Date post: | 26-Aug-2018 |
Category: |
Documents |
Upload: | nguyennguyet |
View: | 215 times |
Download: | 0 times |
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 1
2012 IEBC® Fundamentals2012 IEBC® Fundamentals
Based on the 2012 International Existing Building Code®
Overview Overview The purpose of the IEBC is to encourage
the use and re-use of existing buildings while requiring reasonable upgrades and improvements”
2012 IEBC Fundamentals 2Workbook Page 1
ObjectivesObjectives Upon completion of this seminar, participants
will be better able to: Recognize the limitations and extent of the codes
related to existing buildings. Recognize the classification of work associated
with existing buildings. Identify fire protection systems that need to be
upgraded.
32012 IEBC Fundamentals Workbook Page 1
ObjectivesObjectives Upon completion of this seminar, participants
will be able to: Recognize vertical openings that need partial or
complete enclosure. Identify unsafe interior finishes that need to be
replaced. Determine the adequate means of egress.
2012 IEBC Fundamentals 4Workbook Page 1
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 2
ObjectivesObjectives Upon completion of this seminar, participants
will be able to: Identify needed accessibility improvements. Identify improvements to structural systems. Describe the compliance alternative tabular
method of evaluating existing buildings.
2012 IEBC Fundamentals 5Workbook Page 1
General Purpose and IntentGeneral Purpose and Intent
Why was the IEBC created?
Why not use the IBC?
Is the IEBC to be considered an equivalent to the IBC?
2012 IEBC Fundamentals 6Workbook Page 4
Scope and AdministrationScope and Administration
Module 1Chapter 1:
2012 IEBC Fundamentals 7
101.2 - Scope 101.2 - Scope The IEBC covers all aspects of existing
buildings including maintenance, repairs, alterations, additions, change in use, historic buildings and relocation.
82012 IEBC Fundamentals Workbook Page 7
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 3
101.3 – Intent 101.3 – Intent Alternative approaches (regulations) Application of any enforcement-oriented
interpretive action or judgment. Code official needs to be able to review,
evaluate and rule on performance designs
92012 IEBC Fundamentals Workbook Page 7
101.4 – Applicability 101.4 – Applicability Can a building take advantage of the more
relaxed provisions of the IEBC before construction of the building has begun?
At the time a building was constructed, there was no law or ordinance requiring compliance with an established set of codes or standards, permits or inspections within the jurisdiction: Would the building be considered legally occupied?
102012 IEBC Fundamentals Workbook Page 8
101.7 – Correction of Violations of Other Codes 101.7 – Correction of Violations of Other Codes Repairs or alterations compliant with other
adopted maintenance codes, International Property
Maintenance Code® (IPMC®) International Fire Code® (IFC®),
Are not required to comply with the IEBC unless those codes so provide.
112012 IEBC Fundamentals Workbook Page 8
Language was revised and added to clarify how to deal with conflicts with referenced standards and understanding how the scoping of similar subjects by this code and standard are addressed.
2012 IEBC Fundamentals 12
102.4—Referenced Codes and Standards102.4—Referenced Codes and Standards
Workbook Page 9
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 4
This clarification is particularly important when this code and the standard have similar scopes. This clarification of what provisions take precedence is intended to reflect consistency with other I-codes.
2012 IEBC Fundamentals 13
102.4—Referenced Codes and Standards102.4—Referenced Codes and Standards
Workbook Page 9
Note: this essentially added a new section 102.4.1 and 102.4.2. Section 102.4.1 was based upon existing language and Section 102.4.2 which addresses similar scopes is all new language.
2012 IEBC Fundamentals 14
102.4—Referenced Codes and Standards102.4—Referenced Codes and Standards
Workbook Page 9
102.4.1—Conflicts102.4.1—Conflicts Where conflicts occur between provisions
of this code and the referenced standards, the provisions of this code shall apply.
2012 IEBC Fundamentals 15Workbook Page 9
The provisions of this code, as applicable, take precedence over the provisions in a referenced code or standard where the extent of the reference to a referenced code or standard includes subject matter that is within the scope of this code.
2012 IEBC Fundamentals 16
102.4.2—Conflicting Provisions102.4.2—Conflicting Provisions
Workbook Page 9
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 5
Duties and Power of the code officials - 104Duties and Power of the code officials - 104 104.1 – General 104.2.1 - Preliminary meeting 104.2.1.1 – Building Evaluation
104.6 - Right of Entry
172012 IEBC Fundamentals Workbook Page 9
Duties and Power of the code officials - 104Duties and Power of the code officials - 104 104.9.1 - Used materials and equipment 104.10 – Modifications 104.10.1 - Flood hazard areas
104.11 - Alternative materials, designs and methods of construction and equipment
182012 IEBC Fundamentals Workbook Page 9
Permits - 105Permits - 105 105.1 - Required Requires a permit for work done under auspices of
this code Annual permits allowed for work to already approved
installations Electrical Gas Mechanical or Plumbing
192012 IEBC Fundamentals Workbook Page 11
Permits - 105Permits - 105 105.2 - Work exempt from permit Permits are not required for work as listed in Section
105.2; however, although a permit is not required, any work that is done must not violate the provisions of the IBC or other laws or ordinances of the jurisdiction.
202012 IEBC Fundamentals Workbook Page 11
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 6
Construction documents - 106Construction documents - 106 106.1 - Submittal documents The design of building construction must be
performed by a registered design professional in accordance with the laws of the state where the work takes place.
106.6 - Design professional in responsible charge A registered design professional as the individual who
will oversee the coordination of all design related documents for construction.
212012 IEBC Fundamentals Workbook Page 11
Administration Activity Administration Activity 1. Referring to Section 101 in the code,
which activity does not fit within the scope of the IEBC? Adding an addition to a church that was built
in the year 1956. Converting a two-car garage to a bedroom. Constructing a building on a vacant lot. Repairing a broken window in an auto shop.
222012 IEBC Fundamentals Workbook Page 13
Administration Activity Administration Activity 2. Read the following scenarios. Put a check in
the “Permit not required” or “Permit required” box, whichever is applicable.
Scenario 1A technician is installing a temporary system required to service electrical equipment.
Permit not required Permit required
232012 IEBC Fundamentals Workbook Page 13
Administration Activity Administration Activity 2. Read the following scenarios. Put a check in
the “Permit not required” or “Permit required” box, whichever is applicable.
Scenario 2A contractor is installing a window awning
supported by an exterior wall of a Group R-3 occupancy.
Permit not required Permit required
242012 IEBC Fundamentals Workbook Page 13
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 7
Administration Activity Administration Activity 2. Read the following scenarios. Put a check in the
“Permit not required” or “Permit required” box, whichever is applicable.
Scenario 3A contractor is installing a driveway that is 45 inches
(1143 mm) above grade, is not over a basement or story below and is not part of an accessible route.
Permit not required Permit required
252012 IEBC Fundamentals Workbook Page 13
Administration Activity Administration Activity 3. Work that requires a permit shall be
subject to inspection by the code official. What inspections shall be performed?
26
a.Footing or foundation inspectionb.Concrete slab or under-floor inspectionc.Lowest floor elevationd.Frame inspectione.Lath and gypsum board inspectionf. Fire-resistant penetration inspectiong.Other inspections if requiredh.Special inspections if requiredi. Final inspection
2012 IEBC Fundamentals Workbook Page 13
DefinitionsDefinitionsChapter 2:
2012 IEBC Fundamentals 27
Rewording of the definition is intended to correct awkward grammar and sentence structure and to place the emphasis of “necessary” directly on “support.” (See below)
2012 IEBC Fundamentals 28
Section 202—DangerousSection 202—Dangerous
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 8
In this code, lateral system upgrades are triggered where lateral system damage from any cause is classified as Substantial Structural Damage (SSD). The change from 20 percent to 33 percent of the lateral-load capacity redefined the SSD to what is considered a more reasonable threshold to require an upgrade of a damaged building. (See below)
2012 IEBC Fundamentals 29
Section 202—Substantial Structural DamageSection 202—Substantial Structural Damage
Compliance MethodsCompliance Methods
Module 2Chapter 3:
2012 IEBC Fundamentals 30
Section 101.5, which included the basic procedural provisions of this code, as well as specific seismic evaluation and design criteria, did not belong in Chapter 1. The movement of Sections 101.5 through
101.5.4 to Chapter 3 in the 2012 edition remedies the situation of having technical criteria in the administration chapter.
2012 IEBC Fundamentals 31
301.1 — General301.1 — General
Workbook Page 15
The creation of Chapter 3 resulted in the renumbering of the chapters in this code from this point onward. See the following tables with the renumbered chapters.
2012 IEBC Fundamentals 32
301.1 — General301.1 — General
Workbook Page 15
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 9
2012 Chapters 2009 ChaptersChapter 1: Scope and Administration Chapter 1: Scope and Administration
Chapter 2: Definitions Chapter 2: Definitions
Chapter 3: Compliance Methods Chapter 3: Prescriptive Compliance Method
Chapter 4: Prescriptive Compliance Method
Chapter 4: Classification of Work
Chapter 5: Classification of Work Chapter 5: Repairs
Chapter 6: Repairs Chapter 6: Alterations—Level 1
Chapter 7: Alterations—Level 1 Chapter 7: Alterations—Level 2
Chapter 8: Alterations—Level 2 Chapter 8: Alterations—Level 3
Chapter 9: Alterations—Level 3 Chapter 9: Change of Occupancy
2012 IEBC Fundamentals 33
IEBC Chapter Title ChangesIEBC Chapter Title Changes2012 Chapters 2009 Chapters
Chapter 10: Change of Occupancy Chapter 10: Additions
Chapter 11: Additions Chapter 11: Historic Buildings
Chapter 12: Historic Buildings Chapter 12: Relocated or Moved Buildings
Chapter 13: Relocated or Moved Buildings Chapter 13: Performance Compliance Methods
Chapter 14: Performance Compliance Methods
Chapter 14: Construction Safeguards
Chapter 15: Construction Safeguards Chapter 15: Referenced Standards
Chapter 16: Referenced Standards
Appendix A: Guidelines for the Seismic Retrofit of Existing Buildings
Appendix A: Guidelines for the Seismic Retrofit of Existing Buildings
2012 IEBC Fundamentals 34
IEBC Chapter Title ChangesIEBC Chapter Title Changes
2012 Chapters 2009 ChaptersAppendix B: Supplementary Accessibility Requirements for Existing Buildings and Facilities
Appendix B: Supplementary Accessibility Requirements for Existing Buildings and Facilities
Appendix C: Guidelines for the Wind Retrofit of Existing Buildings (NEW)
2012 IEBC Fundamentals 35
IEBC Chapter Title ChangesIEBC Chapter Title Changes 301.1 – Compliance methods301.1 – Compliance methods The options available to a designer or owner: prescriptive compliance method (Section 301.1.1); work area compliance method (Section 301.1.2); performance compliance method (Section 301.1.3).
