    GENERAL + MEANS OF ESCAPE (Part One)

    By Mdm Eng Yew Hoon

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    3/42

    OLD CLAUSE

    A space mainly used as means ofaccess between a room or protectedshaft and an exit from the building orcompartment

    Chapter 1 : Definitionsclause 1.2.10 : circulation space

    AMENDED CLAUSE

    A space mainly used as means of accessbetween a room or protected shaft andan exit from the building orcompartment. It shall not contain any

    commercial activity such asinformation and reception counter,exhibition and the like.

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    4/42

    Chapter 1 : Definitionsclause 1.2.10 : circulation space

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    5/42

    OLD CLAUSE

    A storey of the building withhabitable room. A habitable roommeans any room not less than 6.5 m2in area and does not include any

    bathroom, water-closet, openverandah, terrace, garage and liftmotor room

    Chapter 1 : Definitionsclause 1.2.36 : habitable floor

    AMENDED CLAUSE

    A floor or part thereof, including rooflevel, regardless whether it is openedto sky or not, designated to be used forany purpose/activity other than

    housing lift motors, fire pumps, watersupply pumps, cooling towers andwater tanks. Such purpose/activityshall include terrace, garden andplayground and other M & E plants.

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    6/42

    NOT HABITABLE FLOOR

    Chapter 1 : Definitionsclause 1.2.36 : habitable floor

    HABITABLE FLOOR

    By introducing a strip ofroof garden has changed

    a non habitable roof to

    habitable roof

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    7/42

    OLD CLAUSE

    The "occupant load" of a building or partthereof means the total number of personsthat may occupy such building or part thereofat any one time.

    The "occupant load" shall be establishedeither:

    (a) by applying to the floor areas availablefor occupation based on the appropriateareas per person as laid down in Table 1.2A,or

    (b) by the actual number of occupants forwhom each occupied space of the building isdesigned as shown on the plans,

    whichever is greater unless otherwisepermitted by the Relevant Authority

    Chapter 1 : Definitionsclause 1.2.45 : occupancy load

    AMENDED CLAUSE

    The "occupant load" of a building or partthereof means the total number of personsthat may occupy such building or partthereof at any one time.

    The occupant load shall be established

    either:(a) by applying to the floor areas availablefor occupation based on the appropriateareas per person as laid down in Table1.2A, or

    (b) by the actual number of occupants for

    whom each occupied space of the buildingis designed as shown on the plans,

    whichever is greater unless otherwisepermitted by the Relevant Authority. or bythe number of fixed seating, ifapplicable, for Assembly Occupancies.

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    8/42

    FOR LOOSE SEATINGS

    The "occupant load" shall beestablished by applying to the floorareas available for occupation basedon the appropriate areas per person aslaid down in Table 1.2A

    Chapter 1 : Definitionsclause 1.2.45 : occupancy load

    FOR FIXED SEATINGS

    Occupant load can be established bynumber of fixed seats for assemblyoccupancies only (eg. Auditorium)

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    9/42

    OLD TABLE

    Factory as defined in the Factories Act,(Chapter 104), 1973

    Chapter 1 : DefinitionsTable 1.2A: v- Factory

    AMENDED TABLE

    A factory refers to any industrialpremises with manufacturing,processing, servicing or testing activities

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    10/42

    OLD CLAUSE

    Entry at every storey level to an exit

    staircase of any building or part of a

    building of more than four storeys above

    ground level shall be through:

    (a) ..

    (b) Smoke-stop lobby

    Chapter 2 : Means of Escapeclause 2.2.13(b) : Smoke Free approach to exit staircase

    AMENDED CLAUSE

    Entry at every storey level (including 1st

    storey) to an exit staircase of any building or

    part of a building of more than four storeys

    above ground level shall be through:

    (a) ..

