OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 1
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
1678MCC
Acceptance Test
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 2
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
CONTENTS
1. INTRODUCTION ...................................................................................................................... 4 1.1. Scope ............................................................................................................................................ 4 1.2. Reminder of Safe Working Practices ....................................................................................... 4 1.3. Data Recording ........................................................................................................................... 5 1.4. Special care ................................................................................................................................. 5 2. TEST PLAN................................................................................................................................ 6 3. PRE-REQUISITES .................................................................................................................... 7 3.1. Reference..................................................................................................................................... 7 3.2. Status of NE................................................................................................................................. 7 3.3. Test Instruments......................................................................................................................... 7 3.4. Test configurations ..................................................................................................................... 7 3.5. Example of Customer Network................................................................................................. 8 4. SECTION A : STANDALONE TEST................................................................................... 9 4.1. VISUAL INSTALLATION / CABLING INSPECTION........................................................ 9 4.2. POWER SUPPLY CHECK /POWER ON ............................................................................ 10 4.3. NETWORK ELEMENT TEST SET-UP ............................................................................... 11
4.3.1. Supervision with ECT................................................................................................ 11 4.3.2. Hardware Configuration of the Equipment ............................................................ 11 4.3.3. Equipment Configuration ......................................................................................... 12
4.4 OPTICAL PORT LOCAL TESTS .........................................................................................13 4.4.1 Laser Safety / Optical Output Power ..................................................................................... 13 4.4.2 OPTICAL RECEIVER SENSITIVITY.................................................................................. 14 4.5. EPS PROTECTION OF THE HO MATRIX (MXXXX) BOARD ..................................... 15 4.6. FLC REDUNDANCY CHECK............................................................................................... 16 4.7. PROTECTION OF THE PSF BOARD (IF APPLICABLE) ............................................... 16 4.8. CLOCK REFERENCE TEST ................................................................................................ 17 4.9. MSP PROTECTION functionality ......................................................................................... 17 4.10. LOCAL BER TEST (OPTICAL/ELECTRICAL-E1, STM-1,4,16,64) ............................... 18 5. SECTION B : SEGMENT TEST.......................................................................................... 20 5.1. Rx OPTICAL LINE PORT ..................................................................................................... 20 5.2. ENGINEERING ORDER WIRE (EOW) .............................................................................. 21
• Selective call (individual call) .................................................................................... 21 • Omnibus call (general call)........................................................................................ 21
6. SECTION C : END TO END TEST....................................................................................... 22 6.1. BER STABILITY END TO END TEST (OVER THE NETWORK) ................................ 22
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 3
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX A: TEST SUMMARY ................................................................................................... 23 APPENDIX B: TEST INSTRUMENTS ........................................................................................... 24 APPENDIX C: MEASUREMENT SHEETS ................................................................................... 25 APPENDIX C.1: VISUAL INSTALLATION / CABLING INSPECTION .................................. 26 APPENDIX C.2: POWER SUPPLY CHECK /POWER ON ......................................................... 27 APPENDIX C.3: NETWORK ELEMENT TEST SET-UP............................................................ 28 APPENDIX C.3: NETWORK ELEMENT TEST SET-UP (INVENTORY)................................ 29 APPENDIX C.3: NETWORK ELEMENT TEST SET-UP (INVENTORY)................................ 30 APPENDIX C.4: OPTICAL PORT LOCAL TESTS..................................................................... 31 APPENDIX C.5: EPS PROTECTION OF THE HO MATRIX (MX160) BOARD..................... 32 APPENDIX C.8: FLC REDUNDANCY CHECK ........................................................................... 33 APPENDIX C.9: PROTECTION OF THE PSF BOARD (IF APPLICABLE)............................ 34 APPENDIX C.10: CLOCK REFERENCE TEST AND INTERNAL CLOCK
ACCURACY.......................................................................................................... 35 APPENDIX C.11: MSP PROTECTION FUNCTIONALITY. ...................................................... 36 APPENDIX C.12: LOCAL BER TEST (OPTICAL/ELECTRICAL- E1, STM-1,4,16,64)......... 37 APPENDIX C.13: Rx OPTICAL LINE PORT TESTS .................................................................. 38 APPENDIX C:14 SERVICE CHANNEL TEST (EOW) ............................................................... 39 APPENDIX C.15: BER STABILITY TEST OVER THE NETWORK ........................................ 40 APPENDIX D : TECHNICAL DATA [ OPTICAL CHARACTERISTIC]................................ 41
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 4
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
1. INTRODUCTION
1.1. Scope The scope of this document is divided into 2 sections which are:
SECTION A : STAND-ALONE TEST This section of the document describes the method used for acceptance testing a 1678MCC after it has been installed on site.
The purpose of this test period is not to test the full functionality of the product or to reproduce all of the tests performed in the factory acceptance test phase. The specific objectives of the Stand Alone Test are as follows:
• To verify that all required parts have been delivered (inventory check).
• To verify that the installation of the product has been performed correctly.
• To verify the functional integrity of the equipment following shipment and installation.
