Use this drawing when: Deploying Motor Control Centers in an existing structured network to provide simplicity and robustness. D C B A D C B A 4 3 2 1 4 3 2 1 Motor Control Center (Cabling Subsystems 3-0) PCD0012-JUNE18-ENG Motor Control Center (MCC) with DIN Rail Industrial Patch Panel Mounted in Pathway, Enabling Ethernet Devices Across Multiple Sections UPS MCCs were Ethernet-enabled by means of industrial switches. Due to the high noise and voltage environment of the MCC, Panduit presents the industrial DIN rail- mounted 8 port patch panel assembled with two loomed pre- terminated cable bundles. This innovative solution removes the consideration for noise and voltage by centrally locating the switch in an Integrated Network Zone System, Industrial Distribution Frame or Micro Data center and enables a structured infrastructure deployment. To Zone / IDF / MDC, see separate pages for more. IndustrialNet Category 5e Shielded 600V-Rated Patch Cord
Transcript
Page 1: 4 3 2 1 Motor Control Center (MCC) with DIN Rail Industrial Patch … › content › dam › panduit › en › solutions › ... · 2018-07-03 · 4 3 2 1 4 3 2 1 Motor Control

Use this drawing when: Deploying Motor Control Centers

in an existing structured network to provide simplicity and robustness.

D

C

B

A

D

C

B

A

4 3 2 1

4 3 2 1

Motor Control Center

(Cabling Subsystems 3-0)PCD0012-JUNE18-ENG

Motor Control Center (MCC) with DIN Rail Industrial Patch Panel Mounted in

Pathway, Enabling Ethernet Devices Across Multiple Sections

1 2 3 5 6 74

+ - + + --INP SEN OUT GND

MOD

NET

CHG

PWR

1

0

CON

8 9

10

UPSMaintenance-free No battery 24VDC

MCC s were Ethernet-enabled by

means of industrial switches.

Due to the high noise and voltage

environment of the MCC, Panduit

presents the industrial DIN rail-

mounted 8 port patch panel

assembled with two loomed pre-

terminated cable bundles.

This innovative solution removes the

consideration for noise and voltage

by centrally locating the switch in an

Integrated Network Zone System,

Industrial Distribution Frame or Micro Data center and enables a

structured infrastructure

deployment.

To Zone / IDF / MDC, see separate pages for more.

IndustrialNet Category 5e

Shielded 600V-Rated

Patch Cord

Page 2: 4 3 2 1 Motor Control Center (MCC) with DIN Rail Industrial Patch … › content › dam › panduit › en › solutions › ... · 2018-07-03 · 4 3 2 1 4 3 2 1 Motor Control

Use this drawing when: Deploying Motor Control Centers

in an existing structured network to provide simplicity and robustness.

D

C

B

A

4 3 2 1

D

C

B

A

4 3 2 1

Motor Control Center

(Cabling Subsystems 2-0)PCD0012-JUNE18-ENG

MODE

Catalyst 3750-X Series

BLANK

MODULEFN

SYSTCONSOLE XPS STAT SPEED DUPLX

S-PWR MAST STACK

Catalyst 3750-X Series

1 2 3 4 5 6 7 8 9 10 11 12

MODE

Catalyst 3750-X Series

BLANK

MODULEFN

SYSTCONSOLE XPS STAT SPEED DUPLX

S-PWR MAST STACK

Catalyst 3750-X Series

1 2 3 4 5 6 7 8 9 10 11 12

Smart-UPS

1 0 0 0

TestI

O

www.apcc.com

Catalyst 2960-S Series

49 50 51 52

MGMT

BASET

CONSOLE

37X

38X

47X

48X

37 38 39 40 41 42 43 44 45 46 47 48

25X

26X

35X

36X

25 26 27 28 29 30 31 32 33 34 35 36

13X

14X

23X

24X

13 14 15 16 17 18 19 20 21 22 23 241 2 3 4 5 6 7 8 9 10 11 12

PoE

STCK

SPED

DPLX

STAT

MSTR

RPS

SYST

MODE

1X

2X

11X

12X

11

12

23

24

12

13

14

11

12

23

24

12

13

14

UPS

Pre-Configured Industrial

Distribution Frame (IDF) is

engineered to deploy and protect

rack mount switches in industrial

applications, providing faster

installation times.

OM3 Indoor Fiber Cable

Wyr-Grid,

Electro Zinc plated

This page presents a Motor Control Center (MCC) deployment that isrouted back to a Industrial Distribution Frame (IDF), while also presenting three

options of cable routing.