362012 IEBC Fundamentals Workbook Page 15
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 10
301.1.4 – Evaluation and design procedures 301.1.4 – Evaluation and design procedures Seismic evaluation and design of an existing
building must be based on the procedures specified in one of four reference materials. IBC Guidelines for the Seismic Retrofit of Existing
Buildings (GSREB) (2012 IEBC, Appendix A) American Society of Mechanical Engineers ASCE 31 ASCE 41
372012 IEBC Fundamentals Workbook Page 16
301.1.4.1 - Compliance with IBC level seismic forces301.1.4.1 - Compliance with IBC level seismic forces
38
2012IEBC Page 13
2012 IEBC Fundamentals Workbook Page 16
301.1.4.2 - Compliance with reduced IBC level seismic forces
301.1.4.2 - Compliance with reduced IBC level seismic forces
39
2012 IEBC Page 14
2012 IEBC Fundamentals Workbook Page 16
Compliance MethodsCompliance Methods 1. When seismic forces are permitted to
meet reduced IBC levels, they must be based on what percent of the assumed forces prescribed in the IBC?
a. 35 b. 55 c. 75 d. 95
402012 IEBC Fundamentals Workbook Page 17
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 11
Compliance MethodsCompliance Methods 2. The seismic analysis must be based on
one of the following procedures in which section of the IEBC?
a. 301.1 b. 301.1.4 c. 101.4.2 d. 101.7
412012 IEBC Fundamentals Workbook Page 17
Prescriptive Compliance MethodPrescriptive Compliance Method
Module 3Chapter 4:
2012 IEBC Fundamentals 42
This Section provides guidance to engineers when selecting system-related design coefficients for existing seismic force systems.
2012 IEBC Fundamentals 43
401.2.3—Existing Seismic-Force-Resisting Systems401.2.3—Existing Seismic-Force-Resisting Systems
Previously, this guidance was located within each individual section related to alterations, additions, repairs and changes of occupancy but has been relocated to a more general section to ensure consistent application.
The intent is that existing systems should be considered “ordinary” by default.
For seismic systems that may provide performance equivalent to that of a detailed, intermediate, or special system, this code requires a demonstration of equivalence
2012 IEBC Fundamentals 44
401.2.3—Existing Seismic-Force-Resisting Systems401.2.3—Existing Seismic-Force-Resisting Systems
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 12
401.2.3—Existing Seismic-Force-Resisting Systems401.2.3—Existing Seismic-Force-Resisting Systems
This only applies to systems for which there is a choice of “ordinary,” “detailed,” "intermediate" or “special” for the permitted seismic force systems.
2012 IEBC Fundamentals 45
For example, light-frame shear walls are not categorized as ordinary, detailed, intermediate or special. Those systems are acceptable, and the system coefficients specified for those systems in ASCE 7 are appropriate.
The relocation is related to the need to emphasize the broad applicability of this provision throughout Chapter 4 and it is not simply limited to repairs.
2012 IEBC Fundamentals 46
401.3—Dangerous Conditions401.3—Dangerous Conditions This revision relocates a provision related to the ability of
the building official to address dangerous conditions from Section 304.1.1 (Section 304, Repairs) to Section 401.3 (Section 401, General).
402.3 - Existing structural elements carrying gravity load 402.3 - Existing structural elements carrying gravity load Where additions and related alterations increase
the force in any existing structural element by more than 5 percent, the structural elements must be altered and replaced to carry the increased load as required for new construction.
472012 IEBC Fundamentals Workbook Page 19
402.4 - Existing structural elements carrying lateral load 402.4 - Existing structural elements carrying lateral load There are three options for seismically designing
an addition to an existing structure: Design the addition as being structurally independent
from the existing building: The addition must be designed to meet the requirements for new construction.
Design the addition as not being structurally independent from the existing building: The addition and existing structure must be designed to meet the requirements for new construction.
482012 IEBC Fundamentals Workbook Page 20
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 13
402.4 - Existing structural elements carrying lateral load 402.4 - Existing structural elements carrying lateral load There are three options for seismically designing
an addition to an existing structure: Design the addition as not being structurally
independent from the existing building: The addition must be designed to meet the requirements for new construction and the addition must not increase the demand-demand-capacity ratio of any existing lateral load-carrying element by more than 10 percent.
492012 IEBC Fundamentals Workbook Page 20
402.5—Smoke Alarms in Existing Portions of a Building 402.5—Smoke Alarms in Existing Portions of a Building This provision was added since Chapter
34 of the International Building Code®
(IBC®) did not currently provide a path to the International Fire Code® (IFC®)for the smoke alarm requirements in existing buildings. This new section connects this code
directly to Section 1103.8 of the IFC.
2012 IEBC Fundamentals 50
402.5—Smoke Alarms in Existing Portions of a Building402.5—Smoke Alarms in Existing Portions of a Building The work area method (chapters 5 through
13) already addresses this link but as Chapter 4 is simply a duplication of Sections 3401 through 3411 of the IBC, this section is now located within Chapter 4, as well.
2012 IEBC Fundamentals 51
This new section is consistent with the addition of new Section 402.5, and with the need in IBC Chapter 34 for the link to the IFC for smoke alarm requirements in existing buildings.
This new section fixes a technical flaw between the IFC and this code by tying the requirements for smoke alarms in individual sleeping units and individual dwelling units in Group R and I-1 directly to the Section 1103.8 of the IFC.
2012 IEBC Fundamentals 52
403.6—Smoke Alarms403.6—Smoke Alarms
Workbook Page 21
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 14
403.6—Smoke Alarms 403.6—Smoke Alarms In the past, this code limited the level of
building fire protection by isolating such requirements to work areas only. The structure of the IFC is that the
retroactive requirements apply to all buildings, whether or not those buildings are undergoing alterations.
2012 IEBC Fundamentals 53Workbook Page 21
Basic repair—that is, restoring the pre-damage condition—is still required even for the exceptions outlined.
2012 IEBC Fundamentals 54
404.2—Substantial Structural Damage to Vertical Elements of the Lateral-Force-Resisting System
404.2—Substantial Structural Damage to Vertical Elements of the Lateral-Force-Resisting System
Two new exceptions that exempt certain combinations of buildings, seismic risk, and damage from triggered seismic upgrades, were added to Section 404.2.
Workbook Page 21
Exception 1,(New) The first exception is for
buildings in areas of low or moderate seismicity [Seismic Design Category (SDC) A, B or C], where the damage was not caused by an earthquake and therefore would not be required to be evaluated or rehabilitated for load combinations that include earthquake effects as in Section 404.2.
2012 IEBC Fundamentals 55
404.2—Substantial Structural Damage to Vertical Elements of the Lateral-Force-Resisting System
404.2—Substantial Structural Damage to Vertical Elements of the Lateral-Force-Resisting System
Workbook Page 21
Exception 1, (New) This exemption of Seismic
Design Category C is new with the 2012 edition. Where earthquakes are rare, it serves no significant public purposes to trigger seismic upgrades following damage caused by fire, collision, wind, etc.
2012 IEBC Fundamentals 56
404.2—Substantial Structural Damage to Vertical Elements of the Lateral-Force-Resisting System
404.2—Substantial Structural Damage to Vertical Elements of the Lateral-Force-Resisting System
Workbook Page 21
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 15
Exception 2, (New) The second exception is for one- and two-
family dwellings, where the public risk is especially low even though the damage may be associated with earthquake effects. Similar revisions were made to Chapter 6, Repairs.
2012 IEBC Fundamentals 57
404.2—Substantial Structural Damage to Vertical Elements of the Lateral-Force-Resisting System
404.2—Substantial Structural Damage to Vertical Elements of the Lateral-Force-Resisting System
Workbook Page 21
This section was revised to remove the list of SDC’s requiring evaluation that is now addressed by Section 404.2, Exception 1, which exempts SDC’s A through C.
Therefore, this section regulates SDC’s D through F.
2012 IEBC Fundamentals 58
404.2.1—Evaluation404.2.1—Evaluation
Workbook Page 21
Additionally, in correlation with the new requirement in Section 401.2.3, the provisions providing guidance to engineers on selecting system-related design coefficients for existing seismic force systems are no longer necessary in this location. In Section 401.2.3 there is a more general application to the entire chapter.
2012 IEBC Fundamentals 59
404.2.1—Evaluation404.2.1—Evaluation
Workbook Page 21
404.3 - Substantial structural damage to gravity load-carrying components 404.3 - Substantial structural damage to gravity load-carrying components
Substantial structural damage to gravity load-carrying elements must be repaired.
Snow loads must also be included where the substantial damage is associated with the effects of snow load.
602012 IEBC Fundamentals Workbook Page 22
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 16
Exceptions 1 and 2 (New) This section added two new exceptions which are
identical to Section 404.2. The reasoning for the exceptions is the same.
The primary differences between the two sections is that: Section 404.2 deals with the vertical elements of the
lateral-force-resisting system. Section 404.3.1 deals with damage caused by wind
and earthquake to the gravity load-carrying components in a building.
2012 IEBC Fundamentals 61
404.3.1—Lateral Force-Resisting Elements404.3.1—Lateral Force-Resisting Elements
Workbook Page 22
404.4 - Less than substantial structural damage 404.4 - Less than substantial structural damage Damage that is not deemed to be substantial
structural damage, repairs are allowed that restore the building to its pre-damaged state using materials and strengths that existed prior to the damage.
New structural members and connections used for this repair must comply with the detailing provisions for new buildings of similar materials, purpose and location.
622012 IEBC Fundamentals Workbook Page 22
Fire Escapes - 405Fire Escapes - 405 405.1.1 - New buildings 405.1.2 - Existing fire escapes 405.1.3 - New fire escapes 405.1.4 – Limitations
632012 IEBC Fundamentals Workbook Page 22
407.1 – Conformance Change in Occupancy 407.1 – Conformance Change in Occupancy A change in occupancy to an existing building
requires the building to meet the requirements of the IBC for the new occupancy.
642012 IEBC Fundamentals Workbook Page 22
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 17
407.4 – Structural 407.4 – Structural When a change in occupancy results in the
structure being reclassified to a higher occupancy category, the seismic requirements for new construction apply to the existing structure.
652012 IEBC Fundamentals Workbook Page 23
408.1 - Historic buildings408.1 - Historic buildings Except for historic structures located in flood
hazard areas, a proposed change of occupancy that does not constitute a distinct life safety hazard may be approved by the code official.
662012 IEBC Fundamentals Workbook Page 23
408.2 - Flood hazard areas 408.2 - Flood hazard areas An historic building located in a flood hazard
area is required to comply with the flood provisions of the IBC unless one of the following is applicable: An historic building is listed in the National Register of
Historic Places; Determined by the U.S. Department of the Interior as
contributing to the historical significance of an historic district; or
Designated as historic under a program that is approved by the U.S. Department of the Interior.
672012 IEBC Fundamentals Workbook Page 23
Accessibility for Existing Buildings – 410 Accessibility for Existing Buildings – 410 The intent is that when a building is altered, it
should be made accessible to the maximum extent possible within reason.
682012 IEBC Fundamentals Workbook Page 23
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 18
The exception that exempted Type B units from being provided in existing buildings being altered or undergoing a change of occupancy was deleted.
2012 IEBC Fundamentals 69
410.1—Scope410.1—Scope
Workbook Page 23
This coordinates with a number of revisions that now require that Type B units be addressed when an alteration affecting over 50 percent of the building is being undertaken with or without a change of occupancy.
2012 IEBC Fundamentals 70
410.1—Scope410.1—Scope
Workbook Page 23
When a change of occupancy includes alterations to more than 50 percent of the building, Type B dwelling or sleeping units, as required by Section 1107 of the IBC, will be required in Group I and R facilities.
