  • AMIT MISHRA 2

    INTRODUCTION

    Alarms are used to monitor the site in case of any fault occur then alarm panel automatically generate the alarm for corresponding fault occurred at site.

  • AMIT MISHRA 3

    Why alarms are used at site?

    External alarm is important at BTS site because in case of any fault occur then as a maintenance engineer it will be easier for us to identify the problem and rectify it accordingly. We can check at DDF, where termination of alarm is done. It provide security and stability to whole BTS site.

  • AMIT MISHRA 4

    ALARM

    BTS

    SITE

    EXTERNAL

    ALARM

    INTERNAL

    ALARM

    TYPES OF ALARM AT BTS SITE

  • AMIT MISHRA 5

    PARAMETER OF EXTERNAL ALARM

    These are parameter which may differ according to manufacturer.

    ALARM NO ALARM

    TYPE(NO/NC)

    ALARM SEVERITY

    ALARM PORT

    NO/PIN NO

    COLOUR CODE

    ROUTE OF

    ALARM

    ALARM NAME OR SYNTAX OR TITLE

    ROOT CAUSE OF

    ALARM

    CAUSE OF ALARM

  • AMIT MISHRA 6

    ALARM NAME OR SYNTAX OR TITLE

    It define the name of the alarm at BTS site. It may differ according to the operator. Depending upon BTS used syntax or title can change. Some of the example of name of alarm operator are as follows..

    BTS NAME ALARM NAME

    NOKIA FLEXI BTS DG FAILS TO START MAINS FAILURE

    ERICSSION RBS 2964 DG FAILS TO STOP DOOR OPEN

  • AMIT MISHRA 7

    NORMALLY

    OPEN

    NORMALLY

    CLOSED

    PARAMETER DESCRIPTION CONTINUED

    ALARM TYPE

    ALARM NO

    Every operator decide a particular alarm no for its BTS site and accordingly series of alarm is decided. for eg-7401 in NOKIA flexi BTS case.

    ALARM TYPE

    Type of alarm means that either alarm will be normally Closed or normally open. Normally open means that state of alarm in normal condition is OPEN. Normally closed means that state of alarm in normal condition is closed.

  • AMIT MISHRA 8

    PARAMETER DESCRIPTION

    SEV

    ER

    ITY

    CRITICAL

    MAJOR

    MINOR

    CRITICAL

    Critical means that ,it require immediate attention, if on BTS site any alarm is critical defined that means that level of alarm severity is high. for eg : LLOP- low lubricant oil pressure.

    MAJOR

    Major means that ,its severity level is lesser than critical but it is also needed attention as soon as possible. for eg: low fuel level

    MINOR

    Minor means that ,its severity level is lesser in compare to other alarm and site may not get affected as much as in case of critical and major. for eg- site on DG.

  • AMIT MISHRA 9

    PORT

    NO/PIN

    NO

    COLOUR

    CODE

    OPERATOR

    SPECIFIC

    ALARM PORT

    Alarm port or pin no is decided by operator itself .

    COLOUR CODE

    The colour code of alarm wire is decided by operator itself. Always it will exist in pair for PCM cables used.

  • AMIT MISHRA 10

    ROUTE

    of

    ALARM

    IT DECIDE ROUTE OF

    ALARM

    ROOT

    CAUSE

    IT DECIDE THE CAUSE

    OF ALARM

    ROUTE OF ALARM

    It decide the route of alarm or we can say that where alarm connection start till termination of that alarm.

    ROOT CAUSE

    Root cause means the exact cause of fault which led to the alarm at the site.

    c

  • AMIT MISHRA 11

    ALARM CABLE CONNECTION Alarm cable are PCM cable. They exist in pairs. Each alarm will be connected to ddf with these cable.(two wire is one pair) 37 pin D-type connector. Alarm ddf installed on shelter wall. Alarms are connected to sensors.

    25 PAIR PCM CABLE

  • AMIT MISHRA 12

    DDF ALARM CONNECTION

    D TYPE 37 PIN

    For connection of alarm these are needed.