    (b) Smoke-stop lobby

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    11/42

    Chapter 2 : Means of Escapeclause 2.2.13(b) : Smoke Free approach to exit staircase

    AMENDED CLAUSE

    Entry at every storey level (including 1st storey) to an exit staircase of any building orpart of a building of more than four storeys above ground level shall be through:

    (a) ..

    (b) Smoke-stop lobby

    StaircaseA

    StaircaseB

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    12/42

    OLD CLAUSE

    Chapter 2 : Means of Escapeclause 2.2.13(b) : Smoke Free approach to exit staircase

    AMENDED CLAUSE

    Over looked by QP

    1st storey 1st storey

    Smoke StopLobby

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    13/42

    OLD CLAUSE

    Entry at every storey level to an exit staircase of anybuilding or part of a building of more than fourstoreys above ground level shall be through:

    (a) ..

    (b) Smoke-stop lobby

    a lobby that is separated from the adjoining areas ofthe building by a wall having a fire resistance of atleast 1 hour. The exit access door shall have fireresistance of at least half an hour fitted withautomatic self-closing device conforming to therequirements of Cl.3.9.2. The design of asmoke-stop lobby must be such as not to impedemovement of occupants through the escape route.

    The floor area of a smoke-stop lobby shall be notless than 3m and if a smoke-stop lobby also servesas a fire fighting lobby, the floor area shall be notsmaller than 6m and with no dimension smallerthan 2m. The floor shall be graded from the lift doortowards the lobby door with a fall not exceeding 1 in200.

    Chapter 2 : Means of Escapeclause 2.2.13 : Smoke Free approach to exit staircase

    AMENDED CLAUSE

    Entry at every storey level (including 1st storey) to anexit staircase of any building or part of a building ofmore than four storeys above ground level shall bethrough:

    (a) ..

    (b) Smoke-stop lobby

    a lobby that is separated from the adjoining areas ofthe building by a wall having a fire resistance ofat least1 hour. The exit access door shall have fire resistance ofat least half an hour fitted with automatic self-closingdevice conforming to the requirements of Cl.3.9.2. Thedesign of a smoke-stop lobby must be such as not toimpede movement of occupants through the escape

    route. The floor area of a smoke-stop lobby shall be notless than 3m and if a smoke-stop lobby also serves as afire-fighting lobby, the floor area shall be not smallerthan 6 m and with no dimension smaller than 2m. Thefloor shall be graded from the lift door towards thelobby door with a fall not exceeding 1 in 200.

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    14/42

    OLD CLAUSE

    A smoke-stop lobby shall be ventilated by:

    (i) permanent fixed ventilation openings

    in the external wall of the lobby; such

    ventilation openings shall have an area of

    not less than 15% of the floor area of thelobby and located not more than 9m from

    any part of the lobby, or

    Chapter 2 : Means of Escapeclause 2.2.13(b)(i) : Smoke-stop lobby ventilation

    AMENDED CLAUSE

    A smoke-stop lobby shall be ventilated by:

    (i) permanent fixed ventilation openings in theexternal wall of the lobby; such ventilationopenings shall have an area of not less than 15 percent of the floor area of the lobby and located not

    more than 9m from an air-well or externalrecessed space of minimum clear area 93m andminimum width of 6m. The air-well or externalrecessed space shall have no obstructionvertically throughout the air space forventilation; or

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    15/42

    Chapter 2 : Means of Escapeclause 2.2.13(b)(i) : Smoke-stop lobby ventilation

    Air well 6m & area >93m2)Constitute effectiveventilation for smokefree lobby

    Ventilationopening 15%lobby area

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    16/42

    OLD CLAUSE

    A smoke-stop lobby shall be ventilated by:

    (ii) mechanical ventilation complying with

    the requirements in Chapter 7, or

    Chapter 2 : Means of Escapeclause 2.2.13(b)(ii) : Smoke-stop lobby ventilation

    AMENDED CLAUSE

    A smoke-stop lobby shall be ventilated by:

    (ii) mechanical ventilation, except for PurposeGroup II, complying with the requirements inChapter 7, or

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    17/42

    OLD CLAUSE

    A smoke-stop lobby shall be ventilated by:

    (iv) cross-ventilated corridor having fixed

    ventilation openings in at least two

    external walls. The openings to each part

    of the external walls shall not be less than50 per cent of the superficial area of the

    wall enclosing the corridors. No part of

    the floor area of the corridor shall be at a

    distance of more than 13m from any

    ventilation openings.

