www.magnaiv.com
Canada
United States
Chile
Engineering & Technical Field Services
CARGILL LIMITED
2016 Transformer Oil Sampling
and
Analysis
June 7, 2016 File: C3330-10
Project Manager: George Shehata, P.Eng.
Superior client serv ice. Electrical confidence.
1103 Parsons Road SW
Edmonton, AB T6X 0X2
p 780.462.3111 f 780.462.9799 tf 800.462.3157 Superior client serv ice. Electrical confidence.
www.magnaiv.com
Canada
United States
Chile
Engineering & Technical Field Services
File: C3330-10
June 28, 2016
CARGILL LIMITED
801 LOW LEVEL ROAD
NORTH VANCOUVER, BC V7L 1A7
Attention: Mr. Ron Ludwig
Supervisor, Electrical
Dear Sir:
Re: Oil Sampling and Analysis – North Vancouver Facility
We are pleased to submit the insulating fluid report and test sheets for the three (3) transformers
and one (1) OCB located at the North Vancouver facility. The transformer sampling was
performed by James Powell on June 7, 2016 in accordance with ASTM D923 and D3613
standards. The laboratory testing was completed by The Chemlab of Calgary. Review of results
and analysis was provided by the undersigned.
Based on the analysis of the laboratory results, all equipment is in good condition and suitable
for continued service. Once again, both the East and West transformers are showing elevated
Ethylene indicating higher temperature internal heating however, since there has been no
significant generation and all other dissolved gases and standard fluid quality tests are within
IEEE acceptable limits for in-service equipment, the units are of no immediate concern. Annual
sampling is highly recommended to monitor any further generation. The Sub 2 transformer is
filled with Natural Ester (FR3) – it appears there is elevated Ethane however, the limits indicated
are for mineral oil only. Natural ester generates Ethane under normal operation (test limit is
400PPM) therefore the current value is within acceptable limits. In addition, the interfacial
tension appears low however, the test limit is 18 for Natural ester. As such all values meet the
recommended test limits for natural ester. The OCB is showing all dissolved gases and tested
fluid quality properties to be within acceptable limits. All equipment is classified as category
Type 1. Equipment in this category shows acceptable test results, with some showing minor
elevated gas levels. Close observation of dissolved gases in the oil, along with the fluid quality
properties, provides the most valuable information about your equipment health. All units are
recommended for annual resampling with electrical tests performed at 2 year intervals. This
testing schedule will allow us to maintain a comprehensive trend of all properties, and provide
accurate analysis on the condition and operational reliability of your equipment. Please see
Section 3.0 – Summary of Results and Deficiencies for a complete breakdown.
Via: email
fax
3 | Pa ge
We trust this report meets with your approval and requirements. Should you need further
information or assistance, please do not hesitate to contact us. Thank you for retaining the
services of Magna IV Engineering. We look forward to being of service to you again in the future.
Yours Truly,
MAGNA IV ENGINEERING
Stephanie Parsons
Oil Analysis Project Manager
4 | Pa ge
INDEX
1.0. SCOPE OF WORK .......................................................................................................................... 5
2.0. SUMMARY OF TESTS ....................................................................................................................... 6
3.0. SUMMARY OF RESULTS AND DEFICIENCIES ................................................................................ 8
4.0. TEST RESULTS ................................................................................................................................... 9
5 | Pa ge
1.0. SCOPE OF WORK
As per Magna IV Engineering’s standard practices for transformer oil sampling, our scope of work consisted of:
Providing Transformer Inspection
Recording Nameplate Data
Reading and resetting Gauges
Providing Inspection Report
Procurement of oil samples in accordance with ASTM D923 & D3613
- obtain one syringe for gas-in-oil analysis & moisture content
- obtain bottle sample for fluid quality tests
The Chemlab of Calgary performs all analytical tests, consisting of:
Gas Analysis (DGA) D-3612
Moisture Content D-1533B
Interfacial Tension D-971
Acid Number D-974
Color Number D-1500
Visual Examination D-1524
Dielectric Breakdown D1816 @ 1mm
The Chemlab is responsible for proper disposal of samples.
Analysis of Laboratory results by Magna IV Engineering. Tools utilized:
Duval Triangle
GA Key Gas Method
DGA Rogers Ratio Method
DGA Cellulose
DGA IEEE/ANSI
Specific History and Trending (Generation vs. Time)
Document, interpret and evaluate results, and recommend corrective or follow up
action.
Prepare traditional summary sheets and lifetime trending graphs.
Prepare report detailing findings, recommendations and corrective action as
required.
6 | Pa ge
2.0. SUMMARY OF TESTS
For your reference and confirmation of the specific tests performed and their analytical
value, we provide the following highlight information. All transformer tests were
performed as per the latest ASTM standards.
Specific tests performed include:
ASTM D1816 - Liquid Dielectric Test
The dielectric breakdown voltage of an insulating liquid is important as a measure of
the liquid’s ability to withstand electric stress without failure. It serves to indicate the presence of contaminating agents, such as water, dirt, moisture, cellulosic fibers or
conducting particles in the liquid, one or more of which may be present in significant
concentrations when low dielectric breakdown values are found by test. However, a
high dielectric breakdown voltage does not indicate that the concentrations of
contaminants that are present in the liquid between the electrodes are not large
enough to negatively affect the average breakdown voltage of the liquid when
tested by this method.
