+ All Categories
Home > Documents > 3 DRFR PRDS - Krueger-HVAC DRFR PRDS REER 2015 FDD | Round Diffuser, Displacement Air Pattern F D D...

3 DRFR PRDS - Krueger-HVAC DRFR PRDS REER 2015 FDD | Round Diffuser, Displacement Air Pattern F D D...

Date post: 03-Apr-2018
Category:
Upload: duongnhan
View: 218 times
Download: 2 times
Share this document with a friend
7
www.krueger-hvac.com | Excellence in Air Distribution E3-22 UNDERFLOOR PRODUCTS UNDERFLOOR PRODUCTS E3 © KRUEGER 2015 FDD | Round Diffuser, Displacement Air Pattern F D D FDD Introduction: FDD Krueger’s FDD round displacement diffusers are designed to seamlessly integrate into any underfloor installation and can supplement a displacement ventilation system. The FDD provides high flow capabilities that exceed the competition. The units are made of a durable and long lasting cast aluminum construction. The FDD is available in a variety of sizes and plenum options. The plenums are pre-painted flat black to conceal them from view through the diffuser. MODEL FDD - Cast Aluminum Round Diffuser for Underfloor with Displacement Air Pattern FEATURES Available in a 4”, 6”, 8” or 10” round nominal size. Ships completely assembled and is easily installed. 180° displacement air pattern on 4” and 6”. 360° displacement air pattern on 8” and 10”. Durable cast aluminum construction to withstand any application. Features a 1250 lbs. load rating. Manual airflow adjustment. Conforms to NFPA 90A fire requirements. Provided with optional factory painted flat black steel plenum on sizes 8” and 10”. Provides silent operation less than 17NC at 100% capacity. When ordered alone, works in 6” raised floors. With plenum option, compatible with 8” raised floors. PLENUM OPTIONS 0 - No plenum for constant volume. P - Open inlet to underfloor plenum for constant volume. D - Elliptical inlet to accept a 6” round compressed duct connection. V - VAV inlet with 0-10 Vdc proportional actuator. H - Heat/Cool changeover unit has an elliptical inlet to accept a 6” round compressed duct connection on one side that is ducted to a underfloor fan powered terminal unit. On the adjacent side is a VAV inlet with 0-10 Vdc proportional actuator for cooling operation. NOTE: Units with the V and H plenum options ship with a quick connect cable for both data and power. FINISH A - Black (RAL 9011) B - Gray (RAL 7012) C - Antique Copper (09/90180) D - Silver Hammertone (09/90250) E - Antique Gray (09/90170) F - Putty (RAL 9002) G - Beige (RAL 1019) H - Antique Gold (09/90200) I - Antique Silver (09/90190) J - Dark Brown (RAL 8014) X - Custom (Provide RAL Number)
Transcript

www.krueger-hvac.com | Excellence in Air DistributionE3-22

UN

DE

RFL

OO

R P

RO

DU

CTS

UNDERFLOOR PRODUCTSE3©

KR

UE

GE

R 2015

FDD | Round Diffuser, Displacement Air Pattern

FDD

FDD

Introduction: FDDKrueger’s FDD round displacement diffusers are designed to seamlessly integrate into any underfloor installation and can supplement a displacement ventilation system. The FDD provides high flow capabilities that exceed the competition. The units are made of a durable and long lasting cast aluminum construction. The FDD is available in a variety of sizes and plenum options. The plenums are pre-painted flat black to conceal them from view through the diffuser.

MODEL FDD - Cast Aluminum Round Diffuser for Underfloor with Displacement Air Pattern

FEATURES• Available in a 4”, 6”, 8” or 10” round nominal size.• Ships completely assembled and is easily installed.• 180° displacement air pattern on 4” and 6”.• 360° displacement air pattern on 8” and 10”.• Durable cast aluminum construction to withstand any application.• Features a 1250 lbs. load rating.• Manual airflow adjustment.• Conforms to NFPA 90A fire requirements.• Provided with optional factory painted flat black steel plenum

on sizes 8” and 10”.• Provides silent operation less than 17NC at 100% capacity.• When ordered alone, works in 6” raised floors.