    Chapter 2 : Means of Escapeclause 2.2.13(b)(iv) : Smoke-stop lobby ventilation

    AMENDED CLAUSE

    A smoke-stop lobby shall be ventilated by:

    (iv) cross-ventilated corridor having fixedventilation openings in at least two opposingexternal walls. The openings to each part of theexternal walls shall not be less than 50 per cent of

    the superficial area of the opposing external wallswall enclosing the corridors. No part of the floorarea of the corridor shall be at a distance of morethan 13m from any ventilation openings.

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    18/42

    Chapter 2 : Means of Escapeclause 2.2.13(b)(iv) : Smoke-stop lobby ventilation

    AMENDED CLAUSE

    A smoke-stop lobby shall beventilated by:

    (iv) cross-ventilated corridorhaving fixed ventilationopenings in at least two

    opposingexternal walls. Theopenings to each part of theexternal walls shall not be lessthan 50 per cent of thesuperficial area of the opposingexternal walls wall enclosingthe corridors. No part of the

    floor area of the corridor shallbe at a distance of more than13m from any ventilationopenings.

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    19/42

    Chapter 2 : Means of Escapeclause 2.2.13(b)(iv) : Smoke-stop lobby ventilation

    Unit 2

    Unit 3

    Unit 1

    Unit 4

    Unit 5

    Unit 6

    Unit 7

    Not having fixed ventilationopenings in at least twoopposingexternal walls

    Not to be considered ascross ventilation

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    20/42

    Chapter 2 : Means of Escapeclause 2.2.13(b)(iv) : Smoke-stop lobby ventilation

    Acceptableas crossventilated

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    21/42

    Chapter 2 : Means of Escapeclause 2.2.13(b)(iv) : Smoke-stop lobby ventilation

    Not Acceptableas crossventilated

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    22/42

    Chapter 2 : Means of Escapeclause 2.3.3(a): Internal Exit Staircases

    OLD CLAUSE

    Cl.2.3.3 (a) Internal exit staircase

    (i) ..

    (ii) ..

    (iii) Unprotected openings

    there shall be no unprotectedopenings of occupancy area within

    1.5m horizontally or within 3mvertically below any part of theventilation openings located in theexternal wall of the internal exitstaircase.

    AMENDED CLAUSE

    Cl.2.3.3 (a) Internal exit staircase

    (i) ..

    (ii) ..

    (iii) Unprotected openings

    there shall be no unprotected openingsof occupancy area within 1.5m

    horizontally or within 3m verticallybelow any part of the ventilationopenings including final dischargeopenings located in the external wall ofthe internal exit staircase.

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    23/42

    Chapter 2 : Means of Escapeclause 2.3.3(a): Internal Exit Staircases

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    24/42

    Chapter 2 : Means of Escapeclause 2.3.3(c)(i): Discharge

    OLD CLAUSEAll exit staircases shall discharge at groundlevel directly into a safe exterior openspace. However, in sprinkler protectedbuilding, maximum 50% of the totalbuilding exits may be allowed to dischargedirectly to the ground level circulationspace subject to the following:

    (i) The discharge point of the exit staircaseshall be at a location in the circulationspace at ground level within sight of andwith direct access to a safe exterior openspace; and

    (ii) The maximum distance between the

    discharge point of an exit staircase and theexterior open space shall not exceed 10m.