  • AMIT MISHRA 13

    TYPE OF EXTERNAL ALARMS 1. DOOR OPEN 2. HIGH TEMPERATURE 3. DG FAILS TO START 4. DG FAILS TO STOP 5. LOW FUEL LEVEL 6. FIRE OR SMOKE 7. LOW LUBRICATION OIL PRESSURE 8. LOAD ON DG 9. AC FAILS TO START(AC-1/AC-2) 10.RECTIFIER MODULE PAIR FAILS 11.LOW BATTERY VOLTAGE 12.SITE ON DG 13.AC -1 FAILS 14.AC-2 FAILS 15.DG RUNNING WITHOUT LOAD

  • AMIT MISHRA 14

    TO ELABORATE ABOVE DESCRIPTION TAKE EXAMPLE OF NOKIA FLEXI BTS

    There are 12 external alarm for nokia flexi BTS. For 12 alarm connection ,we need 37 pin D connector in which 24 pins will be used. For each alarm , we require one pair E1 cable having two wire. Termination of these cable is done on DDF i.e from BTS to DDF and from alarm sensor to DDF.

  • AMIT MISHRA 15

    ALARM NO-7401/ALARM

    NO1

    SYNTAX-MAINS FAILURE

    SEVERITY-MINOR

    ALARM TYPE-NORMALY

    OPEN

    PIN NO-7/25

    COLOR CODE-GREEN&

    GREEN/WHITE

    ROOT CAUSE -MAINS FAILURE

    ROUTE OF ALARM PIU/AMF DDF BTS

  • AMIT MISHRA 16

    ALARM NO-7402/ALARM

    NO2

    SYNTAX-RECTIFIER MODULE FAILURE

    SEVERITY-MINOR

    ALARM TYPE-NORMALY

    OPEN

    PIN NO-8/26

    COLOR CODE-BLUE& BLUE/WHITE

    ROOT CAUSE -RECTIFIER FAILURE

    ALARM CONFIGURATION CONTINUED

    ROUTE OF ALARM POWER

    PLANT DDF BTS

  • AMIT MISHRA 17

    ALARM NO-7403/ALARM

    NO3

    SYNTAX-BATTERY AT 47V/LOW BATTERY

    VOLTAGE

    SEVERITY-CRITICAL

    ALARM TYPE-NORMALY

    OPEN

    PIN NO-9/27

    COLOR CODE-VOILET& WHITE VOILET

    ROOT CAUSE -BATTERY VOLTAGE IS BELOW -48V

    ALARM CONFIGURATION CONTINUED

    POWER

    PLANT DDF BTS ROUTE OF ALARM

  • AMIT MISHRA 18

    ALARM NO-7404/ALARM

    NO4

    SYNTAX-LOAD ON BATTERY

    SEVERITY-MAJOR

    ALARM TYPE-NORMALY

    OPEN

    PIN NO-10/28

    COLOR CODE-GREY& WHITE GREY

    ROOT CAUSE -ALL RECTIFIER IN P.P FAILED

    ALARM CONFIGURATION CONTINUED

    POWER

    PLANT DDF BTS ROUTE OF ALARM

  • AMIT MISHRA 19

    ALARM NO-7405/ALARM

    NO5

    SYNTAX-LOAD ON DG

    SEVERITY-MINOR

    ALARM TYPE-NORMALY

    OPEN

    PIN NO-11/29

    COLOR CODE-PINK& BLACK/RED

    ROOT CAUSE-MAINS FAILURE

    ALARM CONFIGURATION CONTINUED

    PIU/

    AMF DDF BTS ROUTE OF ALARM

  • AMIT MISHRA 20

    ALARM NO-7406/ALARM

    NO6

    SYNTAX-DG LLOP

    SEVERITY-CRITICAL

    ALARM TYPE-NORMALY

    OPEN

    PIN NO-12/30

    COLOR CODE-LIGHTGREEN&

    BLACK/ GREEN

    ROOT CAUSE-WHEN LUBRICANT OIL PRESSURE IN ENGINE GOES BELOW SPECIFIED LEVEL

    ALARM CONFIGURATION CONTINUED

    ROUTE OF ALARM PIU/AMF DDF BTS LLOP

    SENSOR

  • AMIT MISHRA 21

    ALARM NO-7407/ALARM

    NO7

    SYNTAX-LOW FUEL LEVEL

    SEVERITY-MINOR

    ALARM TYPE-NORMALY

    OPEN

    PIN NO-13/31

    COLOR CODE-LIGHT BLUE&BLACK

    ROOT CAUSE -WHEN THE FUEL IN TANK GOES BELOW 40%.

