1. What are the main divisions (components) of power system? Or What is Electrical power (supply) system? The flow (A conveyance) of electrical power from generating station to the customer premises is called an electrical power system and it is the system that deals with (concerns) business of i) Generation, ii) Transmission, iii) Distribution, iv) Utilization, v) Protection and vi) Conservation of electrical energy 2.What are the advantages of interconnected power system? i) Less no. of generators are required as a reserve for operation at peak loads. Hence the reserve capacity of the generating station gets reduced. ii) Less no. of generators which are running without load are required for meeting the sudden unexpected increase in load. iii) It allows the use of most economical sources of power depending on time. 3. What are the problems of interconnection? i) It increase the amount of current, which flows when a short circuit occurs on a system and thereby, requires the installation of circuit breakers which are able to interrupt a larger current. ii) Synchronism must be maintained between of all the interconnected systems . 4.Define single (one) line diagram. A single (one) line diagram is simplified graphical (or) diagrammatic representation of power system by omiting the completed circuit through the neutral and by indicating the
Transcript
Page 1: 2 unit

1. What are the main divisions (components) of power system? Or What is Electrical power (supply) system?The flow (A conveyance) of electrical power from generating station to the customer premises is called an electrical power system and it is the system that deals with (concerns) business of i) Generation, ii) Transmission, iii) Distribution, iv) Utilization, v) Protection and vi) Conservation of electrical energy2.What are the advantages of interconnected power system? i) Less no. of generators are required as a reserve for operation at peak loads. Hence the reserve capacity of the generating station gets reduced. ii) Less no. of generators which are running without load are required for meeting the sudden unexpected increase in load. iii) It allows the use of most economical sources of power depending on time.

3. What are the problems of interconnection? i) It increase the amount of current, which flows when a short circuit occurs on a system and thereby, requires the installation of circuit breakers which are able to interrupt a larger current. ii) Synchronism must be maintained between of all the interconnected systems .

4.Define single (one) line diagram.A single (one) line diagram is simplified graphical (or) diagrammatic representation of power system by omiting the completed circuit through the neutral and by indicating the components of the power system by standard symbols rather than by their equivalent circuits.single line diagram is concise way of communicating the basic arrangement of power system components. single line diagrams (SLDs) use a single line to represent all the three phases. They show relative electrical connections of power system components (generators,tansformers,transmission & distribution lines, loads,circuit breakers,etc.,) used in assembling the power system

What is power system analysis?

Page 2: 2 unit

4) What are the goals (objectives) of power system? Power system should be operated with the goals of achieving i) Highest reliability standards, ii) Lowest operating cost, & iii) Minimum environmental impacts.

Effect of Accelerating Factor? The Accelerating factor which is probably used to reduce the number of iteration and by multiplying with the acceleration factor the approximation of the result which is neccessary to obtain can be attained very easily. The value of the acceleration factor is commanly alpha =1.6

5.What is meant by impedance diagram.The equivalent circuit of all the components of the power system are drawn and they areinterconnected is called impedance diagram.

6.What is meant by reactance diagram.Omitting all static loads ,all resistance. The magnetizing components of each transformer andthe capacitance of the transmission line are reduced from the impedance diagram is calledreactance diagram.

7.Define per unit value.Per unit of any quantity is defined as the ratio of the quantity ti its base value is expressed as adecimal.

8. Need for per unit valuethe per unit impedance referred to either side of a single phase transformer is the same.The chance of confussion b/n line and phase quantities in a three phase balanced system isgreatly reduced.The manufacturers usually produce the impedance values in per unit.

Page 3: 2 unit

9.Define base current.Ratio of base MVA to base KV

10.What is the need for short circuit study.To determine the current interrupting capacity of the circuit breakers so that the faultedequipments can be isolated.To establish the relay requirements and settings to detect the fault and cause the circuit breakerto operate when the current flowing through it exceeds the max. value.

11. Define stability study.Stability studies are performed in order to ensure that the system remains stablefollowing a severe fault or disturbance.

12. What are the eliments of y bus matrix.short circuit driving point adm. Short circuit transfer admittance.

13. What are the eliments if Z bus matrix.Open circuit driving point impedance, open circuit transfer impedances.

14.What are the methods to determine the Ybus$Z bus matrices.Primitive n/w, n/w grafh theory , incidence matrix

15.What is primitive n/wPrimitive network is a set of unconnected elements which provides informationregardin.Primitive n/w is a set of unconnected eliments which provides informationregaurding the characteristics of individual eliments only.

Page 4: 2 unit

16.what is meant gy grafh of a n.w.Agrafh shows the geometrical interconnection of the elements of a n/w.

17. Define sub graph?Asub graph is any subset of elements of a graph.

18 What is meant by path of a n/w?Apath is a subgraph of connected elements with not more than two elementsconnected to any one nide.

19.What is meant by connected oriented graph?Agraph is connected if and only if there is a path b/n every pairs of nodes.If eachelement of the connected graph is assigned a direction it is called oriented graph.

20.What are the properties of a graph.Tree is a sub graph connecting all the nodes of the oriented graph.Tree is a connected subgraph.

21.Define basic cutest?Acutset is the minimum set of elements in the graph, which when removed, divide aconnected graph inti two connected subgraph..

22. What are the quantities whose base values are

Page 5: 2 unit

required to represent the power systemby reactance diagram.The base values of voltage, current, pwer and impedance are required to represent thepower system by reactance diagram. Selection of base valuesfor any two of themdetermines the base values of the remaining two.

23.What is the need for base values?The components of power system may operate at different voltage and power levels. Itwill be convenient for analysis of power system if the voltage, power, current ratings ofthe components of the power system is expressed with referance to a common valuecalled base value.

24.What is impedance and reactance diagram?The impedance diagram is the equivalent circuit of power system in which the variouscomponents of power system are represented by their approximate equivalent circuits.The impedance diagram is used for load flow studies.The reactance diagram is the simplified equivalent circuit of the power system in whichthe various components are represented by their reactance. The reactance ddiagram canbe obtained from impedance diagram if all the resistive components are neglected.

25. What are the approximations made in impedance diagram?The neutral reactances are neglected.The shunt branches in equivalent circuit of induction motor are neglected.

26. What are the approximations made in reactance

Page 6: 2 unit

diagram?The neutral reactances are neglected.The resistances are neglected.All static loads and induction motors are neglected.

27. What is a bus?The meeting point of various components in a power system is called a bus. The busis a conductor made of copper having negligible resistance. The buses are considered as apoints of constant voltage in a system.

28. What is bus admittance matrix?The matrix consisting of the self and mutual admittances of the network of a powersystem is called bus admittance matrix.

29. Name the diagonal and off diagonal elements of bus admittance matrix.The diagonal elements of bus admittance matrix are called self admittances of thebuses and off diagonal elements are called mutual admittances of the buses.

30. What is bus imbedance matrix?The matrix consisting of driving point impedances and transfer impedances of thenetwork of a power system is called bus impedance matrix.

Page 7: 2 unit

31. Name the diagonal elements and off diagonal elements of bus impedance matrix.The diagonal elements of bus impedance matrix are called driving point impedancesof the buses and off diagonal elements of bus impedance matrix are called transferimpedances of the buses.

32.What are the methods available for forming bus impedance matrix.1. Form the bus impedance matrix and then take its inverse to get bus impedancematrix.2. Directly form the bus impedance matrix from the reactance diagram. Thismethod utilizes the techniques of modifications of existing bus impedancematrix due to addition of new bus.

32. Write the four ways of adding an impedance to an existing system so as to modifybus impedance matrix.1. Adding a branch of impedanceZb from a new bus p to the referance bus.2. Adding a branch of impedance Zb from a new busp to an existing bus.3. Adding a branch of impedance Zb from an existing busq to the referancebus.4. Adding a branch of impedance Zb between two existing buses h and q.

33.What are symmetrical components?An unbalanced system of N related vectors can be resolved into N systems ofbalanced vectors. The N sets of balanced vectors are called symmetricalcomponents.

Page 8: 2 unit

33. Write the symmetrical components of three phase system.1.positive sequence components3. negative sequence components.4. zero sequence components.

34. What are positive sequence components?The positive sequence components of a three phase unbalanced vectors consists of threevectors of equal magnatude, displased from each other by 120 in phase and having thesame phase sequence as the original vectors.

35. What are negative sequence components?The negative sequence components of a three phase unbalanced vectors consists of threevectors of equal magnitude displaced from each other by 120 degree in phase and havingthe phase sequence opposite to that of the original vectors.

36.What are zero sequence components?The zero sequence components of a three phase unbalanced vectors consists of 3 vectorsof equal magnitude and with zero phase displacement from each other.

36. What are sequence impedance and sequence networks?The sequence impedances are the impedances offered by the devices for the likesequrnce component of the current.The single phase equivalent circuit of a power system consists of impedances to currentof any one sequence is called sequence network.

Page 9: 2 unit

37.What is meant by positive, negative and zero sequence impedance.The impedance of the circuit element for positive, negative and zero sequencecomponent currents are called positive, negative and zero sequence impedances resp.

38.What is meant by positive, negative and zero sequence reactance.The reactance diagram of a power system, when formed using positive, negative andzero sequence reactances are called positive, negative and zero sequence reactancediagram resp.

39.What is load flow or power flow study?The study of various methods of solution to power system network is reffered to as loadflow study. The solution provides the voltages at various buses, power flowing in variouslines and line losses.

40.What are the information that are obtained from a load flow study.The information obtained from a load flow study are magnatude and phase of busvoltages,real and reactive power flowing in each line and the line losses. T he load flowsolution also gives the initial conditions of the system when the transient behaviour ofthe system to be studied.

41.What is the need for load flow study.The load flow study of a power system is essential to

Page 10: 2 unit

decide the best operation existingsystem and for planning the future expansion of the system. It is also essential fordesigning the power system.

42. What are the quantities associated with each bus ina system?Each bus in a power system is associated with four quantities and they are real power,reactive power, magnitude of voltage, and phase angle of voltage.

43. What are the different types of buses.Load bus,generator bus,slack bus.44.Define voltage controlled bus?A bus is called voltage controlled bus if the magnitude of volte\age and real power arespecified for it. In a voltage controlled bus the magnitude of the voltage is not allowed tochange.

45. What is PQ bus?A bus is called PQ bus when real and reactive components of power are specified for thebus. In a load bus the voltage is allowed to vary within permissible limits.

46. What is swing bus?Abus is called swing bus when the magnitude and phase of the bus voltage are specifiedfor it. The swing bus is the referance bus for load flow solution and it is required foraccounting line losses. Usually one of the generator bus is selected as swing bus.

