Answers for energy.
Medium-Voltage Switchgear
Catalog HA 35.41 2009
Fixed-Mounted Circuit-Breaker SwitchgearType NXPLUS C up to 24 kV, Gas-Insulated
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
2/56
2 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
R
-HA35-126.tif
R-HA35-106.eps
R-HA35-123.eps
R-HA35-107.eps
R-HA35-109.eps
ApplicationPublic power supply system
ApplicationIndustry
ApplicationIndustry and offshore
NXPLUS C switchgear
20 kV (example)
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
3/56
3Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Contents
Application Page
Types, typical uses,ratings 4 and 5
Requirements
Features, safety, technology 6 and 7
Technical data
Electrical data 8 and 9Room planning 10Shipping data, classification 11
Dimensions
Front views, sections, floor openings, fixing points 12 to 20
Product range
Single-busbar panels 21 to 23Double-busbar panels 24
Design
Basic panel design 25
Components
Vacuum circuit-breaker 26 and 27Three-position switches 28 and 29HV HRC fuse assembly 30Allocation of three-position switch-disconnectorwith HV HRC fuses, transformer ratings 31 to 33Vacuum contactor, motor protection 34Busbars 35Current and voltage transformers 36 to 38Panel connection 39Installation possibilities for cable connectionsand surge arresters 40 to 46Panel connection (commercially available
cable sealing ends) 47 and 48Indicating and measuring equipment 49 to 51Protection, control, measuring andmonitoring equipment 52
Standards
Standards, specifications, guidelines 53 and 54
Fixed-Mounted Circuit-Breaker Switchgear
Type NXPLUS C up to24 kV, Gas-InsulatedMedium-Voltage Switchgear
Catalog HA 35.41 2009
Invalid: Catalog HA 35.41 2007Supplement Feb. 2008 to Catalog HA 35.41
The products and systems described in this catalog aremanufactured and sold according to a certified quality andenvironmental management system (acc. to ISO 9001and ISO 14001).(DQS Certificate Reg. No. DQS 003473 QM UM).The certificate is accepted in all IQNet countries.
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
4/56
4 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Types
Application
R-HA35-105a.eps
R-HA35-125.eps
Circuit-breaker panel 600 mm Circuit-breaker panel 900 mm
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
5/56
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
6/56
6 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Requirements
Environmental independenceHermetically tight, welded switchgear vessels made of stainlesssteel make NXPLUS C switchgear:
Insensitive to aggressive ambient conditions, such as:Saline airAir humidityDust
Condensation Tight to ingress of foreign objects, such as:DustPollutionSmall animalsHumidityIndependent of the site altitude.
Compact designThanks to the use of SF6insulation, compact dimensions arepossible.Thus:
Existing switchgear rooms can be used effectivelyNew constructions cost littleCostly city-area space is saved.
Maintenance-free designSwitchgear vessels designed as sealed pressure systems,maintenance-free switching devices and enclosed cable plugsensure:
Maximum supply reliabilityPersonnel safetySealed-for-life design according to IEC 62271-200(sealed pressure system)Installation, operation, extension and replacementwithout SF6gas workReduced operating costsCost-efficient investmentNo maintenance cycles.
Innovation
The use of digital secondary systems and combined protectionand control devices ensures:Clear integration in process control systemsFlexible and highly simplified adaptation to new systemconditions and thus to cost-efficient operation.
Service lifeThe service life of gas-insulated NXPLUS C switchgear is 35 yearsas a minimum.
Personal safetySafe-to-touch and hermetically sealed primary enclosureCable terminations, busbars and voltage transformers aresurrounded by earthed layersAll high-voltage parts including the cable terminations, bus-bars and voltage transformers are metal enclosedCapacitive voltage detecting system to verify safe isolation
from supplyOperating mechanisms and auxiliary switches safely accessibleoutside the primary enclosure (switchgear vessel)Due to the system design, operation is only possible withclosed switchgear enclosureStandard degree of protection IP 65 for all high-voltage partsof the primary circuit, IP 3XD for the switchgear enclosureaccording to IEC 60529 and VDE 0470-1High resistance to internal arcs by logical mechanical interlocksand tested switchgear enclosurePanels tested for resistance to internal faults up to 31.5 kALogical mechanical interlocks prevent maloperationMake-proof earthing by means of the vacuum circuit-breaker.
Security of operationHermetically sealed primary enclosure independent of environ-
mental effects (pollution, humidity and small animals)Maintenance-free in an indoor environment (IEC 62271-1and VDE 0671-1)Operating mechanisms of switching devices accessible outsidethe primary enclosure (switchgear vessel)Metal-coated, plug-in inductive voltage transformers mountedoutside the SF6switchgear vesselCurrent transformers as ring-core current transformersmounted outside the SF6switchgear vesselComplete switchgear interlocking system with logical mechani-cal interlocksWelded switchgear vessels, sealed for lifeMinimum fire loadType and routine-testedStandardized, NC production processes
Quality assurance in accordance with DIN EN ISO 9001 More than 500,000 switchgear panels of Siemens in operationworldwide for many yearsO ption: Aseismic design.
ReliabilityType and routine-testedStandardized, NC production processesQuality assurance in accordance with DIN EN ISO 9001More than 500,000 switchgear panels of Siemens in operationworldwide for many years.
Features Safety
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
7/56
7Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Technology
Requirements
General3-pole enclosure of the primary part consisting of a switchgearvessel made of stainless steelInsulating gas SF 6Three-position switch as busbar disconnector and feeder earth-ing switchMake-proof earthing by means of the vacuum circuit-breaker
Compact dimensions due to SF 6insulationHermetically tight, welded switchgear vessel made of stainlesssteel1-pole, solid-insulated, screened busbars, plug-in typeCable connection with outside-cone plug-in system, or for con-nection of solid-insulated barsWall-standing or free-standing arrangementCable connection access from front
Option: Cable connection access from rear (only circuit-breakerpanel 1250 A)Installation and extension of existing switchgear at both endswithout gas work and without modification of existing panels.
InterlocksAccording to IEC 62271-200 and VDE 0671-200Logical mechanical interlocks prevent maloperation
Three-position disconnector can only be operated with circuit-breaker in OPEN positionCircuit-breaker or contactor can only be operated with three-position switch in end position and operating lever removedSwitch-disconnector, contactor, ring-main and metering panelsare not interlocked due to their own switching capacityThree-position disconnector interlocked against the circuit-breaker in circuit-breaker panels and in bus sectionalizers withone panel widthFeeder locking deviceLocking device for three-position switchCable compartment cover (access to HV HRC fuses) alwaysinterlocked against the three-position switch-disconnector inpanels with HV HRC fuses (switch-disconnector panel, meter-ing panel and contactor panel with fuses)
O ption: Cable compartment cover interlocked against thethree-position switch (circuit-breaker panel, disconnectorpanel, contactor panel without fuses, ring-main panel)O ption: Electromagnetic interlocksO ption: Actuating openings can be padlockedO ption: Feeder earthed locking device.
Modular designPanel replacement possible without SF 6gas workLow-voltage compartment removable, plug-in bus wires.
Instrument transformersCurrent transformers not subjected to dielectric stressEasy replacement of current transformers designed as ring-core
transformersMetal-coated, plug-in and disconnectable voltage transform-ers.
Vacuum circuit-breakerMaintenance-free under normal ambient conditions accordingto IEC 62271-1 and VDE 0671-1No relubrication or readjustmentUp to 10,000 operating cyclesVacuum-tight for life.
Secondary systemsCustomary protection, measuring and control equipmentO ption: Numerical multifunction protection relay with inte-grated protection, control, communication, operating andmonitoring functions
Can be integrated in process control systems.
