86
4. PERFORMANCE ANALYSIS
Analysis of Problem
The problems identified in preceding chapter of system development are
analyzed by using following methods
1. Analysis using programs and softwares based on mathematical background
developed in System Development
2. Building simulation model and obtaining simulation results
3. Computer Analysis of Recorded Events
4. Developing a scientific hypothesis
5. Creation of new idea based on scientific hypothesis
6. Developing Logic based on new idea
4.1. Harmonic Analysis
The power quality disturbances mainly comprise harmonics which are
detrimental for equipment and plant life. The foremost step carried out was load
survey and determining plant powers and harmonics of different orders. Power quality
analyzer, softwares for analysis make the job of harmonic analysis easier.
4.2 Experimental Analysis
Findings in harmonic analysis-Surge Suppressor failure in EAF-2 and
Transformer failure in EAF-1.The EAF-1 has 42/36 KV, 50 kA surge arrestors (LA-
1), which never failed until now, while EAF-2 has 36/30 kV, 10 KA surge arrestors
(LA-2), which failed few times. Most surge arrestors fail when it cannot handle the
quantity of incoming energy. LA-1 with 50 KA capacities can handle much more
energy in Joules. In addition, its line-to-line voltage rating of 42 kV is away from
normal operating range of 33 kV ±10 %, avoiding unintended operation.
LA-2 with 10 kA capacity can handle much lesser energy in Joules. In
addition, its line to line voltage rating of 36 kV is within normal operating range of 33
kV± 10%, increasing possibilities of unattended operation during which huge energy
87
could flow through LA-2, placed between line to line and then between line to earth.
Such unintended operation if happens, continues until the LA itself fails clearing the
first fault, but could trigger another voltage related fault) or the upstream breaker trips
(breaker tripping takes long time typically 70- 100 ms or 500 ms (if secondary relay
acts) which is a long time for any LA, stressing and weakening it. Please also ensure
that the installed LA-2 is of station Class-3 grade and have the potential to handle
higher energy. It is better to replace LA-2 with 10 kA station class-3 (in India 50 kA
is generally not available, station class-3 with appropriate voltage grade can handle
more energy in Joules), 42 kV line-to-line grade (to avoid unintended operation) and
36 kV line to earth voltage grade.
Transformer and/or its component failure in EAF-1
Going by the nature of failures it is unlikely to have triggered by the passing
lightning surges. The more likely causes could 1) lie within transformer or its
components itself or 2) due to momentary high stress.
4.2.1 Harmonic Distortion
Non-Linear Load, the cause of harmonic distortion
Superimposition of harmonics to fundamental waveform causes distortion. Its
magnitude varies depending upon the superimposing harmonics (its magnitude,
frequency & phase angle) with reference to fundamental waveform. When a 3rd
harmonic coincides with fundamental, it distorts the fundamental like a “Square
Wave”. If the same 3rd
harmonic coincides in 900
phase shift, it distorts the
fundamental waveform into a series of “positive and negative spikes’. Odd harmonics
generate square wave, it clip sine wave peak and cause load saturation. A
phenomenon when an increase in voltage does not cause proportional increase in
current. This is why such “Non-Linear “Loads distort current sine wave.
Harmonic can cause both current and supply voltage distortion. Harmonic current
distortion is generally local to a particular facility, while harmonic voltage distortion
pervades through entire electrical system and affects many different localities. This is
88
because harmonically distorted load current from any facility flows through its source,
as it offers least impedance path.
Energy Loss and Harmonic Distortions
Harmonic distortion cause high-energy losses. This is because equipment such
as Transformers, Motors, generators, cables and other inductive loads are designed to
operate at fundamental (50 Hz) frequency. Losses increase since harmonic currents
are of higher frequencies.
Transformer lossesconsist of excitation i.e. no load losses and load losses. No
load losses are the sum of eddy current and hysteresis losses. Load losses include
D.C. winding loss; eddy-current stray loss in the winding (with skin effect&
proximity effects) and other stray losses due to flux linking the tank and structure).
Losses due to harmonics are more pronounced in eddy current losses since it increases
with square of harmonic frequency. Stray losses as electromagnetic flux in windings,
core and shields increase with harmonic distortion.
Motor lossesconsist of iron and copper losses increase with harmonic
distortions. Motor efficiency could reduce by 5 %, depending on the extent of
distortion of the wave shape.
Cable/Line losses increase as the square of harmonic current and its distance.
Additionally harmonic injected losses further compounded due to skin effect arising
due to its high frequency currents and voltages. Turbo-Alternator (TG) or DG loses
are more pronounced for the industry due to phenomenon of negative sequence
harmonics. Just imagine the damaging effect on your TG running at a high speed,
when subjected to this force from opposing direction. Depending upon distortions,
you lose out up to 30 % power burn excess fuel and end up in lowering TG life and
higher maintenance cost.
There are recommended limits, IEEE-519, on the magnitude of harmonics that
a facility could have for optimized operation.
89
4.2.2 Measurement on 33 kV Side Section II, EAF-1 Bus
MDH Germany make, 33 kV, AC furnace is fed from 33 kV bus section II of
switchyard. It was observed that at 9-55 AM, Fourth harmonic filter was switched off.
After 5 minutes, Third harmonics filter was switched off. Thus both filters were
switched off for 15 minutes. The effect of switching off capacitor banks is studied. It
was observed that the frequency increases from 50.1 Hz to 51.4 Hz and current
decreases from 0.7 kA to 0.5 kA.
Figure 4.2.2.1: Photograph of Set Up at 33 kV EAF Bus
The photograph 1 shows the set up used for measurement and data analysis at
33 kV bus bars at section 2 and section 3 for electric arc furnaces 1 and 2 respectively.
