+ All Categories

3 Sagar

Date post: 05-Apr-2018
Category:
Upload: surya-teja
View: 213 times
Download: 0 times
Share this document with a friend

of 58

Transcript
  • 7/31/2019 3 Sagar

    1/58

    ABSTRACT

    Power is an essential requirement for all facets of our life and has been

    recognized as a basic human need. It is the critical infrastructure on which the

    socio economic development of the country depends. the growth of the

    economy and its global competitiveness hinges on the availability of reliable and

    quality power at competitive rates. The demand power is enormous and is

    growing steadily. In order to meet this demand, the power generating stations

    have to transmit the power, which are located at hundreds of kilometers from the

    load centers and due to these long distances we have to place the intermediate

    substation in order to reduce the losses and to increase maximum power transfer

    in the lines.

    The generation for electricity in power generating station is done in

    faraway places from consumers & load centers for various reasons reasons. The

    generated voltage is stepped up at some places and stepped down at some places

    i.e. at 11kv, 33kv it is stepped up to 132, 220, 400kv and transmitted to various

    loads. at load centers the high voltage is stepped down to 11kv or 440 / 220v and

    distributed to consumer. These voltage transformations are carried out at sub

    stations.

    The main equipment in substation is transformer, bus section, circuit

    breaker, line going out of the substation. The protective relaying is necessary

    with almost every electrical substation and no part of the substation is left

    EEE Page 1

  • 7/31/2019 3 Sagar

    2/58

    unprotected. The choice of protection depends on different aspects such as type,

    rating and protection equipment, location and cost.

    The protection relaying scheme senses the abnormal condition of the

    substation. Transient stability can be improved by means of protective relaying.

    Faults cannot be avoided completely but they can be minimized. Hence relays

    can play an important role in minimizing the faults.

    In this project, we give an insight o the substation. it consists of various

    fields which have been elaborated in a detailed manner. The necessity of a

    substation, its features, classifications, specifications are dealt. The various

    equipments used in a substation are explained.

    EEE Page 2

  • 7/31/2019 3 Sagar

    3/58

    CHAPTER 1

    INTRODUCTION

    EEE Page 3

  • 7/31/2019 3 Sagar

    4/58

    Andhra Pradesh Transmission Corporation Ltd., has a great significance

    of transmitting bulk power from four decades for which they have constructed

    number of substations. Transmission substation is located between generating

    power station and distribution substations.

    Visakhapatnam consists of National thermal power corporation Ltd.,

    Known as Simhadhri power plant. The plant generates 2*500MW power. This

    total power is utilized in Andhra Pradesh only. So, AP TRANSCO established a

    400 / 200kv transmission substation at KALAPAKA near NTPC.

    This substation has been inaugurated by Honorable Former chief minister

    Shri Nara Chandrababu Naidu in 2002. The substation is in collaboration with

    J.B.I.C a Japanese company. The substation is spread over vast area of about 70

    acres and the yard length is 900mts. According to area the substation is the

    second largest in ASIA.

    The equipment in this substation like transformers are manufactured by

    CROMPTON GREAVES, Circuit breakers and Relays are manufactured by

    ASIA BROWN BOVERI LTD.

    It is feeded from NTPC by four incoming lines. The power is transmitted

    to Vemagiri, Khammam and Power Grid. The 400kv is step down to 220kv and

    transmits to Visakha dairy farm and Vizag switching station.

    ORGANISATION OF THE MINI PROJECT REPORT:-

    EEE Page 4

  • 7/31/2019 3 Sagar

    5/58

    The work presented in this report is organized in the following manner.

    Chapter 2 deals with the (400/220 KV) substation which includes

    introduction to substation, its necessity, classifications on various bases,

    specifications, essential features & necessary structures within the

    substation. The layout of 400/200KV Kalapaka substation is also

    presented.

    Chapter 3 deals with various elements that are used in the substation.

    The substation equipment comprises of transformers, circuit breakers,

    relays, lightning arresters, isolators, reactors, current transformers,

    capacitor voltage transformers, wave trap, earthing system etc., the

    ratings & specifications of the equipment used in Kalapaka substation

    are also mentioned.

    Chapter 4 deals with various protection schemes employed for the

    protection of transformers & bus bars. The protection schemes for the

    transformers includes buchholz relay, differential protection, over

    fluxing protection, breaker failure relay protection & restricted earth

    fault protection. The bus bar arrangements & protection schemes

    includes back up protection & differential over current protection.

    Chapter 5 deals with the various auxiliary equipments used in the

    kalapaka substation. The auxiliary equipment includes battery operation

    and maintenance, disturbance recorded & event logger.

    EEE Page 5

  • 7/31/2019 3 Sagar

    6/58

    CHAPTER 2

    400 / 220 KV

    SUBSTATION

    EEE Page 6

  • 7/31/2019 3 Sagar

    7/58

    2.1 INTRODUCTION

    The assembly of apparatus used to change some characteristics (i.e., voltage A.C.

    to D.C., frequency, power factor) of electric supply is called a substation. An

    electrical substation is a subsidiary station of a electricity generation,

    transmission and distribution system where voltage is transformed from high to

    low or the reverser using transformers. Electric power may flow through several

    substations between generating plant and consumer, and may be changed in

    voltage in several steps.

    There are several substations between generating station and final load points

    Electrical substation receives power from the incoming lines and the power is

    transferred at desired voltage by the transformer and is then supplied to the

    outgoing lines.

    The electrical sub stations at the various locations in network differ greatly in

    their sizes, design, configuration and appearance. There are different works done

    in a substation.

    Switching Operation

    Voltage Transformation Operation

    Power Converting Operation

    Power Factor Correction Operation.

    EEE Page 7

  • 7/31/2019 3 Sagar

    8/58

    2.2 NECESSITY:

    Between the generation of power and consumer point, transmission and

    distribution exists. Generating stations are designed for generating bulk amount

    of power and the Transmission takes place at high voltages to reduce the line

    losses, where as consumer points are at low voltage. This high voltage is stepped

    down to a lower voltage at different stages with the help of transformer and

    switchgear in the substation.