2012 IEBC Fundamentals 71
410.4— Change of Occupancy410.4— Change of Occupancy
Workbook Page 24
Exception (New) In accordance with the new exception,
when Type B units are required in existing buildings, the additional accessible features listed in Section 410.4.2, Items 1 through 6 are not required for an accessible route to Type B units.
2012 IEBC Fundamentals 72
410.4.2—Complete Change of Occupancy410.4.2—Complete Change of Occupancy
Workbook Page 24
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 19
410.5 – Additions410.5 – Additions Provisions for new
construction apply to additions . Note that if an addition affects accessibility to or contains an area of primary function Section 410.7 applies.
2012 IEBC Fundamentals 73Workbook Page 24
410.6 – Alterations410.6 – Alterations Alterations are required to
comply with the provisions of Chapter 11 of the IBC unless technically infeasible. Note that technically infeasible is a defined term.
2012 IEBC Fundamentals 74Workbook Page 24
410.7 - Alterations affecting an area of primary function410.7 - Alterations affecting an area of primary function The accessible route to that function and any
toilet rooms or drinking fountains serving it must be evaluated for accessibility.
A primary goal is that all buildings will become fully accessible over time.
752012 IEBC Fundamentals Workbook Page 24
Exception 5 (New) Where an alteration affects the
accessibility to, or contains an area of primary function, the route to the primary function area shall be accessible. Per the new exception, this provision
does not apply to altered areas limited to Type B dwelling and sleeping units.
2012 IEBC Fundamentals 76
410.7—Alterations Affecting an Area Containing a Primary Function410.7—Alterations Affecting an Area Containing a Primary Function
Workbook Page 24
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 20
410.8.2 – Elevators 410.8.2 – Elevators All elevators on an accessible
route must be fully accessible in accordance with ICC A117.1.
If a passenger elevator is altered, the altered element must be accessible in accordance with the existing elevator requirements in ICC A117.1 407.
772012 IEBC Fundamentals Workbook Page 25
410.8.3 - Platform lifts 410.8.3 - Platform lifts Given the choice between no accessibility or
accessibility by a platform lift, accessibility is preferable.
782012 IEBC Fundamentals Workbook Page 25
410.8.4 - Stairs and escalators 410.8.4 - Stairs and escalators Intent is that if a route is provided between
accessible levels for a nondisabled person to use, it is reasonable to also expect an accessible route.
792012 IEBC Fundamentals Workbook Page 25
Accessibility for Existing Building - 410Accessibility for Existing Building - 410 410.8.5 – Ramps 410.8.6 - Performance areas 410.8.7 - Dwelling or sleeping units
2012 IEBC Fundamentals 80Workbook Page 26
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 21
This section expands the application of the requirements of Section 1107 of the IBC for Type A units when more than 20 Group R-2 dwelling or sleeping units are added to also include units altered. These requirements apply only to the
quantity of the spaces being altered or added.
2012 IEBC Fundamentals 81
410.8.8—Type A Dwelling or Sleeping Units410.8.8—Type A Dwelling or Sleeping Units
Workbook Page 26
This section has been revised to also require Type B units to be addressed when Group I-1, I-2, R-1, R-2, R-3 or R-4 sleeping or dwelling units are being altered.
2012 IEBC Fundamentals 82
410.8.9—Type B Dwelling or Sleeping Units410.8.9—Type B Dwelling or Sleeping Units
Workbook Page 26
This revision only applies to more extensive alterations (more than 50 percent of the building area) and the requirements only apply to the quantity of spaces being altered.
2012 IEBC Fundamentals 83
410.8.9—Type B Dwelling or Sleeping Units410.8.9—Type B Dwelling or Sleeping Units
Workbook Page 26
Accessibility for Existing Building - 410Accessibility for Existing Building - 410 410.8.10 - Jury boxes and witness stands 410.8.11 - Toilet rooms 410.8.12 - Dressing, fitting and locker rooms 410.8.13 - Fuel dispensers 410.8.14 – Thresholds
2012 IEBC Fundamentals 84Workbook Page 27
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 22
410.9 - Historic buildings 410.9 - Historic buildings If you touch it, fix it. If the alteration contains a primary function area,
address accessible route requirements. The issues for technical infeasibility and
accessible means of egress requirements are also the same.
The difference is if the alterations would threaten, compromise or destroy the historical aspect of the building.
852012 IEBC Fundamentals Workbook Page 28
Exception (New) New exception indicates
that historic buildings are not required to provide Type B units when undergoing a change of occupancy or alterations.
2012 IEBC Fundamentals 86
410.9—Historic Buildings410.9—Historic Buildings
Workbook Page 28
Accessibility for Existing Building - 410Accessibility for Existing Building - 410 410.9.1 - Site arrival points 410.9.2 - Multilevel
buildings and facilities 410.9.3 – Entrances 410.9.4 - Toilet and bathing
facilities
2012 IEBC Fundamentals 87Workbook Page 28
Classification of Work Classification of Work
Module 4Chapter 5
882012 IEBC Fundamentals
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 23
Classification of WorkClassification of Work Traditional Repair
Alteration
Addition
Change of occupancy
Moved structures
892012 IEBC Fundamentals Workbook Page 29
Classification of WorkClassification of Work NARRP Repair
Renovation
Alteration
Reconstruction
Addition
Change of occupancy
90
Workbook page 21- 30
2012 IEBC Fundamentals Workbook Page 29
Classification of WorkClassification of Work Chapter 5 Repair Alteration-Level 1 Alteration-Level 2 Alteration-Level 3 Addition Change of occupancy Relocated or moved buildings Historic Buildings
2012 IEBC Fundamentals 91
Chapter 5 Chapter 5
Workbook Page 29
Classification of WorkClassification of Work
92
Levels of Alteration
AlterationAlteration-Level 1Alteration-Level 2Alteration-Level 3
RenovationAlterationReconstruction
Traditional NARRP IEBC
2012 IEBC Fundamentals Workbook Page 30
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 24
Classification of WorkClassification of Work
93
IEBC Proportional Approach
UPGRADES Alt. Lev.1 Alt. Lev.2 Alt. Lev. 3
1
2
3
IEBC Chapter 7 RequirementsIEBC Chapter 8 RequirementsIEBC Chapter 9 Requirements
REQUIRED
2012 IEBC Fundamentals Workbook Page 30
Activity Activity
1. Use your IEBC to match the statements to the applicable term.
______ Level 1 Alterations
______ Level 2 Alterations
______ Level 3 Alterations
______ Change of Occupancy
______ Additions
94
a. Applies where the work area exceeds 50 percent of the aggregate area of the building.
b. Includes the removal and replacement or the covering of existing materials, elements, equipment or fixtures that serve the same purpose.
c. Includes the reconfiguration of space, the addition or elimination of any door or window, the reconfiguration or extension of any system or the installation of any additional equipment.
d. Must comply with the provisions of Chapter 10.e. Must comply with the provisions of Chapter 11.
b.
c.
a.
d.
e.
2012 IEBC Fundamentals Workbook Page 31
RepairsRepairsChapter 6:
2012 IEBC Fundamentals 95
Repairs Repairs Note that hazardous building materials such as
asbestos and lead based paint shall not be used where the code would not permit such use.
2012 IEBC Fundamentals 96Workbook Page 33
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 25
General - 601General - 601
Repairs are made as a result of maintenance requirements.
Maintained in accordance with the IFC and IPMC.
Repairs need to comply with the IEBC.
2012 IEBC Fundamentals 97Workbook Page 33
602.2 – New and replacement materials 602.2 – New and replacement materials Repairs can be made
with like materials unless such materials are deemed to be hazardous
2012 IEBC Fundamentals 98Workbook Page 34
602.3 - Glazing in hazardous locations 602.3 - Glazing in hazardous locations Replacement glazing,
other than glass block, louvered windows and jalousies in a hazardous location shall comply with the requirements of the IBC or the IRC.
2012 IEBC Fundamentals 99Workbook Page 34
606.1 – General Structural606.1 – General Structural The requirements that pertain to structural
materials and elements in need of repair; Section 606.2.1 addresses repairs for less than
substantial structural damage; Section 606.2.2 addresses repairs for substantial
structural damage to vertical elements of the lateral-force-resisting system; and
Section 606.2.3 addresses repairs for substantial structural damage to gravity load-carrying components.
1002012 IEBC Fundamentals Workbook Page 34
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 26
606.2.1 - Repairs for less than substantial structural damage 606.2.1 - Repairs for less than substantial structural damage Repairs are allowed that restore the building to
its predamaged state. New structural members and connections used
for this repair shall comply with the detailing provisions of the IBC.
1012012 IEBC Fundamentals Workbook Page 34
Two new exceptions that exempt certain combinations of buildings, seismic risk, and damage from triggered seismic upgrades were added to Section 606.2.2.
2012 IEBC Fundamentals 102
606.2.2—Substantial Structural Damage to Vertical Elements of the Lateral-Force-Resisting System
606.2.2—Substantial Structural Damage to Vertical Elements of the Lateral-Force-Resisting System
Basic repair, that is, restoring the pre-damage condition, is still required even for the exceptions outlined.
Workbook Page 35
Exception 1 (New) The first exception is for buildings in areas of
low or moderate seismicity (SDC’s A, B or C), where the damage was not caused by an earthquake.
These buildings would not be required to be evaluated or rehabilitated for load combinations that include earthquake effects as in Section 606.2.2
2012 IEBC Fundamentals 103
606.2.2—Substantial Structural Damage to Vertical Elements of the Lateral-Force-Resisting System
606.2.2—Substantial Structural Damage to Vertical Elements of the Lateral-Force-Resisting System
Workbook Page 35
Exception 1 (New) Where earthquakes
are rare, it serves no significant public purposes to trigger seismic upgrades following damage caused by fire, collision, wind, etc.
2012 IEBC Fundamentals 104
606.2.2—Substantial Structural Damage to Vertical Elements of the Lateral-Force-Resisting System
606.2.2—Substantial Structural Damage to Vertical Elements of the Lateral-Force-Resisting System
Workbook Page 35
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 27
Exception 2 (New) The second exception is for one- and two-
family dwellings where the public risk is especially low even though the damage may be associated with earthquake effects. These are the same exceptions found in
the prescriptive compliance method in Section 404.2.
2012 IEBC Fundamentals 105
606.2.2—Substantial Structural Damage to Vertical Elements of the Lateral-Force-Resisting System
606.2.2—Substantial Structural Damage to Vertical Elements of the Lateral-Force-Resisting System
Workbook Page 35
606.2.3 - Substantial structural damage to gravity load-carrying components 606.2.3 - Substantial structural damage to gravity load-carrying components
Required to be rehabilitated to comply with the provisions for dead and live loads in the IBC.
Required to comply with the detailing provisions of the IBC for new buildings.
1062012 IEBC Fundamentals Workbook Page 35
Exceptions 1 and 2 (New) This section added two new exceptions which are
identical to Section 606.2.2. The reasoning for the exceptions is the same.
The primary differences between the sections is that: Section 606.2.2 deals with the vertical elements of
the lateral-force-resisting system. Section 606.2.3.1 deals with damage caused by
wind and earthquake to the gravity load-carrying components in a building.
