GENERAL NOTES: 8. 6. 5. 7. 3. 4. 1. 2. WHERE INDIVIDUAL 120V HOMERUN CIRCUITS ARE SHOWN ON THE DRAWINGS THEY MAY BE COMBINED AS FOLLOWS; - NO MORE THAN THREE (3) PHASE CONDUCTORS PLUS THREE (3) NEUTRAL AND ONE (1) GROUND PER CONDUIT, EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE. - NO TWO OF THE SAME PHASE CONDUCTOR PER CONDUIT. - PROVIDE 120V CIRCUITS WITH INDIVIDUAL NEUTRALS PER CIRCUIT. NEUTRALS MAY NOT BE SHARED BETWEEN PHASES. PAINT ALL EXPOSED CONDUIT TO MATCH THE SURFACE TO WHICH ATTACHED IF THE SURFACE IS PAINTED. COORDINATE WITH MECHANICAL AND PLUMBING DRAWINGS FOR EXACT LOCATION OF EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS INCLUDING EXACT POINT OF ELECTRICAL CONNECTION. MAKE ADJUSTMENTS TO CONDUIT ROUTING, PLACEMENT OF DISCONNECTS AND STARTERS AS REQUIRED. PROTECT BRANCH CIRCUIT WIRING FROM PAINT OVERSPRAY DURING CONSTRUCTION TO PRESERVE COLOR-CODING. CONDUCTORS PAINTED SHALL BE COMPLETELY CLEANED OF PAINT BEFORE FINAL CONNECTIONS ARE MADE. VERIFY SECURITY SYSTEM OUTLET BOX AND CONDUIT REQUIREMENTS WITH SECURITY SYSTEM PROVIDER PRIOR TO INSTALLATION AND MAKE ALL NECESSARY ADJUSTMENTS. COORDINATE WIRING DEVICE OUTLET BOX LOCATIONS WITH ARCHITECTURAL PLANS, ELECTRICAL PLANS, ENLARGED FLOOR PLANS, EQUIPMENT AND FURNITURE LAYOUTS, SECTIONS, ELEVATIONS, DETAILS AND JOB SITE DIFFERENCES PRIOR TO ROUGHING-IN CONDUITS. MAKE REQUIRED ADJUSTMENTS (WITH ARCHITECTS AND ENGINEERS APPROVAL) AT NO ADDITIONAL COST TO THE OWNER. INSTALL DEVICES SHOWN ON DRAWINGS IN ACCORDANCE WITH MOUNTING HEIGHTS SHOWN IN THE ELECTRICAL LEGEND AND/OR PROJECT SPECIFICATIONS. INSTALL FIRE ALARM DEVICES IN ACCORDANCE WITH A.D.A. REQUIREMENTS. WHERE THE TERM "BRANCH CIRCUITRY" IS USED ON THESE DRAWINGS, IT IS TO BE CONSTRUED TO MEAN CONDUIT AND CONDUCTORS. ELECTRICAL LEGEND: EXISTING 2' X 4' LIGHT FIXTURE. EXISTING 2' X 4' LIGHT FIXTURE CONNECTED TO EXISTING EMERGENCY EGRESS LIGHTING CIRCUIT. 2' X 4' LED LIGHT FIXTURE, SUBSCRIPT NUMBER INDICATES LIGHT FIXTURE TYPE. SUBSCRIPT LETTER INDICATES FIXTURE TO BE CONTROLLED BY CORRESPONDING LIGHTING ZONE. 1' X 2' LED LIGTH FIXTURE, SUBSCRIPT NUMBER INDICATES LIGHT FIXTURE TYPE. 1' X 4' LED LIGHT FIXTURE, SUBSCRIPT NUMBER INDICATES LIGHT FIXTURE TYPE. EXISITING DOWNLIGHT FIXTURE. LED DOWN LIGHT FIXTURE, SUBSCRIPT NUMBER INDICATES LIGHT FIXTURE TYPE. LED DOWN LIGHT FIXTURE WITH SELF CONTAINED BATTERY BACKUP. SUBSCRIPT "N" INDICATES NIGHT LIGHT FIXTURE (ALWAYS ON). LIGHT FIXTURE CONNECTED TO EXISTING EMERGENCY EGRESS LIGHTING CIRCUIT. SUBSCRIPT NUMBER INDICATES LIGHT FIXTURE TYPE. EXISTING WALL MOUNTED LIGHT FIXTURE. WALL MOUNTED LED LIGHT FIXTURE. SUBSCRIPT NUMBER INDICATES LIGHT FIXTURE TYPE. 2' X 4' LED LIGHT FIXTURE WITH SELF CONTAINED BATTERY BACKUP. SUBSCRIPT NUMBER INDICATES LIGHT FIXTURE TYPE. SUBSCRIPT "N" INDICATES NIGHT LIGHT FIXTURE (ALWAYS ON). 2' X 4' LED LIGHT FIXTURE CONNECTED TO EXISTING EMERGENCY EGRESS LIGHTING CIRCUIT. SUBSCRIPT NUMBER INDICATES LIGHT FIXTURE TYPE. 1' X 4' LED LIGHT FIXTURE WITH SELF CONTAINED BATTERY BACKUP, SUBSCRIPT NUMBER INDICATES LIGHT FIXTURE TYPE. WALL MOUNTED LED LIGHT FIXTURE POWERED THROUGH INVERTER. INSTALL TOP OF LIGHT FIXTURE +9'-0" A.F.F. POWER INVERTER FOR WALL MOUNTED LIGHT FIXTURE - ISOLITE CATALOG NUMBER IMI-25-LC-V3 OR APPROVED EQUAL. INSTALL INVERTER ABOVE THE CEILING. EXIT LIGHT FIXTURE WITH BATTERIES BACK UP, PROVIDE DIRECTIONAL ARROWS AS INDICATED ON DRAWINGS. SHADING INDICATES NUMBER OF FACES LIT. SUBSCRIPT NUMBER INDICATES LIGHT FIXTURE TYPE. SITE POLE MOUNTED LIGHT FIXTURE. SUBSCRIPT NUMBER INDICATES LIGHT FIXTURE TYPE. RECESSED CEILING MOUNTED SELF-CONTAINED EMERGENCY LIGHT WITH BATTERY BACKUP. PENDANT MOUNTED LIGHT FIXTURE SINGLE-POLE SWITCH, 20A, 120/277V, A.C., INSTALL +42" A.F.F. THREE-WAY SWITCH, 20A, 120/277V, A.C., INSTALL +42" A.F.F. FOUR-WAY SWITCH, 20A, 120/277V, A.C., INSTALL +42" A.F.F. MOTOR RATED SNAP SWITCH, 20A, 120/277V, A.C., INSTALL +42" A.F.F. OCCUPANCY SENSOR SWITCH, 20A, 120/277V, A.C., INSTALL +42" A.F.F. SINGLE POLE KEY OPERATED SWITCH, 20A, 120/277V, A.C., INSTALL +42" A.F.F. THREE WAY KEY OPERATED SWITCH, 20A, 120/277V, A.C., INSTALL +42" A.F.F. FOUR WAY KEY OPERATED SWITCH, 20A, 120/277V, A.C., INSTALL +42" A.F.F. LINE VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR - EATON CATALOG NUMBER OAC-DT-2000-ML. LOW VOLTAGE OCCUPANCY SENSOR - EATON CATALOG NUMBER OAC-DT-2000. LOW VOLTAGE OCCUPANCY SENSOR - EATON CATALOG NUMBER PDR-RC-4TSB-X. WALL MOUNT 9'-0" A.F.F. LOW VOLTAGE OCCUPANCY SENSOR POWER PACK - EATON CATALOG NUMBER SP20-MV. INSTALL ABOVE CEILING. 2000W WALL MOUNTED PHOTOCELL, PARAGON "CW" SERIES OR EQUAL. CLASSROOM LIGHTING RELAY PANEL - EATON CATALOG NUMBER RC3D-PL. INSTALL CABINET ABOVE CEILING WHERE INDICATED ON THE FLOOR PLANS. PROVIDE JUMPER CABLE TO OVERRIDE THE TWO HOUR TIME CLOCK DRY CONTACT. CLASSROOM LIGHTING CONTROL STATION - EATON CATALOG NUMBER PDR-RC-4TSB-X. PROVIDE SINGLE GANG BOX +48" A.F.F. WITH 1/2" CONDUIT UP TO ABOVE THE CEILING WITH PLENUM RATED CONDUIT BUSHINGS ON BOTH ENDS OF CONDUIT. PROGRAM LIGHTING CONTROL STATION, SUCH THAT FIRST BUTTON (ON TOP) TURNS ALL LIGHT FIXTURES "ON." SECOND BUTTON DIMS ALL LIGHT FIXTURES TO "50%". THIRD BUTTON TURNS LIGHT FIXTURES WITH SUBSCRIPT "A" "OFF". FOURTH BUTTON TURNS ALL LIGHT FIXTURES "OFF". DUPLEX RECEPTACLE, 20A, 120V, INSTALL +18" TO A.F.F., U.O.N. IF CENTER SHADED, INSTALL +6" ABOVE SINK, COUNTER BACKSPLASH, U.O.N. "GFI" WHEN USED INDICATES GROUND FAULT INTERRUPTER. "WP" WHEN USED INDICATES WEATHER RESISTANT, WEATHERPROOF DEVICE WITH WEATHERPROOF WHILE IN USE LOCKABLE COVERPLATE. SUBSCRIPT "W" INDICATES DEVICE IN THE WIREMOLD SURFACE BOX. DOUBLE DUPLEX RECEPTACLE, 20A, 120V, INSTALL +18" A.F.F., U.O.N. DUPLEX RECEPTACLE FOR WALL MOUNTED PROJECTOR. PROVIDE 20A., 120 VOLT RECEPTACLE AND OUTLET BOX +88" A.F.F. TO CENTERLINE OF BOX. COORDINATE RECEPTACLE LOCATION WITH OWNER FURNISHED PROJECTOR MOUNTING BRACKET. SEE DETAIL ON DRAWING SHEET E-403 FOR ADDITIONAL INFORMATION. ELECTRICAL CONNECTION TO EQUIPMENT. ELECTRICAL CONNECTION TO EXHAUST FAN. ELECTRICAL CONNECTION TO WATER HEATER. TRANSFORMER, SEE POWER RISER DIAGRAM ON DRAWING SHEET E-501. DISCONNECT SWITCH, 480V, U.O.N.: 3P = NUMBER OF POLES, 60 = SWITCH RATING, SN = SOLD NEUTRAL, 40 = FUSE RATING (NF INDICATES NONFUSED). PROVIDE IN NEMA 1 ENCLOSURE IF INSTALLED INDOORS AND IN NEMA 3R ENCLOSURE IF INSTALLED OUT OF DOORS, U.O.N. PANELBOARD, 208Y/120 VOLT. PANELBOARD, 480Y/277 VOLT. JUNCTION BOX, SIZE AS REQUIRED IF NOT INDICATED. BRANCH CIRCUIT OR FEEDER WIRING IN CONDUIT. NO TICK MARKS INDICATED 2 #12 CONDUCTORS & 1 #12 GND IN 1/2" CONDUIT U.O.N. TICK MARKS, WHEN SHOWN, INDICATE NUMBER OF CONDUCTORS IF OTHER THAN THREE: ( ) INDICATES GROUNDING CONDUCTOR. SEE PANEL SCHEDULES FOR EXACT CONDUCTOR SIZES. HOMERUNS BRANCH CIRCUITRY TO PANEL. PANEL & CIRCUIT DESIGNATION AS INDICATED. CONDUIT TURNED UP. CONDUIT TURNED DOWN. CONDUIT RUN CONCEALED ABOVE CEILING, IN WALL, BELOW FLOOR SLAB OR UNDERGROUND. S S EF S F 4 T J S 15 E WP 4 GFI 1 H1-7 3P 110 3R 60 40 F/C S M 3 S S OS OS 1 E FAPS FACP S 4K 3K S K S IN 2 7 E E 2 7 8 9 A A 8 T F P U WA 2 PC HS 15 M TP D W GENERAL FIRE ALARM NOTES: 1. 2. 3. 4. 5. ALL DEMOLITION AND NEW WORK ASSOCIATED WITH THE EXISTING FIRE ALARM SYSTEM SHALL BE PERFORMED BY A CERTIFIED NOTIFIER REPRESENTATIVE. THE EXISTING FIRE ALARM CONTROL PANEL IS A NOTIFIER MODEL AFP1010. PROVIDE NEW FIRE ALARM DEVICES THAT ARE COMPATIBLE WITH THE EXISTING FIRE ALARM SYSTEM. AT THE BEGINNING AND THE END OF THE PROJECT, TEST ALL FIRE ALARM DEVICES THAT ARE SCHEDULED TO BE REMOVED AND REINSTALLED AS A PART OF THIS PROJECT. NOTIFY THE OWNER OF ANY DEFECTIVE DEVICES. RETEST ALL FIRE ALARM DEVICES AFTER REINSTALLATION AT THE END OF THE PROJECT. ANY DEVICE FOUND DEFECTIVE AT THE END OF THE PROJECT SHALL BE REPLACED WITH A NEW DEVICE AT NO ADDITIONAL COST TO THE OWNER. MODIFY THE EXISTING FIRE ALARM ANNUNCIATOR PANEL TO ELIMINATE INDICATING LIGHTS FOR DUCT SMOKE DETECTORS THAT ARE REMOVED BY THIS PROJECT. ALL WORK ASSOCIATED WITH THE EXISTING FIRE ALARM SYSTEM SHALL BE ACCOMPLISHED ON THE SAME DAY IT BEGINS. AT NO TIME SHALL THE BUILDING BE LEFT WITHOUT A FULLY FUNCTIONING FIRE ALARM SYSTEM. IF THE BUILDING IS LEFT WITHOUT FIRE ALARM PROTECTION OVERNIGHT THE CONTRACTOR IS REQUIRED TO PROVIDE STAFF TO MONITOR THE BUILDING TO THE SATISFACTION OF THE LOCAL AUTHORITY HAVING JURISDICTION. N DC N 1 OS LR OS L PP WH FIRE ALARM VISUAL DEVICE. INSTALL IN ACCORDANCE WITH ADA REQUIREMENTS. SUBSCRIPT INDICATES CANDELA LEVEL. EXISTING FIRE ALARM AUDIO/VISUAL DEVICE. FIRE ALARM AUDIO/VISUAL DEVICE. INSTALL IN ACCORDANCE WITH ADA REQUIREMENTS. SUBSCRIPT INDICATES CANDELA LEVEL. FIRE ALARM PULL STATION, INSTALL +42" A.F.F. FIRE ALARM SMOKE DETECTOR, SURFACE MOUNTED ON CEILING. PROVIDE 120V POWER TO DOOR HOLD-OPEN DEVICES THROUGH A SINGLE POLE, NORMALLY CLOSED CONTACTOR (COIL VOLTAGE - 120V). PROVIDE POWER TO THE COIL BY TAPPING THE 120V CIRCUIT AHEAD OF THE CONTACTOR AND RUNNING IT THROUGH A RELAY TO BE CONTROLLED BY THE BUILDING FIRE ALARM SYSTEM SO ANY FIRE ALARM INITIATION WILL CAUSE THE RELAY TO OPEN, THE CONTACTOR TO OPEN AND THE DOOR HOLD OPEN DEVICES TO DE- ENERGIZE. THE REVERSE SHALL HAPPEN UPON CLEARING OF THE ALARM. PROVIDE ALL MATERIAL, EQUIPMENT AND HARDWARE NECESSARY FOR A COMPLETE INSTALLATION. INSTALL CONTACTOR AND RELAY IN A SINGLE ENCLOSURE ABOVE THE CEILING ABOVE EACH DOOR OR GROUP OF DOORS CONTROLLED. SERVE CONTACTOR FROM CIRCUIT INDICATED. FIRE ALARM CONTROL PANEL. FIRE ALARM POWER SUPPLY. FIRE ALARM SYSTEM CONNECTION TO SPRINKLER SYSTEM TAMPER SWITCH. FIRE ALARM SYSTEM CONNECTION TO SPRINKLER SYSTEM BELL. FIRE ALARM SYSTEM CONNECTION TO SPRINKLER SYSTEM FLOW SWITCH. CEILING MOUNTED FIRE ALARM AUDIO/VISUAL DEVICE. SEE FLOOR PLANS FOR ADDITIONAL REQUIREMENTS. SUBSCRIPT INDICATES CANDELA LEVEL. MAGNETIC DOOR HOLD-OPEN DEVICE. INSTALL OUTLET BOX AT THE HEIGHT REQUIRED BY THE DOOR HARDWARE PROVIDER. PROJECTOR OUTLET. PROVIDE 1-GANG OUTLET BOX +88" A.F.F. TO CENTERLINE OF BOX. COORDINATE PROJECTOR OUTLET LOCATION WITH OWNER FURNISHED PROJECTOR MOUNTING BRACKET. PROVIDE 1-1/2" EMPTY CONDUIT WITH PULL WIRE RATED FROM OUTLET BOX AND TERMINATE ABOVE THE CEILING. SEE DETAIL ON DRAWING SHEET E-403 FOR ADDITIONAL INFORMATION. SMARTBOARD USB OUTLET. PROVIDE 1-GANG OUTLET BOX INSTALLED HORIZONTALLY +80" A.F.F. COORDINATE OUTLET BOX LOCATION WITH OWNER FURNISHED SMARTBOARD. PROVIDE 1-1/4" EMPTY CONDUIT WITH PULL WIRE RATED FROM OUTLET BOX AND TERMINATE ABOVE THE CEILING. SEE DETAIL ON DRAWING SHEET E-403 FOR ADDITIONAL INFORMATION. OWNER PROVIDED CEILING MOUNTED WIRELESS ACCESS POINT DATA OUTLET. PROVIDE TWO GANG OUTLET BOX WITH 1" CONDUIT WITH PULL WIRE AND PLENUM RATED CONDUIT BUSHINGS. TERMINATE CONDUIT 6" ABOVE LAY-IN TILE CEILING, U.O.N. SUBSCRIPT "2" INDICATES NUMBER OF OWNER PROVIDED PLENUM RATED CAT 6 CABLE HOMERUNS BACK TO IDF ROOM. INSTALL OUTLET +18" A.F.F., U.O.N. SEE DETAIL ON DRAWING SHEET E-403 FOR ADDITIONAL INFORMATION. PROVIDE 2" EMT CONDUIT U.O.N.(WITH PULL WIRE AND PLENUM RATED CONDUIT BUSHINGS) ABOVE CEILING (QUANTITY AS SHOWN) 24" LONG MINIMUM, BUT WITH NOT LESS THAN 2" OF CONDUIT ON EACH SIDE OF WALL. PROVIDE UL APPROVED FIRE SEALS AFTER INSTALLATION OF ALL CABLING. SEE FLOOR PLANS FOR DIFFERENT CONDUIT SIZE REQUIREMENTS. J-HOOKS PROVIDED BY OTHERS. TEACHERS PANEL OUTLET. SEE "TEACHERS PANEL "TP" DETAIL" ON DRAWING SHEET E-403. EXISTING EXTERIOR INTERCOM SPEAKER. OWNER PROVIDED EXTERIOR INTERCOM SPEAKER. CEILING SPEAKER - SCHOOL INTERCOM SYSTEM. PROVIDED BY OWNER. OWNER PROVIDED DOUBLE FACE, CEILING MOUNTED CLOCK. CEILING MOUNTED CCTV CAMERA - SHOWN FOR REFERENCE ONLY. EXTERIOR WALL MOUNTED CCTV CAMERA. SUBSCRIPT "R" INDICATES RELOCATED CAMERA. PROVIDE OUTLET BOXES AND CONDUIT IN ACCORDANCE WITH "EXTERIOR CCTV CAMERA DETAIL" ON SHEET E-403. INTERIOR CEILING MOUNTED SECURITY MOTION DETECTOR AND CABLES PROVIDED BY OWNER. DOOR CONTACTS PROVIDED BY OWNER. SEE "EXTERIOR DOOR CONTACT DETAIL" ON DRAWING SHEET E-503". ROOM NUMBER. DEMOLITION NOTE INDICATOR. NEW WORK NOTE INDICATOR. CARD READER - COORDINATE OUTLET BOX SIZE AND TYPE WITH THE OWNERS SECURITY SYSTEM PROVIDER. PROVIDE 3/4" CONDUIT WITH PULLWIRE FROM OUTLET BOX, UP TO NEAREST LAY-IN TILE CEILING. PROVIDE BUSHINGS ON BOTH ENDS OF CONDUIT. S R 12 E E 15 S E 1 8 16 R B CR E E R P R O F E S S I O N A L E N G I N A E W N O M M O C G R I V F O H T L I N I A KENZIE CAMBAR Lic. No.049752 SHEET NO. JOB N O.: SCALE : DATE : APPR OVED: CHEC KED: DRAW N: AS NO TED REVIS IONS: SHT. OF THOMPSON Consulting Engineers 22 ENTERPRISE PARKWAY TELEPHONE: (757) 599-4415 PROJECT NUMBER: 17041 FAX: (757) 599-4113 HAMPTON, VA 23666 104 03-07-18 3/6/2018 1:47:34 PM E-001 LEGEND, ABBREVIATIONS AND NOTES ADDITION TO HICKORY MIDDLE SCHOOL 1997 HAWK BLVD, CHESAPEAKE VA 23322 MWH KC KC 03/07/18 17005 100% FINAL SUBMITTAL 89
Transcript