Page 11: 2 unit

47.What is the need for slack bus?The slack bus is needed to account for transmission line losses. In a power system thetotal power generated will be equal to sum of power consumed by loads and losses. In apower system only the generated power and load power are specified for buses. Theslack bus is assumed to generate the power required for losses. Since the losses areunknown the real and reactive power are not specified for slack bus.

48.What are the operating constraints imposed in the load flow studies?The operating constraints imposed in load flow studies are reactive power limits forgenerator buses and allowable change in magnitude of voltagefor load buses.

49What are the iterative methods mainly used for solution of load flow study.The Guass sedal method and Newton Raphson method are the two iterative methods.

50.Discuss the effect of acceleration factor in load flow study.The acceleration factor is a real quantity and it modify the magnitude of voltage alone.

Page 12: 2 unit

51What is meant by flat voltage start.In iterative methods of load flow solution, the initial voltages of all buses exept slack busare assumed as 1+j0 pu.This is reffered as flat voltage profile.

52.When the generator buses are treated as load bus.If the reactive power constraints of a generator bus violates the specified limits then thegenerator is treated as load bus.

53. What will be the reactive power and bus voltage whan the generator bus is treated asload bus.When the generator bus is treated as load bus, the reactive power of the bus is equated tothe limit it has violated, and the previous iteration value of bus voltage is used forcalculating current iteration value.

54. What are the advantages of Guass sedal methoa?Calculations are simple and so the programming task is lesses.The memory requirement is lessUseful for small systems

55 What are the disadvantages of Guass seidal method?Requires large no. of iterations to reach convergeNot suitable for large systemsConvergence time increases with size of the system

Page 13: 2 unit

56. How approximations is performed in Newton Raphson method?In N-R method, the set of nonlinear simultaneous equations are approximated to a set oflinear simultaneous equations using tailors series expansion and the terms are limited tofirst order approximation.

57.What is Jacobian matrix? How the elements of Jacobian matrix are computed.The matrix formed from the first derivatives of load flow equations is called Jacobianmatrix.The elements of Jacobian matrix will change in every itration. In each iteration theelements of the jacobian matrix are obtained by partially differentiating the load flowequations w.r. t a unknown variable and then evaluating the first derivatives using thesolution of previous iteration

58.What are the adv. Of N-R method?The N-R method is faster, more reliable and the results are accurate.Requires less no. of iterationsSuitable for large size system

Page 14: 2 unit

59. What are the disadv. Of N-R method?The programming is more complexThe memory requirement is more

60 What is off nominal turns ratio?When the voltage or turns ratio of a transformer is not used to decide the ratio of baseKV then its voltage ratio is called off nominal turns ratio. Usually the voltage ratio ofregulating transformer will be off nominal ratios.

61 What is meant by a fault?A fault in a circuit is any failure which interferes with the normal flow of current. Thefaults are associated with abnormal change in current, voltage and frequency of thepower systwm. The faults may cause dan\mage to the equipments if it is allowed to persitfor a long time. Hence every part of the system has been protected by means of relaysand circuir breakers to sence the faults to isolate the faulty part from the healthy part inthe event of fault.

62Why fault accurs in a power system?The fault occur in a power system due to insulation failure of equipments, flashover oflines initiated by a lightning stroke, due to permanent damage to conductors and towers

Page 15: 2 unit

63. How are faults are classified?The faults are classified as shunt and series faults. The shunt faults are due to shortcircuits in conductors and the series faults are due to oped conductors.

64.List the various types of series and shunt fault?Shunt faults are,Line to ground fault line to line fault, double line to ground fault, three phase fault.Series faults are,One open conductor faultTwo open conductor fault

64 What is symmetrical and unsymmetrical fault?The fault is called symmetrical fault if the fault current is equal in all the phases. Thefault is called unsymmetrical fault if the fault current is not equal in all the phases.

65. Name any two methods of reducing short circuit current/By providing neutral reactance.By introducing a large value of shunt reactance between buses.

Page 16: 2 unit

66. What is meant by fault calculations/The fault condition of a power system can be dived into subtransient, transient and steadystate periods. The currents in the various parts of the system and in the fault are differentin these periods. The estimation of these currents for various types of faults at variouslocations in the system are commenly reffered as fault calculations.

67.Define stability?The stability of a system is defined as the ability of power system to return to stableoperation when it is subjected to a disturbance.

68. Define steady state stabilityThe stady statenstability is defined as the ability of a system to remain stable for smalldisturbance.

69. Define transient stability?The transient stabilitymis defined as the abilitymof a system to remain stable for largedisturbance.

Page 17: 2 unit

70What is steady state state stability limit?The steady state stability limit is the max. power that can be transferred by a machine toareceving system without loss of synchronism.71 Define swing curve? What is the use ofswing curve.The swing curve is the plot between the power angle and time. It is usually plotted for atransient state to stydy the nature of variation in angle for a sudden large disturbance.

71.Define power angle/The power angle is defined as the angular displacement of the rotor from synchronouslyrotating referance frame.

72Define critical clearing time and critiacal clearing angleThe critical clearing angle is the max. allowable change in the power angle before

Page 18: 2 unit

clearing the fault, without loss of synchronism.The critical clearing time can be defined as thw max. time delay that can be allowed toclear a fault without loss of synchronism.

73.Define equal area criterion?The equal area criterion for stability states that the system is stable if the area under pvsangle curve reduces to zero at some value of angle.

74.What is transient state stability limit?The transient state stability limit is the max. power that can be transmitted by a machineto a receiving system without loss of synchronism.In steady state the power transferredby synchronous machine is always less than the steady state stability limit.

75.what is transient stability limit ?The transient stability limit is the max power that can be transmitted by a machine to afault or a receiving system during a transient state

Page 19: 2 unit

without loss of synchronism.Thetransient stability limit is always less than the steady state stability limit.

1. What are the main divisions of power system?The generating system,transmission system,and distribution system

2. What are the adv. Of interconnected power system?1.less no. of generators are required as areserve for operation at peak loads.Hence thereserve capacity of the generating station gets reduced.2.less no. of generators which are running without load are required for meeting the suddenunexpected increase in load.3. it allows the use of most economical sources of power depending on time.

3.What are the problems of interconnection?1.it increase the amount of current which flows when a short circuit occurs on a system andthereby requires the installation of breakers which are able to interrupt a larger current‘2. synchronism must be maintained between of all the interconnected systems .

4.Define one line diagram.A simplified diagram by omiting the completed circuit through the neutral and by indicatingthe components of the power system by standard symbols rather than by their equivalent

Page 20: 2 unit

5.What is meant by impedance diagram.The equivalent circuit of all the components of the power system are drawn and they areinterconnected is called impedance diagram.

6.What is meant by reactance diagram.Omitting all static loads ,all resistance. The magnetizing components of each transformer andthe capacitance of the transmission line are reduced from the impedance diagram is calledreactance diagram.

7.Define per unit value.Per unit of any quantity is defined as the ratio of the quantity ti its base value is expressed as adecimal.

8. Need for per unit value1.the per unit impedance referred to either side of a single phase transformer is the same.2.The chance of confusion b/n line and phase quantities in a three phase balanced system isGreatly reduced.3. The manufacturers usually produce the impedance values in per unit.

Page 21: 2 unit

9.Define base current.Ratio of base MVA to base KV

10.What is the need for short circuit study.To determine the current interrupting capacity of the circuit breakers so that the faultedEquipments can be isolated.To establish the relay requirements and settings to detect the fault and cause the circuit breakerTo operate when the current flowing through it exceeds the max. Value.

11. Define stability study.Stability studies are performed in order to ensure that the system remains stableFollowing a severe fault or disturbance.

12. What are the elements of y bus matrix.Short circuit driving point admittance..Short circuit transfer admittance.

13. What are the elements of Z bus matrix.Open circuit driving point impedance, open circuit transfer impedances.14. What are the methods to determine the Ybus andZ bus matrices.Primitive n/w, n/w graph theory , incidence matrix

Page 22: 2 unit

15. What is primitive n/wPrimitive networkis a set of unconnected elements which provides informationRegarding the characteristics of individual elements only.

16.what is meant grafh of a network.Graph shows the geometrical interconnection of the elements of a n/w.

17. Define sub graph?A sub graph is any subset of elements of a graph.

18 What is meant by path of a n/w?Path is a sub graph of connected elements with not more than two elementsConnected to any one side.

19.What is meant by connected oriented graph?A graph is connected if and only if there is a path b/n every pairs of nodes. If eachElement of the connected graph is assigned a direction it is called oriented graph.

20.What are the properties of a graph.Tree is a sub graph connecting all the nodes of the oriented graph.Tree is a connected sub graph.

Page 23: 2 unit

21. Define basic cutest?Acutest is the minimum set of elements in the graph, which when removed, divide aConnected graph into two connected sub graph..

22. What are the quantities whose base values are required to represent the power systemBy reactance diagram.The base values of voltage, current, power and impedance are required to represent thePower system by reactance diagram. Selection of base values for any two of themDetermines the base values of the remaining two.

23. What is the need for base values?The components of power system may operate at different voltage and power levels. Itwill be convenient for analysis of power system if the voltage, power, current ratings ofthe components of the power system is expressed with reference to a common valueCalled base value.

24. What is impedance and reactance diagram?The impedance diagram is the equivalent circuit of power system in which the variousComponents of power system are represented by their approximate equivalent circuits.The impedance diagram is used for load flow studies.The reactance diagram is the simplified equivalent circuit of the power system in whichThe various components are represented by their reactance. The reactance diagram canBe obtained from impedance diagram if all the resistive components are neglected.

Page 24: 2 unit

25. What are the approximations made in impedance diagram?The neutral reactances are neglected.The shunt branches in equivalent circuit of induction motor are neglected.

26. What are the approximations made in reactance diagram?The neutral reactances are neglected.The resistances are neglected.All static loads and induction motors are neglected.

27. What is a bus?The meeting point of various components in a power system is called a bus. The busis a conductor made of copper having negligible resistance. The buses are considered as aPoints of constant voltage in a system.

28. What is bus admittanceThe matrix consisting of the self and mutual admittances of the network of a powerSystem is called bus admittance matrix.

29. Name the diagonal and off diagonal elements of bus admittance matrix.The diagonal elements of bus admittance matrix are called self admittances of theBuses and off diagonal elements are called mutual admittances of the buses.

Page 25: 2 unit

30. What is bus impedance matrix?The matrix consisting of driving point impedances and transfer impedances of theNetwork of a power system is called bus impedance matrix.

31. Name the diagonal elements and off diagonal elements of bus impedance matrix.The diagonal elements of bus impedance matrix are called driving point impedancesOf the buses and off diagonal elements of bus impedance matrix are called transferImpedances of the buses.