    2.3 CLASSIFICATION OF SUBSTATION.

    The substation may be classified in numerous ways on the basis of

    Nature of Duties

    Service Rendered

    Operating Voltage

    Importance

    Design

    BASED ON THE NATURE OF DUTIES:

    The substation based on the nature of duties may be classified into three types.

    Step Up or Primary Substations

    Primary Grid Substations

    Step Down or Distribution Substations

    EEE Page 8

  • 7/31/2019 3 Sagar

    9/58

    BASED ON THE NATURE OF OPERATING VOLTAGES:

    High voltage Substation

    Extra High Voltage Substation

    Ultra High Voltage Substation

    BASED ON SERVICE RENDERED:

    Transformer Substation

    Switching Substation

    Converting Substation

    BASED ON DESIGN:

    Indoor Type Substation

    Out Door Type Substation.

    2.4 SPECIFICATIONS:

    Specifications of substation denote the design requirement rating, technical

    aspects regarding the substation and its associated electrical, mechanical, civil

    and auxiliary sub system.

    The sub stations are planned on the basis of economic, electrical and local

    conditions at the project planning stage.

    The substation requirements are influenced by network requirement in several

    aspects including the following.

    1. Insulation levels and insulation coordination

    2. Fault levels and their coordination

    3. Voltage control requirement of the network

    4. Clearance and creep age distances

    EEE Page 9

  • 7/31/2019 3 Sagar

    10/58

    5. Network monitoring and data communication between substation and

    load dispatch centers.

    6. Back up protection main protection zones maintenance zones

    7. Switching sequence during normal emergency and post fault conditions.

    ESSENTIAL FEATURES:

    An AC substation has following parts.

    AC switch yard

    Control building

    Low voltage and medium voltage AC system for auxiliaries

    DC battery system and low voltage distribution system

    Station mechanical, electrical and other auxiliaries

    Civil work.

    2.5 LAYOUT OF KALAPAKA SUBSTATION:

    The first step in planning a substation layout is the preparation of a one line

    diagram which shows in simplified from the switching and protection

    arrangement required, as well as the incoming supply lines and outgoing feeders

    or transmission lines. It is a usual practice by many electrical utilities to prepare

    one line diagrams with principal elements (lines, switches, circuit breakers, and

    transformers) arranged on the page similarly to the way the apparatus would be

    laid out in the actual station.

    EEE Page 10

  • 7/31/2019 3 Sagar

    11/58

    2.6 NECESSARY STRUCTURES:

    The following structures are necessary in a conventional open terminal outdoor

    substation.

    Towers of incoming and outgoing transmission lines :

    These are generally located outside the substation boundary adjacent to

    the substation.

    Tower and gantries for supporting strain insulators and flexible bus

    bar :

    These are used for mounting isolator, surge arrester and other equipment

    suitable.

    Towers and gaintries for supporting rigid tabular bus bar mounted

    on post insulator.

    The insulators are supported on horizontal beams. Supporting structures

    of post insulator also support the tubular rigid bus bar, CTs, VTs,

    insulators, CB and lime traps etc.,

    EEE Page 11

  • 7/31/2019 3 Sagar

    12/58

    CHAPTER 3

    ELEMENTS OF SUBSTATION

    EEE Page 12

  • 7/31/2019 3 Sagar

    13/58

    3.1 INTRODUCTION:

    Substations generally have switching, protection and control equipment

    and one or more transformers. In a large substation, circuit breakers are used to

    interrupt any short-circuits or overload currents that may occur on the network.

    Smaller distribution stations may use recloser circuit breakers or fuses for

    protection of distribution circuits. Substations do not usually have generators,

    although a power plant may have a substation nearby. Other devices such as

    power factor correction capacitors and voltage regulators may also be located at

    a substation.

    Substations may be on the surface in fenced enclosures, underground, or

    located in special-purpose buildings. High-rise buildings may have several

    indoor substations. Indoor substations are usually found in urban areas to reduce

    the noise from the transformers, for reasons of appearance, or to protect

    switchgear from extreme climate or pollution conditions.

    Where a substation has a metallic fence, it must be properly grounded to

    protect people from high voltages that may occur during a fault in the network.

    Earth faults at a substation can cause a ground potential rise. Currents flowing in

    the Earths surface during a fault can cause metal objects to have a significantly

    different voltage than the ground under a persons feet; this tough potential

    presents a hazard of electrocution.

    EEE Page 13

  • 7/31/2019 3 Sagar

    14/58

    3.2. TRANSFORMER:

    A Transformer is a static piece of apparatus by means of which electric

    power in one circuit is transferred to another circuit without change in frequency.

    The Transformer works on the principle of mutual inductance between

    two circuits linked by a common magnetic flux.

    Basically Transformers are of two types : ---

    Core type

    Shell type

    CORE TYPE: The winding surrounds a considerable part of the core.

    SHELL TYPE: The core surrounds a considerable portion of the winding.

    EEE Page 14

  • 7/31/2019 3 Sagar

    15/58

    RATING OF A TRANSFORMER:

    The mostly used power transformers in A.P. Region are

    1. 400/220 KV 316 MVA Auto transformer

    2. 220/132 KV 100 MVA Auto transformer

    3. 220/33 KV 50 & 31.5 MVA transformer

    4. 132/66 KV 40 & 27.5 MVA transformer

    5. 132/33 KV 50, 31.5, 25, 16, 15 MVA transformers

    6. 132/11 IV 16, 15 & 7.5 MVA transformers

    7. 33/11 KV 8, 5, 3, 15 MVA transformers.

    Most of the Power Transformer are of 132/11 KV and above are of star-

    star vector grouping with the neutral solidly earthern.

    In substation Auto transformers are preferred over two winding

    transformer.

