45
1/59 Heat sources for heat pumps ground water air
Transcript
Page 1: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

1/59

Heat sources for heat pumps

ground

water

air

Page 2: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

2/59

Natural and waste energy

energy from solar radiation = ambient energy

- solar radiation: 200 to 1000 W/m2

- air

- precipitation, surface water, well water

- ground

geothermal water in specific areas

waste energy

technology processes, laundry, washing, ventilation

Page 3: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

3/59

specific power

heat flow from ambient 10 to 40 W/m2 (in average)

heat flow from Earth core 0,04 to 0,06 W/m2

temperature

under 2-5 m stable conditions > 10 °C

geothermic temperature gradient 3 K/100 m

thermal conductivity

dry sand soil 1,1 W/m.K

wet granite 3,3 W/m.K

Ground energy

average 2 W/m.K

Page 4: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

4/59

Ground temperature

temperature

dept

h

Page 5: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

5/59

vertical bore heat exchangers

drilled dry ground boreholes

horizontal ground heat exchangers

subsurface HX

wells

extraction of ground water – different technology, different heat

pump application

Ground energy extraction

Page 6: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

6/59

Ground vertical boreholes

heat extraction by dry

boreholes under 200 m

usually under 100 m

not space demanding

1 or 2 pipe circuits in borehole

primary circuit temperatures:

from -4 °C to +4 °C

Page 7: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

7/59

design of length and number of boreholes

thermal properties of the ground

risk of undersizing – reveals after years

decrease of heat output and COP, insufficient borehole regeneration

ecology

disruption of water horizons

interconnection of deep horizons with high quality ground water with

shallow horizons with low quality

Knowledge of geology !

Page 8: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

8/59

Ground vertical - Thermal resistance of

ground

]m.K/W[ln2

1

v

z

z

zd

DR

diameter of influenced

field

Dz = 4 to 6 m

diameter of borehole

dv = 100 to 150 mm

HDPE DN25, DN32

thermal conductivity

z = 1,0 to 3,0 W/m.K

bore

stable

field

influenced

field

HP

thermal resistance

Page 9: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

9/59

Ground vertical - Specific heat flow

]W/m[12,

z

vzlz

R

ttq

Ground type specific heat flow

qz,l [W/m]

granite with water 100

conductive stone 80

standard solid stone, average 55

dry sands, low conductivity 30

borehole temperature

tv12 = around 0 °C (+4 to – 4°C)

ground temperature in stable field

tz = 12 °C (+3 K/100 m)

Page 10: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

10/59

Ground vertical - Specific heat flow

EN 15 450 (VDI 4650)

annual extracted energy should be between 100 and 150 kWh/m

Page 11: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

11/59

Ground vertical - Depth (length) of

borehole

final borehole depth given by drilling technology – similar technology

to water wells, not more than 100 m

more boreholes = division of flowrate = lower pressure losses

for nominal conditions determine the heat power and COP

]m[z

vv

q

Ql

COPQQ kv

11

qz considered according to

assumed operation time of HP

(1800, 2400 h)

Page 12: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

12/59

Alternative sizing

determination of annual heat delivered by HP QHP,del and COP

determination of annual extracted energy from borehole Qv

operation period DtHP: 1800 (space heating only), 2400 (space

heating and DHW)

determination of average extraction power (at evaporator)

COPQQ delv

11

HP

vv

QQ

tD design power for borehole

depth calculation

Page 13: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

13/59

Borehole construction

suitable piping: HD-PE, PE-RC (crack resistant), PN16 (100m)

minimum distance > 5 m to avoid the coupling of influenced

fields

better > 10 m: drilling is not completely vertical (deflection 2

m), distance larger than 10 % of borehole length

ground water flow: suitable location of boreholes to avoid

mutual cooling

borehole filling by bentonite (cement mixture)

can’t be filled by extracted soil ! = insulator

Page 14: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

14/59

Borehole construction

injection pipe – filling the borehole with bentonite

reduction – connection of circuits

distance bar – distance between pipes

support bar

U piece – bottom of borehole

anchor

Page 15: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

15/59

Example: ground source HP boreholes

house, heat load 10 kW (te,N = -12 °C, ti = 20 °C)

heat pump QHP = 10 kW, COP = 4,0 (at B0/W35)