2012 IEBC Fundamentals 107
606.2.3.1—Lateral- Force-Resisting Elements606.2.3.1—Lateral- Force-Resisting Elements
Workbook Page 35
Chapter 6 ExampleChapter 6 Example
A fire has caused damage to a one story-building. Many walls, ceilings and doors must be replaced, including the walls and the doors of a corridor that were not fire-resistance rated, but would be required to be fire resistance rated under the IBC. The walls are not load bearing. Can the walls of the corridor be reconstructed, and the other doors be replaced with the same construction and door as before the fire?
2012 IEBC Fundamentals 108Workbook Page 36
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 28
Chapter 6 – Q&AChapter 6 – Q&A Can the walls of the corridor be
reconstructed, and the other doors be replaced with the same construction and door as before the fire?
109
No. The walls of the corridor would be considered an alteration, Level 2 because of
the reconfiguration of the corridor. The construction of the corridor would be
considered new construction; therefore, Section 801.3 would apply and must comply
with all of the requirements of the IBC. A permit would also be required.
2012 IEBC Fundamentals Workbook Page 36
ActivityActivity1. Replacement glazing in locations
determined to be hazardous is allowed to be any approved glazing material.
a. Trueb. False
1102012 IEBC Fundamentals Workbook Page 37
Activity Activity 2. Substantial structural damage is a trigger
for structural repairs to comply with the provisions for new construction. What is required for structural repairs that are less than substantial structural damage?
111
a. They must meet the requirements of the IBC.b. They are permitted to be designed for 80 percent of
the live load and dead loads required by the IBC for a similar use or occupancy.
c. Structural elements being repaired are permitted to be restored to their pre-damage condition.
d. An evaluation in accordance with Section 606.2.2.1 is required to determine what are the minimum requirements.
2012 IEBC Fundamentals Workbook Page 37
Activity Activity 3. New structural frame members used in
the repair of damaged buildings, including anchorage and connections, must comply with which International Code?
IBC
1122012 IEBC Fundamentals Workbook Page 37
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 29
Alterations—Level 1 Alterations—Level 1
Module 6Chapter 7:
2012 IEBC Fundamentals 113
Introductions Introductions The owner of a five-story multi-family building plans to replace all faucets, lavatories and water closets, and all carpeting in the entire building in all units. What requirements should be followed?
2012 IEBC Fundamentals 114
This is an Alteration–Level 1. The fixtures and all materials used to install them must comply with the IPC. Further, all new carpeting must comply with the radiant flux requirements of the IBC. No
additional requirements are triggered.
Workbook Page 39
General –701General –701 Level 1 alterations being performed must
not lessen the safety of the existing building.
1152012 IEBC Fundamentals Workbook Page 39
Building Element and Materials –702Building Element and Materials –702 All new work must comply with the prescribed
materials and methods requirements for new construction.
All interior finishes must comply with the flame spread requirements of the IBC.
Carpeting must comply with the radiant flux requirements of the IBC.
1162012 IEBC Fundamentals Workbook Page 40
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 30
705.1 –Accessibility General 705.1 –Accessibility General Must comply with the accessibility provisions in
Section 705 and Chapter 11 of the IBC unless technically infeasible.
Altered items to review for accessibility include entrances, elevators, ramps and toilet rooms.
1172012 IEBC Fundamentals Workbook Page 40
Exception 3: Type B units are required only when an existing building undergoes a Level 3 alteration. Exception 4: Reference to Chapter 11 of
the IBC and ICC A117.1 have been removed. Rather than refer to the IBC, specific provisions are being added to this code. The wording is revised to reflect that change.
2012 IEBC Fundamentals 118
705.1—Accessibility General705.1—Accessibility General
Workbook Page 40
705.1.8 - Accessible dwelling or sleeping units 705.1.8 - Accessible dwelling or sleeping units Where Group I-1, 1-2, 1-3, R-1, R-2 or R-4
dwelling units or sleeping units are being altered or added, the requirements for accessible units in Section 1107 of the IBC and accessible alarms in Chapter 9 of the IBC apply only to the quantity of spaces being altered or added.
1192012 IEBC Fundamentals Workbook Page 40
705.1.9 - Type A dwelling or sleeping units 705.1.9 - Type A dwelling or sleeping units
24 units within a Group R-2 apartment building are being altered 2 percent of the 24 units being altered would be required to be designed to conform to Type A unit requirements and to incorporate visible alarms in accordance with Chapter 9 of the IBC.
1202012 IEBC Fundamentals Workbook Page 40
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 31
705.2 - Alterations affecting an area containing a primary function 705.2 - Alterations affecting an area containing a primary function
The route to the primary function area must also be accessible, including toilet facilities and drinking fountains: The cost of providing the accessible route is
not required to exceed 20 percent of the costs of alterations affecting the primary function area
1212012 IEBC Fundamentals Workbook Page 41
705.2—Alterations Affecting an Area Containing a Primary Function705.2—Alterations Affecting an Area Containing a Primary FunctionException 5 (New) Where an alteration
affects the accessibility to, or contains an area of primary function, the route to the primary function area shall be accessible.
2012 IEBC Fundamentals 122Workbook Page 41
705.2—Alterations Affecting an Area Containing a Primary Function705.2—Alterations Affecting an Area Containing a Primary Function Exception 5 (New) Per the new exception, this provision does
not apply to altered areas limited to Type B dwelling and sleeping units. (See below)
2012 IEBC Fundamentals 123Workbook Page 41
706.3.1 - Bracing for unreinforced masonry bearing wall parapets 706.3.1 - Bracing for unreinforced masonry bearing wall parapets The failure of parapets in unreinforced masonry
(URM) bearing wall buildings has been a recurring problem in areas that experience significant earthquakes.
The code requires these elements to be braced where the seismic hazard is deemed to be relatively high and reroofing work is greater than 25% of the roof area.
1242012 IEBC Fundamentals Workbook Page 41
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 32
706.3.2—Roof Diaphragms Resisting Wind Loads in High-Wind Regions706.3.2—Roof Diaphragms Resisting Wind Loads in High-Wind Regions In level 1 alterations, evaluation criteria for
wind resistance of roof diaphragms have been revised to clarify which parts of the roof connections need to be evaluated in accordance with the wind-load requirements of the IBC.
2012 IEBC Fundamentals 125Workbook Page 41
706.3.2—Roof Diaphragms Resisting Wind Loads in High-Wind Regions706.3.2—Roof Diaphragms Resisting Wind Loads in High-Wind Regions This section was also revised to allow
compliance with only 75% of the wind loads found in the IBC.
2012 IEBC Fundamentals 126Workbook Page 41
Energy Conversation - 707Energy Conversation - 707 Construction related to
the alterations is required to conform to the requirements IECC, or IRC, as applicable.
The entire building is not required to conform to the IECC or IRC energy provisions.
2012 IEBC Fundamentals 127Workbook Page 42
ActivityActivity1. For a ramp slope that is steeper than 1 unit
vertical in 10 units horizontal (1:10) but not steeper than 1 unit in 8 units horizontal (1:8), the maximum rise is _____ inches.
a. 3b. 6c. 9d. 12
1282012 IEBC Fundamentals Workbook Page 43
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 33
ActivityActivity2. For a ramp slope that is steeper than 1 unit
vertical in 12 units horizontal (1:12) but not steeper than 1 unit vertical in 10 units horizontal (1:10), the maximum rise is _____ inches.
a. 3b. 6c. 9d. 12
1292012 IEBC Fundamentals Workbook Page 43
ActivityActivity3. Where replacement of roofing equipment results in
additional dead loads, structural component supporting such reroofing or equipment must comply with the vertical load requirements of the IBC except when structural elements whose stress is not increased by more than _____ percent.
a. 5b. 10c. 15d. 20
1302012 IEBC Fundamentals Workbook Page 43
ActivityActivity4. The maximum height of thresholds at
doorways shall be ¾ inch (19 mm).
True
131
False
2012 IEBC Fundamentals Workbook Page 43
Alterations—Level 2Alterations—Level 2
Module 7Chapter 8:
2012 IEBC Fundamentals 132
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 34
801.3 – Compliance 801.3 – Compliance All new construction related to level 2 alterations
shall comply with the related International Codes, except for the following: Windows that may be added without meeting light
and ventilation requirements of IBC. Electrical equipment that shall comply with Section
808. Length of dead-end corridors in renovated spaces
that shall comply with Section 805.6. Minimum ceiling height in new habitable and
occupiable spaces that shall be 7 feet (2134 mm).1332012 IEBC Fundamentals Workbook Page 46
803.2 - Vertical openings 803.2 - Vertical openings All existing vertical openings connecting two or
more floors must be enclosed with assemblies of 1-hour fire-resistance-rated construction and approved protected openings.
The scoping provisions of Section 803.1 indicate that the enclosure requirements triggered under Level 2 alterations apply only to work areas.
1342012 IEBC Fundamentals Workbook Page 46
803.3 - Smoke Barriers 803.3 - Smoke Barriers The following requirements apply to smoke barriers
in Group I-2 occupancies: Where the work area exceeds 30 patients, the story shall
be divided into a minimum of two compartments by smoke barrier walls.
Each compartment shall not exceed 22,500 square feet (2090 m2)
Travel distance from any point to door in smoke barrier cannot exceed 200 feet (60 960 mm).
Must have a minimum of a 30-minute fire-resistance rated assembly constructed in accordance with the IBC.
1352012 IEBC Fundamentals Workbook Page 46
Fire Protection - 804Fire Protection - 804 Sprinkler requirements apply to the following: Work areas that include exits and corridors shared by
more than one tenant or serving an occupant load more than 30 in
high-rise buildings and all occupancy groups except B, F-2, R-3 and U.
Windowless stories. Other types of suppression systems listed in the IBC.
1362012 IEBC Fundamentals Workbook Page 47
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 35
Fire Protection - 804Fire Protection - 804 Fire alarm and detection systems shall comply
with the following: Fire alarm systems must be installed in work areas of
Use Groups E, I-2 and I-3, and residential care and assisted living facilities I-1, R-2 and R-4 in accordance with the IFC.
Fire alarms systems must be installed throughout R-1 occupancies in accordance with the IFC.
1372012 IEBC Fundamentals Workbook Page 47
Fire Protection - 804Fire Protection - 804 Fire alarm and detection systems shall comply
with the following: Automatic heat detection is not required if the building
is equipped with automatic suppression in accordance with Section 804.2 (work area).
Fire detection systems must be installed in accordance with NFPA 72 (IBC and IFC).
Smoke alarms must be in accordance with the IFC and shall be installed in work areas of Groups R and I-1.
1382012 IEBC Fundamentals Workbook Page 47
804.2.2—Fire Protection Groups A, B, E, F-1, H, I, M, R-1, R-2, R-4, S-1 and S-2804.2.2—Fire Protection Groups A, B, E, F-1, H, I, M, R-1, R-2, R-4, S-1 and S-2
The 2009 IEBC allowed buildings in areas that do not have a municipal water supply capable of supporting an automatic sprinkler system to be exempt from such systems when they are typically required.
2012 IEBC Fundamentals 139Workbook Page 47
Groups A, B, E, F-1, H, I, M, R-1, R-2, R-4, S-1 and S-2Groups A, B, E, F-1, H, I, M, R-1, R-2, R-4, S-1 and S-2 The code changes provide an alternative
to the installation of a new fire pump, with a requirement to at least provide an early warning to occupants using an smoke detection system. The system, once initiated, is required to
activate the occupant notification system in accordance with Sections 907.4, 907.5 and 907.6 of the IBC.