SECTION B : SEGMENT TEST This section of the document describes the method used for Network Acceptance Test of 1678MCC after Stand-Alone-Test has been performed and all station is supervised.
The purpose of this test period is not to test the full functionality of the product or to reproduce all of the tests performed in the factory acceptance test phase. The specific objectives of the Segment Test are as follows:
• Check the protection provided by the equipment (transmission and synchronization).
• Check, over a 24 hours period (overnight), the error on the links chosen initially to evaluate transmission quality on the network of the main and 24 hour for spare (protection path).
1.2. Reminder of Safe Working Practices Observe anti-static precautions.
Ensure that the optical power has been turned off before viewing or inspecting any optical material.
All optical fiber connectors must be treated with the utmost care and a very high standard of cleanliness maintained as soon as an optical connector is disconnected, the free ends must be protected with dust caps.
Before reconnection, all optical connectors must be inspected and cleaned if necessary.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 5
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
1.3. Data Recording Alcatel (Supplier) and CUSTOMER (Purchaser) representative should sign each test described on one or more data sheets. In the case of a failed test, a Customer Incident Report have to be filled in, giving details about the problem encountered as well as the test title and the testing conditions (software release, test equipment used...). At the end of the test period, the Test Result Sheet, a summary of all tests covered by this procedure, will be filled in by the Supplier representative and signed off by both parties.
1.4. Special care *Special cares to be taken when plugging boards in 1678MCC Subrack, in order not damage back-panel connectors! 1- Before inserting the boards open the blocking levers
2- Insert the boards inside the guide without acting on the blocking levers. Push softly the front plate until the mating of board and shelf connector.
3- Complete the insertion by locking the blocking levers
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 6
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
2. TEST PLAN
Test Number Test Title
SECTION A : STANDALONE TEST
4.1 VISUAL INSTALLATION / CABLING INSPECTION
4.2 POWER SUPPLY CHECK /POWER ON
4.3 NETWORK ELEMENT TEST SET-UP
4.4 OPTICAL PORT LOCAL TESTS
4.5 EPS PROTECTION OF THE HO MATRIX (MX160) BOARD
4.6 EPS PROTECTION OF THE LO MATRIX (LAX20) BOARD (IF APPLICABLE)
4.7 EPS MATRIX ON 1662 OED MATRIX
4.8 FLC REDUNDANCY CHECK
4.9 PROTECTION OF THE PSF BOARD (IF APPLICABLE)
4.10 CLOCK REFERENCE TEST
4.11 MSP PROTECTION FUNCTIONALITY
4.12 LOCAL BER TEST (OPTICAL/ELECTRICAL- E1, STM-1,4,16,64)
SECTION B : SEGMENT TEST
5.1 Rx OPTICAL LINE PORT CHECK
5.2 ENGINEERING ORDER WIRE (EOW)
SECTION C : END TO END TEST
6.1 BER STABILITY END TO END TEST
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 7
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
3. PRE-REQUISITES
3.1. Reference • As referenced within the procedure, the test results sheets in APPENDIX B • Site Installation and Configuration Handbook. • 1678MCC Factory Acceptance Test Procedure and Results
3.2. Status of NE • The equipment (or network element, NE) must be compliant with the basic configuration in
the site installation handbook. • The tests are to be conducted directly on the equipment ports if DDF is not available or if it
can not be done on DDF.
3.3. Test Instruments See APPENDIX C
3.4. Test configurations
Each 1678MCC In Station Test refers to one of the Test Configurations shown below: Figure 1( Configuration for Optical port local test) Figure 2( Configuration for EPS test, BER test etc )
NE under test
STM-64
STM-1/4/16
VariableAttenuators
TestSet
STM-64
OpticalPower meter
Figure 1 Configuration for Optical Port local tests
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 8
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
STM-64Line Port
STM-1 Ports
XMatrix
Test set STM-1
1678MCC under test
Loop
Tx
Rx
STM-64Line Port Loop
Tx
Rx
Test set STM-16 STM-16
Ports
Variable Attenuator
Variable Attenuator
PRE-AMP
Booster
Figure 2 : Configuration for EPS test, BER test…
3.5. Example of Customer Network
Network sample
Figure 3: System Configuration.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 9
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
4. SECTION A : STANDALONE TEST
4.1. VISUAL INSTALLATION / CABLING INSPECTION Purpose
The purpose is to verify that the Installation and the Cabling are done in accordance with the Site Installation Handbook. Test equipment
Multimeter
Procedure 1. Check that the equipment is installed in accordance with the Site Installation Handbook:
• Positioning of rows and racks (labeling), • Positioning of equipment in the rack, • Layout within the equipment rack and Subrack.
2. Check the inventory of the installed equipment with the Site Installation Handbook. • Quantity and type of cards / modules provided, • Type (impedance) and cabling of external synchronization ports, if appropriate, • Connection of the LAN port of both FLCS and FLCC board to a router if the
equipment is used as a GNE. 3. Inspect the quality of installation of all external connections:
• Installation of the optical fibers, their positioning (adequate bending radius, 4 cm at least) and labeling.