GENERAL NOTES:

8.

6.

5.

7.

3.

4.

1.

2.

WHERE INDIVIDUAL 120V HOMERUN CIRCUITS ARE SHOWN ON THE DRAWINGS THEY MAY BE COMBINEDAS FOLLOWS; - NO MORE THAN THREE (3) PHASE CONDUCTORS PLUS THREE (3) NEUTRAL AND ONE (1) GROUND PER

CONDUIT, EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE. - NO TWO OF THE SAME PHASE CONDUCTOR PER CONDUIT. - PROVIDE 120V CIRCUITS WITH INDIVIDUAL NEUTRALS PER CIRCUIT. NEUTRALS MAY NOT BE SHARED

BETWEEN PHASES.

PAINT ALL EXPOSED CONDUIT TO MATCH THE SURFACE TO WHICH ATTACHED IF THE SURFACE ISPAINTED.

COORDINATE WITH MECHANICAL AND PLUMBING DRAWINGS FOR EXACT LOCATION OF EQUIPMENTREQUIRING ELECTRICAL CONNECTIONS INCLUDING EXACT POINT OF ELECTRICAL CONNECTION. MAKEADJUSTMENTS TO CONDUIT ROUTING, PLACEMENT OF DISCONNECTS AND STARTERS AS REQUIRED.

PROTECT BRANCH CIRCUIT WIRING FROM PAINT OVERSPRAY DURING CONSTRUCTION TO PRESERVECOLOR-CODING. CONDUCTORS PAINTED SHALL BE COMPLETELY CLEANED OF PAINT BEFORE FINALCONNECTIONS ARE MADE.

VERIFY SECURITY SYSTEM OUTLET BOX AND CONDUIT REQUIREMENTS WITH SECURITY SYSTEMPROVIDER PRIOR TO INSTALLATION AND MAKE ALL NECESSARY ADJUSTMENTS.

COORDINATE WIRING DEVICE OUTLET BOX LOCATIONS WITH ARCHITECTURAL PLANS, ELECTRICALPLANS, ENLARGED FLOOR PLANS, EQUIPMENT AND FURNITURE LAYOUTS, SECTIONS, ELEVATIONS,DETAILS AND JOB SITE DIFFERENCES PRIOR TO ROUGHING-IN CONDUITS. MAKE REQUIREDADJUSTMENTS (WITH ARCHITECTS AND ENGINEERS APPROVAL) AT NO ADDITIONAL COST TO THEOWNER.

INSTALL DEVICES SHOWN ON DRAWINGS IN ACCORDANCE WITH MOUNTING HEIGHTS SHOWN IN THEELECTRICAL LEGEND AND/OR PROJECT SPECIFICATIONS. INSTALL FIRE ALARM DEVICES IN ACCORDANCEWITH A.D.A. REQUIREMENTS.

WHERE THE TERM "BRANCH CIRCUITRY" IS USED ON THESE DRAWINGS, IT IS TO BE CONSTRUED TOMEAN CONDUIT AND CONDUCTORS.

ELECTRICAL LEGEND:EXISTING 2' X 4' LIGHT FIXTURE.

EXISTING 2' X 4' LIGHT FIXTURE CONNECTED TO EXISTING EMERGENCY EGRESS LIGHTING CIRCUIT.

2' X 4' LED LIGHT FIXTURE, SUBSCRIPT NUMBER INDICATES LIGHT FIXTURE TYPE. SUBSCRIPT LETTERINDICATES FIXTURE TO BE CONTROLLED BY CORRESPONDING LIGHTING ZONE.

1' X 2' LED LIGTH FIXTURE, SUBSCRIPT NUMBER INDICATES LIGHT FIXTURE TYPE.

1' X 4' LED LIGHT FIXTURE, SUBSCRIPT NUMBER INDICATES LIGHT FIXTURE TYPE.

EXISITING DOWNLIGHT FIXTURE.

LED DOWN LIGHT FIXTURE, SUBSCRIPT NUMBER INDICATES LIGHT FIXTURE TYPE.

LED DOWN LIGHT FIXTURE WITH SELF CONTAINED BATTERY BACKUP. SUBSCRIPT "N" INDICATES NIGHT LIGHTFIXTURE (ALWAYS ON).

LIGHT FIXTURE CONNECTED TO EXISTING EMERGENCY EGRESS LIGHTING CIRCUIT. SUBSCRIPT NUMBERINDICATES LIGHT FIXTURE TYPE.

