SECTION 16200 EMERGENCY GENERATOR SET PART 1 - GENERAL 1.1 SECTION INCLUDES A. Packaged Engine Generator System B. Radiator C. Exhaust Silencer and Fittings D. Fuel System E. Control Tuû ñieän F. Battery and Battery Charger G. Automatic Transfer Switch 1.2 REFERENCES A. American Standards, codes and Regulations 1. ANSI/NEMA 250 - Enclosures for Electrical Equipment (1000 Volts Maximum) 2. ANSI/NEMA MG1 - Motors and Generator 3. ANSI/NFPA 70 - National Electric Code 4. ANSI/NFPA 99 - Health Care Facilities. PHAÀN 16200 MAÙY PHAÙT ÑIEÄN KHAÅN PHAÀN 1 - TOÅNG QUAÙT 1.1 PHAÀN NAØY GOÀM A. Heä thoáng maùy phaùt ñieän. B. Boä taûn nhieät C. Boä giaûm aâm thanh khí thaûi vaø phuï tuøng D. Heä thoáng nhieân lieäu. E. Baûng ñieàu khieån. F. Ñieän & bình xaïc ñieän. G. ATS. 1.2 THAM KHAÛO A. Tieâu chuaån Myõ, maõ vaø quy ñònh 1. ANSI/NEMA 250 – Tuû ñieän coù thieát bò ñieän (Ñieän aùp lôùn nhaát 1000) 2. ANSI/NEMA MG1 - Motor vaø maùy phaùt. 3. ANSI/NFPA 70 - Maõ ñieän quoác gia. 4. ANSI/NFPA 99 - Tieâu chuaån söùc khoeû. B. Tieâu chuaån Chaâu Aâu, maõ vaø quy ñònh 16200 - 1 EMERGENCY GENERATOR SET
Transcript
Page 1: 16200-F

SECTION 16200

EMERGENCY GENERATOR SET

PART 1 - GENERAL

1.1 SECTION INCLUDES

A. Packaged Engine Generator System

B. Radiator

C. Exhaust Silencer and Fittings

D. Fuel System

E. Control Tuû ñieän

F. Battery and Battery Charger

G. Automatic Transfer Switch

1.2 REFERENCES

A. American Standards, codes and Regulations

1. ANSI/NEMA 250 - Enclosures for Electrical Equipment (1000 Volts Maximum)

2. ANSI/NEMA MG1 - Motors and Generator

3. ANSI/NFPA 70 - National Electric Code

4. ANSI/NFPA 99 - Health Care Facilities.

B. European Standards, Codes, and Regulations

C. IEC34/1 International Electrotechnical Commission

D. TIS 11-2531 - Building Wires and Cables.

PHAÀN 16200

MAÙY PHAÙT ÑIEÄN KHAÅN

PHAÀN 1 - TOÅNG QUAÙT

1.1 PHAÀN NAØY GOÀM

A. Heä thoáng maùy phaùt ñieän.

B. Boä taûn nhieät

C. Boä giaûm aâm thanh khí thaûi vaø phuï tuøng

D. Heä thoáng nhieân lieäu.

E. Baûng ñieàu khieån.

F. Ñieän & bình xaïc ñieän.

G. ATS.

1.2 THAM KHAÛO

A. Tieâu chuaån Myõ, maõ vaø quy ñònh

1. ANSI/NEMA 250 – Tuû ñieän coù thieát bò ñieän (Ñieän aùp lôùn nhaát 1000)

2. ANSI/NEMA MG1 - Motor vaø maùy phaùt.

3. ANSI/NFPA 70 - Maõ ñieän quoác gia.

4. ANSI/NFPA 99 - Tieâu chuaån söùc khoeû.

B. Tieâu chuaån Chaâu Aâu, maõ vaø quy ñònh

C. IEC34/1 Vaän haønh ñieän quoác teá

D. Daây TIS 11-2531 - vaø caùp

E. Qui ñònh ñòa phöông, luaät, laép ñaët ñieàu chænh, thaåm tra vaät lieäu vaø kieåm tra

16200 - 1 EMERGENCY GENERATOR SET

Page 2: 16200-F

E. Local Ordinances, Rules, Regulations covering installation, material inspection and testing.

F. Emission value of diesel engine : in accordance with TA-Luft or EURI-II standard.

1.3 SYSTEM DESCRIPTION

A. Diesel generator system, incorporated with paralleling switchgear to provide source of emergency power.

B. System Capacity: as indicated at 0.8 power factor lagging, at sea level and ambient temperature up to 40o C, continuous or prime rating using engine mounted radiator.

C. Operation: In accordance with ANSI/NFPA99

1.4 SUBMITTALS

A. Submit product data indicating unit ratings, dimension and finished.

B. Submit factory test report which shall be performed on each generator set and control panel at manufacturer's factory.

C. Submit shop drawing showing acoustic-treatment of the generator room.

D. Submit shop drawing showing electrical diagrams including schematic and interconnection diagrams.

E. Submit statement of compliance. Any deviation from the basic requirement shall be considered only when it renders more superiority in performance.

F. Giaù trò toûa nhieät cuûa ñoäng cô diesen: theo TA-Luft hay tieâu chuaån EURI-II.

1.3 MOÂ TAÛ HEÄ THOÁNG

A Heä thoáng maùy phaùt diesel, keát hôïp vôùi cô caáu chuyeån maïch song song, ñeå cung caáp nguoàn naêng löôïng khan.

B. Coâng suaát heä thoáng: heä soá coâng suaát = 0.8 khi khoâng daãn nhieät so vôùi möïc nöôùc bieån vaø nhieät ñoä xung quanh 40 ñoä C, coâng suaát lieân tuïc vaø coâng suaát ban ñaàu duøng boä taûn nhieät coù ñoäng cô.

C. Hoïat ñoäng: theo tieâu chuaån ANSI/NFPA99

1.4 CAÙC COÂNG VIEÄC ÑEÄ TRÌNH

A. Ñöa döõ lieäu saûn phaåm veà coâng suaát, kích thöôùc vaø vaät hoøan thieän.

B. Ñöa baùo caùo kieåm tra nhaø maùy cuûa moãi maùy phaùt vaø tuû ñieän ñieàu khieån taïi nhaø maùy saûn xuaát

C. Ñöa ra baûn veõ cheá taïo xöû lyù aâm thanh cuûa phoøng maùy phaùt ñieän.

D. Ñöa ra sô ñoà ñieän vaø sô ñoà keát noái ñieän goàm sô ñoà cô sôû vaø sô ñoà keát noái trong

E. Ñöa ra thoûa thuaän xem xeùt. Baát kyø ñoä leäch naøo töø caùc yeâu caàu cô baûn khi coù hoaït ñoäng vôùi hieäu suaát toát hôn

F. Ñöa ra höôùng daãn laép ñaët cuûa nhaø saûn xuaát vaø chæ caùch laép ñaët cuûa maùy phaùt ñieän vaø phuï kieän

16200 - 2 EMERGENCY GENERATOR SET

Page 3: 16200-F

F. Submit manufacturer's installation instructions and shop drawing showing the installation method of the generator set and accessories.

1.5 PROJECT RECORD DOCUMENT

A. Submit record of supply and installation in Thailand of the generator set with same size and larger.

1.6 OPERATION AND MAINTENANCE DATA

A. Submit operation and maintenance data include instructions for normal operation, routine maintenance requirements , service manuals for engine and day tank, oil sampling and analysis for engine wear, and emergency maintenance procedures.

1.7 QUALIFICATIONS

A. Manufacturer: Company specializing in packaged engine generator system with minimum three years documented experience.

B. Supplier: Authorized distributor of generator in Thailand shall be responsible for providing all service facilities and spare parts.

1.8DELIVERY, STORAGE, AND HANDLING

A. Delivery generator set and accessories to site and the materials shall be accepted on site in crates and verified damage.