For EAF-1, it was noticed that the harmonics were maximum at the beginning of the
heat cycle, which approximately comes after one hour. At the initiation of melting and
during melting of cold scrap, it was found that the voltage and current waveforms
were severely distorted. The harmonics are generated. The current harmonics of third,
fourth and fifth order exceeds 3%. The current is resuming its sinusoidal nature after
5-8 minutes. The current refers to charging and meltdown of cold scrap. The flicker
level is also very high. Figure 4.2.2.1 shows the sample waveform with severe
distortion in each phase. The frequency recorded was 49.92 Hz. The values of RMS
voltages for three phases and currents were noted.
90
4.2.3 Harmonic Audit
Table 4.1: Plant Power at various Bus and Harmonic Levels
Date/Load Typica
l
kVA
PF-
Avg
+Lag
-Lead
Avg
Freq.
Typical
Amps
R-Y-B
Typical
Volts
R-Y-B
Major
harmonics
-
Currents
Major
harmonics
-
Voltage 12th Jan
220 kV
MSEB I/C
89,500 1.00 49.30 247
220 230
221.2
221.2 219.1
IO2=21.0%
IO3=09.0% IO4=02.0%
VO2=00.6%
VO3=00.5% VO7=00.4%
14th
Jan
33 KV Trs 1-
MILLS
27,800 1.00 49.70 495
476
482
32.9
33.2
32.9
IO5=03.2%
IO3=03.2%
IO7=02.7%
VO5=00.8%
VO3=00.7%
VO7=00.6%
14th
Jan
33 KVTrs.2
EAF-1
43,700 0.99 49.98 806
733
812
32.7
32.9
32.7
IO3=01.0%
IO7=00.4%
IO5=00.3%
VO5=00.4%
VO3=00.3%
VO7=00.2%
13th Jan
33 KV Trs-3
EAF-2
43,793 1.00 49.29 794
775
800
32.1
32.3
32.1
IO3=16.5%
IO2=05.0%
IO5=03.0%
VO5=03.5%
VO3=01.0%
VO7=00.5%
12th Jan
33 kV HRM
RM
6,380 1.00 49.59 110
112
104
32.9
33.1
33.0
I11=03.3%
I13=02.0%
I23=00.5%
VO5=00.5%
VO7=00.3%
VO3=00.2%
12th Jan
33 kV
HRM
FM
12,020 1.00 49.45 216
201
205
33.2
33.3
33.0
I11=08.0%
I13=06.0%
I23=02.5%
VO5=0.5%
VO7=0.3%
VO3=0.2%
12th Jan
33 KV CRM-1
5,910 0.90 49.94 104
100
102
33.2
33.5
33.2
I05=09.0%
I11=03.0%
I13=02.8%
VO5=0.8%
VO3=0.30%
VO7=0.20%
12th Jan
33 KV CRM-2
5,780 0.80 49.04 102
099
100
33.1
33.4
33.2
I11=06.%
IO5=05.5%
I13=03.8%
VO5=0.8%
VO3=0.3%
VO7=0.2%
14th Jan
11KV HRM
FM entry
1,352 0.021 49.87 70
67
68
11.3
11.4
11.3
IO5=21.0%
IO7=13.0%
I11=09.0%
VO5=1.8%
V13=0.62%
V11=0.55%
13th Jan
11 kVCRM-1
Reel
1,420 0.14 50.10 77
73
75
10.9
10.9
11.0
IO5=46.0%
IO7=12.0%
I11=09.0%
VO5=1.10%
V13=0.82%
V11=0.70%
13th Jan
11 kV CRM-1
Backup
2,370 0.62 49.34 127
121
123
11.1
11.0
11.0
I11=08.2%
IO5=04.5%
I13=02.0%
V11=2.00%
VO3=1.80%
VO5=1.00%
14th Jan
11 kV CRM-2
Entry
1,780 0.20 49.58 96
91
97
11.0
11.0
11.0
I11=08.0%
I13=0.3.0%
IO3=02.0%
V11=1.10%
V13=1.00%
VO3=0.80%
14th Jan
11 kV CRM-2
Top
1,210 0.63 50.11 62
61
62
11.3
11.4
11.3
I11=07.5%
I13=06.0%
I05=04.0%
V11=1.10%
VO5=0.60%
VO3=0.50%
91
4.3 Computational Analysis of Furnace
The furnace analysis is done by FFT analysis and the software used for isPowerflow.
All harmonic trends, flicker,T HD, Current distortion, individual current distortion,
waveforms of current, voltage ,and voltage sag are simulated. The details of all events
are recorded. The analysis of the same is done.
Figure 4.3.1: Voltage as a Function of Time for EAF-1
Voltage waveform is distorted for all three phases due to superimposition of Second
order, Third order, Twenty sixth and Twenty seventh order harmonics predominantly
on fundamental wave. This phenomenon is at the start of heat cycle. When cold scrap
is charged and arc strikes, the current waveform is severely affected.
Figure 4.3.2: Percent of Current Average Fundamental as a Function of Time
92
Figure 4.3.2 shows one heat duration of EAF-1 from 8-27 AM to 9-42 Am. At
8-29 AM, after arc striking the current distortions were noted. The values of Current
average fundamental for various harmonic orders were as follows. IH3= 13.8%; IH5=
6.5%; IH7= 3%; IH9= 1.6%; IH11= 1.8%. The similar results were obtained for next
charging. At the instant of striking of arc and beginning of melting, recorded values
were IH3= 11.18%; IH5= 7.0%; IH7= 3.4%; IH9= 3.4%; IH11=3.1%.
