2 2 2 4 4 4 0 0 0 2 2 2 L L L O O O G G G I I I C C C C C C O O O N N N T T T R R R O O O L L L L L L E E E R R R C C C O O O M M M B B B U U U S S S T T T I I I B B B L L L E E E G G G A A A S S S D D D E E E T T T E E E C C C T T T O O O R R R S S S 2 2 2 I I I N N N P P P U U U T T T C C C H H H A A A N N N N N N E E E L L L S S S 0 0 0 ÷ ÷ ÷ 2 2 2 2 2 2 M M M A A A The 2402 Combustible Gas Controller, for FG/ESD 2400 System, has been designed to interface with the majority of 0÷22mA Combustible Gas Transmitters or SMART Sensor family using 2, 3 or 4 wire connections. This card provides two isolated analogue channels showing the combustible gas level (in L.E.L. percentage) on two digital displays, used also for other service codes. All these information’s are converted in digital format and transmitted to the 2401-CPU Facility module. The 0÷22mA analogue input channels coming from Transmitters or Smart Sensors are connected to the input circuits (isolated amplifier) and they’re converted from voltage levels to digital values through an A/D converter (12 bit resolution) which writes digital data on the bus of the 8 bit microprocessor. The detected gas level is displayed on the digital displays, but on the front panel there are also double LED’s for the status of each channel (Ready, Fault, Warning and Alarm condition). Each information is written by the microprocessor on the input table, which is regularly inquired by the 2401-CPU Facility module, using the proprietary communication software, through a high speed RS 485 serial line. The Warning and Alarm set points are stored on the 2401-CPU Facility module by the Programming Software and during the system start-up are transferred to the 2402 card. Each analogue channel is automatically tested by the microprocessor using a diagnostic routine in order to check the correct operation of the analogue and digital logic circuits. This diagnostic procedure is performed by forcing alternatively each analogue circuit using a pre- fixed current which is read and compared with some programmed values, simulating the presence of combustible gas. In case of discrepancy, the microprocessor will detect it, displaying the Fault state and sending a Fault message to the 2401-CPU Facility module. Furthermore, to assure the correct functionality of the card a Watchdog (WD) timer circuit provides the monitoring of the card operation via a digital output. This is performed during the same diagnostic software routine by the microprocessor. The Watchdog Circuit State is displayed with front panel LED’s and available on a normally Energised (N.E.) relay with SPDT contacts (on the I/O connector). In case of a microprocessor failure, the Watchdog will turn to Alarm condition, switching off the front panel LED’s and will de-active the relay. The front card panel is composed by two displays (with 2 digits each); some double LED’s for the indication of Ready, Warning, Alarm and Fault status for each channel; serial line LED’s which display the communication condition between the 2402 card and the system; a double LED which displays the WatchDog condition; some push buttons for the execution of local commands. These push buttons permit the execution of the following actions: SEL Input channel selection INH Inhibition of the selected channel SET View set point of Warning and Alarm of selected channel TEST Activation of the an auto-test card function and front Lamp test The frontal push buttons can be used only if they were activated by the Facility 2401 module. A particular feature of this card is that it can be easily checked while powered, without affecting its normal operation and specially the system integrity. To perform all the maintenance operations the cards is provided a front connector, for the connection of the Hand Held Monitor (2490 HHM). Using the Hand Held Monitor is possible to read the set point values, read the L.E.L. level and is also possible to force the analogue inputs, in order to test the application software and logic’s. 8 (Eight) auxiliary Open Collector outputs (Max 100mA @ 30Vdc) are available on the I/O connector for the connection of relays, LED’s, or other notification devices. These O.C. outputs are activated by microprocessor following the programmed instructions, related the channels status. Card with appropriate firmware to operate the condition FAIL-TO-SAFE in case of communication or CPU failures through the Open Collector output . I
Transcript
  • 222444000222 LLLOOOGGGIIICCC CCCOOONNNTTTRRROOOLLLLLLEEERRR

    CCCOOOMMMBBBUUUSSSTTTIIIBBBLLLEEE GGGAAASSS DDDEEETTTEEECCCTTTOOORRRSSS 222 IIINNNPPPUUUTTT CCCHHHAAANNNNNNEEELLLSSS 000÷÷÷222222MMMAAA