ASTM D971 - Interfacial Tension
This method has been shown by practice to give a reliable indication of the presence
of hydrophilic compounds. When certain contaminants such as soaps, paints
varnishes and oxidation products are present in the oil, the film strength of the oil is
weakened, thus requiring less force to rupture. For oils in service, a decreasing value
indicates the accumulation of contaminants and oxidation products, which may
attack the insulation and interfere with the cooling of transformer windings.
ASTM D1533 - Moisture Content
The electrical characteristics of an insulating liquid are deleteriously affected by its
water content. A high water content may make a dielectric liquid unsuitable for some
applications because a deterioration in properties such as dielectric breakdown
voltage may occur. This test is suitable for use in acceptance specifications, in control
of processing and in evaluating the condition of dielectric liquids in service.
ASTM D974 - Neutralization Number
The acid number of an oil is a measure of the amount of acidic materials present. As
oils age in service the acidity, and therefore the acid number, increases. A used oil
having a high acid number indicates the oil is either oxidized or contaminated with
materials such as varnish, paint or other foreign matter. This test serves as an indicator
of the potential of the oil to form sludge.
ASTM D1500 – Color Number
The color of a new oil is generally accepted as an index of the degree of
refinement. For oils in service, an increasing or high color number is an indication of
contamination, deterioration or both.
7 | Pa ge
ASTM D3612 - Dissolved Gas Analysis
Gas analysis is based upon the fact that both electrical insulating oil and cellulosic
insulation break down under abnormal thermal or electrical stress. The results of these
stresses are both volatile and non-volatile gases, known as fault gases. Gas analysis is
the technique that identifies fault gases, relates their quantity, generation rate and
relevant ratios to type and severity of fault.
Typical fault gases analyzed are:
Hydrogen H2
Methane CH4
Ethane C2H6
Ethylene C2H4
Acetylene C2H2
Carbon Monoxide CO
Carbon Dioxide CO2
Typical types of transformer problems that can be detected are:
thermal degradation
- low temperature
- high temperature (hot spot)
arcing
partial discharges
degradation of paper insulation
Increased frequency or periodic testing will significantly increase the value and
accuracy of fault gas analysis.
8 | Pa ge
3.0. SUMMARY OF RESULTS AND DEFICIENCIES
Transformers typically can be broken down into the following categories:
Type 1 Transformers in this category show acceptable test results, with a few
transformers showing signs of minor non-serious overheating (re-test
recommended in one year). Variations of Type 1 transformers may exist
pending past records and age of units.
Type 2 This category covers any transformer showing test results where some concern
is evident (re-test recommended in six months).
Type 3 Transformers in this category show signs of serious fault gas concentrations or
very poor chemical properties (prompt re-tests or further investigations are
required).
Type 4 Mechanical deficiencies (corrective action to be taken as soon as possible or
as recommended).
Please refer to the test sheets (5 pages) for a detailed breakdown of results and
recommendations. Following is the Summary of Results and Deficiencies.
Transformer
Identification /
Serial Number
Year
Manufactured
Analysis
Type
Recommended
Retest Comments
East TX
293639
1967 1 1 Year
Slight elevation in Ethylene – higher
temperature internal heating – no
immediate concern. All other dissolved
gases and tested fluid properties within
acceptable limits. Annual sampling highly
recommended to monitor any further
generation. Check loading conditions and
cooling means. No major deficiencies
noted.
West TX
293638
1967 1 1 Year
Slight elevation in Ethylene – higher
temperature internal heating – no
immediate concern. All other dissolved
gases and tested fluid properties within
acceptable limits. Annual sampling highly
recommended to monitor any further
generation. Check loading conditions and
cooling means. No major deficiencies
noted.
Sub 2
1059001354
2010 1 1 Year
All dissolved gases and standard fluid quality
properties within acceptable limits for
Natural Ester Insulating fluid. Annual
sampling should be maintained. No major
deficiencies noted.
6OCB1
60503
1967 1 1 Year
All dissolved gases and standard fluid quality
properties within acceptable limits showing
no significant change. Annual sampling
should be maintained. No major
deficiencies noted.
9 | Pa ge
4.0. TEST RESULTS
Following is a copy of all individual test results. We recommend you review the results
and graphs at your convenience to better understand our analysis and the condition of
your equipment.
Each piece of equipment consists of the following 4 pages of documentation:
Page 1 Transformer nameplate, identification name, oil and gas results and any
notable comments and deficiencies.
Pages 2&3 Graphs for all generated gases and chemical analysis tests. This provides a
more visual idea of determining the trending of these gases. All limits are
based upon standards widely accepted throughout the industry.
Page 4 Inspection sheet, nameplate data, gauge recordings.
