4
162/1-03/a Specifications are subject to change without notice. Please visit our website for the latest revision. 162 Power System 2000 Amps @ +24VDC & 80 Amps @ -48VDC 100 Amp Switchmode Rectifiers Up to 20 can be equipped per bay, for a total of 2000 Amps of +24VDC power 10 Amp Converters Converts the +24VDC supplied by the rectifiers into -48VDC. Up to eight can be equipped for a total of 80 Amps at -48VDC Four Circuit Breaker Configurations for Distribution of +24VDC Option 1 - (80) 0 to 100 Amp Option 2 - (24) 0 to 100 Amp, (5) 125 to 250 Amp, and (4) 300 to 450 Amp Option 3 - (48) 2 to 100 Amp and (6) 125 to 250 Amp Option 4 - (36) 2 to 100 Amp and (8) 125 to 250 Amp Two -48VDC Configurations for Distribution Option 1 - (3) circuit breakers 2 to 60 Amps Option 2 - (20) GMT fuses 0.18 to 7.5 Amps Meter, Monitor, and Control Panel Easy to navigate, pushbutton controller has two lines of text to facilitate plant monitoring and control Small Footprint 23.62" by 23.62" (600mm by 600mm) Front Accessible All installation, operation, and general maintenance is from the front of the unit Product Description The 162 Power and Distribution System supplies 100 to 2000 Amps of +24VDC power in increments of 100 Amps. The system is self-contained, providing power, distribution, alarms, and monitoring within one bay. To create the flexible power needed by the 162, up to twenty switchmode rectifiers can be used. Up to eight optional +24VDC to -48VDC converters can be installed, for a total output current of 80 Amps at -48VDC. The 162 was designed for ease of installation, incorporating all customer connections for loads, controls, alarms, and monitoring from the front of the bay. Users may choose one of four distribution options for +24VDC, and one of two options for -48VDC. All +24VDC distribution options feature A & B sections. The 162 system may be accessed, monitored, and controlled from one entry point via the meter, monitor, and control (MMC) panel, which is easy to use and provided as standard equipment. The system is equipped with eight relays for extending alarms and status remotely, and 22 LEDs for immediate visual notification of alarms and operating status. A & B low voltage load disconnects (LVLD) are optional. Front View Rear View
Transcript
Page 1: 2000amp DC Panel

162/1-03/a Specifications are subject to change without notice. Please visit our website for the latest revision.

162 Power System2000 Amps @ +24VDC & 80 Amps @ -48VDC

• 100 Amp Switchmode Rectifiers Up to 20 can be equipped per bay, for a total of 2000 Amps of +24VDC power

• 10 Amp Converters Converts the +24VDC supplied by the rectifiers into -48VDC.Up to eight can be equipped for a total of 80 Amps at -48VDC

• Four Circuit Breaker Configurations for Distribution of +24VDCOption 1 - (80) 0 to 100 AmpOption 2 - (24) 0 to 100 Amp, (5) 125 to 250 Amp, and

(4) 300 to 450 AmpOption 3 - (48) 2 to 100 Amp and (6) 125 to 250 AmpOption 4 - (36) 2 to 100 Amp and (8) 125 to 250 Amp

• Two -48VDC Configurations for Distribution Option 1 - (3) circuit breakers 2 to 60 AmpsOption 2 - (20) GMT fuses 0.18 to 7.5 Amps

• Meter, Monitor, and Control Panel Easy to navigate, pushbutton controller has two lines of text to facilitate plant monitoring and control

• Small Footprint 23.62" by 23.62" (600mm by 600mm)

• Front Accessible All installation, operation, and general maintenance is from the front of the unit

Product DescriptionThe 162 Power and Distribution System supplies 100 to 2000 Amps of +24VDC power in increments of 100 Amps.The system is self-contained, providing power, distribution, alarms, and monitoring within one bay. To create the flexible power needed by the 162, up to twenty switchmode rectifiers can be used. Up to eight optional +24VDC to -48VDC converters can be installed, for a total output current of 80 Amps at -48VDC. The 162 was designed for ease of installation, incorporating all customer connections for loads, controls, alarms, and monitoring from thefront of the bay.

Users may choose one of four distribution options for +24VDC, and one of two options for -48VDC. All +24VDC distribution options feature A & B sections. The 162 system may be accessed, monitored, and controlled from one entry point via the meter, monitor, and control (MMC) panel, which is easy to use and provided as standardequipment.

The system is equipped with eight relays for extending alarms and status remotely, and 22 LEDs for immediate visual notification of alarms and operating status. A & B low voltage load disconnects (LVLD) are optional.