B. Store and protect products from dirt and moisture by securely wrapping in heavy

1.5 TAØI LIEÄU GHI NHAÄN TAÏI COÂNG TRÖÔØNG

A. Ñöa ra baûn löu cuûa nhaø cung caáp vaø laép ñaët thieát bò maùy phaùt cuøng kích côõ vaø chieàu roäng

1.6 TAØI LIEÄU BAÛO TRÌ VAØ HOAÏT ÑOÄNG

A. Ñöa ra hoaït ñoäng vaø baûo trì goàm höôùng daãn cho hoaït ñoäng thoâng thöôøng, yeâu caàu baûo trì giai ñoaïn, dòch vuï ñieàu khieån baèng tay cho ñoäng cô vaø ngaøy chöùa nguyeân lieäu, maãu daàu vaø baûng phaân tích ñoäng cô hao moøn, vaø quy trình baûo trì khaån.

1.7 CHAÁT LÖÔÏNG

A. Nhaø saûn xuaát: heä thoáng maùy phaùt coù ít nhaát 3 naêm kinh nghieäm

B. Nhaø cung caáp: caùc nhaø phaân phoái coù thaåm quyeàn cuûa maùy phaùt ñieän seõ coù traùch nhieäm cung caáp taát caû caùc dòch vuï thuaän tieän vaø caùc phaàn döï phoøng thay theá

1.8 GIAO HAØNG, CHÖÙA HAØNG VAØ VAÄN HAØNH

A. Phaân phoái maùy phaùt ñieän vaø phuï kieän ñeán coâng tröôøng vaø chaáp nhaän vaät lieäu bò traày vaø xem xeùt hö hoûng

B. Chöùa haøng trong kho vaø baûo veä saûn phaåm khoâng bò dô, aåm baèng caùch quaán plastic daøy

1.9 BAÛO HAØNH

A. Cung caáp baûo haønh theo caùc ñieàu khoaûn hieän haønh cuûa hoà sô thaàu.

16200 - 3 EMERGENCY GENERATOR SET

Page 4: 16200-F

plastic.

1.9 WARRANTY

A. Provide warranty according to the period stated in the Contract Documents.

1.10 MAINTENANCE SERVICE

A. Furnish service and maintenance of packaged engine generator system from Date of Substantial Completion for a warranty period mention.

B. Submit a complete list of spare part, which includes part number, drawing number, current unit prices and source of supply.

C. Submit a list of the genuine spare parts recommended by the manufacturer to be replaced after 3 years of services.

1.11 EXTRA MATERIALS

A. Furnish one set of tools required for preventive maintenance of the engine generator system. Package tools in adequately sized metal tool box.

B. Provide two additional sets of each fuel oil, and air filter element required for the engine generator system.

PART 2 - PRODUCT

2.1 ACCEPTABLE MANUFACTURERS

A. CATERPILLAR : USA

B. MTU : GERMANYC. FG WILSON : ENGLANDD. PERKINS/AVK:

GERMANYE. Mitsubishi :

JAPANF. WAISILA : FRANCEG. Contractor shall submit for

approval

1.10 DÒCH VUÏ BAÛO TRÌ

A. Trang bò dòch vuï vaø baûo trì heä thoáng ñoäng cô maùy phaùt ñieän töø ngaøy hoøan thaønh cho giai ñoïan baûo haønh.

B. Ñöa ra danh muïc hoaøn thieän caùc thieát bò laép raùp, soá baûn veõ, giaù hieän haønh cho töøng vaät lieäu vaø nguoàn goác cung caáp.

C. Nhaø saûn xuaát ñöa ra danh muïc cuûa thieát bò laép raùp ñöôïc ñeà nghò thay theá sau 3 naêm hoaït ñoäng.

1.11 VAÄT LIEÄU THEÂM VAØO

A. Trang bò 1 boä duïng cuï cho baûo trì heä thoáng maùy phaùt ñieän ñoäng cô. Ñoùng goùi duïng cuï theo kích thöôùc ñuùng.

B. Cung caáp theâm 2 boä: 1 boä daàu, vaø boä loïc khoâng khí cho heä thoáng maùy phaùt ñieän

PHAÀN 2 – SAÛN PHAÅM

2.1 NHAØ SAÛN XUAÁT CHAÁP THUAÄN

A. CATERPILLAR : MYÕB. MTU : ÑÖÙCC. FG WILSON : ANHD. PERKINS/AVK : ÑÖÙCE. Mitsubishi : NHAÄTF. WAISILA : PHAÙPG. Nhaø thaàu seõ ñeä trình xin pheâ duyeät

Ghi chuù: maùy phaùt ñieän ñöôïc saûn xuaát hoaøn thieän bôûi caùc nöôùc chính haõng, khoâng ñöôïc chaáp nhaän laép raùp khoâng roõ nguoàn goác.

2.2 BOÄ MAÙY PHAÙT ÑIEÄN ÑOÄNG CÔ

16200 - 4 EMERGENCY GENERATOR SET

Page 5: 16200-F

NOTE The generator set must be manufactured in completed unit from the original countries, the assembly with no certification from original factory will not acceptable.

2.2 ENGINE GENERATOR SET

A. General : Each generator set shall consist of one engine including one radiator, one exciter and one alternator mounted on a steel base.The voltage regulator, switchgear, and control system, accessories shall be mounted on a control panel. The generator set shall be factory assembled and aligned accurately on the steel base. Which shall be strong and rigid enough to ensure permanent alignment of all rotating units and prevent vibrationbuild up and shall permit skidding in any direction during installation.

B. Rating : Rating shall be as follows:

1. Number of sets required: AS INDICATED

2. Out put not less than: AS INDICATED and shall be prime rating

3. Power factor, lagging : 0.8

4. Speed :1500 rpm.

5. Frequency : 50 HZ.

6. Voltage : 80/220 V. or same as utility power

7.

8. Cylinders Type: 12-16 cylinder with turbocharger air to air change cooler

9. Type of excitation: Brushless

10. Load acceptance: Capable for

A. Toång quaùt: moãi maùy phaùt ñieän goàm 1 ñoäng cô, 1 boä taûn nhieät, 1 boä kích töø vaø 1 maùy phaùt ñieän xoay chieàu ñoäng khung treân ñeá theùp. Maùy ñieàu chænh ñieän aùp, coâng taéc, vaø heä thoáng ñieàu khieån, phuï kieän seõ ñöôïc ñoùng khung treân tuû ñieän ñieàu khieån. Maùy phaùt ñieän ñöôïc laép raùp vaø thaúng haøng treân theùp neàn. Maùy phaùt ñieän ñuû raén ñeå baûo ñaûm tính coá ñònh khoâng xoay vaø ngaên taïo rung vaø cho pheùp tröôït ôû baát kyø höôùng naøo khi laép raùp.

B. Coâng suaát: Coâng suaát theo caùc yeâu caàu sau:

1. Yeâu caàu soá cuûa : nhö ñeà caäp

2. Ngoõ ra khoâng nhoû hôn: nhö ñeà caäp

3. Heä soá coâng suaát khoâng daãn nhieät: 0.8

4. Toác ñoä : 1500 rpm.

5. Taàn soá : 50 HZ.

6. Ñieän aùp : 380/220 V. hay ñieän töông töï

7. Pha : 3 pha, 4 daây

8. Loïai xy lanh : 12-16 xy lanh coù boä xaïc turbo boä laøm nguoäi thay ñoåi khí ñeán khí

9. Loïai kích töø : Brushless

10. Chaáp nhaän taûi trong : AÙp duïng caùc öùng duïng khaùc nhau döïa treân pheâ duyeät 75% taûi trong treân böôùc ñôn töø ñieàu kieän khôûi ñoäng ñaàu tieân. Ñieän aùp vaøo 10%

16200 - 5 EMERGENCY GENERATOR SET

Page 6: 16200-F

various applications on the basis of 75% load acceptance in a single step from an initial start up condition. Voltage dip < 10%

11.

a. AmbienTb. Relative

humidity 90%c. Altitude

C. Voltage Regulation : With the engine governing within limit specified above and incorporated with electronic control circuit in automatic voltage regulator, the voltage regulation, at any balanced steady load between no load and full loadat any load power factor from 0.8 to 1 lagging, at any normal service condition of temperature and inclusive of speed variation not exceed 4 1/2 % shall not exceed the limit +/- 0.5% of rated voltage. The instantaneous voltage variation shall be less than 25% of rated voltage when 3phase full load is applied to or removed from the generator set. Recovery to stable operation shall occur within 2 seconds. Other performance deviated from above specified values shall be accepted for consideration only when it renders to the best benefit to the Owner.