2012 IEBC Fundamentals 140Workbook Page 47
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 36
Section Groups A, B, E, F-1, H, I, M, R-1, R-2, R-4, S-1 and S-2Section Groups A, B, E, F-1, H, I, M, R-1, R-2, R-4, S-1 and S-2 The smoke detection
system would cover all occupiable areas other than dwelling or sleeping units, since such units would be equipped with smoke alarms.
2012 IEBC Fundamentals 141Workbook Page 47
Means of Egress - 805Means of Egress - 805 805.1 – Scope 805.3.1 - Minimum number 805.3.1.2 - Fire escapes required 805.3.2 – Mezzanines 805.3.3 - Main entrance–
Group A
2012 IEBC Fundamentals 142Workbook Page 48
Means of Egress - 805Means of Egress - 805 805.3.3 - Main entrance–Group A 805.4.1 - Two egress doorways required 805.4.2 - Door swing 805.4.3 - Door closing
2012 IEBC Fundamentals 143Workbook Page 48
Means of Egress - 805Means of Egress - 805 805.4.4 - Panic hardware 805.5.1 - Corridor doors 805.6 - Dead-end corridors 805.7 - Means-of-egress lighting 805.9 – Handrails
2012 IEBC Fundamentals 144Workbook Page 49
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 37
ACCESSIBILITY - 806ACCESSIBILITY - 806 Facilities being altered shall comply with this
section and Section 705. New escalators and stairways shall comply with
the IBC. Dwelling units and sleeping units being added in
Group I-1, I-2, I-3, R-1, R-2 or R-4 occupancies shall comply with IBC Section 1107 and Chapter 9 as they apply to the quantity of spaces being added.
1452012 IEBC Fundamentals Workbook Page 50
Structural - 807Structural - 807 807.1 – General 807.3 - New structural
elements 807.4 - Existing
structural members
2012 IEBC Fundamentals 146Workbook Page 50
807.5—Existing Structural Elements Resisting Lateral Loads807.5—Existing Structural Elements Resisting Lateral Loads Rather than having Level 2 alterations
reference the provisions of Level 3 alterations (which are split into two classes, substantial and limited), the revisions move the relevant wind and seismic requirements into the Level 2 provisions.
2012 IEBC Fundamentals 147Workbook Page 50
There is one substantive change to Section 807.5, but it is actually a correction: The 2009 provision refers to Section 1613 of the IBC for seismic loads.
This is inconsistent with the provisions of this code for Level 3 alterations, therefore, the reduced IBC-level seismic forces are used in place of the reference to Section 1613 of the IBC.
2012 IEBC Fundamentals 148
807.5—Existing Structural Elements Resisting Lateral Loads807.5—Existing Structural Elements Resisting Lateral Loads
Workbook Page 50
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 38
Additionally, Section 807.5 also requires that the alteration not create a structural irregularity prohibited by ASCE 7, unless the entire structure complies with the reduced IBC level seismic forces.
2012 IEBC Fundamentals 149
807.5—Existing Structural Elements Resisting Lateral Loads807.5—Existing Structural Elements Resisting Lateral Loads
Workbook Page 50
The creation of a new structural irregularity might not cause element demand-capacity ratios to increase by more than 10 percent, but those irregularities should still be avoided. Structural irregularities in existing
construction need not be eliminated.
2012 IEBC Fundamentals 150
807.5—Existing Structural Elements Resisting Lateral Loads807.5—Existing Structural Elements Resisting Lateral Loads
Workbook Page 50
Activity Activity 1. All new construction elements, components,
systems and spaces must comply with the requirements of the IBC except when the minimum ceiling height of the newly created habitable and occupiable spaces and corridors are _____ feet.
a. 5b. 7c. 9d. 11
1512012 IEBC Fundamentals Workbook Page 52
Activity Activity 2. Where the work area on any floor
exceeds 50 percent of that floor area, the enclosure requirements of Section _____ must apply to vertical openings other than stairways throughout the floor.
803.2
1522012 IEBC Fundamentals Workbook Page 52
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 39
Activity Activity 3. 3. Smoke barriers must be fire-resistance
rated for how many minutes?
30 minutes
1532012 IEBC Fundamentals Workbook Page 52
Activity Activity 4. Fire sprinkler systems shall be
supervised. Name five fire systems that do not require supervision.
154
a. Underground gate valve with roadway boxes
b. Halogenated extinguishing systemsc. Carbon dioxide extinguishing systemsd. Dry and wet chemical extinguishing
systemse. Automatic sprinkler systems installed in
accordance with the NFPA 13R, where a common main is used to supply both domestic and automatic sprinkler systems and a separate shutoff valve for the automatic sprinkler systems is not provided.
2012 IEBC Fundamentals Workbook Page 52
Activity Activity 5. Mezzanines in the work area and with an occupant
load of more than 50, or the travel distance to an exit exceeds 75 feet (22 860 mm) must have access to how many independent means of egress?
a. 1b. 2c. 3d. 4. d. 11
1552012 IEBC Fundamentals Workbook Page 52
Activity Activity 6. Plumbing fixtures for the story must be
provided in quantities specified in the IPC based on the increased occupant load where the occupant load of story is increased by more than _____ percent.
a. 10 b. 20 c. 30 d. 40
1562012 IEBC Fundamentals Workbook Page 53
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 40
Activity Activity 7. When is a main exit required for an
existing Group A occupancy undergoing a level 2 alteration?
a. Occupant load of 100 personsb. Occupant load of 300 personsc. Occupant load of 500 personsd. Occupant load of 1000 persons
a. 1572012 IEBC Fundamentals Workbook Page 53
Alterations—Level 3Alterations—Level 3Chapter 9:
2012 IEBC Fundamentals 158
902.2 - Boiler and furnace equipment rooms 902.2 - Boiler and furnace equipment rooms All boiler and furnace-equipment rooms within
the following must be equipped with fire-rated construction (1-hour): Day nurseries – emergency controls required for
equipment. Children’s shelter facilities – emergency controls
required for equipment. Residential – child care facilities – emergency
controls required for equipment.
1592012 IEBC Fundamentals Workbook Page 56
902.2 - Boiler and furnace equipment rooms 902.2 - Boiler and furnace equipment rooms All boiler and furnace-equipment rooms within
the following must be equipped with fire-rated construction (1-hour): Similar Group I-2 occupancies with children under 2½
years of age – emergency controls required for equipment.
Shelter facilities. Residences for the developmentally disabled
1602012 IEBC Fundamentals Workbook Page 56
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 41
902.2 - Boiler and furnace equipment rooms 902.2 - Boiler and furnace equipment rooms All boiler and furnace-equipment rooms within
the following must be equipped with fire-rated construction (1-hour): Group homes – emergency controls required for
equipment. Teaching family homes – emergency controls
required for equipment. Transitional living homes – emergency controls
required for equipment.
1612012 IEBC Fundamentals Workbook Page 56
902.2 - Boiler and furnace equipment rooms 902.2 - Boiler and furnace equipment rooms All boiler and furnace-equipment rooms within
the following must be equipped with fire-rated construction (1-hour): Rooming and boarding houses. Hotels. Multiple dwellings.
1622012 IEBC Fundamentals Workbook Page 56
Building Elements and Materials – 903 Building Elements and Materials – 903 903.1 - Existing shafts
and vertical openings 903.2.1 - Separation
required
2012 IEBC Fundamentals 163Workbook Page 57
904.1 - Automatic sprinkler systems 904.1 - Automatic sprinkler systems Automatic sprinkler systems shall be installed in
work areas in accordance with Section 804.2 for Level 2 alterations.
More stringent requirements for High Rise buildings and rubbish and linen chutes for Level 3
1642012 IEBC Fundamentals Workbook Page 57
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 42
904.2 - Fire alarm and detection systems 904.2 - Fire alarm and detection systems Fire alarm and detection systems complying with
Sections 804.4.1 and 804.4.3 for Level 2 alterations must be provided throughout the building.
Manual and automatic fire alarm systems are required as applicable to occupancy based upon the requirements in the IBC and IFC.
2012 IEBC Fundamentals 165Workbook Page 57
906.1 – General 906.1 – General Compliance with both
Section 705 and 806 is required
2012 IEBC Fundamentals 166
Accessibility
Workbook Page 58
Where an existing building undergoes a Level 3 alteration that includes altering or adding four or more dwelling or sleeping units, Type B requirements in accordance with Section 1107 and Chapter 9 of the IBC for visible alarms are applicable only to the quantity of the spaces being altered or added.
2012 IEBC Fundamentals 167
906.2—Type B Dwelling or Sleeping Units (New)906.2—Type B Dwelling or Sleeping Units (New)
Workbook Page 58
907.4 - Structural alterations 907.4 - Structural alterations All existing lateral load-resisting structural
elements whose demand-capacity ratio with the alteration considered is more than 10 percent greater than its demand-capacity ratio with the alteration ignored must undergo an engineering evaluation and analysis by a registered design professional, which must be submitted to the code official.
1682012 IEBC Fundamentals Workbook Page 58
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 43
The revision included in Section 907.4.2 expands the time frame in which alterations are required to be counted together for purposes of determining whether the project is big enough to trigger a seismic upgrade from one year to five years.
2012 IEBC Fundamentals 169
907.4.2—Substantial Structural Alteration907.4.2—Substantial Structural Alteration
Workbook Page 58
907.4.2—Substantial Structural Alteration907.4.2—Substantial Structural Alteration
This proposal reduces the possibility that this code is applied such that the trigger is intentionally avoided. For example, by phasing alteration work over three
years, it is possible that a cumulative 89 percent of the floor and roof area could be altered in a nonconforming building, thus avoiding the intended upgrade trigger.
Five years was felt to be a period that is appropriate to the nature of seismic upgrades.
2012 IEBC Fundamentals 170Workbook Page 58
This Section correlates with the revisions to Section 807.5 in that Section 907.4.3 now simply references Section 807.5 for the relevant wind and seismic provisions. Also, rather than repeating the criteria for a
substantial structural alteration, simplified text is provided and substantial structural alteration is described in Section 907.4.2.
2012 IEBC Fundamentals 171
907.4.3—Limited Structural Alteration907.4.3—Limited Structural Alteration
Workbook Page 58
907.4.3 - Limited structural Alteration907.4.3 - Limited structural Alteration A building undergoing limited alterations
(less than that required in Section 907.4.2) with a seismic base shear increase greater than 10 percent, needs comply with Section 807.5
2012 IEBC Fundamentals 172Workbook Page 58
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 44
This change relocates the triggered structural improvement of installation of wall anchors for concrete and masonry buildings from Alterations—Level 1 to Alterations—Level 3 where it is more appropriate.
2012 IEBC Fundamentals 173
907.4.4—Wall Anchors for Concrete and Masonry Buildings907.4.4—Wall Anchors for Concrete and Masonry Buildings
Workbook Page 59
Re-roofing does not make the anchor installation more convenient or cost-effective. In some cases, the Level 1 trigger could
result in disproportionate additional costs, discouraging the rather simple, but important, act of maintaining the roof. Therefore, this building improvement makes
more sense as a Level 3 Alteration.
2012 IEBC Fundamentals 174
907.4.4—Wall Anchors for Concrete and Masonry Buildings907.4.4—Wall Anchors for Concrete and Masonry Buildings
Workbook Page 59
This new section requires the installation of a parapet bracing in buildings undergoing a Level 3 alteration and assigned to Seismic Design Category D, E or F that have parapets constructed of unreinforced masonry whether or not reroofing is involved.