    (iii) The clear width of the exit doorsleading to the safe exterior open spaceshall be adequate to receive the occupantload in the 1st storey circulation space andthe total number of people dischargingfrom the internal exit staircases.

    AMENDED CLAUSE(i) All exit staircases shall discharge at ground level directly into a

    safe exterior space opened to the sky. Open-sided externalcorridor which does not have any commercial activity and notmore than 5m measured to the building eave line shall beconsidered as safe exterior open space . In a sprinklerprotected building, maximum 50% of the total number of exitstaircase is allowed to be discharged directly to the ground levelcovered circulation space subject to the following:

    (1) The discharge point of the exit staircase into the ground levelcirculation space shallbe within sight of and with direct access to asafe exterior open space; and

    (2) The maximum distance between the discharge point of an exitstaircase and the exterior open space opened to the skyshall notexceed 10m; and

    (3) Where there are commercial activities e.g. shops or kiosks/cartslocated along one side or both sides of the designated escapepassageway leading to the safe exterior open space, a minimumseparation distance of 10m shall be maintained between the

    commercial activities and the designated escape passageway.The circulation space shall also be installed with engineeredsmoke control system. Alternatively the commercial activitiesshall be fire compartmented with walls and doors of minimumone-hour fire resistance rating.

    (4) The clear width of the exit doors leading to the safe exterior openspace shall be adequate to receive the occupant load in the 1ststorey circulation space and the total number of people dischargingfrom the internal exit staircases >>>>>

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    25/42

    Chapter 2 : Means of Escapeclause 2.3.3(c )(i): Discharge

    AMENDED CLAUSE(i) All exit staircases shall discharge

    at ground level directly into a safeexterior space opened to thesky. Open-sided externalcorridor which does not have any

    commercial activity and notmore than 5m measured to thebuilding eave line shall beconsidered as safe exterior openspace. In a sprinklerprotected building, maximum50% of the total number of exit

    staircase is allowed to bedischarged directly to the groundlevel covered circulation spacesubject to the following:

    >>>>>

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    26/42

    Chapter 2 : Means of Escapeclause 2.3.3(c )(i): Discharge

    AMENDED CLAUSEground level covered circulation space subjectto the following:

    (1) The discharge point of the exit staircase into the groundlevel circulation space shallbe within sight of and withdirect access to a safe exterior open space; and

    (2) The maximum distance between the discharge point of anexit staircase and the exterior open space opened to the

    skyshall not exceed 10m; and

    (3) Where there are commercial activities e.g.shops or kiosks/carts located along one sideor both sides of the designated escapepassageway leading to the safe exterior openspace, a minimum separation distance of 10mshall be maintained between the commercialactivities and the designated escapepassageway. The circulation space shall alsobe installed with engineered smoke controlsystem. Alternatively the commercialactivities shall be fire compartmented withwalls and doors of minimum one-hour fireresistance rating.

    (4) The clear width of the exit doors leading to the safeexterior open space shall be adequate to receive theoccupant load in the 1st stor ey circulation space and thetotal number of people discharging from the internal exit

    staircases >>>>>

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    27/42

    Chapter 2 : Means of Escapeclause 2.3.3(c )(ii): Discharge (for purpose group II)

    NEW CLAUSE(ii) In the case of a Purpose Group II residential building notfitted with an automatic sprinkler system, at least 50% of thetotal number of exit staircases shall discharge to the safeexterior space opened to the sky and the remaining exitstaircase is allowed to be discharged onto the ground levelcovered circulation space subject to the following:

    (1) The ground level covered circulation space shall be freeof any commercial activity; and

    (2) The discharge point into the g round level circulationspace shall be within sight of and provided with at leasttwo alternative routes to the safe exterior space openedto the sky; and

    (3) The maximum distance between the discharge point ofan exit staircase and the safe exterior space opened tothe sky shall not exceed 10m; and

    (4) There shall not be more than 4 residential units openinginto the designated escape passageway at grade level

    into which the exit staircase discharges; and(5) The discharge point of an exit staircase shall be

    effectively cross-ventilated such that:

    each end has at least 50% permanent openings; and

    no part of the circulation space shall be more than 10mfrom the openings on the perimeter walls of the buildingor air-well.