• Installation of the electrical cables including earth bonding. • Installation of anti-static wrist strap bonding point on each rack and availability of
wrist straps. 4. Check the connection of the NGTRU to the equipment:
• Connections of power supply from rectifier to A and B of NGTRU • Connections of power supply connector on the PSF boards in slots 24 and slot 25 to
the NGTRU. • Connection of the 9-way connector on the FLCC board in slot 20 to the NGTRU.
5. Check the mechanical installation of the equipment. • For the stations where seismic bracing is required check that seismic bracing has
been installed in accordance with the Station Installation Handbook. • Check that racks are securely anchored and that the Subrack is securely mounted
within the racks with all required bolts in place. 6. Perform a visual Inspection of the equipment and cards.
• Check that equipment does not have any signs of mechanical damage. • Inspect carefully the back-panel connectors for all the slots and ensure that there are
no broken or bent pins on the back-panel. • Inspect all card connectors to ensure they are not damaged or likely to cause damage
to back-panel when inserted.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 10
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
4.2. POWER SUPPLY CHECK /POWER ON Purpose
The purpose is to verify that the power supply voltage for the equipment is in the range.
Test equipment
Multimeter
Procedure 1. All the circuit breakers have to be in power off position. 2. Check the branch –A and –B coming from DCPDB:
• Input power Range: -38V to –75V • Record the results.
3. Disconnect the power cable from left and right PSF 4. Turn on the fuses and measure the output voltage of NGTRU. 5. The power reading should be as follow:
- Branch Input < -65V Output Power NGTRU ≥ -65V - Branch Input > -65V Output Power NGTRU = Branch Voltage
Output Power Range NGTRU: -65VDC to -75VDC
Figure 5 : NGTRU Output Voltage
6. Turn off the fuses and connect the power cable to the left and right PSF. 7. Turn on the fuses for the power A and B at the NGTRU.
-75VDC
-65VDC
Branch Input
NG
TRU
-38VDC -65VDC -75VDC
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 11
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
4.3. NETWORK ELEMENT TEST SET-UP During the Following tests, we will verify that the Hardware and Software configuration of Network Element is compliant with the Station Installation Handbook and contract-specific requirements.
IMPORTANT:
• Before Stand-Alone-Test can start, the equipment's basic configuration (configuration data specified in the Site Installation Handbook: local OS configurations) must be backed up onto the equipment craft terminal.
• This basic configuration will be re-downloaded at the end of Stand-Alone-Testing to normalize the configuration to that specified in the installation documentation. All SDH port loop-backs, ALS set-up and any remaining cross connections used during Stand –Alone-Test will be removed at the end of the tests.
4.3.1. Supervision with ECT Purpose
Verify the basic functionality of the 1320CT, and the possibility to supervise NE with craft-terminal.
Test equipment
Equipment Craft Terminal
Procedure 1. Connect the equipment craft terminal (ECT) provided to the equipment under test. 2. Launch the 1320CT application, and wait until the NES window (Network Element
Synthesis) is displayed NOTE: If a map has been saved on 1320CT, it may be possible to see all the equipment of the station at the same time, but basically the craft allows to supervise the equipment connected to it.
3. Check that:
• The equipment type and its version is displayed in the right hand part of the NES view when the equipment is selected in the left hand part of this same view,
• The reporting of NE alarms is correct.
4.3.2. Hardware Configuration of the Equipment Purpose
Verify the software version of the equipment.
Test equipment
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 12
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
Equipment Craft Terminal
Procedure 1. From the craft terminal, display in turn the SR78M (Main Shelf) views of the equipment
Subrack. 2. Check that:
• The identity of the boards is correctly reported on the craft terminal in their corresponding slots. Specifically check to ensure the absence of the following alarms for each Subrack slot in the SR78M :
RUTM (Replaceable Unit Type Mismatch),
RUM (Replaceable Unit Missing)
RUP (Replaceable Unit Problem)
NOTE: Alarms other than the above may appear. Clicking the corresponding slot in the SR78M views can dispel any ambiguity; the icons of the above alarms will then become visible at the bottom of the resulting view. They should be colored green.
• That the identity of the SDH port modules is correctly reported on the craft terminal. The correct correspondence can be determined by the absence of any of the above alarms, which can be verified from the green color of the respective icons in the respective interface displays (view IS11 - r01s01sl3/daughter#1 for a STM1 port module for example).
• In the case of an alarm, the origin of the fault (installation in the NE or craft terminal configuration) can be determined by comparing the part numbers of the boards declared and displayed the craft terminal with the information obtained from the remote inventory.
4.3.3. Equipment Configuration Purpose
Verify the equipment configuration of the 1678MCC, compared to the Site Configuration Handbook, and tests requirement.
Test equipment
Equipment Craft Terminal
Procedure Run the 1320CT application and the from the menu bar of EML-USM view verify that the parameters are configured as follows:
• Subrack Configuration (open the equipment view and check that subrack configuration is in conformity with the Site Installation & Configuration Handbook.