Cargill Terminal
East - TX
S/N: 293639
C3330-10
Oil & Gas Results
Nameplate Information
Cargill Limited
Cargill TerminalFluid Test Report
Maintenance
Nameplate Information
Serial Number: 293639
Sample Date:
Job Number:
Nitrogen (N₂)
Total Dissolved Combustible Gas
Total Gas Content (%)
kVA Rating: 4000
Fluid Type: OIL
Designation: East - TXkV Rating: 72.000/0.575
Dissolved Gas Analysis
Fluid Quality Analysis Limits
Additional Fluid Quality Tests
Notes:
D3612-C
Apparatus Type: TRN Manufacturer: WESTINGHOUSE
Year Manufactured: 1967 Fluid Capacity (G): 750
Expressed in PPM
Voltage Class >69kV - <230kV
Hydrogen (H₂)
Methane (CH₄)
Ethane (C₂H₆)
Ethylene (C₂H₄)
Acetylene (C₂H₂)
Carbon Monoxide (CO)
Carbon Dioxide (CO₂)
100
120
65.0
50.0
2.0
1000
10000
Limits
Moisture Content D1533 (ppm)
Interfacial Tension D971 (mN/m)
Acid Number D974 (mg KOH/g)
Color Number D1500 (Relative)
Visual Examination D1524 (Relative)
Dielectric Breakdown @ 1mm D1816 (kV)
Dielectric Breakdown D877 (kV)
25
30.0
0.150
3.5
CLEAR
28
26
PCB D4059 (ppm)
Specific Gravity D4052 (Relative)
Power Factor @ 25°C D924 (%)
Oxidation Inhibitor D2668 (%)
2.0
0.91
0.5
0.08 - 0.3
Limits
Power Factor @ 100°C D924 (%) 5.0
Oxygen (O₂)
16
31.8
33
0.018
L1.5
CLEAR
17
32.4
40
0.022
1.5
CLEAR
4
29000
66800
3
146
7180
3.2
62.0
0.0
218
10.320
5
27500
71200
3
194
7550
3.1
58.2
0.0
263
10.660
Jun-7-2016
C3330-10
Jun-10-2015
C3330-7
- 3.7
Page 1 of 3Serial Number: 293639Magna IV Engineering
Cargill Limited
Cargill TerminalFluid Test Report
Maintenance
Historic Graphs and Diagnostic Charts
Combustible Gases
Total Gas Content (%)
(All Gases)
0
2
4
6
8
10
12
Ju
n-1
6
Ju
n-1
5
Key Gas Comparison (ppm)
0
20
40
60
80
100
120
140
160
CO - H2 - Meth - Eth - Ethy - Ace
Methane (CH4)
0
0.5
1
1.5
2
2.5
3
3.5
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Ethane (C2H6)
0
0.5
1
1.5
2
2.5
3
3.5
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Acetylene (C2H2)
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Ethylene (C2H4)
0
10
20
30
40
50
60
70
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Hydrogen (H2)
0
1
2
3
4
5
6
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Carbon Monoxide (CO)
0
50
100
150
200
250
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Non-Combustible Gases
Carbon Dioxide (CO2)
0
1000
2000
3000
4000
5000
6000
7000
8000
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Nitrogen (N2)
0
10
20
30
40
50
60
70
80
Ju
n-1
6
Ju
n-1
5
Thousands
Pa
rts
Pe
r M
illio
n
Oxygen (O2)
0
5
10
15
20
25
30
35
Ju
n-1
6
Ju
n-1
5
Thousands
Pa
rts
Pe
r M
illio
n
Page 2 of 3Serial Number: 293639Magna IV Engineering
Cargill Limited
Cargill TerminalFluid Test Report
Maintenance
Fluid Analysis
Moisture Content
(Should be <Limit)
0
5
10
15
20
25
30
Jun
-16
Jun
-15
Pa
rts
Pe
r M
illio
n
Interfacial Tension
(Should be >Limit)
0
5
10
15
20
25
30
35
Jun
-16
Jun
-15
mN
/m
Acid Number
(Should <Limit)
0
0.02
0.04
0.06
0.08
0.1
0.12
0.14
0.16
Jun
-16
Jun
-15
mg
KO
H/g
Color Number
(Should be <Limit)
0
0.5
1
1.5
2
2.5
3
3.5
4
Jun
-16
Jun
-15
Dielectric Breakdown D877
(Should be >Limit)
Actual Values
Acceptable Limits
Dielectric Breakdown D1816
(Should be >Limit)
0
5
10
15
20
25
30
35
40
45
Jun
-16
Jun
-15
kV
Page 3 of 3Serial Number: 293639Magna IV Engineering
/
WEIGHT
TEMP RISE
PSI
�
PO# for Sampling Lab:
REPORT RUSH:
� DGA D3612C � Dielectric 1.0mm D1816 Oxidation Inhibitor D2668 NOTES:
� Moisture in Oil D1533B Dielectric 2.0mm D1816 Furfurals (paper degradation) 1. NO WINDING TEMP GAUGE
� Interfacial Tension D971 Power Factor 25°C D924 Metals D3635ICP TRANSFORMER IS IN A VAULT
� Acid Number D974 Power Factor 100°C D924 Viscosity D88