Figure 4.3.3: THD Voltage for EAF-1
At 1-59 AM, THD V1= 20.9%, THD V2=17.1%, THD V3=15.4%; Corresponding
I1=0.51 kA, I2=0.52 kA, I3=0.72kA. After one heat cycle, which is about 70 minutes
duration at 3-08 AM, THD V1= 20.4%, THD V2=17.8%, THD V3=17.1%;
Corresponding I1=0.54 kA, I2=0.45 kA, I3=0.53 kA. Total Harmonic distortion is
higher than power quality standards. Also there is unbalance in current for three
phases. The non-uniform peaks in voltage indicate erratic behavior of arc (Figure 4.4).
Figure 4.3.4: THD Voltage and THD Current
93
Figure 4.3.5: Percent of Voltage Fundamental as a Function of Harmonic
Voltage harmonics of Second order, Third, Twenty sixth and Twenty seventh
are more than 3%. Voltage harmonics are produced in this way through impedance of
the mains supply; the amplitude depends on the value of the harmonic currents
supplied and the effective impedances at the harmonic frequencies.
Because of the non-linear arc resistance, an arc furnace acts as a source of
current harmonics of the order Second, Third, Fourth, Fifth, Sixth, Ninth; their
individual magnitude is more than 3%. All mentioned harmonics exceed the limits
consisting of capacitor C with reactive power, and mains inductance from the mains
short circuit power. Another harmonic current producing source is the energization of
scrap metal and ladle furnace transformers.
Figure 4.3.6: Percent of Current Fundamental as a Function of Harmonic
94
The dynamic inrush current waveform associated with transformer energizing
operation includes both even and odd harmonics, which decay with time until the
transformer magnetizing current reaches steady state (Figure 4.3.7). The most
predominant harmonics during transformer energization are 2nd
, 3rd
, 4th
, and 5th
in
descending order.
Figure 4.3.7: Voltage When Voltage Sag Lasted For 6.5 Cycles
The figure 4.8 shows voltage sag phenomenon, which lasted for 6.5 cycles. It
is observed that oscillatory transients exist at the top and bottom peaks. The
oscillations are multi-frequency. Main circuit oscillations are induced by one or more
arc voltage discontinuities and having energy sources in capacitances of cables,
lumped inductances of the supply side and load side networks. They often cause
chopping of voltage waveform at peaks due to switching in of major capacitor banks,
unloaded line and cable transients, which lasted for several hundred milliseconds [3].
Current waveform during voltage sag is severely distorted. It contains double
frequency transients. Voltage sags are followed by high currents, shown in green
which in turn cause voltage drop at PCC. Asynchronous periodic current waveform is
observed.
Figure 4.3.8 shows that short term flicker severity index (Pst) is more than 1,
which exceeds IEC standards. Also long term Perception (Plt) is more than 0.74 [5].
Both these values are greater than standards. The voltage flickers are predominant at
the beginning of heat cycle when arc strikes and melting starts.
95
Figure 4.3.8: Flicker of EAF-1
From figure 4.3.9, it is noticed that supply frequency to arc furnace is not
constant but varying randomly because of nonlinear behavior of arc and load is not
constant.
Figure 4.3.9: Frequency Variation for EAF-1
The variations in frequency clearly indicate that load is continuously varying
and erratic behavior of arc current is responsible factor.
96
4.4 Comparison between Experimental Analysis and Computational Analysis for
Arc Furnace Harmonics
Arc Furnace 1 and Arc Furnace 2 are analyzed for Harmonic levels at 33 kV Bus.
When fourth Harmonics filter and third Harmonic filter were switched off for 15
minutes. The effect of switching capacitor banks was also studied.
Table No.4.2 : Effect of Switching Capacitor Bank on Harmonics Levels
Experimental Analysis Computational Analysis
Filter Switched
Off
Frequency
49.96 Hz
Current
Harmonics
I03 = 12%
I02 = 4%
I05 = 1.5%
I07 not
recorded
Frequency
49.97Hz
Current
Harmonics
R-Y-B
I03 = 14%
I02 = 6%
I05 = 2%
I07 = 3%
Filter Switched
On
50.13 Hz Current
Harmonics
I03 = 1%
I05 = 3%
I07 = 0.4%
Frequency
49.99Hz
Current
Harmonics
R-Y-B
I03 = 5%
I02 = 3%
I05 = 1.5 %
I07 = .5%
It is observed that, current is reduced and frequency increases as the filter is made on
after switching of for 15 minutes.
4.5 Justification of Error of Arc Furnace for Harmonic Analysis
Ø The instability and non-linearity are greatest during melting down of cold
scrap. The delay and erratic process of striking the arc and resulting gaps in
the current are conspicuous.
Ø As melting down progresses, the striking becomes more stable, but the current
can still contain low-frequency fluctuations. The temperature and heat of the
97
arc are high with a liquid steel bath, and the thermal conduction is low. So that
the arc characteristics begin to approach the linear behavior of an ordinary
resistance.
Ø The non-sinusoidal arc voltage waveform is not entirely adopted by the supply
current. Since inductance in the circuit gives rise to inductive reactance, which
increases with frequency and therefore resists harmonics. The current
waveform then becomes almost sinusoidal. The noticeable harmonic current
causes increase in reactive power and with a higher reactance.
Ø Flicker measured for short duration and long duration are more than the limits
specified in IEEE Standards. Voltage sags on one of the lines has produced
voltage and current unbalances.
4.6 Experimental Analysis of Harmonics in Rolling Mills
220 kV from Supply Company
220 kV/ 34.5 kV
EAF-1
220 kV/ 34.5 kV
EAF-2
EAF-1
FMRM
HR M
In House CRM
11 kV/750 V
4 Motors
11kV/440V
3 motors Thyristor
transforme
33 kV/ 11 kV
Figure 4.6.1 : Single Line Diagram of Lloyd Steel Plant, Bhugaon, Wardha
In this survey, power quality is monitored and the recorded waveforms give
information about many steady state characteristics, including harmonic distortion,
power factor, flicker, frequency, voltage and current harmonics. Because of the
periodic nature, harmonic distortion is analyzed by using Fourier analysis. The
harmonic levels are very high as compare to IEEE standards as shown in table.