    AUTO TRANSFORMER:

    A transformer, in which a part of the winding is common to both the

    primary and secondary circuits, is called an auto-transformer. In a two winding

    transformer, primary and secondary windings are electrically isolated, but in an

    auto-transformer the two windings are not electrically isolated.

    EEE Page 15

  • 7/31/2019 3 Sagar

    16/58

    RATINGS OF AUTO-TRANSFORMER:

    MAKE : M/s. CROMPTION GREAVES LIMITED, MUMBAI

    CAPACITY : 315 MVA

    RATING : 400/220/33 KV

    WEIGHT : 273000 Kg.

    WEIGHT OF OIL : 80,600 Lit.

    EEE Page 16

  • 7/31/2019 3 Sagar

    17/58

    ADVANTAGES OF AUTO TRANSFORMER:

    1. The weight of the (copper and aluminums) for any winding depends

    Upon the cross sectional area and length of the conductor. Hence for

    an auto transformer the weight and cost of the conductor required is

    less compared to two winding transformer.

    2. Owing to the reduction in conductor and core materials, the ohmic

    losses in conductor and the core losses re lowered. Therefore, an auto

    transformer has higher efficiency than a two winding transformer of

    the same output.

    3. Reduction in the conductor material means lower value of ohmic

    resistance. A part of the winding being common, leakage flux and

    therefore, leakage reactance is less. In other words, an auto

    transformer has lower value of leakage impedance and has superior

    voltage regulation then a two-winding transformer of the same output.

    3.3 RELAYS:

    A relay is an electrically operated switch. Many relays use an

    electromagnet to operate a switching mechanism, but other operating principles

    are also used. Relays find applications where it is necessary to control a circuit

    by a low-power signal, or where several circuits must be controlled by one

    signal. Solid state relays control power circuits with no moving parts, instead

    using a semiconductor device to perform switching. Relays with calibrated

    operating characteristics and sometimes multiple operating coils are used to

    EEE Page 17

  • 7/31/2019 3 Sagar

    18/58

    protect electrical circuits from overload or faults; in modern electric power

    systems these functions are performed by digital instruments still called

    protection relays

    Transistor relays are the most widely use static relays. In fact, when we

    talk of static relay we generally mean transistor relays. The fact that the

    transistor can be used both as an amplifying device and a switching device

    makes this component suitable for achieving any functional characteristics.

    The advantages of transistor relays can be summarized as follows:

    1. The power consumption is low and hence provides less burden on CT and

    PT as compare to the conventional electromechanical relays.

    2. The relays are fast in operation.

    3. No moving parts hence friction or contact troubles are absent and as a

    result minimum maintenance is required.

    4. The relays have greater sensitivity as amplication of signals can be obtainvery easily.

    5. The relays has a high reset to pick up and the reset is very quick.

    6. The use of printed circuits avoids wiring error and facilitates

    rationalization of batch production.

    7. It is possible to obtain wide range of characteristics approaching more or

    less to the ideal requirements.

    OPERATION:

    When a current flows through the coil, the resulting magnetic field

    attracts an armature that is mechanically linked to a moving contact. The

    movement either makes or breaks a connection with a fixed contact. When the

    current to the coil is switched off, the armature is returned by a force

    approximately half as strong as the magnetic force to its relaxed position.

    EEE Page 18

  • 7/31/2019 3 Sagar

    19/58

    Usually this is a spring, but gravity is also used commonly in industrial motor

    starters. Most relays are manufactured to operate quickly. In a low voltage

    application, this is to reduce noise. In a high voltage or high current application,

    this is to reduce arcing. If the coil is energized with DC, a diode is frequently

    installed across the coil, to dissipate the energy from the collapsing magnetic

    field at deactivation, which would otherwise generate a spike of voltage and

    might cause damage to circuit components. If the coil is designed to reenergized

    with AC, a small copper ring can be crimped to the end of the solenoid. This

    shading ring creates a small out of-phase current, which increases the minimum

    pull on the armature during the AC Cycle.

    By analogy with the functions of the original electromagnetic device, a

    solid stage relay is made with a thyristor or other solid-stage switching device.

    To achieve electrical isolation, a light emitting diode (LED) is used with a photo

    transistor.

    The type of relays used in Kalapaka substation is distance relays (REL 316

    and REL 100).

    DISTANCE RELAY

    The impedance relays also called distance relays are employed to provide

    protection to transmission lines connected in a network as they are economic and

    possess several technical advantages. They are comparatively simple to apply.

    Operate with extremely high speed and both primary and backup protection

    features are inherent in them with power line carrier facilities and are suitable for

    high sped re-closing. The impedance relay is made to respond to the impedance

    EEE Page 19

  • 7/31/2019 3 Sagar

    20/58

    between the relay location and the point where fault is incident. The impedance

    is proportional to the fault, and is therefore independent of the fault current

    levels.

    DISTANCE RELAYING PRINCIPLE

    A distance relay compares the currents and voltages at the relaying points with

    current providing the operating torque and the voltage provides the restraining

    torque. In other words an impedance relay is a voltage restrained over current

    relay.

    Since the operating characteristics of the relay depend upon the ratio of voltage

    and current and the phase angle between them their characteristics can be best

    represented on an R-X Diagram where both V/I ratio and phase angle can be

    plotted in terms of an impedance R + JX. Future the power system impedance,

    loads, power swings etc., can also be plotted on the same R- X diagram.

    Therefore response of a particular relay during power swing faults and other

    system disturbances can easily be assessed.

    TYPES OF DISTANCE RELAY:

    1. Impedance relay

    2. Reactance relay

    3. Mho relay

    4. Modified impedance relay

    EEE Page 20

  • 7/31/2019 3 Sagar

    21/58

    IMPEDANCE RELAY:

    Operation of the impedance relay is independent of the phase angle between

    V and I the operating characteristics is a circle with its center at the origin

    and hence the relay is non-direction.