32. What are the methods available for forming bus impedance matrix.1. Form the bus impedance matrix and then take its inverse to get bus impedanceMatrix.2. Directly form the bus impedance matrix from the reactance diagram. ThisMethod utilizes the techniques of modifications of existing bus impedanceMatrix due to addition of new bus.

32. Write the four ways of adding an impedance to an existing system so as to modifybus impedance matrix.1. Adding a branch of impedances from a new bus p to the reference bus.2. Adding a branch of impedance Zb from a new busp to an existing bus.3. Adding a branch of impedance Zb from an existing busq to the reference

Page 26: 2 unit

Bus.4. Adding a branch of impedance Zb between two existing buses h and q.

33.What are symmetrical components?An unbalanced system of N related vectors can be resolved into N systems ofBalanced vectors. The N sets of balanced vectors are called symmetricalComponents.

33. Write the symmetrical components of three phase system.1. Positive sequence components3. Negative sequence components.4. Zero sequence components.

34. What are positive sequence components?The positive sequence components of a three phase unbalanced vectors consists of threeVectors of equal magnitude, displaced from each other by 120 in phase and having theSame phase sequence as the original vectors.

35. What are negative sequence components?The negative sequence components of a three phase unbalanced vectors consists of threeVectors of equal magnitude displaced from each other by 120 degree in phase and havingThe phase sequence opposite to that of the original vectors.

36.What are zero sequence components?The zero sequence components of a three phase unbalanced vectors consists of 3 vectors

Page 27: 2 unit

Of equal magnitude and with zero phase displacement from each other.

36. What are sequence impedance and sequence networks?The sequence impedances are the impedances offered by the devices for the likeSequence component of the current.The single phase equivalent circuit of a power system consists of impedances to currentof any one sequence is called sequence network.

37. What is meant by positive, negative and zero sequence impedance.The impedance of the circuit element for positive, negative and zero sequenceComponent currents are called positive, negative and zero sequence impedances resp.

38.What is meant by positive, negative and zero sequence reactance.The reactance diagram of a power system, when formed using positive, negative andZero sequence reactance’s are called positive, negative and zero sequence reactanceDiagram resp.

39. What is load flow or power flow study?The study of various methods of solution to power system network is referred to as loadFlow study. The solution provides the voltages at various buses, power flowing in variousLines and line losses.

40. What are the information that are obtained

Page 28: 2 unit

from a load flow study.The information obtained from a load flow study are magnitude and phase of busVoltages, real and reactive power flowing in each line and the line losses. T he load flowSolution also gives the initial conditions of the system when the transient behavior ofThe system to be studied.

41. What is the need for load flow study.The load flow study of a power system is essential to decide the best operation existingSystem and for planning the future expansion of the system. It is also essential forDesigning the power system.

42. What are the quantities associated with each bus ina system?Each bus in a power system is associated with four reactive power, magnitude of voltage, and phase angleof voltage.

43. What are the different types of buses.Load bus, generator bus,slack bus.

44. Define voltage controlled bus?A bus is called voltage controlled bus if the magnitude of volte\age and real power areSpecified for it. In a voltage controlled bus the magnitude of the voltage is not allowed toChange.

45. What is PQ bus?A bus is called PQ bus when real and reactive components of power are specified for the

Page 29: 2 unit

Bus. In a load bus the voltage is allowed to vary within permissible limits.

46. What is swing bus?A bus is called swing bus when the magnitude and phase of the bus voltage are specifiedFor it. The swing bus is the reference bus for load flow solution and it is required forAccounting line losses. Usually one of the generator bus is selected as swing bus.

47. What is the need for slack bus?The slack bus is needed to account for transmission line losses. In a power system theTotal power generated will be equal to sum of power consumed by loads and losses. In aPower system only the generated power and load power are specified for buses. TheSlack bus is assumed to generate the power required for losses. Since the losses areUnknown the real and reactive power are not specified for slack bus.

48. What are the operating constraints imposed in the load flow studies?The operating constraints imposed in load flow studies are reactive power limits forGenerator buses and allowable change in magnitude of voltage for load buses.

49What are the iterative methods mainly used for solution of load flow study.The Gauss sedal method and Newton Raphson method are the two iterative methods.

50. Discuss the effect of acceleration factor in load flow study.The acceleration factor is a real quantity and it modifies the magnitude of voltage alone.quantities andthey are real power,

Page 30: 2 unit

51What is meant by flat voltage flat.In iterative methods of load flow solution, the initial voltages of all buses except slack busare assumed as 1+j0 pu.This is reffered as flat voltage profile.

52. When the generator buses are treated as load bus.If the reactive power constraints of a generator bus violates the specified limits then theGenerator is treated as load bus.

53. What will be the reactive power and bus voltage whan the generator bus is treated asLoad bus.When the generator bus is treated as load bus, the reactive power of the bus is equated tothe limit it has violated, and the previous iteration value of bus voltage is used forCalculating current iteration value.

54. What are the advantages of Guass sedal method?Calculations are simple and so the programming task is lesses.The memory requirement is lessUseful for small systems

55 What are the disadvantages of Gauss seidal method?

Page 31: 2 unit

Requires large no. of iterations to reach convergeNot suitable for large systemsConvergence time increases with size of the system

56. How approximations are performed in Newton Raphson method?In N-R method, the set of nonlinear simultaneous equations are approximated to a set oflinear simultaneous equations using tailors series expansion and the terms are limited tofirst order approximation.

57.What is Jacobian matrix? How the elements of Jacobian matrix are computed.The matrix formed from the first derivatives of load flow equations is called Jacobianmatrix.The elements of Jacobian matrix will change in every iteration. In each iteration theElements of the jacobian matrix are obtained by partially differentiating the load flowEquations w.ith respect to ta unknown variable and then evaluating the first derivatives using theSolution of previous iteration

58. What are the adv. Of N-R method?The N-R method is faster, more reliable and the results are accurate.Requires less no. of iterationsSuitable for large size system

59. What are the disadv. Of N-R method?The programming is more complexThe memory requirement is more

60 What is off nominal turn’s ratio?

Page 32: 2 unit

When the voltage or turns ratio of a transformer is not used to decide the ratio of baseKV then its voltage ratio is called off nominal turns ratio. Usually the voltage ratio ofRegulating transformer will be off nominal ratios.

61 What is meant by a fault?A fault in a circuit is any failure which interferes with the normal flow of current. TheFaults are associated with abnormal change in current, voltage and frequency of thePower system. The faults may cause dan\mage to the equipments if it is allowed to persitfor a long time. Hence every part of the system has been protected by means of relaysand circuit breakers to since the faults to isolate the faulty part from the healthy part inthe event of fault.

62Why fault accurs in a power system?The fault occur in a power system due to insulation failure of equipments, flashover oflines initiated by a lightning stroke, due to permanent damage to conductors and towers

63. How are faults are classified?The faults are classified as shunt and series faults. The shunt faults are due to shortCircuits in conductors and the series faults are due to open conductors.

64.List the various types of series and shunt fault?Shunt faults are,Line to ground fault line to line fault, double line to ground fault, three phase fault.Series faults are,One open conductor faultTwo open conductor fault

Page 33: 2 unit

64 What is symmetrical and unsymmetrical fault?The fault is called symmetrical fault if the fault current is equal in all the phases. Thefault is called unsymmetrical fault if the fault current is not equal in all the phases.

65. Name any two methods of reducing short circuit currentBy providing neutral reactance.By introducing a large value of shunt reactance between buses.

66. What is meant by fault calculationsThe fault condition of a power system can be dived into sub transient, transient and steadyState periods. The currents in the various parts of the system and in the fault are differentin these periods. The estimation of these currents for various types of faults at variousLocations in the system are commonly referred as fault calculations.

67.Define stability?The stability of a system is defined as the ability of power system to return to stableoperation when it is subjected to a disturbance.

68. Define steady state stabilityThe steady state stability is defined as the ability of a system to remain stable for smallDisturbance.

Page 34: 2 unit

69. Define transient stability?The transient stability is defined as the ability of a system to remain stable for largeDisturbance.

70What is steady state state stability limit?The steady state stability limit is the max. Power that can be transferred by a machine toareceiving system without loss of synchronism.

71 Define swing curve? What is the use ofswing curve.The swing curve is the plot between the power angle and time. It is usually plotted for atransient state to study the nature of variation in angle for a sudden large disturbance.

71.Define power angleThe power angle is defined as the angular displacement of the rotor from synchronouslyRotating reference frame.

72 Define critical clearing time and critiacal clearing angleThe critical clearing angle is the max. Allowable change in the power angle beforeClearing the fault, without loss of synchronism.The critical clearing time can be defined as the max. Time delay that can be allowed toClear a fault without loss of synchronism.

Page 35: 2 unit

73.Define equal area criterion?The equal area criterion for stability states that the system is stable if the area under power vsAngle curve reduces to zero at some value of angle.

74.What is transient state stability limit?The transient stability limit is the max power that can be transmitted by a machine to aFault or a receiving system during a transient state without loss of synchronism. TheTransient stability limit is always less than the steady state stability limit.

1SELVAM COLLEGE OF TECHNOLOGY, NAMAKKAL-3DEPARTMENT OF EEEPOWER SYSTEM ANALYSISUNIT 1: INTRODUCTION1. Explain the requirements of planning the operation of a power system.Planning the operation of a power system requires load studies, fault calculations,the design of means for protecting the system against lightning and switching surges andagainst short circuits, and studies of the stability of the system.2. Define steady state operating condition.A power system is said to be in a steady state operating condition, if all themeasured(or calculated) physical quantities describing the operating condition of thesystem can be considered constant for the purpose of analysis.3. What is a disturbance and what are the two types of disturbances?If a sudden change or sequence of changes occurs in one or more of the systemparameters or one or more of its operating quantities, the system is said to haveundergone a disturbance from its steady state operating condition.The two types of disturbances in a power system are,i) Large disturbance ii) Small disturbance4. What is a small disturbance? Give example.If the power system is operating in a steady state condition and it undergoeschange, which can be properly analyzed by linearized versions of its dynamic andalgebraic equations, a small disturbance is said to have occurred.Example of small disturbance is a change in the gain of the automatic voltageregulator in the excitation system of a large generating unit.5. What is a large disturbance? Give some examples.A large disturbance is one for which the nonlinear equations describing thedynamics of the power system cannot be validly linearized for the purpose of analysis.Examples of large disturbances are transmission system faults, sudden loadchanges, loss of generating units and line switching.6. When is a power system said to be steady-state stable?The power system is steady state stable for a particular steady-state operatingcondition if, following a small disturbance, it returns to essentially the same steady state