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
8/56
8 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Electrical data, filling pressure, temperature for single-busbar switchgear
Technical data
Commonelectricaldata, fillingpressure andtemperature
Rated insulation level Rated voltage Ur kV 7.2 12 15 17.5 24Rated short-duration power-frequency withstand voltage Ud: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV
20 1)23 1)
28 2)322)
3639
3845
5060
Rated lightning impulse withstand voltage Up: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV
60 1)70 1)
75 2)85 2)
95110
95110
125145
Rated frequency fr Hz 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60Rated normal current Ir3)for the busbar up to A 2500 2500 2500 2500 2500Rated filling level pre4) 150 kPa (absolute) at 20 CMinimum functional level pme4) 130 kPa (absolute) at 20 CAmbient air temperature 5 C to +55 C
Data of the switchgear panels
Circuit-breaker panel630 A
Rated normal current Ir3) A 630 630 630 630 630Rated short-time withstandcurrent Ik
for switchgear with tk= 1 s up to kA 20 |25 20 |25 20 |25 20 |25 20 |25for switchgear with tk= 3 s up to kA 20 | 20 | 20 | 20 | 20 |
Rated peak withstand current Ip up to kA 50 |63 50 |63 50 |63 50 |63 50 |63Rated short-circuit making current Ima up to kA 50 |63 50 |63 50 |63 50 |63 50 |63Rated short-circuit breaking current Isc up to kA 20 |25 20 |25 20 |25 20 |25 20 |25Electrical endurance ofvacuum circuit-breakers
at rated normal current 10 000 operating cyclesat rated short-circuit breaking current 50 breaking operations
Circuit-break-er panel andbus sectional-izer,1000 A 5)1250 A 6)2000 A2500 A
Rated normal current Ir3) A A A A
1000125020002500
1000125020002500
1000125020002500
100012502000
100012502000
Rated short-time withstandcurrent Ik
for switchgear with tk= 1 s up to kA 31.5 31.5 31.5 25 25for switchgear with tk= 3 s up to kA 31.5 31.5 31.5 25 25
Rated peak withstand current Ip up to kA 80 80 80 63 63Rated short-circuit making current Ima up to kA 80 80 80 63 63Rated short-circuit breaking current Isc up to kA 31.5 31.5 31.5 25 25
Electrical endurance ofvacuum circuit-breakers
at rated normal current 10 000 operating cyclesat rated short-circuit breaking current 50 breaking operations
Disconnectingpanel1000 A 5)1250 A2000 A2500 A
Rated normal current Ir3) A A A A
1000125020002500
1000125020002500
1000125020002500
100012502000
100012502000
Rated short-time withstandcurrent Ik
for switchgear with tk= 1 s up to kA 31.5 31.5 31.5 25 25
for switchgear with tk= 3 s up to kA 31.5 31.5 31.5 25 25Rated peak withstand current Ip up to kA 80 80 80 63 63
Switch-disconnectorpanel(with HV HRCfuses)
Rated normal current Ir3) for feeder 7) A 200 200 200 200 200Rated short-time withstandcurrent Ik
for switchgear with tk= 1 s up to kA 31.5 31.5 31.5 25 25for switchgear with tk= 3 s up to kA 31.5 31.5 31.5 25 25
Rated peak withstand current Ip7) up to kA 80 80 80 63 63Rated short-circuit making current Ima7) up to kA 80 80 80 63 63Dimension e of HV HRC fuse-links mm 292 8) 292 8) 442 442 442
Ring-mainpanel(switch-disconnectorpanel withoutfuses)
Rated normal current Ir3) for feeder A 630 630 630 630 630Rated short-time withstandcurrent Ik
for switchgear with tk= 1 s up to kA 20 |25 20 |25 20 |25 20 |25 20for switchgear with tk= 3 s up to kA 20 | 20 | 20 | 20 | 20
Rated peak withstand current Ip up to kA 50 |63 50 |63 50 |63 50 |63 50Rated short-circuit making current Ima up to kA 50 |63 50 |63 50 |63 50 |63 50
Vacuumcontactorpanel(with HV HRCfuses)
Rated normal current Ir3) for feeder 7) A 450 450 450 450 450Rated short-time withstandcurrent Ik
for switchgear with tk= 1 s up to kA 31.59) 31.5 9) 31.5 9) 25 9) 25 9)
for switchgear with tk= 3 s up to kA 31.5 9) 31.5 9) 31.5 9) 25 9) 25 9)
Rated peak withstand current Ip7) up to kA 80 80 80 63 63
Rated short-circuit making current Ima7) up to kA 80 80 80 63 63
Electrical endurance at rated normal current 100 000 or 500 000 operating cycles
Dimension e of HV HRC fuse-links mm 292 8) 442 442 442 442
Meteringpanel(with HV HRCfuses)
Rated short-time withstandcurrent Ik
for switchgear with tk= 1 s up to kA 31.5 31.5 31.5 25 25
for switchgear with tk= 3 s up to kA 31.5 31.5 31.5 25 25
Rated peak withstand current Ip7) up to kA 80 80 80 63 63
Dimension e of HV HRC fuse-links mm 292 8) 292 8) 442 442 442
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
9/56
9Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Electrical data, filling pressure, temperature for double-busbar switchgear
Technical data
Commonelectricaldata, fillingpressure andtemperature
Rated insulation level Rated voltage Ur kV 7.2 12 15 17.5 24Rated short-duration power-frequency withstand voltage Ud: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV
20 1)23 1)
28 2)322)
3639
3845
5060
Rated lightning impulse withstand voltage Up: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV
60 1)70 1)
75 2)85 2)
95110
95110
125145
Rated frequency fr Hz 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60Rated normal current Ir3)for the busbar up to A 2500 2500 2500 2500 2500Rated filling level pre4) 150 kPa (absolute) at 20 CMinimum functional level pme4) 130 kPa (absolute) at 20 CAmbient air temperature 5 C to +55 C
Data of the switchgear panels
Circuit-break-er panel, buscoupler 10)
1000 A
Rated normal current Ir3) A 1000 1000 1000 1000 1000Rated short-time withstandcurrent Ik
for switchgear with tk= 1 s up to kA 25 25 25 25 25for switchgear with tk= 3 s up to kA 25 25 25 25 25
Rated peak withstand current Ip up to kA 63 63 63 63 63Rated short-circuit making current Ima up to kA 63 63 63 63 63Rated short-circuit breaking current Isc up to kA 25 25 25 25 25
Electrical endurance ofvacuum circuit-breakers
at rated normal current 10 000 operating cyclesat rated short-circuit breaking current 50 breaking operations
Incomingsectionalizer1250 A
Rated normal current Ir3) A 1250 1250 1250 1250 1250Rated short-time withstandcurrent Ik
for switchgear with tk= 1 s up to kA 25 25 25 25 25for switchgear with tk= 3 s up to kA 25 25 25 25 25
Rated peak withstand current Ip up to kA 63 63 63 63 63Rated short-circuit making current Ima up to kA 63 63 63 63 63Rated short-circuit breaking current Isc up to kA 25 25 25 25 25
Electrical endurance ofvacuum circuit-breakers
at rated normal current 10 000 operating cyclesat rated short-circuit breaking current 50 breaking operations
Further paneltypes
The above-mentioned panel types can on request be combined with panel types ofthe single-busbar range.
Footnotes for pages 8 and 9
1) Higher values of the rated short-duration power-frequencywithstand voltage available with: 32 kV for phase-to-phase, phase-to-earth and open
contact gap, as well as 37 kV across the isolating distanceHigher values of the rated lightning impulse withstand voltage:
60 kV for phase-to-phase, phase-to-earth and opencontact gap, as well as 70 kV across the isolating distance
2) Higher values of the rated short-duration power-frequencywithstand voltage available with: 42 kV for phase-to-phase, phase-to-earth and open
contact gap, as well as 48 kV across the isolating distanceHigher values of the rated lightning impulse withstand voltage: 95 kV for phase-to-phase, phase-to-earth and open
contact gap, as well as 110 kV across the isolating distance
3) The rated normal currents apply to ambient air temperaturesof max. 40 C.The 24-hour mean value is max. 35 C
(according to IEC 62271-1 / VDE 0671-1)2500 A with natural ventilation
4) Pressure values for SF6-insulated switchgear vessels
5) Bus sectionalizer panel 1000 A and disconnector panel 1000 Aonly possible with rated short-time withstand current Ik25 kA(tk1 s and 3 s), rated peak withstand current Ip63 kA and ratedshort-circuit breaking current ISC25 kA
6) Bus sectionalizer panel 1250 A in 2 panel widths only possiblewith rated short-time withstand current Ik25 kA (tk1 s and 3 s),rated peak withstand current Ip63 kA and rated short-circuitbreaking current ISC25 kA
7) Depending on the HV HRC fuse-link, observe max. permissiblelet-through current IDof the HV HRC fuse-links
8) Extension tube (150 mm long) required additionally
9) Applies to combination of vacuum contactor with HV HRC fuses:Vacuum contactor without HV HRC fuse reaches rated short-timewithstand current Ik8 kA (tk1 s and 3 s) and rated peak withstand
current Ip20 kA (applies to the complete switchgear)10) Bus coupler 1250 A on request
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
10/56
10 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Room planning
Technical data
Room planning for single-busbar switchgear
Room planning for double-busbar switchgear
Switchgear installationFor single-busbar applications:
Wall-standing arrangement or Free-standing arrangement Face-to-face arrangement
accordinglyFor double-busbar applications:
Back-to-back arrangement (free-standing arrangement).
Room dimensionsSee opposite dimension drawings.
Door dimensionsThe door dimensions depend onthe dimensions of the individualpanels (see pages 12 to 20).
Switchgear fixingFor floor openings and fixingpoints of the switchgear, seepages 12 to 20Foundations:
Steel girder construction Steel-reinforced concrete with
foundation rails, welded orbolted on.
Panel dimensionsSee pages 12 to 20.
WeightsSingle-busbar panels
Panels for 1250 A:Approx. 800 kgPanels for > 1250 A:Approx. 1400 kg.
Double-busbar panels
Panels for
1250 A:Approx. 1600 kg.
Room height2800 mm
Room height2800 mm
Room height2800 mm
Wall-standing arrangement(top view)Panels without pressure relief duct
Free-standing arrangement (top view)Panels with pressure relief duct
Free-standing arrangement(top view)
Wall-standing arrangement(same as left side) but panelswith pressure relief duct
* Rear pressure relief duct:
Depth 125 mm ** Depending on national require-
ments; for extension/panelreplacement: Control aisle1400 mm is recommended
*** Lateral wall distances on theleft or on the right: 500 mmis recommended
**** 125 mm, if there are exclusively600 mm panels
** For panel replacement: Controlaisle 1400 mm necessary
*** Lateral wall distance 50 mmoptionally possible on the leftor on the right
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
11/56
11Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Shipping data, classification
Technical data
1) Average values depending onthe degree to which panels areequipped
2) The loss of service continuity cate-gory is always referred to the com-plete switchgear, i.e. the panel withthe lowest category determines the
loss of service continuity categoryof the complete switchgear
TransportNXPLUS C switchgear is deliveredin form of individual panels.Please observe the following:
Transport facilities on siteTransport dimensions andtransport weights
Size of door openings in building.In case of double-busbar panelsthe A and B sides are suppliedseparately.
PackingPlace of destination insideGermany or other Europeancountries
Means of transport: Rail andtruckType of packing:
Panels on pallets Open packing with PE
protective foil.
Place of destination overseasMeans of transport: ShipType of packing:
Panels on pallets In closed crates with sealed
upper and lower PE protectivefoil
With desiccant bags With sealed wooden base Max. storage time: 6 months.