D. Frequency Regulation : As defined by engine governor performance.

E. Total Harmonic Content : The line voltage waveform shall have total harmonic content not exceed 3 % of the fundamental under all operating condition.

F. Motor starting an overload capacity equivalent to between 160% and 300% of full load.

11. Ñieàu kieän moâi tröôøng:a. Nhieät ñoä xung quanh 40°cb. Ñoä aåm lieân quan 90%c. Cao ñoä möïc nöôùc bieån

C. Söï ñieàu chænh ñieän aùp: ñoái vôùi ñoäng cô ôû giôùi haïn thoâng soá kyõ thuaät teân vaø saùt nhaäp vaøo maïch ñieàu khieån ñieän taïi caùc maùy ñieàu chænh ñieän aùp töï ñoäng, ñieàu chænh ñieän aùp, taïi baát kyø taûi trong caân baèng naøo giöõa khoâng taûi & taûi naëng, ôû baát kyø heä soá töø 0.8 ñeán 1 chaát khoâng daãn ñieän, taïi baát kyø ñieàu kieän dòch vuï bình thöôøng naøo cuûa nhieät ñoä vaø toác ñoä khaùc khoâng vöôït quaù 4 ½ % khoâng vöôït quaù giôùi haïn +/- 0.5% cuûa ñieän aùp. Söï bieán thieân ñieän aùp töùc thôøi seõ nhoû hôn 25% tæ leä ñieän aùp khi taûi ñaày pha ñöôïc aùp duïng hay di chuyeån tôùi boä maùy phaùt chieám 2 giaây . Hoaït ñoäng khaùc bò leäch töø treân giaù trò chæ ñònh ñöôïc cho xem xeùt chæ khi ñem laïi lôïi ích cho chuû ñaàu tö.

D. Ñieàu chænh taàn soá: theo tính chaát hoaït ñoäng maùy ñieàu toác.

E. Löôïng ñieàu hoøa tuyeät ñoái : Soùng ñieän aùp coù löôïng ñieàu hoøa tuyeät ñoái khoâng vöôït quaù 3% giaù trò cô baûn theo taát caû ñieàu kieän hoïat ñoäng.

F. Ñoäng cô khôûi ñoäng 1 coâng suaát quaù taûi töông ñöông giöõa 160% vaø 300% cuûa taûi ñaày.

G. Hoaït ñoäng maùy phaùt ñieän.

1. Maùy phaùt ñieän hoaøn thieän seõ ñaùp öùng hay vöôït quaù tieâu chuaån hoaït ñoäng sau:Ñieàu chænh ñieän aùp + 0.5% Ñieän aùp ñònh möùc.

Ñoä beàn ñieän aùp + 0.5% coâng suaát ñieän

16200 - 6 EMERGENCY GENERATOR SET

Page 7: 16200-F

G. Generator set performance

1. The completed generator set shall meet or exceed the following performance criteria:Voltage regulation shall be + 0.5 percent rated voltage.

Steady state voltage stability + 0.5 percent rated voltage.

Maximum voltage dip with step application of rated continuous engine generator rating at 0.8 power factor not to exceed 20 percent.

Voltage recovery time with step application of rated continuous engine generator rating at 0.8 power factor not to exceed 4 seconds.

Balanced telephone interference factor (TIF) shall not exceed 50.

Frequency regulation from no load to full load adjustable from isochronous to 5 percent.

Steady state frequency stability shall be + 0.25 HZ

Generator set shall be capable of start-up and accepting rated load within 10 seconds.

2.3 ENGINE

A. Type : Engine shall be a general purpose continuous service diesel for stationary applicationsThe engine shall be the standard product of the manufacturer, a current production model complete with all auxiliaries normally furnished, and shall provide sufficient power to drive the coupled alternator. The engine shall be compression ignition type, watercooled turbo - charged with or without intercooler, 4 stroke cycle, direct injection high pressure Common-Rail injection system, multi cylinder, V Congeal 90o type with removable cylinder liner, designed for

aùp.

Ñieän aùp vaøo lôùn nhaát coù öùng duïng böôùc cuûa coâng suaát maùy phaùt ñieän ñoäng cô lieân tuïc taïi heä soá ñieän 0.8 khoâng vöôït quaù 20%.

Thôøi gian phuïc hoài ñieän aùp coù öùng duïng böôùc cuûa coâng suaát maùy phaùt ñieän ñoäng cô lieân tuïc taïi heä soá ñieän 0.8 khoâng vöôït quaù 4 giaây.

Heä giao thoa ñieän thoaïi caân baèng khoâng vöôït quaù 50.

Taàn soá töø khoâng taûi vaø ñaày taûi ñöôïc ñieàu chænh töø thôøi gian baèng nhau ñeán 5%

Taàn soá oån ñònh beân trong khoûang + 0.25 HZ

Maùy phaùt ñieän coù khaû naêng khôûi ñoäng vaø nhaän taûi troïng ñònh möùc trong 10 giaây.

2.3 ÑOÄNG CÔ

A. Loaïi: laø moät ñoäng cô chaïy baèng diesen lieân tuïc ñeå ñaùp öùng coá ñònh. Ñoäng cô laø saûn phaåm tieâu chuaån cuûa nhaø saûn xuaát, laø kieåu saûn phaåm hieän haønh hoaøn thieän bình thöôøng vaø cung caáp ñieän ñaày ñuû ñeå ñeå phaùt ra doøng ñieän xoay chieàu. Ñoäng cô laø loaïi ñaùnh löûa neùn, naïp ñieän baèng tuabin coù hay khoâng coù thuøng laøm laïnh beân trong, chu trình 4 thì, heä thoáng phun chung – Heä pittoâng, xylanh ña keânh, loaïi congeal V 900 coù lôùp loùt xylanh thaùo rôøi, ñöôïc thieát keá cho coâng trình coâng nghieäp.

B. Maùy ñieàu toác: toác ñoä ñoäng cô ñöôïc ñieàu khieån baèng maùy ñieàu toác ñieän ñeå duy trì toác ñoä taïi thôøi gian baèng nhau roõ

16200 - 7 EMERGENCY GENERATOR SET

Page 8: 16200-F

industrial use.

B. Governor : The engine speed shall be governed by an electronic governor to maintain governed speed at precise isochronous control for 1500 rpm operation. The governor shall provide adjustable speed setting 10 % and permit automatic parallel operation and load sharing with other generator set. The frequency at any constant load including no load shall remain within a steady state band width of +/- 0.25 % of rated frequency . Application and removal of rated load shall allow in transientfrequency change not exceeding 10 % and recover to 3 % change within 10 seconds. Other performance deviated from above specified values shall be accepted for consideration only when it renders to the best benefit to the Owner.

C. Turbocharger: Shall be of the turbine type driven by exhaust gas from the engine cylinders and direct -connected to a blower that supplies air to the engine intake manifolds. The turbocharger shall be pressure - lubricated. All necessary supports and connections shall be provided.

D. Intercoolers : For cooling the intake air from turbochargers shall be of the tubular heat exchanger type. All necessary intercoolingequipment including valves, controls and integral piping shall be provided.

E. Vibration Limitation : The engine generator set shall be equipped with vibration absorber to be free of damaging flexural vibrations and dangerous torsional critical speed.

F. Fuel System : Shall consist of a storage

raøng ñoái vôùi hoaït ñoäng 1500 rpm. Maùy ñieàu toác cung caáp laép ñaët toác ñoä ñieàu chænh 10% vaø cho pheùp hoaït ñoäng song song töï ñoäng vaø phaân chia taûi cho maùy phaùt ñieän khaùc. Taàn soá taïi baát kyø taûi troïng haèng soá naøo goàm khoâng taûi giöõ nguyeân chieàu roäng daûi trong tình traïng ñuùng +/- 0.25% taàn soá ñònh möùc. ÖÙng duïng vaø di chuyeån taûi ñònh möùc cho pheùp hoaït ñoäng taïm thôøi bò leäch töø caùc giaù trò chæ ñònh ñöôïc ñoàng yù cho xem xeùt khi noù ñöa ra lôïi ích toát nhaát cho chuû ñaàu tö.

