
ld≤Mn/Vu+la
Positive moment points for inflection are .146*ln from the supports
.146*ln = 50.00 in from exterior end
At these pts, have 2 #9
Area of one Bar: 1.00 in
Mn = 2503.4 in-kips
Check at the exterior end.
Vu/φ = 33.07 kips
la= smaller of actual extension, that exceeds 50.00 in, or d or 12 db
21.1
Therefore,
Mn/Vu+la = 105.22 OK
d) Perform the Preliminary Calculations for Negative Moment
(ACI 12-5)
No. 6 = 0.75 in
12d b = 9 in
lbh = 15.21 x 0.7 = 10.65
No. 9 = 1.128 in
12d b = 13.536 in
lbh = 22.88 x 0.7 = 16.02
These can be multiplied by .7 since the side cover exceeds 25 in.
77
A-4. GIRDER CALCULATIONS
e) Select Cutoffs the Negative Moment Steel at the Exterior End
Selected Bars for Span: 3 #9
Extend all bars past the negative moment point of inflection
.108ln = 36.98 in (Fig. A-3)
Rule 6. One-third of bars must extend the longer of d, 12db, or ln/16 past the point of inflection
Cutoff at 58.4 in. from the face of the support
Rule 2. Bars must extend ld from the face of the support
38.03 in. OK
f) Select Cutoffs for the Negative Moment Steel at Interior End - 1
Selected Bars for Span: 3 #9 1 #6
Cutoff 2 #9 and 1 #6 bars when no longer needed and extend 2 #9 bar .67As past the negative moment point of inflection
Extend all bars past the negative moment point of inflection
.065ln = 22.26 in (MacGregor Fig. A-3)
Rule 1. Bar must extend 43.4 in. from the face of the support
Rule 2. Bars must extend ld from the face of the support
57.20 in. OK
Cutoff 2 #9 bars 57.20 in. from exterior face of support
Extend remaining bars entire length of beam
.224ln = 76.70 in
Rule 6. One-third of bars must extend the longer of d, 12db, or ln/16 past the point of inflection
Cutoff at 97.8 in. from the face of the support OK
Rule 2. Bars must extend ld past actual cutoff
40.62 in. NO
Cutoff bars at 114.4 in. from exterior face of support
g) Select Cutoffs for the Negative Moment Steel at Interior End - 2
Selected Bars for Span: 3 #9 1 #6
Extend 2 #9 bars the entire length of the beam
.24ln = 82.18 in (MacGregor Fig. A-1)
Rule 6. Bars must extend the longer of d, 12db, or ln/16 past the point of inflection
Cutoff at 103.6 in. from the face of the support
Rule 2. Bars must extend ld from the face of the support
64.52 in. OK
Cutoff bars at 103.6 in. from the face of the support
CALCULATED BY: BAJ
CHECKED BY: KTA
78
A-5. Column Calculations
79
A-5. COLUMN CALCULATIONS
Support Interior Column Design TableFollowing Example 11-1 in Reinforced Concrete Mechanics and Materials
f'c [ksi] 3.5
fy [ksi] 60
Es [ksi] 29000
φ 0.65
Tie dia [in] 0.38
Number of Bars 4
Bar # #8
b [in] 21.26 540
h [in] 21.26 540
As2 [in2] 3.16
As1 [in2] 3.16
ρt 0.014
L [ft] 13.78 4.20
Cover [in] 1.50 Interaction Diagram Curve Data
d [in] 19.76
d' [in] 2.38 Mn [ft*kips] Pn [kips] Mn [kN*m] Pn [kN]
dt [in] 18.88 0.00 1705.04 0.00 7584.38
β1 0.8 563.16 583.02 763.53 2593.42
εy 0.00207 420.39 395.26 569.97 1758.20
εu 0.003 331.66 200.19 449.66 890.50
0.00 -379.20 0.00 -1686.77
1.Concentric Axial Load Capacity and Maximum Axial Load Capacity
φMn [ft*kips] φPn [kips] φMn [kN*m] φPn [kN]
P0 [kips] 1705.04 0.00 1193.53 0.00 5309.06
φ 0.70 394.21 408.12 534.47 1815.39
φP0 [kips] 1193.53 353.71 332.56 479.56 1479.31
φPn,max [kips] 954.82 298.49 180.17 404.69 801.45
φPn,max [kN] 4247.25 0.00 -341.28 0.00 -1518.09
2. Compute φP n and φM n for the General Case Mn [ft*kips] φPn,max [kips] Mn [kN*m] φPn,max [kN]
0 954.82 0.00 4247.25
3. Compute φP n and φM n for the Balanced Failure (ε s1 = - ε y ) 100 954.82 135.58 4247.25