EXISTING WALL MOUNTED LIGHT FIXTURE.

WALL MOUNTED LED LIGHT FIXTURE. SUBSCRIPT NUMBER INDICATES LIGHT FIXTURE TYPE.

2' X 4' LED LIGHT FIXTURE WITH SELF CONTAINED BATTERY BACKUP. SUBSCRIPT NUMBER INDICATES LIGHTFIXTURE TYPE. SUBSCRIPT "N" INDICATES NIGHT LIGHT FIXTURE (ALWAYS ON).

2' X 4' LED LIGHT FIXTURE CONNECTED TO EXISTING EMERGENCY EGRESS LIGHTING CIRCUIT. SUBSCRIPTNUMBER INDICATES LIGHT FIXTURE TYPE.

1' X 4' LED LIGHT FIXTURE WITH SELF CONTAINED BATTERY BACKUP, SUBSCRIPT NUMBER INDICATES LIGHTFIXTURE TYPE.

WALL MOUNTED LED LIGHT FIXTURE POWERED THROUGH INVERTER. INSTALL TOP OF LIGHT FIXTURE +9'-0"A.F.F.

POWER INVERTER FOR WALL MOUNTED LIGHT FIXTURE - ISOLITE CATALOG NUMBER IMI-25-LC-V3 ORAPPROVED EQUAL. INSTALL INVERTER ABOVE THE CEILING.

EXIT LIGHT FIXTURE WITH BATTERIES BACK UP, PROVIDE DIRECTIONAL ARROWS AS INDICATED ONDRAWINGS. SHADING INDICATES NUMBER OF FACES LIT. SUBSCRIPT NUMBER INDICATES LIGHT FIXTURETYPE.

SITE POLE MOUNTED LIGHT FIXTURE. SUBSCRIPT NUMBER INDICATES LIGHT FIXTURE TYPE.

RECESSED CEILING MOUNTED SELF-CONTAINED EMERGENCY LIGHT WITH BATTERY BACKUP.

PENDANT MOUNTED LIGHT FIXTURE

SINGLE-POLE SWITCH, 20A, 120/277V, A.C., INSTALL +42" A.F.F.

THREE-WAY SWITCH, 20A, 120/277V, A.C., INSTALL +42" A.F.F.

FOUR-WAY SWITCH, 20A, 120/277V, A.C., INSTALL +42" A.F.F.

MOTOR RATED SNAP SWITCH, 20A, 120/277V, A.C., INSTALL +42" A.F.F.

OCCUPANCY SENSOR SWITCH, 20A, 120/277V, A.C., INSTALL +42" A.F.F.

SINGLE POLE KEY OPERATED SWITCH, 20A, 120/277V, A.C., INSTALL +42" A.F.F.

THREE WAY KEY OPERATED SWITCH, 20A, 120/277V, A.C., INSTALL +42" A.F.F.

FOUR WAY KEY OPERATED SWITCH, 20A, 120/277V, A.C., INSTALL +42" A.F.F.

LINE VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR - EATON CATALOG NUMBER OAC-DT-2000-ML.

LOW VOLTAGE OCCUPANCY SENSOR - EATON CATALOG NUMBER OAC-DT-2000.

LOW VOLTAGE OCCUPANCY SENSOR - EATON CATALOG NUMBER PDR-RC-4TSB-X. WALL MOUNT 9'-0" A.F.F.

LOW VOLTAGE OCCUPANCY SENSOR POWER PACK - EATON CATALOG NUMBER SP20-MV. INSTALL ABOVECEILING.

2000W WALL MOUNTED PHOTOCELL, PARAGON "CW" SERIES OR EQUAL.

CLASSROOM LIGHTING RELAY PANEL - EATON CATALOG NUMBER RC3D-PL. INSTALL CABINET ABOVECEILING WHERE INDICATED ON THE FLOOR PLANS. PROVIDE JUMPER CABLE TO OVERRIDE THE TWO HOURTIME CLOCK DRY CONTACT.

CLASSROOM LIGHTING CONTROL STATION - EATON CATALOG NUMBER PDR-RC-4TSB-X. PROVIDE SINGLEGANG BOX +48" A.F.F. WITH 1/2" CONDUIT UP TO ABOVE THE CEILING WITH PLENUM RATED CONDUITBUSHINGS ON BOTH ENDS OF CONDUIT. PROGRAM LIGHTING CONTROL STATION, SUCH THAT FIRST BUTTON(ON TOP) TURNS ALL LIGHT FIXTURES "ON." SECOND BUTTON DIMS ALL LIGHT FIXTURES TO "50%". THIRDBUTTON TURNS LIGHT FIXTURES WITH SUBSCRIPT "A" "OFF". FOURTH BUTTON TURNS ALL LIGHT FIXTURES"OFF".

DUPLEX RECEPTACLE, 20A, 120V, INSTALL +18" TO A.F.F., U.O.N. IF CENTER SHADED, INSTALL +6" ABOVESINK, COUNTER BACKSPLASH, U.O.N. "GFI" WHEN USED INDICATES GROUND FAULT INTERRUPTER. "WP"WHEN USED INDICATES WEATHER RESISTANT, WEATHERPROOF DEVICE WITH WEATHERPROOF WHILE INUSE LOCKABLE COVERPLATE. SUBSCRIPT "W" INDICATES DEVICE IN THE WIREMOLD SURFACE BOX.

DOUBLE DUPLEX RECEPTACLE, 20A, 120V, INSTALL +18" A.F.F., U.O.N.

DUPLEX RECEPTACLE FOR WALL MOUNTED PROJECTOR. PROVIDE 20A., 120 VOLT RECEPTACLE ANDOUTLET BOX +88" A.F.F. TO CENTERLINE OF BOX. COORDINATE RECEPTACLE LOCATION WITH OWNERFURNISHED PROJECTOR MOUNTING BRACKET. SEE DETAIL ON DRAWING SHEET E-403 FOR ADDITIONALINFORMATION.

ELECTRICAL CONNECTION TO EQUIPMENT.

ELECTRICAL CONNECTION TO EXHAUST FAN.

ELECTRICAL CONNECTION TO WATER HEATER.

TRANSFORMER, SEE POWER RISER DIAGRAM ON DRAWING SHEET E-501.

DISCONNECT SWITCH, 480V, U.O.N.: 3P = NUMBER OF POLES, 60 = SWITCH RATING, SN = SOLD NEUTRAL, 40 =FUSE RATING (NF INDICATES NONFUSED). PROVIDE IN NEMA 1 ENCLOSURE IF INSTALLED INDOORS AND INNEMA 3R ENCLOSURE IF INSTALLED OUT OF DOORS, U.O.N.

PANELBOARD, 208Y/120 VOLT.

PANELBOARD, 480Y/277 VOLT.

JUNCTION BOX, SIZE AS REQUIRED IF NOT INDICATED.

BRANCH CIRCUIT OR FEEDER WIRING IN CONDUIT. NO TICK MARKS INDICATED 2 #12 CONDUCTORS & 1 #12GND IN 1/2" CONDUIT U.O.N. TICK MARKS, WHEN SHOWN, INDICATE NUMBER OF CONDUCTORS IF OTHERTHAN THREE: ( ) INDICATES GROUNDING CONDUCTOR. SEE PANEL SCHEDULES FOR EXACT CONDUCTORSIZES.

HOMERUNS BRANCH CIRCUITRY TO PANEL. PANEL & CIRCUIT DESIGNATION AS INDICATED.

CONDUIT TURNED UP.

CONDUIT TURNED DOWN.

CONDUIT RUN CONCEALED ABOVE CEILING, IN WALL, BELOW FLOOR SLAB OR UNDERGROUND.

S

S

EF

S

F

4

T

J

S

15

E

WP

4

GFI

1

H1-7

3P

110

3R6040

F/C

S M

3S

S OS

OS

1

E

FAPS

FACP

S4K

3KS

KS

IN

2

7

E

E

2

7

8

9

A

A

8

T

F

P

U

WA

2

PC

HS15

M

TP

D

W

GENERAL FIRE ALARM NOTES:1.

2.

3.

4.

5.

ALL DEMOLITION AND NEW WORK ASSOCIATED WITH THE EXISTING FIRE ALARM SYSTEM SHALL BEPERFORMED BY A CERTIFIED NOTIFIER REPRESENTATIVE.

THE EXISTING FIRE ALARM CONTROL PANEL IS A NOTIFIER MODEL AFP1010. PROVIDE NEW FIRE ALARMDEVICES THAT ARE COMPATIBLE WITH THE EXISTING FIRE ALARM SYSTEM.

AT THE BEGINNING AND THE END OF THE PROJECT, TEST ALL FIRE ALARM DEVICES THAT ARE SCHEDULEDTO BE REMOVED AND REINSTALLED AS A PART OF THIS PROJECT. NOTIFY THE OWNER OF ANY DEFECTIVEDEVICES. RETEST ALL FIRE ALARM DEVICES AFTER REINSTALLATION AT THE END OF THE PROJECT. ANYDEVICE FOUND DEFECTIVE AT THE END OF THE PROJECT SHALL BE REPLACED WITH A NEW DEVICE AT NOADDITIONAL COST TO THE OWNER.

MODIFY THE EXISTING FIRE ALARM ANNUNCIATOR PANEL TO ELIMINATE INDICATING LIGHTS FOR DUCTSMOKE DETECTORS THAT ARE REMOVED BY THIS PROJECT.

ALL WORK ASSOCIATED WITH THE EXISTING FIRE ALARM SYSTEM SHALL BE ACCOMPLISHED ON THE SAMEDAY IT BEGINS. AT NO TIME SHALL THE BUILDING BE LEFT WITHOUT A FULLY FUNCTIONING FIRE ALARMSYSTEM. IF THE BUILDING IS LEFT WITHOUT FIRE ALARM PROTECTION OVERNIGHT THE CONTRACTOR ISREQUIRED TO PROVIDE STAFF TO MONITOR THE BUILDING TO THE SATISFACTION OF THE LOCALAUTHORITY HAVING JURISDICTION.

N

DC

N

1

OSLR

OSL

PP

WH

FIRE ALARM VISUAL DEVICE. INSTALL IN ACCORDANCE WITH ADA REQUIREMENTS. SUBSCRIPTINDICATES CANDELA LEVEL.

EXISTING FIRE ALARM AUDIO/VISUAL DEVICE.

FIRE ALARM AUDIO/VISUAL DEVICE. INSTALL IN ACCORDANCE WITH ADA REQUIREMENTS.SUBSCRIPT INDICATES CANDELA LEVEL.

FIRE ALARM PULL STATION, INSTALL +42" A.F.F.

FIRE ALARM SMOKE DETECTOR, SURFACE MOUNTED ON CEILING.

PROVIDE 120V POWER TO DOOR HOLD-OPEN DEVICES THROUGH A SINGLE POLE, NORMALLYCLOSED CONTACTOR (COIL VOLTAGE - 120V). PROVIDE POWER TO THE COIL BY TAPPING THE120V CIRCUIT AHEAD OF THE CONTACTOR AND RUNNING IT THROUGH A RELAY TO BECONTROLLED BY THE BUILDING FIRE ALARM SYSTEM SO ANY FIRE ALARM INITIATION WILL CAUSETHE RELAY TO OPEN, THE CONTACTOR TO OPEN AND THE DOOR HOLD OPEN DEVICES TO DE-ENERGIZE. THE REVERSE SHALL HAPPEN UPON CLEARING OF THE ALARM. PROVIDE ALLMATERIAL, EQUIPMENT AND HARDWARE NECESSARY FOR A COMPLETE INSTALLATION. INSTALLCONTACTOR AND RELAY IN A SINGLE ENCLOSURE ABOVE THE CEILING ABOVE EACH DOOR ORGROUP OF DOORS CONTROLLED. SERVE CONTACTOR FROM CIRCUIT INDICATED.

FIRE ALARM CONTROL PANEL.

FIRE ALARM POWER SUPPLY.

FIRE ALARM SYSTEM CONNECTION TO SPRINKLER SYSTEM TAMPER SWITCH.

FIRE ALARM SYSTEM CONNECTION TO SPRINKLER SYSTEM BELL.

FIRE ALARM SYSTEM CONNECTION TO SPRINKLER SYSTEM FLOW SWITCH.

CEILING MOUNTED FIRE ALARM AUDIO/VISUAL DEVICE. SEE FLOOR PLANS FOR ADDITIONALREQUIREMENTS. SUBSCRIPT INDICATES CANDELA LEVEL.

MAGNETIC DOOR HOLD-OPEN DEVICE. INSTALL OUTLET BOX AT THE HEIGHT REQUIRED BY THEDOOR HARDWARE PROVIDER.

PROJECTOR OUTLET. PROVIDE 1-GANG OUTLET BOX +88" A.F.F. TO CENTERLINE OF BOX.COORDINATE PROJECTOR OUTLET LOCATION WITH OWNER FURNISHED PROJECTOR MOUNTINGBRACKET. PROVIDE 1-1/2" EMPTY CONDUIT WITH PULL WIRE RATED FROM OUTLET BOX ANDTERMINATE ABOVE THE CEILING. SEE DETAIL ON DRAWING SHEET E-403 FOR ADDITIONALINFORMATION.

