Date post: | 05-Apr-2018 |
Category: |
Documents |
Upload: | surya-teja |
View: | 213 times |
Download: | 0 times |
of 58
7/31/2019 3 Sagar
1/58
ABSTRACT
Power is an essential requirement for all facets of our life and has been
recognized as a basic human need. It is the critical infrastructure on which the
socio economic development of the country depends. the growth of the
economy and its global competitiveness hinges on the availability of reliable and
quality power at competitive rates. The demand power is enormous and is
growing steadily. In order to meet this demand, the power generating stations
have to transmit the power, which are located at hundreds of kilometers from the
load centers and due to these long distances we have to place the intermediate
substation in order to reduce the losses and to increase maximum power transfer
in the lines.
The generation for electricity in power generating station is done in
faraway places from consumers & load centers for various reasons reasons. The
generated voltage is stepped up at some places and stepped down at some places
i.e. at 11kv, 33kv it is stepped up to 132, 220, 400kv and transmitted to various
loads. at load centers the high voltage is stepped down to 11kv or 440 / 220v and
distributed to consumer. These voltage transformations are carried out at sub
stations.
The main equipment in substation is transformer, bus section, circuit
breaker, line going out of the substation. The protective relaying is necessary
with almost every electrical substation and no part of the substation is left
EEE Page 1
7/31/2019 3 Sagar
2/58
unprotected. The choice of protection depends on different aspects such as type,
rating and protection equipment, location and cost.
The protection relaying scheme senses the abnormal condition of the
substation. Transient stability can be improved by means of protective relaying.
Faults cannot be avoided completely but they can be minimized. Hence relays
can play an important role in minimizing the faults.
In this project, we give an insight o the substation. it consists of various
fields which have been elaborated in a detailed manner. The necessity of a
substation, its features, classifications, specifications are dealt. The various
equipments used in a substation are explained.
EEE Page 2
7/31/2019 3 Sagar
3/58
CHAPTER 1
INTRODUCTION
EEE Page 3
7/31/2019 3 Sagar
4/58
Andhra Pradesh Transmission Corporation Ltd., has a great significance
of transmitting bulk power from four decades for which they have constructed
number of substations. Transmission substation is located between generating
power station and distribution substations.
Visakhapatnam consists of National thermal power corporation Ltd.,
Known as Simhadhri power plant. The plant generates 2*500MW power. This
total power is utilized in Andhra Pradesh only. So, AP TRANSCO established a
400 / 200kv transmission substation at KALAPAKA near NTPC.
This substation has been inaugurated by Honorable Former chief minister
Shri Nara Chandrababu Naidu in 2002. The substation is in collaboration with
J.B.I.C a Japanese company. The substation is spread over vast area of about 70
acres and the yard length is 900mts. According to area the substation is the
second largest in ASIA.
The equipment in this substation like transformers are manufactured by
CROMPTON GREAVES, Circuit breakers and Relays are manufactured by
ASIA BROWN BOVERI LTD.
It is feeded from NTPC by four incoming lines. The power is transmitted
to Vemagiri, Khammam and Power Grid. The 400kv is step down to 220kv and
transmits to Visakha dairy farm and Vizag switching station.
ORGANISATION OF THE MINI PROJECT REPORT:-
EEE Page 4
7/31/2019 3 Sagar
5/58
The work presented in this report is organized in the following manner.
Chapter 2 deals with the (400/220 KV) substation which includes
introduction to substation, its necessity, classifications on various bases,
specifications, essential features & necessary structures within the
substation. The layout of 400/200KV Kalapaka substation is also
presented.
Chapter 3 deals with various elements that are used in the substation.
The substation equipment comprises of transformers, circuit breakers,
relays, lightning arresters, isolators, reactors, current transformers,
capacitor voltage transformers, wave trap, earthing system etc., the
ratings & specifications of the equipment used in Kalapaka substation
are also mentioned.
Chapter 4 deals with various protection schemes employed for the
protection of transformers & bus bars. The protection schemes for the
transformers includes buchholz relay, differential protection, over
fluxing protection, breaker failure relay protection & restricted earth
fault protection. The bus bar arrangements & protection schemes
includes back up protection & differential over current protection.
Chapter 5 deals with the various auxiliary equipments used in the
kalapaka substation. The auxiliary equipment includes battery operation
and maintenance, disturbance recorded & event logger.
EEE Page 5
7/31/2019 3 Sagar
6/58
CHAPTER 2
400 / 220 KV
SUBSTATION
EEE Page 6
7/31/2019 3 Sagar
7/58
2.1 INTRODUCTION
The assembly of apparatus used to change some characteristics (i.e., voltage A.C.
to D.C., frequency, power factor) of electric supply is called a substation. An
electrical substation is a subsidiary station of a electricity generation,
transmission and distribution system where voltage is transformed from high to
low or the reverser using transformers. Electric power may flow through several
substations between generating plant and consumer, and may be changed in
voltage in several steps.
There are several substations between generating station and final load points
Electrical substation receives power from the incoming lines and the power is
transferred at desired voltage by the transformer and is then supplied to the
outgoing lines.
The electrical sub stations at the various locations in network differ greatly in
their sizes, design, configuration and appearance. There are different works done
in a substation.
Switching Operation
Voltage Transformation Operation
Power Converting Operation
Power Factor Correction Operation.
EEE Page 7
7/31/2019 3 Sagar
8/58
2.2 NECESSITY:
Between the generation of power and consumer point, transmission and
distribution exists. Generating stations are designed for generating bulk amount
of power and the Transmission takes place at high voltages to reduce the line
losses, where as consumer points are at low voltage. This high voltage is stepped
down to a lower voltage at different stages with the help of transformer and
switchgear in the substation.
