Home >Documents >2a- Concrete Mix Design - Vocational Training mix design.pdf · PDF fileTo design a...

2a- Concrete Mix Design - Vocational Training mix design.pdf · PDF fileTo design a...

Date post:14-Jul-2018
Category:
View:313 times
Download:15 times
Share this document with a friend
Transcript:
  • 1/21

    Normal Concrete Mix Design 1. Prescribed Mix (Standard Mix)

    (Source: General Specification for Civil Engineering Works)

  • 2/21

    2. Designed Mix 2.1 Variability of Strength Design is based on the assumption of certain minimum properties of concrete,

    such as strength.

    Actual strength of the concrete produced is a variable quantity.

    Source of variability include variations in mix ingredients, changes in concrete

    making and placing; variations also occur in sampling procedure and testing.

    Knowledge of variability is required so that the strength values can be

    interpreted properly.

    2.2 Target Strength and Characteristic Strength It is generally accepted that the variation in concrete strengths or a particular

    mix follows the normal distribution as shown below:

    In the figure above, the mean strength of the mix is 40 N/mm2. That is, we can

    expect half of the test results will be higher than 40 N/mm2 and half will be

    lower.

    In practice, we specify the quality of concrete not as a minimum strength, and

    not as a mean strength, but as a characteristic strength below which a specified

    percentage of the test results, often called defectives, may be expected to fall.

    Figure 1 Normal distribution of concrete strength

    (Source: Building Research Establishment)

  • 3/21

    Characteristic strength may be defined as to have any proportion of defectives.

    (BS 5328 Guide to Specifying Concrete, and BS8110 Structural Use of

    Concrete adopt the 5% defective level.)

    As a result, it is necessary to design a mix to have a target mean strength greater

    than the specified characteristic strength by an amount termed the margin.

    Target mean strength = characteristic strength + margin

    fm = fk + k s

    where fm = target mean strength

    fk = characteristic strength

    k s = margin

    k = constant

    s = standard deviation

    Constant k is derived from the mathematics of the normal distribution.

    Defective Constant

    1 % 2.33

    2.5 % 1.96

    5 % 1.64

    Example 1 To design a concrete mix with characteristic strength of 30 MPa, what should the

    target mean strength be?

    Given that : defective level 5%, standard deviation 5 MPa.

    Solution

    fk = 30 MPa k = 1.64 s = 5 MPa

    fm = fk + k s

    = 30 + 1.64 x 5 MPa

    = 38.2 MPa

    The target mean strength should be 38.2 MPa

  • 4/21

    2.3 BRE Mix Design Method (Formerly DoE Method) Design of Normal Concrete Mixes was published by the Building Research

    Establishment Ltd. in 1997. (Formerly by Department of Environment).

    The design procedure is summarized in chart below:

    (Source: Building Research Establishment)

  • 5/21

    (Source: Building Research Establishment)

  • 6/21

    Equations for mix design

    C1 M = k x s

    where M = the margin k = a value appropriate to the percentage defectives permitted below the

    characteristic strength s = the standard deviation

    C2 fm = fc + M

    where fm = the target mean strength fc = the specified characteristic strength M = the margin

    C3 Cement content =

    ratiocement water / -free

    contentwater -free

    C4 Total aggregate content (saturated and surfacedry) = D C W

    where D = the wet density of concrete (kg/m3) C = the cement content (kg/m3) W = the free water content (kg/m3)

    C5 Fine aggregate content = total aggregate content x proportion of fines Coarse aggregate content = total aggregate content fine aggregate content

    C6 Portland cement content =

    F)] 0.3 (C[W / p) 0.7 (100

    Wp) (100

    where W = the free water content (kg/m3) C = the cement content (kg/m3) F = pfa content (of the mix) (kg/m3) p = proportion of pfa specified as percentage of the combined weight of cement and

    pfa the ratio of W/(C+0.3F) is derived from Table 10 and Figure 4

    C7 pfa content =

    p - 100

    C p

    where C = the cement content (kg/m3) p = proportion of pfa specified as percentage of the combined weight of cement and

    pfa

    C8

    F C

    W

    for comparison of maximum free-water/cement ratio

    where W = the free water content (kg/m3) C = the cement content (kg/m3) F = pfa content (kg/m3)

    C9 Total aggregate content (saturated and surface dry) = D (C + F) W

    where W = the free water content (kg/m3) C = the cement content (kg/m3) F = pfa content (of the mix) (kg/m3) D = the wet density of concrete (kg/m3)