• Write down serial number in column given. • Test paths are configured in accordance with the test requirements for
example: SNCP Protection.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 13
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
4.4 OPTICAL PORT LOCAL TESTS
4.4.1 Laser Safety / Optical Output Power
Purpose
To check laser safety and to measure optical output power.
Test equipment
SDH Analyzer with the required SDH optical interfaces equipped for the ports under test Optical power meter 1 Variable optical attenuator Optical fiber FC/PC patch cords Equipment Craft Terminal Procedure
Establish the test configuration shown in Figure 1. 1. Enable ALS on the optical port under test and loop the optical port under test, using a
variable attenuator if required. 2. Using the ECT, ensure that no LOS alarm exist and ALS Current State is Inactive 3. Disconnect the transmit fiber from the receive port of the optical interface (or variable
attenuator if applicable) . 4. Using the ECT, confirm on the SDH port view that a LOS alarm is generated on the receive
port under test and that ALS Current State is active. 5. Using the ECT, force the laser ON by selecting the "Laser Forced ON" option 6. Measure optical output power on the power meter and records the results. Check results
with Appendix F.
IMPORTANT: Ensure that the power meter is set to the correct wavelength for the port under test. 7. Using the ECT, force laser OFF by selecting the "Laser Forced OFF" option. 8. Ensure that the laser turns OFF and that no power is measured on the power meter. 9. Re-connect the transmit fiber and confirm that the LOS alarm remains on the optical port
and that ALS Current State is Inactive. 10. Perform the checking to all optical port and at the end of the test, ensure the configuration
on the ports by setting ALS Enable.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 14
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
4.4.2 OPTICAL RECEIVER SENSITIVITY
Purpose
To verify the received optical sensitivity of STM-64 unit, tributary optical units and pre-amplifiers complies with the equipment specification.
Test equipment
STM-N SDH Analyzer Optical power meter Optical Variable attenuator Optical fiber patch cords Equipment Craft Terminal Procedure
Figure 6 : Optical Port sensitivity test 1. Establish the test configuration shown in Figure 6 2. Perform the tests for all optical ports by creating AU_4 cross-connection for each port. 3. Configure software loopback (matrix looped) or physical loop as figure 2. 4. Connect analyzer output to input of optical attenuator then to Rx of STM-N port. 5. Connect the output STM-N port back to SDH analyzer then check for error free
transmission. 6. Increase the attenuation until errors are indicated on analyzer and decrease attenuation for 1
dBm where the error is clear. 7. Measure the output from optical attenuator ( STM-N port Rx Side) 8. Check, if sensitivity is in specific range by referring to Appendix F. If not, please check the
test setup, clean optical output on board or ODF, exchange board or optical module. 9. Record the result and continue with each port in sequence 10. For STM 64, follow the configuration as Figure 2 with no software loopback and pump-in
the signal from port on others STM-N trib.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 15
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
11. Perform the sensitivity test by increase and decrease the optical attenuator and monitor from analyzer the record the measurement of final receive power.
4.5. EPS PROTECTION OF THE HO MATRIX (MXXXX) BOARD
Purpose
To test the EPS protection functionality / performance of the HOMATRIX (MX160/320/640) board in slot 10 protected by the HOMATRIX in slot 11. Test equipment
SDH Analyzer Equipment Craft Terminal Procedure
1. Establish the test configuration shown in Figure 2 (no attenuation required for STM64 ports).
2. Ensure that the test paths are configured. 3. Configure the SDH Analyzer to transmit and monitor a VC-4 bulk payload within an STM-
1 / STM-16 / STM-64 using a 2E23-1 PRBS signal and ensure error free operation. 4. Press the reset button on protected MX160 board (slot 10). Wait for 20min for the Spare
MX160 board to become active. Check the status of the MX160 in slot 11 is the following (through its respective icon):
• "EPS Protection Status Active", visible in the EML-USM views of this board. 5. At the end of the switchover period, check :
• That not more than 2ES, 2SES and 2AIS was registered on the SDH Analyzer. • The test path is error free after the switchover.
6. Remove the protected MX160 (slot 10). • RUM (Replaceable Unit Missing) alarm occurred on ECT for the MX160 in slot 10
7. Replace the MX160 board in slot 10 (only after the transitional period). Wait for several minutes for the board to initialize. Check:
• That the status of the MX160 board in slot 10 is the following (through its respective icon): "EPS Protection Status Standby" visible in the EML-USM views of this board.
• That traffic is error free during and after replacement of MX160 board in slot 10. 8. Press the reset button on the spare MX160 board (slot 11). Wait for 20 min for the Main
MX160 board to become active. Check the status of MX160 board in slot 10 is the following (through its respective icon):
• "EPS Protection Status Active", visible in the EML-USM views of this board. 9. At the end of the switchover period, check:
• That not more than 2ES, 2SES and 2AIS was registered on the SDH Analyzer following the switchover.
• The test path is error free after the switchover. 10. Remove the spare MX160 (slot 11).
