3/7/2016 1 1 2014 NEC Changes & NC Amendments Instructors: David Burtt, Don Hursey, Jeff Simpson Class Schedule: 8:00 AM – 9:15 AM NC Amendments. 9:15 AM – 9:30 AM Break. 9:30 AM – 10:30 AM NC Amendments. 10:30 AM – 10:45 AM Break. 10:45 AM – 11:50 AM 2014 NEC Changes. Full class handouts: www.jadelearning.com/class Copyright Jade Learning 2016 2014 NEC Adoption in NC Effective April 1, 2016. With state specific amendments. 2 Copyright Jade Learning 2016
Transcript
Page 1: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

1

1

2014 NEC Changes&

NC Amendments

Instructors: David Burtt, Don Hursey, Jeff Simpson

Class Schedule:

8:00 AM – 9:15 AM NC Amendments.

9:15 AM – 9:30 AM Break.

9:30 AM – 10:30 AM NC Amendments.

10:30 AM – 10:45 AM Break.

10:45 AM – 11:50 AM 2014 NEC Changes.

Full class handouts: www.jadelearning.com/class

Copyright Jade Learning 2016

2014 NEC Adoption in NC

• Effective April 1, 2016.

• With state specific amendments.

2Copyright Jade Learning 2016

Page 2: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

2

NC Amendments

3http://www.ncdoi.com/osfm/engineering_and_codes.aspxCopyright Jade Learning 2016

2014 NC Amendments

2014 NC Electrical Code

110.26(E)(2)(b) Dedicated Equipment Space Outdoors.

The space equal to the width and depth of the equipment, and extending from grade to a height of 1.8 m (6 ft) above the equipment, shall be dedicated to the electrical installation. No piping or other equipment foreign to the electrical installation shall be located in this zone.

• Retaining language from 2011 NEC for 110.26 (E)(2).

4Copyright Jade Learning 2016

Page 3: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

3

NC Amendments2014 NC Electrical Code

210.8(A)(3) GFCI Protection Outdoors:

Exception No. 1 to (3): Receptacles that are not readily accessible and are supplied by a branch circuit dedicated to electric snow-melting, deicing, or pipeline and vessel heating equipment shall be permitted to be installed in accordance with 426.28 or 427.22, as applicable.

Exception No. 2 to (3): A single outlet receptacle supplied by dedicated branch circuit which is located and identified for specific use by a sewage lift pump.

5

EFFECTIVE NOW

Copyright Jade Learning 2016

2014 NC Amendments

2014 NC Electrical Code

210.8(A)(7) GFCI Protection. Sinks. Located in areas other than kitchens where receptacles are installed within 6 ft. of the outside edge of the sink.

• Retaining language from 2011 NEC for 210.8(A)(7).

6Copyright Jade Learning 2016

Page 4: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

4

2014 NC Amendments

2014 NC Electrical Code

210.8(D) Kitchen Dishwasher Branch Circuit.

GFCI protection shall be provided for outlets that supply dishwashers installed in dwelling unit locations.

7Copyright Jade Learning 2016

2014 NC Amendments2014 NC Electrical Code

210.12 Arc-Fault Circuit-Interrupter Protection shall be provided as required in 210.12(A) (B), and (C). The AFCI shall be installed in an readily accessible location (see next slide).

(A) Dwelling Units. All 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling unit

8

kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas, or similar rooms or areas shall be protected by any of the means described in 210.12(A)(1) through (6)...

AFCI protection not required for kitchen or laundry circuits in NC.

Copyright Jade Learning 2016

Page 5: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

5

Accessible Vs Readily Accessible

Copyright Jade Learning 2016 9

Accessible

Readily Accessible

NC Amendments

2014 NC Electrical Code

210.52(I) Dwelling Unit Foyers:

Foyers that are not part of a hallway in accordance with 210.52(H) and that have an area that is greater than 60 ft.² shall have at least one receptacle. located in each wall space 900 m (3 ft) or more in width in a straight dimension and unbroken by corners, doorways, floor-to-ceiling windows and similar openings.