SMARTBOARD USB OUTLET. PROVIDE 1-GANG OUTLET BOX INSTALLED HORIZONTALLY +80" A.F.F.COORDINATE OUTLET BOX LOCATION WITH OWNER FURNISHED SMARTBOARD. PROVIDE 1-1/4"EMPTY CONDUIT WITH PULL WIRE RATED FROM OUTLET BOX AND TERMINATE ABOVE THECEILING. SEE DETAIL ON DRAWING SHEET E-403 FOR ADDITIONAL INFORMATION.

OWNER PROVIDED CEILING MOUNTED WIRELESS ACCESS POINT

DATA OUTLET. PROVIDE TWO GANG OUTLET BOX WITH 1" CONDUIT WITH PULL WIRE AND PLENUMRATED CONDUIT BUSHINGS. TERMINATE CONDUIT 6" ABOVE LAY-IN TILE CEILING, U.O.N.SUBSCRIPT "2" INDICATES NUMBER OF OWNER PROVIDED PLENUM RATED CAT 6 CABLEHOMERUNS BACK TO IDF ROOM. INSTALL OUTLET +18" A.F.F., U.O.N. SEE DETAIL ON DRAWINGSHEET E-403 FOR ADDITIONAL INFORMATION.

PROVIDE 2" EMT CONDUIT U.O.N.(WITH PULL WIRE AND PLENUM RATED CONDUIT BUSHINGS)ABOVE CEILING (QUANTITY AS SHOWN) 24" LONG MINIMUM, BUT WITH NOT LESS THAN 2" OFCONDUIT ON EACH SIDE OF WALL. PROVIDE UL APPROVED FIRE SEALS AFTER INSTALLATION OFALL CABLING. SEE FLOOR PLANS FOR DIFFERENT CONDUIT SIZE REQUIREMENTS.

J-HOOKS PROVIDED BY OTHERS.

TEACHERS PANEL OUTLET. SEE "TEACHERS PANEL "TP" DETAIL" ON DRAWING SHEET E-403.

EXISTING EXTERIOR INTERCOM SPEAKER.

OWNER PROVIDED EXTERIOR INTERCOM SPEAKER.

CEILING SPEAKER - SCHOOL INTERCOM SYSTEM. PROVIDED BY OWNER.

OWNER PROVIDED DOUBLE FACE, CEILING MOUNTED CLOCK.

CEILING MOUNTED CCTV CAMERA - SHOWN FOR REFERENCE ONLY.

EXTERIOR WALL MOUNTED CCTV CAMERA. SUBSCRIPT "R" INDICATES RELOCATED CAMERA.PROVIDE OUTLET BOXES AND CONDUIT IN ACCORDANCE WITH "EXTERIOR CCTV CAMERA DETAIL"ON SHEET E-403.

INTERIOR CEILING MOUNTED SECURITY MOTION DETECTOR AND CABLES PROVIDED BY OWNER.

DOOR CONTACTS PROVIDED BY OWNER. SEE "EXTERIOR DOOR CONTACT DETAIL" ON DRAWINGSHEET E-503".

ROOM NUMBER.

DEMOLITION NOTE INDICATOR.

NEW WORK NOTE INDICATOR.

CARD READER - COORDINATE OUTLET BOX SIZE AND TYPE WITH THE OWNERS SECURITYSYSTEM PROVIDER. PROVIDE 3/4" CONDUIT WITH PULLWIRE FROM OUTLET BOX, UP TO NEARESTLAY-IN TILE CEILING. PROVIDE BUSHINGS ON BOTH ENDS OF CONDUIT.

S

R

12

E

E

15

S E

1

8

16

R

B

CR

EER

PROF

ESSIONAL ENGI

N

AE

W

NO

MM

OC

GRI

VFO

HTL

INIAKENZIE CAMBAR

Lic. No.049752

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 1

:47:3

4 P

M E-001

LE

GE

ND

, A

BB

RE

VIA

TIO

NS

AN

D N

OT

ES

AD

DIT

ION

TO

HIC

KO

RY

MID

DL

E S

CH

OO

L

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

MW

H

KC

KC

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

89

TYPE MANUFACTURER'S CATALOG No. VOLT LAMPS MOUNTING REMARKS

5

4

3

2

1

8

7

6

9

10

LIGHT FIXTURE SCHEDULE NOTES:

IS TO BE INSTALLED, COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLANS AND FINISH SCHEDULES.MATCH MOUNTING HARDWARE AND FRAME WITH THE CEILING TYPE OR CONSTRUCTION IN WHICH FIXTURE

1.

SPECIFIC:

GENERAL:

LIGHT FIXTURE SCHEDULE

11 SEE NOTES 3 AND 4

SEE NOTE: 1

SEE NOTE: 2

SURE-LITES CX7-1-R LED277 CEILING/WALL

METALUX 24GR-LD5-30-F1-UNV-CDI 3000 LUMEN LED277 RECESSED

277METALUX 24CZ-LD5-45-UNV-L835-CDI 4500 LUMEN LED RECESSED

5000 LUMEN LED RECESSED

5500 LUMEN LED RECESSED

4000 LUMEN LED SURFACE/PENDANT

METALUX 24CZ-LD5-50-UNV-L835-SDI

METALUX 24CZ-LD5-55-UNV-L835-CDI

METALUX 4SNLED-LD5-40SL-UNV-L835-CDI-U

277

277

277

277

277 2000 LUMEN LED RECESSEDPORTFOLIO LD6B20D010-EU6B10208035-6LBMOH

SURE-LITES CX7-2-R LED277 CEILING

GENERAL AUXILIARY SYSTEMS NOTES:REFER TO DRAWING E-001 FOR SYMBOLS SHOWN ON DRAWINGS E-401, E-402, E-403, AND EXPLANATORY NOTESREGARDING SAME.

PROVIDE 3/4" CONDUIT (U.O.N.) FROM EACH DATA/ TELEPHONE OUTLET TO 6" ABOVE LAY-IN TILECEILING AND TURN CONDUIT OUT +6" FROM WALL. PROVIDE BUSHINGS ON EACH END OF ALL CONDUITS.

INSTALL DEVICES SHOWN ON DRAWINGS E-401 AND E-402 IN ACCORDANCE WITH MOUNTING HEIGHTS SHOWN INLEGEND ON DRAWING SHEET E-001 AND/OR THE PROJECT SPECIFICATIONS.

REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF CEILING SPEAKERS AND OTHERDEVICES SURFACE MOUNTED ON OR RECESSED IN CEILINGS.

WHERE AUXILIARY SYSTEM CABLES ARE RUN ABOVE DRYWALL CEILINGS OR IN AREAS WITH EXPOSEDCONSTRUCTION, RUN CABLING IN CONDUIT, SIZE AS REQUIRED. TERMINATE CONDUIT ABOVE NEAREST CORRIDORWITH LAY-IN TILE CEILING. RUN CONDUIT ABOVE BOTTOM CHORD OF THE STRUCTURE IN AREAS WITH EXPOSEDCONSTRUCTION.

COORDINATE DATA, TELEPHONE AND SPEAKER LOCATIONS WITH ARCHITECTURAL FLOOR PLANS, ELECTRICALPOWER PLANS, ENLARGED FLOOR PLANS, EQUIPMENT AND FURNITURE LAYOUTS, SECTIONS, ELEVATIONS,DETAILS, AND JOB SITE DIFFERENCES PRIOR TO ROUGHING-IN CONDUITS. MAKE REQUIRED ADJUSTMENTS (WITHARCHITECTS APPROVAL) AT NO ADDITIONAL COST TO OWNER.

PROVIDE 3/4" CONDUIT AND PULLWIRE FROM MECHANICAL ROOF EQUIPMENT REQUIRING DUCT SMOKEDETECTORS. RUN CONDUIT AND DUCT SMOKE DETECTOR AND TERMINATE CONDUIT BELOW ROOF AND ABOVENEAREST LAY-IN TILE CEILING FOR FIRE ALARM SUPPLIER USE. COORDINATE ALL WORK AND DUCT DETECTORLOCATION WITH FIRE ALARM SUPPLIER PRIOR TO ROUGH-IN OF CONDUIT.

ALL FIRE ALARM CABLES SHALL BE SHIELDED AND PLENUM RATED. PROVIDE CONDUIT (3/4" MINIMUM) FROMOUTLET BOX IN WALL TO 6" ABOVE CEILING. COORDINATE OUTLET BOX REQUIREMENTS WITH FIRE ALARM SYSTEMSUPPLIER AND PROVIDE AS REQUIRED. IN AREAS WITH CABLE TRAY, ATTACH FIRE ALARM CABLES TO UNDERSIDEOF OWNER PROVIDED CABLE TRAY USING PLENUM RATED TIE-WRAPS.

COORDINATE WITH DOOR HARDWARE SUPPLIER FOR EXACT TYPES OF HOLD OPEN DEVICES TO BE PROVIDED.PROVIDE MATERIAL AND EQUIPMENT AS REQUIRED FOR SATISFACTORY OPERATION OF ALL DOOR HOLD OPENDEVICES. DOOR HOLD OPEN DEVICES SHALL BE PROVIDED BY THE SUPPLIER OF DOOR HARDWARE AND ARESPECIFIED IN SPECIFICATION SECTION 08710.

DUCT SMOKE DETECTORS ARE FURNISHED BY DIVISION 28 FIRE ALARM SYSTEM CONTRACTOR, INSTALLED IN THEDUCT WORK BY DIVISION 23 CONTRACTOR AND CONNECTED TO THE FIRE ALARM SYSTEM BY DIVISION 28CONTRACTOR IN ACCORDANCE WITH SECTION 606 OF THE INTERNATIONAL MECHANICAL CODE. SEE MECHANICALDRAWINGS AND SPECIFICATIONS FOR QUANTITY AND LOCATION OF DUCT SMOKE DETECTORS REQUIRED.

PROVIDE EACH DUCT SMOKE DETECTOR WITH A REMOTE INDICATOR LIGHT IN ACCORDANCE WITH NFPA 72.INSTALL REMOTE INDICATING LIGHT FLUSH IN CEILING BELOW DUCT DETECTOR. LABEL ALL REMOTE INDICATINGLIGHTS WITH MECHANICAL EQUIPMENT DESIGNATIONS THAT ARE ASSOCIATED WITH THE IN-DUCT SMOKEDETECTOR.

COORDINATE WITH ARCHITECTURAL PLANS FOR ALL WALL TYPES, FIRE RATING AND SMOKE WALLS.

EXISTING CONDITIONS ILLUSTRATED HAVE BEEN DETERMINED FROM ORIGINAL CONSTRUCTION DOCUMENTS ANDLIMITED NON-INVASIVE FIELD INVESTIGATION. CONTRACTOR SHALL INVESTIGATE FIELD CONDITIONS PRIOR TOCOMMENCEMENT OF WORK, COORDINATE AND MAKE ADJUSTMENTS AS NECESSARY.

(DRAWINGS E-401 THROUGH E-402)

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

PROVIDE EXIT LIGHT WITH DIRECTIONAL ARROWS AS INDICATED ON THE LIGHTING PLANS.

IN ROOMS WITH NO CEILINGS, PROVIDE UNISTRUT TO SPAN THE UNDERSIDE OF THE TOP CHORD OF THE BARJOISTS FOR MOUNTING THE FIXTURE. PENDANT TO BE OF APPROPRIATE LENGTH TO MOUNT THE BOTTOM OFTHE FIXTURE + 9'-0" A.F.F.

PROVIDE LIGHT FIXTURE WITH HAPCO CATALOG NUMBER SSS14B4-4-BM POLE. PAINT POLE TO MATCH LIGHTFIXTURE. PROVIDE FOUNDATION FOR POLE IN ACCORDANCE WITH "FOUNDATION DETAIL 1" ON THIS SHEET.

INSTALL LIGHT FIXTURES END TO END IN COVE. CONNECT LIGHTS TO EACH OTHER WITH CORD FURNISHEDWITH FIXTURES.

COORDINATE CANOPY CEILING CONSTRUCTION WITH THE ARCHITECT.

PROVIDE LIGHT FIXTURE HANGERS, LENGTH AS REQUIRED TO INSTALL LOWEST POINT OF LIGHT FIXTURE +8'-8"A.F.F.