    THE REACTANCE RELAY

    Reactance relay measures V/I sin O whenever the reactance measured by the

    relay is less than the set value the relay operates.

    EEE Page 21

  • 7/31/2019 3 Sagar

    22/58

    The resistance component of impedance has no effect on the operation of the

    reactance relay. The relay responds solely to reactance component of

    impedance. This relay is inherently non-directional. The relay is most suitable

    to detect earth faults where the effect of are resistance is applicable.

    MHO RELAY:

    This is a directional impedance relay, also known as admittance relay. Its

    characteristics on R-X diagram is a circle whose circumference passes

    through the origin. This relay is inherently directional and it only operates

    for fault in the forward direction.

    MODIFIED IMPEDANCE RELAY:

    EEE Page 22

  • 7/31/2019 3 Sagar

    23/58

    This is also known as mho relay whose characteristics enclose the origin on

    R-X.

    This off set mho relay has three main applications:

    Bus-bar zone

    Carrier starting unit in distance/carrier blocking schemes

    Power swing blocking

    3.4. CIRCUIT BREAKER

    The function of the circuit breaker is to isolate the faulty part of the power

    system in case of abnormal conditions.

    A circuit breaker has two contacts, a fixed contact and a moving contact. Under

    normal conditions these two contacts remain in closed position. When the circuit

    breaker is required to isolate the faulty part, the moving contact moves away to

    interrupt the circuit by separating the contacts. The flow of current is interrupted

    results in the formation of arc between the contacts. The contacts are placed in a

    closed chamber containing some insulation medium which extinguishes the arc.

    ARC INTERRUPTION:

    These are two methods of arc interruption:

    1. High resistance interruption.

    2. Current zero interruption

    HIGH RESISTANCE INTERRUPTION:

    EEE Page 23

  • 7/31/2019 3 Sagar

    24/58

    In this method of arc interruption its resistance is increased so as to reduce the

    current to a value in sufficient to maintain the arc. The arc resistance can be

    increased by cooling, lengthening, constraining and splitting the arc. This

    method is not suitable for large current interruption.

    CURRENT ZERO INTERRUPTION:

    In case of AC supply the current passes through a zero point 100 times per sec at

    the supply frequency of 50 Hz. This feature of arc is utilized for arc interruption.

    The current is not interrupted at any point other than the zero current instant,

    otherwise a high transient voltage will occur across the contact gap.

    RESTRIKING VOLTAGE AND RECOVERY VOLTAGES

    After the arc has extinguished the voltage across the breaker terminals do not

    normalize instantaneously but it oscillates and there is a transient condition. The

    transient voltage which appears across the breaker contact at the instant of arc

    being extinguished is known as restriking voltage. The power frequency runs

    voltage which appears across the arc is finally extinguished and transient

    oscillations die out is called recovery voltage.

    CLASSIFICATION OF CIRCUIT BREAKER:

    EEE Page 24

  • 7/31/2019 3 Sagar

    25/58

    Depending on the arc quenching medium employed the following are important

    types of circuit breaker.

    1. Oil circuit breaker

    2. Air blast circuit breaker

    3. Sulphur hexa fluoride circuit breaker

    4. Vacuum circuit breaker

    RATING OF CIRCUIT BREAKER

    Circuit breakers have the following important ratings.

    1. Breaking capacity

    2. Making capacity

    3. Short time capacity

    BREAKING CAPACITY

    The braking capacity of the circuit breaker is of two types

    1. Symmetrical breaking capacity

    2. Asymmetrical breaking capacity

    SYMMETRICAL BREAKING CAPACITY

    It is the rms value of the AC component of the fault current, the breaker is

    capable of breaking under specified condition of recovery voltage.

    ASYMMETRICAL BREAKING CAPACITY:

    EEE Page 25

  • 7/31/2019 3 Sagar

    26/58

    It is the rms value of the total current comprising of both AC and DC

    components of the fault current that the circuit breaker can break under specified

    condition of recovery voltage.

    MAKING CAPACITY

    The rated making current is defined as the peak value of the current

    including the DC component in the first cycle at which a CB can be closed on to

    a short circuit.

    SHORT TIME CURRENT RATING:

    The circuit breaker must be capable of carrying short circuit current for a

    short period while another circuit breaker is clearing the fault. The rated short

    time current is the rms value of the current that the circuit breaker can carry

    safely for a specified short period.

    RATED CURRENT AND FREQUENCY:

    The rated current is the rms value of the current that the circuit breaker

    can carry continuously without any temperature rise in excess of its specified

    limit.

    EEE Page 26

  • 7/31/2019 3 Sagar

    27/58

    The rated frequency is also mentioned by the manufacture. It is the

    frequency at which the circuit breaker has been designed to be operated. The

    standard frequency is 50 Hz. If a circuit breaker is to be used at a frequency

    other than its rated frequency its effect should be taken into consideration.

    OPENING AND CLOSING TIME:

    Closing and opening time measurement of circuit breaker is done by

    using digital time internal meter.

    SULPHUR HEXAFLUORIDE (SF6) CIRCUIT BREAKER:

    The type of circuit breaker being used in the substation is ASIAN

    BROWN BOVERI made sulphur hexafluoride (SF6) circuit breaker.

    EEE Page 27

  • 7/31/2019 3 Sagar

    28/58

    EXPLANATION:

    Sulphur Hexafluoride (SF6) is an inert, heavy gas having good dielectric and arc

    extinguishing properties. The dielectric strength of the gas increases with

    pressure and is more than of dielectric strength of oil at 3 kg/cm2 SF6 is being

    widely used in electrical equipment like high voltage metal enclosed cables; high

    voltage metal clad switchgear, capacitors, circuit breakers, current transformers,

    brushings etc., The gas is liquefied at certain low temperature, liquefaction

    temperature increases with pressure.