2.3 CLASSIFICATION OF SUBSTATION.
The substation may be classified in numerous ways on the basis of
Nature of Duties
Service Rendered
Operating Voltage
Importance
Design
BASED ON THE NATURE OF DUTIES:
The substation based on the nature of duties may be classified into three types.
Step Up or Primary Substations
Primary Grid Substations
Step Down or Distribution Substations
EEE Page 8
7/31/2019 3 Sagar
9/58
BASED ON THE NATURE OF OPERATING VOLTAGES:
High voltage Substation
Extra High Voltage Substation
Ultra High Voltage Substation
BASED ON SERVICE RENDERED:
Transformer Substation
Switching Substation
Converting Substation
BASED ON DESIGN:
Indoor Type Substation
Out Door Type Substation.
2.4 SPECIFICATIONS:
Specifications of substation denote the design requirement rating, technical
aspects regarding the substation and its associated electrical, mechanical, civil
and auxiliary sub system.
The sub stations are planned on the basis of economic, electrical and local
conditions at the project planning stage.
The substation requirements are influenced by network requirement in several
aspects including the following.
1. Insulation levels and insulation coordination
2. Fault levels and their coordination
3. Voltage control requirement of the network
4. Clearance and creep age distances
EEE Page 9
7/31/2019 3 Sagar
10/58
5. Network monitoring and data communication between substation and
load dispatch centers.
6. Back up protection main protection zones maintenance zones
7. Switching sequence during normal emergency and post fault conditions.
ESSENTIAL FEATURES:
An AC substation has following parts.
AC switch yard
Control building
Low voltage and medium voltage AC system for auxiliaries
DC battery system and low voltage distribution system
Station mechanical, electrical and other auxiliaries
Civil work.
2.5 LAYOUT OF KALAPAKA SUBSTATION:
The first step in planning a substation layout is the preparation of a one line
diagram which shows in simplified from the switching and protection
arrangement required, as well as the incoming supply lines and outgoing feeders
or transmission lines. It is a usual practice by many electrical utilities to prepare
one line diagrams with principal elements (lines, switches, circuit breakers, and
transformers) arranged on the page similarly to the way the apparatus would be
laid out in the actual station.
EEE Page 10
7/31/2019 3 Sagar
11/58
2.6 NECESSARY STRUCTURES:
The following structures are necessary in a conventional open terminal outdoor
substation.
Towers of incoming and outgoing transmission lines :
These are generally located outside the substation boundary adjacent to
the substation.
Tower and gantries for supporting strain insulators and flexible bus
bar :
These are used for mounting isolator, surge arrester and other equipment
suitable.
Towers and gaintries for supporting rigid tabular bus bar mounted
on post insulator.
The insulators are supported on horizontal beams. Supporting structures
of post insulator also support the tubular rigid bus bar, CTs, VTs,
insulators, CB and lime traps etc.,
EEE Page 11
7/31/2019 3 Sagar
12/58
CHAPTER 3
ELEMENTS OF SUBSTATION
EEE Page 12
7/31/2019 3 Sagar
13/58
3.1 INTRODUCTION:
Substations generally have switching, protection and control equipment
and one or more transformers. In a large substation, circuit breakers are used to
interrupt any short-circuits or overload currents that may occur on the network.
Smaller distribution stations may use recloser circuit breakers or fuses for
protection of distribution circuits. Substations do not usually have generators,
although a power plant may have a substation nearby. Other devices such as
power factor correction capacitors and voltage regulators may also be located at
a substation.
Substations may be on the surface in fenced enclosures, underground, or
located in special-purpose buildings. High-rise buildings may have several
indoor substations. Indoor substations are usually found in urban areas to reduce
the noise from the transformers, for reasons of appearance, or to protect
switchgear from extreme climate or pollution conditions.
Where a substation has a metallic fence, it must be properly grounded to
protect people from high voltages that may occur during a fault in the network.
Earth faults at a substation can cause a ground potential rise. Currents flowing in
the Earths surface during a fault can cause metal objects to have a significantly
different voltage than the ground under a persons feet; this tough potential
presents a hazard of electrocution.
EEE Page 13
7/31/2019 3 Sagar
14/58
3.2. TRANSFORMER:
A Transformer is a static piece of apparatus by means of which electric
power in one circuit is transferred to another circuit without change in frequency.
The Transformer works on the principle of mutual inductance between
two circuits linked by a common magnetic flux.
Basically Transformers are of two types : ---
Core type
Shell type
CORE TYPE: The winding surrounds a considerable part of the core.
SHELL TYPE: The core surrounds a considerable portion of the winding.
EEE Page 14
7/31/2019 3 Sagar
15/58
RATING OF A TRANSFORMER:
The mostly used power transformers in A.P. Region are
1. 400/220 KV 316 MVA Auto transformer
2. 220/132 KV 100 MVA Auto transformer
3. 220/33 KV 50 & 31.5 MVA transformer
4. 132/66 KV 40 & 27.5 MVA transformer
5. 132/33 KV 50, 31.5, 25, 16, 15 MVA transformers
6. 132/11 IV 16, 15 & 7.5 MVA transformers
7. 33/11 KV 8, 5, 3, 15 MVA transformers.
Most of the Power Transformer are of 132/11 KV and above are of star-
star vector grouping with the neutral solidly earthern.
In substation Auto transformers are preferred over two winding
transformer.