    The 2402 Combustible Gas Controller, for FG/ESD 2400 System, has been designed to interface with the majority of 0÷22mA Combustible Gas Transmitters or SMART Sensor family using 2, 3 or 4 wire connections. This card provides two isolated analogue channels showing the combustible gas level (in L.E.L. percentage) on two digital displays, used also for other service codes. All these information’s are converted in digital format and transmitted to the 2401-CPU Facility module. The 0÷22mA analogue input channels coming from Transmitters or Smart Sensors are connected to the input circuits (isolated amplifier) and they’re converted from voltage levels to digital values through an A/D converter (12 bit resolution) which writes digital data on the bus of the 8 bit microprocessor. The detected gas level is displayed on the digital displays, but on the front panel there are also double LED’s for the status of each channel (Ready, Fault, Warning and Alarm condition). Each information is written by the microprocessor on the input table, which is regularly inquired by the 2401-CPU Facility module, using the proprietary communication software, through a high speed RS 485 serial line. The Warning and Alarm set points are stored on the 2401-CPU Facility module by the Programming Software and during the system start-up are transferred to the 2402 card. Each analogue channel is automatically tested by the microprocessor using a diagnostic routine in order to check the correct operation of the analogue and digital logic circuits. This diagnostic procedure is performed by forcing alternatively each analogue circuit using a pre-fixed current which is read and compared with some programmed values, simulating the presence of combustible gas. In case of discrepancy, the microprocessor will detect it, displaying the Fault state and sending a Fault message to the 2401-CPU Facility module. Furthermore, to assure the correct functionality of the card a Watchdog (WD) timer circuit provides the monitoring of the card operation via a digital output. This is performed during the same diagnostic software routine by the microprocessor. The Watchdog Circuit State is displayed with front panel LED’s and available on a normally Energised (N.E.) relay with SPDT contacts (on the I/O connector). In case of a microprocessor failure, the Watchdog will turn to Alarm condition, switching off the front panel LED’s and will de-active the relay. The front card panel is composed by two displays (with 2 digits each); some double LED’s for the indication of Ready, Warning, Alarm and Fault status for each channel; serial line LED’s which display the communication condition between the 2402 card and the system; a double LED which displays the WatchDog condition; some push buttons for the execution of local commands. These push buttons permit the execution of the following actions: SEL → Input channel selection INH → Inhibition of the selected channel SET → View set point of Warning and Alarm of selected channel TEST → Activation of the an auto-test card function and front Lamp test The frontal push buttons can be used only if they were activated by the Facility 2401 module. A particular feature of this card is that it can be easily checked while powered, without affecting its normal operation and specially the system integrity. To perform all the maintenance operations the cards is provided a front connector, for the connection of the Hand Held Monitor (2490 HHM). Using the Hand Held Monitor is possible to read the set point values, read the L.E.L. level and is also possible to force the analogue inputs, in order to test the application software and logic’s. 8 (Eight) auxiliary Open Collector outputs (Max 100mA @ 30Vdc) are available on the I/O connector for the connection of relays, LED’s, or other notification devices. These O.C. outputs are activated by microprocessor following the programmed instructions, related the channels status. Card with appropriate firmware to operate the condition FAIL-TO-SAFE in case of communication or CPU failures through the Open Collector output .

    I

  • 222444000222 LLLOOOGGGIIICCC CCCOOONNNTTTRRROOOLLLLLLEEERRR CCCOOOMMMBBBUUUSSSTTTIIIBBBLLLEEE GGGAAASSS DDDEEETTTEEECCCTTTOOORRRSSS