Transport dimensions, transport weights 1)
Panel widths Transport dimensionsWidth x Height x Depth
Transport weightwith packing without packing
mm mm x mm x mm approx. kg approx. kg
Single-busbar switchgear transport inside Germany or to European countries
1 x 600 1100 x 2470 x 1450 900 8001 x 900 1450 x 2470 x 1450 1500 1400
1 x 600 (top-rear cable connection) 1100 x 2470 x 2100 900 800
Transport to overseas
1 x 600 1130 x 2650 x 1450 900 800
1 x 900 1480 x 2650 x 1450 1500 1400
1 x 600 (top-rear cable connection) 1130 x 2650 x 2100 900 800
Double-busbar switchgear transport inside Germany or to European countries
1 x 600 1100 x 2470 x 1450 900 800
Transport to overseas
1 x 600 1130 x 2650 x 1450 900 800
Classification of NXPLUS C switchgear according to IEC 62271-200
Design and construction
Partition class PM (metallic partition)
Loss of service continuity category 2)Panels with HV HRC fusesPanels without HV HRC fuses
LSC 2ALSC 2B
Accessibility to compartments(enclosure)Busbar compartmentSwitching device compartment
Low-voltage compartmentCable compartment without HV HRC fuses with HV HRC fuses
Tool-basedNon-accessible
Tool-based
Tool-basedInterlock-controlled and tool-based
Internal arc classification
Designation of the internal arcclassification IACIAC class for:Wall-standing arrangementFree-standing arrangement
7.2 kV, 12 kV, 15 kV 17.5 kV, 24 kV
IAC A FL 31.5 kA, 1 sIAC A FLR 31.5 kA, 1 s
IAC A FL 25 kA, 1 sIAC A FLR 25 kA, 1 s
Type of accessibility A
F L R
Switchgear in closed electrical service location,access for authorized personnel only according to IEC 62271-200FrontLateralRear (for free-standing arrangement)
Arc test current 25 kA, 31.5 kA
Test duration 1 s
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
12/56
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
13/56
13Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Front views, sections, floor openings, fixing points for single-busbar switchgear
Dimensions
Circuit-breaker panels(cable connection from top rear)
1250 A
For legend and footnotes, see page 12
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
14/56
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
15/56
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
16/56
16 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
1250 A
Bus sectionalizers with disconnector (2 panel widths)
Legend and footnotes
for pages 16 and 171Floor opening for
control cables
2 Option: Pressure relief duct
3 Fixing hole for M8 / M10
4 Fixing hole for M8 / M10(only for aseismic design)
5 Floor opening for high-voltage cables
7 Option:HV HRC fuses
1) 2650 mm for higher low-
voltage compartment
Front views, sections, floor openings, fixing points for single-busbar switchgear
Dimensions
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
17/56
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
18/56
18 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Legend and footnotes
for pages 18 and 19
1Floor opening forcontrol cables
2 Pressure relief duct
3 Fixing hole for M8 / M10
4 Fixing hole for M8 / M10(only for aseismic design)
5 Floor opening for high-voltage cables
1) 2650 mm for higher low-voltage compartment
2) 752 mm for deeper cablecompartment cover
3) 45 mm for deeper cablecompartment cover
4) 1120 mm for deeper cablecompartment cover
6) 2390 mm for deeper cable
compartment cover
Circuit-breaker panels
1000 A
Side A Side B Side B Side A
Front views, sections, floor openings, fixing points for double-busbar switchgear
Dimensions
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
19/56
19Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Incoming sectionalizer
Side A Side B Side B Side A
1250 A
For legend and footnotes, see page 18
Front views, sections, floor openings, fixing points for double-busbar switchgear
Dimensions
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
20/56
20 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Bus coupler
1000 A
Side A Side B Side B Side A
1Floor opening forcontrol cables
2 Pressure relief duct
3 Fixing hole for M8 / M10
4 Fixing hole for M8 / M10(only for aseismic design)
1) 2650 mm for higher low-
voltage compartment
Front views, sections, floor openings, fixing points for double-busbar switchgear
Dimensions
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
21/56
HA35-2541b
eps
21Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Single-busbar panels
Product range
Circuit-breaker panels
630 A 1000 A and 1250 A
1) Only for 1250 A
1250 A, top-rear cable connection2000 A and 2500 A
Three-positiondisconnector
Vacuumcircuit-breaker
Plug-in voltagetransformer
Disconnectable
and plug-in voltage
transformer
Capacitive voltagedetecting system
Busbar earthingswitch
Surge arresteror limiter
Cable connectionwith outside-coneplug (not included inthe scope of supply)
Cable connectionwith outside-coneplug (not included inthe scope of supply)
Current transformerand/or
and/or and/or
and/or
and/or
and/or
and/or
and/or
and/or and/or
and/or and/oror
oror or or
oror
or
oror
or
or
or
or
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
22/56
HA35-2541b
eps
Inverted phases
22 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Single-busbar panels
Product range
1) Only for 1250 A
1000 A and 1250 A
2000 A and 2500 A
Disconnector panels
1250 A, 1 panel width
2000 A and 2500 A, 1 panel width
1250 A, 2 panel widths
Bus sectionalizers
Three-positiondisconnector
Vacuumcircuit-breaker
Plug-in voltagetransformer
Disconnectable
and plug-in voltage
transformer
Capacitive voltagedetecting system
Busbar earthingswitch
Surge arresteror limiter
Cable connection
with outside-coneplug (not included inthe scope of supply)
Cable connectionwith outside-coneplug (not included in
the scope of supply)
Current transformer
and/or
and/or
and/or
and/or
and/or
and/or
and/or
and/or
or
or
or
or
or
or
or
or
or
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
23/56
HA35-2541b
eps
23Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Switch-disconnector panel
Vacuum contactor panel
Ring-main panel
Metering panel
1) Only possible when vacuum contactor
panel is designed without fuse
Three-positionswitch-disconnector
Vacuum contactor
HV HRC fuses
Plug-in voltagetransformer
Disconnectable
and plug-in voltage
transformer
Current transformer
Capacitive voltagedetecting system
2ndearthing switchfor fuses
Surge arresteror limiter
Cable connectionwith outside-coneplug (not included inthe scope of supply)
and/or and/or
and/or and/or
and/oror oror
or
and/orand/or
and/orand/or
and/ororor oror
oror
Single-busbar panels
Product range
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
24/56
HA35-2541b
eps
24 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Double-busbar panels
Product range
1250 A1000 A
1000 A
Circuit-breaker panels Incoming sectionalizer
Bus coupler
Abbreviations:
SS1 = Busbar 1SS2 = Busbar 2
Three-positiondisconnector
Vacuumcircuit-breaker
Plug-in voltagetransformer
Disconnectable
and plug-in voltage
transformer
Plug-in voltage trans-former, mountedseparately, connect-ed through a shortcable
Capacitive voltagedetecting system
Panel bars
Current transformer
Surge arresteror limiter
Cable connectionwith outside-coneplug (not included inthe scope of supply)
and/or
and/orand/or
and/or
and/orand/or
and/or
and/orand/or
and/or
and/or
and/orand/or
or
oror
or
ororor or
or or
or or
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
25/56
25Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Basic panel design
Design
Insulating systemSwitchgear vessel filled with SF 6gasFeatures of SF 6gas:
Non-toxic Odorless and colorless Non-inflammable Chemically neutral
Heavier than air Electronegative (high-qualityinsulator)Pressure of SF 6gas in the switchgearvessel (absolute values at 20 C):
Rated filling level: 150 kPa Design pressure: 180 kPa Design temperature of the SF6gas: 80 C Operating pressure of bursting disc:300 kPa
Bursting pressure: 550 kPa Gas leakage rate: < 0.1 % per year.
Panel designFactory-assembled, type-tested
Metal-enclosed, metal-cladHermetically tight, welded switchgearvessel made of stainless steel1-pole, solid-insulated, screenedbusbars, plug-in typeMaintenance-freeDegree of protection
IP 65 for all high-voltage parts ofthe primary circuit
IP 3XD for the switchgear enclosureVacuum circuit-breaker or vacuumcontactorThree-position disconnector fordisconnecting and earthing by meansof the circuit-breaker
Make-proof earthing by means of the vacuum circuit-breakerThree-position switch-disconnectorCable connection with outside-coneplug-in system according toDIN EN 50 181Wall-standing or free-standing ar-rangementInstallation and possible later exten-sion of existing panels without gasworkReplacement of switchgear vesselwithout gas workReplacement of instrument transform-ers without gas work, as they arelocated outside the gas compartments
Enclosure made of sendzimir-galva- nized sheet steel, front cover, rearcover and end walls painted in colorlight basic (SN 700)Low-voltage compartment removable,plug-in bus wiresLateral, metallic wiring ducts forcontrol cables.
Circuit-breaker panel (example)
Front view
Detail Z:
Side view (cable connection from the front)
1 Low-voltage compart-ment
2 Multifunction protec-tion relay SIPROTEC 4
(example)
3 Position indicator forcircuit-breaker
4 Actuating opening for
charging the circuit-breaker springs
5 ON pushbutton forcircuit-breaker
6 Spring charged indica-tor
7 Operations counter forcircuit-breaker
8 Position indicator fordisconnecting function
of three-position switch
9 Ready-for-service indica-tor
10 Position indicator forready-to-earth function
of three-position switch
11 Control gate and lockingdevice for disconnect-
ing/earthing functions ofthree-position switch
12 Interrogation lever13 Actuating opening for
disconnecting function
of three-position switch
14 Actuating opening forready-to-earth function
of three-position switch
15 Option:Busbar voltagetransformer, plug-in type
16 Busbar, 1-pole, fullyinsulated, plug-in type,
earthed on the outside
17 Option:Busbar current
transformer18 Switchgear vessel, her-
metically welded, filled
with SF6gas19 Three-position discon-
nector
20 OFF pushbutton forcircuit-breaker
21 Vacuum interrupter ofcircuit-breaker
22 Pressure relief (burstingdisc)
23 Capacitive voltagedetecting system
24 Feeder locking device
(suitable for padlocking)
25 Disconnecting facilityfor feeder voltage trans-
former26 Bushing for feeder volt-
age transformer
27 Option:Feeder voltagetransformer
28 Option:Pressure reliefduct
29 Cable compartment30 Operating mechanism for
three-position switch
31 Operating mechanism forcircuit-breaker
32 Feeder current trans-former
33 Cable connection with
outside-cone T-plug34 Operation of disconnect-
ing facility of the feeder
voltage transformer
35 Earthing busbar withearthing connection
36 Air guides for cableconnection
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
26/56
1
2
3
4
5
6
7
11
10
9
8
R-HA35-050
eps
26 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Vacuum circuit-breaker
Components
Vacuum circuit-breakerFeatures
According to IEC 62271-100 and VDE 0671-100 (for standards,see page 53)Application in hermetically welded switchgear vessel inconformity with the systemClimate-independent vacuum interrupter poles in the SF6-filledswitchgear vessel
Maintenance-free for indoor installation according to IEC 62271-1 and VDE 0671-1Individual secondary equipmentA metal bellows is used for gasketless separation of the SF6insulation and the operating mechanism (already used withsuccess for over 2 million vacuum interrupters).
Trip-free mechanismThe vacuum circuit-breaker is fitted with a trip-free mechanismaccording to IEC 62271 and VDE 0671.
Switching duties and operating mechanismsThe switching duties of the vacuum circuit-breaker are depen-dent, among other factors, on its type of operating mechanism.Motor operating mechanism
Motor-operating stored-energy mechanism
For auto-reclosing (K) For synchronization and rapid load transfer (U)Further operating mechanism features
Located outside the switchgear vessel in the operating mecha-nism box and behind the control boardStored-energy spring mechanism for 10,000 operating cycles.
Operating mechanism functionsMotor operating mechanism 1)(M1 *)
In the case of motor operating mechanism, the closing springis charged by means of a motor and latched in the chargedposition (spring charged indication is visible). Closing iseffected either by means of an ON pushbutton or a closingsolenoid. The closing spring is recharged automatically (forauto-reclosing).
