Home > Documents > 14 13 12 11 D - ABB · 2020. 11. 17. · myers type conduit hubs cat no nominal conduit diameter in...

14 13 12 11 D - ABB · 2020. 11. 17. · myers type conduit hubs cat no nominal conduit diameter in...

Date post: 25-Jan-2021
Category:
Upload: others
View: 0 times
Download: 0 times
Share this document with a friend
1
D C B A D C 14 13 12 11 12 13 14 11 B A Industrial Solutions 1.57 40 [ ] 23.50 597 [ ] .49 12 [ ] 9.96 253 [ ] .12 3 [] .12 3 [] 3.69 94 [ ] 3.69 94 [ ] .59 15 [ ] 3.09 78 [ ] 4.98 127 [ ] 5.56 141 [ ] 1.12 28 [ ] 5.44 138 [ ] .19 5 [] 3.03 77 [ ] 2.34 59 [ ] .61 15 [ ] .79 20 [ ] 9.50 241 [ ] 1.88 48 [ ] 2.22 56 [ ] .75 19 [ ] 1.78 45 [ ] 26.31 668,3 [ ] 2.79 71 [ ] 3.19 81 [ ] 3.02 77 [ ] 2.39 61 [ ] 1.06 27 [ ] 1.51 38 [ ] .270 7 [] .969 25 [ ] CHART 2 KNOCKOUTS SYMBOLS CONDIUT SIZE DIAMETER IN MM IN MM A 3 76 3 5/8 92 B 2 1/2 64 3 76 C 2 51 2 1/2 64 D 1 1/2 38 2 51 E 1 25 1 3/8 35 F 3/4 19 1 1/8 29 G 1/2 13 7/8 22 H 9/32 7 9/32 7 FIELD INSTALLABLE NEUTRAL ASSEMBLY AND GROUND KIT CAT NO. PREFIX TYPE AMPERE RATING WIRE SIZE (AWG\KCMIL) TGL1 GND KIT 70-125 AMP (4) #14-8 CU (4) #12-8 AL (3) #14-4 CU (3) #6-4 AL TGL20 GND KIT 150-400 AMP (1) #6-2/0 CU-AL TNIA225 NEUTRAL ASM 225 AMP (1) #1-300 CU-AL CHART 1 CONDUIT UNIVERSAL HUB INTERCHANGEABLE RAINPROOF BOX HUB CAT. NO. USE WITH CAT NO'S USING SUFFIX "R4" 3/4 TC75 - 1" TC100 TC4DH 1 1/4 TC125 TC4EH 1 1/2 TC150 TC4GH 2 TC200 TC4HH 2 1/2 TC250 TC4WH CLOSING CAP TCCP TC4WC CHART 3 MYERS TYPE CONDUIT HUBS CAT NO NOMINAL CONDUIT DIAMETER IN INCHES 343L647G1 1/4 343L647G2 3/8 343L647G3 1/2 343L647G4 3/4 343L647G5 1 343L647G6 1 1/4 343L647G7 1 1/2 343L647G8 2 343L647G9 2 1/2 343L647G10 3 CIRCUIT BREAKER TERMINAL LUG DATA CIRCUIT BREAKER CAT NO. PREFIX AMPERE RATING LUG TYPE WIRE SIZE (AWG/KCMIL) TEB, TED, THED 70-150 TCAL12A (1) #6-2/0 CU (1) #4-2/0 AL TCAL15 (1) #3-3/0 CU (1) #1-3/0 AL TQD, THQD 100-225 TCAL25 (1) #4-300 CU-AL SED,SEH,SEL,SEP 30-150 TCAL18 (1) #12-3/0 CU/AL OUTLINE DRAWING - NEMA TYPE 3R ENCLOSURE TE150R, TQD225R DWG NO. DATE REV 139C5498SH1 04/20 5 THIRD ANGLE SHEET 1 1 of 1 FOR USE WITH ABB TYPE BREAKER TE TEB TED & THED (70-150A) TQD THQD (225A) SEDA, SEHA, SELA & SEPA (30-150A) DUAL DIMENSIONS INCHES [MILLIMETERS] NOTES: 1. MATERIAL: LOW CARBON STEEL 2. FINISH: ELECTROCOAT ENAMEL, GRAY 3. AGENCY APPROVAL: cULus LISTED -FILE E11592 4. SUITABLE FOR USE AS SERVICE EQUIPMENT WHEN NEUTRAL ASSEMBLY IS INSTALLED 5. THE SHORT CIRCUIT RATING OF THIS ENCLOSED CIRCUIT BREAKER IS EQUAL TO THE INTERRUPTING RATING, AT THE SUPPLY VOLTAGE MARKED ON THE CIRCUIT BREAKER INSTALLED 6. FOR ALTERNATE LUGS CONSULT THE BUYLOG 7. HUB MGT HOLES TO BE PROVIDED BY CUSTOMER SEE DETAIL A A,B,C,D E,F,G A,B,C,D HUB SEE CHART 1 (FOR TE150RH & TQD225RH) SEE CHART 3 (FOR TQD225R) A,B,C,D B,C,D H G OUTSIDE EDGE OF THE BOX DETAIL A 4 PLCS MTG HOLE
Transcript
  • D