Effective now

10Copyright Jade Learning 2016

Page 6: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

6

NC Amendments2014 NC Electrical Code

250.50 Grounding Electrode System:

All grounding electrodes as described in 250.52(A)(1) through (A)(7) that are present availableat each building or structure served shall be bonded together to form the grounding electrode system.

Where none of these grounding electrodes exist, one or more of the grounding electrodes specified in 250.52(A)(4) through (A)(8) shall be installed and used.

11

EFFECTIVE NOW

Copyright Jade Learning 2016

NC Amendments2014 NC Electrical Code

250.53(A)(2) Supplemental Electrode Required:

A single rod, pipe, or plate electrode shall be supplemented by an additional electrode of a type specified in 250.52(A)(2) through (A)(8).

Exception No. 1: If a single rod, pipe, or plate grounding electrode has a resistance to earth of 25 ohms or less, the supplemental electrode shall not be required.

Exception No. 2: The supplemental grounding electrode shall not be required at a temporary electrical service installation (saw service pole) at a construction site for one and two-family residences, provided the temporary electrical service does not exceed 150 volts to ground or 100 amperes.

EFFECTIVE NOW

12Copyright Jade Learning 2016

Page 7: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

7

2014 NC Amendments

2014 NC Electrical Code

Section 310.15(B)(7) and Table 310.15(B)(7).

Replace the 2014 NEC text from this code section with the 2011 NEC text and Table 310.15(B)(7).

(KEEP THE TABLE)

13Copyright Jade Learning 2016

NC Amendments

2014 NC Electrical Code

334.15(C) In Unfinished Basements and Crawl Spaces:

Where cable is run at angles with joists in unfinished basements and crawl spaces it shall be permissible to secure cables not smaller than two 6 AWG or three 8 AWG conductors directly to the lower edges of the joists. Smaller cables shall be run either through bored holes in joists or on running boards.

14

EFFECTIVE NOW

Copyright Jade Learning 2016

Page 8: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

8

1. Where the conductors enter the switch box through a raceway.

2. Where the switch box is accessible for additional cable without removing finish materials.

3. Where the switch has an integral enclosure, such as those used for doorjamb switches.

4. Where a switch does not serve a habitable room or bathroom, such as in an attic.

2014 NC Electrical Code404.2(C) Switches Controlling Lighting Loads:Grounded conductor required at switch location except:

5. Where there is more than one switch location, such as for 3-way or 4-way switches, and the entire floor area of the room is visible from a single or combined switch locations.

6. Where the lighting in the area is controlled by automatic means, such as a ceiling mounted occupancy sensor.

7. Where a switch controls a receptacle load.

8. Where installed in residential one- and two- family dwellings.

NC Amendments

NC Amendments

16

2014 NC Electric Code

Grounded conductor NOT required for switches that serve lighting loads:

• Applies only to residential one-and two-family dwellings in NC.

• Applies to any switch: Single, 3-way, 4-way.

EFFECTIVE NOW

Grounded conductor NOT

required

White wire re-identified

Copyright Jade Learning 2016

Page 9: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

9

2014 NC Amendments

2014 NC Electrical Code

406.4(D) Replacements. Replacement of receptacles shall comply with 406.4(D)(1) through (D)(6), as applicable.

AFCI type and GFCI type receptacles shall be installed in an readily accessible location.

17Copyright Jade Learning 2016

NC Amendments2014 NC Electrical Code

406.4(D)(4) Arc-Fault Circuit-Interrupter Protection:

Where a receptacle outlet is supplied by a branch circuit that requires AFCI protection as specified elsewhere in this Code, a replacement receptacle at this outlet shall be one of the following:

(1) A listed outlet branch circuit type AFCI receptacle.

(2) A receptacle protected by a listed outlet branch circuit type AFCI type receptacle.

(3) A receptacle protected by a listed combination type AFCI type circuit breaker.

Exception: Non-grounding type receptacle(s).

EFFECTIVE NOW.

18Copyright Jade Learning 2016

Page 10: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

10

2014 NC Amendments2014 NC Electrical Code

422.5 Ground-Fault Circuit-Interrupter (GFCI) Protection.

The device providing GFCI protection required in this article shall be readily accessible.

19

Exception: For one- and two-family residences, the device providing

the GFCI protection required in this article shall be accessible.