With plenum option, compatible with 8” raised floors.

PLENUM OPTIONS0 - No plenum for constant volume. P - Open inlet to underfloor plenum for constant volume.D - Elliptical inlet to accept a 6” round compressed duct

connection.V - VAV inlet with 0-10 Vdc proportional actuator.H - Heat/Cool changeover unit has an elliptical inlet to

accept a 6” round compressed duct connection on one side that is ducted to a underfloor fan powered terminal unit. On the adjacent side is a VAV inlet with 0-10 Vdc proportional actuator for cooling operation.

NOTE: Units with the V and H plenum options ship with a quick connect cable for both data and power.

FINISHA - Black (RAL 9011)B - Gray (RAL 7012)C - Antique Copper (09/90180)D - Silver Hammertone (09/90250)E - Antique Gray (09/90170)F - Putty (RAL 9002)G - Beige (RAL 1019)H - Antique Gold (09/90200)I - Antique Silver (09/90190)J - Dark Brown (RAL 8014)X - Custom (Provide RAL Number)

Providing You With Air Distribution Solutions E3-23

UN

DE

RFLO

OR

PR

OD

UC

TSUNDERFLOOR PRODUCTS E3

© K

RU

EG

ER

201

5FDD | Round Diffuser, Displacement Air Pattern

FDD

FDD, FACE AND SIDE VIEWS, SIZE 4

SIDE VIEW

4.5” 3.875”

3”

180° AIR PATTERN (ONLY)

4ӯ

FDD, FACE AND SIDE VIEWS, SIZE 6

SIDE VIEW

6.75”

5.75”

COLLAPSABLERETENSION BAR

5”

180° AIR PATTERN (ONLY)

6ӯ

FDD, FACE AND SIDE VIEWS, SIZE 8

SIDE VIEW

COLLAPSABLERETENTION BAR

5”

9.5”

8ӯ

360° AIR PATTERN (ONLY)

FDD, FACE AND SIDE VIEWS, SIZE 10

11.5”

10ӯ

SIDE VIEW

5”

COLLAPSABLERETENTION BAR

360° AIR PATTERN (ONLY)

STANDARD FEATURES• Cast aluminum diffuser face.• 180° displacement air pattern on

sizes 4” and 6”.• 360° displacement air pattern on

sizes 8” and 10”.• 1250 lbs. maximum load rating.• Complies with NFPA 90A.• Manual air flow adjustment with

sliding damper plate.• Tight shut-off.

INSTALLATION• Minimum Access Floor Depth: 6”• Required Tile Cutout Opening: - Size 4: 4.125” Ø - Size 6: 6” Ø - Size 8: 8.3125” Ø - Size 10: 10.625” Ø

PERFORMANCE DATA• Access performance data through

our selection software.

FDD Dimensional Information, Features, and Options

www.krueger-hvac.com | Excellence in Air DistributionE3-24

UN

DE

RFL

OO

R P

RO

DU

CTS

UNDERFLOOR PRODUCTSE3©

KR

UE

GE

R 2015

FDD | Round Diffuser, Displacement Air Pattern

FDD

FDD-D, FACE AND SIDE VIEWS, SIZE 8

SIDE VIEW

PLENUM TOP VIEW

8”

14.25”

10.5”

8.25ӯ

ACCEPTS STANDARD6ӯ DUCT CONNECTION

9.5ӯ

8ӯ

360° AIR PATTERN (ONLY)

STANDARD FEATURES• Cast aluminum diffuser face.• Displacement air pattern.• 1250 lbs. maximum load rating.• Complies with NFPA 90A.• Manual air flow adjustment with

sliding damper plate.• Welded and riveted pre-painted

galvanized steel.• Accepts a standard 6” flex

connection.• Tight shut-off.