• RUM (Replaceable Unit Missing) alarm occurred on ECT for the MX160 in slot 11
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 16
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
11. Replace the MX160 board in slot 11 (only after the transitional period). Wait for several minutes for the board to initialize.
4.6. FLC REDUNDANCY CHECK
Purpose
To test the FLC redundancy of the FLCCongi and FLCService board. Test equipment
SDH Analyzer Equipment Craft Terminal Procedure
1. Establish the test configuration shown in Figure 2. 2. Ensure that the test paths are configured. 3. Configure the SDH Analyzer to transmit and monitor a VC-4 bulk payload within an STM-
1 / STM-16 / STM-64 using a 2E23-1 PRBS signal and ensure error free operation. 4. Perform a software switch command
• Verify the active FLC • Select equipment provisioning menu. • Select the Edit -> FLC EPS switch.
5. Verify that the test path is error free when the switching activity taken place. 6. Wait a while after switch, until the FLC are synchronized again and verify that the active
PLC become standby and vice versa. 7. Record the result.
4.7. PROTECTION OF THE PSF BOARD (IF APPLICABLE) Purpose
Verify that the EPS protection of the PSF board in slot 24 by the PSF board in slot 25 is not traffic affecting. To verify that PSF boards have been connected to the correct circuit breakers. Test equipment
SDH Analyzer Equipment Craft Terminal Procedure
1. Establish the test configuration shown in Figure 2. 2. Ensure that the test paths are configured.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 17
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
3. Configure the SDH Analyzer to transmit and monitor a VC-4 bulk payload within an STM-1 / STM-16 / STM-64 using a 2E23-1 PRBS signal and ensure error free operation.
4. Switch off Battery. A (for PSF slot 24) circuit breaker. • Check that no errors are registered on the analyzer. • Alarms on ECT are recorded correctly.
5. Switch on Battery. A circuit breaker. • Check that no errors occurred on the analyzer. • Alarms cleared on ECT or alarm list.
6. Switch off Battery. B (for PSF slot 25) circuit breaker. • Check that no errors occurred on the analyzer. • Alarms on ECT are recorded correctly.
7. Switch on Battery. B circuit breaker. • Check that no errors occurred on the analyzer. • Alarms cleared on ECT or alarm list.
8. Record the results.
4.8. CLOCK REFERENCE TEST
Purpose
Verify that the clock reference can be configured and lock to the configured source. Test equipment
Equipment Craft Terminal Frequency Counter or SDH Analyzer with internal frequency counter. Procedure
1. Measure the clock output (free running) from FLCSERVE. 2. Verify the internal clock accuracy complies with the specification. 3. Connect the 2 MHz clock source to the synch input at FLCSERVE.
4.9. MSP PROTECTION functionality Purpose To verify the functionality of the MSP 1+1 Standard protection mode when apply to STM-N Optical or Electrical tributary. Test Equipment SDH Analyzer Equipment Craft Terminal Optical fiber patch cords
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 18
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
Procedure 1. Setup the test circuit as shown in figure 2 but using only STM-N tributary unit which are
lower than STM-64 for the whole testing. 2. Setup the SDH Analyser to one of STM-N port (as drop) and loop-back first STM-N port
(as Protected Path) and second STM-N port on the same or different board (as Protecting Path).
3. Create a single cross connection and setting the not revertive MSP 1+1 on the selected port. 4. Create fault at on the protected path by pulling out the optical patchcord . 5. Check that no Errors occur after the transitional switchover period. There shall be only
burst error during the creation of the fault for the analyser and not more than 2ES, 2SES 6. Normalise the protected path by connect back the optical patchcord. 7. Delete the MSP 1+1 setting and prepare another STM-N port with physical loopback. 8. Repeat the step from step 4 to step 8 then record all the result in measurement sheet.
4.10. LOCAL BER TEST (OPTICAL/ELECTRICAL-E1, STM-1,4,16,64) Purpose Verify the transmission integrity and stability of the installed equipment over a 24hours. Test Equipment SDH Analyzer Fixed/Variable optical attenuator Equipment Craft Terminal + Connecting Cord Optical fiber patch cords Procedure 1. Establish the test configuration shown in Figure 2. 2. Configure the SDH Analyzer to transmit and monitor refer to the table below and ensure
error free operation for SDH Analyzer:
Bit rate Code Sequence 2048 Kbit/s ± 50 ppm HDB3 215 -1 pseudorandom 34368 Kbit/s ± 20 ppm HDB3 215 -1 pseudorandom
44736 Kbit/s ± 20 ppm B3ZS 215 -1 pseudorandom 139264 Kbit/s ± 15 ppm CMI 223 -1 pseudorandom
155520 Kbit/s CMI 223 -1 pseudorandom 155,520 kbit/s S1.1, L1.1 L1.2 223 -1 pseudorandom 622,080 kbit/s S4.1, L4.1, L4.2 223 -1 pseudorandom
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 19
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
3. Before starting the stability test, check all electrical & optical port for their continuity.
Please make sure all cascade point is correct. 4. Activate all performance monitoring points (STM-64 MSTTP, STM-1 / 16 MSTTP), then
activate event/error logging on the SDH analyzer so that any errors that occur are recorded with a date and time stamp.