98
Table 4.3: Harmonic Levels in Rolling Mills at Lloyd Steel Plant, Bhugaon
Date/Load Typica
l
kVA
PF-
Avg
+Lag
-Lead
Typical
Amps
R-Y-B
Typical
Volts
R-Y-B
Major
harmonics
-
Currents
Major
harmonics-
Voltage
14th Jan 33 KV Trs
1MILLS
27,800 1.00 495
476
482
32.9
33.2
32.9
IO5=03.2%
IO3=03.2%
IO7=02.7%
VO5=00.8%
VO3=00.7%
VO7=00.6%
12th Jan
33 KV HRM
RM
6,380 1.00 110
112
104
32.9
33.1
33.0
I11=03.3%
I13=02.0%
I23=00.5%
VO5=00.5%
VO7=00.3%
VO3=00.2%
12th Jan
33 KV HRM
FM
12,020 1.00 216
201
205
33.2
33.3
33.0
I11=08.0%
I13=06.0%
I23=02.5%
VO5=0.5%
VO7=0.3%
VO3=0.2%
12th Jan
33 KV CRM-
1
5,910 0.90 104
100
102
33.2
33.5
33.2
I05=09.0%
I11=03.0%
I13=02.8%
VO5=0.8%
VO3=0.30%
VO7=00.20%
12th Jan 33 KV CRM-2
5,780 0.80 102
099 100
33.1
33.4 33.2
I11=06.%
IO5=05.5% I13=03.8%
VO5=0.8%
VO3=0.3% VO7=0.2%
14th Jan
11KV HRM
FM entry
1,352 0.021 70
67
68
11.3
11.4
11.3
IO5=21.0%
IO7=13.0%
I11=09.0%
VO5=1.8%
V13=0.62%
V11=0.55%
13th Jan
11 KVCRM-
1
Reel
1,420 0.14 77
73
75
10.9
10.9
11.0
IO5=46.0%
IO7=12.0%
I11=09.0%
VO5=1.10%
V13=0.82%
V11=0.70%
13th Jan 11 kV CRM-1
Backup
2,370 0.62 127
121
123
11.1
11.0
11.0
I11=08.2%
IO5=04.5%
I13=02.0%
V11=2.00%
VO3=1.80%
VO5=1.00%
14th Jan 11 kV CRM-2
Entry
1,780 0.20 96
91
97
11.0
11.0
11.0
I11=08.0%
I13=0.3.0%
IO3=02.0%
V11=1.10%
V13=1.00%
VO3=0.80%
14th Jan 11 kV CRM-2
Top
1,210 0.63 62
61
62
11.3
11.4
11.3
I11=07.5%
I13=06.0%
I05=04.0%
V11=1.10%
VO5=0.60%
VO3=0.50%
The reason for all round harmonic distortion in many steel plants is often due to
numerous drives. It produces harmonic at load end, which flows upstream as Xd” of
utility grid or DG/TG offers least impedance path to the flow of harmonic current,
causing electrical stress to plant equipment in its path, which are usually dissipated as
energy losses.
In-addition use of capacitor further aggravates harmonic problem. Capacitors
are used for power factor improvement and voltage control. Unfortunately, with
addition of each new capacitor bank, electrical systems resonance frequency is
99
lowered, rendering it to be susceptible to resonance. Thus, though capacitor
themselves do not generate harmonics, but its use with non-linear loads magnify
harmonics to a level as determined by system parameters. PQ disturbance arises
mostly from industry itself. However, end-use equipment is more sensitive to PQ
disturbances. Thus industry not only suffers first but solution also lies within industry
itself. Both Current and voltage harmonic are high at LT level, i.e. AC input to
respective thyristor converter drives, providing scope for improvement and energy
savings by re-construction of the basic wave-shape. In addition to harmonic reduction,
power quality improves, thereby providing stabilization effect enhancing equipment
life. Higher voltage & current harmonic distortion causes stress on cables, bus bars,
alternators, motors, plant electronics and transformers. It reduces their efficiency and
life and increases maintenance and energy cost. This is because such inductive loads
are designed to operate only at fundamental, but get subjected to high frequency
harmonic environment.
The harmonic currents the steel sheet that feed into the rolling mill process
varies over the total period. The harmonics produced by the 12 pulse converters are
related to the pulse number of the drive and can be represented as harmonic current
sources as their characteristics frequencies. For the ideal case of instantaneous
commutation between conducting elements, the generated ac side harmonic currents
and the theoretical magnitudes for 12 pulse drives can be calculated as
n = 12k ± 1
where n-order of the harmonic, k-an integer 1,2,3,…, In - harmonic current magnitude,
I1- fundamental current magnitude. The large dc drives use thyristor converters to
control bus voltage or line current to maintain desired speed. The disadvantage of
thyristor converter is a greater ac current distortion during slower motor speeds.
4.7 Computational Analysis of Rolling Mills
Steel Plants with electric arc furnaces or Arc Plants are generally plagued with power
quality issues out of the harmonic distortions of fundamental wave shape. The
problem arises due to extensive use of non linear loads mainly EAF and
100
ThyristorizedDC driving and holding stage and decays rapidly through melts. The
harmonics generated are like transient phenomenon which rises sharply during initial
arcing stage and decays rapidly through melting and holding stages. Usually EAF
employ harmonic filter to mitigate harmonics and to control voltage flicker.