Copyright Jade Learning 2016

NC Amendments2012 NC Fuel Gas Code

310.1.1 Corrugated stainless steel tubing (CSST):

CSST gas piping systems shall be bonded to the electrical service grounding electrode system at the point where the gas service enters the building. The bonding jumper shall be not smaller than 6 AWG copper wire or equivalent.

CSST with an arc-resistant jacket listed by an approved agency for installation without the direct bonding, as prescribed in this section, shall be installed in accordance with Section 310.1 and the manufacturer’s installation instructions.

20

EFFECTIVE NOW.

Copyright Jade Learning 2016

Page 11: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

11

NC Amendments

By special permission, additional services shall be permitted for either anyof the following:

(1) Multiple-occupancy buildings where there is no available space for service equipment accessible to all occupants.

21

(2) A single building or other structure sufficiently large to make two or more services necessary. Buildings or other structures large enough to allow each service location to be separated by at least 50 feet, meet the criteria for “sufficiently large.”

EFFECTIVE NOW.

2014 NC Electrical Code

230.2(B) Special Occupancies:

Copyright Jade Learning 2016

NC Interpretations

How?What?Why?What if?

22Copyright Jade Learning 2016

Page 12: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

12

NC Interpretations 210.12(B)Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI)

Question: Are lights and smoke detectors, in addition to receptacles, installed in bedrooms of dwellings required to be AFCI protected?

Answer: All branch circuits supplying 15-and 20-ampere, 125 volt, single phase, outlets in dwelling unit bedrooms shall have AFCI protection that provides protection of the entire circuit.

23

Includes devices

Copyright Jade Learning 2016

NC Interpretations 334.10 (Uses Permitted)

NM Cable Other Than Dwellings

Question:

I have a two story office building permitted to be all wood construction. However, the first floor was designed using all masonry construction just for architectural aesthetic purposes. The inspector is not going to allow Type NM cable now because of the use of concrete and masonry for the first floor. If a building is permitted to be of Types III, IV, or V construction, does it matter what material is used as long as either method is allowed for the entire building?

Answer:

Section 334.10 permits type NM cable to be used in construction where that construction is permitted to be either Type III, IV, or V. Use of masonry on the first floor just as preference does not change that status.

*(See next slide for types of construction.)

24Copyright Jade Learning 2016

Page 13: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

13

NC Interpretations 334.10

25

602.2 Types I and II construction: Building elements are noncombustible.602.3 Type III construction: Exterior walls are noncombustible, interior elements are any material permitted by code.602.4 Type IV construction(Heavy Timber, HT): Exterior walls are noncombustible, interior elements are solid or laminated wood without concealed spaces.602.5 Type V construction:Structural elements, exterior and interior walls are of any materials permitted by code.

Copyright Jade Learning 2016

Important 2014 NEC Code Changes

26Copyright Jade Learning 2016

Page 14: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

14

CODE WIDE: VOLTAGE

Voltage Level: Over 1000 Volts

240, OCPD’s. Over 1000 Volts.

250, Grounding and Bonding.

300, General Requirements for Wiring

Methods and Materials.

430, Motors, Motor Circuits, and

Controllers.

490, Equipment Over 1000 Volts.

690, Solar Photovoltaic (PV) Systems.

692, Fuel Cell Systems.

694, Wind Electric Systems. Copyright Jade Learning 2016 27

100 Definitions. Retrofit Kit.

New term: Retrofit kit

Complete subassembly of parts and

devices for field conversion of

utilization equipment.

TransformersSignsSwitchgear

Panelboards

Motor control buckets

Circuit breakers

Luminaires

Copyright Jade Learning 2016 28

Page 15: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

15

110.16 Arc-Flash Hazard Warning

Required when equipment requires

examination, adjustment, servicing,

or maintenance while energized.

• Switchgear added.

• Label can be field or factory

applied.

Copyright Jade Learning 2016 29

New informational note:

Required markings are for selecting

proper equipment ratings, NOT PPE.

NFPA 70E = safety requirements.

110.24(A) AVAILABLE FAULT CURRENT

Copyright Jade Learning 2016 30

Page 16: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

16

110.25 Lockable Disconnecting Means.

Capable of being locked in open position.

The locking means must remain in place

with or without the lock installed.