    >>>>>

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    28/42

    Chapter 2 : Means of Escapeclause 2.3.3(c )(ii): Discharge (for purpose group II)

    1) The ground level coveredcirculation space shall befree of any commercialactivity; and

    2) The discharge point (staircaseY) into the ground levelcirculation space shall bewithin sight of and providedwith at least two alternativeroutes to the safe exteriorspace opened to the sky; and

    3) The maximum

    distance between thedischarge point of anexit staircase and thesafe exterior spaceopened to the skyshall not exceed 10m;and

    4) There shall not be more than4 residential units openinginto the designated escapepassageway at grade level

    into which the exit staircasedischarges; and

    5) The discharge point of an exitstaircase shall be effectivelycross-ventilated such that:

    each end has at least 50%permanent openings; and

    no part of the circulation spaceshall be more than 10m from the

    openings on the perimeter wallsof the building or air-well.

    Staircase Z (50%) with directdischarge to safe exterior spaceopen to sky

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    29/42

    Chapter 2 : Means of Escapeclause 2.3.3(c )(iii): Discharge

    NEW CLAUSE

    (iii) There shall be no unprotectedopenings of occupancy areawithin 3m from discharge point ofthe exit staircase (both internal

    and external). This distance canbe reduced to 1.5m if theunprotected openings are alongthe same plane of the staircaseexit.

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    30/42

    Chapter 2 : Means of Escapeclause 2.3.3(c )(iii): Discharge

    NEW CLAUSE

    (iii) There shall be no unprotectedopenings of occupancy areawithin 3m from discharge point ofthe exit staircase (both internal

    and external). This distance canbe reduced to 1.5m if theunprotected openings are alongthe same plane of the staircaseexit.

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    31/42

    Chapter 2 : Means of Escapeclause 2.3.3(d): Winders , Treads for circular staircase

    OLD CLAUSECl.2.3.3(d) The minimum width and capacity ofexit staircases shall be as specified in Table 2.2A,and such staircases shall comply with thefollowing:

    (i) Winder

    Winders shall not be permitted in any buildingother than for access staircases of residentialbuildings and in such cases, there shall be notmore than 1 winder per 90 degree turn.

    (ii) Treads for circular staircase

    Where circular/geometric staircases are used asexit staircases or access staircase in PurposeGroup I & II, the width of treads measured at the

    narrower end shall be not less than 100mm inresidential buildings and 125mm in otherbuildings and at a distance of half metre fromthe narrower end shall be not less than 225mmin residential buildings and 250mm in otherbuildings

    AMENDED CLAUSECl.2.3.3(d) The minimum width and capacity of exitstaircases shall be as specified in Table 2.2A, andsuch staircases shall comply with the following:

    (i) Winder

    Winders shall not be permitted in any buildingother than for access staircases in a of residentialbuildings unitand in such cases, there shall be notmore than 1 winder per 90 degree turn.

    (ii) Treads for circular staircase

    Where circular/geometric staircases are is used asexit staircases or access staircase in Purpose Group I& II, the width of treads measured at the narrowerend shall be not less than 100mm in residential

    buildings and 125mm in other buildings and at adistance of half metre from the narrower end shallbe not less than 225mm in residential buildings and250mm in other buildings. Such staircase shall notbe more than 10m in height.

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    32/42

    Chapter 2 : Means of Escapeclause 2.3.3(d): Winders , Treads for circular staircase

    10mheightm

    ax

    AMENDED CLAUSE

    Cl.2.3.3(d) The minimum width and capacityof exit staircases shall be as specified in Table2.2A, and such staircases shall comply withthe following:

    (i) Winder

    Winders shall not be permitted in anybuilding other than for access staircases in aof residential buildings unitand in suchcases, there shall be not more than 1 winderper 90 degree turn.