Rolling mill loads are fluctuating and the effect are observed. The dynamic
distortion current waveform caused by voltage sags includes both even and odd
harmonics which decay with time until the input current reaches steady state. The
characteristic of a input current is fundamental current with a percentage of THD. The
values recorded at 1.35 pm are THD I1 = 113.3%, THD I 2= 101.5%, THD I3 = 90.9%.
These values are very high as compared to standards. After a period of 9 minutes
approximately ( light load period) , load is increased with the introduction of new
sheet for rolling, the current shoots up and total harmonic current distortion now
shoots up to THD I1 = 111% , THD I 2=65.45%, THD I3 = 141.6%; the similar
readings are obtained.
Figure 4.7.1 CRM Backup Drive THD Current Variation with Time
Total harmonic distortion at 1.35 pm is THD I1= 113.3%, THD I2= 101.5%, THD
I3= 90.9%, the lowest value of THD at 1.42 pm are THD I1= 13.1%, THD I2= 12.8%,
THD I3= 11.9%. Both these values exceed the permissible limits of 5%. Third
harmonics coincides in 90 degree phase shift; therefore the fundamental waveform is
distorted into a series of positive and negative spikes.
Figure 4.7.2 shows the variation of power factor with time for back up drive in
cold rolling mill. The power factor is lowest as 0.025 and highest as unity power
101
factor. The value of power factor fairly steady for long time is he above 0.7. The wide
variation in power factor indicates the nonlinear and random load which is occurring
on the mill. The power factor is corrected by capacitor bank installed in the plant.
Figure 4.7.2 Power Factor Variation with Time – Back Up Drive
Figure 4.7.3 gives the variation of percent of current fundamental for phase 1
(I1) with time. The harmonics of order Three, fifth, seventh and ninth and eleventh are
predominant. Third order harmonics is within limits; around 3%. But fifth order
harmonics are 17.8%, 12.3%, and 11.4% at different hours of time. The seventh order
harmonics was observed to be maximum 5.8% which is higher value for individual
phase current. The higher values of 5.6 %, 7.4% and 8.1% are also recorded for
eleventh order harmonics at 1.46 pm, 2.25 pm and 2.01 pm respectively. This
indicates the need of filter for eleventh order harmonics. The three peaks correspond
to fifth order harmonics.
Figure 4.7.3:Percent of Current Fundamental Variation with Time
Figure 4.7.4 gives Fast Fourier Transform analysis gives the values of current
fundamental for phase 1,2 and 3 as follows: For predominant harmonics of 11th
order
102
the values are FFT I1 = 7.3% , FFT I2 = 7.3%, FFT I3 = 7.1%; for 13th
order the values
are FFT I1 = 6.9%, FFT I2 = 6.7%, FFT I3 = 6.3%; for 5th
order the values are FFT
I1 = 3.6% , FFT I2 = 3.5%, FFT I3 = 3.1%.The 25th
order harmonics are less than 3%.
Figure 4.7.4: Current Harmonics Variation with Time - 11 kV CRM Back Up Drive
The distortions in shape of the waveform are clearly observed. The waveform
for voltage contains notches nearer to zero crossing and near to peak of the voltage.
The commutation notches are caused by the short circuits caused in the system when
six PulseBridge or twelve PulseBridge is commutated. A six pulse gives six notches
per cycle and twelve pulse bridges gives twelve pulses per cycle. At the bus bar to
which the commutating bridge is connected the line to line voltage is reduced to zero
during the commutation. At other bus bars between the bridge and driving voltage,
the depth of notches is determined by ratio of inductances in the circuit. There are
three important factors related to notching. The first one is more than one notch nearer
to zero crossing. Unfortunately these crossovers are used either to detect frequency or
to give a reference for firing angle. There have been reports of loss of control of
voltage on the plant when there was significant voltage distortion. The solution to this
problem is to add a small filter, just a capacitor in shunt with low voltage input to the
control circuit. The second significant feature oscillations caused by Heaviside
excitation of the system inductances and capacitances. The capacitances are generally
those of either system cabling, power factor correction capacitors or filters. These
oscillations interfere with telecommunications either telephones or signal carrying.
The third significant factor is effect of firing angle of the bridge when it is near to the
103
peak of the supply voltage. The high rate of change of voltage dv/dt associated with
beginning and end of commutation have an effect on insulation lifetime .
Figure 4.7.5:Voltage Variation with Time – 11 kV CRM Entry Drive
33 kV Cold Rolling Mill Current and Voltage Wave Form
Figure 4.7.6: Current and Voltage Wave Form - Cold Rolling Mill
Figures 4.7.7 and 4.7.8 shows for back up drive, the harmonics of 3rd,
5th
, 11th
,
and 15th are more than 3%. The ripple content of harmonics distorts the current
waveform to the greatest extent. Odd harmonics generate square wave, it clips sine
wave peak and cause load saturation. If system is sharply resonant at one of the
predominant harmonic frequencies, the harmonic current will excite the system
causing voltage distortion and resonant, thus producing more harmonic current to
further excite the resonant system. This interaction between the resonant system and
current producing that effect from voltage sags can produce very high values of
104
rmsand peak voltage which can degrade and damage equipment and lead to
equipment failure.
Figure 4.7.7:Current Variation with Time – 11 kV CRM Back Up Drive
Figure 4.7.8:Frequency Variation with Time – 11 kV CRM Back Up Drive
It is observed that the real power drawn is not constant but depends on loading.
At the start of rolling the power increases typically to 6.392 MW, 6.74 MW from
0.001, 0.004 MW within 1 minute as can be seen from peaks in the Fig.4.6.10. The
power factor is lowest as 0.072 lag and highest 0.245 lag for reel drive (Fig. 4.5.11).