Exception: Cord-and plug locking

provisions.

Copyright Jade Learning 2016 31

110.26(C)(3) Spaces about Electrical Equip.

Equipment rated 1200 800 amperes and

more.

Listed panic hardware required for

entry/egress doors within 25’ of workspace.

Panic bars, pressure plates, or other devices

that are normally latched but open under

simple pressure.

Copyright Jade Learning 2016 32

Page 17: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

17

200.4 Neutral Conductors.Must group grounded and ungrounded conductors of the same circuit in any

enclosure.

Exceptions: obvious grouping or pass through a box or conduit body without a

loop, splice or termination.

Copyright Jade Learning 2016 33

210.8(A)(9) GFCI Protection. Bathtubs or Shower Stalls

Bathtub or shower stalls: GFCI

protection required for

receptacles within 6 ft. of

outside edge.

Copyright Jade Learning 2016 34

Page 18: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

18

210.8(A)(10) GFCI Protection. Laundry Areas.

GFCI protection: Required

for 125-volt, single-phase,

15- and 20-ampere

receptacles in dwelling unit

laundry areas.

Copyright Jade Learning 2016 35

210.8(B) GFCI Protection. Other Than Dwelling Units. Exception No. 1. Rooftops.

Outlets on rooftops are

considered readily

accessible from the rooftop.

Copyright Jade Learning 2016 36

Page 19: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

19

210.8(B) GFCI Protection. Other Than Dwelling Units. Garages.

All 15- and 20 amp single-

phase 125 V receptacles in

garages, service bays.

Not required in exhibition halls

or showrooms.

Copyright Jade Learning 2016 37

210.12 AFCI Protection.

The arc-fault circuit interrupter shall be installed in a readily accessible location.

• Kitchen added (Not in NC)

• Laundry added (Not in NC)

Copyright Jade Learning 2016 38

Page 20: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

20

210.12(A)(1)-(6) AFCI Protection.

3 New Methods:

(1)Listed branch/feeder AFCI circuit breaker and OBC type AFCI receptacle

(2)Listed supplemental AFCI circuit breaker with a listed OBC type AFCI receptacle (conditions)

(3)Listed OBC type AFCI device as first outlet with a listed circuit breaker (conditions)

Copyright Jade Learning 2016 39

210.12(B) Exception. AFCI Protection.

• Modifications must be AFCI protected

• New Exception: No AFCI required if circuits not extended more than 6 ft., and no additional outlets or devices are added.

Copyright Jade Learning 2016 40

Page 21: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

21

210.12(C) AFCI Protection. Dormitory Units.

AFCI required in Dorms: 120 V, single-phase, 15- and 20 amp branch circuit outlets.

• Bedrooms

• Living rooms

• Hallways

• Closets

• Similar rooms

Copyright Jade Learning 2016 41

210.17 Electric Vehicle Charging Circuit.

• Any outlets installed for charging electric vehicles require a separate branch circuit.

• No other outlets on circuit.

Copyright Jade Learning 2016 42

Page 22: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

22

210.19(A)(1)Conductors – Minimum Ampacity and Size.

Double Derating is ok

More Than 3 Conductors in Raceway or Cable

Temperature above 86° F

Never Triple Derate

More Than 3 Conductors in Raceway or Cable

Temperature above 86° F

Continuous Load

Copyright Jade Learning 2016 43

• Step 2: 7 current-carrying conductors. What is the adjustment? 70%.

100 amps ÷ .70 = 143 amps (1/0 AWG THWN cu.)

210.19(A)(1)Conductors – Minimum Ampacity and Size.Example: What size THWN cu. conductor is required to supply a 100-amp continuous load when there are 7 current-carrying conductors in conduit:

Step 1: 100 A continuous load = 100 x 125% = 125 A. (1 AWG THWN) cu.

• Step 3: Select the larger of the two conductors.

Copyright Jade Learning 2016 44

Page 23: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

23

210.52(E)(1) Outdoor Dwelling Unit. Receptacles.

• Outlet required at front and back of one-family dwellings

• Readily accessible while standing at grade level from grade

• Not more than 6.5 ft. above grade level

Copyright Jade Learning 2016 45

210.52(E)(3) Balconies, Decks, Porches.