    Sulphur Hexafluoride gas is prepared by burning coarsely crushed roll sulphur in

    the fluorine gas, in a steel box, provided with staggered horizontal shelves, each

    EEE Page 28

  • 7/31/2019 3 Sagar

    29/58

    bearing about 4 Kg of sulphur. The steel box is made gas tight. The gas thus

    obtained contains other fluorides such as S2F10, SF4 and must be purified

    Further SF6 gas generally supplier by chemical firms. The cost of the gas is

    low if manufactured in large scale.

    SF6 circuit breakers operate to switch electric circuits and equipment in and out

    of the system. These circuit breakers are filled with compressed Sulphur

    Hexafluoride gas which acts to open and close the switch contacts. The gas also

    interrupts the current flow when the contacts are open.

    During the arcing period SF6 gas is blown axially the arc. The gas removes the

    heat from the arc by axial convection and radial dissipation. As a result, the arc

    diameter reduces small during the decreasing mode of the current wave. The

    diameter becomes small during the current zero and the arc is extinguished. Due

    to its electro-negativity and low are timely constant, the SF6 gas regains its

    dielectric strength is very high and the time constant is very small.

    3.5 ISOLATOR

    Isolating switches are employed only for isolating circuits. They ensure that the

    current is not switched into the circuit until everything is in order.

    Isolators or disconnecting switches are designed to operate under no load

    condition. Isolators are employed in addition to circuit breaker and are provided

    on each side of every CB to provide isolation. While opening a circuit the CB is

    opened first, then the isolator. If an isolator is opened carelessly, when carrying

    a heavy current, the resulting are could easily cause a flash over to ground. This

    EEE Page 29

  • 7/31/2019 3 Sagar

    30/58

    may shatter the supporting insulator and may even cause a fatal accident to the

    operator particularly in HV circuit. While closing a circuit the isolator is first

    closed then circuit breaker. Isolators are necessary on the supply side of the CB

    in order to ensure isolation of the CB from the live parts.

    Isolators employed in power system are usually three pole isolator each having

    three identical poles. Each pole consists of two or three insulators posts mounted

    on a fabricated support. The fixed end has moving conducting rods which swing

    apart and isolation is obtained.

    The simulataneous operation of three poles is obtained by mechanical inter

    locking of the three poles.

    There are two types of isolators which are used in this substation.

    They are

    Horizontal break center rotating double break isolator

    Pantograph isolator.

    HORIZONTAL CENTER BREAK ISOLATOR

    EEE Page 30

  • 7/31/2019 3 Sagar

    31/58

    In this type of construction there are two insulator stacks per pole. The two on

    each side are fixed and one at the centre is rotating type. The center stacks can

    swing about its vertical axis through about 90 degrees. The fixed contacts are

    provided on the top of each of the insulator stacks on the side. In closed position

    the contact shaft connects the two fixed contacts. While opening the central

    stack rotates through 90 degrees.

    PANTOGRAPH ISOLATOR:

    While closing the pantograph the linkages are brought nearer by rotating the

    insulator column. In closed position the upper two arms of the pantograph close

    on the Over head station bus bar giving a grip. The current is carried by the

    EEE Page 31

  • 7/31/2019 3 Sagar

    32/58

    upper bus bar to the lower bus bar thought he conducting arms of the pantograph

    isolators. While opening, the rotating insulator columns are rotated about their

    axes, thereby the pantograph blades, collapse in vertical plane and vertical

    isolation is obtained between the lime terminals. And pantographs isolator

    covers less area. Each pole can be located at a suitable point and the three poles

    need not be in one line and can be located in a line at desired angle with the bus

    axis.

    EEE Page 32

  • 7/31/2019 3 Sagar

    33/58

    3.6 REACTORS:

    Under light load or no load conditions the receiving end voltage is greater than

    the sending end voltage due to capacitance effect, this is known as Ferranti

    effect. To reduce this capacitance effect shunt reactors (Inductors) are placed at

    the sending and receiving end terminals to absorb leading vars.

    RATINGS OF 400 KV LINE REACTORS:

    MAKE : BHEL, BHOPAL

    CAPACITY : 63 Mvar

    RATING : 420 Kv 87 A

    WEIGHT : 121970 Kg.

    EEE Page 33

  • 7/31/2019 3 Sagar

    34/58

    WEIGHT OF OIL : 39,730 Lit

    3.7 LIGHTNING ARRESTERS:

    Lightning arrester is a surge diverter and is used for the protection of

    power system against the high voltage surges. It is connected between the line

    and earth and so diverts the incoming high voltage wave to the earth.

    Lightning arresters act as safely valves designed to discharge electric

    surges resulting from lightning strokes, switching or other disturbances, which

    would otherwise flash over the insulators or puncture insulation, resulting in a

    line outage and possible failure of equipment. They are designed to absorb

    enough transient energy to prevent dangerous reflections and to cut off the flow

    of power frequency

    Follow current at the first current zero. After the discharge of the transient

    energy, arresters have the insulation that can break down the voltage being

    independent of the steepness of the wave form.

    Lightning protection by means of lightning arresters and gaps and over

    head ground wire is a means of reducing outage and preventing damage to the

    substation equipment from lightning disturbance. The amount and kind of

    protection vary in different applications.

    EEE Page 34

  • 7/31/2019 3 Sagar

    35/58

    The type of lightning arresters used in Kalpaka substation is HORN GAP

    lightning arrester.

    The horn gap consists of two horn shaped rods separated by a small

    distance. One end of this connected to the line and the other to the earth with

    or without a series resistance. The choke connected between the equipment

    to be protected and the horn gap serves two purposes:

    1. The steepness of the wave incident on the equipment to be protected

    is reduced.

    2. It reflects the voltage surge back on to the horn.

    EEE Page 35

  • 7/31/2019 3 Sagar

    36/58

    Whenever the surge voltage exceeds the breakdown value of the gap a

    discharge takes place and the energy content in the rest part of the wave is

    by-past to the ground. An arc is setup between the gap, which acts like a

    flexible conductor and raises upwards under the influence of the

    electromagnetic forces, thus increasing the length of the arc which eventually

    blows out.