    222 IIINNNPPPUUUTTT CCCHHHAAANNNNNNEEELLLSSS 000÷÷÷222222MMMAAA TECHNICAL DATA

    Power Supply (Line Isolated ISO) : 24 VDC Nom. (20÷30VDC) Power Supply (Line I/O) : 24 VDC Nom. (20÷30VDC) Power Consumption 24Vdc ISO : 3,5 W Max in Alarm condition Power Consumption 24Vdc I/O : 1,4 W Max without Detectors and Loads Isolation : 1500 Volts RMS between (I/O) and (ISO) Channel per Module : 2 with differential inputs Input Impedance : 47,5 Ohm Resolution A/D Converter : 12 bit Range Signal Input Current : 0÷22 mA Fault : 0÷3,4 mA Calibration : 1,5÷2,5 mA (Priority on Fault) Measuring Sensor Drift : 3,5÷3,9 mA Measuring 0÷100% LEL : 4÷20 mA Over-range : 20÷22 mA Channel 1 | Channel 2 Alarm : OC1 Max. 0,1A @ 30VDC | Alarm : OC5 Max. 0,1A @ 30VDC Warning : OC2 Max. 0,1A @ 30VDC | Warning : OC6 Max. 0,1A @ 30VDC Fault : OC3 Max. 0,1A @ 30VDC | Fault : OC7 Max. 0,1A @ 30VDC Fail to safe or : OC4 Max. 0,1A @ 30VDC | Fail to safe or : OC8 Max. 0,1A @ 30VDC Calibration | Calibration Watchdog : K1 Relay Energized, SPST Max. - 1A @ 30VDC - 0,3A @ 125/250VAC – Communication lines : 2 lines RS-485 Full-Duplex in Redundant mode Operating Temperature : 0°C ÷ 70°C (+32°F ÷ +158°F) Storage Temperature : -40°C ÷ 85°C (-40°F ÷ +185°F) Humidity : 0 ÷ 95% non-condensing Weight : 440 gr.

    SYSTEM STANDARDS CONFORM

    - CE marked according to CEE directive - 89/336 CEE EMC - 93/68 CEE LVD - - EMC certification according to EN61000-6-4 Level 4 (+/-4KV) - Radiated Conducted Emission certification according to IEC 1000-4-4 - Conducted Susceptibility, Fast Transient/Burst certification according to EN 50082-2, EN 61000-6-2 - Conform EN-54 EN-61508 (SIL2)

    ORDERING INFORMATION

    2401 Master → code 034560 2402 HC Gas 0÷22mA → code 034561 SMART S-500.54 HC → code 135012 2401 Slave → code 034560 2403 HC Gas Pellistor → code 034619 SMART S-500.90 IR → code 135312 2400 SW PLC Program → code ............ 2404 TX Gas 0÷22mA → code 034562 Remote Red J.Box S-500→ code 112320 2490 Hand Held Monitor → code 034571 2407 OX Gas 0÷22mA → code 034563 2405 Addr. Digital Display → code 034601 2408 Flame 0÷22mA → code 034564 Connector 32DZ → code 026026 2405C Addr. Digital Display → code 034599 2411 Digital Inputs → code 034566 Blank Panel 5TE → code 080555 2406 Addressable Loop Contr. → code 034629 2420 Supervised Outputs → code 034567 * Master Rack 19” → code 081043 2409 Conventional Loop Cont. → code 034565 2422 Digital Outputs → code 034568 **Exp. Rack 19” → code 081045 * Master Rack Include BUS-2480 & BUS-2481 on Rack 19” with N°12 I/O slots (like 2402) N°2 CPU-2401 slots ** Expansion Rack Include BUS-2480 on rack 19” with N°16 I/O slots (like 2402) . OVERVIEW FG-ESD-2400

    II

  • 222444000222 LLLOOOGGGIIICCC CCCOOONNNTTTRRROOOLLLLLLEEERRR CCCOOOMMMBBBUUUSSSTTTIIIBBBLLLEEE GGGAAASSS DDDEEETTTEEECCCTTTOOORRRSSS

    222 IIINNNPPPUUUTTT CCCHHHAAANNNNNNEEELLLSSS 000÷÷÷222222MMMAAA

    LOGIC DIAGRAM CONNECTION

    CONNECTOR REAR SIDE For connection to Sensor use Shielded cable with 3 core conductors

    Core Section and Cables Length mm2 AWG Meters Feet

    2.5 14 1372 4500 1.5 16 685 2250 1 18 488 1600

    2490 Hand Held Monitor’sConnection

    Pushbuttons

    Display

    Leds

    UP

    WATCHDOG

    CIRCUITI/O

    SECTION

    2 CH. SERIALCOMMUNICATION

    SECTION

    ANALOGINPUTS Mimic Panel - LED's Signals

    Relay

    N° 2 RS485 Internal Serial Link

    8 O.C. out 100 mA

    I/O Connector

    OPTOISOL.