• Balcony, deck, or porch must be attached to dwelling and accessible from inside.

• Receptacle outlet no longer required to be “within the perimeter”.

Copyright Jade Learning 2016 46

Page 24: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

24

210.52(G) Basements, Garages, Accessory Buildings.

• At least one receptacle outlet

for each car space.

• Branch circuit shall not

supply outlets outside of the

garage.

Copyright Jade Learning 2016 47

210.52(G) Basements, Garages, Accessory Buildings.

Copyright Jade Learning 2016 48

Page 25: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

25

210.64 Electrical Service Areas.

• 125 V, single-phase, 15- or 20-

amp receptacle outlet.

• Within 50 ft. of electrical service

equipment.

• N/A for 1 & 2 family dwellings.

Copyright Jade Learning 2016 49

220.12 Lighting Load for Specified Occupancies.

Lighting load can be calculated using energy code IF:

1. Power monitoring system

2. Set with alarm values

3. Demand factors in 220.42 not

applied.

Copyright Jade Learning 2016 50

Page 26: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

26

Hub

230.28 Service Masts as Supports.• Hubs used for service masts must be identified for use with service

masts service-entrance equipment.

• Overhead service conductors cannot be attached to the service mast

between the weatherhead and a coupling in the conduit that is above the

last point of support to the building.

Copyright Jade Learning 2016 51

230.82 Equipment Connected to the Supply Side of Service Disconnect.• Voltage: 1000 volts

• Labeling requirement:

METER DISCONNECT

NOT SERVICE EQUIPMENT

Copyright Jade Learning 2016 52

Page 27: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

27

250.64(B) Grounding Electrode Conductor Installation. Securing and Protection.

• Table 300.5 does not apply to buried

grounding electrode conductors and

grounding electrode bonding jumpers.

Copyright Jade Learning 2016 53

250.66(A)&(B) Connections to a Rod, Pipe, or Plate and Concrete-Encased Electrode(s).

• Grounding electrode conductor to more

than one driven ground rod –not larger

than No. 6 AWG copper.

• Grounding electrode conductor to more

than one concrete-encased electrode – not

larger than No. 4 AWG copper.

Copyright Jade Learning 2016 54

Page 28: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

28

250.68(C) Grounding Electrode Connections.

(3) A concrete-encased electrode of either the conductor type, or rebar installed in accordance with 250.52(A)(3) extended from its location within the concrete to an accessible location above the concrete shall be permitted.

Copyright Jade Learning 2016 55

Table 250.102(C) Grounded Conductor...

• Grounded Conductor

• Main Bonding Jumper

• System Bonding Jumper

• Supply-Side Bonding

Jumper

Copyright Jade Learning 2016 56

Page 29: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

29

250.122(B) Size of Equipment Grounding Conductors. Increased in Size.

Increase equipment grounding

conductor in size ONLY if

ungrounded conductors are

increased in size beyond what is

needed for sufficient ampacity.

Copyright Jade Learning 2016 57

250.130(C) Nongrounding Receptacle Replacement or Branch Circuit Extensions.

Ok to use an equipment

grounding conductor that is part

of another branch circuit

originating in the same enclosure.

Copyright Jade Learning 2016 58

Page 30: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

30

300.11(B)(1) Securing and Supporting.

• The raceway is used to support boxes or conduit bodies in accordance with 314.23 or to support luminaires in accordance with 410.36(E).

• The raceway contains power supply conductors for electrically controlled equipment and is used to support Class 2 circuit conductors or cables that are solely for the purpose of connection to the equipment control circuits.

• The raceway or means of support is identified for the purpose as a means of support.

A raceway can be used as a means of support if:

59Copyright Jade Learning 2016

300.22(C)(1) Other Spaces Used For Environmental Air (Plenums).

• Metallic raceways/wiring methods.

• MI Cable – without nonmetallic covering.

• Cable ties/cable accessories: listed as low smoke and heat release properties.

Copyright Jade Learning 2016 60

Page 31: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

31

Table 310.15(B)(3)(a) Adjustment Factors.

Table now applies to:

• Spare conductors.

• Conductors that cannot be energized simultaneously excluded from adjustment requirements.