AUTO TRANSFORMER:
A transformer, in which a part of the winding is common to both the
primary and secondary circuits, is called an auto-transformer. In a two winding
transformer, primary and secondary windings are electrically isolated, but in an
auto-transformer the two windings are not electrically isolated.
EEE Page 15
7/31/2019 3 Sagar
16/58
RATINGS OF AUTO-TRANSFORMER:
MAKE : M/s. CROMPTION GREAVES LIMITED, MUMBAI
CAPACITY : 315 MVA
RATING : 400/220/33 KV
WEIGHT : 273000 Kg.
WEIGHT OF OIL : 80,600 Lit.
EEE Page 16
7/31/2019 3 Sagar
17/58
ADVANTAGES OF AUTO TRANSFORMER:
1. The weight of the (copper and aluminums) for any winding depends
Upon the cross sectional area and length of the conductor. Hence for
an auto transformer the weight and cost of the conductor required is
less compared to two winding transformer.
2. Owing to the reduction in conductor and core materials, the ohmic
losses in conductor and the core losses re lowered. Therefore, an auto
transformer has higher efficiency than a two winding transformer of
the same output.
3. Reduction in the conductor material means lower value of ohmic
resistance. A part of the winding being common, leakage flux and
therefore, leakage reactance is less. In other words, an auto
transformer has lower value of leakage impedance and has superior
voltage regulation then a two-winding transformer of the same output.
3.3 RELAYS:
A relay is an electrically operated switch. Many relays use an
electromagnet to operate a switching mechanism, but other operating principles
are also used. Relays find applications where it is necessary to control a circuit
by a low-power signal, or where several circuits must be controlled by one
signal. Solid state relays control power circuits with no moving parts, instead
using a semiconductor device to perform switching. Relays with calibrated
operating characteristics and sometimes multiple operating coils are used to
EEE Page 17
7/31/2019 3 Sagar
18/58
protect electrical circuits from overload or faults; in modern electric power
systems these functions are performed by digital instruments still called
protection relays
Transistor relays are the most widely use static relays. In fact, when we
talk of static relay we generally mean transistor relays. The fact that the
transistor can be used both as an amplifying device and a switching device
makes this component suitable for achieving any functional characteristics.
The advantages of transistor relays can be summarized as follows:
1. The power consumption is low and hence provides less burden on CT and
PT as compare to the conventional electromechanical relays.
2. The relays are fast in operation.
3. No moving parts hence friction or contact troubles are absent and as a
result minimum maintenance is required.
4. The relays have greater sensitivity as amplication of signals can be obtainvery easily.
5. The relays has a high reset to pick up and the reset is very quick.
6. The use of printed circuits avoids wiring error and facilitates
rationalization of batch production.
7. It is possible to obtain wide range of characteristics approaching more or
less to the ideal requirements.
OPERATION:
When a current flows through the coil, the resulting magnetic field
attracts an armature that is mechanically linked to a moving contact. The
movement either makes or breaks a connection with a fixed contact. When the
current to the coil is switched off, the armature is returned by a force
approximately half as strong as the magnetic force to its relaxed position.
EEE Page 18
7/31/2019 3 Sagar
19/58
Usually this is a spring, but gravity is also used commonly in industrial motor
starters. Most relays are manufactured to operate quickly. In a low voltage
application, this is to reduce noise. In a high voltage or high current application,
this is to reduce arcing. If the coil is energized with DC, a diode is frequently
installed across the coil, to dissipate the energy from the collapsing magnetic
field at deactivation, which would otherwise generate a spike of voltage and
might cause damage to circuit components. If the coil is designed to reenergized
with AC, a small copper ring can be crimped to the end of the solenoid. This
shading ring creates a small out of-phase current, which increases the minimum
pull on the armature during the AC Cycle.
By analogy with the functions of the original electromagnetic device, a
solid stage relay is made with a thyristor or other solid-stage switching device.
To achieve electrical isolation, a light emitting diode (LED) is used with a photo
transistor.
The type of relays used in Kalapaka substation is distance relays (REL 316
and REL 100).
DISTANCE RELAY
The impedance relays also called distance relays are employed to provide
protection to transmission lines connected in a network as they are economic and
possess several technical advantages. They are comparatively simple to apply.
Operate with extremely high speed and both primary and backup protection
features are inherent in them with power line carrier facilities and are suitable for
high sped re-closing. The impedance relay is made to respond to the impedance
EEE Page 19
7/31/2019 3 Sagar
20/58
between the relay location and the point where fault is incident. The impedance
is proportional to the fault, and is therefore independent of the fault current
levels.
DISTANCE RELAYING PRINCIPLE
A distance relay compares the currents and voltages at the relaying points with
current providing the operating torque and the voltage provides the restraining
torque. In other words an impedance relay is a voltage restrained over current
relay.
Since the operating characteristics of the relay depend upon the ratio of voltage
and current and the phase angle between them their characteristics can be best
represented on an R-X Diagram where both V/I ratio and phase angle can be
plotted in terms of an impedance R + JX. Future the power system impedance,
loads, power swings etc., can also be plotted on the same R- X diagram.
Therefore response of a particular relay during power swing faults and other
system disturbances can easily be assessed.
TYPES OF DISTANCE RELAY:
1. Impedance relay
2. Reactance relay
3. Mho relay
4. Modified impedance relay
EEE Page 20
7/31/2019 3 Sagar
21/58
IMPEDANCE RELAY:
Operation of the impedance relay is independent of the phase angle between
V and I the operating characteristics is a circle with its center at the origin
and hence the relay is non-direction.
