Version: 4.70 ‧ English Original document Revision: - (Build 41140) © 2019 Smart view Manual SMARTV-4.70-EN-MAN Parameter Setting and Evaluation Software
Transcript

Version: 4.70 English

Original document

Revision: - (Build 41140) 2019

Smart view

Manual SMARTV-4.70-EN-MANParameter Setting and Evaluation Software

Manual (original)

Woodward Kempen GmbH

Krefelder Weg 47 D47906 Kempen (Germany)

Postfach 100755 (P.O.Box) D47884 Kempen (Germany)

Telephone: +49(0)21521451

2019 Woodward Kempen GmbH

2 Smart view SMARTV-4.70-EN-MAN

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

Table of contents1 Important Definitions 2 Introduction to Smart view 3 Setting up the Connection between PC and Device 3.1 Connect a HighPROTEC Device via a USB Cable 3.2 Connect a HighPROTEC Device via TCP/IP (Ethernet) 3.3 Connect a HighPROTEC Device via a Serial RS232 Interface 3.4 Connect a High Tech Line 3 Device 3.5 Troubleshooting during Setting up the Connection 3.5.1 Persistent Connection Problems (*) 4 Command-Line Parameters and Exit Codes 5 Smart view Keyboard Commands 6 Operating a HighPROTEC Protection Device 6.1 Loading of Device Data when using Smart view 6.2 Transfer Device Data from Smart view to the Device 6.3 Backup and Documentation when using Smart view 6.4 Offline Device Planning via Smart view 6.5 Measuring Values 6.6 Acknowledgments and Resets 6.7 Status Display via Smart view 6.8 Recorders 6.8.1 Disturbance Recorder 6.8.2 Fault Recorder 6.8.3 Trend Recorder 6.8.4 Event Recorder 6.8.5 Motor Start Recorder 6.8.6 Statistic Recorder 6.8.7 Internal Messages (Self-Supervision Recorder) 6.9 Passwords 6.10 Device Planning 6.11 Parameters 6.11.1 Parameter Files 6.12 Digital Inputs 6.13 Synchronize Date and Time via Smart view 6.14 Display Version Information 6.15 Display of ANSI-Codes 6.16 Graphical Display of Tripping Characteristics 6.17 Single-Line Diagrams 6.18 Programmable Logic via Smart view 6.19 Communication (SCADA) 6.19.1 IEC 61850(*) 6.19.2 Configurable Communication Protocols(*) 6.19.3 Remote Configuration for Line Differential Protection Devices(*) 7 Operating a High Tech Line 3 Device 7.1 Loading of Device Data when using Smart view 7.2 Transfer Device Data from Smart view to the Device 7.3 Backup and Documentation when using Smart view 7.4 Offline Device Planning via Smart view 7.5 Measuring Values

3Smart viewSMARTV-4.70-EN-MAN

Table of contents

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

7.6 Status Display via Smart view 7.7 Recorders 7.8 Parameters 7.9 Synchronize Date and Time via Smart view 7.10 Version via Smart view 8 Index

4 Smart view SMARTV-4.70-EN-MAN

Table of contents

1 Important DefinitionsThe types of messages shown below serve the safety of life and limb as well as for theappropriate operating life of the device.

DANGER!

DANGER indicates an immediately dangerous situation that will result in death or seriousinjury if it is not avoided.

WARNING!

WARNING indicates a hazardous situation that can result in death or serious injury if it isnot avoided.

CAUTION!

CAUTION indicates a possibly hazardous situation that can result in minor or moderateinjuries if it is not avoided.

NOTICE!

NOTICE is used to address practices not related to personal injury.

This symbol indicates useful tips and recommendations as well as information for efficientand trouble-free operation.

Proper Use of the Device and of This Manual

WARNING!

FOLLOW INSTRUCTIONS

Read this entire manual and all other publications pertaining to the work to be performedbefore installing, operating, or servicing this equipment. Practice all plant and safetyinstructions and precautions. Failure to follow instructions can cause personal injuryand/or property damage.

5Smart viewSMARTV-4.70-EN-MAN

1 Important Definitions

WARNING!

PROPER USE

Any unauthorized modifications to or use of this equipment outside its specifiedmechanical, electrical, or other operating limits may cause personal injury and/orproperty damage, including damage to the equipment. Any such unauthorizedmodifications: (1) constitute misuse and/or negligence within the meaning of theproduct warranty thereby excluding warranty coverage for any resulting damage, and (2)invalidate product certifications or listings.

The programmable devices subject to this manual are designed for protection and alsocontrol of power installations and operational devices that are fed by voltage sources witha fixed frequency, i.e. fixed at 50 or 60 Hertz. They are not intended for use with VariableFrequency Drives. The devices are further designed for installation in low-voltage (LV)compartments of medium voltage (MV) switchgear panels or in de-centralized protectionpanels. The programming and parameterization has to meet all requirements of theprotection concept (of the equipment that is to be protected). You must ensure that thedevice will properly recognize and manage (e.g. switch off the circuit breaker) on thebasis of your programming and parameterization all operational conditions (failures). Theproper use requires a backup protection by an additional protective device. Beforestarting any operation and after any modification of the programming (parameterization)test make a documentary proof that your programming and parameterization meets therequirements of your protection concept.

The Self-Supervision Contact (Life-Contact) has to be wired with the substationautomation system in order to supervise and monitor the state of health of theprogrammable protective device. It is very important that an alarm annunciation is drivenfrom the programmable protective device self-supervision contact (Life-Contact) thatrequires immediate attention when tripped. The alarm indicates that the protectivedevice is no longer protecting the circuit and the system should be serviced.

Typical applications for this product family/device line are for instance:

Feeder protection Mains protection Machine protection Transformer Protection Generator Protection

Any usage beyond these applications the devices are not designed for. This applies alsoto the use as a partly completed machinery. The manufacturer cannot be held liable forany resulting damage, the user alone bears the risk for this. As to the appropriate use ofthe device: The technical data and tolerances specified by Woodward have to be met.

6 Smart view SMARTV-4.70-EN-MAN

1 Important Definitions

Out-of-date documentation?

This publication may have been revised or updated since this copy was produced. Toverify that you have the latest revision, please visit the download section of our website.

Please check the web site of Woodward for the latest revision of this Technical Manual andif there is an Errata Sheet with updated information.

Visit the company website ( www.woodward.com) and search for the documentsyou are interested in. (The ID of every document is printed on its cover page.)

Alternatively, every HighPROTEC device has a QR code printed on it. Scan this code,and you are taken to an online directory that contains all relevant documents in themost recent version.

Important Information

WARNING!

In line with the customers requirement the devices are combined in a modular way (incompliance with the order code). The terminal assignment of the device can be found onthe top of the device (wiring diagram).

7Smart viewSMARTV-4.70-EN-MAN

1 Important Definitions

http://www.woodward.com/

CAUTION!

Electrostatic Discharge Awareness

All electronic equipment is electro static-sensitive, some components more than others.To protect these components from electro static damage, you must take specialprecautions to minimize or eliminate electrostatic discharges. Follow these precautionswhen working with or near the control.

1. Before doing maintenance on the electronic control, discharge the static electricity onyour body to ground by touching and holding a grounded metal object (pipes, cabinets,equipment, etc.).

2. Avoid the build-up of static electricity on your body by not wearing clothing made ofsynthetic materials. Wear cotton or cotton-blend materials as much as possible becausethese do not store static electric charges as much as synthetics.

3. Keep plastic, vinyl, and Styrofoam materials (such as plastic or Styrofoam cups, cupholders, cigarette packages, cellophane wrappers, vinyl books or folders, plastic bottles,and plastic ash trays) away from the control, the modules, and the work area as much aspossible.