    ALARM CONFIGURATION CONTINUED

    ROUTE OF ALARM FUEL

    SENSOR PIU/AMF DDF BTS

  • AMIT MISHRA 22

    ALARM NO-7408/ALARM

    NO8

    SYNTAX-DG FAIL TO START

    SEVERITY-MAJOR

    ALARM TYPE-NORMALY

    OPEN

    PIN NO-14/32

    COLOR CODE-WHITE BLACK/WHITE

    ROOT CAUSE-DG DOESNT START AFTER 3 ATTEMPTS BY PIU/AMF

    ALARM CONFIGURATION CONTINUED

    PIU/

    AMF DDF BTS ROUTE OF ALARM

  • AMIT MISHRA 23

    ALARM NO-7409/ALARM

    NO9

    SYNTAX-AC FAILS

    SEVERITY-MAJOR

    ALARM TYPE-NORMALY

    OPEN

    PIN NO-15/33

    COLOR CODE-LIGHT GREY& LIGHT GREY

    /BLACK

    ROOT CAUSE-BOTH AC FAILS

    ALARM CONFIGURATION CONTINUED

    ROUTE OF ALARM- MICRO

    CONTROLLER DDF BTS

  • AMIT MISHRA 24

    ALARM N0-7410/ALARM

    NO10

    SYNTAX-DOOR OPEN

    SEVERITY-MINOR

    ALARM TYPE-NORMALY CLOSED

    PIN NO-16/34

    COLOR CODE-GREEN&

    GREEN/WHITE

    ROOT CAUSE -WHEN SHELTER DOOR IS OPEN.

    ALARM CONFIGURATION CONTINUED

    ROUTE OF ALARM- DOOR

    SENSOR PIU/AMF DDF BTS

  • AMIT MISHRA 25

    ALARM NO-7411/ALARM

    NO11

    SYNTAX-HIGH

    TEMPERATUR-E

    SEVERITY-MAJOR

    ALARM TYPE-NORMALY

    OPEN

    PIN NO-17/35

    COLOR CODE-ORANGE/

    RED&ORANGE/LIGHT GREY

    ROOT CAUSE -WHEN TEMPERATURE REACHES ALARMING LEVEL.

    ALARM CONFIGURATION CONTINUED

    ROUTE OF ALARM- MICRO

    CONTROLLER DDF BTS

  • AMIT MISHRA 26

    ALARM CONFIGURATION CONTINUED

    ALARM NO-7412/ALARM

    NO12

    SYNTAX-FIRE/SMOKE

    SEVERITY-CRITICAL

    ALARM TYPE-NORMALY

    OPEN

    PIN NO-18/36

    COLOR CODE-ORANGE

    /BLACK&ORA-NGE/GREEN

    ROOT CAUSE -WHEN TEMPERATURE REACHES ALARMING LEVEL.

    ROUTE OF ALARM- FUEL

    SENSOR PIU/AMF DDF BTS

  • AMIT MISHRA 27

    APART FROM THESE ALARMS OF NOKIA FLEXI BTS WE HAVE FEW MORE AS FOLLOWS

    SYNTAX-DG FAILS TO

    STOP

    COLOUR CODE-

    OPERATOR SPECIFIC

    PIN NO-OPERATOR SPECIFIC

    ALARM NO-OPERATOR SPECIFIC

    ALARM TYPE-NORMALLY

    CLOSED

    SEVERITY-MINOR

    PIU/AMF DDF BTS ROUTE OF ALARM-

    ROOT CAUSE-WHEN PIU OR AMF NOT ABLE TO STOP DG AFTER 3 ATTEMPT.