Copyright Jade Learning 2016 61

310.15(B)(3)(c) Ex. and Table. Rooftops.

• Table applies to circular raceways raceways or cables.

• Table 310.15(B)(3)(c) does NOT apply to XHHW-2 conductors.

Copyright Jade Learning 2016 62

Page 32: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

32

314.15 Damp or Wet Locations.

Now ok to drill drainage openings not larger than ¼ inch.

Copyright Jade Learning 2016 63

314.25 Covers and Canopies.

No drywall screws for covers.

Must use proper machine screws matching thread gauge of box or screws required in the manufacturer’s instructions.

Copyright Jade Learning 2016 64

Page 33: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

33

314.27(C) Boxes at Ceiling-Suspended (Paddle) Fan Outlets.

• Outlet boxes supporting ceiling fans to be listed for the purpose.

• 2 family dwellings added.

Copyright Jade Learning 2016 65

330.30(D)(3) Securing and Supporting.

Where flexibility is needed:

Interlocked armor type MC cable be unsupported up to 3 ft. from the last point where it is securely fastened.

Copyright Jade Learning 2016 66

Page 34: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

34

334.10 Installation. Uses Permitted.Type NM, NMC, NMS cables can be used as follows: (Except as prohibited in 334.12)

1. One- and two-family dwellings and their attached/detached garages, and their storage buildings.

2. Multi-family dwellings permitted to be of Types III, IV, and V construction. Except as prohibited in 334.12

3. Other structures permitted to be of Types III, IV, and V construction. Cables shall be concealed within walls, floors, or ceilings that provide a thermal barrier that has at least a 15-minute finish rating as identified in listings of fire-rated assemblies. Except as prohibited in 334.12.

4. Cable trays in structures permitted to be Types III, IV, or V where the cables are identified for the use.

5. Types I and II construction where installed within raceways permitted to be installed in Types I and II construction.

Copyright Jade Learning 2016 67

376.22(B) Number of Conductors and Ampacity.

Ampacity adjustment now only required in a

metal wireway if the number of current-

carrying conductors exceeds 30 at any cross

section.

Copyright Jade Learning 2016 68

Page 35: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

35

376.56(B)(5) Power Distribution Blocks.

Conductors shall be arranged so the power distribution block terminals are unobstructed following installation.

Copyright Jade Learning 2016 69

392.20(A)&(B) Multiconductor Cables.

Cables rated 2,000 V

Cables rated 600 V

All cables operate at 480 V.No separation required

Copyright Jade Learning 2016 70

Conductors that operate at over 600 volts must be separated from conductors operating at 600 volts or less if installed in the same cable tray.

Page 36: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

36

Article 393. Low Voltage Suspended Ceiling Power Dist. Systems.New Article

Ceiling grid rails as bus –

distribute low voltage power

through ceiling.

Copyright Jade Learning 2016 71

400.7(A)(11) Flexible Cords and Cables. Uses Permitted.

• Must be a listed assembly, specific for the application.

• The wiring interconnecting the inlet to the single receptacle outlet shall be a Chapter 3 wiring method.

Copyright Jade Learning 2016 72

Page 37: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

37

404.2(C) Switches Controlling Lighting Loads.

1. Where the conductors enter the switch box through a raceway.

2. Where the switch box is accessible for additional cable without removing finish materials.

3. Where the switch has an integral enclosure, such as those used for doorjamb switches.

4. Where a switch does not serve a habitable room or bathroom, such as in an attic.

5. Where there is more than one switch location, such as for 3-way or 4-way switches, and the entire floor area of the room is visible from a single or combined switch locations.

6. Where the lighting in the area is controlled by automatic means, such as a ceiling mounted occupancy sensor.

7. Where a switch controls a receptacle load.

Grounded conductor required at switch location except:

8. In NC, a grounded conductor is not

required for switches controlling lighting loads in one- and two- family

dwellings.

Copyright Jade Learning 2016 73

406.3(E) Receptacle Rating and Type.

Nonlocking, 125 V, 15-20- amperes, controlled by an automatic control device – must be marked with new symbol.

Copyright Jade Learning 2016 74

Page 38: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

38

406.9(B)(1) 15 and 20 Ampere Receptacles in a Wet Location.