5. In the Diagnosis pull–down menu, select the Log Browsing option -> Alarm Log. Clear all the alarms in the Alarm Log.
6. Start (‘run’) the BER stability test by pressing start button. 7. At the end of the stability period, examine the NE PM registers, via the ECT, and confirm
that no spurious performance parameter counts have been recorded. Confirm that no errors have been detected by the Test sets. Examine the alarm logs via the ECT and confirm that no unexpected alarms (such as RUP alarm for example) were raised.
8. After the test, remove all the PM from the equipment. 9. Repeat the test for all equipped optical and electrical ports and record the results.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 20
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
5. SECTION B : SEGMENT TEST
5.1. Rx OPTICAL LINE PORT
1678MMC 1678MMC
ODF ODF
RADIOMETER
STM-N STM-N port port
Station - A Station - B
C.T.
Rx line optical cable
Purpose
Verify the optical power of the signal received from the remote 1660SM (Station B on the test bench). Test equipment
Power Meter Equipment Craft Terminal + Connecting Cord Optical fiber patch cords Procedure
1. Disconnect the Rx optical cable line from the ODF and connect it to the Radiometer input. 2. By means of the C.T. turn-on the laser. 3. Wait for 180 sec. and then check that the Rx optical power complies with the expected
value. Note: Rx power must be calculated on plant data. (PTx – Theoretical line attenuation based on Customer data).
4. Repeat the check on the other port with “Line port” function.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 21
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
5.2. ENGINEERING ORDER WIRE (EOW)
Purpose
To ensure all calls and selective calling are operational. Test equipment
Equipment Craft Terminal Handset (Engineering Order Wire) Procedure 1. Follow the actual implementation plan for the set up. 2. Create the overhead cross-connection and correct order wire number for all station. 3. Push the call button and made selective call and general call.
• Selective call (individual call) After lifting the handset, dial the telephone number of the NE to be reached according to the EOW table. Check that the call is routed to the correct NE and that voice signals are transmitted. Follow the procedure above to call all sites on the link and vice –versa.
• Omnibus call (general call) After lifting the handset, dial "00". Check that all sites are called and that the voice signal is transmitted.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 22
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
6. SECTION C : END TO END TEST
6.1. BER STABILITY END TO END TEST (OVER THE NETWORK)
Purpose
The aim of these tests is to monitor the transmission quality on the circuits provided as per Network Plan. Test equipment
Equipment Craft Terminal SDH Analyzer Procedure
1. Create cross connection for each NE referring to Customer Network Diagram. 2. Setup the SDH Analyser and connect to the port in the originating station and with a
physical loop back at the end station. The port to be tested is 1 E1 and 1 STM1 port as a sample port.
3. Activated related performance monitoring on the equipment and ensure it should have no errors over a five or less than a minute period on the test sets.
4. Clear all unnecessary alarm on the system for all station. 5. Activate the SDH analyser of the 7 days BER test. 6. Print-out the BER test results and attach in the Appendix E.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 23
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX A: TEST SUMMARY
STATION : NE NAME:
Test No. Test Title Passed* Failed* Comment
SECTION A : STANDALONE TEST
4.1 VISUAL INSTALLATION / CABLING INSPECTION
4.2 POWER SUPPLY CHECK /POWER ON
4.3 NETWORK ELEMENT TEST SET-UP
4.4 OPTICAL PORT LOCAL TESTS
4.5 EPS PROTECTION OF THE HO MATRIX (MX160)
4.6 EPS PROTECTION OF THE LO MATRIX (LAX20)
4.7 EPS MATRIX ON 1662 OED MATRIX
4.8 FLC REDUNDANCY CHECK
4.9 PROTECTION OF THE PSF BOARD (IF APPLICABLE)
4.10 CLOCK REFERENCE AND ACCURACY TEST
4.10 MSP PROTECTION FUNCTIONALITY
4.12 BER TEST (OPTICAL/ELECTRICAL-STM-1,4,16,64)
SECTION B : SEGMENT TEST
5.1 Rx OPTICAL LINE PORT
5.2 ENGINEERING ORDER WIRE (EOW)
SECTION C : END TO END TEST
6.1 BER STABILITY END TO END TEST
Note: If a test failed, a Customer Incident Report has to be issued and its number must be filled in the « Customer Incident Report Number » column. A customer incident report may also be established for a passed test if there are some comments to be made. Alcatel Tester CUSTOMER Representative Name: Name: Signature: Signature: Date: PASS FAIL Date: PASS FAIL
Note *: enter a cross in the appropriate column.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 24
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX B: TEST INSTRUMENTS
STATION : NE NAME:
Equipment Option Supplier Serial Number Cal Due Date
STM-1/4/16 Analyzer Variable Optical
attenuators
Optical power meter
Multimeter
Alcatel Tester CUSTOMER Representative Name: Name: Signature: Signature: Date: PASS FAIL Date: PASS FAIL
Note *: enter a cross in the appropriate column.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 25
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX C: MEASUREMENT SHEETS
STATION : NE NAME:
1678MCC ACCEPTANCE TEST FOR CUSTOMER PROJECT
CUSTOMER Representative ........................................................ Signature ............................................................................... Date ..........................