INSTALLATION• Minimum Access Floor Depth: 8”• Required Tile Cutout Opening:

8.4375” Ø

PERFORMANCE DATA• Access performance data through

our selection software.

FDD-D, FACE AND SIDE VIEWS, SIZE 10

10.625ӯ

ACCEPTS STANDARD6ӯ DUCT CONNECTION

8”

14.25”

10.5”

6.875”

11.5ӯ10ӯ

PLENUM TOP VIEW

SIDE VIEW

360° AIR PATTERN (ONLY)

STANDARD FEATURES• Cast aluminum diffuser face.• Displacement air pattern.• 1250 lbs. maximum load rating.• Complies with NFPA 90A.• Manual air flow adjustment with

sliding damper plate.• Welded and riveted pre-painted

galvanized steel.• Accepts a standard 6” flex

connection.• Tight shut-off.

INSTALLATION• Minimum Access Floor Depth: 8”• Required Tile Cutout Opening:

10.6875“ Ø

PERFORMANCE DATA• Access performance data through

our selection software.

FDD Dimensional Information, Features, and Options

Providing You With Air Distribution Solutions E3-25

UN

DE

RFLO

OR

PR

OD

UC

TSUNDERFLOOR PRODUCTS E3

© K

RU

EG

ER

201

5FDD | Round Diffuser, Displacement Air Pattern

FDD

FDD-H, FACE AND SIDE VIEWS, SIZE 8

ACCEPTS STANDARD6ӯ DUCT CONNECTION

5.5”

12.5”

8”

14.25”16.25”

8.25ӯ

9.5ӯ

8ӯ

PLENUM TOP VIEW

SIDE VIEW

360° AIR PATTERN (ONLY) 1.5”

STANDARD FEATURES• Cast aluminum diffuser face.• Displacement air pattern.• 1250 lbs. maximum load rating.• Complies with NFPA 90A.• Manual air flow adjustment with

sliding damper plate.• DC synchronized magnetic motor.• Welded and riveted pre-painted

galvanized steel.• Multi-function circuit board for

varying control strategies.• Tight shut-off.• One (1) PAP-1 cable provided with

the unit.

INSTALLATION• Minimum Access Floor Depth: 8”• Required Tile Cutout Opening:

8.4375” Ø

PERFORMANCE DATA• Access performance data through

our selection software.

FDD-H, FACE AND SIDE VIEWS, SIZE 10

14.25”

1.5”

5.5”

12.5”

16.25”

8”

ACCEPTS STANDARD6ӯ DUCT CONNECTION

11.5ӯ10ӯ

PLENUM TOP VIEW

SIDE VIEW

360° AIR PATTERN (ONLY)

STANDARD FEATURES• Cast aluminum diffuser face.• Displacement air pattern.• 1250 lbs. maximum load rating.• Complies with NFPA 90A.• Manual air flow adjustment with

sliding damper plate.• DC synchronized magnetic motor.• Welded and riveted pre-painted

galvanized steel.• Multi-function circuit board for

varying control strategies.• Tight shut-off.• One (1) PAP-1 cable provided with

the unit.

INSTALLATION• Minimum Access Floor Depth: 8”• Required Tile Cutout Opening:

10.6875“ Ø

PERFORMANCE DATA• Access performance data through

our selection software.