    3.8 CURRENT TRANSFORMER:

    Protective relays in AC power system are connected in the secondary

    circuit of current transformer and potential transformer. The design and use

    of these transformers is quite different from that of well known transformer.

    In current transformer primary current is not controlled by condition of the

    secondary circuit. Hence primary current is a dominant factor. The current

    transformers are classified into two groups depending on the usage of

    secondary.

    EEE Page 36

  • 7/31/2019 3 Sagar

    37/58

    Protective current transformer used in association with relay trip coil,

    pilot wire etc.,

    Measuring current transformer used in connection with ammeter, wattmeter

    etc., as a rule, the ratio error is very important in protective current

    transformer and phase angle error may be less. But current transformer and

    voltage transformer comes under the INSTRUMENT TRANSFORMERS.

    3.9CAPACITOR VOLTAGE TRANSFORMER:

    Capacitor voltage transformer is used for line voltmeter, protective relays,

    tariff meter etc,

    The performance of capacitor voltage transformer is inferior to that of

    electromagnetic voltage transformer. Its performance is affected by the supply

    frequency, switching transient, magnitude of connected burden etc., the capacitor

    EEE Page 37

  • 7/31/2019 3 Sagar

    38/58

    voltage transformer is more economical than an electromagnetic voltage

    transformer when the nominal system voltage increases above 66 kV.

    The carrier current equipment can be connected via the capacitor of the

    capacitor voltage transformers. Thereby there is no need of separate coupling

    capacitors.

    EEE Page 38

  • 7/31/2019 3 Sagar

    39/58

    Capacitor type PT is used for voltages 66 kV and above. At such

    voltages cost of electromagnetic type PTs tends to be too high. The capacitors

    connected in series act like potential dividers provided the current taken by the

    burden is negligible compared with the current passing through the series

    connected capacitors. However, the burden current becomes relatively larger

    and ratio error and phase error is introduced. Compensation is carried out by

    tuning the reactor connected in series with the burden is adjustable to such a

    value that at supply frequency it resonates with the sum of two capacitors. This

    eliminates the error. The construction of capacitor type PT depends on the form

    of capacitor voltage divider. Generally HV capacitor is enclosed in the porcelain

    housing. A large sheet box at the base encloses the tuning coil intermediate

    transformer.

    3.10 WAVE TRAP:

    Wave traps are used in power line communication. One of the devices

    employed in power line carrier is the line trap, sometimes called a wave trap. A

    wave trap is a parallel resonant circuit installed on the power line at a specific

    frequency or frequencies. Properly tuned, the line trap shows its highest

    magnitude of impedance, power frequency to pass. It is generally represented as

    an inductor with a capacitor in parallel. Wave trap should be connected in series.

    EEE Page 39

  • 7/31/2019 3 Sagar

    40/58

    RATINGS OF WAVE TRAP:

    MANUFACTURER : AREVA Transformers Pvt. Ltd.,

    INDUCTANCE : 1mH

    FREQUENCY : 50 Hz

    WEIGHT : 195 Kg

    ISC : 20 KA/Sec

    IR : 800 A

    3.11 EARTHING SYSTEM:

    The purpose of earthing is to safe guard against dangers of shock and fire etc., It

    is essential to have good and effective earthing or grounding.

    Station earthing system comprises of:

    Ground mat risers, earthing strips, earthing spikes.

    Over head earth wires for shielding against lightning strokes or

    lightning masts.

    EEE Page 40

  • 7/31/2019 3 Sagar

    41/58

    Galvanized steel structures or towers and gantries for support.

    PLCC equipment including wave trap and tuning unit, coupling

    capacitor etc.,

    Power cables

    Control cables for protection and control

    Station lightning system.

    EEE Page 41

  • 7/31/2019 3 Sagar

    42/58

    PURPOSE OF EARTHING:

    An electric iron is connected to supply through 3-wire cable. The line and

    neutral are connected to heating element where as the earth wire is connected to

    the metal frame iron. The earth terminal is connected to the neutral earthing at

    substation through mass of earth. Due to insulation damage or otherwise, the

    line wire touches the metal frame of the iron is effectively gets connected to the

    earth, if the person holds the iron the current will not pass through his body

    because the resistance of the earth wire will be les than the human body

    resistance. Hence the person will be protected from electric shock. Mean while

    the current will pass through the low resistance path of the earth wire is not

    provided then if the live wire accidentally makes contact with the iron frame the

    latter will be at the same potential as the live wire. If a person holds the iron

    unknowingly, the current flows through the body of the person which is very

    dangerous to life.

    The non-current carrying metallic parts in the neighborhood of electrical circuits

    must be earthed, which ensures safety to human life. The non-current carrying

    parts include the following:

    1. Motor body, switch gear metal enclosure, transformer bank, conduits of

    Wiring etc.

    2. Supporting structures, towers, poles etc.,

    3. Sheaths of cables

    4. Body of portable equipment such as iron, oven, heater, kettle etc.,

    EEE Page 42

  • 7/31/2019 3 Sagar

    43/58

    .

    CHAPTER - 4

    PROTECTION SCHEMES

    EEE Page 43

  • 7/31/2019 3 Sagar

    44/58

    DIFFERENT PROTECTION SCHEMES

    4.1 TRANSFORMER PROTECTION

    The transformer is the main equipment which has to be protected mainly

    in the power system.

    Types of faults subjected to transformer.

    1. Through Faults:

    These are due to over load condition and external short circuits. Time graded

    overloaded and earth fault relays are provided for external short circuit

    conditions.

    2. Internal Faults:

    a. Electrical Faults: The faults which causes immediate serious damage such as

    line to ground faults, Line to Line fault or short circuits between transformers

    HV and LV Windings.

    b. Incipient Faults: Which are initially minor faults, causing slowly developing

    such as poor electrical connection of conductors or breakdown of insulation.