Endurance class of circuit-breaker
Function Class Standard Property of NXPLUS C
BREAKING M2 IEC 62271-100 10,000 times mechanicallywithout maintenance
E2 IEC 62271-100 10,000 times rated normalcurrent without maintenance50 times short-circuit breakingcurrent without maintenance
C2 IEC 62271-100 Very low probability ofrestrikes
Operating times
Closing time Closing solenoid < 75 ms
Opening time 1strelease2ndrelease
< 65 ms< 50 ms
Arcing time at 50 Hz < 15 ms
Break time 1strelease2ndrelease
< 80 ms< 65 ms
Dead time 300 ms
Total charging time < 15 s
1 Gear with motor (M1 *) 2 Position switch (S4 *) 3Closing spring 4 Closing spring charged indication 5 Closing solenoid (Y9 *)
6Operations counter 7 Auxiliary switch 6 NO + 6 NC (S1 *), option: 12 NO + 12 NC 8 CLOSED / OPEN position indicator for circuit-breaker 9Option: 2ndrelease (Y2 *)10 1strelease (Y1 *)11 Feeder locking device
12Fixed terminal13Pole support14Vacuum interrupter15 Moving terminal
16Metal bellows17 Switchgear vessel, SF6-insulated, with vacuum interrupter18 Operating mechanism box (see figure above)19Operating kinematics
Section through the vacuum circuit-breaker
Open on the side of the operating mechanism
Abbreviations for switching duties:U = Synchronization and rapid load transfer (closing time 90 ms)K = Auto-reclosing
1) Motor rating at 24 V to 220 V DC: 350 W
110 V and 220 V AC: 400 VA* Item designation
For further technical data and description of typical applications,please refer also to Catalog HG 11.05 3AH5 Vacuum Circuit-
Breakers.
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
27/56
27Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Vacuum circuit-breaker
Components
Secondary equipmentThe scope of the secondary equipment of the vacuum circuit-breaker depends on the type of application and offers a widerange of variations, thus allowing even the highest requirementsto be satisfied:
Closing solenoid
Type 3AY15 10 (Y9 *) For electrical closing.
Shunt releasesTypes:
Standard: 3AY15 10 (Y1 *) Option: 3AX11 01 (Y2 *), with energy store
Tripping by protection relay or electrical actuation.
C.t.-operated releaseType 3AX11 02 (Y4 *), 0.5 AType 3AX11 04 (Y6 *) for tripping pulse 0.1 Ws inconjunction with suitable protection systemsUsed if external auxiliary voltage is missing, tripping viaprotection relay.
Undervoltage releaseType 3AX11 03 (Y7 *)Comprising:
Energy store and unlatching mechanism Electromagnetic system, which is permanently connected to
voltage while the vacuum circuit-breaker is closed; tripping isinitiated when this voltage dropsConnection to voltage transformers possible.
Anti-pumping (mechanical and electrical)Function: If constant CLOSE and OPEN commands are presentat the vacuum circuit-breaker at the same time, the vacuumcircuit-breaker will return to the open position after closing. Itremains in this position until a new CLOSE command is given.In this manner, continuous closing and opening (= pumping)
is avoided.Circuit-breaker tripping signal
For electrical signaling (as pulse > 10 ms), e.g. to remotecontrol systems, in the case of automatic tripping (e.g.protection)Via limit switch (S6 *) and cut-out switch (S7 *).
Varistor moduleTo limit overvoltages to approx. 500 V for protection devices(when inductive components are mounted in the vacuumcircuit-breaker)For auxiliary voltages 60 V DC.
Auxiliary switchType 3SV9 (S1 *)
Standard: 6 NO + 6 NC, free contacts thereof 1)3 NO + 4 NCO ption: 12 NO + 12 NC, free contacts thereof 1)9 NO + 6 NC.
Position switchType 3SE4 (S4 *)For signaling closing spring charged.
Mechanical interlockMechanical interlocking to the three-position disconnectorDuring operation of the three-position switch, the vacuumcircuit-breaker cannot be operated.
Switching rate of the vacuum interrupter
Electrical data (curve 1)
Rated voltage 24 kVRated short-circuit breaking current 25 kARated normal current 2000 A
Electrical data (curve 2)
Rated voltage 15 kVRated short-circuit breaking current 31.5 kARated normal current 2500 A
Rated operating sequences
Rapid load transfer (U): O-t-CO-t-CO (t0.3 s, t 3 min)Auto-reclosing (K): O-t-CO-t-CO (t0.3 s, t 3 min)Multiple-shot reclosing: O-t-CO-t-CO-t-CO-t-CO (t0.3 s, t 15 s)
O = OPEN operationCO = CLOSE operation with subsequent OPEN operation
at the shortest internal close-open time of the vacuumcircuit-breaker
Possible release combinations
Release Release combination
1 2 3 4 5
1stshunt release type type 3AY15 10
2ndshunt release type type 3AY11 01
C.t.-operated release type 3AX11 02,0.5 A, or type 3AX11 04, 0.1 Ws
Undervoltage release type 3AX11 03
1 unit of each release, a maximum of 2 releases can be combined only.
1) For utilization by the customer
* Item designation
Abbreviations: NO = normally open contactNC = normally closed contact
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
28/56
R-HA35-040a
eps
R-HA35-047
eps
5
6
7
8 8
9
1
2
3
4
28 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Three-position switches
Components
Common featuresAccording to IEC 62271-102 and VDE 0671-102 (for standards,see page 53)Application in hermetically welded switchgear vessel inconformity with the systemClimate-independent contacts in the SF 6-filled switchgearvessel
Maintenance-free for indoor installation according to IEC 62271-1 and VDE 0671-1Individual secondary equipmentA metal bellows is used for gasketless separation of the SF 6insulation and the operating mechanism (already used withsuccess for over 2 million vacuum interrupters)A rotary bushing is used for separation of the SF 6insulationand the operating mechanism (already used with successmillions of times in medium-voltage and high-voltageswitchgear)Compact design due to short contact gaps in SF 6gasOperation via gas-tight welded-in metal bellows or rotarybushing at the front of the switchgear vesselReliable mechanical switch position up to the operatingfront of the panel (in double-busbar switchgear, the positionindication for side B is done on side A via electrical position
indicators).
Three-position disconnectorApplication in:
Circuit-breaker panel 1000 A to 2500 A(with interlock against the circuit-breaker)
Disconnector panel 1000 A to 2500 A Bus sectionalizer 1000 A to 2500 A
2000 mechanical operating cycles forCLOSED / OPEN / READY-TO-EARTH.
Three-position switch-disconnectorApplication in:
Circuit-breaker panel 630 A (as disconnector withinterlock against the circuit-breaker)
Switch-disconnector panel Ring-main panel Contactor panel Metering panel
2000 1)mechanical operating cycles forCLOSED / OPEN / EARTHEDSwitching functions as general-purpose switch-disconnector according to:
IEC 60265-1 VDE 0670-301 IEC 62271-102 VDE 0671-102 (for standards, see page 53)
Designed as a multi-chamber three-position switchwith the functions:
Switch-disconnector and
Make-proof earthing switch.
Switch positions of the three-position switches
Three-position disconnector
(in OPEN position)with vacuum circuit-breaker arranged below (view intothe switchgear vessel opened at the rear)
1 Fixed contact at the busbar2Swivel-mounted contact blade3 Fixed contact for feeder EARTHED4 Operating shaft
Three-position switch-disconnector
(exploded view)
5 Fixed contacts to earth6 Rotary contact blade7 Operating shaft8 Fixed contact to the feeder9 Fixed contact to the busbar
CLOSED
CLOSED
OPEN
OPEN
FeederEARTHED
FeederEARTHED
Switch positions
Switch positions
1) For switch-disconnector panel:
1000 mechanical operating cycles forCLOSED / OPEN / EARTHED
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
29/56
29Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
ComponentsThree-position switches
InterlocksSelection of permissible switching operations by means of acontrol gate with mechanically interlocked vacuum circuit-breakerCorresponding operating shafts are not released at the operat-ing front until they have been pre-selected with the controlgate
Operating lever cannot be removed until switching operation has been completedCircuit-breaker cannot be closed until control gate is in neutralposition againSwitchgear interlocking system also possible with electro-mechanical interlocks if switchgear is equipped with motoroperating mechanisms (mechanical interlocking for manualoperation remains).
Switch positionsCLOSED, OPEN, EARTHED or READY-TO-EARTHIn circuit-breaker panels, earthing and short-circuitingthe cable connection is completed by closing the vacuumcircuit-breaker.
Operating mechanism
Spring-operated mechanism, used in: Circuit-breaker panels 630 A to 1250 A Bus sectionalizers 1000 A, 1250 A Disconnector panels 1000 A, 1250 A Vacuum contactor panel Metering panel Ring-main panel
Slow motion mechanism, used in: Circuit-breaker panels 2000 A, 2500 A Bus sectionalizers 2000 A, 2500 A Disconnector panels 2000 A, 2500 A
Spring-operated / stored-energy mechanism, used in: Switch-disconnector panel
Spring-operated and spring-operated / stored-energy andslow motion mechanism actuated via
operating lever at the operating front of the panelSeparate operating shafts for the DISCONNECTING andEARTHING or READY-TO-EARTH functions Option: Motor operating mechanism for the DISCON-NECTING and EARTHING or READY-TO-EARTH functionsSpring-operated/stored-energy mechanism for theswitch-disconnector function with fuses: Opening springprecharged (after closing)Maintenance-free due to non-rusting design of partssubjected to mechanical stressBearings which require no lubrication.
Transmission principle for operating mechanisms(see illustration)
Transmission of operating power from outside into thegas-filled switchgear vessel by means of a metal bellows
Gas-tight Maintenance-free.
Endurance class of three-position disconnector
Function Class Standard Property of NXPLUS C
DISCONNECTING M1 IEC 62271-102 2000 times mechanical lywithout maintenance
READY-TO-EARTH 1000 times mechanicallywithout maintenance
EARTHING E2 1) IEC 62271-102 50 times rated short-circuit making current Imawithout maintenance
Endurance class of three-position switch-disconnector
Function Class Standard Property of NXPLUS C
DISCONNECTING M1 2) IEC 62271-102 2000 times mechanicallywithout maintenance
LOAD BREAKING M1
E3
IEC 60265-1
IEC 60265-1
1000 times mechanicallywithout maintenance100 times rated mainly ac-tive load breaking currentI1without maintenance5 times rated short-circuitmaking current Imawith-out maintenance
EARTHING E2 IEC 62271-102 5 times rated short-circuitmaking current Imawith-out maintenance
1) By closing the circuit-breaker
2) For switch-disconnector panel: M0 1000 times mechanicallywithout maintenance
Transmission principle for operating mechanisms
1 Gas-filled switch-gear vessel
2 Gas-tight welded-inmetal bellows orrotary bushing
Three-position switch-disconnector
Three-position disconnector
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
30/56
30 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
HV HRC fuse assembly
Components
FeaturesApplication in:
Switch-disconnector panel Contactor panel Metering panel
HV HRC fuse-links according to DIN 43 625 (main dimensions)with striker in medium version according to IEC 60282 /
VDE 0670-4 As short-circuit protection before transformers inthe switch-disconnector panel
As short-circuit protection before motors in the contactorpanel
As short-circuit protection before voltage transformersin the metering panel
With selectivity (depending on correct selection) toupstream and downstream connected equipment
1-pole insulatedRequirements according to IEC 62271-105 and VDE 067-105fulfilled by combination of HV HRC fuses with the three-position switch-disconnectorClimate-independent and maintenance-free, with fuse boxesmade of cast resinFuse assembly connected to the three-position switch-
disconnector via welded-in bushings and connecting barsArrangement of fuse assembly below the switchgear vesselFuses can only be replaced if feeder is earthed
Option: Fuse tripped indication for remote electrical indica-tion with 1 normally open contact.