THE REACTANCE RELAY
Reactance relay measures V/I sin O whenever the reactance measured by the
relay is less than the set value the relay operates.
EEE Page 21
7/31/2019 3 Sagar
22/58
The resistance component of impedance has no effect on the operation of the
reactance relay. The relay responds solely to reactance component of
impedance. This relay is inherently non-directional. The relay is most suitable
to detect earth faults where the effect of are resistance is applicable.
MHO RELAY:
This is a directional impedance relay, also known as admittance relay. Its
characteristics on R-X diagram is a circle whose circumference passes
through the origin. This relay is inherently directional and it only operates
for fault in the forward direction.
MODIFIED IMPEDANCE RELAY:
EEE Page 22
7/31/2019 3 Sagar
23/58
This is also known as mho relay whose characteristics enclose the origin on
R-X.
This off set mho relay has three main applications:
Bus-bar zone
Carrier starting unit in distance/carrier blocking schemes
Power swing blocking
3.4. CIRCUIT BREAKER
The function of the circuit breaker is to isolate the faulty part of the power
system in case of abnormal conditions.
A circuit breaker has two contacts, a fixed contact and a moving contact. Under
normal conditions these two contacts remain in closed position. When the circuit
breaker is required to isolate the faulty part, the moving contact moves away to
interrupt the circuit by separating the contacts. The flow of current is interrupted
results in the formation of arc between the contacts. The contacts are placed in a
closed chamber containing some insulation medium which extinguishes the arc.
ARC INTERRUPTION:
These are two methods of arc interruption:
1. High resistance interruption.
2. Current zero interruption
HIGH RESISTANCE INTERRUPTION:
EEE Page 23
7/31/2019 3 Sagar
24/58
In this method of arc interruption its resistance is increased so as to reduce the
current to a value in sufficient to maintain the arc. The arc resistance can be
increased by cooling, lengthening, constraining and splitting the arc. This
method is not suitable for large current interruption.
CURRENT ZERO INTERRUPTION:
In case of AC supply the current passes through a zero point 100 times per sec at
the supply frequency of 50 Hz. This feature of arc is utilized for arc interruption.
The current is not interrupted at any point other than the zero current instant,
otherwise a high transient voltage will occur across the contact gap.
RESTRIKING VOLTAGE AND RECOVERY VOLTAGES
After the arc has extinguished the voltage across the breaker terminals do not
normalize instantaneously but it oscillates and there is a transient condition. The
transient voltage which appears across the breaker contact at the instant of arc
being extinguished is known as restriking voltage. The power frequency runs
voltage which appears across the arc is finally extinguished and transient
oscillations die out is called recovery voltage.
CLASSIFICATION OF CIRCUIT BREAKER:
EEE Page 24
7/31/2019 3 Sagar
25/58
Depending on the arc quenching medium employed the following are important
types of circuit breaker.
1. Oil circuit breaker
2. Air blast circuit breaker
3. Sulphur hexa fluoride circuit breaker
4. Vacuum circuit breaker
RATING OF CIRCUIT BREAKER
Circuit breakers have the following important ratings.
1. Breaking capacity
2. Making capacity
3. Short time capacity
BREAKING CAPACITY
The braking capacity of the circuit breaker is of two types
1. Symmetrical breaking capacity
2. Asymmetrical breaking capacity
SYMMETRICAL BREAKING CAPACITY
It is the rms value of the AC component of the fault current, the breaker is
capable of breaking under specified condition of recovery voltage.
ASYMMETRICAL BREAKING CAPACITY:
EEE Page 25
7/31/2019 3 Sagar
26/58
It is the rms value of the total current comprising of both AC and DC
components of the fault current that the circuit breaker can break under specified
condition of recovery voltage.
MAKING CAPACITY
The rated making current is defined as the peak value of the current
including the DC component in the first cycle at which a CB can be closed on to
a short circuit.
SHORT TIME CURRENT RATING:
The circuit breaker must be capable of carrying short circuit current for a
short period while another circuit breaker is clearing the fault. The rated short
time current is the rms value of the current that the circuit breaker can carry
safely for a specified short period.
RATED CURRENT AND FREQUENCY:
The rated current is the rms value of the current that the circuit breaker
can carry continuously without any temperature rise in excess of its specified
limit.
EEE Page 26
7/31/2019 3 Sagar
27/58
The rated frequency is also mentioned by the manufacture. It is the
frequency at which the circuit breaker has been designed to be operated. The
standard frequency is 50 Hz. If a circuit breaker is to be used at a frequency
other than its rated frequency its effect should be taken into consideration.
OPENING AND CLOSING TIME:
Closing and opening time measurement of circuit breaker is done by
using digital time internal meter.
SULPHUR HEXAFLUORIDE (SF6) CIRCUIT BREAKER:
The type of circuit breaker being used in the substation is ASIAN
BROWN BOVERI made sulphur hexafluoride (SF6) circuit breaker.
EEE Page 27
7/31/2019 3 Sagar
28/58
EXPLANATION:
Sulphur Hexafluoride (SF6) is an inert, heavy gas having good dielectric and arc
extinguishing properties. The dielectric strength of the gas increases with
pressure and is more than of dielectric strength of oil at 3 kg/cm2 SF6 is being
widely used in electrical equipment like high voltage metal enclosed cables; high
voltage metal clad switchgear, capacitors, circuit breakers, current transformers,
brushings etc., The gas is liquefied at certain low temperature, liquefaction
temperature increases with pressure.