  • 7/21

    Figure 3 Relationship between standard deviation and characteristic strength

    Figure 4 Relationship between compressive strength and free-water/cement ratio

  • 8/21

    Figure 5 Estimated wet density of fully compacted concrete

  • 9/21

    Figure 6 Recommended proportions of fine aggregate according to percentage passing 600 m sieve

  • 10/21

    Example 2 unrestricted design Specification of the mix:

    Characteristic compressive strength 30 N/mm2 at 28 days

    Defective rate 2.5 %

    No previous control data

    Cement: OPC class 42.5

    Slump required, 10-30 mm

    Maximum free-water/Cement ratio 0.55

    Minimum cement content 290 kg/m3

    Coarse aggregate: Uncrushed single sized 10 mm and 20 mm (1:2 by weight)

    Fine aggregate: Uncrushed with 70% passing 600 m sieve

    Relative density of aggregate : 2.6 (assumed)

    Volume of trial mix : 0.05 m3

    Example 3 mix restricted by maximum water/cement ratio Specification of the mix:

    Characteristic compressive strength 25 N/mm2 at 28 days

    No previous control data but a margin of 10 N/mm2 is specified

    Cement: OPC class 42.5

    Slump required, 30-60 mm

    Maximum free-water/Cement ratio 0.5

    Minimum cement content 290 kg/m3

    Coarse aggregate: Uncrushed single sized 10, 20 and 40 mm

    (Suggested ratio 1 : 1.5 : 3 by weight)

    Fine aggregate: Uncrushed with 90% passing 600 m sieve

    Relative density of aggregate : 2.5 (assumed)

    Volume of trial mix : 0.08 m3

  • 11/21

    Solution of Example 2

    (Source: Building Research Establishment)

  • 12/21

    Solution of Example 3

    (Source: Building Research Establishment)

  • 13/21

    Example 4 mix restricted by minimum cement content Specification of the mix:

    Same as example, but

    Slump required 0 -10 mm

    Example 5 mix restricted by maximum cement content Specification of the mix:

    Characteristic compressive strength 50 N/mm2 at 7 days

    Defective rate 1 %

    Previous control data: standard deviation 5 N/mm2

    Cement: RHPC class 52.5

    Slump required, 30-60 mm

    Maximum cement content 550 kg/m3

    Coarse aggregate: Crushed single sized 10 mm

    Fine aggregate: Uncrushed with 45% passing 600 m sieve

    Relative density of aggregate : 2.7 (assumed)

    Volume of trial mix : 0.08 m3

  • 14/21

    Solution of Example 4

    (Source: Building Research Establishment)

  • 15/21

    Solution of Example 5

    (Source: Building Research Establishment)

  • 16/21

    3 Trial Mixes 3.1 Moisture conditions of aggregates: Aggregates may be in the following conditions:

    Oven dry:- prolonged drying in an oven would eventually remove the moisture

    completely.

    Air dry:- when the aggregate is allowed to stand in dry air, some water will

    evaporate so that the aggregate is air-dry.

    Saturated surface dry (SSD):- all pores in the aggregate are full of water, i.e.,

    saturated, but the surface of the aggregate is dry.

    Damp or wet:- containing an excess of moisture on the surface (free water).

    3.2 Adjustment to mix proportion in trial mix The batch quantities determined in the mix design are based on saturated

    surface-dry (SSD) aggregates.

    Very often, aggregates are in other conditions, adjustment of actual weights of

    aggregates and water have to be made.

    Moisture Condition of Aggregate (Source: Design and Control of Concrete Mixtures Portland Cement Association)

  • 17/21

    3.3 Determination of mass of aggregate for trial mix

    3.3.1 MT = MD ( A 1M.C. 1

    )

    where

    MT = the mass of aggregate to be weighed for trial mix

    MD = mass of aggregate designed, which the aggregate is assumed in SSD

    condition.

    M.C. = insitu moisture content of the aggregate (mass of water/mass of dry

    aggregate) presented in decimal.

    A = water absorption of the aggregate (mass of absorbed water/mass of dry

    aggregate) presented in decimal.

    3.3.2 A simplified formula: MT = MD (1 + M.C. A) This formula gives an approximate result only but is accurate enough for most

    practical purpose.

    3.4. Determination of mass of water for trial mix MD = MT or MTw + MTf + MT10 + MT20 + MT40 = MDw + MDf + MD10 + MD20 + MD40 MTw = MDw + MDf + MD10 + MD20 + MD40 - (MTf + MT10 + MT20 + MT40)

  • 18/21

    Example 6 Quantities of the constituent materials for 0.05 m3 of a designed mix are: Material Designed Mass (kg) Absorption (%)

    Cement 17.0 -

    Coarse aggregate (SSD) 69.2 1

Click here to load reader

Embed Size (px)
Recommended