FDD Dimensional Information, Features, and Options

www.krueger-hvac.com | Excellence in Air DistributionE3-26

UN

DE

RFL

OO

R P

RO

DU

CTS

UNDERFLOOR PRODUCTSE3©

KR

UE

GE

R 2015

FDD | Round Diffuser, Displacement Air Pattern

FDD

FDD-P, FACE AND SIDE VIEWS, SIZE 8

4.75” PLENUM OPENING

10.5”13.25”

14.25”

8”

8.25ӯ

9.5ӯ

8ӯ

PLENUM TOP VIEW

SIDE VIEWFRONT VIEW

360° AIR PATTERN (ONLY)

STANDARD FEATURES• Cast aluminum diffuser face.• Displacement air pattern.• 1250 lbs. maximum load rating.• Complies with NFPA 90A.• Manual air flow adjustment with

sliding damper plate.• Welded and riveted pre-painted

galvanized steel.• Tight shut-off.

INSTALLATION• Minimum Access Floor Depth: 8”• Required Tile Cutout Opening:

8.4375” Ø

PERFORMANCE DATA• Access performance data through

our selection software.

FDD-P, FACE AND SIDE VIEWS, SIZE 10

4.75” PLENUM OPENING

10.5”13.25”

14.25”

10.625ӯ

8”

11.5ӯ10ӯ

PLENUM TOP VIEW

SIDE VIEWFRONT VIEW

360° AIR PATTERN (ONLY)

STANDARD FEATURES• Cast aluminum diffuser face.• Displacement air pattern.• 1250 lbs. maximum load rating.• Complies with NFPA 90A.• Manual air flow adjustment with

sliding damper plate.• Welded and riveted pre-painted

galvanized steel.• Tight shut-off.

INSTALLATION• Minimum Access Floor Depth: 8”• Required Tile Cutout Opening:

10.6875“ Ø

PERFORMANCE DATA• Access performance data through

our selection software.

FDD Dimensional Information, Features, and Options

Providing You With Air Distribution Solutions E3-27

UN

DE

RFLO

OR

PR

OD

UC

TSUNDERFLOOR PRODUCTS E3

© K

RU

EG

ER

201

5FDD | Round Diffuser, Displacement Air Pattern

FDD

FDD Dimensional Information, Features, and OptionsFDD-V, FACE AND SIDE VIEWS, SIZE 8

6.875”

12.5”

14.25”

8.25ӯ

16.25”

8”

9.5ӯ

8ӯ

PLENUM TOP VIEW

SIDE VIEW

360° AIR PATTERN (ONLY)

STANDARD FEATURES• Cast aluminum diffuser face.• Displacement air pattern.• 1250 lbs. maximum load rating.• Complies with NFPA 90A.• Manual air flow adjustment with

sliding damper plate.• DC synchronized magnetic motor.• Welded and riveted pre-painted

galvanized steel.• Multi-function circuit board for

varying control strategies.• Tight shut-off.

INSTALLATION• Minimum Access Floor Depth: 8”• Required Tile Cutout Opening:

8.4375” Ø

PERFORMANCE DATA• Access performance data through

our selection software.

FDD-V, FACE AND SIDE VIEWS, SIZE 10

10.625ӯ

12.5”

14.25”

8”

16.25”

5.5”

11.5ӯ10ӯ

PLENUM TOP VIEW

SIDE VIEW

360° AIR PATTERN (ONLY)

STANDARD FEATURES• Cast aluminum diffuser face.• Displacement air pattern.• 1250 lbs. maximum load rating.• Complies with NFPA 90A.• Manual air flow adjustment with

sliding damper plate.• DC synchronized magnetic motor.• Welded and riveted pre-painted

galvanized steel.• Multi-function circuit board for

varying control strategies.• Tight shut-off.• One (1) PAP-1 cable provided with

the unit.