  • AMIT MISHRA 28

    SYNTAX-AC-1 FAILS

    ALARM NO-OPERATOR SPECIFIC

    COLOUR CODE-OPERATOR SPECIFIC

    SEVERITY-MINOR

    ALARM TYPE-NORMALLY

    OPEN

    PIN NO OPERATOR SPECIFIC

    APART FROM THESE ALARMS OF NOKIA FLEXI BTS WE HAVE FEW MORE AS FOLLOWS

    MICRO

    CONTROLLER DDF BTS ROUTE OF ALARM-

    ROOT CAUSE-WHEN AC-1 FAILS

  • AMIT MISHRA 29

    SYNTAX-AC-2 FAILS

    ALARM NO-OPERATOR SPECIFIC

    COLOUR CODE-OPERATOR SPECIFIC

    SEVERITY-MINOR

    ALARM TYPE-NORMALLY

    OPEN

    PIN NO OPERATOR SPECIFIC

    APART FROM THESE ALARMS OF NOKIA FLEXI BTS WE HAVE FEW MORE AS FOLLOWS

    MICRO

    CONTROLLER DDF BTS ROUTE OF ALARM-

    ROOT CAUSE-WHEN AC-2 FAILS

  • AMIT MISHRA 30

    LIST OF DIFFERENT OPERATOR EXTERNAL ALARM

    Ericsson RBS2954

    DG on DG fails to start Main fails DG fuel level LLOP DG fails to stop Cabinet temperature Fire & smoke Door smoke BFU fault Spare SMPS input fail Battery low voltage DC disconnected alarm Battery breaker off Battery disconnected

  • AMIT MISHRA 31

    LIST OF DIFFERENT OPERATOR EXTERNAL ALARM

    Ericsson RBS2964

    DG on DG fails to start Main fails DG fuel level LLOP DG fails to stop Cabinet temperature Fire & smoke Door open BFU fault Spare SMPS input fail Battery low voltage DC disconnected alarm Battery breaker off Battery disconnected

  • AMIT MISHRA 32

    LIST OF DIFFERENT OPERATOR EXTERNAL ALARM

    HUAWEI 3900 Intruder A/C failure High room temperature Fire alarm Fire fighting Mains failure Generator failure Generator run Rectifier high voltage Tower light failure Rectifier 2/more failure Tower amplifier fail Rectifier low voltage Rectifier common alarm GN auto mode Low fuel in main tank

  • AMIT MISHRA 33

    LIST OF DIFFERENT OPERATOR EXTERNAL ALARM

    ZTE ZXG 10

  • AMIT MISHRA 34

    Sl. No External Alarms ID Breaking Closing Level 1 DG ON 0 Closing 2 2 DG fail to Start 1 Closing 1 3 Mains Fail 2 Closing 1 4 High Shelter 3 Closing 1 Temperature 5 DG Fuel Level Low 4 Closing 1 6 LLOP 5 Closing 2 7 DG Fail to Stop 6 Closing 1 8 Fire and Smoke 7 Closing 1 9 Door Open 8 Closing1 10 AC 1 - OFF 9 Closing 1 11 AC 2 OFF A Closing 1 12 Spare B 13 Battery Fuse Fail C Closing 1 14 Rectifier Fail D Closing 1 15 Battery Low Voltage E Closing 1 16 SMPS Input Fail F Closing 1

    ALARM DEFINED IN ERICSSON SITES:

  • AMIT MISHRA 35

    Port ID External Alarms Closing/Breaking Level 1 0 DG ON Closing 2 2 1 DG FAIL TO START Closing 1 3 2 MAINS FAIL Closing 1 4 3 DG FUEL LEVEL LOW Closing 1 5 4 LLOP Closing 2 6 5 DG FAIL TO STOP Closing 1 7 6 CABINET TEMPERATRE Closing 1 HIGH 8 7 FIRE AND SMOKE Closing 1 9 8 BBS DOOR OPEN Closing 1 10 9 BFU FAULT Closing 1 11 10 SPARE 12 B SMPS INPUT FAIL Closing 1 13 C BATTERY LOW VOLTAGE Closing 1 14 D DC DISCONNECTED ALARM Closing 1 15 E BATTERY BREAKER OFF Closing 1 16 F BATTERY DISCONNECTED Closing1