Sulphur Hexafluoride gas is prepared by burning coarsely crushed roll sulphur in
the fluorine gas, in a steel box, provided with staggered horizontal shelves, each
EEE Page 28
7/31/2019 3 Sagar
29/58
bearing about 4 Kg of sulphur. The steel box is made gas tight. The gas thus
obtained contains other fluorides such as S2F10, SF4 and must be purified
Further SF6 gas generally supplier by chemical firms. The cost of the gas is
low if manufactured in large scale.
SF6 circuit breakers operate to switch electric circuits and equipment in and out
of the system. These circuit breakers are filled with compressed Sulphur
Hexafluoride gas which acts to open and close the switch contacts. The gas also
interrupts the current flow when the contacts are open.
During the arcing period SF6 gas is blown axially the arc. The gas removes the
heat from the arc by axial convection and radial dissipation. As a result, the arc
diameter reduces small during the decreasing mode of the current wave. The
diameter becomes small during the current zero and the arc is extinguished. Due
to its electro-negativity and low are timely constant, the SF6 gas regains its
dielectric strength is very high and the time constant is very small.
3.5 ISOLATOR
Isolating switches are employed only for isolating circuits. They ensure that the
current is not switched into the circuit until everything is in order.
Isolators or disconnecting switches are designed to operate under no load
condition. Isolators are employed in addition to circuit breaker and are provided
on each side of every CB to provide isolation. While opening a circuit the CB is
opened first, then the isolator. If an isolator is opened carelessly, when carrying
a heavy current, the resulting are could easily cause a flash over to ground. This
EEE Page 29
7/31/2019 3 Sagar
30/58
may shatter the supporting insulator and may even cause a fatal accident to the
operator particularly in HV circuit. While closing a circuit the isolator is first
closed then circuit breaker. Isolators are necessary on the supply side of the CB
in order to ensure isolation of the CB from the live parts.
Isolators employed in power system are usually three pole isolator each having
three identical poles. Each pole consists of two or three insulators posts mounted
on a fabricated support. The fixed end has moving conducting rods which swing
apart and isolation is obtained.
The simulataneous operation of three poles is obtained by mechanical inter
locking of the three poles.
There are two types of isolators which are used in this substation.
They are
Horizontal break center rotating double break isolator
Pantograph isolator.
HORIZONTAL CENTER BREAK ISOLATOR
EEE Page 30
7/31/2019 3 Sagar
31/58
In this type of construction there are two insulator stacks per pole. The two on
each side are fixed and one at the centre is rotating type. The center stacks can
swing about its vertical axis through about 90 degrees. The fixed contacts are
provided on the top of each of the insulator stacks on the side. In closed position
the contact shaft connects the two fixed contacts. While opening the central
stack rotates through 90 degrees.
PANTOGRAPH ISOLATOR:
While closing the pantograph the linkages are brought nearer by rotating the
insulator column. In closed position the upper two arms of the pantograph close
on the Over head station bus bar giving a grip. The current is carried by the
EEE Page 31
7/31/2019 3 Sagar
32/58
upper bus bar to the lower bus bar thought he conducting arms of the pantograph
isolators. While opening, the rotating insulator columns are rotated about their
axes, thereby the pantograph blades, collapse in vertical plane and vertical
isolation is obtained between the lime terminals. And pantographs isolator
covers less area. Each pole can be located at a suitable point and the three poles
need not be in one line and can be located in a line at desired angle with the bus
axis.
EEE Page 32
7/31/2019 3 Sagar
33/58
3.6 REACTORS:
Under light load or no load conditions the receiving end voltage is greater than
the sending end voltage due to capacitance effect, this is known as Ferranti
effect. To reduce this capacitance effect shunt reactors (Inductors) are placed at
the sending and receiving end terminals to absorb leading vars.
RATINGS OF 400 KV LINE REACTORS:
MAKE : BHEL, BHOPAL
CAPACITY : 63 Mvar
RATING : 420 Kv 87 A
WEIGHT : 121970 Kg.
EEE Page 33
7/31/2019 3 Sagar
34/58
WEIGHT OF OIL : 39,730 Lit
3.7 LIGHTNING ARRESTERS:
Lightning arrester is a surge diverter and is used for the protection of
power system against the high voltage surges. It is connected between the line
and earth and so diverts the incoming high voltage wave to the earth.
Lightning arresters act as safely valves designed to discharge electric
surges resulting from lightning strokes, switching or other disturbances, which
would otherwise flash over the insulators or puncture insulation, resulting in a
line outage and possible failure of equipment. They are designed to absorb
enough transient energy to prevent dangerous reflections and to cut off the flow
of power frequency
Follow current at the first current zero. After the discharge of the transient
energy, arresters have the insulation that can break down the voltage being
independent of the steepness of the wave form.
Lightning protection by means of lightning arresters and gaps and over
head ground wire is a means of reducing outage and preventing damage to the
substation equipment from lightning disturbance. The amount and kind of
protection vary in different applications.
EEE Page 34
7/31/2019 3 Sagar
35/58
The type of lightning arresters used in Kalpaka substation is HORN GAP
lightning arrester.
The horn gap consists of two horn shaped rods separated by a small
distance. One end of this connected to the line and the other to the earth with
or without a series resistance. The choke connected between the equipment
to be protected and the horn gap serves two purposes:
1. The steepness of the wave incident on the equipment to be protected
is reduced.
2. It reflects the voltage surge back on to the horn.
EEE Page 35
7/31/2019 3 Sagar
36/58
Whenever the surge voltage exceeds the breakdown value of the gap a
discharge takes place and the energy content in the rest part of the wave is
by-past to the ground. An arc is setup between the gap, which acts like a
flexible conductor and raises upwards under the influence of the
electromagnetic forces, thus increasing the length of the arc which eventually
blows out.