Mode of operationIn the event that an HV HRC fuse-link has tripped, the switch istripped via an articulation which is integrated into the cover ofthe fuse box (see figure).In the event that the fuse tripping fails, e.g. if the fuse hasbeen inserted incorrectly, the fuse box is protected by thermalprotection. The overpressure generated by overheating trips theswitch via the diaphragm in the cover of the fuse box and via anarticulation. This breaks the current before the fuse box incurs
irreparable damage.This thermal protection works independently of the type anddesign of the HV HRC fuse used. Like the fuse itself, it is mainte-nance-free and independent of any outside climatic effects.Furthermore, the SIBA HV HRC fuses release the striker depend-ing on the temperature and trip the three-position switch-dis-connector as early as in the fuse overload range. Impermissibleheating of the fuse box can be avoided in this way.
Replacement of HV HRC fuse-linksThe transformer feeder has to be isolated and earthed.Subsequent manual replacement of the HV HRC fuse-linkafter removing the cable compartment cover.
HV HRC fuse assembly
Basic design
1 Bushing2 Switchgear vessel3 Sealing cover with seal
4 Tripping pin for spring-operated / stored-energymechanism
5 Fuse box6HV HRC fuse-link7 Striker of the HV HRC fuse-link and articulation
for tripping the spring-operated / stored-energymechanism
Schematic sketches for
fuse tripping
Fuse-link in servicecondition
Fuse trippingthrough striker
Fuse tripping throughoverpressure, e.g.if HV HRC fuse-link hasbeen inserted incorrectly
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
31/56
31Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Allocation of three-position switch-disconnector with HV HRC fuses, transformer ratings
Components
Operatingvoltage U
kV
Transformer Rated normal current of the HV HRC fuse
Ratedpower SNkVA
Relative impedancevoltage uk%
Ratedcurrent I1A
Lowestvalue
A
Highest value
A
3.3 to 3.6 203050
444
3.55.258.75
6.31016
101620
75100125
444
13.117.521.9
2031.531.5
254040
160200250
444
283543.7
405063
506380
315400
44
55.170
80100
100100
4.16 to 4.8 203050
444
2.784.166.93
6.31016
6.31016
75100125
444
10.413.917.35
162025
202531.5
160200
250
44
4
22.227.75
34.7
31.540
50
4050
63315400500
444
43.755.570
6380100
80100100
5 to 5.5 203050
444
2.33.45.7
6.36.310
6.31016
75100125
444
8.611.514.4
161620
202025
160200250
444
18.42328.8
31.54040
405050
315400500
630
444
4
36.346.157.7
72.74
506380
100
6380100
1006 to 7.2 203050
444
1.92.84.8
6.36.310
6.36.316
75100125
444
7.29.612
161620
162025
160200250
444
15.419.224
31.531.540
31.54050
315400500630
4444
30.338.44861
506380100
6380100125
8 203050
444
1.52.273.7
6.3510
6.36.310
75100125
444
5.77.69.5
161620
161620
160200250
444
12.115.219
31.531.540
31.531.540
315400500630
4444
23.930.337.947.8
506380100
506380100
The opposite table shows therecommended HV HRC fuse-linksmake SIBA (electrical data validfor ambient air temperatures ofup to 40 C) for fuse protectionof transformers.
RecommendationThe three-position switch-disconnector in the transformerfeeder (transformer switch) wascombined with HV HRC fuse-linksand tested in accordance withIEC 62271-105. Higher trans-former ratings on request.
StandardsHV HRC fuse-links with striker inmedium version according to
IEC 60282VDE 0670-4 and 402DIN 43 625 main dimensions.
Note
The exact selection of the SIBAfuse to be used is given in
the operating and installationinstructions of NXPLUS C
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
32/56
32 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Allocation of three-position switch-disconnector with HV HRC fuses, transformer ratings
Components
Operatingvoltage U
kV
Transformer Rated normal current of the HV HRC fuse
Ratedpower SNkVA
Relative impedancevoltage uk%
Ratedcurrent I1A
Lowestvalue
A
Highest value
A
10 to 12 203050
444
1.151.72.9
46.310
46.310
75100125
444
4.35.87.2
101616
101616
160200250
444
9.311.514.5
202525
202531.5
315400500
444
18.323.129
31.54050
405060
6308001000
45 to 65 to 6
36.446.258
6363100
8080100
12.5 to 13.4 203050
444
0.921.382.3
3.1546.3
3.1546.3
75
100125
4
44
3.46
4.65.7
10
1616
10
1616
160200250
444
7.49.211.5
162025
162031.5
315400500
444
14.518.423
254040
31.54050
630800
45 to 6
2936.9
6380
6380
13.8 203050
444
0.81.252.1
3.1546.3
3.1546.3
75100125
444
3.24.25.3
6.31010
101616
160200250
444
6.78.410.5
161620
162025
315400500
444
13.216.821
2531.540
31.531.540
63080010001250
45 to 65 to 65 to 6
26.433.541.952.3
506380100
506380100
The opposite table shows therecommended HV HRC fuse-linksmake SIBA (electrical data validfor ambient air temperatures ofup to 40 C) for fuse protectionof transformers.
RecommendationThe three-position switch-disconnector in the transformerfeeder (transformer switch) wascombined with HV HRC fuse-linksand tested in accordance withIEC 62271-105. Higher trans-former ratings on request.
StandardsHV HRC fuse-links with striker inmedium version according to
IEC 60282VDE 0670-4 and 402DIN 43 625 main dimensions.
Note
The exact selection of the SIBAfuse to be used is given in
the operating and installationinstructions of NXPLUS C
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
33/56
33Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Allocation of three-position switch-disconnector with HV HRC fuses, transformer ratings
Components
Operatingvoltage U
kV
Transformer Rated normal current of the HV HRC fuse
Ratedpower SNkVA
Relative impedancevoltage uk%
Ratedcurrent I1A
Lowestvalue
A
Highest value
A
15 to 17.5 203050
444
0.771.151.9
3.153.156.3
3.153.156.3
75125160
444
2.94.86.2
6.31616
101616
200250315
444
7.79.712.2
202531.5
202531.5
400500630
444
15.519.324.3
31.531.540
31.54063
80010001250
5 to 65 to 65 to 6
30.938.548.2
6380100
6380100
20 to 23 203050
444
0.570.861.5
3.153.156.3
3.153.156.3
75
100125
4
44
2.2
2.93.6
6.3
6.310
6.3
6.310
160200250
444
4.75.87.3
101616
101616
315400500
444
9.211.614.5
162025
202531.5
6308001000
45 to 65 to 6
18.223.129
31.531.550
4031.550
125016002000
5 to 65 to 65 to 6
3646.557.8
5080100
63100100
The opposite table shows therecommended HV HRC fuse-linksmake SIBA (electrical data validfor ambient air temperatures ofup to 40 C) for fuse protectionof transformers.
RecommendationThe three-position switch-disconnector in the transformerfeeder (transformer switch) wascombined with HV HRC fuse-linksand tested in accordance withIEC 62271-105. Higher trans-former ratings on request.
StandardsHV HRC fuse-links with striker inmedium version according to
IEC 60282VDE 0670-4 and 402DIN 43 625 main dimensions.
Note
The exact selection of the SIBAfuse to be used is given in
the operating and installationinstructions of NXPLUS C
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
34/56
R-HA35-110
eps
5
4
32
1
34 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Vacuum contactor, motor protection
Components
FeaturesAccording to IEC 60470 andVDE 0670-501 (for standards,see page 53)Application in hermeticallywelded switchgear vessel inconformity with the system
Climate-independent vacuum interrupter poles in the SF6-filled switchgear vesselMaintenance-free for indoorinstallation according toIEC 62271-1 and VDE 0671-1Individual secondary equipmentA metal bellows is used forgasketless separation of theSF6insulation and the operat-ing mechanism (already usedwith success for over 2 millionvacuum interrupters)Magnet coil for operationlocated outside the switchgearvessel
100,000 or 500,000 operatingcycles at rated normal current.
Short-circuit and overloadprotection in connectionwith motorsIn circuits subjected to short-circuit currents, HV HRC fuse-linksprotect switching devices withoutshort-circuit breaking capacity(e.g. vacuum contactors).The instant when the motorstarts represents the maximumstress for the HV HRC fuse-links(starting currents, starting time
and starting frequency).Motor starting must neither oper-ate nor pre-damage the fuses.
Vacuum contactor (open on the side of the operating mechanism)
Section through the vacuum contactor
1 Metal bellows 2 Pole support 3 Vacuum interrupter 4 Operating mechanism box
with magnet coil 5 Base plate (welded into
the switchgear vessel) 6Fixed terminal 7 Pole support 8Vacuum interrupter 9 Moving terminal10 Switchgear vessel, SF6-insulat-
ed, with vacuum interrupter11 Metal bellows
12 Operating mechanism box(see illustration above)
13 Operating kinematics
Motor protection table(see also note on pages 31 to 33)
Numberof startsper hour
Maximum permissible motor starting current in Aat rated normal current of HV HRC fuse
40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 224 A 250 A
3.3 to 7.2 kV>7.2 to 12 kV>12 to 23 kV
YesYesYes
YesYesYes
YesYesYes
YesYesYes
YesYesYes
YesYesNo
YesYesNo
YesYesNo
YesNoNo
YesNoNo
HV motors withstarting timesup to 5 s
2 95 115 135 160 210 415 560 765 860 960 4 85 105 120 145 190 370 500 705 840 960
8 75 95 110 130 170 340 455 640 760 960
16 70 85 95 115 150 300 405 575 680 925
32 63 75 85 105 140 270 370 520 615 840
HV motors withstarting timesup to 15 s
2 90 105 120 145 190 335 445 625 730 960
4 80 95 110 130 170 300 400 560 655 890
8 70 85 100 120 155 270 360 510 595 805
16 65 75 90 105 140 240 325 455 535 720
32 60 70 80 95 125 220 290 410 485 655
HV motors withstarting timesup to 30 s
2 85 100 115 140 185 300 390 555 645 865
4 75 90 105 125 165 265 350 500 575 780
8 70 80 95 115 150 245 320 450 525 705
16 60 75 85 100 135 210 285 405 470 63032 55 65 75 90 120 190 260 365 425 570
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
35/56
R-HA35-051
eps
35Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Busbars
Components
Features1-pole, plug-in and bolteddesignConsisting of round-bar copper,insulated by means of siliconerubberBusbar joints with cross and
end adapters, insulated bymeans of silicone rubberField control by means of elec-trically conductive layers onthe silicone-rubber insulation(both inside and outside)Touchable as the externallayers are earthed with theswitchgear vesselInsensitive to pollution andcondensationSafe-to-touch due to metalcoverSwitchgear extension orpanel replacement is possiblewithout SF6gas work.