ABBREVIATIONS:A, AMP AMPERE

A.C. ALTERNATING CURRENT

A.F.F. ABOVE FINISHED FLOOR BKR BREAKER

CCTV CLOSED CIRCUIT TELEVISON

CKT CIRCUIT

CUH CABINET UNIT HEATER

DS DISTRIBUTION SWITCHBOARD

EF EXHAUST FAN

EMT ELECTRICAL METALLIC TUBING

FACP FIRE ALARM CONTROL PANEL

FAPS FIRE ALARM POWER SUPPLY

GFI GROUND FAULT INTERRUPTER

HWRP HOT WATER RECULATING PUMP

IU INDOOR UNIT

KV KILOVOLT

KVA KILOVOLT AMPERE

KW KILOWATT

L/C LIGHTING CONTACTOR

LED LIGHT EMITTING DIODE

MCB MAIN CIRCUIT BREAKER

MLO MAIN LUG ONLY

MTD MOUNTED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NO. NUMBER

OU OUTDOOR UNIT

ø PHASE

P/C POWER CONTACTOR

P POLE

RTU ROOF TOP UNIT

SPD SURGE PROTECTION DEVICE

SN SERIAL NUMBER

TYP TYPICAL

U.O.N. UNLESS OTHERWISE NOTIFIED

UH UNIT HEATER

VAV VARIABLE AIR VOLUME

W WIRE

WA WIRELESS ACCESS

WH WATER HEATER

WP WEATHERPROOF

XFMR TRANSFORMER

Y WYE

2.

SEE NOTE: 23200 LUMEN LED SURFACE/PENDANTMETALUX 4SNLED-LD5-32SL-UNV-L835-CDI-U

WATTS

2 W

31 W

36 W

41 W

46 W

23 W

28 W

19 W

2 W

SEE NOTE: 1

277 1500 LUMEN LED RECESSEDPORTFOLIO LD4B15D010-EU4B10208035-4LBMOH 15 W

AMETRIX LC-1-35K-1C-UNV-24-30 1500 LUMEN LED277 COVE18 W

3.

13

12

14

16 SEE NOTE 3

-6200 LUMEN LED WALL +11'-6" A.F.F.COOPER XTOR6B-W-BZ-277 277

277 1350 LUMEN LED RECESSEDNEO-RAY DR-LO-35-PES-0048-1-U-ED-1-W

LUMARK RDG-E02-LED-E-U-T3-BZ 5900 LUMEN LED277 POLE

58 W

14 W

65 W

277 2700 LUMEN LED RECESSEDNEO-RAY DR-LO-35-PES-0096-1-U-ED-1-W 28 W

4.

NOT TO SCALE

FOUNDATION DETAIL 1

FINISHED GRADE

3/4" PVC SCH. 40 CONDUIT FORLIGHTING CIRCUITRY.

60"

ANCHOR BOTLS ASREQUIRED BY POLEMANUFACTURER

FILL WITH NON-SHRINKGROUT TO INSURE SOUNDSEAT ON FOOTING

STUB UP CONDUITS TOWITHIN 3" OF HANDHOLE

HANDHOLE - MAXIMUM 24" A.F.G.

CONCRETE FOOTING FROM3000 PSI CONCRETE

24" DIA.

8 #4 BARS VERITICALWITH #3 TIES AT12" O.C.

24"

MIN

.

POLE AND FINISH ASSPECIFIED SEE LIGHTFIXTURE SCHEDULE

CAST ALUMINUM NUT COVER

1/2" CHAMFER ALL AROUND

NOTE: PROVIDE HEX NUTS BOTH TOP AND BOTTOM OF POLE BASE PLATE. ATTACHCOPPER EQUIPMENT GROUND CONDUCTOR TO INTERNAL LUG ON INTERIOR OF POLE.

NOT TO SCALE

FOUNDATION DETAIL 2

FINISHED GRADE

3/4" PVC SCH. 40 CONDUIT FORLIGHTING CIRCUITRY.

78"

PROVIDE ANCHOR BOLTS TOMATCH EXISTING POLEFOUNDATION.

FILL WITH NON-SHRINKGROUT TO INSURE SOUNDSEAT ON FOOTING

STUB UP CONDUITS TOWITHIN 3" OF HANDHOLE

HANDHOLE - MAXIMUM 24" A.F.G.

CONCRETE FOOTING FROM3000 PSI CONCRETE

24" DIA.

8 #4 BARS VERITICALWITH #3 TIES AT12" O.C.

24"

MIN

.

POLE AND FINISH ASSPECIFIED SEE LIGHTFIXTURE SCHEDULE

CAST ALUMINUM NUT COVER

1/2" CHAMFER ALL AROUND

NOTE: PROVIDE HEX NUTS BOTH TOP AND BOTTOM OF POLE BASE PLATE. ATTACHCOPPER EQUIPMENT GROUND CONDUCTOR TO INTERNAL LUG ON INTERIOR OF POLE.

15 SEE NOTE 54050 LUMEN LED277 RECESSED42 W

17 -METALUX 2SNLED-LD5-24L-UNV-L85-CD1-U 2400 LUMEN LED277 SURFACE21 W

SEE NOTE 5

NEO-RAY DR-LO-35-PES-0144-1-U-ED-1-W

SEE NOTE 5

5.

3"

3"

18 -SURE-LITES GC15042-SD LED277 RECESSED5 W

19 SEE NOTE 6ELAN LIGHTING 84031 LED277 PENDANT15 W

6.

EER

PROF

ESSIONAL ENGI

N

AE

W

NO

MM

OC

GRI

VFO

HTL

INIAKENZIE CAMBAR

Lic. No.049752

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 1

:37:1

6 P

M E-002

LIG

HT

FIX

TU

RE

SC

HE

DU

LE

AN

D N

OT

ES

AD

DIT

ION

TO

HIC

KO

RY

MID

DL

E S

CH

OO

L

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

RA

B

KC

KC

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

90

2E

5E

6

F

E

E

E E

E

2

1

1

12 TYP.

7

WP 4

WP

3

SS

8

11

10

9

E

E

E

EER

PROF

ESSIONAL ENGI

N

AE

W

NO

MM

OC

GRI

VFO

HTL

INIAKENZIE CAMBAR

Lic. No.049752

0' 1' 5' 10' 20'1/8" = 1'-0"

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

GRAPHIC SCALE

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 1

:39:0

1 P

M ED-101

FLO

OR

PLA

N -

AR

EA

1 -

DE

MO

LIT

ION

AD

DIT

ION

TO

HIC

KO

RY

MID

DL

E S

CH

OO

L

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

MA

C

KC

KC

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

91

1/8" = 1'-0"

FLOOR PLAN - AREA 1 - DEMOLITION

KEY PLANN.T.S.

1

DEMOLITION NOTES: (THIS DRAWING ONLY)

EXISTING TO REMAIN.

REMOVE LIGHT FIXTURE / EXIT LIGHT AND BRANCH CIRCUITRY BACK TO LAST OUTLET TO REMAIN.

COORDINATE REMOVAL OF EXISTING CCTV CAMERA WITH THE OWNER.

REMOVE DUPLEX RECEPTACLE, COVERPLATE AND BRANCH CIRCUITRY BACK TO LAST OUTLET TOREMAIN. ABANDON OUTLET BOX IN PLACE.

REMOVE LIGHT FIXTURE AND BRANCH CIRCUITRY. ABANDON OUTLET BOX IN PLACE.

REMOVE INTERCOM SYSTEM SPEAKER, GRILLE AND WIRING BACK TO LAST OUTLET TO REMAIN.ABANDON OUTLET BOX IN PLACE.

EXISTING FIRE ALARM PULL STATION TO REMAIN.

REMOVE LIGHT FIXTURE & POLE AND SAVE FOR REUSE. REMOVE POLE FOUNDATION.

REMOVE BRANCH CIRCUITRY TO NEXT LIGHT FIXTURE. SEE DRAWING ED-102 FOR CONTINUATION.

REMOVE CONDUCTORS FROM LIGHT FIXTURE BEING REMOVED, BACK TO NEXT EXISTING LIGHTFIXTURE (APPROXIMATELY 100 FEET AWAY). REMOVE CONDUIT TO POINT INDICATED AND SAVEREMAINING CONDUIT FOR REUSE.

REMOVE EXISTING CONDUIT TO THIS POINT.

1

2

3

4

5

6

7

8

9

10

11

3WA

JWP

76

EE

E

E

E E

1 1

1

2TYP.

F 4

J5

5

SE

WP

1

SE

8PCE 14

2

J

2TYP.E

EWP

3

6S

1

1

2

2

E

E

E

E

E

E

E

E

E

ETYP.

13

2

WP

PANEL"GH2"

PANEL "DLS"

PANEL "DL1"

PANEL "DH2"

PANEL "DH1"

PANEL "FL2"

PANEL "FL1"

PANEL "FH1"

PANEL "FH2"

9

10

1

1

1

E

E

11

12

E

E

1

1

1

1

E

1

1

1

1

1

E

EER

PROF

ESSIONAL ENGI

N

AE

W

NO

MM

OC

GRI

VFO

HTL

INIAKENZIE CAMBAR

Lic. No.049752

0' 1' 5' 10' 20'1/8" = 1'-0"

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

GRAPHIC SCALE

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 1

:39:0

2 P

M ED-102

FLO

OR

PLA

N -

AR

EA

S 2

& 3

- D

EM

OLIT

ION

AD

DIT

ION

TO

HIC

KO

RY

MID

DL

E S

CH

OO

L

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

MA

C

KC

KC

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

92

1/8" = 1'-0"

FLOOR PLAN - AREAS 2 & 3 - DEMOLITION

KEY PLANN.T.S.

23

DEMOLITION NOTES: (THIS DRAWING ONLY)

EXISTING TO REMAIN.

REMOVE LIGHT FIXTURE / EXIT LIGHT AND BRANCH CIRCUITRY BACK TO LAST OUTLET TOREMAIN.

COORDINATE REMOVAL OF EXISTING CCTV CAMERA WITH THE OWNER.

EXISTING FIRE ALARM PULL STATION TO REMAIN.

REMOVE LIGHT FIXTURE AND BRANCH CIRCUITRY. ABANDON OUTLET BOX IN PLACE.

REMOVE INTERCOM SYSTEM SPEAKER, GRILLE AND WIRING BACK TO LAST OUTLET TOREMAIN. ABANDON OUTLET BOX IN PLACE.

COORDINATE REMOVAL OF EXISTING WEATHERPROOF WIRELESS ACCESS ANTENNA WITHTHE OWNER.

REMOVE INTERCOM SYSTEM SPEAKER, GRILLE AND WIRING BACK TO LAST OUTLET TOREMAIN. PROVIDE BLANK WEATHERPROOF COVERPLATE FOR OUTLET BOX.

REMOVE LIGHT FIXTURE & POLE AND SAVE FOR REUSE. REMOVE POLE FOUNDATION.

REMOVE BRANCH CIRCUITRY TO NEXT LIGHT FIXTURE. SEE DRAWING ED-101 FORCONTINUATION.

REMOVE CONDUCTORS FROM LIGHT FIXTURE BEING REMOVED, BACK TO NEXT EXISTINGLIGHT FIXTURE (APPROXIMATELY 100 FEET AWAY). REMOVE CONDUIT TO POINT INDICATEDAND SAVE REMAINING CONDUIT FOR REUSE.

1

2

3

4

5

6

7

8

9

10

11

THE SITE LIGHTING CIRCUIT BEING INTERRUPTED IS FED BY PANEL "GH2". PANEL "GH2" ISLOCATED IN AN ELECTRICAL CLOSET BETWEEN TWO SCIENCE LABS.

REMOVE RECEPTACLE. REMOVE CONDUCTORS BACK TO LAST OUTLET TO REMAIN.

EXISTING PHOTOCELL TO REMAIN.

12

13

14

102-1

103

104

105109

106

120

110123

107B

A

B

B

B

B

B

B

B

R

D

A

A

A

A

B

B

B

B

R

D A

B

OS

LR31

A

3

A

3

A

3 3

3

3

3

3

R

D

B

3

3

3

3

3

3

3

3

3

3

3

3

A

A

A

AB

B

B

B

B

B

B

2

6

6

2

2

2

3

3

3

33

2

2

2

2

8

8

3

8

8

88

88

8 8

RD

R

D

4

B

4

B

4

A

4

A

4

B

4

B

4

B

4

B

4

A

4

A

4

B

4

B

4

A 4

A

4

A

4

A

22

22

22

4

B

4

B4

B

4

B

4

B

4

B

4

B

4

B

D

22

2 2

4

4

B4

B4

B4

B4

B4

B4

B4

A4A4A4

R D

BA

5

A

122

1

8

8

22

R

9

9

3

3

3

B

3

3

PANEL"H"

H-3

T/C

9

LR

H-7

LR

J

H-1

12

12

H-9 VIAT/C

6 TYPICAL

1

2

E

E

10

5

E

6

5

B

5

B

5

A

5

B

5

B

5

B

5 5 5 5 5

11

11

11

7

7

7

7

LR

2

2

2

9

9

16

16

16

6

63

H-5

1818

9

13

14

14

14

14

14

14

15

19

J

J

8

8

B B B

1

L

L

L

L

B

3

B

3

B

3

3

2

2

2

2

8

8

2 2

10

6

E

4

113

108

111A

111B

112

120

1413

19

19

19

19

EER

PROF

ESSIONAL ENGI

N

AE

W

NO

MM

OC

GRI

VFO

HTL

INIAKENZIE CAMBAR

Lic. No.049752

0' 1' 5' 10' 20'1/8" = 1'-0"

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

GRAPHIC SCALE

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 1

:37:2

6 P

M E-101

FLO

OR

PLA

N -

AR

EA

A -

LIG

HT

ING

AD

DIT

ION

TO

HIC

KO

RY

MID

DL

E S

CH

OO

L

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

MA

C

KC

KC

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

93

1/8" = 1'-0"

FLOOR PLAN - AREA A - LIGHTING

KEY PLANN.T.S.