    The following are the types of relays that employed for transformer protection:

    a. Buchholz relay

    b. Over fluxing relay

    c. Differential relay

    d. Breaker failure relay

    e. Restricted earth fault relay

    A) BUCHHOLZ RELAY:

    EEE Page 44

  • 7/31/2019 3 Sagar

    45/58

    It is placed in between transformer of tank and conservator tank.

    Whenever the fault on a transformer develops slowly, heat is produced locally,

    which begins to decompose solid of liquid insulating materials and then to

    produce inflammable gas and oil flow. Initially it sends an alarm signal

    whenever a fault is detected; if the fault is left unaffected then it sends a trip

    signal to the CB which opens the circuit.

    SILICAGEL BREATHER:

    EEE Page 45

  • 7/31/2019 3 Sagar

    46/58

    Expansion and contraction of oil cause breathing action. Any humidity in

    the air is absorbed by the silica get dehydrating breather. An oil seal in the air

    intake prevents the external moisture being absorbed when no breathing occurs.

    The breather container is filled with silica gel crystals. It is arranged such that

    the air breathed must pass through it.

    The desiccant is impregnated with cobalt chloride and when those Silica

    gel crystals are fully active, they have deep blue colour. If colour changes to a

    whitish pink, they are then saturated with moisture and the charge contained

    should be replaced by a new reactivated one.

    (B) DIFFERENTIAL PROTECTION:

    EEE Page 46

  • 7/31/2019 3 Sagar

    47/58

    The differential protection used for transformer is based on the principle

    of current circulation. This type of protection is mostly used for transformers as

    this respond not only to inter turn fault but also provide protection against phase-

    to-phase fault.

    If the current circulation principle is applied to transformer great care is to

    be taken because of unequal voltage and different types of connections on the

    primary and secondary sides of transformer resulting into different phase angles

    and currents on both sides.

    The relay use for differential protection must have time delay

    characteristics in order to neutralize the unbalancing currents caused by the

    switching surge of the magnetizing current. When transformer is energized that

    is when the transformer is switched to supply the magnetizing currents may

    assume very high values momentarily and may cause operation of relay, but such

    peaks are generally transient.

    The two basic requirements of differential relay connections must satisfy.

    a. It must not be operated for external or load faults.

    b. It must operate for internal faults.

    c. The current flowing through operating coil of relay should be zero during

    Normal operating condition and for external short circuit.

    C. BREAKER FAILURE RELAY:

    EEE Page 47

  • 7/31/2019 3 Sagar

    48/58

    Main protective schemes provided for lines, transformers, generators are

    required to operate and clear the fault immediately, isolating the faulty section of

    the system.

    It is then important than the circuit breaker operates correctly, clearing the

    fault quickly by tripping. However there is risk that breaker may not trip (either

    due to mechanical sluggishness or due to inability to interrupt heavy fault

    current) then the fault gets cleared by backup relays at remote sections.

    Increase in power system complexity demands shorter faults clearing times. It is

    therefore necessary to provide breaker failure relay. This scheme will isolate the

    bus to which the local breaker backup relay (LBB) is connected faster. It

    comprises of over load and earth load relays with a timer. The LBB relay is

    energized by trip command of main protection schemes and thus initiates master

    trip relay of the bus-bar protection scheme after elapsing of defined time. Then

    the entire breakers connected to the bus get tripped, thus isolating faulty element.

    (D) RESTRICTED EARTH FAULT PROTECTION:

    This relay is operative only for the internal faults of the transformer and

    thus fast operating time can be achieved.

    1. An external fault on the star side will result in current flowing in line current

    transformer of the effected phase and balancing current in the neutral CT and

    current in the relay is zero and hence relay is stable. During an internal fault,

    the line current on the line CT gets reversed and hence relay operates.

    EEE Page 48

  • 7/31/2019 3 Sagar

    49/58

    2. The arrangement of residually connected CTs on the delta side of

    transformer is only sensitive to earth faults on the delta side because the delta

    winding blocks zero sequence currents.

    (E) OVER FLUXING PROTECTION:

    1. Over fluxing condition in a transformer can occur during system over voltage

    and/or under frequency conditions (V/F).

    2. The over fluxing condition does not call for high sped tripping. The tripping

    can be delayed depending on the over flux withstand capability of transformer.

    3. Relays with definite time delay (Nearly 30 sec.) and inverse characteristics

    are being employed.

    4.2 BUS BAR ARRANGEMENTS

    In order to maintain system stability and minimize fault damage due to high fault

    levels, instantaneous tripping for bus bar faults is necessary.

    Bus bar protection scheme should be:

    1. Completely reliable.

    2. Absolutely stable for high faults

    3. Selective

    4. Accurate and fast operating.

    GENERAL BUS BAR ARRANGEMENTS:

    a. SINGLE BUS BAR ARRANGEMENTS:

    EEE Page 49

  • 7/31/2019 3 Sagar

    50/58

    This has only single bus bar to which all lines transformers generators etc., are

    connected. In the event of the fault on the bus bar entire bus has to be de-

    energized and a major outage occurs.

    b. SINGLE SECTIONALISED BUS BAR SCHEME

    In this, main bus is divided into two sections with a circuit breaker. One

    complete section can be taken out for maintenance or for break down works

    without distribution continuity of other sections.

    c. MAIN AND TRANSFER BUS BAR SCHEME:

    With this arrangement, any line breaker (one at a tie) requiring

    maintenance can be transferred to transfer bus. The feeder protection thus gets

    transferred to trip bus couple breaker. On fault occurrence or maintenance,

    entire bus becomes reenergized.

    d. DOUBLE BUS BAR ARRANGEMENT:

    It has the flexibility of transferring any line to any of the buses. On fault

    occurrences or maintenance only one bus becomes dead. While other bus

    remains in service.

    e. DOUBLE BUS & TRANSFER BUS BAR ARRANGEMENT:

    Combination of main, transfer bus and double buses arrangement

    4.3 BUS BAR PROTECTION SCHEMES

    Back up protection

    EEE Page 50

  • 7/31/2019 3 Sagar

    51/58

    Differential over current protection

    All the protection schemes must also be provided with a check system to

    ensure that the protection responds only to earth faults occurring within the bus

    zone not extraneous earth faults.