    EXTERNAL ALARMS FOR BTS (RBS 2954) SITES:

  • AMIT MISHRA 36

    S/N TTSL Requirement Node colour code 1 AC mains fail blue-white 2 High room temperature Orange-white 3 fire alarm Green-white 4 Battery Discharge Brown-white 5 rectifier fail Blue-red 6 intruder Orange-red 7 DG low fuel Red-green 8 DG running Brown-red After we connect the cable on krone block we will give loop with krone tool one by one and check weather alarm get disappear in OMCR or not. Same way we have to check for all the 8 ports.

    BELOW MENTIONED COLOUR CODE OF RBS(2954)-

  • AMIT MISHRA 37

    EXTERNAL ALARM IN HUAWEI 3900 BTS AND COLOUR CODE-

    KRONE NO:1 KRONE NO:2

    NO: port SLOT DDF ALARM NO: port SLOT DDF ALARM

    1 0 18 1 INTRUDER 9 0 19 1

    RECTIFIER

    HIGH

    VOLTAGE

    2 1 18 2 A/C

    FAILURE 10 1 19 2

    TOWER

    LIGHT

    FAILURE

    3 2 18 3

    HIGH

    ROOM

    TEMPERA

    TURE

    11 2 19 3

    RECTIFIER

    2/MORE

    FAILURE

    4 3 18 4 FIRE

    ALARM 12 3 19 4

    TOWER

    AMPLIFIE

    R FAIL

    5 4 18 5 FIRE

    FIGHTING 13 4 19 5

    RECTIFIER

    LOW

    VOLTAGE

    6 5 18 6 MAINS

    FAILURE 14 5 19 6

    RECTIFIER

    COMMON

    ALARM

    7 6 18 7

    GENERAT

    OR

    FAILURE

    15 6 19 7 GN AUTO

    MODE

    8 7 18 8 GENERAT

    OR RUN 16 7 19 8

    LOW FUEL

    IN MAIN

    TANK

  • AMIT MISHRA 38

    HUAWEI EXTERNAL ALARMS(COLOURS)

    EXTERNAL ALARM COLOUR CODES

    CABLE NO: PAIR COLOUR

    1 1 WHITE

    ORANGE

    2 1 ORANGE

    3 2 WHITE

    GREEN

    4 2 GREEN

    5 3 WHITE

    BLUE

    6 3 BLUE

    7 4 WHITE

    BROWN

    8 4 BROWN

  • AMIT MISHRA 39

    INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE

    LIST OF ALARMS (1)RECTIFIER & BTS DOOR CABINET ALARM (2)RECTIFIER MAJOR ALARM (3)RECTIFIER MINOR ALARM (4)LOW DC VOLTAGE (5)HEAT MANAGEMENT ALARM(FOR AC CABINET ONLY) (6)TEMPERATURE ALARM(FOR FAN COOL CABINE ONLY)

    CORRESPONDING ALARM NO- ALARM NO1 ALARM NO2 ALARM NO3 ALARM NO4 ALARM N05 ALARM NO7

  • AMIT MISHRA 40

    INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE

    LIST OF COLOUR CODE OF ABOVE ALARM

    ALARM NO1-RECTIFIER & BTS DOOR CABINET ALARM- GREEN & WHITE GREEN ALARM NO2-RECTIFIER MAJOR ALARM-BLUE & WHITE BLUE ALARM NO3-RECTIFIER MINOR ALARM-VIOLET & WHITE VIOLET ALARM NO4-LOW DC VOLTAGE-GREY & WHITE GREY ALARM NO5-HEAT MANAGEMENT ALARM(FOR AC CABINET ONLY)-BLUE/BLACK &BLACK BLUE ALARM NO7-TEMPERATURE ALARM(FOR FAN COOLED CABINET ONLY)-LIGHTBLUE &LIGHT BLUE/ BLACK