Page 36: 2 unit

condition of operation.7. When is a power system said to be transiently stable?If the machines of the system are found to remain essentially in synchronismwithin the first second following a system fault or other large disturbance, the system isconsidered to be transiently stable.8. What is transient state of the power system?The state of the system in the first second following a system fault or largedisturbance is called the transient state of the power system.29. Give the formula to calculate base current, Ib and base impedance of a threephasesystem.The equation for base current Ib is,bbb kVkVAI3=The equation for base impedance is,bbb IkV xZ31000=Where,Ib = Line value of base current.kVAb = 3-phase base KVAkVb = line to line base kVZb = Base impedance per phase.10.Give the equation for load impedance and load admittance per phase of abalanced star connected load.Load impedance per phase, P jQVZ L−=2Load admittance per phase, 21L VP jQZY−= =Where,P = Three phase active power of star connected load in watts.Q = Three phase reactive power of star connected load in VARs.VL = Line voltage of load.11. Give the equation for load impedance and load admittance per phase of a

Page 37: 2 unit

balanced delta connected load.Load impedance per phase, P jQVZ L−=2 3Load admittance per phase, 2 31L VP jQZY−= =Where,P = Three phase active power of delta connected load in watts.Q = Three phase reactive power of delta connected load in VARs.VL = Line voltage of load.312. What is the advantage of per unit method over percent method?The advantage of per unit method over percent method is that the product of twoquantities expressed in per unit is expressed in per unit itself, but the product of twoquantities expressed in percent must be divided by 100 to obtain the result in percent.13. Define base impedance and base kilovoltamperes.The base impedance is the impedance which will have a voltage drop across itequal to the base voltage when the current flowing in the impedance is equal to the basevalue of the current.bbb kVAkV xZ( )2 1000=The base kilovoltamperes in single-phase systems is the product of base voltagein kilovolts and base current in amperes.b b b kVA = kV xI14.Define per unit value of any electrical quantity.The per unit value of any electrical quantity is defined as the ratio of the actualvalue of the quantity to its base value expressed as a decimal.Base valueActual valuePerunitvalue =15. What are the quantities whose base values are required to represent the powersystem by reactance diagram?The base value of voltage, current, power and impedance are required to representthe power system by reactance diagram. Selection of base values for any two of themdetermines the base values of the remaining two. Usually the base values of voltage andpower are chosen in kilovolt and kVA or mVA respectively. The base values of currentand impedance are calculated using the chosen bases.16. What is the need for base values?The components of various sections of power system may operate at differentvoltage and power levels. It will be convenient for analysis of power system if the

Page 38: 2 unit

voltage, power, current and impedance ratings of power system components areexpressed with reference to a common value called base value. Then all the voltages,power, current and impedance ratings of the components are expressed as a percent or perunit of the base value.17. Write the equation for converting the per unit impedance expressed in one baseto another. ì ì=b oldb newb newb oldp u new p u old MVAMVAxkVkVZ Z x,,2,,. , . ,18. List the advantages of per unit computations.(1) The per unit impedance referred to either side of a single phase transformer is thesame.(2) The per unit impedance referred to either side of a three phase transformer is thesame regardless of the three phase connections whether they are Y-Y, Δ-Δ or Δ-Y4(3) The chance of confusion between the line and phase quantities in a three phasebalanced system is greatly reduced.(4) The manufacturers usually provide the impedance values in per unit.(5) The computational effort in power system is very much reduced with the use ofper unit quantities.19. What are the factors that affect the transient stability?The transient stability is generally affected by two factors namely,(1) Type of fault (2) Location of fault.20. List the methods of improving the transient stability limit of a power system.(1) Increase of system voltage, use of AVR.(2) Use of high speed excitation systems.(3) Reduction in system transfer reactance.(4) Use of high speed reclosing breakers.

Page 39: 2 unit

21. What is meant by stability study?The procedure of determining the stability of a system upon occurrence of adisturbance followed by various switch off and switch on actions is called a stabilitystudy.22. What is meant by short circuit fault?Short circuit faults involve power conductor or conductors-to-ground or shortcircuit between conductors. These faults are characterized by increase in current and fallin voltage and frequency.23. What is a reactor?Reactor is a coil, which has high inductive reactance as compared to its resistanceand is used to limit the short circuit current during fault conditions.24. Give the equation for transforming base kV on LV side to HV side of atransformer and vice versa.LV ratingHV ratingBase kV on HV side = Base kV on LV side xHV ratingLV ratingBase kV on LV side = Base kV on HV side x25.Give the equation for base current and base impedance of a balanced three phasecircuit.LL xbasevoltage kVbase kVABasecurrent A3 ,3,φ=( )3φ2 ,baseMVAbasevoltage kVBaseimpedance= LL526. Why the line value of voltage directly used for per unit calculation in three phasesystems?The per unit value of a line-to-neutral(VLN) on the line-to-neutral voltagebase(Vb,LN) is equal to the per unit value of the line-to-line voltage(VLL) at the same pointon the line-to-line voltage base(Vb,LL) if the system is balanced.b L LL Lb L NL NVVVVi e, ,. ., =27. Why the three phase kVA directly used for per unit calculation in three phasesystems?

Page 40: 2 unit

The per unit value of a 3-phase kVA on the 3-phase kVA base is identical to theper unit value of kVA per phase on the kVA per phase base.Base kVA per phasekVA per phasephasebase kVAphase kVAi e =−−33. .,Therefore in 3 phase systems, the line value of voltage and 3 phase kVA aredirectly used for per unit calculations.Possible 16-mark questions and answers1. What is the need for system analysis in planning and operation of power system?Explain. (APR/MAY 2004)2. Explain the advantages of the p.u form of representation?3. Define the per unit value of a quantity. How will you change the base impedance fromone set of base values to another set?4. Explain the steady state and transient state with the help of a RL circuit.5. Why is Per phase analysis done in a symmetrical three-phase system.6. What are the advantages of using per unit system?7. Explain the per phase generator model with required diagrams.8. With neat diagrams, explain the transformer model used for per phase analysis.9. Discuss in detail about the modeling of transmission lines.10. Clearly explain the basic components of a power system.Reference books:R1 – Hadi saadat, “Power System Analysis”, Tata McGraw HillR2 – I J Nagarath, D P Kothari ’Modern Power system Analysis’, TMH Pub. Co. Ltd.,1994.R3 – Nagoor Kani, “Power System Analysis”\6SELVAM COLLEGE OF TECHNOLOGY, NAMAKKAL-3DEPARTMENT OF EEEPOWER SYSTEM ANALYSISUNIT 1: INTRODUCTION1.The equation for base current Ib is,bbb kVkVAI3=2.The equation for base impedance is,bbb IkV xZ31000=

Page 41: 2 unit

3.The equation for base current Ib is,bbb kVkVAI3=4.The equation for base impedance is,bbb IkV xZ31000=5.The base impedance isbbb kVAkV xZ( )2 1000=6.The base kilovolt amperes isb b b kVA = kV xI7.The equation for converting the per unit impedance expressed in one base toanother. ì ì=b oldb newb newb oldp u new p u old MVAMVAxkVkVZ Z x,,

Page 42: 2 unit

2,,. , . ,8.The equation for transforming base kV on LV side to HV side of a transformerand vice versa.LV ratingHV ratingBase kV on HV side = Base kV on LV side xHV ratingLV ratingBase kV on LV side = Base kV on HV side x79.The equation for base current and base impedance of a balanced three-phasecircuit.xbasevoltage kVLLbase kVABasecurrent A3 ,3,φ=10.3-phase kVA base is identical to the per unit value of kVA per phase on the kVAper phase base.Base kVA per phasekVA per phasephasebase kVAphase kVAi e =−−33. .,11.The line-to-line voltage base (Vb,LL) if the system is balanced.b L LL Lb L NL NVVVVi e, ,. ., =12.The per unit impedance referred to either side of a single-phase transformer isthe same.13.The per unit impedance referred to either side of a three phase transformer is thesame regardless of the three phase connections whether they are Y-Y, Δ-Δ or Δ-Y14.The chance of confusion between the line and phase quantities in a three phasebalanced system is greatly reduced.15.The manufacturers usually provide the impedance values in per unit.

Page 43: 2 unit

16.The computational effort in power system is very much reduced with the use ofper unit quantities.17. The transient stability is generally affected by two factors namely,(1) Type of fault(2) Location of fault.( )3φ2 ,baseMVAbasevoltage kVBaseimpedance= LL8SELVAM COLLEGE OF TECHNOLOGY, NAMAKKAL-3DEPARTMENT OF EEEPOWER SYSTEM ANALYSISUNIT 2:MODELLING OF VARIOUS COMPONENTSPossible 2-mark questions and answers1. Write the most important mode of operation of power system and mention themajor problems encountered with it.Symmetrical steady state is the most important mode of operation of powersystem. Three major problems are encountered in this mode of operation. They are,1) Load flow problem2) Optimal load scheduling problem3) Systems control problem2.Why power flow analysis is made?Power flow analysis is performed to calculate the magnitude and phase angle ofvoltages at the buses and also the active power and reactive voltamperes flow for thegiven terminal or bus conditions. The variables associated with each bus or node are,a. Magnitude of voltage |V|b. Phase angle of voltage δc. Active power, Pd. Reactive voltamperes, Q3. What is power flow study or load flow study?The study of various methods of solution to power system network is referred toas load study. The solution provides the voltages at various buses, power flowing inVarious lines and line losses.4. What are the information that are obtained from a load flow study?The information obtained from a load flow study are magnitude and phase anglesof bus voltages, real and reactive power flowing in each line and line losses. The loadflow solution also gives the initial conditions of the system when the transient behavior ofthe system is to be studied.5. What is the need for load flow study? (MAY/JUNE 2006)The load flow study of a power system is essential to decide the best operation ofexisting system and for planning the future expansion of the system. It is also essentialfor designing a new power system.6. What are the works involved in a load flow study? (NOV/DEC 2004)The following has to be performed for a load flow study.a. Representation of the system by single line diagram.b. Formation of impedance diagram using the information in single line diagram.c. Formulation of network equationsd. Solution of network equations.97. What are the different types of buses in a power system?The buses of a power system can be classified into three types based on the