    (ii) Treads for circular staircase

    Where circular/geometric staircases are is

    used as exit staircases or access staircase inPurpose Group I & II, the width of treadsmeasured at the narrower end shall be notless than 100mm in residential buildings and125mm in other buildings and at a distance ofhalf metre from the narrower end shall be notless than 225mm in residential buildings and250mm in other buildings. Such staircase

    shall not be more than 10m in height.

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    33/42

    Chapter 2 : Means of Escapeclause 2.3.3(e): Handrails

    OLD CLAUSE

    Cl.2.3.3(e) Handrails

    Where the width of the exit staircase

    exceeds 2000 mm, handrails shall beprovided in accordance with therequirements of Cl. 2.2.8

    AMENDED CLAUSE

    Cl.2.3.3(e) Handrails

    (i) Every exit staircase shall have

    walls, grilles or handrails on bothsides, except that staircases that are1250mm or less in width, can have ahandrail one side only; and

    (ii) Where the width of the exit staircaseexceeds 2000 mm, handrails shall beprovided in accordance with therequirements of Cl. 2.2.8

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    34/42

    Chapter 2 : Means of Escapeclause 2.3.3(e): Handrails

    AMENDED CLAUSE

    Cl.2.3.3(e) Handrails

    (i) Every exit staircase shall have

    walls, grilles or handrails on bothsides, except that staircases that are1250mm or less in width, can have ahandrail one side only; and

    (ii) Where the width of the exit staircaseexceeds 2000 mm, handrails shall beprovided in accordance with therequirements of Cl. 2.2.8

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    35/42

    Chapter 2 : Means of Escapeclause 2.3.3(f): Ventilation

    OLD CLAUSE

    Cl.2.3.3(f) Ventilation

    All exit staircases shall be ventilated

    by fixed openings in the externalwalls, such openings being of area notless than 10% of the floor area perfloor of the staircase, or mechanicallyventilated to comply with therequirements in Chapter 7. Exit

    staircase and occupancy area shall notshare the same airwell or void forlighting and ventilation.

    AMENDED CLAUSECl.2.3.3(f) Ventilation

    All exit staircases shall be ventilated byfixed openings in the external walls,

    such openings being of area not lessthan 10 per cent of the floor area perfloor of the staircase, or mechanicallyventilated to comply with therequirements in Chapter 7. Ventilationopenings fronting an air-well, externalrecessed space or external shall be inaccordance with Table 1.2.1(A). Exit

    staircase and occupancy area shall notshare the same airwell or void forlighting and ventilation. Mechanicalventilation is not allowed for PurposeGroup II, except for staircase storeyshelter.

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    36/42

    Chapter 2 : Means of Escapeclause 2.3.3(f): Ventilation

    AMENDED CLAUSE

    Cl.2.3.3(f) Ventilation

    All exit staircases shall beventilated by fixed openings inthe external walls, suchopenings being of area not less

    than 10 per cent of the floorarea per floor of the staircase,or mechanically ventilated tocomply with the requirementsin Chapter 7. Ventilationopenings fronting an air-well,external recessed space orexternal shall be in

    accordance with Table1.2.1(A). Exit staircase andoccupancy area shall not sharethe same airwell or void forlighting and ventilation.Mechanical ventilation is notallowed for Purpose Group II,except for staircase storeyshelter.

    Table 1.2.1A isonlyapplicable toventilation forstaircases,please do notapply it tosmoke stop

    lobby

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    37/42

    Chapter 2 : Means of Escapeclause 2.3.3(h): Different Mode of Ventilation

    NEW CLAUSE

    2.3.3(h) Different modes of ventilationwithin a single staircase shaft

    For buildings exceeding 24m inhabitable height, the internal exit

    staircase can be naturally ventilated atits upper part and mechanicallyventilated at its lower part providedthis lower part does not exceed 24m inhabitable height and there shall not beany intermediate staircase landingdoor separating the 2 modes ofventilation. If the lower part exceeds24m in habitable height, this lowerpart shall be pressurized instead.