3.8 CURRENT TRANSFORMER:
Protective relays in AC power system are connected in the secondary
circuit of current transformer and potential transformer. The design and use
of these transformers is quite different from that of well known transformer.
In current transformer primary current is not controlled by condition of the
secondary circuit. Hence primary current is a dominant factor. The current
transformers are classified into two groups depending on the usage of
secondary.
EEE Page 36
7/31/2019 3 Sagar
37/58
Protective current transformer used in association with relay trip coil,
pilot wire etc.,
Measuring current transformer used in connection with ammeter, wattmeter
etc., as a rule, the ratio error is very important in protective current
transformer and phase angle error may be less. But current transformer and
voltage transformer comes under the INSTRUMENT TRANSFORMERS.
3.9CAPACITOR VOLTAGE TRANSFORMER:
Capacitor voltage transformer is used for line voltmeter, protective relays,
tariff meter etc,
The performance of capacitor voltage transformer is inferior to that of
electromagnetic voltage transformer. Its performance is affected by the supply
frequency, switching transient, magnitude of connected burden etc., the capacitor
EEE Page 37
7/31/2019 3 Sagar
38/58
voltage transformer is more economical than an electromagnetic voltage
transformer when the nominal system voltage increases above 66 kV.
The carrier current equipment can be connected via the capacitor of the
capacitor voltage transformers. Thereby there is no need of separate coupling
capacitors.
EEE Page 38
7/31/2019 3 Sagar
39/58
Capacitor type PT is used for voltages 66 kV and above. At such
voltages cost of electromagnetic type PTs tends to be too high. The capacitors
connected in series act like potential dividers provided the current taken by the
burden is negligible compared with the current passing through the series
connected capacitors. However, the burden current becomes relatively larger
and ratio error and phase error is introduced. Compensation is carried out by
tuning the reactor connected in series with the burden is adjustable to such a
value that at supply frequency it resonates with the sum of two capacitors. This
eliminates the error. The construction of capacitor type PT depends on the form
of capacitor voltage divider. Generally HV capacitor is enclosed in the porcelain
housing. A large sheet box at the base encloses the tuning coil intermediate
transformer.
3.10 WAVE TRAP:
Wave traps are used in power line communication. One of the devices
employed in power line carrier is the line trap, sometimes called a wave trap. A
wave trap is a parallel resonant circuit installed on the power line at a specific
frequency or frequencies. Properly tuned, the line trap shows its highest
magnitude of impedance, power frequency to pass. It is generally represented as
an inductor with a capacitor in parallel. Wave trap should be connected in series.
EEE Page 39
7/31/2019 3 Sagar
40/58
RATINGS OF WAVE TRAP:
MANUFACTURER : AREVA Transformers Pvt. Ltd.,
INDUCTANCE : 1mH
FREQUENCY : 50 Hz
WEIGHT : 195 Kg
ISC : 20 KA/Sec
IR : 800 A
3.11 EARTHING SYSTEM:
The purpose of earthing is to safe guard against dangers of shock and fire etc., It
is essential to have good and effective earthing or grounding.
Station earthing system comprises of:
Ground mat risers, earthing strips, earthing spikes.
Over head earth wires for shielding against lightning strokes or
lightning masts.
EEE Page 40
7/31/2019 3 Sagar
41/58
Galvanized steel structures or towers and gantries for support.
PLCC equipment including wave trap and tuning unit, coupling
capacitor etc.,
Power cables
Control cables for protection and control
Station lightning system.
EEE Page 41
7/31/2019 3 Sagar
42/58
PURPOSE OF EARTHING:
An electric iron is connected to supply through 3-wire cable. The line and
neutral are connected to heating element where as the earth wire is connected to
the metal frame iron. The earth terminal is connected to the neutral earthing at
substation through mass of earth. Due to insulation damage or otherwise, the
line wire touches the metal frame of the iron is effectively gets connected to the
earth, if the person holds the iron the current will not pass through his body
because the resistance of the earth wire will be les than the human body
resistance. Hence the person will be protected from electric shock. Mean while
the current will pass through the low resistance path of the earth wire is not
provided then if the live wire accidentally makes contact with the iron frame the
latter will be at the same potential as the live wire. If a person holds the iron
unknowingly, the current flows through the body of the person which is very
dangerous to life.
The non-current carrying metallic parts in the neighborhood of electrical circuits
must be earthed, which ensures safety to human life. The non-current carrying
parts include the following:
1. Motor body, switch gear metal enclosure, transformer bank, conduits of
Wiring etc.
2. Supporting structures, towers, poles etc.,
3. Sheaths of cables
4. Body of portable equipment such as iron, oven, heater, kettle etc.,
EEE Page 42
7/31/2019 3 Sagar
43/58
.
CHAPTER - 4
PROTECTION SCHEMES
EEE Page 43
7/31/2019 3 Sagar
44/58
DIFFERENT PROTECTION SCHEMES
4.1 TRANSFORMER PROTECTION
The transformer is the main equipment which has to be protected mainly
in the power system.
Types of faults subjected to transformer.
1. Through Faults:
These are due to over load condition and external short circuits. Time graded
overloaded and earth fault relays are provided for external short circuit
conditions.
2. Internal Faults:
a. Electrical Faults: The faults which causes immediate serious damage such as
line to ground faults, Line to Line fault or short circuits between transformers
HV and LV Windings.
b. Incipient Faults: Which are initially minor faults, causing slowly developing
such as poor electrical connection of conductors or breakdown of insulation.