  • AMIT MISHRA 41

    INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE

    MATERIAL REQUIREMENT- ALARM CABLE KRONE RACK CAT-5 CABLE 7-9 METER SOLDERING IRON OTHRE BASIC TOOLS

  • AMIT MISHRA 42

    INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE

    INSTALLATION PROCESS- Initial step before installation-

    (1)Alarm cable is too long so cut it into two pieces. (2)1st cable will be used to take alarm from rectifier smart pack i/o ports to crone. (3)2nd cable with connector at one end will be used for taking alarms from krone to BTS EAC port(2G cabinet).

  • AMIT MISHRA 43

    INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE

    INSTALLATION PROCESS CONTINUE-

    STEP-1 KRONE INSTALLATION

    Install the krone on rack and fix this rack in rectifier cabinet. Use proper size bolts and washer.

  • AMIT MISHRA 44

    Alarm cable installation(BTS KRONE)

    INSTALLATION PROCESS CONTINUE-

    Connect the alarm cable connector on EAC port at BTS(2G cabinet) Bring the other end of alarm cable to rectifier through roxtec. Punch the alarm cable on the lower side of krone according to the alarms sequence. The alarm cable should be fixed properly with ties and properly routed.

  • AMIT MISHRA 45

    INSTALLATION PROCESS CONTINUE-

    Route this cable properly with ties and fix it near the Rectifier I/O

    ports

    Connect Green & White Green (Alarm nu 1) with Pins 8 & 9 of CON1

    (X1)

    Connect Grey & White Grey (Alarm nu 4) with Pins 9 & 10 of CON2

    (X2)

    Connect Violet & White Violet (Alarm nu 3) with Pins 15 & 16 of

    CON2 (X2)

    Connect Blue & White Blue (Alarm nu 2) with Pins 18 & 19 of CON2

    (X2)

    Connect Light Blue & Light Blue Black (Alarm nu 7) with Pins 12 & 13

    of CON2 (X2) (Only for Fan Cool Rectifier Cabinets)

  • AMIT MISHRA 46

    CON 2

    ( X2 )

    CON 1

    ( X1 )

  • AMIT MISHRA 47

    HEAT MANAGEMENT ALARM

    INSTALLATION PROCESS CONTINUE-

    Air condition in the door usually has Red & Yellow cable for Air Condition Alarm. This cable is connected to Pins 3 & 4 on CON1. Remove this cable from there & punch it on Krone.

    AIR CON ALARM CABLE

  • AMIT MISHRA 48

    Remove this cable from pins &

    punch it on Krone as shown Air Con Alarm cable

    INSTALLATION PROCESS CONTINUE-

  • AMIT MISHRA 49

    To test Heat Management Alarm cover the AC from outside with plastic so that no air can go through as shown below Air Condition covered with plastic sheet

    TESTING HEAT MANAGEMENT ALARM-

    INSTALLATION PROCESS CONTINUE-

  • AMIT MISHRA 50

    900 BTS CABINET DOOR SENSOR

    INSTALLATION PROCESS CONTINUE-

    The BTS Cabinet door sensor cable is very small so we have to extend it Take 1 pair from CAT-5 Cable and solder it with the sensor wires in BTS (900 Cabinet) Route this cable properly and fix it near Smart Pack I/O ports Connect this pair with pins 3 & 4 of CON 2

    BTS Cabinet door Sensor

  • AMIT MISHRA 51

    INSTALLATION PROCESS CONTINUE-

    RECTIFIER CABINET DOOR SENSOR

    Usually Rectifier door Sensor cables are already connected to the CON 1 (X1) If it is not connected then connect Rectifier Door Alarm Cable with pins 1 & 2 of CON 1 (X1) Rectifier Door cable connected to pins 1 & 2 of CON 1

    Rectifier Door Sensor

  • AMIT MISHRA 52

    Overall summary is that on any BTS site external alarms are important. Alarms make fault finding easy. External alarms make BTS site safer and easy to maintain. Each alarm has its own importance cannot be neglected.

    SUMMARY