4. Do not remove any printed circuit board (PCB) from the control cabinet unlessabsolutely necessary. If you must remove the PCB from the control cabinet, follow theseprecautions:

Verify the safe isolation from supply. All connectors have to be unplugged. Do not touch any part of the PCB except the edges. Do not touch the electrical conductors, the connectors, or the components with

conductive devices or with your hands. When replacing a PCB, keep the new PCB in the plastic antistatic protective bag it

comes in until you are ready to install it. Immediately after removing the old PCBfrom the control cabinet, place it in the antistatic protective bag.

To prevent damage to electronic components caused by improper handling, read andobserve the precautions in the Woodward manual 82715, Guide for Handling andProtection of Electronic Controls, Printed Circuit Boards, and Modules.

Woodward reserves the right to update any portion of this publication at any time.Information provided by Woodward is believed to be correct and reliable. However, noresponsibility is assumed by Woodward unless otherwise expressly undertaken.

2019 Woodward. All Rights Reserved.

8 Smart view SMARTV-4.70-EN-MAN

1 Important Definitions

2 Introduction to Smart viewSmart view is a parameter setting and evaluation software.

It is primarily intended to be connected with devices from the HighPROTEC family ofprotection devices, and therefore this is the main focus of this manual, especially becausethe devices from this series offer the most complexity and feature-richness. However,there are also a lot of protection devices from the High Tech Line 3, the Professional Lineand the WI Line series supported. Woodward will continue to add support for more andmore devices (plus of course further enhancements in general); therefore it isworthwhile making sure to always have the latest Smart view version installed.

However, please be aware that for devices from the High Tech Line 3, theProfessional Line and the WI Line series, not all functionality described in this manual isavailable; only those features can be used that are actually supported by the connecteddevice.

The full feature set, as available with HighPROTEC devices, comprises:

Menu-controlled parameter setting incl. validity checks

Offline configuration of all relay types

Reading and evaluating of statistical data and measuring values

Setting into operation assistance

Display of the device status

Fault analysis via event- and fault recorder

NOTICE!

Smart view 3.0 or higher supports reading parameter files generated by older versions ofSmart view. Parameter files generated by Smart view 3.0 and higher cannot be read byolder versions of Smart view.

Installation of Smart view

NOTICE!

The TCP/IP ports in the range 52152 52163 must not be blocked by a firewall, and noneof these ports must be used by any other (non-Woodward) application.

NOTICE!

If the Windows User Access Control pops up while installing Smart view, please Allow allinstallation requirements concerning Smart view.

System requirements:

Windows 7, Windows 8.x or Windows 10

9Smart viewSMARTV-4.70-EN-MAN

2 Introduction to Smart view

The Smart view setup file is available on the product DVD, that is part of the delivery ofthe protective device. The setup program Smartview_SE_Install.exe is contained inthe Smart view SE folder of the product DVD.

In addition, the Smart view setup can also be retrieved from this Woodward downloadarea: wwdmanuals.com/smart_view

To install Smart view:

Double-click on the installation file with the left mouse button.

Select a language for the installation procedure.

Confirm by pressing the Continue button in the INFO frame.

Select an installation path or confirm the standard installation path by mouse clickon the Continue button.

Confirm the entry for the suggested installation folder by mouse click onthe Continue button.

By mouse click on the Install button, the installation routine is started.

Close the installation procedure by mouse click on the Complete button.

Now you can launch the program via [Start / Programs / Woodward / Smart view].

Silent Installation

In some cases it is required to perform an unattended (silent) installation. For example,an IT department might want to remotely install or upgrade Smart view without the PCuser being distracted by dialog windows.

The setup program features a special silent mode for this purpose, which is entered ifcommand-line options are given as follows:

Smartview_SE_Install.exe /SILENT

This command performs a silent installation of all Smart view-related applicationsincluding USB driver, and there is no user interaction needed for the installationprocess. However, the Installation Progress window is visible during the installationprocess.

Smartview_SE_Install.exe /VERYSILENT

This command performs a very silent installation of all Smart view-relatedapplications including USB driver: There is no user interaction needed for theinstallation process, and no dialog or window is visible.

The SILENT and VERYSILENT options may be used with another option, UNINSTOLD.

Smartview_SE_Install.exe /SILENT /UNINSTOLD

Smartview_SE_Install.exe /VERYSILENT /UNINSTOLD

In addition to the silent and very silent installation described above, it is checkedwhether there are any previous (old) versions of Smart view installed, and if this isthe case then the previous version(s) are uninstalled (also in a silent manner,without any user interaction).

10 Smart view SMARTV-4.70-EN-MAN

2 Introduction to Smart view

http://wwdmanuals.com/smart_view

NOTICE!

Note that additional preparations might be necessary to let the installation process runseamlessly; in particular, the UAC (User Access Control) dialog of the Windowsoperating system has to be managed via the Microsoft System Center and theMicrosoft Group Policy.

Uninstalling Smart view

Via the usual Software Control Panel [Start / System Control / Software] the Smart viewcan be removed from your computer.

Optional Accessories

The type of cable required for the connection is dependent on the type of protectivedevice. The cables are not part of the product delivery, but can be ordered separatelyfrom Woodward.

Smar

tV_Z

22

Smar

tV_Z

23

Smar

tV_Z

24

USB cable, for protectivedevices with USB frontconnector.

Woodward article:

54501946

Null Modem cable, for protectivedevices with RS232 frontconnector.

Woodward article:

COMRS232Nullm

USB/Serial adaptor, forprotective devices with RS232front connector and PC withoutRS232 connector.

Woodward article:

USB2RS232ADAP

Switching the Language of the Graphical User Interface

Within the menu [Settings / Language], you can change the language of the graphicaluser interface.

Program Exit

You quit Smart view by clicking the menu item [File / Exit] or, alternatively, clickingthe Exit icon () top right of the window, as usual with Windows applications.

If any modifications have been made in a currently loaded parameter setting file, you areasked to save these changes.

If a device is still connected, this connection will be closed.

11Smart viewSMARTV-4.70-EN-MAN

2 Introduction to Smart view

3 Setting up the Connection between PC andDeviceThe menu item [Settings / Device Connection] allows for selecting the type of connectionthat is used for connecting Smart view with a protection device. There are variousoptions:

Serial connection, see Connect a HighPROTEC Device via a Serial RS232Interface

USB connection, see Connect a HighPROTEC Device via a USB Cable

Ethernet connection, see Connect a HighPROTEC Device via TCP/IP (Ethernet)

HTL3/PL/WIP device connection, which is used for connecting with a protectiondevice from the High Tech Line 3, the Professional Line or WI Line series; see Connect a High Tech Line 3 Device

NOTICE!

If a firewall is installed on your computer, make sure that no TCP/IP port in the range52152 52163 is blocked. (This is required for all connection types listed here.)

Secured Communication

Only for HighPROTEC devices as of Release 3.4: For security reasons, it is possibleto restrict or disable the connection between Smart view and the HighPROTEC device. Ofcourse, the following descriptions assume that the access has not been blocked.

Only for HighPROTEC devices as of Release 3.6: Moreover, a connection isestablished only after a connection password has been entered. Finally, the connection isfully encrypted, and certificates guarantee the correct identity of the communicationparties. The user, however, need not take care of the encryption, this is establishedautomatically in the background. (See the Security chapter of the device manual fordetails.)

12 Smart view SMARTV-4.70-EN-MAN

3 Setting up the Connection between PC and Device

3.1 Connect a HighPROTEC Device via a USB Cable

Smar

tV_Z

04

Smart view

USB Cable5450-1946

Protective Relay

Fig. 1: Parameter setting and evaluation via USB cable.

NOTICE!

For HighPROTEC devices as of Release 3.4 it is possible for security reasons to disable thisconnection type (though the factory default is that it is set active). Of course, thefollowing description assumes that the access has been activated.

1. Please install Smart view in case that it has not yet been installed on your PC.

2. Connect your PC/notebook via a USB cable with a powered/running device.

3. Start Smart view.

4. Select the menu point Device Connection in menu Settings.

5. Within this menu select the communication option USB connection.

6. Within the Drop-Down-Menu select the connected USB device.

If the interface is chosen for the first time, a pop-up window will appear Theselected connection is currently not installed. Should this connection be used fordevice communication?.