CableBroadbandBroadbandWirelessWireline

CableBroadbandBroadbandWirelessWireline

Front View

Rear View

Page 2: 2000amp DC Panel

162/1-03/a

Voltage Range 176 - 264VAC, single phaseFrequency Range 47 - 63HzCurrent 18 Amps (220VAC input and 100A output)

2000 Amps @ +24VDC & 80 Amps @ -48VDC

162 Power System Specifications

Input - 220VAC

162 Power System

Float Voltage Range 23.5 - 28.5VDC. Factory set @ 27.2VDCCurrent Maximum of 2000 Amps at + 24VDC per bay (from rectifiers)

Maximum of 80 Amps at - 48VDC per bay (from converters)

Height 84.0" (2133.6 mm)Width 23.62" (600 mm)Depth 23.62" (600 mm)Weight 1,000 lbs. (453.6kg) when equipped with 20 rectifiers and 8 convertersMounting Floor Cooling Front-to-rear fans in rectifiers and converters

Mechanical

Output

Storage Ambient -40˚F to +85˚F (-40°C to +85°C )Operating Ambient (NEBS) 23˚F to 122˚F (-5°C to +50°C)Humidity < 95% non-condensing (maximum)

Environmental

Product Manual 4380211PDSystem Layout Drawing J-438162P

Documentation

Visual Indicators

LED Description Color LED Description ColorMMC Front Panel: Power Major Red Battery Fuse Red

Power Minor Amber Battery Distribution RedRectifier Major Red Battery Discharge AmberRectifier Minor Amber Load Disconnect RedBattery Monitor Amber Total Current AmberDistribution Fuse Red AC Fail AmberDistribution Current Amber Temp High/Low AmberMMC OK Green Float Mode GreenLow Low Voltage Red Equalize Mode AmberLow Voltage Amber BTC Active AmberHigh Voltage Red

Specifications are subject to change without notice. Please visit our website for the latest revision.

Page 3: 2000amp DC Panel

162/1-03/a Specifications are subject to change without notice. Please visit our website for the latest revision.

2000 Amps @ +24VDC & 80 Amps @ -48VDC162 Power System

Options

List # Description PECO II Part Number1 Basic +24VDC @ 2,000 Amp bay including frame, controller,

distribution bus bar and rectifier shelves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6070836P5 OPTION 1: (80) 2-100 Amp plug-in circuit breaker positions, including output terminator

bus & ground return bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6180602P6 OPTION 2: (24) 2-100 Amp, (5) 125 - 250 Amp, (4) 300 - 450 Amp circuit breaker positions

including output termination bus bar & ground return bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6180603P7 OPTION 3: (48) 2 - 100 Amp, (6) 125 - 250 Amp circuit breaker positions

including output termination bus bar & ground return bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6180606P8 OPTION 4: (36) 2 - 100 Amp, (8) 125 - 250 Amp circuit breaker positions

including output termination bus bar & ground return bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6180608P20 +24 VDC @ 100 Amp rectifier module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SM100F24-UP22 Rectifier blank for unused rectifier positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4361154P25 -48 VDC @ 10 Amp DC/DC converter module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SM48P10A-D27 DC/DC converter blank for unused converter positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4361159P30 -48 VDC @ 40 Amp “initial” converter plant consisting of (1) 40 Amp converter shelf and wiring,

add up to (4) list 25 converters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6420552P31 -48 VDC @ 40 Amp ”supplemental” converter plant consisting of

(1) 40 Amp converter shelf and wiring, add up to (4) list 25 converters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6420552P-1 32 Converter distribution: (3) 2 - 60A circuit breaker positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6420556P33 Converter distribution: (20) 0.18 - 7.5A GMT fuse positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6420556P-140 Load A/B disconnects for +24VDC distribution options, list 5-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6420554P41 Load C disconnect for -48VDC DC/DC converter plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6420553P

Distribution Circuit BreakersPlug-in TypeDescription PECO II Part Number2 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-25 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-57 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-78 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-810 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-1015 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-1520 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-2025 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-2530 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-3035 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-3540 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-4045 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-4550 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-5060 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-6070 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-7080 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-8090 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-90100 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050107P-100

Bolt-on TypeDescription PECO II Part Number125 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050116P-125150 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050116P-150175 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050116P-175200 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050116P-200225 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050116P-225250 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050116P-250300 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050115P-300350 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050115P-350400 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050115P-400450 Amp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3050115P-450

Notes: distribution options list 6, 7, 8One 300-450A breaker can be installed in any two adjacent125-250A positions

Page 4: 2000amp DC Panel

162/1-03/aSpecifications are subject to change without notice. Please visit our website for the latest revision.

Option 3 Option 4

2000 Amps @ +24VDC & 80 Amps @ -48VDC

Line Drawing

162 Power System

Certifications:

162 Power System is shown

Option 1 Option 2


Recommended