1 2 3 5 6 74

+ - + + --INP SEN OUT GND

MOD

NET

CHG

PWR

1

0

CON

8 9

10

UPSMaintenance-free No battery 24VDC

Options for Cable Routing

Wyr-Grid

J-Pro Hooks

Conduit

IndustrialNet

8-Port DIN Mount

Copper Patch Panel

Grounding and Bonding

Mini-Com TX6A 10Gig

Shielded Jack Modules

Pre-configured MCC cable

bundle pre-terminated w/

RJ45 jack modules(Recommendation: If bundle

will be in close proximity to

power cables select a 600V

rated cable option.)

Page 3: 4 3 2 1 Motor Control Center (MCC) with DIN Rail Industrial Patch … › content › dam › panduit › en › solutions › ... · 2018-07-03 · 4 3 2 1 4 3 2 1 Motor Control

Use this drawing when: Deploying Motor Control Centers

in an existing structured network to provide simplicity and robustness.

D

C

B

A

4 3 2 1

D

C

B

A

4 3 2 1

Motor Control Center

(Cabling Subsystems 2-0)PCD0012-JUNE18-ENG

This page presents a Motor Control Center (MCC) deployment that isrouted back to a Network Zone System with two industrial switches, while also

presenting three options of cable routing.

24" x 36" Network Zone System

with industrial switches each with 2

1Gb MM fiber optic uplinks,

redundant 100-250Vac power

supply input and UPS pre-installed.

Wyr-Grid,Electro Zinc plated

1 2 3 5 6 74

+ - + + --INP SEN OUT GND

MOD

NET

CHG

PWR

1

0

CON

8 9

10

UPSMaintenance-free No battery 24VDC

Options for Cable Routing

Wyr-Grid

J-Pro Hooks

Conduit

12

34

56

78

91

01

11

21

31

41

51

61

71

81

92

02

12

22

32

4

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

+ + - -

24-28V

DCon

®

N LAC 100-240V

1606-XLE80E

1606-XLE

+ + - -

24-28V

DCon

®

N LAC 100-240V

1606-XLE80E

1606-XLE

+ + - -

24-28V

DC ok

®

N L

InputAC 100-240V

1606-XLS240E

1606-XLS

OVL

DC ok

+ -

!

TM

1

2

4

3 8

7

Tecnology

2

1 6

5

Con

sole

DC -Pwr B

DC +

Major Alarm

DC -Pwr A

DC +

Major Alarm

!

TM

1

2

4

3 8

7

Tecnology

2

1 6

5

Con

sole

DC -Pwr B

DC +

Major Alarm

DC -Pwr A

DC +

Major Alarm

IndustrialNet

8-Port DIN Mount

Copper Patch Panel

OM3 Indoor Fiber Cable

Grounding and Bonding

Mini-Com TX6A 10Gig

Shielded Jack Modules

Pre-configured MCC cable

bundle pre-terminated w/

RJ45 jack modules(Recommendation: If bundle

will be in close proximity to

power cables select a 600V

rated cable option.)

Page 4: 4 3 2 1 Motor Control Center (MCC) with DIN Rail Industrial Patch … › content › dam › panduit › en › solutions › ... · 2018-07-03 · 4 3 2 1 4 3 2 1 Motor Control

Use this drawing when: Deploying Motor Control Centers

in an existing structured network to provide simplicity and robustness.

D

C

B

A

4 3 2 1

D

C

B

A

4 3 2 1

Motor Control Center

(Cabling Subsystems 3-0)PCD0012-JUNE18-ENG

Pre-configured Micro Data Center,

24 RU, includes two side panels,

network cabling, patch panels,

cable management, grounding,

casters, shock pallet and ramp

Panduit Wyr-Grid,

Electro Zinc plated

This page presents a Motor Control Center (MCC) deployment that isrouted back to a Micro Data Center (MDC), while also presenting three options of

cable routing.

1 2 3 5 6 74

+ - + + --INP SEN OUT GND

MOD

NET

CHG

PWR

1

0

CON

8 9

10

UPSMaintenance-free No battery 24VDC

Options for Cable Routing

Wyr-Grid

J-Pro Hooks

Conduit

IndustrialNet

8-Port DIN Mount

Copper Patch Panel

21

16

11

6

1

24

23

22

20

19

18

17

15

14

13

12

10

9

8

7

5

4

3

2

21

16

11

6

1

24

23

22

20

19

18

17

15

14

13

12

10

9

8

7

5

4

3

2

OUTPUT 30A

200-240V~

G(Hi-pot)

CIRCUITBREAKER200-240V~

20A

CIRCUITBREAKER200-240V~

20A

RO

O

OUTPUT 20A 200-240V~OUTPUT 20A 200-240V~

BATTERYCONNECTOR180V33A

OR

RS

232

CO

NT

AC

TS

RP

OB

AT

TE

RY

DE

TE

CT

ION

( )+ ( )-( )