INSTALLATION• Minimum Access Floor Depth: 8”• Required Tile Cutout Opening:

10.6875“ Ø

PERFORMANCE DATA• Access performance data through

our selection software.

www.krueger-hvac.com | Excellence in Air DistributionE3-28

UN

DE

RFL

OO

R P

RO

DU

CTS

UNDERFLOOR PRODUCTSE3©

KR

UE

GE

R 2015

FDD | Round Diffuser, Displacement Air Pattern

FDD

1. SERIES: (XXX) FDD - Cast Aluminum Round Diffuser for Underfloor with Displacement Air Pattern

2. THROW PATTERN: (X) H - 180° Air Pattern* F - 360° Displacement Air Pattern**

3. SIZE: (XX) 4”, 6”, 8”, or 10”

4. PLENUM OPTION: (X) 0 - None D - 6” Ellipsoid Duct Connection P - Plenum Opening for Constant Volume V - VAV Air Valve H - VAV Air Valve with 6” Ellipsoid Duct Connection

5. FINISH: (X) A - Black (RAL 9011) B - Gray (RAL 7012) C - Antique Copper (09/90180) D - Silver Hammertone (09/90250) E - Antique Gray (09-90170) F - Putty (RAL 9002) G - Beige (RAL 1019) H - Antique Gold (09/90200) I - Antique Silver (09/90190) J - Dark Brown (RAL 8014) X - Custom (Provide RAL Number)

* 180° air pattern available on sizes 4” and 6”.** 360° air pattern available on sizes 8” and 10”.

FDDUnderfloor diffusers shall be Krueger model FDD. The diffuser shall be constructed of solid cast aluminum and meet NFPA 90A requirements. The FDD diffuser shall have a maximum load rating of 1250 lbs. The diffuser, damper assembly, and dirt catch pan are shipped fully assembled and can be securely installed in floor tile by turning the center screw and allow retention bar to clip to bottom side of floor tile. The diffuser shall not be removed without use of hexagonal key. The FDD floor diffuser shall be designed such that the access floor panel is not removed from the floor system for installation of the diffuser. The diffuser core design shall produce a low displacement air pattern that complies with ASHRAE Standard 62. The diffuser shall have a sliding manual damper capable of adjusting the volume from full closed to full open. The FDD diffuser shall be factory painted with a powder coat finish.

The FDD-D shall be provided with an optional plenum. The plenum shall be factory painted flat black and be a minimum of 20 gauge galvanized steel and shall support all diffuser components. The plenum shall be provided with an ellipsoid duct connection that will accept a standard six inch duct.

The FDD-P shall be provided with an optional plenum. The plenum shall be factory painted flat black and be a minimum of 20 gauge galvanized steel and shall support all diffuser components. The plenum shall be provided with one side open to the underfloor plenum for constant volume operation and to control sound transmission from the underfloor plenum to the occupied zone.

The FDD-V shall be provided with an optional plenum. The plenum shall be factory painted flat black and be a minimum of 20 gauge galvanized steel and shall support all diffuser components. The plenum shall be provided with a an actuated air valve damper controlled by a 90-degree stepper type motor having no stops, springs, gears, belts or linkages, and shall rotate continuously in one direction (not reversing) to minimize wear. The motor shall directly drive the damper blade. The damper assembly shall be rated and tested for a life of 100 million cycles (factory tests of at least 20 million cycles at normal operating speeds are required). A proportional 0-10 Vdc control signal can be used to modulate the damper position to adjust the volume of air in response to the thermostat signal.

The FDD-H shall be provided with an optional plenum. The plenum shall be factory painted flat black and be a minimum of 20 gauge galvanized steel and shall support all diffuser components. The plenum shall be provided with an ellipsoid duct connection that will accept a standard six inch duct. The plenum shall be provided with an actuated air valve damper controlled by a 90-degree stepper type motor having no stops, springs, gears, belts or linkages, and shall rotate continuously in one direction (not reversing) to minimize wear. The motor shall directly drive the damper blade. The damper assembly shall be rated and tested for a life of 100 million cycles (factory tests of at least 20 million cycles at normal operating speeds are required). A proportional 0-10 Vdc control signal can be used to modulate the damper position to adjust the volume of air in response to the thermostat signal.

SAMPLE CONFIGURATION: FDD - H - 4 - D - G

FDD Suggested Specification & Configuration


Recommended