The following are the types of relays that employed for transformer protection:
a. Buchholz relay
b. Over fluxing relay
c. Differential relay
d. Breaker failure relay
e. Restricted earth fault relay
A) BUCHHOLZ RELAY:
EEE Page 44
7/31/2019 3 Sagar
45/58
It is placed in between transformer of tank and conservator tank.
Whenever the fault on a transformer develops slowly, heat is produced locally,
which begins to decompose solid of liquid insulating materials and then to
produce inflammable gas and oil flow. Initially it sends an alarm signal
whenever a fault is detected; if the fault is left unaffected then it sends a trip
signal to the CB which opens the circuit.
SILICAGEL BREATHER:
EEE Page 45
7/31/2019 3 Sagar
46/58
Expansion and contraction of oil cause breathing action. Any humidity in
the air is absorbed by the silica get dehydrating breather. An oil seal in the air
intake prevents the external moisture being absorbed when no breathing occurs.
The breather container is filled with silica gel crystals. It is arranged such that
the air breathed must pass through it.
The desiccant is impregnated with cobalt chloride and when those Silica
gel crystals are fully active, they have deep blue colour. If colour changes to a
whitish pink, they are then saturated with moisture and the charge contained
should be replaced by a new reactivated one.
(B) DIFFERENTIAL PROTECTION:
EEE Page 46
7/31/2019 3 Sagar
47/58
The differential protection used for transformer is based on the principle
of current circulation. This type of protection is mostly used for transformers as
this respond not only to inter turn fault but also provide protection against phase-
to-phase fault.
If the current circulation principle is applied to transformer great care is to
be taken because of unequal voltage and different types of connections on the
primary and secondary sides of transformer resulting into different phase angles
and currents on both sides.
The relay use for differential protection must have time delay
characteristics in order to neutralize the unbalancing currents caused by the
switching surge of the magnetizing current. When transformer is energized that
is when the transformer is switched to supply the magnetizing currents may
assume very high values momentarily and may cause operation of relay, but such
peaks are generally transient.
The two basic requirements of differential relay connections must satisfy.
a. It must not be operated for external or load faults.
b. It must operate for internal faults.
c. The current flowing through operating coil of relay should be zero during
Normal operating condition and for external short circuit.
C. BREAKER FAILURE RELAY:
EEE Page 47
7/31/2019 3 Sagar
48/58
Main protective schemes provided for lines, transformers, generators are
required to operate and clear the fault immediately, isolating the faulty section of
the system.
It is then important than the circuit breaker operates correctly, clearing the
fault quickly by tripping. However there is risk that breaker may not trip (either
due to mechanical sluggishness or due to inability to interrupt heavy fault
current) then the fault gets cleared by backup relays at remote sections.
Increase in power system complexity demands shorter faults clearing times. It is
therefore necessary to provide breaker failure relay. This scheme will isolate the
bus to which the local breaker backup relay (LBB) is connected faster. It
comprises of over load and earth load relays with a timer. The LBB relay is
energized by trip command of main protection schemes and thus initiates master
trip relay of the bus-bar protection scheme after elapsing of defined time. Then
the entire breakers connected to the bus get tripped, thus isolating faulty element.
(D) RESTRICTED EARTH FAULT PROTECTION:
This relay is operative only for the internal faults of the transformer and
thus fast operating time can be achieved.
1. An external fault on the star side will result in current flowing in line current
transformer of the effected phase and balancing current in the neutral CT and
current in the relay is zero and hence relay is stable. During an internal fault,
the line current on the line CT gets reversed and hence relay operates.
EEE Page 48
7/31/2019 3 Sagar
49/58
2. The arrangement of residually connected CTs on the delta side of
transformer is only sensitive to earth faults on the delta side because the delta
winding blocks zero sequence currents.
(E) OVER FLUXING PROTECTION:
1. Over fluxing condition in a transformer can occur during system over voltage
and/or under frequency conditions (V/F).
2. The over fluxing condition does not call for high sped tripping. The tripping
can be delayed depending on the over flux withstand capability of transformer.
3. Relays with definite time delay (Nearly 30 sec.) and inverse characteristics
are being employed.
4.2 BUS BAR ARRANGEMENTS
In order to maintain system stability and minimize fault damage due to high fault
levels, instantaneous tripping for bus bar faults is necessary.
Bus bar protection scheme should be:
1. Completely reliable.
2. Absolutely stable for high faults
3. Selective
4. Accurate and fast operating.
GENERAL BUS BAR ARRANGEMENTS:
a. SINGLE BUS BAR ARRANGEMENTS:
EEE Page 49
7/31/2019 3 Sagar
50/58
This has only single bus bar to which all lines transformers generators etc., are
connected. In the event of the fault on the bus bar entire bus has to be de-
energized and a major outage occurs.
b. SINGLE SECTIONALISED BUS BAR SCHEME
In this, main bus is divided into two sections with a circuit breaker. One
complete section can be taken out for maintenance or for break down works
without distribution continuity of other sections.
c. MAIN AND TRANSFER BUS BAR SCHEME:
With this arrangement, any line breaker (one at a tie) requiring
maintenance can be transferred to transfer bus. The feeder protection thus gets
transferred to trip bus couple breaker. On fault occurrence or maintenance,
entire bus becomes reenergized.
d. DOUBLE BUS BAR ARRANGEMENT:
It has the flexibility of transferring any line to any of the buses. On fault
occurrences or maintenance only one bus becomes dead. While other bus
remains in service.
e. DOUBLE BUS & TRANSFER BUS BAR ARRANGEMENT:
Combination of main, transfer bus and double buses arrangement
4.3 BUS BAR PROTECTION SCHEMES
Back up protection
EEE Page 50
7/31/2019 3 Sagar
51/58
Differential over current protection
All the protection schemes must also be provided with a check system to
ensure that the protection responds only to earth faults occurring within the bus
zone not extraneous earth faults.