Wet locations:

Outlet box hood to be listed and “extra duty”

Copyright Jade Learning 2016 75

406.12 Tamper-Resistant Receptacles.Exceptions now apply to dwelling units, guest rooms and guest suites of hotels and motels, and child care facilities:

1. Receptacles more than 5 ½ ft. above the floor.

2. Receptacles that are part of a luminaire or appliance.

3. A single or duplex receptacle for two appliances located within dedicated space and not easily moved.

4. Nongrounding receptacles used for replacements.

Copyright Jade Learning 2016 76

Page 39: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

39

408.4(B) Field Identification Required.

Switchboards, switchgear, panelboards supplied by feeders (other than 1 or 2 family dwellings).

Must be marked to indicate eachdevice or equipment where the power originates.

Copyright Jade Learning 2016 77

404.10(B) Mounting of Snap Switches.

• Use screws provided with switch or,

• Machine screws with 32 TPI (threads per inch).

Copyright Jade Learning 2016 78

Page 40: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

40

410.10(F) Luminaires Installed Under Roof Decking.

Copyright Jade Learning 2016 79

Luminaires under metal-corrugated roof decking require 1.5 inches between the roof and top of the luminaire.

410.23 Covering of Combustible Material at Outlet Boxes.

Exposed combustible surfaces of 180 sq. in.

or more must be covered with

noncombustible material.

Copyright Jade Learning 2016 80

Page 41: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

41

410.130(G) Disconnecting Means.

Exceptions:

1. Luminaires in hazardous locations.

2. Emergency lighting & exit signs.

3. Cord and plug connected luminaires where the plug and receptacle are accessible.

4. In industrial establishments where conditions of maintenance and supervision ensure that only qualified persons service the installation.

5. If there is more than one luminaire in a space, and there is a way to disconnect the luminaires so that the space cannot be left in total darkness, then each luminaire is not required to have a disconnecting means.

Fluorescent luminaires that use double ended lamps.

Copyright Jade Learning 2016 81

422.5 GFCI Protection.

The device providing the GFCI

protection for appliances must be

readily accessible.

Copyright Jade Learning 2016 82

Page 42: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

42

422.19, 422.20 Space for Conductors.

• Capacity of fan canopy and outlet box

can be added.

• Cover required for outlet box.

• Any exposed combustible ceiling between

fan canopy and outlet box covered with

noncombustible material.

Copyright Jade Learning 2016 83

422.23 Tire Inflation and Automotive Vacuum Machines.

• GFCI protection required for

tire inflation and auto vacuum

machines for public use.

• Not voltage specific.

Copyright Jade Learning 2016 84

Page 43: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

43

422.51 Vending Machines.

• GFCI protection required

• Directly wired

• Cord-and-plug connected

• Not voltage specific

Copyright Jade Learning 2016 85

424.66(A)&(B) Duct Heaters. Installation.• Duct heaters above a ceiling

• Equipment to be accessible by ceiling tiles or access panels.

• Work space to be 30 in. wide or the width of the equipment, whichever is greater.

• Access panels/doors on equipment must open at least 90°.

• Depth of working space in front of the equipment is to comply with the requirements of Table 110.26(A)(1).

Copyright Jade Learning 2016 86

Page 44: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

44

445.11 Generators. Marking.

To be marked by the

manufacturer to specify

whether or not the

generator neutral is bonded

to the generator frame.

Copyright Jade Learning 2016 87

445.18 Disconnecting Means Required for Generators.• Disconnecting means

• Lockable in OFF position

• Not required if:

The driving means for the generator can be readily shut down, is rendered incapable of restarting, and is lockable in the OFF position in accordance with 110.25.

The generator is not arranged to operate in parallel with another generator or other source of voltage.

Copyright Jade Learning 2016 88

Page 45: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

45

Cannot be installed on or over any vented portion of the enclosure

450.10(A) Grounding. Dry-Type Transformer Enclosures.

A terminal bar for equipment grounding conductors and SSBJ’s at terminal bar mounted inside the transformer enclosure.

Copyright Jade Learning 2016 89

450.11(B) Source Marking.

A transformer can be supplied

at the marked secondary

voltage (BACKFED) if installed

in accordance with the

manufacturer’s instructions.