C. Boä naïp ñieän: laø loïai tubin ñöôïc truyeàn baèng khí thaûi töø xy lanh ñoäng cô vaø keát noái tröïc tieáp ñeán quaït gioù cung caáp khí ñeán ñöôøng oáng phaân phoái cho ñoäng cô. Boä naïp ñieän ñöôïc boâi trôn aùp suaát.

D. Laøm laïnh: Ñoái vôùi vieäc laøm laïnh khí laáy vaøo töø boä naïp baèng tuabin laø loaïi maùy ñoåi nhieät coù hình oáng. Cung caáp taát caû thieát bò thuøng laøm laïnh caàn thieát goàm van, ñieàu khieån vaø ñöôøng oáng beân trong.

E. Giôùi haïn ñoä rung: maùy phaùt ñieän ñoäng cô ñöôïc trang bò thieát bò giaûm xoùc ñeå traùnh hö hoûng ñoä rung uoán khuùc vaø toác ñoä tôùi haïn xoaén nguy hieåm.

F. Heä thoáng naêng löôïng: goàm maùy bôm nhieät lieäu, heä thoáng loïc ñoâi, thuøng oâ vaø maùy bôm nhieän lieâu ñoäng cô.

1. Boàn chöùa nhieân lieäu: coù dung tích 10.000 lit vaø vò trí chính xaùc treân baûn veõ. Nhoû nhaát cuûa thuøng: goàm moät oáng

16200 - 8 EMERGENCY GENERATOR SET

Page 9: 16200-F

tank fuel transfer pump, dual filtering system, day tank and engine fuel pump.

1. Fuel Storage Tank : Shall have the capacity of 7,000 Litre and location shown on the Drawings. As a minimum, the tank shall include a fill pipe, vent pipe, fuel gauge and an overflow return line from the day tank. Tank protective coating shall be provided.

2. Fillpoint calimate : Shall be wall mounted type consist of 2- BSP valve, contents gavge, will alarm and shall be installed where the oil truck accessible.

3. Fuel Transfer Pump : An electric, motor driven, automatic transfer pump shall be utilized to pump fuel from the storage tank to day tank. The pump shall be controlled by high and low level switches in the day tank., the pump shall be explosion proof.

4. Fuel Filtering System : Shall consist of a strainer, located between the storage tank and fuel transfer pump and a duplex filter, located between the engine fuel pump and the engine. The filtering system shall be easily accessible for quick and easy replacement of the filter element and cleaning of the strainer.

5. Day Tank : Shall be mounted on non combustible supports near the engine to provide an immediate fuel supply to the engine fuel pump and shall be situated so that the fuel level in the day tank above the engine injection pump. A flexible suction line to the engine, an excess fuel return line from the engine to the day tank, a vent, a drain pipe, an overflow return line to the bulk m storage tank and high-low transfer pump shall be completely provided. Capacity is to supply engine at rated power not

laøm ñaày, oáng thoâng hôi, maùy ño nhieân lieâu vaø ñöôøng oáng ñeå nhieân lieäu traøn trôû laïi boàn chöùa. Cung caáp lôùp phuû baûo veä boàn

2. Fillpoint calimate : laø loïai gaén vaøo töôøng goàm van 2 – BSP, van chöùa, seõ baùo ñoäng vaø laép vaøo vò trí maø xe chôû daàu vaøo ñöôïc.

3. Maùy bôm truyeàn nhieân lieäu: maùy bôm ñieän, maùy bôm truyeàn ñoäng cô, maùy bôm truyeàn töï ñoäng ñöôïc duøng ñeå bôm nhieân lieäu töø beå chöùa ñeán boàn chöùa nguyeân lieäu. Maùy bôm ñöôïc ñieàu khieån baèng coâng taéc möùc thaáp vaø cao trong thuøng ngaøy, maùy bôm choáng noå.

4. Heä thoáng loïc nhieân lieäu: goàm 1 caùi loïc, ñònh vò giöõa beå chöùa vaø maùy bôm truyeàn nhieân lieäu vaø boä loïc keùp, ñònh vò giöõa maùy bôm nhieân lieäu ñoäng cô vaø ñoäng cô. Heä thoáng loïc vaøo deã daøng cho vieäc thay theá nhanh vaø deã daøng cuûa pin loïc vaø veä sinh boä loïc.

5. Boàn chöùa: ñöôïc gaén vaøo vaät khoù chaùy gaàn ñoäng cô ñeå cung caáp nhieân lieäu ngay laäp töùc cung caáp cho maùy bôm nhieân lieäu ñoäng cô vaø ôû tình traïng möùc nhieân lieäu trong boàn chöùa treân maùy bôm phun ñoäng cô. Ñöôøng huùt deûo ñeán ñoäng cô, moät ñöôøng trôû laïi nguyeân lieäu vöôït möùc töø ñoäng cô ñeán boàn chöùa, 1 loã thoâng, 1 ñöôøng oáng thoaùt, 1 ñöôøng trôû laïi thöøa ñeán beå chöùa haøng vaø maùy bôm truyeàn thaáp -- cao ñöôïc cung caáp hoaøn toaøn. Cung caáp ñoäng cô coù coâng suaát taïi ñieän aùp ñònh möùc khoâng nhoû hôn 2 tieáng.

6. Maùy bôm nhieân lieäu ñoäng cô: laø söï dòch chuyeån coù tích ñieän, maùy bôm

16200 - 9 EMERGENCY GENERATOR SET

Page 10: 16200-F

less than 2 hours.

6. Engine Fuel Pump : Shall be a positive displacement, engine driven pump capable of supplying an adequate quantity of fuel to the engine under all operational conditions. Solenoid shut-off valve in fuel discharge line shall be interlocked emergency shutdown circuitry., the pump shall be explosion proof.

7. Leak Detection System : Storage tank shall be monitored by leak detection system which indicates by audible and visual alarms the occurrence of a leak in any part of either tank shell.

8. Level Monitoring: Storage tank and day tank shall be monitor by level monitoring system and interface to SCADA system.

G. Lubrication : The engine shall be provided with a complete lubricating oil system, pressurized by an engine-driven oil pump. A relief valve for oil pressure regulation and a gauge or dip-stick for oil level indication shall be furnished.

1. Filtering : Full flow oil filters with replaceable element including a spring loaded bypass valve to ensure oil circulation, if filter are clogged, conveniently located for servicing, shall be provided.

2. Oil Cooling : An oil cooler, if necessary shall be incorporated within the lubricating system.

H. Engine Cooling System : Shall be water cooled, pressurized system having sufficient capacity for cooling the engine during engine operation at full load at ambient temperature 40o C. 1. Radiator Cooling : An engine - mounted radiator or separated radiator with an engine driven pusher fan or electrical

truyeàn ñoäng cô coù khaû naêng cung caáp soá löôïng ñaày ñuû nhieân lieäu ñeán ñoäng cô theo taát caû ñieàu kieän hoaït ñoäng. Van khoùa lieân ñoäng trong ñöôøng naïp nhieân lieäu ñöôïc khoùa trong voøng ngöng taïm thôøi maùy bôm laø choáng noå

7. Heä thoáng doø tìm roø ræ: beå chöùa ñöôïc giaùm saùt baèng heä thoáng doø tìm roø ræ chæ ra baùo chaùy baèng tieáng vaø thaáy ñöôïc söï coá roø ræ trong baát kyø phaàn naøo cuûa voû thuøng.

8. Ñònh löôïng möùc: beå chöùa vaø boàn chöùa ñöôïc giaùm saùt baèng heä thoáng kieåm tra ñònh löôïng möùc vaø maët phaân caùch ñeán heä thoáng SCADA

G. Boâi trôn: ñoäng cô ñöôïc cung caáp coù heä thoáng daàu boâi trôn, ñöôïc ñieàu aùp baèng maùy bôm daàu truyeàn ñoäng cô. Moät van xaû cho ñieàu chænh aùp suaát daàu vaø maùy ño hay que ño möïc nöôùc cho chæ daãn möïc daàu ñöôïc trang bò

1. Boä loïc: boä loïc daàu vôùi thaønh phaàn coù theå thay theá ñöôïc goàm moät nhaùnh taûi ñaûm baûo söï löu thoâng daàu, neáu boä loïc bò taéc, ñònh vò thuaän tieän cho phuïc vuï ñöôïc cung caáp.