7. Confirm this by pressing the Yes button.

Only for HighPROTEC devices as of Release 3.6: Remember that later, whileestablishing a connection, Smart view might ask for a connection password (USBconnection, unless this has been set empty). See 3 Secured Communication,

13Smart viewSMARTV-4.70-EN-MAN

3 Setting up the Connection between PC and Device3.1 Connect a HighPROTEC Device via a USB Cable

6.9 Change Passwords via Smart view and the Security chapter in the TechnicalManual of the relay.

14 Smart view SMARTV-4.70-EN-MAN

3 Setting up the Connection between PC and Device3.1 Connect a HighPROTEC Device via a USB Cable

3.2 Connect a HighPROTEC Device via TCP/IP (Ethernet)

WARNING!

Mixing up IP-Addresses (In case that there is more than one protective device within theTCP/IP network). Establishing an unintentional wrong connection to a protective devicebased on a wrong entered IP-Address. Transferring parameters into a wrong protectivedevice might lead to death, personal injury or damage of electrical equipment.

In order to prevent faulty connections the user has to document and maintain a list withthe IP addresses of any switchboard/protective device.

The user has to doublecheck the IP addresses of the connection that is to be established.That means, the user must first read out the IP address at the HMI of the device (withinmenu [Device Para / TCP/IP / TCP/IP config]), then compare the IP address with the list. Ifthe addresses are identical, establish the connection. Otherwise do not connect.

Smar

tV_Z

03

Smart view

TCP/IP CableEthernet RJ45

Protective Relay

IP Address

Fig. 2: Parameter Setting and Evaluation via TCP/IP.

NOTICE!

Establishing a connection via TCP/IP to the device is only possible if your device isequipped with an Ethernet interface.

Contact your IT administrator in order to establish the network connection.

For HighPROTEC devices as of Release 3.4 it is possible for security reasons to disable thisconnection type. Of course, the following description assumes that the access ispermitted.

15Smart viewSMARTV-4.70-EN-MAN

3 Setting up the Connection between PC and Device3.2 Connect a HighPROTEC Device via TCP/IP (Ethernet)

Part 1: Set the TCP/IP Parameters at the panel (Device).

Enter the menu branch [Device Para / TCP/IP / TCP/IP config] at the HMI (panel) and setthe following parameters:

TCP/IP address

Subnet mask

Gateway

Part 2: Setting the IP address within Smart view

1. Enter the menu [Settings / Device Connection] within Smart view.

2. Select the button Ethernet-Connection.

3. Enter the IP-Address of the device that should be connected.

Only for HighPROTEC devices as of Release 3.6: Remember that later, whileestablishing a connection, Smart view might ask for a connection password (Remotenetwork connection, unless this has been set empty). See 3 SecuredCommunication, 6.9 Change Passwords via Smart view and the Security chapterin the Technical Manual of the relay.

3.3 Connect a HighPROTEC Device via a Serial RS232 Interface

NOTICE!

The serial connection described here is applicable only for older HighPROTEC protectiondevices (until Release 2.5).

As of Release 3.0, all HighPROTEC protection devices have a USB interface, instead ofRS232. (Therefore the description in Connect a HighPROTEC Device via a USBCable is applicable for these.)

Smar

tV_Z

23

Null Modem cable

Woodward article:

COMRS232Nullm

SmartV_Z06

After installation of the Smart view, the Connection PC/Notebook to the Device has tobe configured once so that you are able to read device data or re-write them into thedevice by means of Smart view.

16 Smart view SMARTV-4.70-EN-MAN

3 Setting up the Connection between PC and Device3.3 Connect a HighPROTEC Device via a Serial RS232 Interface

NOTICE!

For connection of your PCs/notebooks with the device, you need the following equipment:

a zero-modem cable (Woodward article COMRS232Nullm, no serial cable)!

Please refer to chapter Zero Modem Cable within the device manual.

If your PC/notebook does not have a serial interface, you need a special USB-to-serial-adapter (Woodward article USB2RS232ADAP).

Only if the USB-to-serial-adapter is correctly installed - aided by the provided CD the communication with the device can be established. (See 3.3 Setting up/Configuring the Connection.)

Smar

tV_Z

23

Null Modem cable

Woodward article:

COMRS232Nullm

Smar

tV_Z

24

USB/Serial adaptor

Woodward article:

USB2RS232ADAP SmartV_Z06

Setting up/Configuring the Connection

1. Connect your PC/notebook with the device via a zero-modem cable.

Start the software Smart view.

2. Select the menu point Device Connection in menu Settings.

3. Click on Serial Connection.

4. Select the serial interface (COM-Port) where the device shall be connected to.

5. Confirm the adjustments by clicking the OK button.

If the interface is chosen for the first time, a popup window will appear Theselected connection is currently not installed. Should this connection be used fordevice communication? .

6. Confirm this by pressing the Yes button.

Establishing the Connection via a USB-/RS232-Adapter

If your PC/notebook is not provided with a serial interface, this can be compensated by aspecial USB-/RS232-Adapter+Zero Modem-Cable.

17Smart viewSMARTV-4.70-EN-MAN

3 Setting up the Connection between PC and Device3.3 Connect a HighPROTEC Device via a Serial RS232 Interface

NOTICE!

Only an adapter accepted by Woodward is to be used (USB2RS232ADAP). First install theadapter (with the related driver that you can find on the CD) and then establish theconnection (Smart view => Device). The adapters must support very high speed.

3.4 Connect a High Tech Line 3 Device

NPEP

NPEP

HTL_

Z42

AdapterRS485 RS232COMRS232Nullm

High Tech Line Device (back view)

PC

Fig. 3: Connection of a High Tech Line protection device with a PC.

NOTICE!

For connection of your PCs/notebooks with the device, you need the following equipment:

an RS485 to RS232 adapter (any supplier), and a zero-modem cable (Woodward article COMRS232Nullm, no serial cable)!

NOTICE!

If your PC/notebook does not have a serial interface, you also need a special USB-to-serial-adapter (Woodward article USB2RS232ADAP).

Setting up/Configuring the Connection

1. Connect your PC/notebook with the device via a zero-modem cable and RS485 toRS232 adapter (see diagram above).

Start the software Smart view.

2. Select the menu point Device Connection in menu Settings.

18 Smart view SMARTV-4.70-EN-MAN

3 Setting up the Connection between PC and Device3.4 Connect a High Tech Line 3 Device

3. Click on HTL3 / PL / WIP Device Connection.

4. Select the serial interface (COM-Port) where the device shall be connected to.

19Smart viewSMARTV-4.70-EN-MAN

3 Setting up the Connection between PC and Device3.4 Connect a High Tech Line 3 Device

3.5 Troubleshooting during Setting up the ConnectionGeneral

If a firewall is installed on your computer, make sure that no TCP/IP port in the range52152 52163 is blocked.

Ethernet Connections

Make sure that all TCP/IP data has been configured correctly (including theconfiguration of the protection device).

Check that the IP address of the protection device has been correctly entered inSmart view.

Note that currently only IPv4 addresses are supported.

Serial Connections (RS232) and USB Connections

Make sure whether the Windows service Telephony is started. If you press theWindows start button and navigate to [Start / System Control / Administration /Services] the service Telephony must be visible and must have also been started.If not, the service has to be started.

For establishing the connection, you need to have sufficient rights (administrationrights).

If your computer is not provided with a serial interface, you need a USB-to-serial-adapter (Woodward article USB2RS232ADAP). This adapter has to be properlyinstalled.

Ensure that a zero-modem cable is used (a standard serial cable without controlwires does not enable communication).