� Color/Visual D1500, D1524 Specific Gravity D1298 Other:
Dielectric 2.5mm D877 PCB
BREATHERS
�
GAUGE DOCUMENTATION
DESCRIPTION YES DESCRIPTION OK
�
DUSTY
40 °C
COMMENTS
NITROGEN ADDED
NO
RADIATORS INSTALLED
CONSERVATOR TANK
BLUE
HV BUSHINGS ACCESSIBLE HV BUSHING CONDITION �
RELIEF VALVE INSTALLED
�
GROUNDING (2 LOCATIONS) �
PHYSICAL DAMAGE
NO
DIRT ACCUMULATION
750
PROPER LEVEL
NO
OIL LEAKS (WHERE)
DUSTY
FAIL
CORROSION / RUST ACCUMULATION � PAINT IS GOOD
� DUSTY
COMMENTS
3.7 PPM
LV BUSHING CONDITION �
DM 635 1006975
RADIATOR CONDITION N/A
50 °C
� SILICA DESICANT CONDITION �
�
�
NO
INSPECTIONS
�
CRITERIA
�
ADEQUATE CLEARANCE
TANK PRESSURE (Min: -1 Psi (-6.89 kPa))
�
LOW OIL LEVEL (GAUGE @ LOW)
LV BUSHINGS ACCESSIBLE
�
Tests Required (Internal Purposes Only)
CRITERIAYES
Sampler: JMP
78 %
27.0 °C
BOTTOM VALVE
Syringe #:
�
KPA
READING
SEE DIAGRAM AT RIGHT
HUMIDITY
AMB. TEMP
SEDIMENT
SAMPLE POINT
� OK
SO# 293639 AMPS
PRE-SAMPLING CHECKLIST
CAPACITY GALSLTRS
NO
RESET GAUGE
OIL LEVEL
PRESSURE
GAUGE READING DRAGHAND
OIL TEMP
N/A
SAMPLE COLOR
SAMPLE DATA
NO
YES / NOWINDING TEMP
ONAN SEC VOLTS 575 %IMPED
WESTINGHOUSE PRI VOLTS 72KV 3 3
PREPARED FOR
CARGILL
AREA
SITE
WO#
MAIN SUB
CARGILL TERMINAL
C3330-10 DATE
TEST BY
APPROVED BY
EAST TX
JMP
STANDARD MAINTENANCE
OIL FILLED EQUIPMENT INSPECTION SHEETTAG #
CANF-5E006
LEMON YELLOW
STRAW YELLOW
STRAW WHITE
BROWN
REDDISH ORANGE
ORANGE BLACK
OTHER:
OIL TYPE MINERAL SYSTEM BREATHING
DATE OF LAST OIL CHANGE (IF KNOWN) UNKNOWN
NAMEPLATE DATA
June 7, 2016
PCB CONTAMINATED
# OF TAPS
TAP FOUND/LEFT
YES
5EQUIPMENT TX KVA 4000
MANUF.
YEAR 1967
3.70%TYPE
East Tx Oil Filled Equipment Inspection Page 1 of 1
Cargill Terminal
West - TX
S/N: 293638
C3330-10
Oil & Gas Results
Nameplate Information
Cargill Limited
Cargill TerminalFluid Test Report
Maintenance
Nameplate Information
Serial Number: 293638
Sample Date:
Job Number:
Nitrogen (N₂)
Total Dissolved Combustible Gas
Total Gas Content (%)
kVA Rating: 4000
Fluid Type: OIL
Designation: West - TXkV Rating: 72.000/0.575
Dissolved Gas Analysis
Fluid Quality Analysis Limits
Additional Fluid Quality Tests
Notes:
D3612-C
Apparatus Type: TRN Manufacturer: WESTINGHOUSE
Year Manufactured: 1967 Fluid Capacity (G): 750
Expressed in PPM
Voltage Class >69kV - <230kV
Hydrogen (H₂)
Methane (CH₄)
Ethane (C₂H₆)
Ethylene (C₂H₄)
Acetylene (C₂H₂)
Carbon Monoxide (CO)
Carbon Dioxide (CO₂)
100
120
65.0
50.0
2.0
1000
10000
Limits
Moisture Content D1533 (ppm)
Interfacial Tension D971 (mN/m)
Acid Number D974 (mg KOH/g)
Color Number D1500 (Relative)
Visual Examination D1524 (Relative)
Dielectric Breakdown @ 1mm D1816 (kV)
Dielectric Breakdown D877 (kV)
25
30.0
0.150
3.5
CLEAR
28
26
PCB D4059 (ppm)
Specific Gravity D4052 (Relative)
Power Factor @ 25°C D924 (%)
Oxidation Inhibitor D2668 (%)
2.0
0.91
0.5
0.08 - 0.3
Limits
Power Factor @ 100°C D924 (%) 5.0
Oxygen (O₂)
13
32.3
39
0.014
L2.0
CLEAR
7
32.8
36
0.014
2
CLEAR
7
28300
74300
5
212
4880
4.3
71.9
0.0
300
10.780
8
24300
68400
5
231
4640
4.1
64.8
0.0
313
9.770
Jun-7-2016
C3330-10
Jun-10-2015
C3330-7
- 6
Page 1 of 3Serial Number: 293638Magna IV Engineering
Cargill Limited
Cargill TerminalFluid Test Report
Maintenance
Historic Graphs and Diagnostic Charts
Combustible Gases
Total Gas Content (%)
(All Gases)
0
2
4
6
8
10
12
Ju
n-1
6
Ju
n-1
5
Key Gas Comparison (ppm)
0
50
100
150
200
250
CO - H2 - Meth - Eth - Ethy - Ace
Methane (CH4)
0
1
2
3
4
5
6
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Ethane (C2H6)
0
1
2
3
4
5
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Acetylene (C2H2)
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Ethylene (C2H4)