2. Laøm nguoäi daàu: thuøng laøm nguoäi daàu, neáu caàn thieát thì phoái hôïp vôùi heä thoáng boâi trôn

H. Heä thoáng laøm nguoäi ñoäng cô: laøm nguoäi baèng nöôùc, heä thoáng ñieàu aùp coù coâng suaát ñaày ñuû cho vieäc laøm nguoäi ñoäng cô trong suoát hoaït ñoäng ñoäng cô taïi taûi ñaày taïi nhieät ñoä xung quanh 400C. 1. Laøm nguoäi boä taûn nhieät: ñoäng cô laép boä taûn nhieät hay boä taûn nhieät rieâng bieät coù quaït maùy truyeàn ñoäng cô hay

16200 - 10 EMERGENCY GENERATOR SET

Page 11: 16200-F

motor fan capable of maintaining a 15o F temperature differential between inlet and outlet water. The driving belt shall be enclosed in fan Cowling and hand protection guard.

2. Raw-Water Circulating Pump : Shall be an engine driven centrifugal pump with an automatic controlled by-pass valve to maintain the engine at recommended temperature level and to assist rapid heat up after starting maneuver.

3. Provide remoted radiator if ventilation can’t sufficient for cooling. (provide if indicated)

I. Air - Intake System.

1. Air Filter : The engine air - intake opening shall be equipped with an effective, easily cleaned air filter which is capable of removing all material down to 100 micron. The filter unit shall be easily removable to allow replacement of filter element.

2. Silencer : For suppression of high frequency sounds which as capable of reducing the sound level at the air intake to a point that is acceptable for residential use.

J. Exhaust System : Shall be complete with separate system for each engine and shall include a flexible section, a muffler and exhaust piping graded away from the engine to the outside.

1. Flexible exhaust section : Shall consist of convoluted seamless tube without joints or packing and be capable for absorbing vibration from the engine and thermal expansion and contraction of exhaust piping.

quaït ñoäng cô ñieän coù khaû naêng duy trì ñoä leäch nhieät ñoä 150F giöõa ngoõ vaøo vaø ngoõ ra nöôùc. Loaïi driving ñöôïc ñính keøm vaøo traïng thaùi baûo veä baèng tay vaø naép ñaäy quaït.

2. Maùy bôm tuaàn hoaøn nöôùc thoâ: laø maùy bôm ly taâm truyeàn ñoäng cô coù van reõ ñieàu khieån töï ñoäng ñeå duy trì ñoäng cô taïi möùc nhieät ñoä ñeà nghò vaø ñeå hoã trôï nhieät nhanh leân sau khi khôûi ñoäng maneuver

3. Cung caáp boä taûn nhieät ñieàu khieån neáu söï thoâng hôi khoâng ñuû cho quaù trình laøm nguoäi ( cung caáp neáu ñöôïc chæ ñònh)

I. Heä thoáng laáy khoâng khí ngoaøi.

1. Boä loïc khí: loã hôû laáy khoâng khí ngoaøi cuûa ñoäng cô ñöôïc trang bò baèng boä loïc khí coù hieäu quaû vaø saïch seõ cho pheùp dôøi taát caû vaät lieäu xuoáng coøn 100 micromet. Ñi qua boä loïc deã daøng, deã thaùo rôøi cho pheùp thay theá caùc thaønh phaàn.

2. Boä giaûm thanh: ñôn vò neùn aâm thanh taàn soá cao coù khaû naêng giaûm möùc ñoä aâm thanh taïi ñaàu laáy khoâng khí ngoaøi ñeå tieän cho vieäc söû duïng cho daân cö.

J. Heä thoáng thoaùt khí: ñöôïc hoaøn thaønh baèng heä thoáng rieâng reõ cho moãi ñoäng cô vaø goàm moät phaàn meàm, moät ñöôøng oáng thoaùt khí vaø giaûm thanh ñöôïc choïn loïc töø ñoäng cô ñeán beân ngoaøi.

1. Boä phaän huùt khí meàm: goàm ñöôøng noái xoaén coù moái noái ngoaøi hay mieáng ñeäm vaø coù khaû naêng huùt rung töø ñoäng cô vaø giaõn nôõ nhieät vaø co ruùt oáng xaû.

16200 - 11 EMERGENCY GENERATOR SET

Page 12: 16200-F

2. Exhaust muffler : Shall be of the chamber typeconstructed of welded steel. Each muffler shall be provided with eyebolts, lugs, flanges, or other items necessary for mounting. Pressure drop through the muffler shall not exceed the recommendations of the engine manufacturer. Outside mufflers shall be zinc coated.

3. Exhaust Silencer Critical Type : Shall reduce the exhaust sound spectrum between low frequency band (20-75 HZ.) and high frequency band (4,800-10 KHZ) to below 37-40 dB, used full engine load.

4. Exhaust System Installation : The exhaust piping shall be securely supported, prevented from rain entering the outlet pipe and shall incorporate a condenser trap and drain valve in exhaust piping. All part of the exhaust system shall be insulated with sufficient non-flammable insulation covering to prevent heat dissipation and burns from accidental contact.

5.Maximum Allowable silence pressure drop 2 Kpa

K. Starting System : The engine shall be equipped with an electric starting system which is arranged for fully automatic starting upon the failure of any phase of the main power supply.

1.Battery : The storage battery shall be a lead acid, sealed-in plastic for maintenance free type complete with battery rack and intercell connectors. The battery shall be of sufficient capacity, at ambient temperature of 40o C. to provide at least 4 cranking periods of 30 seconds each, with 2-minute rest between cranks.

2. Battery Charger : A current-limiting battery charger shall be furnished to automatically recharge the batteries. The charger shall be capable of a high charge

2. Boä giaûm aâm thoaùt khí: laø loaïi buoàng, ñöôïc xaây döïng töø theùp haøn. Moãi boä giaûm thanh cung caáp ñinh khuy, giaù, gôø noåi hay caùc haïng muïc khaùc caàn thieát cho vieäc laép khung. Ñoä suït aùp qua boä giaûm thanh thoâng qua giôùi thieäu cuûa nhaø saûn xuaát ñoäng cô. Boä giaûm thanh ngoaøi ñöôïc phuû lôùp keõm.

3. Loaïi giôùi haïn giaûm thanh thoaùt khí: giaûm aâm thanh thoaùt khí giöõa daûi taàn soá thaáp (20-75 HZ) vaø daûi taàn soá cao (4.800-10 HZ) ñeán döôùi 37-40 dB, ñöôïc söû duïng cho taûi ñoäng cô ñaày.

4. Laép ñaët heä thoáng khí: oáng thoaùt khi ñöôïc hoã trôï an toaøn, ngaên nöôùc möa vaøo oáng ñaàu ra vaø phoái hôïp nuùt nöôùc ngöng vaø van thoaùt nöôùc trong oáng thoaùt khí. Taát caû phaàn heä thoáng thoaùt nöôùc ñöôïc caùch ly vôùi lôùp phuû choáng chaùy thích hôïp ñeå ngaên tieâu nhieät vaø ñoát chaùy töø tieáp xuùc ngaãu nhieân.

5. Ñoä suït aùp suaát lôùn nhaát cho pheùp 2 Kpa

K. Heä thoáng khôûi ñoäng: ñoäng cô ñöôïc trang bò moät heä thoáng khôûi ñoäng ñieän ñöôïc saép xeáp cho vieäc khôûi ñoäng töï ñoäng treân vieäc khoâng thöïc hieän ñöôïc baát kyø pha cuûa nguoàn cung caáp ñieän chính naøo.

1. AÉc qui: aéc qui laø axit chì, ñöôïc traùm baèng nhöïa cho vieäc baûo trì mieãn phí loaïi giaù ñôõ cuûa aéc qui vaø boä noái. AÉc qui coù coâng suaát ñaày ñuû, taïi nhieät ñoä xung quanh 400C ñeå cung caáp ít nhaát 4 chu kyø quay tay trong moãi 30 giaây, coù 2 phuùt nghó giöõa moãi kyø quay tay.

2. Boä naïp aéc qui: boä naïp aéc qui giôùi haïn doøng ñieän ñöôïc cung caáp ñeå naïp töï

16200 - 12 EMERGENCY GENERATOR SET

Page 13: 16200-F

rate for recharging fully depleted batteries within 8 hours, and a low charge rate for maintaining the batteries in prime starting condition. An ammeter shall be provided to indicate charging rate.