3.5.1 Persistent Connection Problems (*)

(*) applies only to serial connections (RS232) and USB connections

In case of persistent connection problems you should remove all connection settings andestablish them again afterwards. In order to remove all connection settings pleaseproceed as follows:

1. Remove the settings for the Dial-up Network

1. Close Smart view

2. Launch the Control Panel.

3. Choose Network & Internet.

4. On the left side, click on Manage Network Connections.

5. Click on HighPROTEC Direct Connection with the right-hand mouse key.

6. Choose Delete from the shortcut menu.

7. Click on the OK button.

20 Smart view SMARTV-4.70-EN-MAN

3 Setting up the Connection between PC and Device3.5 Troubleshooting during Setting up the Connection

2. Remove the virtual modem

1. Launch the Control Panel.

2. Choose Hardware & Sound.

3. Choose Phone & Modem Options.

4. Go to Tab Modem.

5. Click on the correct (in case there is more than one) entry Connection cablebetween two computers.

6. Click on the Remove button.

21Smart viewSMARTV-4.70-EN-MAN

3 Setting up the Connection between PC and Device3.5 Troubleshooting during Setting up the Connection

4 Command-Line Parameters and Exit CodesCommand-Line Parameters

It is possible to start the Smart view application with additional command-line options.

All the options listed below are not case-sensitive. All these options may also start with aslash character /, instead of a dash -.

Option Description

-noLogo This option suppresses the display of the sign-on banner (splashscreen) during the start-up phase of the application.

-file: must be an existing parameter file. Smart view thendirectly opens this file during the start-up phase.

-checkParameter A plausibility check (see 6.11 Plausibility check) is performed forthe currently loaded parameter data.

-minimize This options starts Smart view with a minimized main window.

-deviceModelFolder:

must be an existing directory. Smart view then uses thisdirectory as standard repository for device model files.

-exportCSV: Smart view creates a file in CSV-format from the currently loadedsetting data.

Example:

Smartview.exe -file:MySettings.HptPara -exportCSV:MyData.csv

-iec61850CreateSCD:

Smart view creates an IEC 61850 SCD file (Substation ConfigurationDescription) from the currently loaded setting data.

Example:

Smartview.exe -file:MySettings.HptPara -iec61850CreateSCD:MyDev.scd

-iec61850SendConfig:

must be an existing and valid IEC 61850 SCD file. Smartview sends the SCD file to the connected protection device.

Example:

Smartview.exe

-file:MySettings.HptPara

-iec61850SendConfig:MyDev.scd

-password:1234

This example command starts Smart view and makes it load theexisting parameter file MySettings.HptPara, connects to a device(with the current connection settings). Then it creates the IEC 61850configuration from the SCD file MyDev.scd and sends this configurationdata to the device.

22 Smart view SMARTV-4.70-EN-MAN

4 Command-Line Parameters and Exit Codes

Option Description

-language:

Sets the language of the graphical user interface.

must specify any of the supported languages:

ENG(English) DEU(German) ESP(Spanish) FRA(French) PLK(Polish) PTB(Portuguese [Brazil]) RUS(Russian) ROM(Romanian)

-newFile:

-deviceModel:

must be an non-existing parameter file.

must be an existing device model file. (If no path isspecified then the standard device model path is used.)

Smart view writes a new parameter file from the specified devicemodel file. The result can be checked from the application exit code.

Example:

Smartview.exe -newFile:MySettings.HptPara -deviceModel:MRA4_V3.4.a.dm_c

-paraKey:

-paraValue:

-paraSetnumber:

-paraAdaptiveSet:

is the case-sensitive internal description of theparameter to be modified.

is the new value of the parameter.

is optional and valid only for Setting GroupParameters. It can be the number of the parameter set to be used.(Possible values: 0 [default], 1, 2, 3.)

is optional and valid only for Adaptive Parameters. Itcan be the number of the adaptive set to be used. (Possible values: 0[default], 1, 2, 3.)

Smart view writes a specific parameter setting value into the currentlyloaded parameter file.

Example 1:

Smartview.exe

-newFile:MySettings.HptPara

-deviceModel:MRA4_V3.4.a.dm_c

-paraKey:"/root/MDMs/CT_1_1/SingleSet/Current/CTprim"

-paraValue:1234

-quit

23Smart viewSMARTV-4.70-EN-MAN

4 Command-Line Parameters and Exit Codes

Option DescriptionThis example command starts Smart view and makes it create a newparameter file MySettings.HptPara, then it assigns a new value 1234of a particular parameter, and finally exits.

This example parameter belongs to the setting CT pri of the nominalcurrent of the primary side of the current transformers. (In thegraphical user interface of Smart view, this setting can be found in themenu branch [Field Para / CT]. If Smart view has been launched withthe -serviceInfo option (see below), then it shows the internal for every parameter.)

Example 2:

Smartview.exe

-file:MySettings.HptPara

-paraKey:"/root/MDMs/I1/MultiSet/Fct/Char"

-paraValue:NINV

-paraSetnumber:2

-checkParameter

-saveParameter

This example command starts Smart view and opens an existingparameter file MySettings.HptPara, then it assigns a new value NINVof a particular Setting Group Parameter within the specified parameterset. Then it checks all settings for plausibility and finally saves theparameter file.

-paraListFile:

must be an existing text file that specifies parametersetting values.

Smart view reads these settings and writes them into the currentlyloaded parameter file.

The text file must contain one setting per line, and each line musthave the following format:

The specifications within each line must be separated one fromanother by a blank character. For example:

/root/MDMs/CT_1_1/SingleSet/Current/CTprim 1234 0

/root/MDMs/I1/MultiSet/Fct/Char NINV 2

In addition, comment lines are allowed: Every line that starts witheither #, ; or // is ignored.

Command-Line Example:

Smartview.exe

24 Smart view SMARTV-4.70-EN-MAN

4 Command-Line Parameters and Exit Codes

Option Description-file:MySettings.HptPara

-paraListFile:"MyParameterValues.txt"

-checkParameter

-saveParameter

This example command starts Smart view and opens an existingparameter file MySettings.HptPara, then it reads the settings fromthe file MyParameterValues.txt. Then it checks all settings forplausibility and finally saves the parameter file.

-password: is a valid access level password for the connected device.

This password is necessary to change settings on the device. Fordevices which support different access levels with different passwords,always the password of the highest required access level must begiven.

-connectionPassword:

is the connection password for the protection device.

Depending on how the protection device is connected this is either theUSB connection password or the Remote network connectionpassword.

A password for establishing a Smart view connection is supported byHighPROTEC devices as of Release 3.6.

(See Chapter 6.9.)

-quit This option makes Smart view exit immediately after it has finished allits tasks.

Example:

Smartview.exe

-newFile:MySettings.HptPara

-deviceModel:MRA4_V3.4.a.dm_c

-quit

This example command starts Smart view and makes it create a newparameter file MySettings.HptPara, then exits.

-rasConnection

-rasConnection:

Specify that the communication with the device shall be done with a(e.g. serial PPP) network connection.

If an optional is available, then this connectionis used for the communication.

Example:

Smartview -rasConnection:HighPROTEC Direct Connection

25Smart viewSMARTV-4.70-EN-MAN

4 Command-Line Parameters and Exit Codes

Option Description

-Htl3PIConnection:

Specify that the communication shall be done with a with a devicefrom the High Tech Line 3, the Professional Line or the WI Line series.

is the number of the serial COM port to which the deviceis connected.

Example:

Smartview -Htl3PIConnection:1

-receiveParameter This option makes Smart view connect to a device and receive allparameters from it.

Example:

Smartview

-receiveParameter

-saveParameter:MySettings.HptPara

-quit

This example command starts Smart view and makes it receive allparameters from the connected device, then saves these to theparameter file MySettings.HptPara, finally exits.

-saveParameter

-saveParameter:

The currently loaded parameter data is saved with the currentfilename.

If a has been specified then the parameter data is savedto the specified file.

-sendParameter

-sendParameter:modified

All the currently loaded parameter data are transferred to theconnected device, or if in case of modified only the modifiedparameters are transferred.