Page 44: 2 unit

quantities being specified for the buses, which are as follows:a. Load bus or PQ bus (P and Q are specified)b. Generator bus or voltage controlled bus or PV bus (P and V are specified)c. Slack bus or swing bus or reference bus (|V| and δ are specified)8. Define voltage controlled bus(generator bus/PV bus).A bus is called voltage controlled bus if the magnitude of voltage |V| and realpower (P) are specified for it. In a voltage controlled bus, the magnitude of the voltage isnot allowed to change. Voltage controlled bus is also called as Generator bus and PV bus.9. What is PQ bus(load bus)? (APR/MAY 2005)A bus is called PQ bus or load bus when real and reactive components of powerare specified for the bus. In a load bus, the voltage is allowed to vary within permissiblelimits.10.What is swing bus(slack bus/reference bus)?A bus is called swing bus when the magnitude and phase of bus voltage arespecified for it. The swing bus is the reference bus for load flow solution and it isrequired for accounting for the line losses. Usually one of the generator bus is selected asthe swing bus.11. What is the need for slack bus? (APR/MAY 2004),(NOV/DEC 2004)The slack bus is needed to account for transmission line losses. In a powersystem, the total power generated will be equal to sum of power consumed by loads andlosses. In a power system, only the generated power and load power are specified for thebuses. The slack bus is assumed to generate the power required for losses. Since thelosses are unknown, the real and reactive power are not specified for slack bus. They areestimated through the solution of line flow equations.12. List the quantities specified and the quantities to be determined from load flowstudy for various types of buses. (MAY/JUNE 2006)The following table shows the quantities specified and the quantities to beobtained for various types of buses.Bus type QuantitiesspecifiedQuantities tobe obtainedLoad BusGeneratorBusSlack BusP,QP, |V||V|, δ|V|, δQ, δP, Q1013. Write the load flow equation of Gauss and Gauss-Seidel method.The load flow equation of Gauss method is given by,

ï ï ï ï ï ï ï ï ï ï ï ï ï

Σ≠=

Page 45: 2 unit

−−+ =nq pqKYpqVqKVpPp jQpYppKVp* 11 1The load flow equation of Gauss-Seidel method is given by,

ï ï ï ï ï ï ï ï ï ï ï ï ï

Σ= +Σ −=−−+ =nq pKYpqVqpqKYpqVqKVpPp jQpYppKVp1

Page 46: 2 unit

1* 11 1VpK+1 and VpK= (K+1) and Kth iteration voltage of bus ‘p’ respectively.VqK+1 and VqK = (K+1) and Kth iteration voltage of bus ‘q’ respectively.14. Write the load flow equation of Newton-Raphson method.The load flow equation of Newton Raphson method is given by,Σ== + + − nqPp ep eqGpq f pBpq f p fqGpq e pBpq1( ) ( )Σ=− − + = nqQp f p eqGpq f pBpq ep fqGpq epBpq1( ) ( )2 2 2V p = ep + f p15. Discuss the effect of acceleration factor in the load flow solution algorithm.(APR/MAY 2004)In load flow solution by iterative methods, the number of iterations can bereduced if the correction voltage at each bus is multiplied by some constant. Themultiplication of the constant will increase the amount of correction to bring the voltagecloser to the value it is approaching. The multipliers that accomplish this improvedconverged are called acceleration factors. An acceleration factor of 1.6 is normally usedin load flow problems.16. How will you account for voltage controlled buses in the load flow algorithm?The acceleration factor is a real quantity and it modifies the magnitude of busvoltage alone. Since in voltage controlled bus, the magnitude of bus voltage is notallowed to change, the acceleration factor is not used for voltage controlled bus.1117. Why do we go for iterative methods to solve load flow problems?The load (or power) flow equations are nonlinear algebraic equations and soexplicit solution is not possible. The solution of nonlinear equations can be obtained onlyby iterative numerical techniques.18. What do you mean by a flat voltage start?In iterative methods of load flow solution, the initial voltage of all buses exceptslack bus are assumed as 1+j0 p.u. This is referred to as flat voltage start.19.When the generator bus is treated as load bus? What will be the reactive power

Page 47: 2 unit

and bus voltage when the generator bus is treated as load bus?If the reactive power of a generator bus violates the specified limits, then thegenerator bus is treated as load bus. The reactive power of that particular bus is equatedto the limit it has violated and the previous iteration value of bus voltage is used forcalculating current iteration value.20. What are the advantages of Gauss-Seidel method?The advantages of Gauss-Seidel method are,a. Calculations are simple and so the programming task is lessb. The memory requirement is lessc. Useful for small systems.21.What are the disadvantages of Gauss-Seidel method?The disadvantages of Gauss-Seidel method are,a. Requires large number of iterations to reach convergence.b. Not suitable for large systems.c. Convergence time increases with size of the system.22.How approximation is performed in Newton-Raphson method?In Newton-Raphson method, the set of non-linear simultaneous (load flow)equations are approximated to a set of linear simultaneous equations using Taylor’s seriesexpansion and the terms are limited to first order approximation.23. What is Jacobian matrix? How the elements of Jacobian matrix are computed?The matrix formed from the derivates of load flow equations is called Jacobianmatrix and it is denoted by J.The elements of Jacobian matrix will change in every iteration. In each iteration,the elements of the Jacobian matrix are obtained by partially differentiating the load flowequations with respect o unknown variable and then evaluating the first derivates usingthe solution of previous iteration.24.What are the advantages of Newton-Raphson method?The advantages of Newton-Raphson method are,a. This load flow method is faster, more reliable and he results are accurate.b. Requires less number of iterations for convergence.c. The number of iterations are independent of the size of the system.12d. Suitable for large system.25.What are the disadvantages of Newton-Raphson method?The disadvantages of Newton-Raphson method are,a. Programming is more complex.b. The memory requirement is more.c. Computational time per iteration is higher due to larger number ofcalculations per iteration.26.Mention (any) three advantages of N-R method over G-S method?The three advantages of N-R method over G-S method are,a. The N-R method has quadratic convergence characteristics and so convergesfaster than G-S method.b. The number of iterations for convergence is independent of the system in N-Rmethod.c. In N-R method, the convergence is not affected by the choice of slack bus.27.Compare G-S method and N-R methods of load flow solutions.G-S method N-R method1. The variables are expressed inrectangular co-ordinates.2. Computation time per iteration is less.3. It has linear convergence characteristics.4. The number of iterations required forconvergence increase with size of the

Page 48: 2 unit

system.5.The choice of slack bus is critical.1. Variables are expressed in polar coordinates.2. Computation time per iteration is more3. It has quadratic convergencecharacteristics.4.The number of iterations are independentof the size of the system.5. The choice of slack bus is arbitrary.28.How the convergence of N-R method is speeded up?The convergence can be speeded up in N-R method by using Fast DecoupledLoad Flow (FDLF) algorithm. In FDLF method, the weak coupling between P-δ and Q-Vare decoupled and then the equations are further simplified using the knowledge ofpractical operating conditions of a power system.29. How the disadvantages of N-R method are overcome?The disadvantage of large memory requirement can be overcome by decouplingthe weak coupling between P-δ and Q-V (i.e., using decoupled load flow algorithm). Thedisadvantage of large computational time per iteration can be reduced by simplifying thedecoupled load flow equations. The simplifications are based on the practical operatingconditions of a power system.30. Write the equation for power flow in the transmission line.The equation for power low in the transmission line (say p-q) at bus ‘p’ is given by,Spq = Ppq-jQpq= Ep* ipq13= Ep*[Ep-Eq]Ypq + Ep*Ep.(Ypq’/2)Sqp = Pqp-jQqp= Eq* iqp= Eq*[Eq-Ep]Ypq + Eq*Eq.(Ypq’/2)31.Define primitive network.Primitive network is a set of unconnected elements which provides informationregarding the characteristics of individual elements only. The performance equations ofprimitive network are given below.V + E = ZI (In Impedance form)I + J = YV (In Admittance form)where V and I are the element voltage and current vectors respectively.J and E are source vectors.Z and Y are the primitive Impedance and Admittance matrices respectively.32. What is a bus?The meeting point of various components in a power system is called a bus. Thebus is a conductor made of copper (or) aluminium having negligible resistance. The busesare considered as points of constant voltage in a power system.33.Explain bus incidence matrix.For the specific system, we can obtain the following relation (relation betweenelement voltage and bus voltage).V = A VBUSwhere A is the bus incidence matrix, which is a rectangular and singular matrix. Itselements are found as per the following rules.

Page 49: 2 unit

aik = 1, if ith element is incident to and oriented away from the kth node (bus).= -1, if ith element is incident to but oriented towards the kth node.= 0, if ith element is not incident to the kth node.34. What is bus admittance matrix? (MAY/JUNE 2006)The matrix consisting of the self and mutual admittance of the power systemnetwork is called bus admittance matrix. It is given by the admittance matrix Y in thenode basis matrix equation of a power system and it is denoted as Ybus. Bus admittancematrix is a symmetrical matrix.35. Write the equation for the bus admittance matrix.The equation for bus admittance matrix is,YbusV = IwhereYbus = Bus admittance matrix of order (n x n )V = Bus voltage matrix of order (n x1)I = Current source matrix of order (n x1)n = Number of independent buses in the system1436. Give the matrix notation of YbusV = I ï ï ï ï ï ï ï= ï ï ï ï ï ï ï ï ï ï ï ï ï ïn n n nn n nnnnnIIIIVVVVY Y Y YY Y Y YY Y Y YY Y Y Y.

Page 50: 2 unit

.

.

.

.

.

. . .

.

.

.

.

.

.

.

.

.

.

.

.

. . .

. . .

. . .3322113211 2 331 32 33 321 22 23 211 12 13 137. Give the equation to find the kth bus voltage.The equation to find the kth bus voltage is,[ ] k k k k nk nn V Δ I +Δ I +Δ I + + Δ IΔ= ...11 11 2 22 3 33Σ=ΔΔ=njk jk jj V I11where Δ = Determinant of Ybus matrix.Ijj = Sum of the currents injecting current to node j.Δjk = Cofactor of the element Yjk of bus admittance matrix.38.Mention the advantages of bus admittance matrix, Ybus.i) Data preparation is simple.ii) Formation and modification is easy.