0
10
20
30
40
50
60
70
80
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Hydrogen (H2)
0
1
2
3
4
5
6
7
8
9
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Carbon Monoxide (CO)
0
50
100
150
200
250
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Non-Combustible Gases
Carbon Dioxide (CO2)
0
1000
2000
3000
4000
5000
6000
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Nitrogen (N2)
0
10
20
30
40
50
60
70
80
Ju
n-1
6
Ju
n-1
5
Thousands
Pa
rts
Pe
r M
illio
n
Oxygen (O2)
0
5
10
15
20
25
30
Ju
n-1
6
Ju
n-1
5
Thousands
Pa
rts
Pe
r M
illio
n
Page 2 of 3Serial Number: 293638Magna IV Engineering
Cargill Limited
Cargill TerminalFluid Test Report
Maintenance
Fluid Analysis
Moisture Content
(Should be <Limit)
0
5
10
15
20
25
30
Jun
-16
Jun
-15
Pa
rts
Pe
r M
illio
n
Interfacial Tension
(Should be >Limit)
0
5
10
15
20
25
30
35
Jun
-16
Jun
-15
mN
/m
Acid Number
(Should <Limit)
0
0.02
0.04
0.06
0.08
0.1
0.12
0.14
0.16
Jun
-16
Jun
-15
mg
KO
H/g
Color Number
(Should be <Limit)
0
0.5
1
1.5
2
2.5
3
3.5
4
Jun
-16
Jun
-15
Dielectric Breakdown D877
(Should be >Limit)
Actual Values
Acceptable Limits
Dielectric Breakdown D1816
(Should be >Limit)
0
5
10
15
20
25
30
35
40
45
Jun
-16
Jun
-15
kV
Page 3 of 3Serial Number: 293638Magna IV Engineering
/
WEIGHT
TEMP RISE
PSI
�
PO# for Sampling Lab:
REPORT RUSH:
� DGA D3612C � Dielectric 1.0mm D1816 Oxidation Inhibitor D2668 NOTES:
� Moisture in Oil D1533B Dielectric 2.0mm D1816 Furfurals (paper degradation) 1. NO WINDING TEMP GAUGE
� Interfacial Tension D971 Power Factor 25°C D924 Metals D3635ICP TRANSFORMER IS IN VAULT.
� Acid Number D974 Power Factor 100°C D924 Viscosity D88 2. IMPERIAL GALLONS
� Color/Visual D1500, D1524 Specific Gravity D1298 Other:
Dielectric 2.5mm D877 PCB
OIL TYPE MINERAL SYSTEM BREATHING
DATE OF LAST OIL CHANGE (IF KNOWN) UNKNOWN
NAMEPLATE DATA
June 7, 2016
PCB CONTAMINATED
# OF TAPS
TAP FOUND/LEFT
YES
5EQUIPMENT TX KVA 4000
MANUF.
YEAR 1967
3.70%TYPE
LEMON YELLOW
STRAW YELLOW
STRAW WHITE
BROWN
REDDISH ORANGE
ORANGE BLACK
OTHER:
PREPARED FOR
CARGILL
AREA
SITE
WO#
MAIN SUB
CARGILL TERMINAL
C3330-10 DATE
TEST BY
APPROVED BY
WEST TX
JMP
STANDARD MAINTENANCE
OIL FILLED EQUIPMENT INSPECTION SHEETTAG #
CANF-5E006
ONAN SEC VOLTS 575 %IMPED
WESTINGHOUSE PRI VOLTS 72KV 3 3
SO# 293638 AMPS
PRE-SAMPLING CHECKLIST
CAPACITY GALSLTRS
NO
RESET GAUGE
OIL LEVEL
PRESSURE
GAUGE READING DRAGHAND
OIL TEMP
N/A
SAMPLE COLOR
SAMPLE DATA
NO
YES / NOWINDING TEMP
Tests Required (Internal Purposes Only)
CRITERIAYES
Sampler: JMP
78 %
26.0 °C
BOTTOM VALVE
Syringe #:
�
KPA
READING
SEE DIAGRAM AT RIGHT
HUMIDITY
AMB. TEMP
SEDIMENT
SAMPLE POINT
� OK
�
NO
�
INSPECTIONS
�
CRITERIA
�
ADEQUATE CLEARANCE
TANK PRESSURE (Min: -1 Psi (-6.89 kPa))
�
LOW OIL LEVEL (GAUGE @ LOW)
LV BUSHINGS ACCESSIBLE
�
CO 376 1006975
RADIATOR CONDITION N/A
40 °C
� SILICA DESICANT CONDITION �
�
NO
DIRT ACCUMULATION
750
PROPER LEVEL
NO
OIL LEAKS (WHERE)
DUSTY
FAIL
CORROSION / RUST ACCUMULATION � PAINT IS GOOD
� DUSTY
COMMENTS
6 PPM
LV BUSHING CONDITION �
35 °C
COMMENTS
NITROGEN ADDED
NO
RADIATORS INSTALLED
CONSERVATOR TANK
BLUE
HV BUSHINGS ACCESSIBLE HV BUSHING CONDITION �
RELIEF VALVE INSTALLED
�
GROUNDING (2 LOCATIONS) �
PHYSICAL DAMAGE
BREATHERS
�
GAUGE DOCUMENTATION
DESCRIPTION YES DESCRIPTION OK
�
DUSTY
West Tx Oil Filled Equipment Inspection Page 1 of 1
Cargill Terminal
Sub 2
S/N: 1059001354
C3330-10
Oil & Gas Results
Nameplate Information
Cargill Limited
Cargill TerminalFluid Test Report
Maintenance
Nameplate Information
Serial Number: 1059001354
Sample Date:
Job Number:
Nitrogen (N₂)
Total Dissolved Combustible Gas
Total Gas Content (%)
kVA Rating: 3000