Example 1:

Smartview.exe

-file:MySettings.HptPara

-sendParameter

-password:1234

-silent

-quit

This example command starts Smart view and opens the parameterfile MySettings.HptPara, then all parameters contained in this file aretransferred to the connected device. Finally Smart view exits.

Example 2:

26 Smart view SMARTV-4.70-EN-MAN

4 Command-Line Parameters and Exit Codes

Option DescriptionSmartview.exe

-file:MySettings.HptPara

-paraListFile:"MyParameterValues.txt"

-checkParameter

-sendParameter:modified

-password:1234

-quit

This example command starts Smart view and opens an existingparameter file MySettings.HptPara, then it reads the settings fromthe file MyParameterValues.txt. Then it checks all settings forplausibility, it transfers the modified parameters to the connecteddevice. Finally Smart view exits.

-serviceInfo This option makes Smart view additional service information. Ingeneral, this kind of information is needed only for service and testingpurposes.

-silent This option makes Smart view avoid user interactions while executingsome its tasks. This can be helpful if particular operations shall beexecuted via command-line.

-TcpIp

-TcpIp:

Specify that the communication with the device shall be done with aTCP/IP connection.

If an optional is available, then this address is usedfor the communication.

Example:

Smartview -TcpIp:192.168.0.8

-typecode: is a valid typecode string for the currently loadedparameter data.

Example:

Smartview

-newFile:MySettings.HptPara

-deviceModel:MRA4_V3.4.a.dm_c

-typecode:MRA4-2A0AAA

-saveParameter

-quit

This example command starts Smart view, it creates a new parameterfile from the existing device model based on the specified typecode

27Smart viewSMARTV-4.70-EN-MAN

4 Command-Line Parameters and Exit Codes

Option Descriptionvalues. Then it saves this parameter modification in the parameter file,and Smart view finally exits.

Exit Codes

After one has called Smart view via command-line options it can be interesting to checkthe exit code (also called return code).

The exit code gives information about whether the Smart view execution has beensuccessful or some error has occurred.

Exit Code Description

0 Smart view has successfully exited. No error.

1 File already exists.

2 Error in device template file.

3 Implausible parameter file.

4 Unknown error.

5 Error during writing parameter file.

6 No parameter data available.

7 Error during sending parameter data to a connected device.

8 Single parameter value could not be written with specific command-line option.

9 Cannot read device template file.

10 Cannot read text file with list of parameter values.

11 Invalid typecode.

28 Smart view SMARTV-4.70-EN-MAN

4 Command-Line Parameters and Exit Codes

5 Smart view Keyboard CommandsYou can control Smart view alternatively by means of keyboard commands (instead of themouse)

Key Description

Moving up within the navigation tree or parameter list.

Moving down within the navigation tree or parameter list.

Collapse the tree item or select a folder on a higher level.

Expands the tree item or selects a subfolder.

Numpad + Expands the tree item.

Numpad Collapses the tree item.

POS1 Moves to the top of the active window.

ENDE Moves to the bottom of the active window.

STRG+O Opens the file opening dialog. Browsing through the file system for anexisting device file.

STRG+N Creates a new parameter file file by means of a template.

STRG+S Saves actual loaded parameter file.

F1 Displays the Smart view help information.

F2 Load Device Data

F5 Reloads the displayed data of a device.

STRG+F5 Enables automatic refresh.

STRG+Umschalt+T Back to the navigation window.

Home Walks through the tabular forms (detail windows).

Page Previous value (parameter setting).

Page Next value (parameter setting).

Ctrl+Shift+Alt+S Switches on/off the service info mode, which displays additionalservice information.

29Smart viewSMARTV-4.70-EN-MAN

5 Smart view Keyboard Commands

6 Operating a HighPROTEC Protection Device

6.1 Loading of Device Data when using Smart view1. Start Smart view.

2. Make sure the connection has been established properly. (See Setting up theConnection between PC and Device.)

3. Connect your PC with the device.

4. Select Receive Data from Device in menu [Device].

HPT_

ZB9

MCDGV4

MenuRecMeas

Communication

Device connectedReady

Shortcuts Device Data

Smart view

?

Operation

Device planning

Device Para

1,0

Field Para

50/60

Protection Para

765

MCDGV4OperationDevice planningDevice ParaField ParaProtection ParaControlLogicsService

FileDeviceEditViewSettingsToolsWindowHelp

Fig. 4: After you have selected Receive Data from Device, Smart view presents the full menu treeof the connected device.

30 Smart view SMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.1 Loading of Device Data when using Smart view

6.2 Transfer Device Data from Smart view to the Device

WARNING!

Via the button Transfer only modified parameters into the device only modifiedparameters are transmitted into the device.

Parameter modifications are indicated by a red star symbol in front of the parameter.

The star symbol (in the device tree window) indicates that parameters in the opened file(within Smart view) differ from parameters stored on your local hard disk.

Via the button Transfer only modified parameters into the device, you can transmit allparameters that are marked by this symbol.

If a parameter file is saved on your local hard drive, these parameters are no longerclassified to be modified and cannot be transmitted via the button Transfer only modifiedparameters into the device.

In case that you have loaded and modified a parameter file from the device and saved itto your local hard drive without transferring the parameters into the device beforehand,you cannot use the button Transfer only modified parameters into the device. In a caselike that, use Transfer all parameters into the device.

NOTICE!

The button Transfer only modified parameters into the device only works if modifiedparameters are available in the Smart view.

In contrast to that, all parameters of the device are transferred when the button Transferall parameters into the device is pressed (unless there are invalid or implausible deviceparameters, see 6.11 Change a Parameter via Smart view Example).

1. In order to (re-)transfer parameters into the device, please select either Transfer allparameters into the device or Transfer only modified parameters into thedevice in menu [Device].

2. Confirm the safety inquiry Shall the parameters be overwritten into the device?.

3. Enter the password for setting parameters in the popup window.

Thereafter the changed data is transferred to the device and adopted.

4. Confirm the inquiry Parameters successfully updated. It is recommended to savethe parameters into a local file on your hard drive. Shall The Data Be Saved Locally? with Yes (recommended). Select a suitable folder on your hard disk.

5. Confirm the chosen folder by clicking Save.

The changed parameter data is now saved in the folder chosen by you.

Error Message: Invalid Device Type

31Smart viewSMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.2 Transfer Device Data from Smart view to the Device

NOTICE!

In order to be able to transmit a parameter file into the device the following data must beequal:

Type Code (written on the top of the device/type label) and Version of the device model (can be found at [Device Para / Version] DM-Version.

In case of a non-matching device type the error message Invalid Device Type is issued.

32 Smart view SMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.2 Transfer Device Data from Smart view to the Device

6.3 Backup and Documentation when using Smart viewHow to Save Device Data on a PC

1. Click on Save as ... in menu [File].

2. Specify a name and choose a folder on your hard disk.

3. Save the device data accordingly.

Printing of Device Data when using Smart view (Setting List)

The Printing menu offers the following options:

Printer setting

Page preview

Printing

Export the selected printing range into a txt-file.

The printing menu of the Smart view software offers contextual different types of printingranges.

Printing of the complete parameter tree:All values and parameters of the presentparameter file are printed.

Printing of the displayed working window:

Only the data shown on the relevant working window are printed, i.e. this applies, ifat least one window is opened.

Printing of all opened working windows:

The data shown on all windows are printed, i.e. this applies only if more than onewindow is opened.

Printing of the device parameter tree as from a shown position on:

All data and parameters of the device parameter tree are printed as from theposition/marking in the navigation window. Below this selection the complete nameof the marking is additionally displayed.

Saving Data as a txt-file via Smart view

Within the print menu [File / Print] you can choose Export into File in order to export thedevice data into a text-file.

NOTICE!

Only the actual selected printing range will be exported into a text-file. That means: If youhave chosen the Complete device parameter tree then the Complete device parametertree will be exported. But, if you have chosen Actual working window, only this windowwill be exported.

You can print out operating data but not export them.