Copyright Jade Learning 2016 90

Page 46: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

46

590.4(D)(1) Receptacles in Wet Locations.Temporary installations will now also require “extra duty” covers for 15-and 20-ampere 125- and 250- volt receptacles in wet locations.

Copyright Jade Learning 2016 91

590.4(I) Termination(s) at Devices.

Fittings need to be listed for the

purpose of connecting flexible

cords and cables to boxes.

Copyright Jade Learning 2016 92

Page 47: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

47

590.4(J) General. Support.

Temporary wiring:

• Must be supported in place.

• Protected from physical damage.

• Shall not be installed on floor or ground.

Copyright Jade Learning 2016 93

590.4(J) General. Support.

Copyright Jade Learning 2016 94

Page 48: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

48

600.6(A)(1) Disconnects. At Point of Entry.

A sign disconnect is required at

the point the feeder circuit or

branch circuit(s) enters the sign

enclosure.

Copyright Jade Learning 2016 95

680.21(C) Motors. GFCI Protection.

All 15 and 20-amp single-phase, 120 through 240 volt branch circuits that supply pool pump motors are required to be GFCI protected.

Copyright Jade Learning 2016 96

Page 49: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

49

680.22(A)(1) Receptacles. Required.

Dwellings All locations

At least one, GFCI protected, 125 V,

15- or 20- amp receptacle

Location:

At least 6 ft. from pool

Not more than 20 ft.

Not more than 6 ½ ft. above

grade/deck level.

Copyright Jade Learning 2016 97

680.42(B) Outdoor Installations. Bonding.

• It must be self-contained and listed for aboveground use.

• It cannot be identified for indoor use only.

• It must be installed according to the manufacturer’s instructions.

• The top rim of the tub must be a minimum of 28 inches above any surface that extends up to 30 inches horizontally from the spa or hot tub.

Copyright Jade Learning 2016 98

No bonding grid required for hot tub if all conditions apply:

Page 50: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

50

690.5(A) Ground-Fault Protection.

Ground-fault protection devices must detect a ground fault in the

PV array, interrupt the flow of fault current, provide indication of

the fault, and be listed.

Copyright Jade Learning 2016 99

690.12 Rapid Shutdown of PV Systems on Buildings.• Rapid shutdown required.

• Must reduce voltage on PV conductors more

than 5 ft. (inside building) or more than 10

ft. from array.

• Voltage reduced to 30 volts or less within

10 seconds.

Copyright Jade Learning 2016 100

• If the building has a utility service, a permanent plaque must be posted:

PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN.

Page 51: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

51

690.15(C) Direct-Current Combiner Disconnects.

Combiner: A device used in the PV source and

PV output circuits to combine two or more DC

circuit inputs and provide one DC circuit output.

DC Disconnects for outputs of DC combiners on

roofs.

• Must be load break rated.

• In combiner or within 6 ft. of the combiner

Copyright Jade Learning 2016 101

700.12(F) Emergency Systems. Unit Equip.

The exception has been changed to allow a separate branch circuit to the emergency lighting only if the normal branch circuits that supply lighting to the area are NOT part of a multwire branch circuit.

Copyright Jade Learning 2016 102

Page 52: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

52

700.19 Emergency Systems. Multiwire Branch Circuits.

The branch circuit serving

emergency lighting and

power circuits shall not be

part of a multiwire branch

circuit.

Copyright Jade Learning 2016 103

702.7(C) Optional Standby Systems. Power Inlet.

• Sign required.

• Identifies type of generator that can be connected to the power inlet.

Copyright Jade Learning 2016 104

Page 53: 2014 NEC Adoption in NC - Jade Learning · 2018. 4. 18. · 3/7/2016 12 NC Interpretations 210.12(B) Arc-Fault Circuit-Interrupters in Bedrooms of Dwellings (AFCI) Question: Are lights

3/7/2016

53

105

QUESTIONS?

2 YEARS CREDIT FOR ONLY $200!

• Go online to www.Jade1.com

• Take any 2 electrical courses

• Use your discount code to

get $25 off each course!

• 2014 NEC Changes & NC Amendments

Copyright Jade Learning 2016


Recommended