3. Exerciser : An automatic plant exerciser timer shall be provided to permit periodic operation of the standby generator set.

L. Piping and Fittings : Pipe anchors, pipesleeves, Plates, flashing and flexible pipe connector shall be provided for pipe installation.

M. Safety System:

1. Shutdown controls : The engine shall equipped with automatic safety controls, switches and circuitry which shutdown the engine and open the generator circuit breaker immediately, in the event of low lubricating oil pressure, high jacket - water temperature, engine overspeed and engine underspeed.

2. Alarm System : The safety systemincorporate visual-audio alarm signals that become operational before engine shutdown and corresponding device activates.

3. Time Delay Device : Shall be installed in automatic cranking tuû ñieän for automatic start stop operation of generator set. The time delay relay shall by-pass the low oil-pressure shutdown switch during cranking and return oilpressure switch to the circuit after engine starts.

N. Flywheel : Shall be statically and dynamically balanced and capable of being rotated at 125 percent of rated speed without damage.

O. Engine Instrumentation : The engine

ñoäng vaøo aéc qui. Boä naïp coù khaû naêng naïp vôùi toác ñoä cao cho vieäc naïp laïi ñaày ñuû aéc qui ñaõ xaûy ra trong voøng 8 tieáng vaø tyû leä naïp thaáp cho vieäc baûo trì aéc qui trong ñieàu kieän khôûi ñoäng ñaàu tieân. Ampe keá seõ hieån thò doøng ñieän ñònh möùc naïp vaøo.

3. Söû duïng: thieát bò baám giôø exerciser töï ñoäng ñöôïc cung caáp ñeå maùy phaùt ñieän döï phoøng hoaït ñoäng ñònh kyø

L. OÁng vaø phuï tuøng: neo oáng, oáng ngoaøi, taám, boä noái oáng meàm vaø choáng thaám ñöôïc cung caáp cho vieäc laép ñaët oáng.

M. Heä thoáng an toaøn:

1. Ñieàu khieån ngöng taïm thôøi: ñoäng cô ñöôïc trang bò coù ñieàu khieån an toaøn töï ñoäng, coâng taéc vaø maïch ñieän taét taïm thôøi ñoäng cô vaø môû CB maùy phaùt ñieän ngay laäp töùc trong tröôøng hôïp aùp suaát daàu boâi trôn thaáp, nhieät ñoä nöôùc neùn cao, ñoäng cô quaù toác ñoä vaø ñoäng cô döôùi toác ñoä.

2. Heä thoáng baùo ñoäng: heä thoáng an toaøn keát hôïp tín hieäu baùo ñoäng thaáy vaø nghe ñöôïc seõ hoaït ñoäng tröôùc khi ñoäng cô taïm ngöng vaø töông öùng vôùi hoaït ñoäng thieát bò.

3. Thieát bò thôøi gian treãø: ñöôïc laép treân tuû ñieän chu kyø quay tay töï ñoäng ñoái vôùi hoaït ñoäng töï ñoäng cuûa maùy phaùt ñieän. Role treã giôø seõ ñi voøng qua coâng taéc ñoùng taïm thôøi aùp suaát daàu thaáp trong suoát chu kyø quay tay vaø aùp suaát daàu trôn laïi ñeán maïch sau khi ñoäng cô khôûi ñoäng.

16200 - 13 EMERGENCY GENERATOR SET

Page 14: 16200-F

instrument tuû ñieän which is attached to the engine by vibration absorbing type mountings shall contain the following items for proper engine surveillance and maintenance:

1. Cooling water temperature gauge or thermometer

2. Lubricating oil pressure gauge

3. Running time meter

4. Tachometer

5. Emergency stop switch

6. Key switch for manual start

7. Automatic shutdown alarm

2.4 ALTERNATOR

A. Construction : The alternator shall be directly coupled to the engine flywheel through a flexible driving disc for positive alignmentThe alternator housing shall be bolted directly to the engine flywheel housing and shall have single or double bearing, prepacked with lubricant, support for the rotor which shall be statically and dynamically balanced. Foot mounting and lifting points shallarranged around the center of gravity. The alternator shall be protected and enclosed in drip-proof casing with balanced cooling fan.

B. Excitation : The field excitation shall be performed by a rotating three phase AC exciter and a brushless rotating silicon diode rectifier with surge protector assembly mounted on the rotor shaft. Constant output voltage control shall be achieved transistorized automatic voltage regulator which adjusts the exciter field current to

N. Baùnh ñaø: ñöôïc caân baèng tónh hoïc vaø ñoâïng hoïc vaø coù khaû naêng xoay quanh taïi 125% toác ñoä ñònh möùc maø khoâng bò thieät haïi.

O. Thieát bò ño ñoäng cô: tuû ñieän ño ñoäng cô ñöôïc gaén ñeán ñoäng cô baèng söï rung ñoäng coù caùc haïng muïc sau cho giaùm saùt vaø baûo döôõng ñoäng cô thích hôïp.

1. Maùy ño nhieät ñoä laøm nguoäi vaø thieát bò ño.

2. Maùy ño aùp suaát daàu boâi trôn

3. Ñoàng hoà ño thôøi gian hoaït ñoäng.

4. Maùy ño toác ñoä

5. Coâng taéc taét khaån caáp

6. Coâng taéc khoùa cho khôûi ñoäng soá tay

7. Baùo ñoäng taét taïm thôøi töï ñoäng.

2.4 MAÙY PHAÙT ÑIEÄN XOAY CHIEÀU

A. Xaây döïng: maùy phaùt ñieän xoay chieàu laø maùy ñoâi ñeán baùnh ñaø ñoäng cô qua ñóa ñeäm meàm cho lieân keát roõ raøng. Voû boïc maùy phaùt ñieän xoay chieàu coù gaén bu loâng tröïc tieáp ñeán baùnh ñaø ñoäng cô vaø coù söùc chòu taûi ñôn vaø ñoâi, ñoùng thuøng chaát boâi trôn tröôùc. Khung chaân vaø ñieåm naâng saép xeáp xung quanh troïng löïc trung taâm. Taát caû maùy phaùt ñieän xoay chieàu ñöôïc baûo veä vaø ñính keøm trong vaät ñuùc ngaên nhoû gioït coù quaït laøm nguoïi caân baèng.

B. Kích thích: coâng tröôøng ñöôïc hoaït ñoäng baèng boä kích töø AC 3pha xoay vaø maùy chænh hö diot silicon xoay brushless coù

16200 - 14 EMERGENCY GENERATOR SET

Page 15: 16200-F

compensate for all variations. The voltage regulator shall maintain the voltage within the limits of plus or minus 0.5 percent from no load to full load.

C. Insulation : The alternator shall be suitably treated for operation under tropical climate. All windings shall be impregnated with epoxy resin of thermosetting insulation vanish to establish class H insulation.

D. Voltage Regulator : Shall be of static solid statetype three phase with silicon diode control. A device for manual adjustment of regulated voltage shall be provided and shall extend a range of 10 percent above and below rated voltage under all operating conditions. A manual automatic switch shall permit selection of manual and automatic control of voltage.

E. Overload Capability : A compound circuit incorporated in the system shall ensure additional excitation during motor starting duties and fault condition.

F. Parallel Operation : Fully inter-connected pole face damping windings shall be incorporated to ensure smooth operation. An automatic load sharing device shall be provided for quadrature current compounding in conjunction with the specified electronic governor to enable generator set to run satisfactorily in parallel with utility.

G. Non-linear Load: The Alternator shall be furnished together with special control system to enable the

laép duïng cuï baûo hoä treân truïc roâto. Ñieàu khieån ñieän aùp ñaàu ra baát bieán ñaït ñöôïc boä ñieàu chænh ñieän aùp töï ñoäng taïm thôøi ñieàu chænh doøng ñieän coâng tröôøng boä kích töø ñeå buø cho taát caû bieán thieân. Boä ñieàu chænh ñieän aùp duy trì ñieän aùp trong giôùi haïn +/- 0.5% töø khoâng taûi ñeán taûi ñaày.