ALCATEL Representative ........................................................ Signature ............................................................................... Date ..........................
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 26
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX C.1: VISUAL INSTALLATION / CABLING INSPECTION
STATION : NE NAME:
Item Pass
*
Fail
*
N/A
*
Comments
Row / Rack / Subrack and Grounding
- Rack and Subrack Grounding - DDF subrack and DDF grounding - Electrical (E1/E3/E4) port Grounding
Equipment installation compliance
- Power Cable (main and protection) - Electrical cable interface between NE to DDF
- Optical cable interface between NE to OTB/client
- HKU cable interface (optional) - DCN cable connection (optional)
Optical and electrical connections
Visual inspection for damage / back-plane
connectors / card connectors
Seismic bracing (if applicable)
Fiber labeling
Alcatel Tester CUSTOMER Representative Name: Name: Signature: Signature: Date: PASS FAIL Date: PASS FAIL
Note *: enter a cross in the appropriate column.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 27
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX C.2: POWER SUPPLY CHECK /POWER ON
STATION : NE NAME:
Item Pass* Fail* N/A* Comments
Voltage Measurement
A -48V NGTRU
connections B -48V
Voltage Measurement
Slot 24 PSF connections
Slot 25
Power Supply Cabling
- Cabling arrangement and type (2 power cable main and protection) between NGTRU and DCPDB and between DCPDB and Rectifier
Check
……..Amp
Alcatel Tester CUSTOMER Representative Name: Name: Signature: Signature: Date: PASS FAIL Date: PASS FAIL
Note *: enter a cross in the appropriate column.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 28
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX C.3: NETWORK ELEMENT TEST SET-UP
STATION : NE NAME:
Item Pass* Fail* N/A* Comments
Supervision
Software version: Release :
…………………………………
Hardware configuration of the equipment
Equipment configuration
Local Confguration
Sys Id : ___________________________
___________________________
Alcatel Tester CUSTOMER Representative Name: Name: Signature: Signature: Date: PASS FAIL Date: PASS FAIL
Note *: enter a cross in the appropriate column.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 29
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX C.3: NETWORK ELEMENT TEST SET-UP (INVENTORY)
STATION : NE NAME:
1678MCC MAIN EQUIPMENT CONFIGURATION
SLOT NO: DESCRIPTION SERIAL
NUMBER/QUANTITY SLOT NO: DESCRIPTION SERIAL NUMBER/QUANTITY
1 FLCSERV 23 FAN 10 MX 24 PSF 11 MX 25 PSF
LAX20 26 FAN LAX20
20 FLCCONGI 21 BUSTERM 22 BUSTERM
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 30
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX C.3: NETWORK ELEMENT TEST SET-UP (INVENTORY)
STATION : NE NAME:
1678MCC MAIN EQUIPMENT CONFIGURATION (Continue)
SLOT NO: DESCRIPTION SERIAL
NUMBER/QUANTITY SLOT NO: DESCRIPTION SERIAL NUMBER/QUANTITY
Alcatel Tester CUSTOMER Representative Name: Name: Signature: Signature: Date: PASS FAIL Date: PASS FAIL
Note *: enter a cross in the appropriate column.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 31
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX C.4: OPTICAL PORT LOCAL TESTS
STATION : NE NAME:
SLOT(PORT) DESCRIPTION/TYPE Safety OK/KO TX
(dBm)
RX Sensitivity
(dBm) PASS* FAIL* N/A* COMMENTS
Alcatel Tester CUSTOMER Representative Name: Name: Signature: Signature: Date: PASS FAIL Date: PASS FAIL
Note *: enter a cross in the appropriate column.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 32
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX C.5: EPS PROTECTION OF THE HO MATRIX (MX160) BOARD
STATION : NE NAME:
Item Pass
*
Fail
*
N/A
*
Comments
Press reset button on protected HOMATRIX
Remove protected HOMATRIX
Replace protected HOMATRIX
Press reset button on protecting HOMATRIX
Remove protected HOMATRIX
Replace protected HOMATRIX
Alcatel Tester CUSTOMER Representative Name: Name: Signature: Signature: Date: PASS FAIL Date: PASS FAIL
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 33
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX C.8: FLC REDUNDANCY CHECK
STATION : NE NAME:
Item Pass
*
Fail
*
N/A
*
Comments
Software switch to slot 1
Software switch to slot 20
Alcatel Tester CUSTOMER Representative Name: Name: Signature: Signature: Date: PASS FAIL Date: PASS FAIL
Note *: enter a cross in the appropriate column.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX C.9: PROTECTION OF THE PSF BOARD (IF APPLICABLE)
STATION : NE NAME:
Item Pass
*
Fail
*
N/A
*
Comments
Switch off Battery A breaker
Switch on Battery A breaker
Switch off Battery B breaker
Switch on Battery B breaker
Alcatel Tester CUSTOMER Representative Name: Name: Signature: Signature: Date: PASS FAIL Date: PASS FAIL
Note *: enter a cross in the appropriate column.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 35
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX C.10: CLOCK REFERENCE TEST AND INTERNAL CLOCK ACCURACY
STATION : NE NAME:
Description Measurement(MHz)
Pass
*
Fail
* Comments/CIR
External clock out ADDITIONAL COMMENTS Free running frequency 2.048MHz ± 4.6 p.p.m as reported in ITU-T Standard G703. Alcatel Tester CUSTOMER Representative Name: Name: Signature: Signature: Date: PASS FAIL Date: PASS FAIL
Note *: enter a cross in the appropriate column.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 36
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX C.11: MSP PROTECTION FUNCTIONALITY.