Fluid Type: ESTER
Designation: Sub 2kV Rating: 12.400/0.575
Dissolved Gas Analysis
Fluid Quality Analysis Limits
Additional Fluid Quality Tests
Notes:
D3612-C
Apparatus Type: TRN Manufacturer: COOPER
Year Manufactured: 2010 Fluid Capacity (L): 1250
Expressed in PPM
Voltage Class ≤69kV
Hydrogen (H₂)
Methane (CH₄)
Ethane (C₂H₆)
Ethylene (C₂H₄)
Acetylene (C₂H₂)
Carbon Monoxide (CO)
Carbon Dioxide (CO₂)
100
120
65.0
50.0
2.0
1000
10000
Limits
Moisture Content D1533 (ppm)
Interfacial Tension D971 (mN/m)
Acid Number D974 (mg KOH/g)
Color Number D1500 (Relative)
Visual Examination D1524 (Relative)
Dielectric Breakdown @ 1mm D1816 (kV)
Dielectric Breakdown D877 (kV)
35
25.0
0.200
3.5
CLEAR
23
26
PCB D4059 (ppm)
Specific Gravity D4052 (Relative)
Power Factor @ 25°C D924 (%)
Oxidation Inhibitor D2668 (%)
2.0
0.91
0.5
0.08 - 0.3
Limits
Power Factor @ 100°C D924 (%) 5.0
Oxygen (O₂)
12
23.3
37
0.020
CLEAR
15
22.9
47
0.024
CLEAR
36
1500
67600
6
36
310
192.9
6.3
0.0
277
6.970
36
2400
66000
6
38
330
195.6
8.2
0.0
284
6.900
Jun-7-2016
C3330-10
Jun-10-2015
C3330-7
- <0.5
Limits based on Mineral Oil Insulating Fluid.
All Results considered normal for Natural Ester Insulating Fluid.
07/06/2016 :
Page 1 of 3Serial Number: 1059001354Magna IV Engineering
Cargill Limited
Cargill TerminalFluid Test Report
Maintenance
Historic Graphs and Diagnostic Charts
Combustible Gases
Total Gas Content (%)
(All Gases)
0
1
2
3
4
5
6
7
8
Ju
n-1
6
Ju
n-1
5
Key Gas Comparison (ppm)
0
50
100
150
200
250
CO - H2 - Meth - Eth - Ethy - Ace
Methane (CH4)
0
1
2
3
4
5
6
7
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Ethane (C2H6)
0
50
100
150
200
250
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Acetylene (C2H2)
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Ethylene (C2H4)
0
1
2
3
4
5
6
7
8
9
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Hydrogen (H2)
0
5
10
15
20
25
30
35
40
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Carbon Monoxide (CO)
0
5
10
15
20
25
30
35
40
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Non-Combustible Gases
Carbon Dioxide (CO2)
0
50
100
150
200
250
300
350
Ju
n-1
6
Ju
n-1
5
Pa
rts
Pe
r M
illio
n
Nitrogen (N2)
0
10
20
30
40
50
60
70
80
Ju
n-1
6
Ju
n-1
5
Thousands
Pa
rts
Pe
r M
illio
n
Oxygen (O2)
0
0.5
1
1.5
2
2.5
3
Ju
n-1
6
Ju
n-1
5
Thousands
Pa
rts
Pe
r M
illio
n
Page 2 of 3Serial Number: 1059001354Magna IV Engineering
Cargill Limited
Cargill TerminalFluid Test Report
Maintenance
Fluid Analysis
Moisture Content
(Should be <Limit)
0
5
10
15
20
25
30
35
40
Jun
-16
Jun
-15
Pa
rts
Pe
r M
illio
n
Interfacial Tension
(Should be >Limit)
0
5
10
15
20
25
30
Jun
-16
Jun
-15
mN
/m
Acid Number
(Should be <Limit)
0
0.05
0.1
0.15
0.2
0.25
Jun
-16
Jun
-15
mg
KO
H/g
Color Number
(Should be <Limit)
Dielectric Breakdown D877
(Should be >Limit)
Actual Values
Acceptable Limits
Dielectric Breakdown D1816
(Should be >Limit)
0
5
10
15
20
2530
35
40
45
50
Jun
-16
Jun
-15
kV
Page 3 of 3Serial Number: 1059001354Magna IV Engineering
/
WEIGHT
TEMP RISE
PSI
�
PO# for Sampling Lab:
REPORT RUSH:
� DGA D3612C � Dielectric 1.0mm D1816 Oxidation Inhibitor D2668 NOTES:
� Moisture in Oil D1533B Dielectric 2.0mm D1816 Furfurals (paper degradation) 1. NO WINDING TEMP GAUGE
� Interfacial Tension D971 Power Factor 25°C D924 Metals D3635ICP TRANSFORMER IS IN A VAULT
� Acid Number D974 Power Factor 100°C D924 Viscosity D88
� Color/Visual D1500, D1524 Specific Gravity D1298 Other:
Dielectric 2.5mm D877 PCB
OIL TYPE FR3 SYSTEM BREATHING
DATE OF LAST OIL CHANGE (IF KNOWN) NEW TRANSFORMER
NAMEPLATE DATA
June 7, 2016
PCB CONTAMINATED
# OF TAPS
TAP FOUND/LEFT
YES
5EQUIPMENT TX KVA 3000
MANUF.