C. Caùch ñieän: maùy phaùt ñieän xoay chieàu ñöôïc xöû lyù hoaït ñoäng theo khí haäu. Tính chaát gioù seõ ñöôïc taåm baèng nhöïa thoâng epoxy cho vieäc khöû caùch ly phaûn öùng nhieät ñeå thieát laäp caùch ñieän loaïi H.

D. Ñieàu chænh ñieän aùp: laø loaïi thieát bò cöùng tónh coù 3 pha coù ñieàu khieån diot silicon. Moät thieát bò cho ñieàu chænh soá tay cuûa ñieän aùp ñònh möùc cung caáp vaø keùo daøi daõy ra 10% treân haøng ñöôïc ñieän aùp ñònh möùc theo taát caû ñieàu kieän hoaït ñoäng. Coâng taéc töï ñoäng soá tay cho pheùp choïn löïa soá tay hay ñieàu khieån töï ñoäng ñieän aùp.

E. Tình traïng quaù taûi: maïch hoãn hôïp keát hôïp vôùi heä thoáng ñaûm baûo kích thích theâm vaøo trong suoát quaù trình khôûi ñoäng moto vaø ñieàu kieän chaïm ñaát.

F. Hoaït ñoäng song song: lieân keát beà maët ñieän cöïc khoái bò veânh ñeå ñaûm baûo hoaït ñoäng suoân seõ. Thieát bò chia taûi töï ñoäng cung caáp cho doøng ñieän keát hôïp vaøo hoäp noái coù maùy ñieàu toác ñieän ñeå laøm maùy phaùt ñieän hoaït ñoäng song song coù ích.

G. Taûi khoâng tuyeán tính: trang bò maùy phaùt ñieän xoay chieàu coù heä thoáng ñieàu

16200 - 15 EMERGENCY GENERATOR SET

Page 16: 16200-F

set to deliver the output power for the non linear load up to 40% of rated output without effecting to its performance. (Less waveform distortion).

H. Radio and Telephone Interference : An appropriated radio, telephone frequency interference and line disturbance suppression circuits shall be provided.

I. Exciter field power shall be provided by a separate to the brushless exciter. Provide sufficient power to the excitations system to produce 250% short circuit from the main operator armature during a three phase fault with sufficient duration for protective devices to operate.

2.5 GENERATOR CONTROL BOARD

A. Generator control board shall be provided which incorporated complete controls for all function of the set. The control board shall be free standing, floor mounting, suitably ventilated, bottom or top entry with front access and constructed with heavy gauge, corrosion resisting material coated steel sheet. Full width lockable hinged door shall be provided to allow an accessibility to all internal and front mounted instruments and components. The control board shall be painted with acrylic stove enamel finish. The wiring in the control board shall be loomed and clipped to a high standard workmanship. All wire and cable end shall be clearly identified with markers. The control board shall contain the

khieån ñaëc bieät ñeán maùy ñeå phaân phoái ñieän ñaàu ra cho taûi lôùn nhaát 40% ñònh möùc ñaàu ra maø khoâng coù aûnh höôûng ñeán hoaït ñoäng maùy (ít bieán daïng soùng).

H. Söï nhieãu cuûa radio vaø ñieän thoaïi:1 radio thích hôïp, söï nhieãu taàn soá ñieän vaø cung caáp maïch choáng nhieãu.

I. Cung caáp ñieän töø tröôøng boä kích hoïat qua boä kích hoïat rieâng reõ. Cung caáp ñieän caàn thieát ñeán heä thoáng ñeå hoaït ñoäng 250% boä ngaén maïch töø trong suoát loõi 3 pha coù ñoä beàn caàn thieát cho thieát bò baûo veä ñeå hoaït ñoäng.

2.5 BAÛNG ÑIEÀU KHIEÅN MAÙY PHAÙT ÑIEÄN

A. Cung caáp baûng ñieàu khieån maùy phaùt ñieän keát hôïp vôùi ñieàu kieän hoaøn taát cho taát caû chöùc naêng maùy phaùt ñieän. Baûng ñieàu khieån ñöùng töï do, gaén saøn, thoâng gioù, loái vaøo ñænh vaø ñaùy coù loái vaøo maët tröôùc vaø ñöôïc xaây döïng coù quy moâ, taám theùp phuû vaät lieäu khaùng ræ. Cung caáp cöûa gaén khoùa ñeå cho pheùp vaøo ñeán thieát bò gaén tröôùc maët vaø beân trong vaø caùc thaønh phaàn. Baûng ñieàu khieån vaø nhaân coâng tieâu chuaån cao. Taát caû daây ñieän vaø caùp ñöôïc ñònh daïng roõ raøng coù ghi chuù. Baûng ñieàu khieån coù thieát bò caàn thieát vaø thieát bò ño nhö:

1. Duïng cuï ño ñieän aùp AC coù coâng taéc boä choïn pha.

2. Khoùa chuyeån maïch Ampe keá.16200 - 16 EMERGENCY GENERATOR SET

Page 17: 16200-F

necessary equipment and measuring instrument such as :

1. AC voltmeter with phase selector switch

2. AC ammeer with phase selector switch

3. Frequency meter

4. Automatic voltage regulator control

5. Kilowatt meter

6. Power factor meter

7. Kilowatt-hour meter

8. Main circuit breaker

9. Paralleling cross-current compensation control

10.Control switch for motorized governor

11. Battery charge with automatic setting

12. Automatic start-stop cranking.

13. Signal Lamp for operation and alarm/

14. Selector switch for manual-automatic synchronizing.

15. Other necessary components.

2.6 ALARM SYSTEM

Visual and audible alarm shall be completely provided and connected to scada system

2.7 CONTROL SYSTEM

A. A control system comprising of a

3. Duïng cuï ño taàn soá. 4. Ñieàu khieån boä ñieàu khieån ñieän aùp töï ñoäng.

5. Duïng cuï ño KW.

6. Duïng cöï ño heä soá ñieän.

7. Duïng cuï ño KW/giôø.

8. Boä ngaét maïch chính.

9. Ñieàu khieån buø doøng ñieän ngang qua song song.

10. Coâng taéc ñieàu khieån cho maùy ñieàu toác töï ñoäng.

11. Xaïc aéc quy coù boä caøi ñaët töï ñoäng.

12. Chu kyø quay tay taét môû töï ñoäng.

13. Ñeøn tín hieäu cho hoaït ñoäng vaø baùo ñoäng.

14. Coâng taéc boä choïn cho hoaït ñoäng ñoàng boä töï ñoäng – soá tay.

15. Caùc thaønh phaàn caàn thieát.

2.6 HEÄ THOÁNG BAÙO ÑOÄNG

Cung caáp heä thoáng baùo ñoäng nghe vaø thaáy ñöôïc, keát noái ñeán heä thoáng Scada.

2.7 HEÄ THOÁNG ÑIEÀU KHIEÅN

A. Cung caáp heä thoáng ñieàu khieån goàm maïch xöû lyù phoái hôïp vôùi role, coâng taéc vaø caùc thieát bò khaùc, ñi daây caàn thieát cho hoaït ñoäng töï ñoäng vaø soá tay maùy phaùt ñieän. Taát caû duïng cuï ñöôïc gaén treân moãi taám ñieàu khieån heä thoáng goàm:

16200 - 17 EMERGENCY GENERATOR SET

Page 18: 16200-F

microprocessor incorporated with relays, switching and other devices and necessary wiring shall be provided for fully automatic and manual operation of all generator sets. All devices shall be mounted in each control board. The control system shall comprise of the following features:

A. Manual - Automatic start/stop of each generator sets.

B. Manual - Automatic synchronization of the generator sets.

C. Manual - Automatic and manual transfer and retransfer of load.

D. Start delay to prevent unnecessary starting of the set in the event of false main failure or momentary transient break of main supply.

E. Multi start attempt, if the engine fail to start on the first attempt.

F. Main return delay to prevent unnecessary load retransfer in the event of flase main restoration.

G. Run on time delay for relieving stresses in the engine by allowing it to cool down before stopping.

H. Other feature according to manufacturer's standard practice.

I. Remote Engine Annunciator Panel include engine run and low fuel indicator lights and remote start-stop switch.

2.8 OPERATION UPON MAIN FAILURE

See Section 16350 paralleling switch gear.