    OPTOISOL.

    Card 2402

    EMERGENCY ACTIONFAIL-TO-SAFE

    III

    2d z IN. CH. 1-

    IN. CH. 2-

    +24 Vdc I/O

    GND I/O

    OUT O.C. - WARNING 1

    OUT O.C. - WARNING 2

    - CALIBRATION 2NCNC

    NCNC

    NCNC

    NCNC

    OUT O.C. MALF. 2

    OUT O.C. ALARM 2

    OUT O.C. MALF. 1

    OUT O.C. ALARM 1

    GND I/O

    +24 Vdc I/O

    IN. CH. 2+

    IN. CH. 1+

    GND I/O

    +24 Vdc I/O

    Watch Dog n.o. contact *

    GND I/O

    GND I/O+24 Vdc I/O

    Watch Dog common contact

    GND I/O

    4

    6

    8

    10

    12

    14

    16

    18

    20

    22

    24

    26

    28

    30

    32

    OUT O.C. - FAIL-TO-SAFE 2

    OUT O.C. - FAIL-TO-SAFE 1- CALIBRATION 1

  • 222444000222 LLLOOOGGGIIICCC CCCOOONNNTTTRRROOOLLLLLLEEERRR CCCOOOMMMBBBUUUSSSTTTIIIBBBLLLEEE GGGAAASSS DDDEEETTTEEECCCTTTOOORRRSSS

    222 IIINNNPPPUUUTTT CCCHHHAAANNNNNNEEELLLSSS 000÷÷÷222222MMMAAA

    FIELD WIRING INFORMATION’S This drawing shows the typical arrangement for the connection of devices to the 2402 Combustible Gas Card

    Specification subject to change without notice DOCUMENT SES-DS-2402-E-R1

    Shield

    Shield

    Shield

    CurrentInput

    CurrentInput

    Isolator

    Isolator

    6d

    28d/z

    INTERNALSYSTEM

    CARD

    I/O ConnectorB

    Terminal board

    FIELD

    +24V I/O

    +24V I/O

    +24V I/O

    +24V I/O

    +24V I/O

    +24V I/O

    +24V I/O

    +24VI/O

    +24VI/O

    Opto-Isolator

    Opto-Isolator

    Opto-Isolator

    Opto-Isolator

    Opto-Isolator

    Opto-Isolator

    Opto-Isolator

    Opto-Isolator

    +24VI/O

    +24VI/O

    +24VI/O

    +24VI/O

    +24VI/O

    +24VI/O

    +24VISO

    Relay Watch Dog

    R

    R

    Lamp

    Max 2,4W

    Relay

    OC AL1

    OC WR1

    OC MF1

    OC CAL1

    OC AL2

    OC WR2

    OC MF2

    OC CAL2

    10d

    10z

    12d

    12z

    14d

    14z

    16d

    16z

    30d

    30z

    GND I/O

    GND I/O

    GND I/O

    CH1

    CH2

    +

    +

    -

    -

    2d

    32d/z

    2z

    8d

    6z

    4d

    4z

    8z

    3x1,5 mm2

    + Shield

    3x1,5 mm2

    + Shield

    10 mt. max

    *

    PSU24Vdc I/O

    +

    IV

    TECHNICAL DATA SYSTEM STANDARDS CONFORM ORDERING INFORMATION OVERVIEW FG-ESD-2400 LOGIC DIAGRAM CONNECTION CONNECTOR FIELD WIRING INFORMATION’S

    DFHDF: Legal Seat : Via G. Galilei N. 5 - 20091 Bresso (MI) - ItalyFactory: Via C. Romani N.8/10 - 20091 Bresso (MI) – ItalyTel.: +39 02 610371 Fax.: +39 02 66507091www.ses-enser.com - [email protected]