c [in] 11.18 200 954.82 271.16 4247.25
εs2 0.00236 300 954.82 406.74 4247.25
εs1 -0.00207 400 954.82 542.32 4247.25
fs2 [ksi] 68.51
a [in] 8.94
Cc [kips] 565.5
Fs1 [kips] -189.60
Fs2 [kips] 207.10
Pn [kips] 583.02
Mn [ft*kips] 563.16
φPn [kips] 408.11611
φMn [ft*kips] 394.21
4. Compute φP n and φM n for Z= -2
c [in] 7.94
εs2 0.00210
εs1 -0.00414
fs2 [ksi] 60.97
a [in] 6.35
Cc [kips] 401.6
Fs1 [kips] -189.60
Fs2 [kips] 183.26
Pn [kips] 395.26
Mn [ft*kips] 420.39
φ 0.8413793
φPn [kips] 332.56
φMn [ft*kips] 353.71
h d
b
d'
dt
80
A-5. COLUMN CALCULATIONS
5. Compute φP n and φM n for Z= -4
c [in] 5.02
εs2 0.00158
εs1 -0.00828
fs2 [ksi] 45.88
a [in] 4.02
Cc [kips] 254.2
Fs1 [kips] -189.60
Fs2 [kips] 135.57
Pn [kips] 200.19
Mn [ft*kips] 331.66
φ 0.9
φPn [kips] 180.17
φMn [ft*kips] 298.49
6. Compute the Capacity in Axial Tension
Pnt [kips] -379.2
φ 0.9
φPnt [kips] -341.28
Slenderness test
k 1.2
M1 [kN*m] 99.9
M2 [kN*m] 220.9
Slender Colum? Yes *ACI 10.11.2
Design the lap splices
Column w/ max Pn 2.2
Pn [kN] 3831.371
Column w/ max Mn 3.4
Mn [kN*m] 220.891
Pn [kips] 861.33
Mn [ft*kips] 162.92
Pu / bh 1.239 *check Figs. A-6 and A-7 for stress in bars adjacent to the tension face
Mu / bh2
0.011 *check ACI Sec 12.17.2.2 and 12.17.2.3 to see if splice is Class A or Class B
Stress in bars 0.2 *check ACI Sec. 12.17.2.2, stress must be less then 0.5f y
α 1.00 *obtained from ACI Sec 12.2.4
β 1.00
λ 1.00
ld [in] 50.709 *we will assume that all of the bars are spliced at the same location
1.3ld [in] 65.922 *if this approaches half of column height then reduce reinforcing size and inc. number of bars
1.3ld [m] 1.675
Select the ties
Selected tie diameter 3 *if the bar is smaller then a #10 then the smallest tie that can be used is a #3
Condition #1 [in] 16 *16 logitudinal bar diameters
Condition #2 [in] 18 *48 tie diameters
Condition #3 [in] 21 *least dimension of the column
Required spacing [in] 16 *the required spacing is the smallest of the previous conditions
Required spacing [m] 0.407
CALCULATED BY: JAL
CHECKED BY: KLS
81
A-6. Foundation Calculations
82
A-6. FOUNDATION CALCULATIONS
Design for Base Area of Footing (F0.1)Service DL [kips] 0
Service LL [kips] 0
Service Surcharge [ksf] 0.1
Allowed Soil Pressure [ksf] 2
Column Dimesion [in] 18.11 460
Depth [ft] 3
Strength of Concrete [kips] 3.5
Strength of Steel [kips] 60
Determin Base Area
Af [ft2] 262 24.36
Min Square Footing Side Length [ft] 16.20 4.938
Design Square Footing Side Length [ft] 16.21 4.940
Factored Loads and Soil Reaction
Pu [kips] 395.87 1761
qs [ksf] 1.51
Design for Depth of Footing
f'c [psi] 3500
Pu [kips] 395.87
qs [ksf] 1.51
Assumptions
Footing Thickness [in] 23.62 0.6
Average Effective Thickness, d [in] 17.72 0.45 Assume a .15m difference between Footing Thickness
and Average Effective Thickness
Wide Beam Action
bw [ft] 16.2
Trib. Area [ft2] 95.2
Vu [kips] 143
Φ 0.75
ΦVn [kips] 306 OK
Two-way Action
Trib. Area [ft2] 253.8
Vu [kips] 382
bo [in] 143.3 40 for interior columns
βc 1.5 30 for edge columns
bo / d 8.09 20 for corner columns
αs 40
2 + 4 / βc 4.651113468
(αs*d) / bo + 2 6.95
4 4
Governing Value [min] 4
ΦVc [kips] 451 OK
Design for Footing Reinforcement
Critical section for moment on face of column
Mu [ft-kips] 659.63
f'c [psi] 3500
fy [psi] 60000
Compute required A s assuming tension-controlled section
Φ 0.9
Rn [psi] 144.08
Avg. Weight of Soil & Conc. Above Footing Base
[kcf]0.13
L
Depth
Surcharge
P
d
v v v v v v v v v v v
83
A-6. FOUNDATION CALCULATIONS
ρ 0.0025