A

NEW WORK NOTES: (THIS DRAWING ONLY)

CONNECT BRANCH CIRCUITRY TO EXISTING LIGHT FIXTURE ON EMERGENCYEGRESS LIGHTINGCIRCUIT.

CONNECT BRANCH CIRCUITRY TO EXISTING LIGHT FIXTURE ON NORMAL LIGHTING CIRCUIT.

INTERLOCK ALL OCCUPANCY SENSORS IN ALL CORRIDORS SUCH THAT THE ACTIVATION OF ANYSENSOR WILL ENERGIZE THE BRANCH CIRCUIT FOR THE LIGHT FIXTURES.

RELOCATE SITE LIGHTING FIXTURE AND POLE SAVED DURING DEMOLITION. PROVIDEFOUNDATION FOR POLE IN ACCORDANCE WITH "FOUNDATION DETAIL 2" ON DRAWING E-002.

PROVIDE 3/4" CONDUIT FROM THE END OF EXISTING CONDUIT SAVED DURING DEMOLITION ANDEXTEND TO RELOCATED POLE. PROVIDE 2 #8 AND 1 #10 GROUND FROM RELOCATED SITE LIGHTTO EXISTING SITE LIGHT APPROXIMATELY 80'-0" AWAY AND CONNECT TO EXISTING SITE LIGHTBRANCH CIRCUITRY IN EXISTING POLE.

BRANCH CIRCUITRY SHOWN OUTSIDE OF THE BUILDING FOR CLARITY PURPOSES ONLY.CONCEAL ALL BRANCH CIRCUITRY INSIDE THE BUILDING ABOVE THE CEILINGS.

PROVIDE 2 #8 AND 1 #10 GROUND IN 3/4" CONDUIT.

PROVIDE TWENTY FOUR (24) TYPE "11" LIGHT FIXTURES. CONNECT LIGHT FIXTURES TOGETHERWITH CORD AND CONNECTOR FURNISHED WITH LIGHT FIXTURE.

PROVIDE UNSWITCHED PHASE CONDUCTOR IN BRANCH CIRCUIT. CONNECT CONDUCTOR TOBATTERY PACKS IN TYPE "14" AND "15" LIGHT FIXTURES. CONDUCTOR SHALL BYPASS TIMECLOCK TO REMAIN ENERGIZED AT ALL TIMES.

PROVIDE POLE FOUNDATION IN ACCORDANCE WITH "FOUNDATION DETAIL 1" ON DRAWING SHEETE-002. INSTALL EXISTING POLE AND LIGHT FIXTURE SAVED DURING DEMOLITION ON NEWFOUNDATION.

PROVIDE POLE FOUNDATION IN ACCORDANCE WITH "FOUNDATION DETAIL 2" ON DRAWING SHEETE-002.

1

2

3

4

5

6

7

8

9

10

11

122

119

118

116

115

114

113

111A

117

B B

D

R

A

A

A

A

B

B

B

B

B

B

B

B

D R

A

A

A

A

B

B

B

B

B

B

B

BDR

D

R

A

A

A

A

A

B

B

B

B

B

B

B

DR

A

A

A

A

B

B

B

B

B

B

B

B

R

D

B

B

B

B

B

B

B

B

B

R

D

1

2

44

4 4

44

4

4

4

4

4

4

4

4

4

4

4

4

B

A

A

A

B

B

B

B

B

B

B

4

4

4

4

4

4

4

4

4

4

4

2

2

2

3

B

3

B

3

B

3

B

3

B

3

55

2

22

28

2

2

2

2

2

2

8

8

2

2

2

23

3

3

3

3

3

3

3

3

3 3

3

3

3

3

3

3

3

3

3

3

3

3

8

2

2

2

2

3

3

3

3

3

3

3

3

A

A

A

A

3

3

3

3

7

2

2

9

9

112

8

8

8

8

8

8

81 8

8

1

8

4

4

4

4

44

4

9

5 E

12

12

6 TYPICAL

2

12

PANEL"H"

LR

B 5

B 5

A

5

B 5

B 5

A 5 A 5

B 5

B 5

8

8

8

8

8

8

6

6

9

9

J

2

2

2

2

9

9

H-7

L

H-5

R

H-3

3

3

6

6

6

1

2

13

14

14

14

14

7

10

16

7

T/C

H-1

3

18

18

J

J

11

8

8

E

4

18

18

8

8

LL

L

L

L

J

14

124

22

120

121

1

19

19

19

19

19

19

19

EER

PROF

ESSIONAL ENGI

N

AE

W

NO

MM

OC

GRI

VFO

HTL

INIAKENZIE CAMBAR

Lic. No.049752

0' 1' 5' 10' 20'1/8" = 1'-0"

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

GRAPHIC SCALE

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 1

:37:4

1 P

M E-102

FLO

OR

PLA

N -

AR

EA

B -

LIG

HT

ING

AD

DIT

ION

TO

HIC

KO

RY

MID

DL

E S

CH

OO

L

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

MA

C

KC

KC

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

94

KEY PLANN.T.S.

B

1/8" = 1'-0"

FLOOR PLAN - AREA B - LIGHTING

NEW WORK NOTES: (THIS DRAWING ONLY)

CONNECT BRANCH CIRCUITRY TO EXISTING LIGHT FIXTURE ON EMERGENCY EGRESSLIGHTING CIRCUIT.

CONNECT BRANCH CIRCUITRY TO EXISTING LIGHT FIXTURE ON NORMAL LIGHTING CIRCUIT.

INTERLOCK ALL OCCUPANCY SENSORS IN ALL CORRIDORS SUCH THAT THE ACTIVATION OFANY SENSOR WILL ENERGIZE THE BRANCH CIRCUIT FOR THE LIGHT FIXTURES.

RELOCATE SITE LIGHTING FIXTURE AND POLE SAVED DURING DEMOLITION. PROVIDEFOUNDATION FOR POLE IN ACCORDANCE WITH "EXISTING SITE LIGHT FOUNDATION" ONDRAWING E-002.

PROVIDE 3/4" CONDUIT FROM THE END OF EXISTING CONDUIT SAVED DURING DEMOLITIONAND EXTEND TO RELOCATED POLE. PROVIDE 2 #8 AND 1 #10 GROUND FROM RELOCATEDSITE LIGHT TO EXISTING SITE LIGHT APPROXIMATELY 80'-0" AWAY AND CONNECT TO EXISTINGSITE LIGHT BRANCH CIRCUITRY IN EXISTING POLE.

BRANCH CIRCUITRY SHOWN OUTSIDE OF THE BUILDING FOR CLARITY PURPOSES ONLY.CONCEAL ALL BRANCH CIRCUITRY INSIDE THE BUILDING ABOVE THE CEILINGS.

PROVIDE 2 #8 AND 1 #10 GROUND IN 3/4" CONDUIT

PROVIDE FOURTY (40) TYPE "11" LIGHT FIXTURES. CONNECT LIGHT FIXTURES TOGETHERWITH CORD AND CONNECTOR FURNISHED WITH LIGHT FIXTURE.

1

2

3

4

5

6

7

PROVIDE POLE FOUNDATION IN ACCORDANCE WITH "FOUNDATION DETAIL 1" ON DRAWINGSHEET E-002. INSTALL EXISTING POLE AND LIGHT FIXTURE SAVED DURING DEMOLITION ONNEW FOUNDATION.

PROVIDE POLE FOUNDATION IN ACCORDANCE WITH "FOUNDATION DETAIL 2" ON DRAWINGSHEET E-002.

PROVIDE 5 #12 AND 1 #12 GROUND IN 1/2" CONDUIT.

9

8

10

11

102-1

103

104

105

109

106

110

111B

113

123

107B

108

120

120

4

4

GFI

GFI

F/C

GFI

E20203P

WH-1

HWRP

4

4

4

4

4

4

4

1E-202

L-5

L-3

L-39

L-37

L-36, 38

41

L-31

L-29

L-1

L-7

E-5

E-3

E-1

2

H-8

4 L-24, 26

1

L-27

L-25

4

L-20, 22

1

L-21

4

L-28, 30

1

L-17

L-19

L-23

L-16, 18

1

4

L-12, 14

4 1

L-13

L-15

L-9

4

L-8, 101

L-11

41

L-32,34

L-33

L1-25

GFI

GFI GFI

111A

112

EER

PROF

ESSIONAL ENGI

N

AE

W

NO

MM

OC

GRI

VFO

HTL

INIAKENZIE CAMBAR

Lic. No.049752

0' 1' 5' 10' 20'1/8" = 1'-0"

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

GRAPHIC SCALE

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 1

:38:3

6 P

M E-201

FLO

OR

PLA

N -

AR

EA

A -

PO

WE

RA

DD

ITIO

N T

O H

ICK

OR

Y M

IDD

LE

SC

HO

OL

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

MA

C

KC

KC

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

95

1/8" = 1'-0"

FLOOR PLAN - AREA A - POWER KEY PLANN.T.S.

A

NEW WORK NOTES: (THIS DRAWING ONLY)

CONNECT EACH DUPLEX RECEPTACLE TO A SEPARATE CIRCUIT.

COORDINATE MOUNTING HEIGHT OF RECEPTACLE FOR DATA RACK WITH THE OWNER.

1

2

123

122

107B

119

118

116

115

114

113

111B

111A

110

117

4

4

4

4

GFI

GFI

4

4

GFI

GFI

4

F/C

PANEL "DLS"

PANEL "DL1"

PANEL "DH2"

PANEL "DH1"

PANEL "FL2"

PANEL "FL1"

PANEL "FH1"

PANEL "FH2"

L-35

41

L-32,34

L-33

L1-1

L-41

41

L-40,42

L1-3

4

L1-2,4

1

L1-5

L1-6,84

1

L1-7

L1-9

L1-11

L1-13

44

L1-10,12

L1-14,16

1 1

L1-15L1-17

4

L1-18,201

L1-21

L1-19

1E-202

2

W

W

120

112

GFI

3

3

3

3

3

3

3

3

F/C

107A

E

4

L1-25

TPANEL "L1"

PANEL "L"

PANEL "E"T

XFMR "T1"

XFMR "TE"

PANEL "H"

E-7

FAPS

EER

PROF

ESSIONAL ENGI

N

AE

W

NO

MM

OC

GRI

VFO

HTL

INIAKENZIE CAMBAR

Lic. No.049752

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 1

:38:4

0 P

M E-202

FLO

OR

PLA

N -

AR

EA

B -

PO

WE

RA

DD

ITIO

N T

O H

ICK

OR

Y M

IDD

LE

SC

HO

OL

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

MA

C

KC

KC

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

96

KEY PLANN.T.S.

B

1/8" = 1'-0"

FLOOR PLAN - AREA B - POWER

1/4" = 1'-0"

ENLARGED POWER ROOM 111B1E-201

NEW WORK NOTES: (THIS DRAWING ONLY)

CONNECT EACH DUPLEX RECEPTACLE TO A SEPARATE CIRCUIT.

PROVIDE SURFACE METAL BOX EXTENSIONS ON EXISTING RECEPTACLE OUTLET BOXES.PROVIDE 2 #12 AND 1 #12 GROUND IN SURFACE METAL RACEWAY BETWEEN OUTLET BOXESAND CONNECT TO EXISTING BRANCH CIRCUITRY. PAINT BOX EXTENSIONS AND RACEWAY TOMATCH SURFACE ON WHICH ATTACHED.

EXISTING REUSED.

PROVIDE ELECTRICAL CONNECTION TO BACKFLOW PREVENTER VAULT. COORDINATE EXACTLOCATION WITH CIVIL DRAWINGS. COORDINATE ROUGH-IN REQUIREMENTS WITH EQUIPMENTSUPPLIER.