Possible componentsCurrent transformersVoltage transformersSurge arrestersCables with
straight plug or T-plug
Fully-insulated bars(e.g. make Duresca).
Legend
1 Cap 2 Busbar insulation made
of silicone rubber 3 Clamps 4 Busbar (round-bar copper) 5 End adapter or coupling end
adapter 6 Connection bolt 7 Switchgear vessel 8 Metal cover of busbars 9 Cross adapter or coupling
cross adapter
10 Bushing11 Earthing connection
Busbars (example)
Busbars 1250 A, plug-in type, fully insulated
(as front view of three panels, without low-voltage compartments)
Section of 1250 A busbar (basic design)Panel width 600 mm
Section of 1600 A, 2000 A or 2500 A busbar (basic design)
Panel width 600 mm
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
36/56
36 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Current transformers
Components
FeaturesAccording to IEC 60044-1 andVDE 0414-1Designed as ring-core currenttransformers, 1-poleFree of dielectrically stressedcast-resin parts (due to design)
Insulation class E Inductive typeCertifiableClimate-independentSecondary connection bymeans of a terminal strip in thelow-voltage compartment ofthe panel.
InstallationArranged outside the primaryenclosure (switchgear vessel).
Mounting locationsAt the busbar (1)At the panel connection (2)
Around the cable (3).
Current transformer typesBusbar current transformer (1):
Inside of transformer56 mm /1250 A and56 x 300 mm / > 1250 A
Max. usable height 140 mmFeeder current transformer (2):
Inside of transformer106 mm /1250 A and106 x 240 mm / > 1250 A
Max. usable height 205 mmCable-type current transformer(3) for shielded cables:
Inside
of transformer 55 mm Max. usable height 170 mmZero-sequence current trans-former (4) underneath thepanels (included in the scope ofsupply); on-site installation.
Busbar current transformers
Example 1250 A
Front views:
Side views:
630 A, 1000 Aand 1250 A
2000 A and 2500 A
Current transformer installation (basic scheme)
Panel with busbar1250 A
Panel with busbar2500 A
Electrical data
Designation Type 4MC
Operating voltage max. 0.8 kV
Rated short-durationpower-frequency withstandvoltage (winding test)
3 kV
Rated frequency 50 / 60 Hz
Rated continuousthermal current
max. 1.2 xrated current(primary)
Rated thermal short-timecurrent, max. 3 s
max. 31.5 kA
Rated current dynamic primary
secondary
unlimited40 A to2500 A1 A and 5 A
Designation Type 4MC
Multiratio (secondary) 200 A 100 A
to 2500 A 1250 A
Core data according torated primary current:
max. 3 cores
Measuring Ratingcore Class Overcurrent
factor
2.5 VA to 30 VA0.2 to 1
FS 5, FS 10
Protection Ratingcore Class Overcurrent
factor
2.5 VA to 30 VA5 P or 10 P
10 to 30
Permissible ambient airtemperature
max. 60 C
Insulation class E
Current transformers
1 Busbar current transformer2 Feeder current transformer at
the panel connection3 Cable-type current transformer
4 Zero-sequence current transformer
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
37/56
37Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Voltage transformers
Components
FeaturesAccording to IEC 60044-2 andVDE 0414-21-pole, plug-in designConnection system with plug-incontactInductive type
Safe-to-touch due to metal coverCertifiableClimate-independentSecondary connection bymeans of plugs inside the panelCast-resin insulatedArranged outside the primaryenclosure (switchgear vessel)Mounting locations:
At the busbar At the panel connection.
Voltage transformer typesBusbar voltage transformer4MT2:
Pluggable in the cross adaptersof the busbar 1250 A usingadditional adapters(> 1250 A on request)No separate metering panelrequiredSuitable for 80 % of the ratedshort-duration power-frequencywithstand voltage at ratedfrequencyRepeat test at 80 % of the ratedshort-duration power-frequencywithstand voltagepossible with mounted voltagetransformer (also valid for
higher insulation ratingsaccording to GOST and GBstandards)Feeder voltage transformer4MT3 at the panel connection:Switchable through an SF 6-insulated disconnecting facilityin the switchgear vesselPositions: CLOSED and Trans-former bushing EARTHEDOperation of the disconnectingfacility from outside througha metal bellows welded in theswitchgear vesselVoltage testing of switch-gear and cables possible with
mounted and earthed voltagetransformerFeeder voltage transformer4MU2 at the panel connectionof the incoming sectionalizer(side B)Connection to bushing withshort, flexible cable.
Voltage transformer
Feeder voltage transformer(metal-coated)
Voltage transformer installation (basic design) Disconnecting facility forfeeder voltage transformer
(detail Z)
OPEN and EARTHED
CLOSED
Front view: Side view:
1 Busbar voltage transformer2 Feeder voltage transformer
at the panel connection3 Operating lever for
disconnecting facility4 Panel connection5 Switchgear vessel wall
(earthed)
R-HA35-120
eps
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
38/56
38 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Voltage transformers
Components
GOST : Russian standardGB : Chinese standard
Rated voltage
kV
Rated short-durationpower-frequencywithstand voltage
kV
Rated lightningimpulse withstandvoltage
kV
Standard Operating voltage
kV
3.6 10 20 IEC 3.3 / 3
7.2 20 60 IEC 3.6 / 3; 4.8 / 3; 5.0 / 3;6.0 / 3; 6.3 / 3; 6.6 / 3
32 60 GOST 6.0 / 3; 6.3 / 3; 6.6 / 3
12 28 75 IEC 7.2 / 3; 10 / 3; 11 / 3
42 75 GOST 10 / 3; 11 / 3
42 75 GB 10 / 3; 11 / 3
17.5 38 95 IEC 13.2 / 3; 13.8 / 3; 15 / 3
24 50 125 IEC 17.5 / 3; 20 / 3; 23 / 3
Fortype
Operatingvoltage
V
Auxiliarywinding
V
Thermallimit current(measuringwinding)A
Rated long-time current8 h
A
Rating at accuracy class
0.2
VA
0.5
VA
1
VA
3
VA
4MT34MU2
100 / 3;110 / 3;120 / 3
100 / 3;110 / 3;120 / 3
6 4 IEC
10, 15, 20,25, 30
10, 15, 20,25, 30, 45,50, 60, 75,90
10, 15, 20,25, 30, 45,50, 60, 75,90, 100, 120,
150, 180
10, 15, 20,25, 30, 45,50, 60, 75,90, 100, 120,
150, 180GOST 32 / 60 kV
10, 15, 20,25, 30
10, 15, 20,25, 30, 45,50, 60, 75,90
10, 15, 20,25, 30, 45,50, 60, 75,90, 100, 120,150, 180
10, 15, 20,25, 30, 45,50, 60, 75,90, 100, 120,150, 180
GOST 42 / 75 kV, GB 42 / 75 kV
10, 15, 20,25
10, 15, 20,25, 30, 45,50, 60, 75
10, 15, 20,25, 30, 45,50, 60, 75,90, 100, 120,150
10, 15, 20,25, 30, 45,50, 60, 75,90, 100, 120,150
4MT2 100 / 3;110 / 3;120 / 3
100 / 3;110 / 3;120 / 3
8 6 IEC
5, 10, 15,20, 25
10, 15, 20,25, 30, 45
10, 15, 20,25, 30, 45,
50, 60, 75
10, 15, 20,25, 30, 45,
50, 60, 75GOST 32 / 60 kV
5 10, 15 10, 15, 20,25, 30
10, 15, 20,25, 30
GOST 42 / 75 kV, GB 42 / 75 kV
5, 10 10, 15, 20,25, 30
10, 15, 20,25, 30, 45,50, 60
10, 15, 20,25, 30, 45,50, 60
Electrical data
Primary data
For types 4MT3, 4MT2 and 4MU2For operating voltages from 3.3 to 23 kV, rated voltage factor Un/ 8h = 1.9; Un/ continuous = 1.2
Secondary data
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
39/56
39Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Panel connection
Components
FeaturesBushings with outside coneWith bolted contact (M16) asinterface type C according toEN 50 180 / EN 50 181For cable connection heights,see table on the right
Max. connection depth: 584 mm or 732 mm with stan-dard cable compartment cover,752 mm with deep cable com-partment coverWith cable bracket, e.g.type C40 according toDIN EN 50 024O ption: Access to the cablecompartment only if the feederhas been isolated and earthedFor thermoplastic-insulatedcablesFor shielded cable T-plugs orcable elbow plugs with boltedcontact
For connection cross-sectionsup to 630 mm2Larger cross-sections on requestCable routing downwards, cableconnection from the frontO ption: Cable routing upwardsto the rear, cable connectionfrom the rear (only for circuit-breaker panel 1250 A)For rated normal currents upto 2500 ACable plugs and cable sealingends are not included in thescope of supply.
Surge arrestersPluggable on cable T-plugSurge arresters recommendedif, at the same time,the cable system is directly con-nected to the overhead line,the protection zone of thesurge arrester at the end towerof the overhead line does notcover the switchgear.
Surge limitersPluggable on cable T-plugSurge limiters recommendedwhen motors with starting cur-rents < 600 A are connected.