STATION : NE NAME:
Slot (Port) Description(Type) Error Count Pass Fail Comment/ CIR
Alcatel Tester CUSTOMER Representative Name: Name: Signature: Signature: Date: PASS FAIL Date: PASS FAIL
Note *: enter a cross in the appropriate column.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 37
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX C.12: LOCAL BER TEST (OPTICAL/ELECTRICAL- E1, STM-1,4,16,64)
STATION : NE NAME:
PORT (E1, STM-1, 4, 16,64)
SLOT /PORT NUMBER PASS* FAIL* N/A Compliant* BER 24Hrs REMARK
Attached BER Results Alcatel Tester CUSTOMER Representative Name: Name: Signature: Signature: Date: PASS FAIL Date: PASS FAIL
Note *: enter a cross in the appropriate column.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 38
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX C.13: Rx OPTICAL LINE PORT TESTS
STATION : NE NAME:
SLOT(PORT) DESCRIPTION/TYPE Rx (dBm) PASS* FAIL* N/A* COMMENTS
Alcatel Tester CUSTOMER Representative Name: Name: Signature: Signature: Date: PASS FAIL Date: PASS FAIL
Note *: enter a cross in the appropriate column.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 39
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX C:14 SERVICE CHANNEL TEST (EOW)
STATION NAME STATION NUMBER
PASS*
FAIL * Comments*/CIR
ADDITIONAL COMMENTS: Alcatel Tester CUSTOMER Representative Name: Name: Signature: Signature: Date: PASS FAIL Date: PASS FAIL
Note *: enter a cross in the appropriate column.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 40
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX C.15: BER STABILITY TEST OVER THE NETWORK
BER Link description: PASS* FAIL* BER Non
Compliant*
ADDITIONAL COMMENTS: Alcatel Tester CUSTOMER Representative Name: Name: Signature: Signature: Date: PASS FAIL Date: PASS FAIL
Note *: enter a cross in the appropriate column.
OPTICAL NETWORK DIVISION
Page 1678MCC__ACCEPTANCE_TEST_ED4 41
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
APPENDIX D : TECHNICAL DATA [ OPTICAL CHARACTERISTIC]
Mean TX Power (dBm)
Main Rx Power (dBm) CUSTOMERtal
Signal Application
Code Wavelength
(nm) Max Min Max(ovld) Min(stvty)
S-1.1 1261 - 1360 -8 -15 -8 -28 L-1.1 1280 - 1335 0 -5 -10 -34 STM1 L-1.2 1480 - 1580 0 -5 -10 -34
S-4.1 1274-1356 -8 -15 -8 -28 L-4.1 1280-1335 +2 -3 -8 -28 L-4.2 1480-1580 +2 -3 -8 -28
STM4
L-4.2JE 1530-1560 +2 -3 -8 -32
I-16.1 1266-1360 -3 -10 -3 -18 S-16.1 1270-1360 0 -5 0 -18 L-16.1 1280-1335 +2 -2 -8 -27 L-16.2 1500-1580 +2 -2 -8 -28
L-16.2JE2 1550-1560 +2 -2 -9 -29 L-16.2JE2 6400ps/nm +2 -3 -10 -23
STM16
L-16.2JE2 12800ps/nm +2 -3 -10 -23
I-64-1 1290-1330 -1 -6 -1 -11 S-64.2b 1530-1565 +2 -1 -1 -14 L-64.2b 1530-1565 +12 +10 -1 -14
L-64.2CF Colored +6.5 +2 -8 -20 V-64.2 1550.12 +6.5 +2 -13.5 -33
STM64
U-64.2 1550.12 +12 +10 -13 -34
Booster L-1.1 1530-1565 +12 +10 4 -6
62.5 υm 770-860 N.A -9.5 N.A -17 1000 Base SX Gbe 50 υm 770-860 N.A -9.5 N.A -17
62.5 υm 1270-1355 -3 -11.5 N.A -19 50 υm 1270-1355 -3 -11.5 N.A -19 1000 Base LX
Gbe 10 υm 1270-1355 -3 -11.5 N.A -19
Reference: Alcatel Tech. H.book 1678MCC Rel. 3.1A (3AG24163ABAA – Ed.02)