2012 IEBC Fundamentals 175
907.4.5—Bracing for Unreinforced Masonry Parapets (New)907.4.5—Bracing for Unreinforced Masonry Parapets (New)
Workbook Page 59
This change is similar to the current requirements within Alteration—Level 1, Section 706.3.1, except that Section 706.3.1 is only required if a roofing permit is obtained and work exceeds 25 percent of the roof area.
2012 IEBC Fundamentals 176
907.4.5—Bracing for Unreinforced Masonry Parapets (New)907.4.5—Bracing for Unreinforced Masonry Parapets (New)
Workbook Page 59
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 45
Alterations – Level 3Alterations – Level 3 Consider a two-story building where the
rearrangement of several tenant spaces results in the reconfiguration of more than 55 percent of the first floor and 50 percent of the second floor.
2012 IEBC Fundamentals 177Workbook Page 59
Alterations-Level 3Alterations-Level 3
178
Existing First Floor
M W C
M W C
Proposed First Floor
2012 IEBC Fundamentals Workbook Page 60
Alterations-Level 3Alterations-Level 3
179
Existing Second Floor
M W C
M W C
Proposed Second Floor
2012 IEBC Fundamentals Workbook Page 60
Activity Activity 1. Match the following sections
with the statements below:
______ Section 705.1
______ Section 804.2
______ Section 902.1
______ Section 903.2
180
a. Any building having occupied floors more than 75 feet above the lowest level of fire department vehicle access shall comply with the requirements of this section.
b. Automatic sprinkler systems shall be provided in all work areas in accordance with this section.
c. Fire separation in Group R-3 occupancies shall be in accordance with this section.
d. A building, facility or element that is altered shall comply with this section.
d.
b.
a.
c.
2012 IEBC Fundamentals Workbook Page 62
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 46
Activity Activity 2. Means of egress from the highest area
floor to the floor of exit discharge must be provided with artificial lighting within the exit enclosure in accordance with the requirements of which International Code?
IBC
1812012 IEBC Fundamentals Workbook Page 62
ActivityActivity3. Where there is not more than 30 percent
of the total floor and roof areas of the building involved in structural alteration within a 5 year period, what must the evaluation and analysis demonstrate?
182
The evaluation analysis shall demonstrate that the altered building or structure complies with the loads applicable at the time the building was constructed.
2012 IEBC Fundamentals Workbook Page 62
Change of OccupancyChange of Occupancy
Module 9Chapter 10:
2012 IEBC Fundamentals 183
General - 1001 General - 1001 There are three basic types of change of
occupancy: One in which the occupancy classification
changes to a different group. One where the occupancy classification
changes within a group. One where the occupancy classification stays
the same but the level of activity changes.
1842012 IEBC Fundamentals Workbook Page 64
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 47
General - 1001 General - 1001 Triggers in this chapter are predicated on a
change of occupancy to a higher hazard classification and a change in occupancy classification.
A change of use of a historic building must comply with Section 1205.
1852012 IEBC Fundamentals Workbook Page 64
Special Use and Occupancy -1002Special Use and Occupancy -1002 This section
addresses ten special use and occupancy categories.
Any change to one of these occupancies would be required to comply with the provisions of the IBC.
2012 IEBC Fundamentals 186Workbook Page 65
There are new additional requirements for ambulatory care facilities in Section 422 of the IBC. This section adds ambulatory care
facilities to its list of special use or occupancy categories in which a change in character or use of an existing building requires compliance with the IBC.
2012 IEBC Fundamentals 187
1002.1—Compliance with the Building Code1002.1—Compliance with the Building Code
Workbook Page 65
1007.3.1 - Compliance with the IBC level seismic forces1007.3.1 - Compliance with the IBC level seismic forces If the change of occupancy results in higher risk
categories (Table 1604.5 of the IBC) or results in a higher hazard category (Table 1012.4) or where a Group M occupancy is changed to a Group A, E, I-1, R-1, R-2 or R-4 occupancy with at least two-thirds of the floors involved in Level 3 alteration work, the building must comply with the seismic requirements of the IBC, provided one of the exceptions is not met.
1882012 IEBC Fundamentals Workbook Page 65
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 48
TABLE 1012.4TABLE 1012.4MEANS OF EGRESS HAZARD CATEGORIESRELATIVE HAZARD OCCUPANCY
CLASSIFICATIONS1 (Highest Hazard) H
2 I-2, I-3, I-43 A, E, I-1, M, R-1, R-2, R-
44 B, F-1, R-3, S-1
5 (Lowest Hazard) F-2, S-2, U
2012 IEBC Fundamentals 189
2012 IBCPage 50
Workbook Page 67
TABLE 1012.5TABLE 1012.5HEIGHTS AND AREAS HAZARD CATEGORIES RELATIVE HAZARD OCCUPANCY
CLASSIFICATIONS
1 (Highest Hazard) H2 A-1, A-2, A-3, A-4, I, R-1,
R-2, R-43 E, F-1, S-1, M
4 (Lowest Hazard) B, F-2, S-2, A-5, R-3, U
2012 IEBC Fundamentals 190
2012 IEBC Page 51
Workbook Page 67
TABLE 1012.6TABLE 1012.6EXPOSURE OF EXTERIOR WALLS HAZARD CATEGORIES RELATIVE HAZARD OCCUPANCY
CLASSIFICATION1 (Highest Hazard) H
2 F-1, M, S-13 A, B, E, I, R
4 (Lowest Hazard) F-2, S-2, U
2012 IEBC Fundamentals 191
2012 IEBCPage 51
Workbook Page 67
1012.4.1 - Means of egress for change to higher hazard category 1012.4.1 - Means of egress for change to higher hazard category Whenever a change of occupancy classification
is made to a higher hazard category, the means of egress shall comply with Chapter 10 of the IBC.
Exceptions:1. Stairway enclosures shall comply with Section
903.1.2. Existing stairways that comply with Chapter 9 can be
allowed upon approval from the code official.
1922012 IEBC Fundamentals Workbook Page 68
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 49
1012.4.1 - Means of egress for change to higher hazard category 1012.4.1 - Means of egress for change to higher hazard category Exceptions:
3. A new stairway replacing an existing stairway can be built to the previous slope or pitch that impacts the rise height and tread depth if the existing construction that supports or encloses the stairway is such that it makes it impractical to comply with the rise and tread requirements of the IBC.
4. Existing corridor walls constructed of wood lath and plaster or ½-inch (13 mm) gypsum board shall be permitted, provided such construction is in good condition and provides a barrier that inhibits the spread of smoke, heat and fire. an emergency escape opening.
2012 IEBC Fundamentals 193Workbook Page 68
1012.4.1 - Means of egress for change to higher hazard category 1012.4.1 - Means of egress for change to higher hazard category Exceptions:
5. Existing corridor doorways, transoms and other corridor openings shall comply with the requirements in Sections 805.5.1, 805.5.2 and 805.5.3, respectively.
6. Dead-end corridors shall comply with Section 805.6. 7. An existing operable window with clear opening of 4
square feet (0.37 m2), minimum opening height of 22 inches (559 mm) and a minimum opening width of 20 inches (508 mm) shall be acceptable as an emergency escape opening.
2012 IEBC Fundamentals 194Workbook Page 68
An alternative method for subdividing a building into separate buildings with fire barriers and horizontal assemblies has been added. This provides more design flexibility in existing buildings.
2012 IEBC Fundamentals 195
1012.5.1.1—Fire Wall Alterative (New)1012.5.1.1—Fire Wall Alterative (New)
Workbook Page 69
This allowance does come with several required criteria: An NFPA 13 sprinkler system. Equivalent fire-resistance ratings in
accordance with fire wall ratings. A limitation on maximum allowable area that
does not allow an increase for an automatic sprinkler system.
2012 IEBC Fundamentals 196
1012.5.1.1—Fire Wall Alterative (New)1012.5.1.1—Fire Wall Alterative (New)
Workbook Page 69
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 50
Exception: Where horizontal assemblies are used to limit the maximum allowable area, the required fire-resistance rating of the horizontal assemblies is permitted to be reduced by 1-hour reduction provided the sprinkler credit that would otherwise be given for the increase in height and number of stories currently allowed by Chapter 5 of the IBC has not been applied.
2012 IEBC Fundamentals 197
1012.5.1.1—Fire Wall Alterative (New)1012.5.1.1—Fire Wall Alterative (New)
Workbook Page 69
1012.6.3 - Opening protectives1012.6.3 - Opening protectives
Exceptions:1. Where IBC permits openings greater than 50
percent.2. Group R buildings less than four stories in height
and at least 3 feet (914 mm) from the property line do not require protected openings.
3. Sprinklers may substitute for protectives.4. Not required if occupancy is equal or lower
1982012 IEBC Fundamentals Workbook Page 70
1012.7 - Enclosure of vertical shafts1012.7 - Enclosure of vertical shafts Exceptions:
1. For all occupancies other than Group I, an enclosure is not required for stairs serving one adjacent floor and not connected with corridors or stairs from other floors.
2. Stairways that were previously unenclosed are not required to be enclosed if each story has a 1-hour separation (or wired glass in steel frames), and all exit corridors are sprinklered.
3. Existing penetrations of stair enclosures are acceptable if protected as required by the IBC.
1992012 IEBC Fundamentals Workbook Page 70
1012.7 - Enclosure of vertical shafts1012.7 - Enclosure of vertical shafts When a change of occupancy is to a higher
hazard per Table 1012.4, all shafts (other than stairs)must be enclosed in accordance with the IBC.
Exceptions:1. Shafts that have a 1-hour fire rating are acceptable if
a higher rating is required.2. Fully sprinklered buildings, other than Group I, are
not required to have openings enclosed, provided they connect less than six stories.
2002012 IEBC Fundamentals Workbook Page 70
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 51
Exception (New): In accordance with the new exception, a
change of occupancy or group now requires that Type B units be addressed when a change of occupancy involves a Level 3 alteration. This correlates with Chapter 4 of this code and Chapter 34 of the IBC.
2012 IEBC Fundamentals 201
1012 .8—Accessibility1012 .8—Accessibility
Workbook Page 71
Exception: In accordance with the new
exception, when Type B units are required in existing buildings, the accessible features listed in 1012.8.2, Items 1 through 6 are not required for an accessible route to Type B units.
2012 IEBC Fundamentals 202
1012.8.2—Complete Change of Occupancy1012.8.2—Complete Change of Occupancy
Workbook Page 71
Activity Activity 1. What must be issued where a change of
occupancy occurs that results in a different occupancy classification as determined by the IBC?
A certificate of occupancy
2032012 IEBC Fundamentals Workbook Page 73
Activity Activity 2. Buildings subject to a change of
occupancy where such change in the nature of occupancy results in higher uniform or concentrated loads based on Table 1607.4 of the IBC must comply with which provisions of the IBC?
Gravity load provisions
2042012 IEBC Fundamentals Workbook Page 73
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 52
Activity Activity 3. Where the occupancy of existing building
or part of an existing building is changed such that the new occupancy is subject to different kitchen exhaust requirements, the new occupancy must comply with the intent of which International Code?