YEAR 2010
TYPE
LEMON YELLOW
STRAW YELLOW
STRAW WHITE
BROWN
REDDISH ORANGE
ORANGE BLACK
OTHER:
PREPARED FOR
CARGILL
AREA
SITE
WO#
SUB 2
CARGILL TERMINAL
C3330-10 DATE
TEST BY
APPROVED BY
SUBSTATION 2
SB
STANDARD MAINTENANCE
OIL FILLED EQUIPMENT INSPECTION SHEETTAG #
CANF-5E006
ONAN SEC VOLTS 575 %IMPED
COOPER PRI VOLTS 12.4Kv 3 3
SO# 1059001354 AMPS
PRE-SAMPLING CHECKLIST
CAPACITY GALSLTRS
NO
RESET GAUGE
OIL LEVEL
PRESSURE
GAUGE READING DRAGHAND
OIL TEMP
N/A
SAMPLE COLOR
SAMPLE DATA
NO
YES / NOWINDING TEMP
Tests Required (Internal Purposes Only)
CRITERIAYES
Sampler: SB
40 %
26.0 °C
BOTTOM VALVE
Syringe #:
�
KPA
READING
SEE DIAGRAM AT RIGHT
1
HUMIDITY
AMB. TEMP
SEDIMENT
SAMPLE POINT
� OK
�
NO
INSPECTIONS
�
CRITERIA
�
ADEQUATE CLEARANCE
TANK PRESSURE (Min: -1 Psi (-6.89 kPa))
�
LOW OIL LEVEL (GAUGE @ LOW)
LV BUSHINGS ACCESSIBLE
DS 264 1006975
RADIATOR CONDITION � OK
40 °C
SILICA DESICANT CONDITION
�
NO
DIRT ACCUMULATION
1250
PROPER LEVEL
NO
OIL LEAKS (WHERE)
FAIL
CORROSION / RUST ACCUMULATION � PAINT IS GOOD
� DUSTY
COMMENTS
UNKNOWN
LV BUSHING CONDITION
40 °C
COMMENTS
NITROGEN ADDED
NO
�
�
RADIATORS INSTALLED
CONSERVATOR TANK
NOT USED
HV BUSHINGS ACCESSIBLE HV BUSHING CONDITION
RELIEF VALVE INSTALLED
�
GROUNDING (2 LOCATIONS) �
PHYSICAL DAMAGE
�
BREATHERS
GAUGE DOCUMENTATION
DESCRIPTION YES DESCRIPTION OK
�
Substation 2 Oil Filled Equipment Inspection Page 1 of 1
Cargill Terminal6OCB1
S/N: 60503
C3330-10Oil & Gas Results
Nameplate Information
Cargill LimitedCargill Terminal
Fluid Test ReportMaintenance
Nameplate InformationSerial Number: 60503
Sample Date:
Job Number:
Nitrogen (N₂)Total Dissolved Combustible Gas
Total Gas Content (%)
kVA Rating:Fluid Type: OIL
Designation: 6OCB1kV Rating: 72.000
Dissolved Gas Analysis
Fluid Quality Analysis Limits
Additional Fluid Quality Tests
Notes:
D3612-C
Apparatus Type: OCB Manufacturer: GEYear Manufactured: 1967 Fluid Capacity (G): 575
Expressed in PPM
Voltage Class >69kV - <230kV
Hydrogen (H₂)Methane (CH₄)Ethane (C₂H₆)Ethylene (C₂H₄)Acetylene (C₂H₂)Carbon Monoxide (CO)
Carbon Dioxide (CO₂)
100
120
65.0
50.0
2.0
1000
10000
Limits
Moisture Content D1533 (ppm)
Interfacial Tension D971 (mN/m)
Acid Number D974 (mg KOH/g)
Color Number D1500 (Relative)
Visual Examination D1524 (Relative)
Dielectric Breakdown @ 1mm D1816 (kV)
Dielectric Breakdown D877 (kV)
25
30.0
0.150
3.5
CLEAR
28
26
PCB D4059 (ppm)
Specific Gravity D4052 (Relative)
Power Factor @ 25°C D924 (%)
Oxidation Inhibitor D2668 (%)
2.0
0.91
0.5
0.08 - 0.3
Limits
Power Factor @ 100°C D924 (%) 5.0
Oxygen (O₂)
32.0
32
0.022
L1.5
CLEAR
32.5
36
0.025
1.5
CLEAR
0
30300
65500
1
25
560
0.0
0.8
0.0
27
9.630
1
27400
63900
1
31
580
0.0
0.7
0.0
34
9.200
Jun-7-2016
C3330-10
Jun-10-2015
C3330-7
- <0.5
All results considered normal for OCB operation2016-06-07 :
Page 1 of 3Serial Number: 60503Magna IV Engineering
Cargill LimitedCargill Terminal
Fluid Test ReportMaintenance
Historic Graphs and Diagnostic Charts
Combustible Gases
Total Gas Content (%)(All Gases)
0
2
4
6
8
10
12
Jun-
16
Jun-
15
Key Gas Comparison (ppm)
0
5
10
15
20
25
30
CO - H2 - Meth - Eth - Ethy - Ace
Methane (CH4)
0
0.2
0.4
0.6
0.8
1
1.2
Jun-
16
Jun-
15
Parts
Per
Milli
on
Ethane (C2H6)
0
0.2
0.4
0.6
0.8
1