Page 51: 2 unit

iii) Since the bus admittance matrix is sparse matrix(i.e., most of its elements are zero),the computer memory requirements are less.Possible 16-mark questions and answers1.With the help of a neat flow chart, explain the Newton-Raphson method of load flowsolution when the system contains voltage controlled busses in addition to swing bus andload bus.(APR/MAY 2004)2.Compare Gauss-Seidel method and Newton-Raphson method of load flow studies(NOV/DEC 2004)3.Explain clearly with detailed flowchart, the computational procedure for load flowsolution using N-R method when the system contains all types of buses.(NOV/DEC 2004)4.Explain the step by step computational procedure for the Newton-Raphson method ofload flow studies.(APR/MAY 2005)5. Explain bus classification in power flow analysis with their known and unknownquantities.15(APR/MAY 2005)6. Derive the static load flow equations of n-Bus system.(APR/MAY 2005)7. Explain the step by step computational procedure for the Gauss-Seidel method of loadflow studies (MAY/JUNE 2006)8. Derive the basic equations for the load flow study using Gauss-Seidel method. Withrespect to this method, explain the following:a. Acceleration factor.b. Handling of PV buses.9. Draw the representation schemes fora. Phase shifting transformerb. Tap changing transformer10. Draw the mathematical model of phase shifting transformer to be used in power flowanalysis.11. Give the advantages and disadvantages of Gauss-Seidel method and Newton-Raphsonmethod of load flow analysis.12. Write the equations to calculate Slack bus power, Transmission losses and Lineflows.Reference books:R1 – Hadi saadat, “Power System Analysis”, Tata McGraw HillR2 – I J Nagarath , D P Kothari ’Modern Power system Analysis’, TMH Pub. Co. Ltd.,1994.R3 – Nagoor Kani, “Power System Analysis”16SELVAM COLLEGE OF TECHNOLOGY, NAMAKKAL-3DEPARTMENT OF EEEPOWER SYSTEM ANALYSISUNIT 3:POWER FLOW ANALYSISPossible 2 mark questions:1. What is the need for short circuit studies or fault analysis?The short circuit studies are essential in order to design or develop the protectiveschemes for various parts of the system. The protective scheme consists of current andvoltage sensing devices, protective relays and circuit breakers. The selection of thesedevices mainly depends on various currents that may flow in the fault conditions.2. What is the reason for transients during short circuits?The faults or short circuits are associated with sudden change in currents. Most of

Page 52: 2 unit

the components of the power system have inductive property which opposes any suddenchange in currents, so the faults are associated with transients.3. What is meant by a fault?A fault in a circuit is any failure which interrupts with the normal flow of current.The faults are associated with abnormal change in current, voltage and frequency of thepower system. The faults may cause damage to the equipments, if it is allowed to persistfor a long time. Hence every part of a system has been protected by means of relays andcircuit breakers to sense the faults and to isolate the faulty part from the healthy part ofthe network in the event of fault4. Why faults occur in a power system?Faults occur in a power system due to insulation failure of equipments, flashoverof lines initiated by a lightening stroke, permanent damage to conductors and towers oraccidental faulty operations.5. How are the faults classified?In one method, the faults are classified as,1. Shunt faults - due to short circuits in conductors2. Series faults - due to open conductors.In another method,1. Symmetrical faults - fault currents are equal in all the phases and can beanalyzed on per phase basis2. Unsymmetrical faults – fault currents are unbalanced and so they can beanalyzed only using symmetrical components.6. List the various types of shunt and series faults.Various types of shunt faults are1. Single line-to-ground fault2. Line-to-line fault173. Double line-to-ground fault4. Three phase faultVarious types of series faults are,1. One open conductor fault2. Two open conductor fault7. What is meant by symmetrical fault?The fault is called symmetrical fault if the fault current is equal in all the phases.This fault conditions are analyzed on per phase basis using Thevenin’s theorem or usingbus impedance matrix. The three-phase fault is the only symmetrical fault.8. List out the differences in representing the power system for load flow and shortcircuit studies.Load flow studies Fault analysis1. Both resistances and reactances areConsidered.2. Bus admittance matrix is useful.3. The exact voltages and currents are to bedetermined.Resistances are neglected.Bus impedance matrix is used.The voltages can be safely assumed as 1p.u. and the prefault current can beneglected.9. For a fault at a given location, rank the various faults in the order of severity.In a power system, the most severe fault is three phase fault and less severe faultis open conductor fault. The various faults in the order of decreasing severity are,1) 3 phase fault2) Double line-to-ground fault

Page 53: 2 unit

3) Line-to-line fault4) Single line-to-ground fault5) Open conductor fault10. What is meant by fault calculations?The fault condition of a power system can be divided into sub transient, transient,and steady state periods. The currents in the various parts of the system and in the faultlocations are different in these periods. The estimation of these currents for various typesof faults at various locations in the system is commonly referred to as fault calculations.11. What are the assumptions made in short circuit studies of a large power systemnetwork? (APR/MAY 2005)1) The phase to neutral emfs of all generators remain constant, balanced and unaffectedby the faults.2) Each generator is represented by an emf behind either the subtransient or transientreactance depending upon whether the short circuit current is to be found immediatelyafter the short circuit or after about 3 – 4 cycles.3) Load currents may often be neglected in comparison with fault currents.4) All network impedances are purely reactive. Thus the series resistances of lines andtransformers are neglected in comparison with their resistances.185) Shunt capacitances and shunt branches of transformers are neglected. Hence,transformer reactances are taken as their leakage reactances.12. What is synchronous reactance?The synchronous reactance is the ratio of induced emf and the steady state rmscurrent (i.e., it is the reactance of a synchronous machine under steady state condition). Itis the sum of leakage reactance and the reactance representing armature reaction. It isgiven by,Xs = Xl + XaWhere,Xs = Synchronous reactanceXl = Leakage reactanceXa = Armature reaction reactance.13. Define subtransient reactance.(APR/MAY 2004)The subtransient reactance is the ratio of induced emf on no-load and thesubtransient symmetrical rms current, (i.e., it is the reactance of a synchronous machineunder subtransient condition). It is given by,Subtransient reactance,a f dwlgdX X XXIEX1 1 11''''+ += = +WhereXl = Leakage reactanceXa = Armature reaction reactance

Page 54: 2 unit

Xf = Field winding reactanceXdw = Damper winding reactance.14. Define transient reactance.The transient reactance is the ratio of induced emf on no-load and the transientsymmetrical rms current. (i.e.,it is the reactance of synchronous machine under transientcondition). It is given by,Transient reactance,a flgdX XXIEX1 11''+= = +WhereXl = Leakage reactan Xa = Armature reaction reactance Xf = Field winding reactance15.What is the significance of subtransient reactance and transient reactance inshort circuit studies?The subtransient reactance can be used to estimate the initial value of fault currentimmediately on the occurrence of the fault. The maximum momentary short circuitcurrent rating of the circuit breaker used for protection or fault clearing should be lessthan this initial fault current.The transient reactance is used to estimate the transient state fault current. Most ofthe circuit breakers open their contacts only during this period. Therefore for a circuit19breaker used for fault clearing (or protection), its interrupting short circuit current ratingshould be less than the transient fault current.16. Write down the equation determining fault current in a generator when itsreactance is known.The equation is,dgXEI = , ''dgXEI =whereI = Steady state symmetrical fault currentI ' = Transient symmetrical fault currentXd = Direct axis synchronous reactanceXd

Page 55: 2 unit

’ = Direct axis transient reactanceg E = RMS voltage from one terminal to neutral at no load.17.Write the equation for subtransient and transient internal voltage of thegenerator.The equation for subtransient internal voltage is,'' ''g t L d E =V + jI XTransient internal voltage is,' 'g t L d E = V + jI XwhereEg’’ = Subtransient internal voltage of generatorEg’ = Transient internal voltage of generatorVt = Terminal voltageIL = Load currentXd’’ =Direct axis subtransient reactanceXd’ =Direct axis transient reactance18.Write the equation for subtransient and transient internal voltage of the motor.The equation for subtransient internal voltage is,'' ''m t L d E = V − jI XTransient internal voltage is,' 'm t L d E = V − jI X swhereEm’’ = Subtransient internal voltage of generatorEm’ = Transient internal voltage of generatorVt = Terminal voltageIL = Load currentXd’’ =Direct axis subtransient reactance20Xd’ =Direct axis transient reactance19. How symmetrical faults are analyzed?The symmetrical faults are analyzed using per unit reactance diagram of the powersystem. Once the reactance diagram is formed, then the fault is simulated by shortcircuit or by connecting the fault impedance at the fault point. The currents andvoltages at various parts of the system can be estimated by any of the followingmethods.1) Using Kirchoff’s laws2) Using Thevenin’s theorem3) By forming bus impedance matrix.20. Define doubling effect and DC off-set current.Doubling effect:If a symmetrical fault occurs when the voltage wave is going through zero thenthe maximum momentary short circuit current will be double the value of maximumsymmetrical short circuit current. This effect is called doubling effect.

Page 56: 2 unit

DC off-set current:The unidirectional transient component of short circuit current is called DC offsetcurrent.21.Differentiate between subtransient and transient reactance.Subtransient reactance Transient reactance1) This is the ratio of induced emf andsubtransient current.2) Flux created by induced currents in thedamper winding is included.3) This is the smallest reactance among thereactance values.4) This cannot be extrapolated.1) This is the ratio of induced emf andtransient current.2) There is no damper winding and henceno flux is created.3) This is larger than the subtransientreactance.4) This can be extrapolated backwards intime22.What are symmetrical components?An unbalanced system of N related vectors can be resolved into N systems ofbalanced vectors called symmetrical components. Positive sequence componentsNegative sequence componentsZero sequence components.23. Write the symmetrical components of three phase system.In a 3-phase system, the three unbalanced vectors (either current or voltagevectors) can be resolved into three balanced system of vectors. They are,1) Positive sequence components2) Negative sequence components3) Zero sequence components.2124. Define negative sequence and zero sequence components.Negative sequence components consist of three phasors equal in magnitude,displaced from each other by 120o in phase, and having the phase sequence opposite tothat of the original phasors. Va2, Vb2 and Vc2 are the negative sequence components of Va,Vb and vc.Zero sequence components consist of three phasors equal in magnitude and withzero phase displacement from each other. Vao, Vbo and Vco are the zero sequencecomponents of Va, Vb and Vc.25.Express the unbalanced voltages Va, Vb and Vc in terms of symmetricalcomponents Va1, Va2 and Va0.The expression of unbalanced voltages in terms of symmetrical components are,Va =Vao +Va1+Va21 22aaVaa VaoVbV = + +

Page 57: 2 unit

221 aa VaaVaoVcV = + +(Or) ï ï ï ï= ï ï21022111 1 1aaacbaVVVa aa aVVV26. Express the symmetrical components Va1, Va2 and Va0 in terms of unbalancedvectors Va, Vb and Vc.