IMC
2052012 IEBC Fundamentals Workbook Page 73
Activity Activity 4. 4. True or False? An existing building
must comply with all of the applicable requirements of Chapter 10 of the IEBC when an occupancy classification of a building changes, including a change of occupancy classification within a group (i.e. A-3 to A-2).
True
2062012 IEBC Fundamentals Workbook Page 73
AdditionsAdditions
Module 10Chapter 11:
2012 IEBC Fundamentals 207
1102.2 - Area limitations 1102.2 - Area limitations An addition shall not increase the height and
area of an existing building beyond that allowed by the IBC.
Exception: If there is an alteration within a building that includes
closing of floor openings, these are not be considered additions .
If a nonoccupiable appendage, is being added by connecting to the existing exterior wall of an existing building, this would not be considered an addition as it relates to the height and area requirements.
2082012 IEBC Fundamentals Workbook Page 75
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 53
1103.2 - Additional Gravity Loads1103.2 - Additional Gravity Loads
Shall comply with the requirements of the IBC unless the stress is not increased by more than 5 percent or in Group R buildings with no more than five dwelling units or sleeping units.
2092012 IEBC Fundamentals Workbook Page 76
1103.3.1 - Vertical addition 1103.3.1 - Vertical addition Members meet two specific lateral load
requirements; wind load requirements of the IBC and IBC level seismic provisions as specified in Section
301.1.4.1. Any element not meeting these provisions
requires replacement, reinforcement or other measures in order to comply.
2102012 IEBC Fundamentals Workbook Page 76
1103.3.2 - Horizontal addition 1103.3.2 - Horizontal addition A horizontal addition that is isolated from the
existing structure is self-supporting. Where this is not the case, portions of the
existing lateral-force-resisting system affected by the addition, are required to meet two specific lateral load requirements; the wind load requirements of the IBC and the IBC level seismic provisions as specified in Section 301.1.4.1.
2112012 IEBC Fundamentals Workbook Page 76
Structural – 1103 Structural – 1103 1103.3.3 - Voluntary addition of structural
elements to improve the lateral-force-resisting system
1103.4 - Snow drift loads 1103.5 - Flood hazard areas
2122012 IEBC Fundamentals Workbook Page 76
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 54
This section was revised to increase the scope to include all Group l-1 and R occupancies. This aligns with Section 804.4.3 (Alterations—Level 2), as well as Section 907.2.10.3 of the IFC, which addresses smoke alarms in new construction.
2012 IEBC Fundamentals 213
1104.1—Smoke Alarms in Existing Portions of a Building1104.1—Smoke Alarms in Existing Portions of a Building
Workbook Page 77
1105.1 - Minimum requirements1105.1 - Minimum requirements
Additions must comply with accessibility requirements for new construction.
2142012 IEBC Fundamentals Workbook Page 77
Section 1106 is new to the 2012 edition of this code. The new section addresses energy conservation as it relates to additions. More specifically this requirement is essentially a reminder that all new additions need to comply with the International Energy Conservation Code ® (IECC® ) or the International Residential Code ® (IRC® ), as applicable.
2012 IEBC Fundamentals 215
1106—Energy Conservation (New)1106—Energy Conservation (New) Activity Activity
a. Voluntary additions of structural elements to improve the lateral-force-resisting system of a building must comply with this section.
b. b. An addition that affects the accessibility to or contains an area of primary function must comply with the requirement of this section for accessible routes.
216
1. Match the following sections to the applicable statements.
______ Section 705.2
______ Section 807.6
b.
a.
2012 IEBC Fundamentals Workbook Page 79
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 55
Activity Activity 2. The existing building must be provided
with smoke alarms as required by the IBC or the IRC whenever an addition is made to a building or structure of which two group occupancies?
Group RGroup I-1
2172012 IEBC Fundamentals Workbook Page 79
Activity Activity 3. Existing structural elements supporting
any additional gravity loads, as a result of additions must comply with the IBC except when structural elements’ stress is not increased by more than what percent?
5 percent
2182012 IEBC Fundamentals Workbook Page 79
Historic BuildingsHistoric Buildings
Module 11Chapter 12:
2012 IEBC Fundamentals 219
When putting together a report for a historic building in SDC D, E, or F the engineer needs to include a structural evaluation requiring, at minimum, a description of the vertical and horizontal elements of the lateral-force-resisting system and any strengths or weaknesses of that system.
2012 IEBC Fundamentals 220
1201.2—Report1201.2—Report
Workbook Page 81
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 56
The language in the 2009 edition required that the engineer describe a complete load path, whether one was present or not. Further, the term “earthquake resistant
features” was vague and has been deleted.
2012 IEBC Fundamentals 221
1201.2—Report1201.2—Report
Workbook Page 81
Wording in the 2009 edition allowed repairs with original or like materials and original methods of construction.
This was been expanded to specify that the use of hazardous materials, such as asbestos and lead-based paint, that would not be code compliant in new construction, would not be permitted in repairing buildings of similar occupancy, purpose and location.
2012 IEBC Fundamentals 222
1202.1—General1202.1—General
Workbook Page 82
This section was revised to use the term “unsafe” in place of the term “dangerous” as the terms have specific meanings in Chapter 2. Dangerous is specific to
structural issues. Unsafe has a more general
meaning.
2012 IEBC Fundamentals 223
1202.2—Unsafe Conditions1202.2—Unsafe Conditions
Workbook Page 82
Repairs - 1202Repairs - 1202 1202.3 – Relocated buildings Foundations of relocated historic buildings shall
comply with the IBC but the rest of the building shall be permitted to comply with Chapter 12.
1202.4 – Replacement Replacement glazing is required to comply with
Chapter 24 of the IBC Otherwise original materials are permitted for
replacement
2242012 IEBC Fundamentals Workbook Page 82
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 57
Fire Safety – 1203 Fire Safety – 1203 1203.2 – General Historic buildings that constitute a distinct hazard are
required to be sprinklered. Sprinklers can not be used as an alternative to the
required number of exits. 1203.3 – Means of egress Allows narrower openings and when approved by the
code official nased upon actual use. Doors can swing the opposite direction if other
approved means of egress provides sufficient capacity.
2252012 IEBC Fundamentals Workbook Page 82
Fire Safety – 1203 Fire Safety – 1203 1203.4- Transoms Fully sprinklered R-1, R-2, R-3 with existing transoms
can remain in corridors and rated walls if they are closed and sprinklers are located on both sides of the transom.
1203.5 – Interior finishes Historic finishes are allowed but they must be
demonstrated to be historic.
2262012 IEBC Fundamentals Workbook Page 82
Fire Safety – 1203 Fire Safety – 1203 1203.6 – Stairway enclosure In historic buildings 3 stories or less stairway
enclosures are only required to be enclosed by smoke tight doors and solid building elements.
Fire resistance rated construction is not required. 1203.7 – One-hour fire resistant assemblies Wood or metal lath and plaster in good condition can
be considered equivalent to 1 hour fire resistance rated construction.
2272012 IEBC Fundamentals Workbook Page 82
Fire Safety – 1203 Fire Safety – 1203 1203.8 – Glazing in fire resistance rated systems Historic glazing materials are permitted in interior
walls normally required to have a 1 hour fire resistance rated construction when approved smoke seals and the area affected is provided with and automatic sprinklers.
2282012 IEBC Fundamentals Workbook Page 82
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 58
Fire Safety – 1203 Fire Safety – 1203 1203.9 – Stairway railings Grand stairways shall be accepted without complying
with the handrail and guardrail requirements. Handrails and guards are required to be structurally
stable 1203.11 – Exit signs Alternative signs are permitted with approval of the
code official where exit signs would damage the historic character of the building.
2292012 IEBC Fundamentals Workbook Page 82
Alterations– 1204 Alterations– 1204 1204 – Alterations The alteration requirements are focused primarily on
accessibility. Section 705, 806 and 906 apply as applicable unless
technically infeasible. Type B accessible unit requirements are not
applicable for historic structures.
2302012 IEBC Fundamentals Workbook Page 83
Exception (New) Historic buildings
are not required to provide Type B units when undergoing alterations.
2012 IEBC Fundamentals 231
1204.1—Alterations: Accessibility Requirements1204.1—Alterations: Accessibility Requirements
Workbook Page 83
1205 – Change of Occupancy 1205 – Change of Occupancy Historic buildings undergoing a change of
occupancy comply with chapter 10 and Chapter 7, 8 and 9 as applicable unless the provisions of this section allow exceptions to these requirements.
Topics covered including fire protection, means of egress, stair construction, natural light and accessibility.
Accessibility requirements of Section 1012.8 apply unless technically infeasible.
2322012 IEBC Fundamentals Workbook Page 83
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 59
1205.15—Change of Occupancy: Accessibility Requirements1205.15—Change of Occupancy: Accessibility Requirements Historic buildings are
not required to provide Type B units when undergoing a change of occupancy.
2012 IEBC Fundamentals 233Workbook Page 83
1206 – Structural1206 – Structural The structural aspect of existing buildings
should comply with the level of work as classified in Chapter 5.
There is an exception that allows operational controls to limit live loads.
Dangerous conditions are required to be remedied.
2342012 IEBC Fundamentals Workbook Page 83
Unnecessary language has been deleted from this section. In addition, the title is editorially changed
from “unsafe structural elements” to “dangerous conditions” to be consistent with the definitions of “unsafe” and “dangerous” in Chapter 2.
2012 IEBC Fundamentals 235
1206.2—Dangerous Conditions1206.2—Dangerous Conditions
Workbook Page 83
Relocated or Moved Buildings Relocated or Moved Buildings
Module 12Chapter 13:
2012 IEBC Fundamentals 236
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 60
Relocated or Moved BuildingsRelocated or Moved Buildings Relocated or moved buildings are not defined in
the IEBC.
Relocated buildings musty comply with the requirements of the IBC or IRC, whichever is applicable for location on the lot and foundation.
2372012 IEBC Fundamentals Workbook Page 85
The wind upgrade trigger for relocated or moved buildings has been revised to be consistent with those already in Sections 402.4, 403.4, 807.5, 907.4.3 and 1103.3. Over the last several code cycles, all the
lateral triggers have been increased from 5 percent to 10 percent.
2012 IEBC Fundamentals 238
Section 1302.3—Wind LoadsSection 1302.3—Wind Loads
Workbook Page 85
The seismic upgrade trigger for relocated or moved buildings has been revised to be consistent with those already in Sections 402.4, 403.4, 807.5, 907.4.3 and 1103.3. Over the last several code cycles, all the
lateral triggers have been increased from 5 percent to 10 percent.
2012 IEBC Fundamentals 239
Section 1302.4—Seismic LoadsSection 1302.4—Seismic Loads
Workbook Page 85
Chapter 12 Chapter 12 1. What is the intent of Chapter 12 "Historic
Buildings"?
To provide means for the Preservation of historic buildings and still provide an
acceptable level of safety.
2402012 IEBC Fundamentals Workbook Page 86
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 61
Chapter 12 Chapter 12 2. In addition to Chapter 12, which other
chapter of the IEBC must historic buildings undergoing repairs comply with?
Chapter 6
2412012 IEBC Fundamentals Workbook Page 86
Activity Activity 1. Buildings must comply with the IBC or
IRC wind provisions as applicable except when the stress of structural elements are not increased by more than what percent?
10 percent
2422012 IEBC Fundamentals Workbook Page 86
Activity Activity 2. If relocated or moved into a flood hazard
area, structures must comply with what section of the IBC?