1) BACK UP PROTECTION
In principle it is a simplest of all to protect the buses with the aid of back
up protections of the connected supplying elements which should respond to any
fault appearing on the buses, when no separate bus protection is provided but
distance protection is provided for the feeders connected to the bus. It is possible
to cover the bus bars within zone to reach distance relays.
Distance protection is widely employed for the protection of transmission
lines. Hence it is quite economical to use the same for bus protection the draw
backs of this protection are : firstly delayed action, secondly disconnection of
more circuits in case there are two or more incoming lines and thirdly exact
discrimination not possible.
Bus back up protection may also mean that in case the breaker fails to
operate for a fault on the outgoing feeder, then it must be regarded as a bus fault.
It should then open all breakers on that bus such a backup protection can be
provided with appropriate time delay through a timer.
(2) DIFFERENTIAL OVER CURRENT PROTECTION
EEE Page 51
7/31/2019 3 Sagar
52/58
It is based on the fact that any fault within electrical equipment would cause the
current entering it to be different from the current leaving it. By comparing the
two currents either in magnitude or in phase or in both, fault can be determined.
It is an attractive option if both the ends of the apparatus are located hears each
other.
EEE Page 52
7/31/2019 3 Sagar
53/58
CHAPTER 5
AUXILIARY EQUIPMENT
EEE Page 53
7/31/2019 3 Sagar
54/58
5.1 BATTERY OPERATION AND MAINTENANCE:
In case of failure of the supply, as a backup protection for the control room a
battery room is provided within the substation for its functioning.
At KALAPAKA substation 106 batteries with 1000ampere hour rating and
220volts and it have two types of charging.
1. Boost charge
2. Float charging.
Boost charging:
When there is a sudden drop in the voltage / also when there is considerable fall
in voltage the charger with automatically switch on to boost charging mode from
float charging mode.
Float charging:
This is a constant charging mode means these batteries will be constantly being
charged. When there is no load it takes less current. And these cells have to be
charged continuously so that they will not get discharged. As these has to supply
DC supply when there is a fail in AC supply.
There are two sources of batteries SOURCE I and SOURCE II for safety and
reliability that is if one of the sources fails then immediately source II will be
connected to I and this is called DC change over contractor.
5.2 DISTURBANCE RECORDED:-
EEE Page 54
7/31/2019 3 Sagar
55/58
Behavior during recording:
The inducted 650 fault recorder continuously monitors all signals for trigger
conditions. The input values are continuously stores in a memory with the
capacity which equals the pre event history setting. Recording starts as soon as
a trigger condition exists. The even is then stored along with its pre event and
post event history.
This relay recorder is a fully electronics, digital, data acquisition module for
decentralized fault monitoring in electricity supply networks.
The indactic 650 fault recorders can either be used as a single acquisition unit
with 9 analog and 16 digital inputs, or several units may be combined possibly in
a decentralized set up, to form a logical acquisition station with a corresponding
larger number of inputs. Furthermore several such stations can be combined to
form an interconnected system. The acquisition units or stations communicate
among themselves via fast bus connections using co axial cables or fiber optic
cables.
5.3 EVENT LOGGER:
EEE Page 55
7/31/2019 3 Sagar
56/58
Function:
The sequential events recorder is a versatile high speed distributed
microprocessor based data acquisition system design to monitor and record in
real time changes of state of customer supplied field inputs with an accuracy of
one millisecond.
The event information includes alarm and return to normal status; time in hours,
minutes, seconds and milliseconds. Input address and up to 60 characters of
descriptive legends. Even t information can be recorded on a printer or printer
terminal, displayed on a CRT monitor or transmitted to a remote computer or
distributed control system via RS 232 ASC II data links.
The SER is designed for optimum versatility and flexibility and flexibility with
minimum user hardware adjustments. The equipment operating configuration is
accomplished by means of key board entries employing user friendly software
commands. In addition, the operator can print various operating and
configuration states reports and initiate a system functional test.
CONCLUSION
EEE Page 56
7/31/2019 3 Sagar
57/58
Electrical sub station consists of Transformers, bus bars, circuit breakers,
isolators, relays instrumental transformers and other equipments. The Protection
of a system is required when the short circuits and abnormal conditions often
occur on a power system.
If a fault occurs in an element of a power system an automatic protective devices
are needed to isolate the faulty element as quickly as possible to keep the healthy
section of system in normal operation.
The substation can be used for Switching Operation, Voltage Transformation
Operation, Power Converting Operation, and Power Factor Correction
Operation. The consumers can require different range of voltages for utilization,
so to achieve this sub stations are used.
The basis electrical quantities which are likely to change during the abnormal
conditions are current, voltage, phase angle and frequency. The protective relays
utilize one or more of these quantities to detect the abnormal conditions on a
power system.
Different types of protection schemes were employed for protection of
transformers, bus bars and equipment in substation. All schemes must to used
different types of protective relays.
BIBLIOGRAPHY
EEE Page 57
7/31/2019 3 Sagar
58/58
Text book of power system engineering
M.L.Soni Gupta Bhatnagar, TataMc GrawHill publisher
Electrical power system
J.B. Gupta Khanna Publishers
ABB Relays manual
Protection system 400kv substation manual
http://en.wikipedia.org.