2.9 ASSEMBLY

A. Taét/môû töï ñoäng - ñieàu khieån baèng tay cho moãi maùy phaùt ñieän.

B. Heä thoáng ñoàng boä töï ñoäng – soá tay maùy phaùt ñieän.

C. Soá tay – töï ñoäng vaø truyeàn soá tay vaø truyeàn laïi taûi.

D. Khôûi ñoäng role ñeå ngaên caùc khôûi ñoäng khoâng caàn thieát cho thieát bò ngay khi phaù hoûng chính hay moái gaõy taïm thôøi cuûa nguoàn cung caáp chính.

E. Ña khôûi ñoäng, neáu ñoäng cô khoâng khôûi ñoäng.

F. Söï trôû laïi treã ñeå ngaên truyeàn laïi taûi khoâng caàn thieát ngay khi phuïc hoài aùnh saùng chính.

G. Chaïy treã thôøi gian cho xaû öùng xuaát trong ñoäng cô baèng caùch cho pheùp noù nguoäi laïi tröôùc khi döøng.

H. Caùc ñieåm ñaëc tröng khaùc theo öùng duïng tieâu chuaån cuûa nhaø saûn xuaát.

I. Tuû ñieän tín hieäu ñoäng cô ñieàu khieån töø xa goàm raõnh ñoäng cô vaø duïng cuï ño nhieân lieäu thaáp vaø ñieàu khieån coâng taéc taét/môû töø xa.

2.8 OPERATION UPON MAIN FAILURE

Xem phaàn 16350 boä chuyeån ñoåi maïch song song.

2.9 LAÉP RAÙP

Maùy phaùt ñieän, taám ñieàu khieån vaø cubicle coâng taéc truyeàn ñöôïc laép raùp vaø

16200 - 18 EMERGENCY GENERATOR SET

Page 19: 16200-F

The generator set, control board and transfer switch cubicle shall be assembled and tested at the factory the manufacturer and shall have a certain product range and own type, model number and code.

2.10 SOUND LEVEL CONTROL

Provide sound proof material to control sound level from generator room by keepsound level less than 85 dB, at 1 m. from outside wall.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Verify that surfaces are ready to receive work and field dimensions are as shown on the Drawings.

B. Verify that required utilities are available in proper location and ready for use.

C. Beginning of installation means installer accepts existing conditions.

3.2 INSTALLATION

A. Provide concrete base for all sets. Location and weight of each sets are shown on the Drawings.

B. Install the sets in accordance with manufacturer's instructions.

3.3 FIELD QUALITY CONTROL

A. Field inspection and testing will be performed after completion of the work according to NEMA MG1.

B. Provide full load test utilizing without interruption portable test bank, if required, for four hours minimum. Simulate power failure including operation of transfer switch,

kieåm tra taïi nhaø maùy vaø coù saûn phaåm chaéc chaén, ñuùng loaïi, ñuùng soá maãu maõ.

2.10 ÑIEÀU KHIEÅN MÖÙC AÂM THANH

Cung caáp vaät lieäu caùch aâm ñeå ñieàu khieån möùc aâm thanh töø maùy phaùt ñieän baèng caùch giöõ möùc aâm thanh nhoû hôn 85 dB, caùch töôøng trong 1m.

PHAÀN 3 - THI COÂNG

3.1 KIEÅM TRA

A. Kieåm tra beà maët saøn coù saün ñeå nhaän coâng vieäc vaø khoái löôïng coâng vieäc nhö trong baûn veõ.

B. Kieåm tra caùc utilities coù söû duïng trong vò trí thích hôïp vaø saün saøng hoaït ñoäng.

C. Baét ñaàu vieäc laép ñaët coù nghóa laø nhaø laép ñaët cung öùng ñoàng yù caùc ñieàu kieän hieän höõu.

3.2 LAÉP ÑAËT

A. Cung caáp neàn beâ toâng cho taát caû boä maùy. Vò trí vaø troïng löôïng cuûa moãi thieát bò ñöôïc chæ trong baûn veõ.

B. Laép thieát bò theo höôùng daãn nhaø saûn xuaát.

3.3 ÑIEÀU KHIEÅN CHAÁT LÖÔÏNG COÂNG TRÖÔØNG

A. Tieán haønh thaåm tra vaø kieåm tra hieän traïng sau khi hoaøn thaønh coâng vieäc theo tieâu chuaån NEMA MG1.

B. Cung caáp ñaày ñuû kieåm tra taûi ñeå khoâng bò giaùn ñoïan ít nhaát 4 giôø. Phaù hoûng naêng löôïng goàm hoaït ñoäng coâng

16200 - 19 EMERGENCY GENERATOR SET

Page 20: 16200-F

automatic starting cycle, and automatic shutdown, and return to normal, and paralleling function.

C. During test, record the following at 20 minute intervals:

1.

Kilowatts.

2.Amperes.

3.Voltage.

4.Coolant

temperature.

5.Room

temperature.

6.

Frequency.

7. Oil pressure.

D. Test alarm and shutdown circuits by simulating conditions.

3.4 SOUND LEVEL CONTROL A. The sound level from generator shall be less than 85 dB, at 1m. from the wall of the generator room.

3.5 CONTRACTOR FIELD SERVICES

A. Prepare, start, test, and adjust systems until the systems are ready to operate.

B. Any defects found during this test shall be corrected by the Contractor.

3.6 ADJUSTING

taéc truyeàn, chu trình khôûi ñoäng töï ñoäng vaø taét taïm thôøi töï ñoäng vaø trôû veà vò trí bình thöôøng, vaø chöùc naêng song song.

C. Trong quaù trình kieåm tra, ghi nhaän laïi caùc ñieàu sau moãi 20 phuùt:

1. Kilowatts.

2. Amperes.

3. Ñieän aùp.

4. Coolant temperature.

5. Nhieät ñoä phoøng.

6. Taàn soá.

7. AÙp suaát daàu.

D. Baùo ñoäng kieåm tra vaø maïch taét taïm thôøi baèng vieäc taùi taïo caùc ñieàu kieän treân

3.4 ÑIEÀU KHIEÅN MÖÙC AÂM THANH A. Möùc aâm thanh töø maùy phaùt ñieän nhoû hôn 85 dB, caùch töôøng cuûa phoøng maùy phaùt ñieän 1m

3.5 DÒCH VUÏ COÂNG TRÖÔØNG CUÛA NHAØ THAÀU

A. Chuaån bò, baét ñaàu, kieåm tra vaø ñieàu chænh heä thoáng cho ñeán khi heä thoáng saün saøng hoaït ñoäng.

B. Baát kyø hö hoûng naøo xuaát hieän trong quaù trình kieåm tra seõ do nhaø thaàu söûa chöõa.

3.6 ÑIEÀU CHÆNH

A. Ñieàu chænh coâng vieäc khi caàn thieát.

B. Ñieàu chænh ñieän aùp ñaàu ra maùy phaùt ñieän vaø toác ñoä ñoäng cô ñeå ñaït giaù trò ñònh möùc.

16200 - 20 EMERGENCY GENERATOR SET

Page 21: 16200-F

A. Adjust work as necessary.

B. Adjust generator output voltage and engine speed to rated value.

3.7 CLEANING

A. Clean work thoroughly.

B.Clean engine and generator surfaces. Replace oil and fuel filters after test procedure.

3.8 DEMONSTRATION

A. Provide systems demonstration and describe loads connected to emergency system and restrictions for future load additions.

B. Simulate power outage by interrupting normal source, and demonstrate that system operates to provide emergency power.

END OF SECTION

3.7 VEÄ SINH

A. Veä sinh toaøn boä coâng vieäc.

B. Veä sinh ñoäng cô vaø beà maët maùy phaùt ñieän. Thay theá boä loïc daàu vaø nhieân lieäu sau khi kieåm tra.

3.8 DIEÃN GIAÛI

A. Cung caáp giaûi thích heä thoáng vaø moâ taû taûi keát noái ñeán heä thoáng khaån vaø giôùi haïn cho taûi theâm vaøo sau naøy.

B. Taùi taïo nguoàn ñieän ra baèng nguoàn bình thöôøng ñöùt quaõng vaø giaûi thích söï hoaït ñoäng cuûa heä thoáng ñeå cung caáp ñieàu khieån..

END OF SECTION

16200 - 21 EMERGENCY GENERATOR SET