Connectable cablesCable T-plug with coupling insert
Cable T-plug with coupling T-plug
Cable compartment
Panel width 600 mm
* Cable connectionheight for switch-disconnector andcontactor panels withHV HRC fuses
Connection with1 cable per phaseConnection with2 cables per phase
Connection with2 cables per phaseConnection with4 cables per phase
Connection with2 cables per phaseConnection with4 cables per phase
Connection with3 cables per phaseConnection with6 cables per phase
Connection with 3 cables per phaseConnection with 6 cables per phase
Connection with 4 cables per phaseConnection with 8 cables per phase
Panel width 600 mm
Panel width 900 mm
Legend
1 Cable T-plug2 Coupling T-plug
3 Screw-type coupling insert
Cable connection heights
Panels Heightof cablecompart-ment
mm
Distancebetween bush-ing and cablebracket
mm600 mm 702 500
900 mm 577 400
Switch-dis-connectorpanel andcontactorpanel withfuse
450 280
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
40/56
40 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Installation possibilities for cable connections and surge arresters,single-core PE and XLPE-insulated
Components
Numberof cablesper paneland phase
Make Conductorcross-section 1)
mm2
Cable T-plugs Coupling inserts /coupling plugs
Surge arresters with coupling inserts According tostandardArresters Coupling inserts
bolted12 kV24 kV
bolted12 kV24 kV
additionally GOST for Russia& GUSGB / DL for China
Circuit-breaker panel 630 A, 1000 A Switch-disconnector panel 630 A Disconnector panel 1000 A Ring-main panel 630 A Contactor panel Circuit-breaker panel with top-rear cable connection 1250 A 2)
1 Euromold 35 to 300 1x 400TB / G1x K400TB / G1x K400TB / G-CSxxx
400PB-5(10)-SA-xxx
IEC, GOST, GB / DLIECGOST, GB / DL
35 to 300 1x 430TB-630A1x K430TB-630A1x K430TB-630A-CSxxx
300SA-5(10)SA
IEC, GOST, GB / DLIECGOST, GB / DL
400 to 630 1x 440TB / G1x K440TB / G1x K440TB / G-CSxxx
400PB-5(10)-SA-xxx
IEC, GOST, GB / DLIECGOST, GB / DL
Sdkabel 50 to 30025 to 240
1x SET 121x SET 24
MUT 23
IEC, GOST, GB / DLIEC, GOST, GB / DL
400 to 500300 to 500
1x SEHDT 131x SEHDT 23
MUT 23
IEC, GOST, GB / DLIEC, GOST, GB / DL
nkt cables 25 to 30025 to 50025 to 300
1x CB 12-6301x CB 17.5-6301x CB 24-630
CSA 12-xCSA 17.5-xCSA 24-x
IECGOST, GB / DLIEC, GOST, GB / DL
400 to 630 1x CB 36-630(1250)
1x CB 36-630(1250)
CSA 12-x
CSA 24-x
IEC, GOST, GB / DL
IEC, GOST, GB / DLTycoElectronicsRaychem
25 to 300 1x RSTI-L56xx1x RSTI-L56xx
RSTI-CC-L56SAxxxxRSTI-CC-66SAxxxx
IECIEC
25 to 300 1x RSTI-L56xx-CEE011x RSTI-L56xx-CEE01
RSTI-CC-L56SAxxxxRSTI-CC-66SAxxxx
GOSTGOST
25 to 300 1x RSTI-58xx1x RSTI-58xx
RSTI-CC-58SAxxxx
IECIEC
25 to 300 1x RSTI-58xx-CEE011x RSTI-58xx-CEE01
RSTI-CC-58SAxxxx
GOSTGOST
400 to 630 1x RSTI-36Lxx1x RSTI-56Lxx
RSTI-L56SAxxxxRSTI-66SAxxxx
RSTI-66CP-M16RSTI-66CP-M16
IECIEC
400 to 630 1x RSTI-36Lxx-CEE011x RSTI-56Lxx-CEE01
RSTI-L56SAxxxxRSTI-66SAxxxx
RSTI-66CP-M16RSTI-66CP-M16
GOSTGOST
3M 50 to 24025 to 240
1x 93-EE 705-61x 93-EE 705-6
IEC, GOST, GB / DLIEC, GOST, GB / DL
300 to 400 1x 93-EE 715-6
1x 93-EE 715-6
IEC, GOST, GB / DL
IEC, GOST, GB / DL2 Euromold 35 to 300 2x 400TB / G
2x K400TB / G2x K400TB / G-CSxxx
1x 400CP1x K400CP1x K400CP
IEC, GOST, GB / DLIECGOST, GB / DL
35 to 300 1x 430TB-630A1x K430TB-630A1x K430TB-630A-CSxxx
1x 300PB-630A1x K300PB-630A1x K300PB-630A-CSxxx
300SA-5(10)SA
IEC, GOST, GB / DLIECGOST, GB / DL
400 to 630 2x 440TB / G2x K440TB / G2x K440TB / G-CSxxx
1x 440CP1x K440CP1x K440CP
IEC, GOST, GB / DLIECGOST, GB / DL
Sdkabel 50 to 30025 to 240
1x SET 121x SET 24
1x SEHDK 13.11x SEHDK 23.1
IEC, GOST, GB / DLIEC, GOST, GB / DL
50 to 30025 to 240
2x SET 122x SET 24
1x KU 23.21x KU 23.2
IEC, GOST, GB / DLIEC, GOST, GB / DL
400 to 500300 to 500
2x SEHDT 132x SEHDT 23
1x KU 231x KU 23
IEC, GOST, GB / DLIEC, GOST, GB / DL
nkt cables 25 to 300
25 to 50025 to 300
1x CB 12-630
1x CB 17.5-6301x CB 24-630
1x CC 12-630
1x CC 17.5-6301x CC 24-630
CSA 12-x
CSA 17.5-xCSA 24-x
IEC
GOST, GB / DLIEC, GOST, GB / DL
25 to 300 2x CB 12-6302x CB 24-630
1x CP 630-C1x CP 630-C
CSA 12-xCSA 24-x
IECIEC, GOST, GB / DL
400 to 630 1x CB 36-630(1250)1x CB 36-630(1250)
1x CC 36-630(1250)1x CC 36-630(1250)
CSA 12-xCSA 24-x
IEC, GOST, GB / DLIEC, GOST, GB / DL
400 to 630 2x CB 36-630(1250)2x CB 36-630(1250)
1x CP 630-M161x CP 630-M16
CSA 12-xCSA 24-x
IEC, GOST, GB / DLIEC, GOST, GB / DL
TycoElectronicsRaychem
25 to 300 1x RSTI-L56xx1x RSTI-L56xx
1x RSTI-CC-L56xx1x RSTI-CC-L56xx
RSTI-CC-L56SAxxxxRSTI-CC-66SAxxxx
IECIEC
25 to 300 1x RSTI-L56xx-CEE011x RSTI-L56xx-CEE01
1x RSTI-CC-L56xx-CEE011x RSTI-CC-L56xx-CEE01
RSTI-CC-L56SAxxxxRSTI-CC-66SAxxxx
GOSTGOST
25 to 300 1x RSTI-58xx1x RSTI-58xx
1x RSTI-CC-58xx1x RSTI-CC-58xx
RSTI-CC-58SAxxxx
IECIEC
1) Observe the actual short-circuit and current carrying capacity of the cables and sealing ends2) At a normal current of more than 1150 A, cable sealing ends with tin-plated, nickel-plated or silver-plated cable lugs are required
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
41/56
41Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Installation possibilities for cable connections and surge arresters,single-core PE and XLPE-insulated
Numberof cablesper paneland phase
Make Conductorcross-section 1)
mm2
Cable T-plugs Coupling inserts /coupling plugs
Surge arresters with coupling inserts According tostandardArresters Coupling inserts
bolted12 kV24 kV
bolted12 kV24 kV
additionally GOST for Russia& GUSGB / DL for China
Circuit-breaker panel 630 A, 1000 A Switch-disconnector panel 630 A Disconnector panel 1000 A Ring-main panel 630 A Contactor panel Circuit-breaker panel with top-rear cable connection 1250 A 2)
2 TycoElectronicsRaychem
25 to 300 1x RSTI-58xx-CEE011x RSTI-58xx-CEE01
1x RSTI-CC-58xx-CEE011x RSTI-CC-58xx-CEE01
RSTI-CC-58SAxxxx
GOSTGOST
400 to 630 2x RSTI-36Lxx2x RSTI-56Lxx
1x RSTI-66CP-M161x RSTI-66CP-M16
IECIEC
400 to 630 2x RSTI-36Lxx-CEE012x RSTI-56Lxx-CEE01
1x RSTI-66CP-M161x RSTI-66CP-M16
GOSTGOST
3M 50 to 24025 to 240
2x 93-EE 705-62x 93-EE 705-6
1x KU 23.21x KU 23.2
IEC, GOST, GB / DLIEC, GOST, GB / DL
240150 to 240
1x 93-EE 705-61x 93-EE 705-6
1x 93-EE 718-61x 93-EE 718-6
IEC, GOST, GB / DLIEC, GOST, GB / DL
300 to 400 2x 93-EE 715-62x 93-EE 715-6
1x KU 23.21x KU 23.2
IEC, GOST, GB / DLIEC, GOST, GB / DL
3 Euromold 35 to 300 1x 430TB-630A1x K430TB-630A1x K430TB-630A-CSxxx
2x 300PB-630A2x K300PB-630A2x K300PB-630A-CSxxx
IEC, GOST, GB / DLIECGOST, GB / DL
nkt cables 25 to 30025 to 50025 to 300
1x CB 12-6301x CB 17.5-6301x CB 24-630
2x CC 12-6302x CC 17.5-6302x CC 24-630
IECGOST, GB / DLIEC, GOST, GB / DL
400 to 630 1x CB 36-630(1250)1x CB 36-630(1250)
2x CC 36-630(1250)2x CC 36-630(1250)
IEC, GOST, GB / DLIEC, GOST, GB / DL
TycoElectronicsRaychem