1

2

3

0 1' 5' 10' 20'

1/8" = 1'-0"

40'

GRAPHIC SCALES0

1/4" = 1'-0"

1' 5' 10' 20'

4

FACP

PANEL "H"

EXISTINGDISTRIBUTIONSWITCHBOARD"DS" 2

EXISTINGPANEL"EHE"

2

3

4

5

1

EER

PROF

ESSIONAL ENGI

N

AE

W

NO

MM

OC

GRI

VFO

HTL

INIAKENZIE CAMBAR

Lic. No.049752

01/16" = 1'-0"

5' 10' 20' 40'

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

GRAPHIC SCALE

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 1

:38:4

1 P

M E-203

PA

RT

IAL O

VE

RA

LL E

LE

CT

RIC

AL P

LA

NA

DD

ITIO

N T

O H

ICK

OR

Y M

IDD

LE

SC

HO

OL

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

RA

B

KC

KC

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

97 1/16" = 1'-0"

PARTIAL OVERALL ELECTRICAL PLAN

NEW WORK NOTES: (THIS DRAWING ONLY)

EXISTING SIMPLEX MODEL 4020 ADDRESSABLE FIRE ALARM CONTROL PANEL (FACP). PROVIDEPLENUM RATED FIRE ALARM WIRING FROM THE FACP AND CONNECT ALL NEW FIRE ALARMINITIATING, SIGNALLING AND MONITORING DEVICES IN THE ADDITION TO THE EXISTING FIREALARM CONTROL PANEL IN ACCORDANCE WITH MANUFACTURERS REPRESENTATIVE.

SEE "POWER RISER DIAGRAM" ON DRAWING E-501 FOR WORK ASSOCIATED WITH EXISTINGELECTRICAL EQUIPMENT.

PROVIDE PULL BOX ABOVE THE EXISTING CEILING. SIZE IN ACCORDANCE WITH THE N.E.C.

SEAL CONDUIT PENETRATIONS THROUGH FIRE WALL ON BOTH SIDES WITH FIRE RETARDANTSEALANT THAT MEETS OR EXCEEDS THE FIRE RATING OF THE WALL. COORDINATEREQUIREMENTS WITH THE GENERAL CONTRACTOR.

PROVIDE DISCONNECT SWITCH ON PRIMARY SIDE OF 15 KVA TRANSFORMER SERVING PANEL "E".SEE "POWER RISER DIAGRAM" ON DRAWING E-501 FOR ADDITIONAL INFORMATION

1

2

3

4

5

A

B

KEY PLANN.T.S.

123

105

109

106

120

110107B

108

104

103

102-1

VAV-8-1

VAV-8-2

VAV-8-3

VAV-8-4

VAV-8-5

VAV-8-9

VAV-8-10

E

E

E

E

E

E

VAV-8-8

E

E

E

VAV-8-6

E

E

CUH-3

CUH-1

VAV-8-17

E

H-26

4

5

30153P SN 1

30153P SN 1

3

J

5

52

30153P SN1

E

IU-1

6

4J

5

5

5

3

30153P SN1

30153P SN 1

2

5

30153P SN 1

45

30153P SN 1

35

H-11

30153P SN 1

2

J

5

J

5

J

5

5H-14

30NF3P 1

5

7

J

5

3

30NF3P 1

PANEL "H"

PANEL "L"

107A

EER

PROF

ESSIONAL ENGI

N

AE

W

NO

MM

OC

GRI

VFO

HTL

INIAKENZIE CAMBAR

Lic. No.049752

0' 1' 5' 10' 20'1/8" = 1'-0"

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

GRAPHIC SCALE

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 1

:38:4

9 P

M E-301

FLO

OR

PLA

N -

AR

EA

A -

HV

AC

PO

WE

RA

DD

ITIO

N T

O H

ICK

OR

Y M

IDD

LE

SC

HO

OL

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

MA

C

KC

KC

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

98

1/8" = 1'-0"

FLOOR PLAN - AREA A - HVAC POWER

KEY PLANN.T.S.

A

NEW WORK NOTES: (THIS DRAWING ONLY)

INSTALL DISCONNECT SWITCH ON WALL ABOVE THE CEILING. MAINTAIN NEC REQUIREDWORKING CLEARANCES AROUND DISCONNECT SWITCH AND ALL REQUIRED WORKINGCLEARANCE AROUND MECHANICAL EQUIPMENT AS DIRECTED BY THE MECHANCIALCONTRACTOR.

PROVIDE 4 #12 AND 1 #12 GROUND IN 1/2" CONDUIT. CONNECT VAV BOX FAN TO PHASE "A"CONDUCTOR AND NEUTRAL IN VAV BOX CONTROL PANEL.

PROVIDE 4 #12 AND 1 #12 GROUND IN 1/2" CONDUIT. CONNECT VAV BOX FAN TO PHASE "B"CONDUCTOR AND NEUTRAL IN VAV BOX CONTROL PANEL.

PROVIDE 4 #12 AND 1 #12 GROUND IN 1/2" CONDUIT. CONNECT VAV BOX FAN TO PHASE "C"CONDUCTOR AND NEUTRAL IN VAV BOX CONTROL PANEL.

PROVIDE 4 #8 AND 1 #10 GROUND IN 1" CONDUIT.

PROVIDE 1" CONDUIT UP TO OU-1 FOR EQUIPMENT WIRING FURNISHED BY SUPPLIER OFMECHANICAL EQUIPMENT IN ACCORDANCE WITH MECHANICAL SPECIFICATIONS. ELECTRICALCONNECTIONS TO EQUIPMENT SHALL BE BY THE ELECTRICAL CONTRACTOR. SEE DRAWINGE-303 FOR CONTINUATION.

PROVIDE ELECTRICAL CONNECTION TO "IU" VIA 3P DISCONNECT SWITCH PROVIDED WITH UNIT.

1

6

5

4

3

2

7

VAV-8-15E

VAV-8-14

E

E

VAV-8-13

E

VAV-8-11

VAV-8-12

VAV-8-7VAV-8-16E

E

E

VAV-8-18

E

E

E

UH-1

CUH-2

30153P SN 1

H-32

H-30

30153P SN 1

4

3

J

5

30153P SN 1

2

J

5

5

5

230153P SN 1

J

5

5

H-255

J

5

5

30153P SN 1

3

30153P SN

1

30153P SN

1

2

J

5

53

530153P SN1

H-205

5

30NF3P1

4

J 5

5

J5

J

E

5

5

230153P 1

VAV-8-19

PANEL "H"

EER

PROF

ESSIONAL ENGI

N

AE

W

NO

MM

OC

GRI

VFO

HTL

INIAKENZIE CAMBAR

Lic. No.049752

0' 1' 5' 10' 20'1/8" = 1'-0"

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

GRAPHIC SCALE

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 1

:38:5

0 P

M E-302

FLO

OR

PLA

N -

AR

EA

B -

HV

AC

PO

WE

RA

DD

ITIO

N T

O H

ICK

OR

Y M

IDD

LE

SC

HO

OL

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

MA

C

KC

KC

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

99

1/8" = 1'-0"

FLOOR PLAN - AREA B - HVAC POWER

KEY PLANN.T.S.

B

NEW WORK NOTES: (THIS DRAWING ONLY)

INSTALL DISCONNECT SWITCH ON WALL ABOVE THE CEILING. MAINTAIN NEC REQUIREDWORKING CLEARANCES AROUND DISCONNECT SWITCH AND ALL REQUIRED WORKINGCLEARANCE AROUND MECHANICAL EQUIPMENT AS DIRECTED BY THE MECHANCIALCONTRACTOR.

PROVIDE 4 #12 AND 1 #12 GROUND IN 1/2" CONDUIT. CONNECT VAV BOX FAN TO PHASE "A"CONDUCTOR AND NEUTRAL IN VAV BOX CONTROL PANEL.

PROVIDE 4 #12 AND 1 #12 GROUND IN 1/2" CONDUIT. CONNECT VAV BOX FAN TO PHASE "B"CONDUCTOR AND NEUTRAL IN VAV BOX CONTROL PANEL.

PROVIDE 4 #12 AND 1 #12 GROUND IN 1/2" CONDUIT. CONNECT VAV BOX FAN TO PHASE "C"CONDUCTOR AND NEUTRAL IN VAV BOX CONTROL PANEL.

PROVIDE 4 #8 AND 1 #10 GROUND IN 1" CONDUIT.

1

2

3

4

5

EF-23

EF-25

EF-24EF

EF

EF

RTU-8

E

OU-1

L1-23

E

H-38 4

L1-24 4WP,GFI

2

E

WP,GFI

L1-22 6

2

5

3

E-86

200150

3P 3R 1

3015

2P 240V,3R1

EER

PROF

ESSIONAL ENGI

N

AE

W

NO

MM

OC

GRI

VFO

HTL

INIAKENZIE CAMBAR

Lic. No.049752

0' 1' 5' 10' 20'1/8" = 1'-0"

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

GRAPHIC SCALE

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 1

:38:5

1 P

M E-303

PA

RT

IAL R

OO

F P

LA

N -

HV

AC

PO

WE

RA

DD

ITIO

N T

O H

ICK

OR

Y M

IDD

LE

SC

HO

OL

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

RA

B

KC

KC

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

100

KEY PLANN.T.S.

A

B

1/8" = 1'-0"

PARTIAL ROOF PLAN - HVAC POWER

NEW WORK NOTES: (THIS DRAWING ONLY)

INSTALL DISCONNECT SWITCH ON A NON-REMOVABLE PANEL ON MECHANICAL EQUIPMENT.LOCATE AS DIRECTED BY THE MECHANCIAL CONTRACTOR.

INSTALL RECEPTACLE IN A WEATHERPROOF OUTLET BOX ON A NON-REMOVABLE PANEL ONMECHANICAL EQUIPMENT. LOCATE AS DIRECTED BY THE MECHANCIAL CONTRACTOR.

PROVIDE ELECTRICAL CONNECTION TO ENTHALPY MODULE IN RTU. COORDINATEREQUIREMENTS WITH THE MECHANCIAL CONTRACTOR.

RUN HOMERUN UP THROUGH ROOF CURB. COORDINATE ROUTING WITH THE MECHANCIALCONTRACTOR.

PROVIDE 1" CONDUIT DOWN TO IU-1 FOR EQUIPMENT WIRING FURNISHED BY SUPPLIER OFMECHANICAL EQUIPMENT IN ACCORDANCE WITH MECHANICAL SPECIFICATIONS. ELECTRICALCONNECTIONS TO EQUIPMENT SHALL BE BY THE ELECTRICAL CONTRACTOR. SEE DRAWINGE-301 FOR CONTINUATION.

RUN HOMERUN UP THROUGH ROOF PENETRATION PROVIDED BY THE MECHANICALCONTRACTOR. COORDINATE REQUIREMENTS WITH THE MECHANCIAL CONTRACTOR.

ALL CONDUIT RUN EXPOSED ON THE ROOF SHALL BE LIQUID-TIGHT FLEXIBLE METAL CONDUIT.

SEE DRAWING E-202 FOR LOCATION OF PANELS "H", "L1" AND "E".

1

2

3

4

5

6

7

8

7 8

123

105

106

107B

108

120

110

109

120

104

103

102-1

TP

TP

TP

TP

TP

TP

TP

HS

WA

30

UP

UP

WA

HS30

HS

WA

HS

U

P

UP

UP

WA

HS

WA

HS30

30

HS

WA

HS

WA

30

U P

U

P

30

15F

DC

15

15

F/C

15

DC

30

1

2

1

2

2

2

2

22

2

2

2

2

2

2

2

CR

CR

15

30

DC

R

R

M

M

FAPS

SE

CR

DC3

2

F

15

15

M

107A111A

112

111B

113

101

EER

PROF

ESSIONAL ENGI

N

AE

W

NO

MM

OC

GRI

VFO

HTL

INIAKENZIE CAMBAR

Lic. No.049752

0' 1' 5' 10' 20'1/8" = 1'-0"

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

GRAPHIC SCALE

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 1

:38:5

8 P

M E-401

FLO

OR

PLA

N -

AR

EA

A -

AU

XIL

IAR

Y S

YS

TE

MS

AD

DIT

ION

TO

HIC

KO

RY

MID

DL

E S

CH

OO

L

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

MA

C

KC

KC

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

101

1/8" = 1'-0"

FLOOR PLAN - AREA A - AUXILIARY SYSTEMS

KEY PLANN.T.S.

A

NEW WORK NOTES: (THIS DRAWING ONLY)

SEE EXTERIOR DOOR DETAIL ON DRAWING SHEET E-403 FOR ADDITIONAL REQUIREMENTS.

PROVIDE 4" EMT CONDUIT SLEEVE THROUGH WALL WITH PLENUM RATED BUSHINGS ONBOTH ENDS.

PROVIDE THREE (3) 4" EMT CONDUIT SLEEVES THROUGH WALL PLENUM RATED BUSHINGS ONBOTH ENDS. COORDINATE SLEEVE LOCATION WITH OWNERS DATA CABLING INSTALLER.

1

2

3

122

119

118

116115

114113

111B

111A

117

TP

TP

TPTP

TP

TP

TP

HS

WA30

P U

HS

WA30

P

U

HS

WA

30

U

P

HS

30

WA

U

P

HS

WA

HS

WA

30

30

UP

2

2

UP

30

HS

UP

30

WA

DC

F

15

15

15

F/C

F/C

2

12

2

2

22

2

2

2

2

2

2

E-9

DC

M

CR

M

3

2WA

30

15

120

121

120

112

107A

CR

15

126

EER

PROF

ESSIONAL ENGI

N

AE

W

NO

MM

OC

GRI

VFO

HTL

INIAKENZIE CAMBAR

Lic. No.049752

0' 1' 5' 10' 20'1/8" = 1'-0"

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

GRAPHIC SCALE

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 1

:39:0

0 P

M E-402

FLO

OR

PLA

N -

AR

EA

B -

AU

XIL

IAR

Y S

YS

TE

MS

AD

DIT

ION

TO

HIC

KO

RY

MID

DL

E S

CH

OO

L

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

MA

C

KC

KC

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

102

1/8" = 1'-0"

FLOOR PLAN - AREA B - AUXILIARY SYSTEMS

KEY PLANN.T.S.