105
Figure 4.7.9Real Power Variation with Time – 11 kV CRM Entry Drive
Figure 4.7.10: Power Factor Variation with Time– 11 kV CRM Real Drive
The current and voltage harmonics are high at LT level. By reconstructing wave
shape there is scope for improvement and energy savings. Tuned harmonic filters are
required to be installed at locations where distortions are higher than limits prescribed
by 519-1992. In addition to harmonics reduction the power quality is improved and
provides stabilization effect and enhances equipment life. Filters restrict harmonics to
enter TG or DG, relieving the plant as a whole. They also restrict negative sequence
harmonics.
106
Very fast switching with suitable tuning reactor will be suitable in
consideration of fast varying load of the rolling mill. This will meet the dual purpose
of power factor improvement and harmonic limiting to a better extent. This will
achieve
• Reduced THDv
• Reduced voltage fluctuation
• Increased available driver power due to improved voltage
• Improved power factor
• KVA of the plant is reduced
• Transients free
• Rapid switching, fast response to meet the load pattern
Harmonic studies and analysis will increase system reliability and keep the
operations trouble free. The feasibility of tuned filters can be studied by calculations
of payback period. The TCR and DVR installation can benefit the plant.
4.8 Comparison between Experimental Analysis and Computational Analysis
The measurements of parameters related to arc furnace are recorded by
Candura Instruments. Electrical measurement is experienced on the high current side.
Measurements are carried out by Power Analyzer – Candura Instruments. The
PowerPro instrument is used for measuring and recording the following quantities.
Trends in voltage, current, power and frequency, Waveforms and harmonic trends to
64th
harmonic for both voltage and current, Voltages sags and swells Voltage
transients, Current Inrush, THD trend for voltage and current ,Frequency deviations
.It is noticed that harmonic performance at both furnaces almost matches with
computational performance, the reasons of accuracy of FFT method used is high and
for analysis Power flow software is very powerful. It generates harmonics of any
order and displayed the results for very small sampling time.
107
4.9 Justification of Error of Rolling Mill
There is slight difference in field measurements and software analysis. The variation
is due to inaccurate CTs used for connection, saturation of CTs, software analysis
accuracy will depend on input data.
4.10 Arc Furnace Performance Analysis
An AC arc furnace performance is determined by arc parameters study, arc stability.
The analytical performance can be estimated from circle diagram. The statistical
analysis can be done by using Histograms. Data from furnace can be analyzed to
arrive at conclusions. The arc parameters have influence on refractory wear. Wild
phase is issue in furnace operation. Effect of Refractive index on furnace operation
and regulation is studied.
4.11 Experimental Analysis of Arc Furnace Operation
The comparison of various taps is done for operating parameters of arc
furnaces 1 and 2
Table 4.4: Furnace Parameters for Arc Furnaces 1 and 2
Dec 06 Apr 03 Dec 06 Apr 03
Average Furnace Currents KAmp 39 41 41 41
Average Tap Voltage 491 504 505 505
Furnace Active Power (MW) 29.2. 30.7 32.3 33.6
Furnace Reactive Power (MVAR) 14.9 16.2 14.8 12.9
Furnace Apparent Power 33.0 35.4 35.7 36.0
Power Loss(MW) 2.34 2.66 2.52 2.57
Power factor 0.88 0.87 0.91 0.93
Operating Reactance-mohms 3.51 5.74 2.95 2.53
Current Balance % 96.9 92.6 81.0 97.1
108
Table 4.5: Arc Parameters for Furnaces 1 and 2
Arc Power (MW) 26.83 28.01 29.81 30.98
Arc Voltage in Volts 231 227 244 250
Arc Resistance in milliohms 5.96 5.52 6.05 6.07
Average Arc lengths (mm) 228 223 243 250
Electrical Efficiency of Arc (%) 92.0 91.3 92.2 92.3
Arc Stability Index 1.40 2.30 1.18 1.01
Arc Radiation Index (MWV/ sq.cm) 68 70 79 85
Arc Radiation Intensity (MW-
meter)
2.0 2.1 2.4 2.6
Table 4.6: Regulation Parameters for Furnaces 1 and 2
Current change rate – kA/Sec 5.8 4.3 1.3 1.7
Regulation deviation % (Constant
Current)
14.9 10.3 3.3 4.2
I/I0 of regulation System (Constant
current)
0.6 0.64 0.9 0.7
Average impedance (milliohms) 7.3 7.1 7.1 7.0
Impedance change rate 1.5 4.07 0.27 0.48
Regulation Deviation % -(Constant
Impedance)
20.6 57.7 3.8 6.9
Z/Z0 of Regulation System (Constant
Impedance)
1.7 1.60 1.6 1.6
109
Table 4.7: Analysis of Furnace Parameters for EAF 1
Furnace –EAF-1 Phase-wise Deviation Cumulative
Operating Voltages
Volts
U1 284.3 ∆ U1 1.3% Fur. Voltage
491 U2 284.2 ∆ U2 1.2%
U3 281.9 ∆ U3 1.4%
Operating Currents
kA
I1 39.2 ∆ I1 15.9%
Fur. currents
38.8 kA
I2 39.2 ∆ I2 13.2%
I3 38.0 ∆ I3 15.6%
Active Power Input
MW
P1 9.6 ∆ P1 18.6% Total 3 ph.