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    38/42

    Chapter 2 : Means of Escapeclause 2.3.3(h): Different Mode of Ventilation

    NEW CLAUSE

    2.3.3(h) Different modes of

    ventilation within a single staircase

    shaft

    For buildings exceeding 24m in

    habitable height, the internal exitstaircase can be naturally

    ventilated at its upper part and

    mechanically ventilated at its lower

    part provided this lower part does

    not exceed 24m in habitable height

    and there shall not be any

    intermediate staircase landing doorseparating the 2 modes of

    ventilation. If the lower part

    exceeds 24m in habitable height,

    this lower part shall be pressurized

    instead.

    Note:In order topressurized thelower part , thethe wholestaircase shouldbe MV

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    39/42

    Chapter 2 : Means of Escapeclause 2.3.4: Scissor Exit Staircase

    OLD CLAUSE

    2.3.4 Scissor Exit Staircase

    a) Where two separate internal exit

    staircases are contained within the

    same enclosure, each exit staircase

    shall be separated from the other bynon-combustible construction having

    fire resistance for a minimum period

    equal to that required for the

    enclosure, and

    b) Such scissor exit staircases shall

    comply with all applicable provisionsfor exit staircase, and

    c) Door opening into scissor exit

    staircases shall be at least 7m travel

    distance from each other.

    AMENDED CLAUSE2.3.4 Scissor Exit Staircase

    a) Where two separate internal exit staircases arecontained within the same enclosure, each exitstaircase shall be separated from the other bynon-combustible construction having fire resistancefor a minimum period equal to that required for theenclosure, and

    b) Such scissor exit staircases shall comply with allapplicable provisions for exit staircase, and

    c) Door opening into scissor exit staircases shall be atleast 7m measured as travel distance between thetwo closer edges of the staircase doors, and

    d) Where there is only one pair of scissor exitstaircases, the door opening into scissor exitstaircases shall be spaced at least 1/3 the diagonaldimension of the area to be served in a sprinkler

    protected building and the diagonal dimensionin a non-sprinkler protected building in accordancewith Cl.1.2.60, and

    e) (e) The ventilation openings of each staircase shallbe located on alternate storeys if such openings orwindows are serving both staircases on the samewall

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    40/42

    Chapter 2 : Means of Escapeclause 2.3.4: Scissor Exit Staircase

    AMENDED CLAUSE2.3.4 Scissor Exit Staircase

    a) Where two separate internal exitstaircases are contained within the sameenclosure, each exit staircase shall beseparated from the other bynon-combustible construction having fireresistance for a minimum period equal to

    that required for the enclosure, andb) Such scissor exit staircases shall comply

    with all applicable provisions for exitstaircase, and

    c) Door opening into scissor exit staircasesshall be at least 7m measured as traveldistance between the two closer edgesof the staircase doors, and

    d) Where there is only one pair of scissorexit staircases, the door opening intoscissor exit staircases shall be spaced atleast 1/3 the diagonal dimension of thearea to be served in a sprinklerprotected building and the diagonaldimension in a non-sprinkler protectedbuilding in accordance with Cl.1.2.60,and

    >>>>>

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    41/42

    Chapter 2 : Means of Escapeclause 2.3.4: Scissor Exit Staircase

    NEW CLAUSE2.3.4 Scissor Exit Staircase

    (e) The ventilation openings ofeach staircase shall belocated on alternate storeys

    if such openings or windowsare serving both staircaseson the same wall

  • 7/27/2019 4 IFE FireCode2013Chap1&2 Part1 MdmEng

    42/42