B

NEW WORK NOTES: (THIS DRAWING ONLY)

SEE EXTERIOR DOOR DETAIL ON DRAWING SHEET E-403 FOR ADDITIONAL REQUIREMENTS.

PROVIDE TWO (2) 2" EMT CONDUITS WITH PULL WIRES RUN ABOVE SLOPED CEILING FOR USEBY THE OWNER. PROVIDE PLENUM RATED BUSHINGS ON BOTH ENDS OF CONDUITS AND CAPUNUSED CONDUIT FOR FUTURE USE.

SEAL CONDUIT PENETRATIONS THROUGH FIRE WALL ON BOTH SIDES WITH FIRE RETARDANTSEALANT THAT EXCEEDS THE FIRE RATING OF THE WALL. COORDINATE REQUIREMENTS WITHTHE GENERAL CONTRACTOR.

1

2

3

P

FLOOR

SHELF

POWER BRANCH CIRCUITRY

PROVIDE SINGLE GANG BOX POWER AND DATA

PROVIDE 1-1/2" EMPTY CONDUIT WITH PLENUMRATED BUSHING STUBBED ABOVE CEILING

PROVIDE 1-1/4" EMPTY CONDUIT WITH PLENUMRATED BUSHING STUBBED ABOVE CEILING

88" A.F.F. TO BOTTOM OF BOXES

PROVIDE SINGLE GANG BOX INSTALLEDHORIZONTALLY FROM SMARTBOARD USBINTERFACE. COORDINATE HORIZONTAL BOXLOCATION WITH OWNER'S CABLING CONTRACTOR.

SMARTBOARD PROJECTOR MOUNT WITH (2) SINGLE GANG BOX"CUT-OUTS" FOR ELECTRICAL ROUGH-INS. MOUNTPROVIDED BY THE OWNER. COORDINATE ROUGH-IN WITH BACK PLATE.

CEILING

9'-0"

78"

17"

14" U

3-1/4"

C

32" MAX

3-1/4"

CEILING

FLOOR LINE

18" A.F.F.

PROVIDE SINGLE GANGOUTLET BOX FOR USBINTERFACE

PROVIDE TWO GANG,3" DEEP OUTLET BOX

POWER BRANCHCIRCUITRY

PROVIDE 1-1/2" CONDUITWITH PLENUM RATED BUSHINGSTUBBED ABOVE THE CEILING

CEILING

18" A.F.F.

DUPLEXRECEPTACLE

PROVIDE 2 GANGBOX WITH 1 GANGPLASTER RING

PROVIDE 1" CONDUIT WITHPLENUM RATED BUSHINGSTUBBED UP ABOVE THE CEILING

POWER BRANCHCIRCUITRY

2

FLOOR LINE

PROVIDE 1" CONDUITWITH PLENUM RATEDBUSHING STUBBED UPABOVE THE CEILING

EER

PROF

ESSIONAL ENGI

N

AE

W

NO

MM

OC

GRI

VFO

HTL

INIAKENZIE CAMBAR

Lic. No.049752

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 1

:39:0

0 P

M E-403

TY

PIC

AL A

UX

ILLIA

RY

SY

ST

EM

S D

ET

AIL

SA

DD

ITIO

N T

O H

ICK

OR

Y M

IDD

LE

SC

HO

OL

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

RA

B

KC

KC

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

103

NOT TO SCALE

SMARTBOARD/PROJECTOR DETAIL

NOT TO SCALE

TEACHER PANEL DETAIL "TP"NOT TO SCALE

DATA OUTLET DETAIL

NOT TO SCALE

EXTERIOR DOOR CONTACTS DETAIL

PANEL "H" 600 AMP 480Y/277V, 3∅, 4W, M.L.O., SURFACE MTD.

CBACKT.NO.

WIRESIZE TRIP

CKT.BKR.

KAIC

LOAD (AMPS)

CBA

PHASENO.CKT.

SIZEWIRECKT.BKR.

TRIPKAICCBA

LOAD (AMPS)LOAD SERVEDLOAD SERVED

8

3029

2827

1512262550 8

2423

2221

2019

1817

1615

1413

1211

109

87

65

43

7.8

7.8

7.8

28.9

28.9

28.9

35.6

35.6

35.6

235 1

50

VAV BOXES

CUH-3

PANEL "L" 400 AMP 208Y/120V, 3∅, 4W, M.C.B., SURFACE MTD.

50 835.6

35.6

35.6

VAV BOXES

7.8

7.8

12 1220

20 10

1025

20 12

OUTSIDE LIGHTS

LIGHTS

28.9

28.9

28.9

14.4

14.4

14.4

WATER HEATER

VAV BOXES

-

-

-

12

508

20

- 20

12

4241

4039

1501/03837175 2/0

3635

3433

3231

120

120

120

135

135

135

7.8

7.8

7.8

15

PANEL "L"&"L1"

CUH-2

RTU-1

20 --

-

-

-

-

SPARE

SPARE

SPARE

CBACKT.NO.

WIRESIZE TRIP

CKT.BKR.

KAIC

LOAD (AMPS)

CBA

PHASENO.CKT.

SIZEWIRECKT.BKR.

TRIPKAICCBA

LOAD (AMPS)LOAD SERVEDLOAD SERVED

3029

2827

2625

2423

2221

2019

1817

1615

1413

1211

109

87

65

43

10.5

10

9

222 1

10

10.5

10

10.5

10

10.5

20 12HWRP

RECEPTACLES

12

12

12

CHARGE CART

-

-

-

12 20

- 20

4241

4039

3837

3635

3433

3231

9

10

10.5

10

10.5

10

PANEL "L1" 400 AMP 208Y/120V, 3∅, 4W, M.L.O., SURFACE MTD.

CBACKT.NO.

WIRESIZE TRIP

CKT.BKR.

KAIC

LOAD (AMPS)

CBA

PHASENO.CKT.

SIZEWIRECKT.BKR.

TRIPKAICCBA

LOAD (AMPS)LOAD SERVEDLOAD SERVED

3029

2827

--262510

2423

2221

2019

1817

1615

1413

1211

109

87

65

43

-

-

-

12

-

-

12

3

10

222 1

-

- -

- -

-

VAULT HEATER

ROOF RECEPTACLES

ENTHALPY MODULE

SPACE

SPACE

SPACE

9

10

11EF-23,24,25

10

10.5

10

20 12RECEPTACLES 12

12

12

CHARGE CART

-

-

-

-

-

4241

4039

30103837-

3635

3433

3231

1

1

1

-

-

-

-

-

-

-

-

- SPACE

SPACE

SPACE

SPD

--

-

-

-

-

PANEL "E" 60 AMP 208Y/120V, 3∅, 4W, M.C.B., SURFACE MTD.

CBACKT.NO.

WIRESIZE TRIP

CKT.BKR.

KAIC

LOAD (AMPS)

CBA

PHASENO.CKT.

SIZEWIRECKT.BKR.

TRIPKAICCBA

LOAD (AMPS)LOAD SERVEDLOAD SERVED

1817

1615

1413

1211

109

87

65

43

210 1

-

-

-

-

-

-

12

12

-

20 12

12

12

FAPS

SPRINKLER SYS.BELL

SPARE

IDF RECEPTACLE

-

-

-

11

11

-

OU-1

SPACE

SPACE

SPACE

SPACE

1

1

1

SPD

-

12

-

--

-

- -

-

15

10 30

LIGHTS

LIGHTS

LIGHTS

CUH-1

UH-1

VAV BOXES

VIA XFMR "T1"

10.5

10

7.8

9

9

10.5

20 12

20 12

20 12

1025

1025

20

20

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

10.5

9

10

3

10.5

7.5

PANEL "L" IS THE LEFT HAND SECTION OF A TWO SECTION PANELBOARD.

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

12 20

12 20

12 20

12 20

12 20

12 20

12 20

12 20

12 20

12 20

12 20

12 20

12 20

12 20

12 20

12 20

12 20

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

PANEL "L1" IS THE RIGHT HAND SECTION OF A TWO SECTION PANELBOARD.

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

CHARGE CART

10.5

10

10.5

10

12

10

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

20

20

20

20

20

20

20

20

20

20

20

20

12

12

12

12

12

12

IDF RECEPTACLE

IDF RECEPTACLE

SPARE

SPARE

SPARE

10

3

-

10

10

10

20

20

20

20

20

20

20

20

2210

SPARE

SPARE

SPARE

20

20

-

-

10

SPARE

SPARE

SPARE

-

-

20

20

35

EXISTING 480Y/277 VOLTDISTRIBUTION SWITCHBOARD "DS"

PANEL

"H"

PANEL

"L"

PANEL

"L1"

FLOOR

XFMR"T1"

POWER RISER DIAGRAMNOT TO SCALE

PANEL

"E"

XFMR"TE"

PANEL

"EHE"

EXISTING

1

2 3

10

13

12

11

14

10

9

8

76

14

430NF3P

5

5

2

15

10

EER

PROF

ESSIONAL ENGI

N

AE

W

NO

MM

OC

GRI

VFO

HTL

INIAKENZIE CAMBAR

Lic. No.049752

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 1

:39:0

1 P

M E-501

PA

NE

LB

OA

RD

SC

HE

DU

LE

S A

ND

PO

WE

RR

ISE

R D

IAG

RA

M

AD

DIT

ION

TO

HIC

KO

RY

MID

DL

E S

CH

OO

L

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

RA

B

KC

KC

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

104

POWER RISER DIAGRAM NOTES:

PROVIDE 600A-3P SIEMENS TYPE HLD6 CIRCUIT BREAKER WITH ALL REQUIRED MOUNTINGHARDWARE AND INSTALL IN AVAILABLE SPACE IN SWITCHBOARD. PROVIDE NEW BAKELITENAMEPLATE FOR SWITCHBOARD TO MATCH EXISTING SWITCHBOARD LABELS.

PROVIDE TWO (2) 3-1/2" CONDUITS WITH 4-350 KCMIL AND 1 #1 GROUND IN EACH CONDUIT.CONNECT TO NEW CIRCUIT BREAKER PRIVIDED BY POWER RISER DIAGRAM NOTE 1.

PROVIDE PULL BOX ABOVE EXISTING CEILING. SIZE IN ACCORDANCE WITH THE N.E.C.

PROVIDE 25A-3P, 14 KAIC CIRCUIT BREAKER AND INSTALL IN AVAILABLE SPACE IN EXISTINGPANEL "EHE". CHANGE PANEL INDEX TO REFLECT LOAD SERVED.

PROVIDE 3 #8 AND 1 #8 GROUND, IN 1" CONDUIT. CONNECT TO NEW CIRCUIT BREAKERPRIVIDED BY POWER RISER DIAGRAM NOTE 4.

PROVIDE 112.5 KVA 480-208Y/120 VOLT, K-4 RATED DRY TYPE TRANSFORMER.

PROVIDE 5-600 KCMIL AND 1 #1/0 GROUND IN 4" CONDUIT.

PROVIDE 1 #1/0 GROUNDING ELECTRODE CONDUCTOR IN 3/4" CONDUIT AND GROUNDTRANSFORMER IN ACCORDANCE WITH ARTICLE 250 OF THE N.E.C.

PROVIDE THRU-FEED LUGS IN FIRST SECTION OF THE PANE. PROVIDE CONDUCTORSMATCHING FEEDER BETWEEN THE THRU FEED LUGS AND THE MAIN LUGS OF THE SECONDSECTION OF THE PANELBOARD.

PROVIDE SURGE PROTECTION DEVICE (SPD) IN NEMA 1 ENCLOSURE. PROVIDE 4 #10 AND 1 #10 GROUND IN 1/2" CONDUIT ANC CONNECT TO CIRCUIT BREAKER IN PANELBOARD INACCORDANCE WITH THE PANELBOARD SCHEDULE.

PROVIDE 15 KVA 480-208Y/120 VOLT, K-4 RATED DRY TYPE TRANSFORMER.

PROVIDE 1 #8 GROUNDING ELECTRODE CONDUCTOR IN 1/2" CONDUIT AND GROUNDTRANSFORMER IN ACCORDANCE WITH ARTICLE 250 OF THE N.E.C.

PROVIDE 5 #6 AND 1 #8 GROUND IN 1-1/2" CONDUIT.

PROVIDE HOUSEKEEPING PAD IN ACCORDANCE WITH SPECIFICATION SECTION 262200.

PROVIDE 3 #2/0 AND 1 #6 GROUND IN 2" CONDUIT.