33Smart viewSMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.3 Backup and Documentation when using Smart view

If you export a txt-file, the content of this file is encoded as Unicode (UTF8). Thereforethe application that you want to use to open the file must support this encoding. (This,however, should be the case with all modern PC applications.)

34 Smart view SMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.3 Backup and Documentation when using Smart view

6.4 Offline Device Planning via Smart view

NOTICE!

In order to be able to transmit a parameter file (e.g. offline created) into the device thefollowing data must be equal:

Type Code (written on the top of the device/type label) and Version of the device model (can be found at [Device Para / Version] DM-Version.

The Smart view software enables also to parameterize offline. The advantage is: By usingdevice models you can do planning jobs for a device and set parameters in advance.

You can also read the parameter file out of the device, further process it offline (e.g. fromyour office) and finally re-transfer it to the device.

You can either:

load an existing parameter file from a device (see Loading of Device Data whenusing Smart view).

create a new parameter file (see below),

open a locally saved parameter file (backup).

In order to create a new device/parameter file by way of a device template offline:

1. In order to create a new offline parameter file please choose within the menu [File]the entry Create new parameter file.

2. A dialog window pops up. Please make sure that you select the right device typewith the correct version and configuration.

3. Finally click on Apply.

4. In order to save the device configuration select Save out of the [File] menu.

5. Within the menu [Edit / Modify Device Configuration (Typecode)] you can modify thedevice configuration or simply find out the type code of your current selection.

For the transfer of the parameter file into a device, see Transfer Device Data fromSmart view to the Device.

35Smart viewSMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.4 Offline Device Planning via Smart view

6.5 Measuring ValuesRead out of Measured Values via Smart view

1. In case Smart view is not running please start it.

2. If the device data were not yet loaded select Receive Data from Device frommenu [Device].

3. Double click on icon Operation in the navigation tree.

4. Double click on icon Measured Values within the navigation tree [Operation].

5. Within the Measured Values, double click the category of measured values thatyou are interested in.

The measured and calculated values are shown now in tabular form on thewindow.

NOTICE!

To have the measuring data read in a cyclic manner, select Auto refresh in menu[View]. The measured values are read out about every two seconds.

36 Smart view SMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.5 Measuring Values

6.6 Acknowledgments and ResetsManual Acknowledgment via Smart view

1. In case Smart view is not running please start it.

2. If the device data were not yet loaded select Receive Data from Device frommenu [Device].

3. Double click on icon Operation in the navigation tree.

4. Double click on icon Acknowledgement within the operation menu.

5. Double click the entry within the popup that is to be acknowledged.

6. Press the button Execute immediately.

7. Confirm the question if the changes should be executed by Yes.

8. Enter your password.

External Acknowledge via Smart view

1. In case Smart view is not running please start it.

2. If the device data were not yet loaded select Receive Data from Device frommenu [Device].

3. Double click on icon Device Para in the navigation tree.

4. Double click on icon Ex Acknowledge within the operation menu.

5. In the dialog window, you can assign now each one signal that resets allacknowledgeable LEDs, a signal that resets all binary outputs, a signal that resetsthe SCADA-signals respectively a signal that acknowledges a pending trip command.

Manual Resets via Smart view

1. In case Smart view is not running please start it.

2. If the device data were not yet loaded select Receive Data from Device frommenu [Device].

3. Double click the Operation icon in the navigation tree.

4. Double click the icon Reset within the menu [Operation].

5. Double click the entry within the popup that is to be reset or deleted.

37Smart viewSMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.6 Acknowledgments and Resets

6.7 Status Display via Smart view1. In case Smart view is not running please start it.

2. If the device data were not yet loaded select Receive Data from Device frommenu [Device].

3. Double click the Operation icon in the navigation tree.

4. Double click the icon Status Display within the menu [Operation].

5. Double-click on any of the subordinated modules. If, for example, you want to seethe states of general alarms, double-click on the entry Prot.

NOTICE!

To have the data read in a cyclic manner, select Auto refresh in menu [View]. Themeasured values are read out about every two seconds.

Signal State / Module Input Display within Smart view

false / 0 0

true / 1 1

No connection to the device or busy. ?

38 Smart view SMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.7 Status Display via Smart view

6.8 Recorders

6.8.1 Disturbance Recorder

Disturbance records / DataVisualizer

With the tool DataVisualizer it is possible to visualize the disturbance records of thedevice. The DataVisualizer is always installed along with Smart view.

Disturbance records can be downloaded (read out) by means of the parametersetting and evaluation software Smart view.

The disturbance records can be viewed and analyzed within DataVisualizer.

Disturbance records can be converted into the COMTRADE file format by means ofDataVisualizer.

A disturbance record contains measuring values inclusively some (configured) pre-trigger-time. By means of Smart view / DataVisualizer the oscillographic curves of the analog(current, voltage) and digital channels/traces can be shown and evaluated in a graphicalform. The disturbance recorder has a storage capacity of 120 s. The disturbance recorderis able to record up to 15 s (adjustable) per record. The amount of records depends on thesize of each record.

Check Disturbance Records via Smart view

1. In case Smart view is not running please start it.

2. If the device data were not yet loaded select Receive Data from Device frommenu [Device].

3. Double click the Operation icon in the navigation tree.

4. Navigate to the menu branch [Operation / Recorders] and double-click on Disturbrec.

In the window the disturbance records are shown in tabular form.

5. Double-click any disturbance record and choose a folder where it is to be saved to.

6. You can analyze the disturbance records using the software DataVisualizer afterclicking on Yes when you are asked Shall the received disturbance record beopened by the DataVisualizer?

Delete Disturbance Records via Smart view

1. In case Smart view is not running please start it.

2. If the device data were not yet loaded select Receive Data from Device frommenu [Device].

3. Double click the Operation icon in the navigation tree.

4. Navigate to the menu branch [Operation / Recorders] and double-click on Disturbrec.

In the window the disturbance records are shown in tabular form.

39Smart viewSMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.8 Recorders

5. In order to delete a disturbance record double-click on: (the red x) in front of thedisturbance record and confirm.

6.8.2 Fault Recorder

Check Fault Records via Smart view

1. In case Smart view is not running please start it.

2. If the device data were not yet loaded select Receive Data from Device frommenu [Device].

3. Double click the Operation icon in the navigation tree.

4. Navigate to the menu branch [Operation / Recorders] and double-click on Faultrec.

In the window the fault records are shown in tabular form.

5. In order to see more detailed information on a fault, double-click the item in the list.

Via the print menu you can export the data into a file. Please proceed as follows:

1. Open the data as described above.

2. Press the button Print.

3. Press the button Export to File.

4. Enter a file name.

5. Choose a location where to save the file.

6. Press the button Save.

6.8.3 Trend Recorder

Trend Recorder

The Trend Data are data points stored by the Trend Recorder on the relay device overfixed intervals of time, and can be downloaded from the device using Smart view. A TrendRecord is viewable using the Data Visualizer software by selecting files saved by Smartview with a file extension of . HptTr.

The list of available trend recorder data is viewable by selecting [Operation / Recorders /Trend rec].

When viewed within the DataVisualizer, the trend record will show the observed values(up to 10) that the user has specified. The values available in the Trend Recorder dependon the type of the connected device and the configuration of the Trend Recorder.

Managing Trend Records

To download information from the Trend Recorder, select [Operation / Recorders / Trendrec] from the menu tree. The user will find three options within the Trend Recorderwindow that will allow to:

Receive Trend Records,

40 Smart view SMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.8 Recorders

Refresh the Trend Recorder, and

Delete Trend Records.

Selecting the Receive Trend Record button will download data from the relay to theuser's PC. By selecting the Refresh Trend Recorder, Smart view updates the list of TrendRecords. The Delete Trend Records button removes all trend data from the relay. TrendRecorder data previously stored on the user's PC remains untouched.