25 to 300 1x RSTI-L56xx1x RSTI-L56xx
2x RSTI-CC-L56xx2x RSTI-CC-L56xx
IECIEC
25 to 300 1x RSTI-L56xx-CEE011x RSTI-L56xx-CEE01
2x RSTI-CC-L56xx-CEE012x RSTI-CC-L56xx-CEE01
GOSTGOST
25 to 300 1x RSTI-58xx1x RSTI-58xx
2x RSTI-CC-58xx2x RSTI-CC-58xx
IECIEC
25 to 300 1x RSTI-58xx-CEE011x RSTI-58xx-CEE01
2x RSTI-CC-58xx-CEE012x RSTI-CC-58xx-CEE01
GOSTGOST
Circuit-breaker panel 1250 A 2) Disconnector panel 1250 A 2) DBB circuit-breaker panel 1000 A DBB incoming sectionalizer 2)
1 Euromold 35 to 300 1x 400TB / G1x K400TB / G
400PB-5(10)-SA-xxx IEC, GOST, GB / DLIEC, GOST, GB / DL
35 to 300 1x 430TB-630A1x K430TB-630A
300SA-5(10)SA IEC, GOST, GB / DL
IEC, GOST, GB / DL400 to 630 1x 440TB / G1x K440TB / G
400PB-5(10)-SA-xxx IEC, GOST, GB / DLIEC, GOST, GB / DL
Sdkabel 50 to 30025 to 240
1x SET 121x SET 24
MUT 23 IEC, GOST, GB / DLIEC, GOST, GB / DL
400 to 500300 to 500
1x SEHDT 131x SEHDT 23
MUT 23 IEC, GOST, GB / DLIEC, GOST, GB / DL
nkt cables 25 to 30025 to 50025 to 300
1x CB 12-6301x CB 17.5-6301x CB 24-630
CSA 12-xCSA 17.5-xCSA 24-x
IECGOST, GB / DLIEC, GOST, GB / DL
400 to 630 1x CB 36-630(1250)1x CB 36-630(1250)
CSA 12-xCSA 24-x
IEC, GOST, GB / DLIEC, GOST, GB / DL
TycoElectronicsRaychem
25 to 300 1x RSTI-L56xx1x RSTI-L56xx
RSTI-CC-L56SAxxxxRSTI-CC-66SAxxxx
IECIEC
25 to 300 1x RSTI-L56xx-CEE011x RSTI-L56xx-CEE01
RSTI-CC-L56SAxxxxRSTI-CC-66SAxxxx
GOSTGOST
25 to 300 1x RSTI-58xx
1x RSTI-58xx
RSTI-CC-58SAxxxx
IEC
IEC25 to 300 1x RSTI-58xx-CEE01
1x RSTI-58xx-CEE01
RSTI-CC-58SAxxxx
GOSTGOST
400 to 630 1x RSTI-36Lxx1x RSTI-56Lxx
RSTI-L56SAxxxxRSTI-66SAxxxx
RSTI-66CP-M16RSTI-66CP-M16
IECIEC
400 to 630 1x RSTI-36Lxx-CEE011x RSTI-56Lxx-CEE01
RSTI-L56SAxxxxRSTI-66SAxxxx
RSTI-66CP-M16RSTI-66CP-M16
GOSTGOST
3M 50 to 24025 to 240
1x 93-EE 705-61x 93-EE 705-6
IEC, GOST, GB / DLIEC, GOST, GB / DL
300 to 400 1x 93-EE 715-61x 93-EE 715-6
IEC, GOST, GB / DLIEC, GOST, GB / DL
2 Euromold 35 to 300 2x 400TB / G2x K400TB / G
1x 400CP1x K400CP
400PB-5(10)-SA-xxx IEC, GOST, GB / DLIEC, GOST, GB / DL
Components
1) Observe the actual short-circuit and current carrying capacity of the cables and sealing ends2) At a normal current of more than 1150 A, cable sealing ends with tin-plated, nickel-plated or silver-plated cable lugs are required
8/12/2019 22kv Siemens Nxplusc-ha 35 41 En1-2009
42/56
42 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2009
Numberof cablesper paneland phase
Make Conductorcross-section 1)
mm2
Cable T-plugs Coupling inserts /coupling plugs
Surge arresters with coupling inserts According tostandardArresters Coupling inserts
bolted12 kV24 kV
bolted12 kV24 kV
additionally GOST for Russia& GUSGB / DL for China
Circuit-breaker panel 1250 A 2) Disconnector panel 1250 A 2) DBB circuit-breaker panel 1000 A DBB incoming sectionalizer 2)
2 Euromold 35 to 300 1x 430TB-630A1x K430TB-630A 1x 300PB-630A1x K300PB-630A 300SA-5(10)SA IEC, GOST, GB / DLIEC, GOST, GB / DL
400 to 630 2x 440TB / G2x K440TB / G
1x 440CP1x K440CP
400PB-5(10)-SA-xxx
IEC, GOST, GB / DLIEC, GOST, GB / DL
Sdkabel 50 to 30025 to 240
1x SET 121x SET 24
1x SEHDK 13.11x SEHDK 23.1
MUT 23
IEC, GOST, GB / DLIEC, GOST, GB / DL
50 to 30025 to 240
2x SET 122x SET 24
1x KU 23.21x KU 23.2
MUT 23
IEC, GOST, GB / DLIEC, GOST, GB / DL
400 to 500300 to 500
2x SEHDT 132x SEHDT 23
1x KU 231x KU 23
MUT 23
IEC, GOST, GB / DLIEC, GOST, GB / DL
nkt cables 25 to 30025 to 50025 to 300
1x CB 12-6301x CB 17.5-6301x CB 24-630
1x CC 12-6301x CC 17.5-6301x CC 24-630
CSA 12-xCSA 17.5-xCSA 24-x
IECGOST, GB / DLIEC, GOST, GB / DL
25 to 300 2x CB 12-6302x CB 24-630
1x CP 630-C1x CP 630-C
CSA 12-xCSA 24-x
IECIEC, GOST, GB / DL
400 to 630 1x CB 36-630(1250)1x CB 36-630(1250)
1x CC 36-630(1250)1x CC 36-630(1250)
CSA 12-xCSA 24-x
IEC, GOST, GB / DLIEC, GOST, GB / DL
400 to 630 2x CB 36-630(1250)2x CB 36-630(1250)
1x CP 630-M161x CP 630-M16
CSA 12-xCSA 24-x
IEC, GOST, GB / DLIEC, GOST, GB / DL
TycoElectronicsRaychem
25 to 300 1x RSTI-L56xx1x RSTI-L56xx
1x RSTI-CC-L56xx1x RSTI-CC-L56xx
RSTI-CC-L56SAxxxxRSTI-CC-66SAxxxx
IECIEC
25 to 300 1x RSTI-L56xx-CEE011x RSTI-L56xx-CEE01
1x RSTI-CC-L56xx-CEE011x RSTI-CC-L56xx-CEE01
RSTI-CC-L56SAxxxxRSTI-CC-66SAxxxx
GOSTGOST
25 to 300 1x RSTI-58xx1x RSTI-58xx
1x RSTI-CC-58xx1x RSTI-CC-58xx
RSTI-CC-58SAxxxx
IECIEC
25 to 300 1x RSTI-58xx-CEE011x RSTI-58xx-CEE01
1x RSTI-CC-58xx-CEE011x RSTI-CC-58xx-CEE01
RSTI-CC-58SAxxxx
GOSTGOST
400 to 630 2x RSTI-36Lxx2x RSTI-56Lxx
1x RSTI-66CP-M161x RSTI-66CP-M16
RSTI-L56SAxxxxRSTI-66SAxxxx
RSTI-66CP-M16RSTI-66CP-M16
IECIEC
400 to 630 2x RSTI-36Lxx-CEE012x RSTI-56Lxx-CEE01
1x RSTI-66CP-M161x RSTI-66CP-M16
RSTI-L56SAxxxxRSTI-66SAxxxx
RSTI-66CP-M16RSTI-66CP-M16
GOSTGOST
3M 50 to 24025 to 240
2x 93-EE 705-62x 93-EE 705-6
1x KU 23.21x KU 23.2
IEC, GOST, GB / DLIEC, GOST, GB / DL
240150 to 240 1x 93-EE 705-61x 93-EE 705-6 1x 93-EE 718-61x 93-EE 718-6 IEC, GOST, GB / DLIEC, GOST, GB / DL
300 to 400 2x 93-EE 715-62x 93-EE 715-6
1x KU 23.21x KU 23.2
IEC, GOST, GB / DLIEC, GOST, GB / DL
3 Euromold 35 to 300 3) 3x 400TB / G3x K400TB / G
2x 400CP2x K400CP
IEC, GOST, GB / DLIEC, GOST, GB / DL
35 to 300 1x 430TB-630A1x K430TB-630A
2x 300PB-630A2x K300PB-630A
300SA-5(10)SA
IEC, GOST, GB / DLIEC, GOST, GB / DL
400 to 630 3) 3x 440TB / G3x K440TB / G
2x 440CP2x K440CP
IEC, GOST, GB / DLIEC, GOST, GB / DL
nkt cables 25 to 30025 to 50025 to 300
1x CB 12-6301x CB 17.5-6301x CB 24-630
2x CC 12-6302x CC 17.5-6302x CC 24-630
CSA 12-xCSA 17.5-xCSA 24-x
IECGOST, GB / DLIEC, GOST, GB / DL
400 to 630 1x CB 36-630(1250)1x CB 36-630(1250)
2x CC 36-630(1250)2x CC 36-630(1250)
CSA 12-xCSA 24-x
IEC, GOST, GB / DLIEC, GOST, GB / DL
TycoElectronics
Raychem
25 to 300 1x RSTI-L56xx1x RSTI-L56xx
2x RSTI-CC-L56xx2x RSTI-CC-L56xx
RSTI-CC-L56SAxxxxRSTI-CC-66SAxxxx
IECIEC
25 to 300 1x RSTI-L56xx-CEE011x RSTI-L56xx-CEE01
2x RSTI-CC-L56xx-CEE012x RSTI-CC-L56xx-CEE01
RSTI-CC-L56SAxxxxRSTI-CC-66SAxxxx
GOSTGOST
25 to 300 1x RSTI-58xx1x RSTI-58xx
2x RSTI-CC-58xx2x RSTI-CC-58xx
RSTI-CC-58SAxxxx
IECIEC
25 to 300 1x RSTI-58xx-CEE011x RSTI-58xx-CEE01
2x RSTI-CC-58xx-CEE012x RSTI-CC-58xx-CEE01
RSTI-CC-58SAxxxx
GOSTGOST
400 to 630 3x RSTI-36Lxx3x RSTI-56Lxx
2x RSTI-66CP-M162x RSTI-66CP-M16
IECIEC
400 to 630 3x RSTI-36Lxx-CEE013x RSTI-56Lxx-CEE01
2x RSTI-66CP-M162x RSTI-66CP-M16
GOSTGOST
4 Euromold 35 to 300 1x 430TB-630A1x K430TB-630A
3x 300PB-630A3x K300PB-630A
IEC, GOST, GB / DLIEC, GOST, GB / DL
1) Observe the actual short-circuit and current carrying capacity of the cables and sealing ends
2) At a normal current of more than 1150 A, cable sealing ends with tin-plated, nickel-plated or silver-plated cable lugs are required3) Only possible with deep cable compartment cover
Installation possibilities for cable connections and surge arresters,single-core PE and XLPE-insulated
Components