    C

    B

    A

    D

    C

    14 13 12 11

    121314 11

    B

    AIndustrial Solutions

    1.5740[ ]

    23.50597[ ]

    .4912[ ]

    9.96253[ ]

    .123[ ]

    .123[ ]

    3.6994[ ]

    3.6994[ ]

    .5915[ ]

    3.0978[ ]

    4.98127[ ]

    5.56141[ ]

    1.1228[ ]

    5.44138[ ] .19

    5[ ]

    3.0377[ ]

    2.3459[ ]

    .6115[ ]

    .7920[ ]

    9.50241[ ]

    1.8848[ ]

    2.2256[ ]

    .7519[ ]

    1.7845[ ]

    26.31668,3[ ]

    2.7971[ ]

    3.1981[ ]

    3.0277[ ]

    2.3961[ ]

    1.0627[ ]

    1.5138[ ]

    .2707[ ]

    .96925[ ]

    CHART 2KNOCKOUTS

    SYMBOLSCONDIUT SIZE DIAMETER

    IN MM IN MMA 3 76 3 5/8 92

    B 2 1/2 64 3 76

    C 2 51 2 1/2 64

    D 1 1/2 38 2 51

    E 1 25 1 3/8 35

    F 3/4 19 1 1/8 29

    G 1/2 13 7/8 22

    H 9/32 7 9/32 7

    FIELD INSTALLABLE NEUTRAL ASSEMBLY AND GROUND KITCAT NO.PREFIX TYPE

    AMPERERATING

    WIRE SIZE(AWG\KCMIL)

    TGL1 GND KIT 70-125 AMP(4) #14-8 CU(4) #12-8 AL(3) #14-4 CU(3) #6-4 AL

    TGL20 GND KIT 150-400 AMP (1) #6-2/0 CU-ALTNIA225 NEUTRAL ASM 225 AMP (1) #1-300 CU-AL

    CHART 1

    CONDUIT

    UNIVERSALHUB

    INTERCHANGEABLERAINPROOF BOX HUB

    CAT. NO. USE WITH CAT NO'SUSING SUFFIX "R4"3/4 TC75 -1" TC100 TC4DH

    1 1/4 TC125 TC4EH1 1/2 TC150 TC4GH

    2 TC200 TC4HH2 1/2 TC250 TC4WH

    CLOSING CAP TCCP TC4WC

    CHART 3MYERS TYPE CONDUIT HUBS

    CAT NO NOMINAL CONDUITDIAMETER IN INCHES343L647G1 1/4343L647G2 3/8343L647G3 1/2343L647G4 3/4343L647G5 1343L647G6 1 1/4343L647G7 1 1/2343L647G8 2343L647G9 2 1/2

    343L647G10 3

    CIRCUIT BREAKER TERMINAL LUG DATACIRCUIT BREAKER

    CAT NO.PREFIX

    AMPERERATING

    LUGTYPE

    WIRE SIZE(AWG/KCMIL)

    TEB, TED, THED 70-150 TCAL12A (1) #6-2/0 CU(1) #4-2/0 AL

    TCAL15 (1) #3-3/0 CU(1) #1-3/0 ALTQD, THQD 100-225 TCAL25 (1) #4-300 CU-AL

    SED,SEH,SEL,SEP 30-150 TCAL18 (1) #12-3/0 CU/AL

    OUTLINE DRAWING - NEMA TYPE 3R ENCLOSURE

    TE150R, TQD225RDWG NO. DATE REV

    139C5498SH1 04/20 5

    THIRD ANGLE SHEET 1

    1 of 1

    FOR USE WITH ABB TYPE BREAKERTE TEB TED & THED (70-150A)

    TQD THQD (225A)SEDA, SEHA, SELA & SEPA (30-150A)

    DUAL DIMENSIONS INCHES[MILLIMETERS]

    NOTES:1. MATERIAL: LOW CARBON STEEL2. FINISH: ELECTROCOAT ENAMEL, GRAY3. AGENCY APPROVAL: cULus LISTED -FILE E115924. SUITABLE FOR USE AS SERVICE EQUIPMENT WHEN NEUTRAL ASSEMBLY IS INSTALLED5. THE SHORT CIRCUIT RATING OF THIS ENCLOSED CIRCUIT BREAKER IS EQUAL TO THE INTERRUPTING RATING, AT THE SUPPLY VOLTAGE MARKED ON THE CIRCUIT BREAKER INSTALLED6. FOR ALTERNATE LUGS CONSULT THE BUYLOG7. HUB MGT HOLES TO BE PROVIDED BY CUSTOMER

    SEE DETAIL A

    A,B,C,D

    E,F,G

    A,B,C,D

    HUBSEE CHART 1 (FOR TE150RH & TQD225RH)SEE CHART 3(FOR TQD225R)

    A,B,C,DB,C,D

    H

    G

    OUTSIDE EDGE OFTHE BOX

    DETAIL A4 PLCS MTG HOLE

    Sheet 1Viewsmain_viewright_1bottom_1A