    1) BACK UP PROTECTION

    In principle it is a simplest of all to protect the buses with the aid of back

    up protections of the connected supplying elements which should respond to any

    fault appearing on the buses, when no separate bus protection is provided but

    distance protection is provided for the feeders connected to the bus. It is possible

    to cover the bus bars within zone to reach distance relays.

    Distance protection is widely employed for the protection of transmission

    lines. Hence it is quite economical to use the same for bus protection the draw

    backs of this protection are : firstly delayed action, secondly disconnection of

    more circuits in case there are two or more incoming lines and thirdly exact

    discrimination not possible.

    Bus back up protection may also mean that in case the breaker fails to

    operate for a fault on the outgoing feeder, then it must be regarded as a bus fault.

    It should then open all breakers on that bus such a backup protection can be

    provided with appropriate time delay through a timer.

    (2) DIFFERENTIAL OVER CURRENT PROTECTION

    EEE Page 51

  • 7/31/2019 3 Sagar

    52/58

    It is based on the fact that any fault within electrical equipment would cause the

    current entering it to be different from the current leaving it. By comparing the

    two currents either in magnitude or in phase or in both, fault can be determined.

    It is an attractive option if both the ends of the apparatus are located hears each

    other.

    EEE Page 52

  • 7/31/2019 3 Sagar

    53/58

    CHAPTER 5

    AUXILIARY EQUIPMENT

    EEE Page 53

  • 7/31/2019 3 Sagar

    54/58

    5.1 BATTERY OPERATION AND MAINTENANCE:

    In case of failure of the supply, as a backup protection for the control room a

    battery room is provided within the substation for its functioning.

    At KALAPAKA substation 106 batteries with 1000ampere hour rating and

    220volts and it have two types of charging.

    1. Boost charge

    2. Float charging.

    Boost charging:

    When there is a sudden drop in the voltage / also when there is considerable fall

    in voltage the charger with automatically switch on to boost charging mode from

    float charging mode.

    Float charging:

    This is a constant charging mode means these batteries will be constantly being

    charged. When there is no load it takes less current. And these cells have to be

    charged continuously so that they will not get discharged. As these has to supply

    DC supply when there is a fail in AC supply.

    There are two sources of batteries SOURCE I and SOURCE II for safety and

    reliability that is if one of the sources fails then immediately source II will be

    connected to I and this is called DC change over contractor.

    5.2 DISTURBANCE RECORDED:-

    EEE Page 54

  • 7/31/2019 3 Sagar

    55/58

    Behavior during recording:

    The inducted 650 fault recorder continuously monitors all signals for trigger

    conditions. The input values are continuously stores in a memory with the

    capacity which equals the pre event history setting. Recording starts as soon as

    a trigger condition exists. The even is then stored along with its pre event and

    post event history.

    This relay recorder is a fully electronics, digital, data acquisition module for

    decentralized fault monitoring in electricity supply networks.

    The indactic 650 fault recorders can either be used as a single acquisition unit

    with 9 analog and 16 digital inputs, or several units may be combined possibly in

    a decentralized set up, to form a logical acquisition station with a corresponding

    larger number of inputs. Furthermore several such stations can be combined to

    form an interconnected system. The acquisition units or stations communicate

    among themselves via fast bus connections using co axial cables or fiber optic

    cables.

    5.3 EVENT LOGGER:

    EEE Page 55

  • 7/31/2019 3 Sagar

    56/58

    Function:

    The sequential events recorder is a versatile high speed distributed

    microprocessor based data acquisition system design to monitor and record in

    real time changes of state of customer supplied field inputs with an accuracy of

    one millisecond.

    The event information includes alarm and return to normal status; time in hours,

    minutes, seconds and milliseconds. Input address and up to 60 characters of

    descriptive legends. Even t information can be recorded on a printer or printer

    terminal, displayed on a CRT monitor or transmitted to a remote computer or

    distributed control system via RS 232 ASC II data links.

    The SER is designed for optimum versatility and flexibility and flexibility with

    minimum user hardware adjustments. The equipment operating configuration is

    accomplished by means of key board entries employing user friendly software

    commands. In addition, the operator can print various operating and

    configuration states reports and initiate a system functional test.

    CONCLUSION

    EEE Page 56

  • 7/31/2019 3 Sagar

    57/58

    Electrical sub station consists of Transformers, bus bars, circuit breakers,

    isolators, relays instrumental transformers and other equipments. The Protection

    of a system is required when the short circuits and abnormal conditions often

    occur on a power system.

    If a fault occurs in an element of a power system an automatic protective devices

    are needed to isolate the faulty element as quickly as possible to keep the healthy

    section of system in normal operation.

    The substation can be used for Switching Operation, Voltage Transformation

    Operation, Power Converting Operation, and Power Factor Correction

    Operation. The consumers can require different range of voltages for utilization,

    so to achieve this sub stations are used.

    The basis electrical quantities which are likely to change during the abnormal

    conditions are current, voltage, phase angle and frequency. The protective relays

    utilize one or more of these quantities to detect the abnormal conditions on a

    power system.

    Different types of protection schemes were employed for protection of

    transformers, bus bars and equipment in substation. All schemes must to used

    different types of protective relays.

    BIBLIOGRAPHY

    EEE Page 57

  • 7/31/2019 3 Sagar

    58/58

    Text book of power system engineering

    M.L.Soni Gupta Bhatnagar, TataMc GrawHill publisher

    Electrical power system

    J.B. Gupta Khanna Publishers

    ABB Relays manual

    Protection system 400kv substation manual

    http://en.wikipedia.org.


Recommended