After having received trend data from the device, the user can view the data in theDataVisualizer by double-clicking on the received .HptTr file stored on the PC. Oncethe .HptTr file is open, the user will see the Analog Channels that are monitored bythe Trend Recorder. By clicking on the Analog Channels, all monitored parameters arelisted. To view a channel, the user must click on the left mouse key, then drag and dropthe channel onto the right-hand side of the DataVisualizer screen. The channel is thenlisted under the Displayed Channels.

To remove a channel from view, the user must select the Trend Data to be removed inthe Displayed Channels menu tree, then click on the right mouse button to bring up themenu options. Here, the user finds the Remove menu option that, when selected,removes the trend data.

6.8.4 Event Recorder

Check Event Records via Smart view

1. In case Smart view is not running please start it.

2. If the device data were not yet loaded select Receive Data from Device frommenu [Device].

3. Double click the Operation icon in the navigation tree.

4. Navigate to the menu branch [Operation / Recorders] and double-click on Eventrec.

In the window the event records are shown in tabular form.

NOTICE!

To have the event data read in a cyclic manner, select Auto refresh in menu [View].

Smart view is able to record more events than the device itself, if the window of the eventrecorder is opened and Automatic Up-Date is set to active.

Via the print menu you can export the data into a file. Please proceed as follows:

1. Open the data as described above.

2. Select the menu [File / Print].

3. Choose Print Actual Working Window within the popup.

4. Press the button Print.

5. Press the Export to File button.

6. Enter a file name.

41Smart viewSMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.8 Recorders

7. Choose a location where to save the file.

8. Press the button Save.

42 Smart view SMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.8 Recorders

6.8.5 Motor Start Recorder

Manage Motor Start Records

The Motor Start Recorder logs information during a motor start-up. These records arestored in a fail-safe manner and the capacity allows for recording up to 5 start-ups. After5 start-ups, every following start-up overwrites the recording of the oldest one (First inFirst out principle).

Every recording consists of a summary of information and recorded analog trends.However, the exact set of data is dependent on the ordered device variant. The summarydata can be accessed using Smart view or via the front panel interface. This featureprovides information recorded at the time of each start of the motor such as:

Date of the motor start event

Record number

IL1 max RMS, IL2 max RMS, IL3 max RMS, IG max RMS Maximum RMS phasecurrent of the respective phase

Unbalance max Maximum current unbalance during the motor start-up

I avg Average current of all three phases at the time of the start-to-run transition

Speed The motor nominal speed (1 or 2)

Time (duration) values:

tS-tI The time that elapses from the start until the current value drops belowthe set start-up threshold

tS-tR The time that elapses from the start until the motor is running, or incase of an incomplete start sequence until the trip command

I2T used Thermal capacity used, specified as percentage of the maximum thermalcapacity

Start success This is set to 1 if the motor start has been successful (and equals 0otherwise).

Smart view allows for storing the summary information as text files, or have them printedout.

The analog trends can be viewed using the DataVisualizer software. Examples forrecorded analog trends are:

Phase current values

Current unbalance

Thermal capacity

Temperatures (in case an RTD box is fitted)

Read Motor Start Records via Smart view:

The start recorder data can be downloaded by means of Smart view from the device.

Start Smart view if this has not been done already.

43Smart viewSMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.8 Recorders

If the data has not been downloaded from the device yet, select the menu itemReceive Start Recorder in the Device menu.

Within the navigation tree, go to the [Operation / Recorders] menu. Here the userwill find the Start rec menu item.

When Start rec is selected the Start Recorder Window appears.

To access data that has been stored in the device using Smart view, the user must select theReceive Start Recorder button in the upper left hand corner of the Start Rec window. Whenclicked, the Smart view software will retrieve the highlighted record from the device.

After selecting one of the max. 5 recordings a summary of the Start Recorder data can beretrieved (for the selected recording) by clicking the Receive Summary Data button in theupper left hand corner of the Start Rec window.

A list of all currently available Start Records is viewable by selecting the Refresh StartRecorder button on the start recorder.

It is possible to delete individual records that are stored on the protective device. First, selectReceive Start Recorder, and then select the record to be deleted by clicking on the recordnumber, followed by the selection of the Delete Start Record button in the upper left handcorner of the Start Rec window.

To permanently remove all start records within a device's start recorder, select the Delete AllStart Records button also located in the upper left hand corner of the Start Rec window.This removes all previously stored start records within the device to which the user ispresently connected.

Open a Start Record file from a local storage device. Please note that it is possible to comparean archived Start Record against archived Parameter settings that are also stored on a localdevice. Read the Caution information below (page 6).

When using Smart view to view the Start Recorder data, the Start Recorder features canalso be found by right clicking anywhere within the Start Rec window.

NOTICE!

The Print button takes the user to the printing dialogue, where it is possible to exportthe summary into a text file. This is done the following way:

Retrieve the data in the Start Rec window, as described above. Click on the button Receive Summary Data. Click on the Print button. Click on the button Export to file. Enter a valid file name. Select the file path. Click on the Save button.

Display Start Records:

When a Start Record is called up, a window with the following options pops up.

44 Smart view SMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.8 Recorders

View motor start data graphically in the DataVisualizer software. In theDataVisualizer software the user can view the RMS value of the phase currents,thermal capacity used, and temperatures measured by the URTD module if a URTDis installed and attached to the relay.

View motor start data overlayed with the Motor Protection Curves (Starting ProfilePlot versus Protection limits). The user can view the average current recordedduring the motor start versus protection elements such as 50P, or the ThermalModel. The user has the option to alter the displayed setting groups.

Please note: Protective elements that are not projected within the device planningare not visible.

The Starting Profile Plot offers two user scenarios:

Adapt the protection settings to the recorded start curve: The user then sees theimpact of parameter changes in the Profile Plot. By means of this the user candecide if the relay settings match the protection requirements.

Analyze a Start Record: Since a Start Record does not include the relay settings, theuser has to ensure that backups of the relay settings are available that were valid atthe time of recording.

CAUTION!

Please note that the Starting Profile Plot shows the recorded average current versus thecurrent relay settings. The relay settings itself are not part of a Start Record.

Adaptive parameters and their impacts wont be visible within the Starting Profile.

Blockings wont be visible within the Starting Profile.

Please make sure to save the setting files together with this record to guarantee thegraph represents the conditions of when this event occurred.

45Smart viewSMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.8 Recorders

6.8.6 Statistic Recorder

The Statistic Recorder shows motor specific statistical data on a monthly base. TheStatistic Recorder can record up to 24 monthly reports. The reports are power fail safestored.

In order to view information from the Statistic Recorder, the user has to select[Operation / Recorders / Statistic rec] from the menu tree.

When using Smart view, a double-click on the Date of Record shows detailed statisticalinformation such as the number of starts, the number of successful starts, the averagestart time, the average I2T value during any start, and the average of all maximumcurrents value seen during each start.

6.8.7 Internal Messages (Self-Supervision Recorder)

Check Self-Supervision Messages via Smart view

NOTICE!

This feature is available only when connecting with a recent HighPROTEC protectiondevice (as of version 3.4).

The protection device supervises its own functionality by constantly performing variousself-tests. If it detects any serious problem, or any event that has a serious impact on theoperation of the device then this event is recorded.

HighPROTEC protection devices as of version 3.6 use this recorder also for security-related messages, for example to report a problem with the encrypted communication orif a wrong password has been entered.

The menu [Operation / Self-Supervision / Messages] gives access to this list of internalmessages. The following data is part of each entry:

Record Number a counter without special meaning

Date of Record timestamp of the event

Message a message ID with a (short, heavily abbreviated) message text

Value additional data specific to the event

All messages that can potentially appear here are described in detail in a separatedocument, the HighPROTEC Troubleshooting Guide (HPT4.70ENTSG).

46 Smart view SMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.8 Recorders

6.9 PasswordsIn general, there are access level passwords, that permit to change the setting values ofrelated parameters, and connection passwords, that permit to establish a connection ofthe Smart view with the operating software Smart view.