heating season, monovalent operation

te,av = 4,3 °C, ti,av = 20 °C, 225 days of heating, correction factor 0,75

space heating demand QSH

hot water demand QHW = 3.5 MWh/a

= 19,9 MWh/a NeNi

avgeavgi

NSHtt

ttQQ

,,

,,24225

6

,

106,3365

CWHWdayHW

HW

ttcVQ

Page 16: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

16/59

Example: ground source HP boreholes

theoretical approach (power approach)

cooling power of the heat pump Qv = QHP (1 − 1/COP)

borehole

z = 2,5 W/mK, dv = 150 mm, Dz = 4 m, tz = 12 °C, tv1 = +2 °C, tv2 = -2 °C

thermal resistence of ground

specific heat power qz = (tz − tv12)/Rz

borehole length (depth)

v

z

z

zd

DR ln

2

1

= 0,22 mK/W

= 7.5 kW

= 54 W/m

lv = 140 m]m[z

vv

q

Ql

Page 17: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

17/59

Example: ground source HP boreholes

practical approach (demand approach): heating only 1800 h

heat extracted by heat pump Qex = QSH*(1 − 1/COP)

average cooling power of heat pump Qv = Qex / 1800 h

tables: average soil with 1,5 < z < 3,0

borehole length (depth)

= 14,9 MWh

= 8.3 kW

lv = 138 m

qz = 60 W/m (1800 h)

Page 18: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

18/59

Example: ground source HP boreholes

practical approach (demand approach): SH+HW 2400 h

heat extracted Qex = (QSH + QHW)*(1 − 1/COP)

average cooling power of heat pump Qv = Qex / 2400 h

tables: average soil with 1,5 < z < 3,0

borehole length (depth)

= 17,5 MWh

= 7.3 kW

lv = 146 m

qz = 50 W/m (2400 h)

Page 19: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

19/59

Horizontal ground heat exchangers

heat extraction from

subsurface layer (up to 2 m

depth)

possible influence of vegetation

space demanding excavation

large land need

HX temperatures around 0 °C

Page 20: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

20/59

Horizontal ground heat exchangers

depth min. 0,2 m under non freezing level

h = 0,6 to 2 m

pipe distance (spacing)

s = min. 0,8 m to 1,1 m

HDPE pipes 25 – 40 mm

thermal conductivity

z = 1,0 to 3,0 W/m.K

]m.K/W[2sinh2

ln2

1

s

h

d

sR

z

z

non freezing level

Page 21: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

21/59

Horizontal ground heat exchangers

Soil type specific heat flow

qz,l [W/m]

dry sands, non cohesive 10 – 15

dry solid soil 15 – 20

moist solid soil 20 – 25

soil saturated with ground water 25 – 30

soil with ground water flow 35 – 40

]W/m[12,

z

vzlz

R

ttq

temperature in pipes

tv12 = around 0 °C (+4 to – 4°C)

temperature of ground

tz = 10 °C

Page 22: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

22/59

Length and area of ground HX

]m[z

elk

z

vv

q

PQ

q

Ql

]m[ 2

,, Az

v

lz

v

q

Q

q

sQS

for a distance s = 1 m

qz,l becomes qz,A

Soil type specific heat flow

qz,A [W/m2]

dry sands, non cohesive 10 – 15

dry solid soil 15 – 20

moist solid soil 20 – 25

soil saturated with ground water 25 – 30

soil with ground water flow 35 – 40

Page 23: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

23/59

Specific heat flow EN 15 450 (VDI 4650)

annual extracted energy should be between 50 and 70 kWh/m2

for nominal conditions determine heat power and COP (at B0/W35)

]m[ 2

,Az

v

q

QS

COPQQ kv

11

qz,A is considered according to

assumed operation time of HP

(1800, 2400 h)

Page 24: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

24/59

Alternative sizing

determination of annual heat delivered by HP QHP,del and COP

determination of annual extracted energy from borehole Qv

operation period DtHP: 1800 (space heating only), 2400 (space

heating and DHW)

determination of average extraction power (at evaporator)

COPQQ delv

11

HP

vv

QQ

tD design power for ground HX

area calculation

Page 25: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

25/59

Construction of ground HX

length of cirucits should not exceed 100 m for DN25 ... or 400 m

for DN40 (pressure loss)

distribution of flowrate to number of circuits

circuit from one pipe, no junctions

surface above HX – permeable for rain (no concrete of asphalt

layers) for regeneration

mind the roots!