Page 58: 2 unit

The expression of symmetrical components in terms of unbalanced vectors are,( )31cVbVaVaoV = + +)2(311 ca VbaVaVaV = + +)2(312 caVba VaVaV = + +(Or) ï ï ï ï=

Page 59: 2 unit

ï ïcbaaaaVVVa aa aVVV22210111 1 1312227. Define the operator ‘a’ and express the value of ‘a’ and ‘a2’ in both polar andrectangular form.An operator which causes a rotation of 120o in the anticlockwise direction isknown as operator ‘a’. The value of ‘a’ is 1∠120o.The polar form and rectangular form of operator ‘a’ is given by,a = 1∠120o --------polar form= -0.5 + j0.806 ----------rectangular formThe polar form and rectangular form of operator ‘a2’ is given by,a2 = 1∠240o --------polar form= -0.5 - j0.806 ----------rectangular form28.what are sequence impedances and sequence networks?The sequence impedances are the impedances offered by the devices orcomponents for the like sequence component of the current.The single phase equivalent circuit of a power system consisting of impedances tocurrent of any one sequence only is called sequence network.29. What assumption is made at the star / delta transformer?It is that the positive sequence quantities on the HV side lead their correspondingpositive sequence quantities on the LV side by 30o. The reverse is the case for negativesequence quantities wherein HV quantities lag the corresponding LV quantities by 30o.30.What is an unsymmetrical fault? List the various unsymmetrical faults.The fault is called unsymmetrical fault if the fault current is not equal in all thephases. The unsymmetrical faults in a power system are,1) Single line-to-ground fault.2) Line-to-line fault.3) Double line-to-ground fault

Page 60: 2 unit

4) Open conductor fault.31.Define positive sequence and negative sequence impedances.The positive sequence impedance of an equipment is the impedance offered bythe equipment to the flow of positive sequence current.The negative sequence impedance of an equipment is the impedance offered bythe equipment to the flow of negative sequence current.23Possible 16 marks:1. Explain the need for short circuit studies.2. Draw the relationship between the phase components and the sequencecomponents.3. The phase ‘b’ of a three phase circuit is open. The currents in phases ‘c’ and ‘a’are I and –I respectively. Determine the positive, negative and zero sequencecomponents of the current in phase ‘a’.4. With the help of a detailed flow chart, explain how a symmetrical fault can beanalysed using ZBus.5. What are the various types of faults? Discuss their frequency of occurrence andseverity? Find the fault current when an L-L-G fault occurs at the terminals of anunloaded generator.6. Derive an expression for the positive sequence current Ia1 of an unloadedgenerator when it is subjected to a double line to ground fault.(APR/MAY 2004).7. Explain the short circuit model of a synchronous machine under short circuitconditions.8. What symmetrical components? Explain the symmetrical componenttransformation.9. What is meant by sequence impedance? Explain the sequence network of anunloaded generator.10. Explain the procedure for making short circuit studies of a large power systemusing digital computer. Illustrate the answer by considering a symmetrical fault.(NOV/DEC 2004)Reference books:R1 – Hadi saadat, “Power System Analysis”, Tata McGraw HillR2 – I J Nagarath , D P Kothari ’Modern Power system Analysis’, TMH Pub. Co. Ltd.,1994.R3 – Nagoor Kani, “Power System Analysis”24SELVAM COLLEGE OF TECHNOLOGY, NAMAKKAL-3DEPARTMENT OF EEEPOWER SYSTEM ANALYSISUNIT 4: SHORT CIRCUIT ANALYSISPossible 2 mark questions:1. What is meant by a fault?A fault in a circuit is any failure which interrupts with the normal flow of current.The faults are associated with abnormal change in current, voltage and frequency of thepower system. The faults may cause damage to the equipments, if it is allowed to persistfor a long time.2. Give the reason for faults in power system?Faults occur in a power system due to insulation failure of equipments, flashoverof lines initiated by a lightening stroke, permanent damage to conductors and towers oraccidental faulty operations.3. List the various types of symmetrical and unsymmetrical faults. (MAY/JUNE2006)Symmetrical fault:5. Three phase fault

Page 61: 2 unit

Unsymmetrical faults:6. Single line-to-ground fault7. Line-to-line fault8. Double line-to-ground fault4. For a fault at a given location, rank the various faults in the order of severity.In a power system, the most severe fault is three phase fault and less severe faultis open conductor fault. The various faults in the order of decreasing severity are,6) 3 phase fault7) Double line-to-ground fault8) Line-to-line fault9) Single line-to-ground fault10) Open conductor fault5. What is meant by fault calculations?The fault condition of a power system can be divided into subtransient, transient,and steady state periods. The currents in the various parts of the system and in the faultlocations are different in these periods. The estimation of these currents for various typesof faults at various locations in the system is commonly referred to as fault calculations.256. What is synchronous reactance?The synchronous reactance is the ratio of induced emf and the steady state rmscurrent (i.e., it is the reactance of a synchronous machine under steady state condition). Itis the sum of leakage reactance and the reactance representing armature reaction. It isgiven by,Xs = Xl + XaWhere,Xs = Synchronous reactanceXl = Leakage reactanceXa = Armature reaction reactance.7. Define subtransient reactance.(APR/MAY 2004)The subtransient reactance is the ratio of induced emf on no-load and thesubtransient symmetrical rms current, (i.e., it is the reactance of a synchronous machineunder subtransient condition). It is given by,Subtransient reactance,a f dwlgdX X XXIEX1 1 11''''+ += = +WhereXl = Leakage reactanceXa = Armature reaction reactanceXf = Field winding reactanceXdw = Damper winding reactance.8. Define transient reactance.

Page 62: 2 unit

The transient reactance is the ratio of induced emf on no-load and the transientsymmetrical rms current. (i.e.,it is the reactance of synchronous machine under transientcondition). It is given by,Transient reactance,a flgdX XXIEX1 11''+= = +Where Xl = Leakage reactance Xa = Armature reaction reactanceXf = Field winding reactance9.What is the significance of subtransient reactance and transient reactance in shortcircuit studies?The subtransient reactance can be used to estimate the initial value of fault currentimmediately on the occurrence of the fault. The maximum momentary short circuitcurrent rating of the circuit breaker used for protection or fault clearing should be lessthan this initial fault current.The transient reactance is used to estimate the transient state fault current. Most ofthe circuit breakers open their contacts only during this period. Therefore for a circuit26breaker used for fault clearing (or protection), its interrupting short circuit current ratingshould be less than the transient fault current.10. Write down the equation determining fault current in a generator when itsreactance is known.The equation is,dgXEI = , ''dgXEI =whereI = Steady state symmetrical fault currentI ' = Transient symmetrical fault currentXd = Direct axis synchronous reactanceXd’ = Direct axis transient reactanceg E = RMS voltage from one terminal to neutral at no load.11.Write the equation for subtransient and transient internal voltage of the

Page 63: 2 unit

generator.The equation for subtransient internal voltage is,'' ''g t L d E =V + jI XTransient internal voltage is,' 'g t L d E = V + jI XwhereEg’’ = Subtransient internal voltage of generatorEg’ = Transient internal voltage of generatorVt = Terminal voltageIL = Load currentXd’’ =Direct axis subtransient reactanceXd’ =Direct axis transient reactance12.Write the equation for subtransient and transient internal voltage of the motor.The equation for subtransient internal voltage is,'' ''m t L d E = V − jI XTransient internal voltage is,' 'm t L d E = V − jI X swhereEm’’ = Subtransient internal voltage of generatorEm’ = Transient internal voltage of generatorVt = Terminal voltageIL = Load currentXd’’ =Direct axis subtransient reactance27Xd’ =Direct axis transient reactance13. Define doubling effect and DC off-set current.Doubling effect:If a symmetrical fault occurs when the voltage wave is going through zero thenthe maximum momentary short circuit current will be double the value of maximumsymmetrical short circuit current. This effect is called doubling effect.DC off-set current:The unidirectional transient component of short circuit current is called DC offsetcurrent.14.Differentiate between subtransient and transient reactance.Subtransient reactance Transient reactance1) This is the ratio of induced emf andsubtransient current.2) Flux created by induced currents in thedamper winding is included.3) This is the smallest reactance among thereactance values.4) This cannot be extrapolated.

Page 64: 2 unit

1) This is the ratio of induced emf andtransient current.2) There is no damper winding and henceno flux is created.3) This is larger than the subtransientreactance.4) This can be extrapolated backwards intime15.What are symmetrical components?An unbalanced system of N related vectors can be resolved into N systems ofbalanced vectors called symmetrical components. Positive sequence componentsNegative sequence component Zero sequence components.16. Write the symmetrical components of three phase system. (MAY/JUNE 2006)In a 3-phase system, the three unbalanced vectors (either current or voltagevectors) can be resolved into three balanced system of vectors. They are,4) Positive sequence components5) Negative sequence components6) Zero sequence components.17. Define negative sequence and zero sequence components.Negative sequence components consist of three phasors equal in magnitude,displaced from each other by 120o in phase, and having the phase sequence opposite tothat of the original phasors. Va2, Vb2 and Vc2 are the negative sequence components of Va,Vb and vc.Zero sequence components consist of three phasors equal in magnitude and withzero phase displacement from each other. Vao, Vbo and Vco are the zero sequencecomponents of Va, Vb and Vc.2818.Express the unbalanced voltages Va, Vb and Vc in terms of symmetricalcomponents Va1, Va2 and Va0.The expression of unbalanced voltages in terms of symmetrical components are,Va =Vao +Va1+Va21 22aaVaa VaoVbV = + +221 aa VaaVaoVcV = + +(Or)

Page 65: 2 unit

ï ï ï ï= ï ï21022111 1 1aaacbaVVVa aa aVVV19. Express the symmetrical components Va1, Va2 and Va0 in terms of unbalancedvectors Va, Vb and Vc.The expression of symmetrical components in terms of unbalanced vectors are,( )31cVbVaVaoV = + +)

Page 66: 2 unit

2(311 ca VbaVaVaV = + +)2(312 caVba VaVaV = + +(Or) ï ï ï ï= ï ïcbaaaaVVV

Page 67: 2 unit

a aa aVVV22210111 1 13120. Define the operator ‘a’ and express the value of ‘a’ and ‘a2’ in both polar andrectangular form.An operator which causes a rotation of 120o in the anticlockwise direction isknown as operator ‘a’. The value of ‘a’ is 1∠120o.The polar form and rectangular form of operator ‘a’ is given by,a = 1∠120o --------polar form= -0.5 + j0.806 ----------rectangular formThe polar form and rectangular form of operator ‘a2’ is given by,a2 = 1∠240o --------polar form= -0.5 - j0.806 ----------rectangular form2921.what are sequence impedances and sequence networks?The sequence impedances are the impedances offered by the devices orcomponents for the like sequence component of the current.The single phase equivalent circuit of a power system consisting of impedances tocurrent of any one sequence only is called sequence network.22. What assumption is made at the star / delta transformer?It is that the positive sequence quantities on the HV side lead their correspondingpositive sequence quantities on the LV side by 30o. The reverse is the case for negativesequence quantities wherein HV quantities lag the corresponding LV quantities by 30o.23.Define positive sequence and negative sequence impedances.The positive sequence impedance of an equipment is the impedance offered bythe equipment to the flow of positive sequence current.The negative sequence impedance of an equipment is the impedance offered bythe equipment to the flow of negative sequence current.24. Draw the equivalent sequence network diagram for a single phase to groundfault in a power system. (APR/MAY 2005)25. Draw the zero sequence network diagram of a delta-delta connectedtransformer. (NOV/DEC 2005)26. In which fault, the negative and zero sequence currents are absent?In three phase fault, the negative and zero sequence currents are absent.27. Draw the connection of sequence networks or line –to-line fault without faultimpedance.30Possible 16 marks:11. Draw the relationship between the phase components and the sequencecomponents..12. Derive the expression for fault current for a double line to ground fault in anunloaded generator in terms of symmetrical components. (MAY/JUNE 2006)