Note, however, that connection passwords are always prompted for by Smart view, i.e.they are always entered via PC keyboard. (See the Security chapter of the TechnicalManual of your HighPROTEC device for a detailed description.)

Entering wrong passwords (regardless whether connection password or access levelpassword, and regardless whether via HMI or Smart view) triggers a time penalty stage:The Smart view blocks any further password entry for an increasing amount of time, untila correct password has been entered. A dedicated message informs the user about this

blocking. This timer affects only the password entry (i.e. the Softkey on the HMI),so that it does not prevent the user from doing some other, password-free activitiesduring this blocking time.

Change Passwords via Smart view

Download the parameter file from the device.

1. Passwords can be changed by a double-click within the menu [Device Para /Security / Password] on the corresponding password.

2. Enter the old password and the new password twice.

3. Confirm the changes by a click on OK.

47Smart viewSMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.9 Passwords

6.10 Device PlanningDevice Planning means to change the functional range to a degree that suits theprotection task to be fulfilled (i.e.: the device deactivates all functions that are notneeded, and shows only the active ones).

There is a top-level menu item [Device planning] that is dedicated to this; it collects asetting parameter for each function which can be set to - or to use. (In some casesthere are additional setting options, for example with devices featuring directiondetermination).

If the user, for example, activates the voltage protection function, all menu branchesrelated to this function appear in the menu tree. All corresponding events, signals, etc.,are activated as well.

WARNING!

It MUST be taken into account that Device Planning changes the functionality of thedevice.

If, for example, the user cancels the directional feature of the overcurrent protections, thedevice will no longer trip in a directional way but merely in a non-directional way. If theuser deactivates a protection function, the device will no longer trip according to thecriteria related to this protection function.

The manufacturer does not accept liability for any personal or material damage as aresult of incorrect planning.

Contact your Woodward Customer Service representative for more information.

WARNING!

Beware of the inadvertent deactivating of protective functions/modules, because all thesettings of a deativated module get lost (i.e. are set back to their respective defaultvalues)!

This means: If the user is activating any of these modules again at some later time, allparameters of the re-activated modules need to be reconfigured.

48 Smart view SMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.10 Device Planning

6.11 ParametersParameter Setting via Smart view

Smart view shows within the windows, where parameters are edited also the requiredaccess level for the parameters and settings. The required access authorizations will beverified when the parameter file should be transferred into the protective device. For thetransmission, two options are available.

The transfer of all Parameters. This always requires the Supervisor (administrator)password.

The transfer of the modified Parameters only. Smart view checks the set of accesslevels that are required by the parameter to be modified, and it prompts for thehighest required passwords (access authorizations).

Example 1:

A Prot-Lv1 parameter and a Prot-Lv2 parameter have been edited and are about tobe transferred. The user is being prompted for the password Prot-Lv2.

Example 2:

A Prot-Lv1 parameter, a Prot-Lv2 parameter and a device planning parameter havebeen edited and are about to be transferred. The user is being prompted for theadministrator password Supervisor-Lv3.

Example 3:

A Prot-Lv1 parameter, a Prot-Lv2 parameter and a Control-Lv1 parameter havebeen edited and are about to be transferred. The user is being prompted for the twopasswords Prot-Lv2 and Control-Lv1.

Change a Parameter via Smart view Example

Example: Changing of a protective parameter. (We want to alter the characteristic for theovercurrent protection function I[1] in parameter set 1).

1. In case Smart view is not running please start it.

2. If the device data were not yet loaded select Receive Data from Device frommenu [Device].

3. Double-click the icon Protection Para in the navigation tree.

4. Within the [Protection Para] menu, double-click the icon Set 1.

5. Within the parameter set 1, double-click I-Prot.

6. Double-click I[1].

In the dialog window a tabulated overview appears, showing the parametersassigned to this protective function.

7. In this table double-click the value/parameter you want to change (here: Char).

8. An editing dialog window is opened where you can select the required characteristic.

9. Close this window by clicking the OK button.

10. Additional parameters can be changed if required.

49Smart viewSMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.11 Parameters

11. There are two options available within the menu [device]: Transfer all parameters tothe device, or only the modified ones. See Transfer Device Data from Smartview to the Device.

12. Confirm the safety inquiry Shall The Parameters Be Overwritten?.

13. Enter all the passwords that you are prompted for.

Afterwards the parameters are transferred to the protection device.

14. We recommend to confirm the inquiry Shall The Data Be Saved Locally? with Yes.

Select a suitable storing location on your hard disk.

Confirm the chosen storing location by clicking Save.

The changed parameter data is saved now in the data file chosen by you.Thereafter the changed data is transferred to the device and adopted.

NOTICE!

A star (asterisk) symbol in front of the changed parameters indicates that the alterationshave not yet been stored in a parameter file. This is independent of whether theparameters have been transferred to the device in the meantime.

In order to make things easier to follow, especially where complex parameter changes areinvolved, the menu tree indicates the parameter change by the star symbol on everysuperior/higher menu level, too (star trace). This makes it possible to control or followup from the main menu level at any time where parameter changes have been made butnot been saved yet.

The star trace is cleared only if the parameter changes are saved in a parameter file, orif all device data is reloaded from the device.

NOTICE!

Once you have entered a password, Smart view remembers it for ca. 10 minutes so thatyou are not asked again during this time. This time interval is re-started wheneverparameters are transmitted into the device. If no parameters are transmitted into thedevice for a duration of more than 10 minutes, Smart view clears its password memory sothat you are asked again when you are trying to transmit parameters into the device.

50 Smart view SMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.11 Parameters

Plausibility check

NOTICE!

In order to prevent obvious wrong settings the software monitors constantly all temporarysaved parameter changes. If it detects an implausibility, this is indicated by a questionmark in front of the respective parameter.

In order to make things easier to follow up, especially where complex parameter changesare involved, on every superior/higher menu level above of the temporary savedparameters, an implausibility is indicated by a question mark (plausibility trace). Thismakes it possible to control or follow from the main menu level at any time whereimplausibilities exist.

So it is possible to see from each point of the menu tree that implausibilities have beendetected by the software.

A star/parameter change indication is always overwritten by the question mark/implausibility symbol.

If the software detects an implausibility it rejects saving and adopting of the parameters.

Switch Setting Groups (Parameter Sets) via Smart view

1. In case Smart view is not running please start it.

2. If the device data were not yet loaded select Receive Data from Device frommenu [Device].

3. Double-click the icon Protection Para in the navigation tree.

4. Within the [Protection Para] menu, double-click the icon PSet-Switch.

5. Configure the Setting Group Switch respectively choose an active set manually.

Copying Setting Groups (Parameter Sets) via Smart view

NOTICE!

Setting groups can only be copied if there are no implausibilities (no red question mark,see the Notice at the end of 6.11 Change a Parameter via Smart view Example).

It is not necessary to set up two setting groups that only differ in a few parameters.

With the help of Smart view you can copy simply an existing setting group to anotherone(not yet configured) . You only need to change those parameters where the twosetting groups are different.

To establish efficiently a second parameter set where only a few parameters are different,proceed as follows:

1. In case Smart view is not running please start it.

2. Open an (offline) parameter file of a device or load data of a connected device.

3. By way of precaution, save (the relevant) device parameters: [File / Save as]

51Smart viewSMARTV-4.70-EN-MAN

6 Operating a HighPROTEC Protection Device6.11 Parameters

4. Select Copy Parameter Sets out of the menu [Edit].

5. Define the source and destination parameter set for copying (source = copy from;destination: copy to).

6. Click on OK to start copy procedure.

The copied parameter set is cached now, but not yet saved.

7. Then modify the copied parameter set(s) as required.

8. Assign a new file name to the revised device parameter file and save it on your harddisk (backup copy).

9. Transfer the modified parameters back to the device (see Transfer Device Datafrom Smart view to the Device.)

Compare Setting Groups via Smart view

1. In case Smart view is not running please start it.