p (gross area) 0.00185
ρmin 0.0018 OK
As [in2] 11.46
Chosen As [in2] 11.78
No. Bars 15
Diameter of Bars [in] 1
Check net tensile strain
a 1.22
β1 0.85
c 1.44
εt 0.034
Check development of reinforcement
Clear cover (bott. and side) [in] 3
Center-to-center bar spacing [in] 13.4
Clear cover + bar dia. 3.5
Bar spacing / 2 6.7
c (Governing Value [min]) 3.5
Ktr 0 0 no transverse reinforcement
(c + Ktr) / db 3.50
2.50 <- use 2.5 if ((c + Ktr) / db) > 2.5
α 1 =1.0 if less than 12" concrete below bars
β 1 =1.0 for uncoated reinforcement
αβ 1 OK
γ 1 =1.0 if larger than No. 7 bars
λ 1 =1.0 for normal weight concrete
ld [in] 30.4 OK
Max. available for development 85.19129449 OK
Design for Transfer of Force at Base of Column
f'c (column) [psi] 3500
f'c (footing) [psi] 3500
fy [psi] 60000
Pu [kips] 395.8728
ΦPnb [kips] 633.9079079 OK
Bearing Strength Increase Factor
A1 [in2] 327.8127514
A2 [in2] 12677.36132
sqrt(A2/A1) 6.218727299
if ^ greater than 2, use 2 2
ΦPnb [kips] 1267.815816 OK
Required dowel bars btw column and footing
As (min) [in2] 1.64
Chosen As [in2] 1.77
No. Bars 4
Diameter of Bars [in] 0.750
In Column
ldc [in] 15.21 Governs
ldc (min) 13.5
In Footing
ldc [in] 15.21 Governs
ldc (min) 13.5
Available length for development in footing
Tension controlled, assumption OK
84
A-6. FOUNDATION CALCULATIONS
17.87 OK
Dimensions m
A 4.94
B 0.34
C 0.0762
D 0.60
E 0.486
F 0.511
G 0.39
H
CALCULATED BY: AJL
CHECKED BY: JAL
85
A-7. Land Development Calculation
86
A-7. LAND DEVELOPMENT CALCULATIONS
Using Wastewater Engineering: Treatment, Disposal, and Reuse By Metcale and Eddy, Inc
Septic Tank Sizing:
Using pg 19, Table 2-4
User Unit Range Typical
School, day
w/o cafeteria or gym
To size the septic tank, the typical value of 10 gal/student*day was chosen.
At this point, the exact occupancy of the proposed building is unknown.
Currently, the septic tanks will be designed for use by 100 students.
Total water-use value:
100 students @ 10 gal/student*day = 1000 gal/day
For an average retention time in the tank of 5 days, the septic tanks will
need to be able to hold a total of 5000 gals
In order to account for redundancy, several tanks will be chosen instead of
one large tank.
Design for: 2 tanks 3000 gal
This will be able to hold 6000 gals. This accounts for present needs,
contingency, and room for expansion.
3000 gals = 11.356 m3
CALCULATED BY: KTA
CHECKED BY: KLS
Disposal Field For Septic Tank Effluent Design:
Given the average daily flowrate and septic tank volume calculated above, the
average detention time in the septic tank at peak flow is calculated as follows:
*Assume 30% of the volume is lost because of sludge and scum accumulations
*Daily peaking factor of 3 is used based on average flow
Detention Time = [(Septic Tank Volume)*(0.30)]/[(Peaking Factor)*(Daily Flow)]
Detention Time = 1.4 days (min of 0.5; ok)
*Assume maximum trench depth and width to be 5 ft. and 1 ft.m, respectively
*Assume maximum depth in trenches below the distribution pipe is 4 ft.
*Allowable hydraulic loading rate of 0.3 gal/ft^2*d assumed (from Table 14-13)
Sanitary Sewer System Calculations:
Flow, gal/unit*d
5-15 10student
87
A-7. LAND DEVELOPMENT CALCULATIONS
Percolation Capacity = 2.4 gal/ft. of trench
Required Trench Length = Daily Flow/Percolation Capacity
Trench Length = 417 ft. (use 130 m)
*Since 140m is quite long, divide trench into shorter sections; use 4 separate
trenches, each 35 meters in length.
CALCULATED BY: KLS
CHECKED BY: KTA
88
B. Drawing Set
89
C. Project Schedule