Section 1612
2432012 IEBC Fundamentals Workbook Page 86
Performance ComplianceMethods Compliance AlternativesPerformance ComplianceMethods Compliance Alternatives
Module 13Chapter 14
2442012 IEBC Fundamentals
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 62
General - 1401General - 1401 There are 19 categories that are evaluated
including the following: Building height Building area Compartmentation Tenant and dwelling unit separation Corridor walls Vertical openings HVAC systems
2452012 IEBC Fundamentals Workbook Page 87
General - 1401General - 1401 There are 19 categories that are evaluated
including the following: Automatic fire detection systems Fire alarm systems Smoke control Means of egress capacity Dead ends Maximum exit access travel distance Elevator control
2462012 IEBC Fundamentals Workbook Page 87
General - 1401General - 1401 There are 19 categories that are evaluated
including the following: Means of egress emergency lighting Mixed occupancies Automatic sprinklers Standpipes Incidental use area protection
2472012 IEBC Fundamentals Workbook Page 87
1401.1 – Scope1401.1 – Scope To maintain or increase the current degree of
public safety health and welfare in existing buildings while permitting repairs, alterations, additions and changes in occupancy classifications without requiring full compliance with Chapters 4 through 13 or the International Codes for new construction.
2482012 IEBC Fundamentals Workbook Page 88
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 63
General - 1401General - 1401 1401.2 – Applicability 1401.4 - Investigation and evaluation 1401.5 – Evaluation
2492012 IEBC Fundamentals Workbook Page 88
1401.6 - Evaluation process 1401.6 - Evaluation process The evaluation process is required to be
followed in its entirety. All 19 areas are required to be evaluated,
not just a portion of them.
2502012 IEBC Fundamentals Workbook Page 88
1401.9 - Evaluation of building safety1401.9 - Evaluation of building safety The mandatory safety score listed in Table
1401.8 shall be subtracted from the building score entered in Table 1401.7 for each category
The building is in compliance if the final score is equal to or greater than zero.
2512012 IEBC Fundamentals Workbook Page 89
Construction SafeguardsConstruction Safeguards
Module 14Chapter 15
2522012 IEBC Fundamentals
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 64
Construction SafeguardsConstruction Safeguards The building construction process involves a
number of known and unanticipated hazards.
These regulations are intended to supersede the federal regulation known as Occupational Safety and Health Act, as well as state laws with parallel intent.
2532012 IEBC Fundamentals Workbook Page 91
Multi-use StructureMulti-use Structure Purpose: The purpose of this case study is to provide
you with an opportunity to discuss how the 2012 IEBC can be applied in a real-world situation. It will also give you an opportunity to have general discussions concerning the major points of the2012 IEBC. In the case study, you will walk through the phases of site design and development as related to each chapters 6 through 9 of the 2012 IEBC.
2012 IEBC Fundamentals 254Workbook Page 93
Multi-use StructureMulti-use Structure Directions: After you complete an overview of each chapter
of the 2012 IEBC, you will be provided a situation to analyze concerning the case study as it pertains to the topics covered in the particular chapters. Select two or three individuals and form a team. After you read the information, answer the discussion questions provided using the information within the case study and the 2012 IEBC. You should be prepared to share your answers with the entire group.
2012 IEBC Fundamentals 255Workbook Page 93
Multi-use StructureMulti-use Structure Case Study Background Information: An existing 3 story multi-tenant Group B building
in Dublin, Ohio is being converted into a multi-use structure. The building is a 7,500 square feet per floor (687
m2), constructed with masonry exterior walls and concrete floors supported on open web steel joists. Currently the building does not have sufficient
water supply for a sprinkler system without the installation of a new fire pump.
2012 IEBC Fundamentals 256Workbook Page 93
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 65
Multi-use StructureMulti-use Structure Scope of Work Alterations need to be made to 100 percent of
the ground floor; 60 percent of the second floor and 25 percent of the third floor. Additionally, there is a change of occupancy
on the entire first floor from Group B to a restaurant (Group A-2).
2012 IEBC Fundamentals 257Workbook Page 93
Multi-use StructureMulti-use Structure Classification of Work What is the classification of work for this
building?
2012 IEBC Fundamentals 258Workbook Page 93
Multi-use StructureMulti-use Structure Code Compliance Considerations:
Alterations With the Alternations being completed in the
building, what code compliance the owners will need to consider? Building elements and materials Fire Protection Means of Egress
2012 IEBC Fundamentals 259Workbook Page 94
Multi-use StructureMulti-use Structure Code Compliance Considerations:
Alterations With the Alternations being completed in the
building, what code compliance the owners will need to consider? Accessibility Structural Energy Conservation
2012 IEBC Fundamentals 260Workbook Page 94
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 66
Multi-use StructureMulti-use Structure Code Compliance Considerations:
Change of Occupancy With the change in occupancy in the building,
what are the code compliance the owners will need to consider? Structural Electrical Mechanical Plumbing
2012 IEBC Fundamentals 261Workbook Page 94
Multi-use StructureMulti-use Structure Code Compliance Considerations:
Change of Occupancy With the change in occupancy in the building,
what are the code compliance the owners will need to consider? Fire Protection Systems Means of Egress Building Height and Area Enclosure of Vertical Shafts
2012 IEBC Fundamentals 262Workbook Page 94
2012 IEBC® Case Study2012 IEBC® Case Study
Based on the 2012 International Existing Building Code® and the 2012 International Building Code®
The IEBCThe IEBC Encourages the use and reuse of existing
buildings while requiring reasonable upgrades and improvements and extent of the work, not the expense.
2012 IEBC Case Strudy 264
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 67
The IEBCThe IEBC Applicable upgrades and improvements are life-
safety related includes upgrading fire protection systems partially or completely enclosing of the vertical
openings replacing unsafe interior finishing ensuring adequate means of egress improving accessibility and the structural system
2012 IEBC Case Strudy 265
The IEBCThe IEBC It is important to note that the necessity of the
upgrades and/or improvements is determined by the type and extent of the work, not the expense.
2012 IEBC Case Strudy 266
Chapter 11 of the IEBCChapter 11 of the IEBC States that an existing building or structure is not
required to comply with the provisions of Chapter 11 or any of the codes that follow, but an addition to a building or structure shall comply with the provisions of Chapter 11 and the: International Building Code® (IBC®) International Mechanical Code® (IMC®) International Plumbing Code® (IPC®)
2012 IEBC Case Strudy 267
Chapter 12 of the IEBCChapter 12 of the IEBC Applies to preservation of historic buildings,
which addresses the following: Repair Alteration Relocation Change of occupancy
2012 IEBC Case Strudy 268
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 68
Case Study ~ Historical LibraryCase Study ~ Historical Library
2012 IEBC Case Strudy 269
What we know:What we know: The addition consists of: An 880 square foot basement expansion An elevator Accessible restrooms A staff mezzanine
2012 IEBC Case Strudy 270
What we know:What we know: Alteration consists of adding a second means of
egress for all floors and some other miscellaneous alterations.
It has been determined that the library is a contributing building within the proposed boundary increase for the West Chester downtown historical district and a letter has also been submitted by the Pennsylvania Historical Commission.
2012 IEBC Case Strudy 271
Discussion Activity QuestionsDiscussion Activity Questions
1. Will the historical provisions be applicable to this building?
2012 IEBC Case Strudy 272
2012 IEBC 2012 IBCYes. Section 202 definition of historic buildingsincludes buildings that contribute to a historicdistrict. Chapter 12, Historic Buildings, couldbe used.
No. The historic building definition inSection 202 does not include contributingbuildings to a historic district. Section3407 could not be used.
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 69
Discussion Activity QuestionsDiscussion Activity Questions
2. Will a special report be required to be submitted?
2012 IEBC Case Strudy 273
2012 IEBC 2012 IBCDepends on whether the code official finds itnecessary to ask for a report. (Section 1201.2)
No. There are no provisions in Chapter34 to allow the code official to ask for anadditional report.
Discussion Activity QuestionsDiscussion Activity Questions
3. Currently, the building has two exit doors: A 30 inch by 89 inch door
(762 mm by 2261 mm) A 31 inch by 80 inch door
(787 mm by 2032 mm) Are the existing doors required to be widened,
even though a new complying exit door is being provided as part of the alteration project?
2012 IEBC Case Strudy 274
2012 IEBC 2012 IBCThe existing doors are not required to bewidened, as they comply with the capacitybased on occupant load (Even assuming theentire buildings occupant load passes through one of three doors the required width would be 84 X 0.2 = 16.8” for elements other than stairways and 84 X 0.3 = 25.2” for stairways, much below what is already provided at 30” and 31”). However, the code official can require the doors to be widened if in their opinion the doors are not wide enough for a person to pass through. (Section 1203.3)
One or both of the existing doors could possibly be required to be widened ifthey are in the area of alterations or if they will be serving any part of the newadditions. (Section 3403.1)
Discussion Activity QuestionsDiscussion Activity Questions
4. Assuming there will not be a fire barrier constructed between the new library basement addition and the existing basement, will a sprinkler system be required?
If yes, in what parts of the building?
2012 IEBC Case Strudy 275
2012 IEBC 2012 IBC Because the A-3 fire area is being expanded, itis below the level of exit discharge and is notseparated by a fire barrier, a sprinkler system will be required in the entire building. (IEBC Section 1102.3 and IBC Section 903.2.1.3)
Only the basement addition will require asprinkler system. (Sections 3403.1 and903.2.1.3)
Discussion Activity QuestionsDiscussion Activity Questions
5. If the installation of the sprinkler system in the entire building adversely affects the historical character of the building, what might be done?
2012 IEBC Case Strudy 276
2012 IEBC 2012 IBCSeparate the basement addition from the restof the building with fire barriers and horizontalassemblies, then a sprinkler system is required in the addition only. (IEBC Section 1102.3 and IBC Section 903.2.1.3)
An evaluation of the buildings height andarea (with the addition) would need to beperformed as it relates to Chapter 5 of the IBC. (Sections 3403.1 and903.2.1.3)
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 70
Discussion Activity QuestionsDiscussion Activity Questions
6. The handrails and guards at the existing stairs are not in compliance with the current building code. Are the handrails and guards required to be brought up to code?
2012 IEBC Case Strudy 277
2012 IEBC 2012 IBCThe existing handrails and guards can remain as they are as long as they are not structurally dangerous. (Section 1203.9)
The existing handrails and guards canremain as they are as long as they arenot being altered. (Section 3404.1)
Discussion Activity QuestionsDiscussion Activity Questions
7. Are the new handrails and guards required to comply with the IBC?
2012 IEBC Case Strudy 278
2012 IEBC 2012 IBC Yes. (Section 1101.1)
Yes. (Section 3403.1)
279
International Code Council is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members. Certificates of Completion for non-AIA members are available on request.
This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.
2012 IEBC Fundamentals 280
Copyright Materials
This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation without written permission of the speaker is
prohibited.
© International Code Council 2014
2012 IEBC Fundamentals
2012 IEBC Fundamentals 12/11/2017
Copyright 2012 International Code Council 71
Thank you for participating!Thank you for participating!
To schedule a seminar, contact:The Learning Center™
1‐888‐ICC‐SAFE (422‐7233) Ext. 33818or
E‐mail: [email protected]
2012 IEBC Fundamentals 281