Page 68: 2 unit

13. Derive the expression for fault current for a single line-to-ground fault in a powersystem faulted through fault impedance Zf.14. Explain the need for short circuit studies15. The phase ‘b’ of a three phase circuit is open. The currents in phases ‘c’ and ‘a’are I and –I respectively. Determine the Fpositive, negative and zero sequencecomponents of the current in phase ‘a’.16. What are the various types of faults? Discuss their frequency of occurrence andseverity?17. Find the fault current when an L-L-G fault occurs at the terminals of an unloadedgenerator. Derive an expression for the positive sequence current Ia1 of anunloaded generator when it is subjected to a double line to groundfault.(APR/MAY 2004).18. Explain the short circuit model of a synchronous machine under short circuitconditions. What symmetrical components? Explain the symmetrical componenttransformation.19. Write about the impedances in phase and sequence form.20. What is meant by sequence impedance? Explain the sequence network of anunloaded generator.21. Explain the procedure for making short circuit studies of a large power systemusing digital computer. Illustrate the answer by considering a symmetrical fault.(NOV/DEC 2004)Reference books:R1 – Hadi saadat, “Power System Analysis”, Tata McGraw HillR2 – I J Nagarath , D P Kothari ’Modern Power system Analysis’, TMH Pub. Co. Ltd.,1994.R3 – Nagoor Kani, “Power System Analysis”31SELVAM COLLEGE OF TECHNOLOGY, NAMAKKAL-3DEPARTMENT OF EEE POWER SYSTEM ANALYSIS UNIT 5:STABILITY ANALYSIS 1.Define Stability (of power system).The stability of a system is defined as the ability of power system to return to a (its) stable operation (mode) in which various synchronous machines of the system remain in synchronism or ‘in step’ with each other, when it is subjected to a sudden disturbances.2.Define Stability (of synchronous machine connected to a power system).The stability (of a synchronous machine connected to a power system) is defined as the ability of a synchronous machine connected to a power system to return to a (its) stable operation (mode) or ‘in step’ with that power system, when it is subjected to a sudden disturbances.3. Define Instability.Instability refers to the loss of synchronism (or falling out of step) of synchronous machine connected to power system when it is subjected to a sudden disturbances (changes).2. Define steady state stability.The steady state stability is defined as the ability of a power

Page 69: 2 unit

system to remainstable i.e., without loosing synchronism for small disturbances.3. Define transient stability.The transient stability is defined as the ability of a power system to remain stablei.e., without loosing synchronism for large disturbances.4.Write any three assumptions upon transient stability.a. Rotor speed is assumed to be synchronous. In fact, it varies insignificantlyduring the course of the stability study.b. Shunt capacitances are not difficult to account for in a stability study.c. Loads are modeled as constant admittances.5. What is meant by steady state stability limit?When the load on the system is increased gradually,maximum power that can betransmitted without losing synchronism is termed as steady state stability limit. In steadystate, the power transferred by synchronous machine of a power system is always lessthan the steady state stability limit.6. What is transient stability limit?When the load on the system is increased suddenly, maximum power that can betransmitted without losing synchronism is termed as transient state stability limit.Normally, steady state stability limit is greater than transient state stability limit.7. How to improve the transient stability limit of power system?a. Increase of system voltagesb. Use of high speed excitation systems.c. Reduction in system transfer reactanced. Use of high speed reclosing breakers.8. What is stability study?The procedure of determining the stability of a system upon occurrence of adisturbance followed by various switching off and switching on actions is called stabilitystudy.329.How do you classify steady state stability limit. Define them.Depending on the nature of the disturbance, the steady state stability limit isclassified into,a. Static stability limit refers to steady state stability limit that prevails withoutthe aid of regulating devices.b. Dynamic stability limit refers to steady state stability limit prevailing in anunstable system with the help of regulating devices such as speed governors,voltage regulators, etc.

Page 70: 2 unit

10.What are the machine problems seen in the stability study.1. Those having one machine of finite inertia machines swinging with respect toan infinite bus2. Those having two finite inertia machines swinging with respect to each other.11. Give the expression for swing equation. Explain each term along with theirunits.(APR/MAY 2005)Where H = Inertia constant in MJ/MVA.f = Frequency in Hz.M = Inertia constant in p.u.Pm= Mechanical power input to the system (neglecting mechanical losses) in p.u.Pe = Electrical power output of the system (neglecting electrical losses) in p.u.12. What are the assumptions made in solving swing equation?1) Mechanical power input to the machine remains constant during the period ofelectromechanical transient of interest.2) Rotor speed changes are insignificant that had already been ignored informulating the swing equations.3) Effect of voltage regulating loop during the transient are ignored.13. Define swing curve. What is the use of swing curve?The swing curve is the plot or graph between the power angle δ, and time, t.It is usually plotted for a transient state to study the nature of variation in δ for asudden large disturbance. From the nature of variations of δ, the stability of a system forany disturbance can be determined.14.Give the control schemes included in stability control techniques?The control schemes included in the stability control techniques are:a. Excitation systemsb.Turbine valve controlc.Single pole operation of circuit breakersd.Faster fault clearing times3315.What are the systems design strategies aimed at lowering system reactance?The system design strategies aimed at lowering system reactance are:a. Minimum transformer reactanceb.Series capacitor compensation of linesc.Additional transmission lines.16.What are coherent machines? (APR/MAY 2004)Machines which swing together are called coherent machines. When both ωs and δ

Page 71: 2 unit

are expressed in electrical degrees or radians, the swing equations for coherent machinescan be combined together even though the rated speeds are different. This is used instability studies involving many machines.17.State equal area criterion. (NOV/DEC 2004)In a two machine system under the usual assumptions of constant input , no dampingand constant voltage being transient reactance , the angle between the machines eitherincreases or else, after all disturbances have occurred oscillates with constant amplitude.There is a simple graphical method of determining whether the system comes to rest withrespect to each other. This is known as equal area criterion18.What are various faults that increase severity of equal area criterion?The various faults that increases severity of equal area criterion are,A Single line to ground faultA Line to line faultA Double line to ground faultA Three phase fault19.Give the expression for critical clearing timeThe expression for the critical clearing time tcr is given bytcr =Where, H is the constantδcr is the critical clearing angleδo is the rotor anglePm is the mechanical powerωs is the synchronous speed20.List the types of disturbances that may occur in a single machine infinite bus bar system of the equal area criterion stabilityThe types of disturbances that may occur are,Sudden change in mechanical inputEffect of clearing time on stabilitySudden loss of one of parallel linesSudden short circuit on one of parallel linesi) Short circuit at one end of lineii) Short circuit away from line endsiii) Reclosure3421.Define critical clearing angleThe critical clearing angle δcc is the maximum allowable change in the power angle δbefore clearing the fault , without loss of synchronism.22. Define critical clearing time.The critical clearing time , tcc can be defined as the maximum time delay that canbe allowed to clear a fault without loss of synchronism . The time corresponding to thecritical clearing angle is called critical clearing time tcc.23. What are the assumptions that are made inorder to simplify

Page 72: 2 unit

the computational task in stability studies?The assumptions are,• The D.C offset currents and harmonic components are neglected. Thecurrents and voltages are assumed to have fundamental componentalone.• The symmetrical components are used for the representation ofunbalanced faults.• It is assumed that the machine speed variations will not affect thegenerated voltage.24.What is Multimachine stability?If a system has any number of machines, then each machine is listed for stability byadvancing the angular position, δ of its internal voltage and noting whether the electricpower output of the machine increases (or) decreases. If it increases,i.e if ∂Pn / ∂δn > 0then machine n is stable. If every machine is stable, then the system having anynumber of machine is stable.25. What is meant by an infinite bus?The connection or disconnection of a single small machine on a large system wouldnot affect the magnitude and phase of the voltage and frequency. Such a system ofconstant voltage and constant frequency regardless of the load is called infinite bus barsystem or infinite bus.26.List the assumptions made in multimachine stability studies.The assumptions made are,• The mechanical power input to each machine remains constant duringthe entire period of the swing curve computation• Damping power is negligible• Each machine may be represented by a constant transient reactance inseries with a constant transient voltage.• The mechanical rotor angle of each machine coincides with δ , theelectrical phase angle of the transient internal voltage.27. Explain the concept synchronous speed.35The mechanical torque Tm and the electrical torque Te are considered positive forsynchronous generator. Tm is the resultant shaft torque which tends to accelerate therotor in the positive θm direction of rotation . Under steady-state operation of thegenerator Tm and Te are equal and the accelerating torque Ta is

Page 73: 2 unit

zero. Hence there is noacceleration of deceleration of the rotor, masses and the resultant constant speed is thesynchronous speed.Possible 16 marks1. Derive the swing equation for a single machine connected to infinite bus system. Statethe assumptions if any and state the usefulness of this equation. Neglect the damping.R4-Pg.No 2462.Discuss the various factors affecting the transient stability of the system.R1-Pg.No 5.423. With the help of a neat flowchart, explain the modified Euler method of solving theswing equations.R1-Pg.No 5.694.State the bad effects of instability. Distinguish between steady state and transientstability.R1-Pg.No5.65.Write short notes on assumptions made in deducing equal area criterion.R1-Pg.No5.45, R2 - 3466. State and explain equal area criterion. How do you apply equal area criterion to findthe maximum additional load.R1-Pg.No5.47, R4-2567. Describe the equal area criterion for transient stability analysis of a system.R1-Pg.No5.45 APR/MAY 20048. Mention the assumptions clearly and developing necessary equations, describe the stepby step solution of swing bus.R1-Pg.No5.28 APR/MAY 20049. Derive the swing equation of a synchronous machine swinging against an infinite bus.Clearly state the assumptions in deducing the swing equation.R1-Pg.No5.8 NOV/DEC 200410. Derive the swing equation for a synchronous machine.R1-Pg.No5.8 APR/MAY 2005.11. Explain critical clearing time and critical clearing angle, deriving the expressions.R1-Pg.No5.54, Pg.No5.60 APR/MAY 200612.Explain the solution of swing equation by Runge Kutta Method..R1-Pg.No5.63Book:R1. Power System Analysis – K.B. Hemalatha, S.T. JayaChrista.R2 – Hadi saadat, “Power System Analysis”, Tata McGraw HillR3 – I J Nagarath , D P Kothari ’Modern Power system Analysis’, TMH Pub. Co. Ltd.,1994.R4 – Nagoor Kani, “Power System Analysis”