MVA
29.16
P2 10.0 ∆ P2 17.1%
P3 9.5 ∆ P3 18.7%
Transformer output
MVA
S1 11.14 ∆ S1 17.7% Total 3 ph-
MVA
32.98
S2 11.14 ∆ S2 16.1%
S3 10.70 ∆ S3 48.5%
Operating Reactance-
m ohms
X op-1 3.86 ∆ X op-1 25.9%
Xop3.51 mΩ X op-2 3.20 ∆ X op-2 22.0%
X op-3 3.46 ∆ X op-3 25.6%
Operating Impedance
m ohms
Z op-1 7.78 ∆ Z op-1 21.4%
Z op 7.77 Z op-2 7.63 ∆ Z op-2 16.5%
Z op-3 7.91 ∆ Z op-3 20.0%
Operating power
factor
Cos Φ1 0.86 ∆ Cos Φ1 8.8%
Avg Cos Φ
0.88
Cos Φ2 0.90 ∆ Cos Φ2 7.5%
Cos Φ3 0.89 ∆ Cos Φ3 7.3%
110
Table 4.8: Power Distribution Balance for EAF 1
Current Distribution
Ph-1 101.1% Voltage
Distribution
Ph-1 102.6%
Ph-2 101.0% Ph-2 102.3%
Ph-3 97.9% Ph-3 95.1%
Power Distribution
Ph-1 33.0% Overall
Power
balance
%
94.8 Ph-2 34.4%
Ph-3 32.6%
Overall
Current Balance
%
96.9 overall
voltage
Balance
%
99.1
Table 4.9: Arc Parameters for Furnace 1
Arc resistance
m ohms
R a-1 5.76 ∆ R a-1 25.4% R a 5.96
mΩ
R a-2 6.03 ∆ R a-2 21.4%
R a-3 6.09 ∆ R a-3 26.1%
Arc Power
MW
P a-1 8.83 ∆ P a-1 5.9% Total arc
power
26.83
P a-2 9.24 ∆ P a-2 5.6%
P a-3 8.76 ∆ P a-3 5.9%
Arc Voltage
Volts
V a-1 226 ∆ V a-1 42.60% Arc voltage
231 V a-2 236 ∆ V a-2 49.2%
V a-3 232 ∆ V a-3 11.4%
Arc Intensity MW-
meter
Ri-1 1.95 Arc
stability
index
STB-1 1.54
Ri-2 2.16 STB-2 1.28
Ri-3 2.00 STB-3 1.38
Relative refractive
index
RRi-1 33.1% Arc
radiation
index
MWV/
Rx-1
R x-2
Rx-3
65
RR i-2 34.5% 72
RR i-3 32.4% 67
111
sq.cm
Arc efficiency
(Electrical)
ηa-1 91.7 Power loss
MW
(inc.s/c
loss)
Lp-1
Lp-2
Lp-3
0.80
ηa-2 92.1 0.79
ηa-3 92.1 0.75
Arc length -mm La-1 221 Impedance
distribution
Ph-1
Ph-2
Ph-3
100%
La-2 234 98%
The performance of electric arc furnace is determined from circle diagrams. The
performance can be calculated provided the electrical parameters like arc length,
efficiency, refractive index, etc are measured. For two furnaces the measurements are
carried out and the various graphs are plotted.
4.12 Statistical Analysis of Arc Furnace
Current in kA
Phase Current 1
Phase Current 2
Phase Current 3
Figure 4.12.1: Histogram for Phase Current for Tap 19, 505 V, Scrap Melting
112
Current in kA
Phase Cur rent 1
Phase Cur rent 2
Phase Cur rent 3
Figure 4.12.2: Histogram for Phase Current for Tap 21, 545 V, Scrap Melting
Phase Cur rent 1
Phase Cur rent 2
Phase Cur rent 3
Current in kA
Figure 4.12.3: Histogram for Phase Impedance for Tap 19, 505 V Scrap Melting
113
Phase Current 1
Phase Current 2
Phase Current 3
Figure 4.12.4: Histogram for Phase Impedance for Tap 21, 545 V Scrap Melting
The Histograms are plotted to determine the quality of regulation and study
the pattern of current distribution and Percentage Phase Impedance at taps 19 and 21
during scrap melting. It is observed that at tap 19, the fast acting of regulation is
required. The sensitivity of all phases seem to be acceptable showing upward trend.
For tap 21, with higher currents, it was found that, there are few very high current
fluctuations showing similar upward trend.
The histograms for Phase Impedance for tap 19 shows almost equal
distribution of values for all phases. The impedance set point is well and level of
sensitivity is good. Significant upward trend is noticed. For higher tap 21, the
impedance set points are very well placed showing high level of sensitivity. Graph of
phase two is shifted due to high current in phase 2.
4.12.1 Analysis from Circle Diagram
The relation between the electrical properties of the arc furnace and the arc
resistance can be described by the circle diagram. Assuming the concept of balanced
operation, the figure illustrates the the equivalent circuit diagram of one phase.
The performance of electric arc furnace is determined from circle diagrams. The
114
circle diagrams are drawn for the commonly used tap 21, 19 and 14. the diagrams are
based on nominal secondary tap voltages which translates to nominal primary voltage
of 33 kV. The measured primary voltage was normally around 32 kV. That means the
diagrams show always little higher values for voltage and power than the furnace
actually performs.
The furnace is operating in general in the range of stable arc ignition
(particularly during DRI-melting and finishing, when the slag conditions are good.),
just in the beginning of melting the arc tends to be unstable. Because the current
during early stage of melting is slightly below the calculated limits. (e.g. for tap 19:
505 V the Theoretical limit is 42.2 kA
Figure 4.12.1.1 (a): Operating Points on Circle Diagram
A usual way of describe an electrical system is circle (or PQ) diagram, where active
power P is plotted versus reactive power Q. In this diagram the working points
corresponding to a certain secondary voltage are located along a semi-circular shaped
curve (that can be deformed if a variable operational reactance is considered). An
example of a typical circular diagram is shown in Fig. 1.The ideal circular diagram is
a useful design tool. It is obtained from equations Eq. 1, where U is the voltage, X is
the short-circuit reactance and cos Ф is the power factor. For a given secondary
voltage selected by the chosen transformer tap, and assuming a constant reactance
Using this diagram it is possible to define the right set points of operation in order to
achieve the highest active power within the arc stability limits.