Jun-
16
Jun-
15
Parts
Per
Milli
on
Acetylene (C2H2)
00.10.20.30.40.50.60.70.80.9
1
Jun-
16
Jun-
15
Parts
Per
Milli
on
Ethylene (C2H4)
00.10.20.30.40.50.60.70.80.9
Jun-
16
Jun-
15
Parts
Per
Milli
on
Hydrogen (H2)
0
0.2
0.4
0.6
0.8
1
1.2
Jun-
16
Jun-
15
Parts
Per
Milli
on
Carbon Monoxide (CO)
0
5
10
15
20
25
30
35
Jun-
16
Jun-
15
Parts
Per
Milli
on
Non-Combustible GasesCarbon Dioxide (CO2)
0
100
200
300
400
500
600
700
Jun-
16
Jun-
15
Parts
Per
Milli
on
Nitrogen (N2)
0
10
20
30
40
50
60
70
Jun-
16
Jun-
15
Thousands
Parts
Per
Milli
on
Oxygen (O2)
0
5
10
15
20
25
30
35
Jun-
16
Jun-
15
Thousands
Parts
Per
Milli
on
Page 2 of 3Serial Number: 60503Magna IV Engineering
Cargill LimitedCargill Terminal
Fluid Test ReportMaintenance
Fluid AnalysisMoisture Content
(Should be <Limit)Interfacial Tension(Should be >Limit)
0
5
10
15
20
25
30
35
Jun-
16
Jun-
15
mN
/m
Acid Number(Should <Limit)
00.020.040.060.080.1
0.120.140.16
Jun-
16
Jun-
15
mg
KOH/
g
Color Number(Should be <Limit)
0
0.51
1.5
2
2.53
3.5
4
Jun-
16
Jun-
15
Dielectric Breakdown D877(Should be >Limit)
Actual ValuesAcceptable Limits
Dielectric Breakdown D1816(Should be >Limit)
05
10152025303540
Jun-
16
Jun-
15
kV
Page 3 of 3Serial Number: 60503Magna IV Engineering
/
WEIGHT
TEMP RISE
PSI
�
PO# for Sampling Lab:
REPORT RUSH:
� DGA D3612C � Dielectric 1.0mm D1816 Oxidation Inhibitor D2668 NOTES:
� Moisture in Oil D1533B Dielectric 2.0mm D1816 Furfurals (paper degradation)
� Interfacial Tension D971 Power Factor 25°C D924 Metals D3635ICP
� Acid Number D974 Power Factor 100°C D924 Viscosity D88
� Color/Visual D1500, D1524 Specific Gravity D1298 Other:
Dielectric 2.5mm D877 PCB
OIL TYPE MINERAL SYSTEM BREATHING
DATE OF LAST OIL CHANGE (IF KNOWN) UNKNOWN
NAMEPLATE DATA
June 7, 2016
PCB CONTAMINATED
# OF TAPS
TAP FOUND/LEFT
YES
N/AEQUIPMENT OCB KVA
MANUF.
N/AYEAR 1967
N/ATYPE
LEMON YELLOW
STRAW YELLOW
STRAW WHITE
BROWN
REDDISH ORANGE
ORANGE BLACK
OTHER:
PREPARED FOR
CARGILL
AREA
SITE
WO#
MAIN SUB
CARGILL TERMINAL
C3330-10 DATE
TEST BY
APPROVED BY
6 OCB1
JMP
STANDARD MAINTENANCE
OIL FILLED EQUIPMENT INSPECTION SHEETTAG #
CANF-5E006
WSO SEC VOLTS %IMPED
GE PRI VOLTS 72KV
SO# 60503 AMPS 1200
PRE-SAMPLING CHECKLIST
CAPACITY GALSLTRS
NO
RESET GAUGE
OIL LEVEL
PRESSURE
GAUGE READING DRAGHAND
OIL TEMP
SAMPLE COLOR
SAMPLE DATA
YES / NO
YES / NOWINDING TEMP
Tests Required (Internal Purposes Only)
CRITERIAYES
Sampler: JMP
78 %
23.0 °C
BOTTOM VALVE
Syringe #:
�
KPA
READING
SEE DIAGRAM AT RIGHT
HUMIDITY
AMB. TEMP
SEDIMENT
SAMPLE POINT
� OK
NO
�
INSPECTIONS
CRITERIA
�
ADEQUATE CLEARANCE
TANK PRESSURE (Min: -1 Psi (-6.89 kPa))
�
LOW OIL LEVEL (GAUGE @ LOW)
LV BUSHINGS ACCESSIBLE
�
DS 901 1006975
RADIATOR CONDITION N/A
� SILICA DESICANT CONDITION
�
YES / NO
DIRT ACCUMULATION
575
NO GAUGE
NO
OIL LEAKS (WHERE)
SOME CHIPS
FAIL
CORROSION / RUST ACCUMULATION � PAINT IS POOR
� NONE VISIBLE
COMMENTS
< 0.5 PPM
LV BUSHING CONDITION
26 °C
COMMENTS
NITROGEN ADDED
NO
RADIATORS INSTALLED
CONSERVATOR TANK
NOT USED
HV BUSHINGS ACCESSIBLE HV BUSHING CONDITION
RELIEF VALVE INSTALLED
�
GROUNDING (2 LOCATIONS) �
PHYSICAL DAMAGE
BREATHERS
�
GAUGE DOCUMENTATION
DESCRIPTION YES DESCRIPTION OK
�
N/A
6 OCB1 Oil Filled Equipment Inspection Page 1 of 1