documentation of piping location

Page 26: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

26/59

Construction of ground HX

Page 27: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

27/59

Connection to house (borehole, HX)

brines (tF < -10°C): propylenglycol-water (30 / 70 %)

ethanol-water (40 / 60 %)

pipe with slope from distributor – deaeration

similar lengths of circuits – easy hydraulic balancing

passage into building in insulated protector

safety distance from building constructions (basements) –

pipes under freezing point

attention for crossing the water installation

piping inside building in insulation – condensation and freezing

Page 28: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

28/59

Borehole connection to house

Page 29: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

29/59

Ground HX connection to house

Page 30: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

30/59

Distributor

distributor located outside:

platic casing

concrete casing

Page 31: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

31/59

Ground water

chemical quality

quantity

stable water temperature =

average annual air

temperature

Page 32: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

32/59

Water

warm waste water: cooling processes

t = 20 to 25 °C

surface water: rivers, lakes

t = 0 to 18 °C, temperature infulenced by ambient climate

ground water: wells, boreholes

t = 7 to 10 °C, uniform temperature during the year

geothermal water: deep boreholes

t = 10 to 13 °C, temperature gradient 3 K/100 m

t > 25 °C, geotermal water

Page 33: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

33/59

Ground water

pumping well (max. 15 m

deep: pump power)

drain well (15 m from pumping well)

cooling by 3 to 4 K

for Qk = 10 kW ~ 1500 l/h (0,4 kg/s)

]kg/s[

21 vvv

vv

ttc

QM

water quantity (constant flowrate)

pumping test: 30 days, or more !

pumping

well

drain

well

Page 34: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

34/59

Pumping and drain well

drain well pumping

well

HP

Page 35: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

35/59

Water quality

chemical content

corrosion (stainless steel) – chlorides, oxygen

minerals (heat exchanger fouling)

fine particles - filters with automatic cleaning

Page 36: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

36/59

Example: water well sizing

heat pump QHP = 10 kW, COP = 4,0

cooling power of the heat pump Qv = QHP (1 − 1/COP)

tv1 = 10 °C, Dt = 4 K

water flowrate Mw = 0,45 kg/s

= 7.5 kW

= 27 l/min

Page 37: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

37/59

Ambient air

use of ambient heat

heat power dependent on

climate conditions

winter: COP < 3

summer: COP > 4

mostly bivalent operation

removal of condensate

noise (large flowrates)

Page 38: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

38/59

Ambient air

0

100

200

300

400

500

600

700

800

I II III IV V VI VII VIII IX X XI XII

Qp

[k

Wh

]

-5

0

5

10

15

20

t e [

°C]

t e

temperature of air is lowest

in the time of highest heat demand

Page 39: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

39/59

Ambient air – energy content, enthalpy

xttxtcltch Da 184010.5,21010 6

0

ca specific heat of dry air, v J/(kg.K);

t air temperature, v °C;

l0 latent heat of water (evaporation), v J/kg;

cD specific heat of water vapour, v J/(kg.K);

x specific humidity of air, v kg w/kg da.

21 vv

vv

hh

QV

Page 40: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

40/59

Construction

indoor units outdoor units

Page 41: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

41/59

Indoor units

Page 42: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

42/59

Outdoor units

Page 43: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

43/59

Condensate

condensation of water content in air at evaporator of heat pump

removal of condensate

drainage to ground (outdoor units)

connection to sewer system

(indoor units)

transfer pump

concrete sheet

gravel layer condensate

removal

Page 44: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

44/59

Frost

frosting at evaporator surface

reduction of heat transfer

decrease of evaporator pressure and temperature, power, COP

reduction of cross section, increase of pressure loss, increase of fan

power, operation restriction

defrosting

internal cycle (favourable): hot vapor, reverse cycle

outter heating: electric cables at evaporator

by air above +3 °C, HP is OFF, fan is ON

Page 45: 1/59 Heat sources for heat pumps - users.fs.cvut.cz

45/59

Noise protection

large flowrates at evaporator, big fan - source of noise

grass not refection surfaces

noise barriers

(walls, green fences)

protection by distance

antivibrating layers under HP

noise reducers for piping (water, air)


Recommended