OFF

ON

OFF

20

ON

20

NO

RM

AL

AC

SO

UR

CE

OU

TP

UT

OUTPUT

NORMAL AC SOURCE

1200W AC

1200W ACM

SS

PC

Ie 4

5

PC

Ie 5

PC

Ie 6

12

PC

Ie 1

PC

Ie 2

PC

Ie 3

1

2

PSU

MLOM

4321

MODE

Catalyst 3750-X Series

BLANK

MODULE1X

2X

11X

12X

13X

14X

FN

SYSTCONSOLE XPS STAT SPEED DUPLX

S-PWR MAST STACK

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

HDMI HDMI

ee e e ee e e

AC

DC

AC

DC

MODE

Catalyst 3750-X Series

BLANK

MODULE1X

2X

11X

12X

13X

14X

FN

SYSTCONSOLE XPS STAT SPEED DUPLX

S-PWR MAST STACK

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1200W AC

1200W ACM

SS

PC

Ie 4

5

PC

Ie 5

PC

Ie 6

12

PC

Ie 1

PC

Ie 2

PC

Ie 3

1

2

PSU

MLOM

4321

1200W AC

1200W ACM

SS

PC

Ie 4

5

PC

Ie 5

PC

Ie 6

12

PC

Ie 1

PC

Ie 2

PC

Ie 3

1

2

PSU

MLOM

4321

OM3 Indoor Fiber Cable

Mini-Com TX6A 10Gig

Shielded Jack Modules

Grounding and Bonding products

Pre-configured MCC cable

bundle pre-terminated w/

RJ45 jack modules(Recommendation: If bundle

will be in close proximity to

power cables select a 600V

rated cable option.)

Page 5: 4 3 2 1 Motor Control Center (MCC) with DIN Rail Industrial Patch … › content › dam › panduit › en › solutions › ... · 2018-07-03 · 4 3 2 1 4 3 2 1 Motor Control

For more information contact your local distributor, Panduit Sales Representative, or the Panduit Industrial Network Infrastructure team at [email protected].

Part Number Description

I4JPBJLU* Category 6A, plenum motor control center cabling bundle system

I4KOTJLUX* Category 6A, outdoor motor control center cabling bundle system

CDPP8RGIndustrialNet, 8-port DIN rail mount patch panel. Includes screws to

attach faceplate and Ultimate ID labels and clear label covers.

CADIN1IG

Mini-Com DIN Rail Mount Adapter mounts to standard 35mm DIN

rail and accepts any single port Mini-Com Module, international gray.

Includes a label and label cover.

ISFCH6X04ATL-UGCopper Cable, Industrial, Cat 6A 4-pair, 24/7 AWG Stranded,

SF/UTP, CMR, 600V rated, Oil Res., UV Res.,Tea

FOPPX12Y50um OM3 12 Fiber Indoor Armored Cable, Plenum (OFCP), 900um

buffered fibers

ISTPHCH2MTLPatch cord, IndustrialNet, category 5e, shielded, 600V, RJ45 plug to

RJ45 plug, teal, 2 meter.

CJS6X88TGYCategory 6A, RJ45, 10 Gb/s, 8-position, 8-wire universal shielded

black module with integral shield.

JP2SBC50-L20

J-Pro Cable support system, with screw-on beam clamp for use with

flanges up to 1/2 (12.7mm) thick, 2.00 (50.8mm) max. bundle

capacity, nylon 6.6 with metal attachments, black.

WG12BL10 12" W x 10' L Wyr-Grid pathway section

HLB2S-C0Tak-Ty hook & loop stacked strip cable tie, 7.0 (178mm) length, 0.75

(19.1mm) width, nylon loop, polyethylene hook, black

Z23**

Pre-Configured Network Zone System, 24" x 36", mild steel

enclosure, for two industrial switches, includes (16) Cat 6 UTP

copper patch cords and jacks, (4) MM LC fiber patch cords with (6)

adaptors, backplane and cable management.

ZDF48-RAPre-configured Industrial Distribution Frame enclosure ready for two

access and two distribution switches.

MDC***

Pre-Configured Micro Data Center, includes two side panels,

network cabling, patch panels, cable management, grounding,

casters, shock pallet and ramp.

For an expanded product offering visit panduit.com/networkpartsamerica or the online catalog

at panduit.com.

Motor Control Center

Cabling, Connectors and Pathways

Network Zone System, Industrial Distribution Center and Micro Data Center

**Network Zone Enclosures available in mild steel, stainless steel or sloped versions and

various levels of integration.

***Micro Data Centers available in 24 and 42 RU versions with various add-on kits.

*Motor Control Center Cable Bundles available in a variety of loom options, termination ends

and overwrap options.

Bill of Materials


Recommended