115
The development of the flicker phenomenon in AC electric arc furnaces is also
explained by means of the circle diagram, The active power absorbed by the furnace
is
P = ( !" # )
( !" #)" $! (4.1)
whereVPCCis the voltage at the common point of coupling, Rtand Xtare respectively
the resistance and the inductance of the supply system and Ra is the arc resistance.
Thus the active power consumed by the load is maximum when Rt + Ra = Xtand is
equal to
Pmax = %
&$! (4.2)
P
R
A
A1
A2
Q X
X
Figure 4.12.1.1 (b): Operating Points on Circle Diagram
Operating diagram of the AC furnace can be drawn in the (X, R) plane as in
Fig.f.12.1.1 (a). From equations (1) and (2) it is deduced that the maximum active
power for an operating point corresponds to the same amount of reactive power
consumption. Arc furnaces consume consequently large quantities of reactive power
which should be compensated.
Around an operating point the resistance variations of the arc provoke
essentially variations of reactive power as shown in Fig.f.12.1.1 (b). If the operating
point moves from A1 to A2, the variation of the reactive power can be up to ten times
larger than the variation in active power. It is well known that the variation of the
reactive power has a direct impact on the voltage profile of the transmission system.
This explains why the variation of the reactive power consumption of an arc furnace
produces flicker phenomena.
The maximum active power for an operating point corresponds to the same
amount of reactive power consumption. Arc furnaces consume consequently large
116
quantities of reactive power which should be compensated. Around an operating point
the resistance variations of the arc provoke essentially variations of reactive power as
shown in Fig.1. If the operating point moves from A1 to A2, the variation of the
reactive power can be up to ten times larger than the variation in active power. It is
well known that the variation of the reactive power has a direct impact on the voltage
profile of the transmission system. This explains why the variation of the reactive
power consumption of an arc furnace produces flicker phenomena.
4.12.2 Effect of Electrode Regulation System on the Operating Point
It is concluded that the observed behavior is a consequence of the electrode
regulation system, whose effects are noticeable in the time scale (several seconds) that
is being considered in the measurements. In a short time scale (a cycle) the
characteristics that determine the arc behavior (voltage, reactance, arc length) can be
considered stable, and the relationships among them can be obtained theoretically or
from experimental measurements of wave forms, and expressions relating operational
reactance to intensities can be obtained. But in a longer time scale these relationships
are no longer valid; because they are superseded by a stronger (but slower) driving
force, that is, the electrode regulation system.
Figure 4.12.2.1: Setting of Operating Point by Electrode Control
117
As the electrical magnitudes change continuously during process in order to
keep a selected working point (for example a constant intensity), an active system that
is able to dynamically change some parameter is required. This is the task of the
regulation system, that monitors some system variable (intensities, impedance, power
and moves electrodes up or down until the right value is achieved. The movement of
the electrodes, that is the response of the regulation system, is much slower than the
fluctuations that are taking place in the arcs. So when we look at the system in a long
time scale the observed results are controlled by the regulation, and not by other short
time effects. In the long scale (several minutes), if operational settings (tap, intensity)
are not changed the secondary intensity is constant. Intensity will fluctuate a lot and it
can’t be considered constant in a short time scale, but in the long scale regulation
dominates; so on average intensity can be taken as constant. Thus, the fluctuations in
the arc behavior in the long scale cannot manifest as intensity variations, because it is
kept constant by the regulation, so it manifests as variations in tension and power
factor. But using the same reasoning in the long scale voltage is also constant
(transformer tap) so the only degree of freedom is the power factor.
4.12.3 Response to an Increase of Primary Voltage
Due to maintenance operations in the substation yard at Bhugaon Plant,
Wardha the second harmonic filter was down during some time. When it was working
again, an increase in the primary voltage of the EAF transformer was observed, .
Comparing power data before and after the primary voltage increase and separating
data collected during main melting phase and during slag foaming, different behavior
is observed. For data collected from slag foaming stage the averaged reactive power
remains constant after the change, while the apparent power is higher. This is not
observed for data collected during main melting phase, where reactive power and
apparent power both increase. Active power logically increases in both cases. This
different behavior can be explained using the constant apparent power diagram.
Comparing power data before and after the primary voltage increase and separating
data collected during main melting phase and during slag foaming, different behavior
118
is observed. For data collected from slag foaming stage the averaged reactive power
remains constant after the change, while the apparent power is higher. This is not
observed for data collected during main melting phase, where reactive power and
apparent power both increase. Active power logically increases in both cases. This
different behavior can be explained using the constant apparent power diagram. The
higher voltage is translated into a longer arc length. The reactive power during slag
foaming has the same value before and after the change because, first, secondary
intensity is the same (due to the electrode regulation set point) and, second, because
operating reactance has the same value: the minimum possible value. Slag foaming
stabilizes the arc in such way that despite of the arc length the measured reactance is
approximately the short-circuit reactance. In both situations the arc is fully covered by
the foamy slag. So reactive power, that can be expressed as Q = 3X (remains
constant. On the other hand, apparent power logically increases because voltage is
higher and intensity is constant. In a circle diagram, the new average working point
obtained after the primary voltage increase is obtained by a vertical displacement
from the point P1 (that lies on the S1 curve) to P2 (that lies on the S2 curve) . As active
power increases while reactive power doesn’t, power factor must also increase. This is
confirmed by the data collected: average power factor (computed as P/S) raises from
0.855 to 0.864 with the primary voltage increase.
P (MW)
COSϕ
P3
P2
P1
S1 (Vp<<)
S2 (Vp<<)
Q (Mvar)
Figure 4.12.3.1: Variation of Power with Increase in Primary Voltage
119
For the data collected during main melting phase the increase in primary
voltage results in increases both of apparent and reactive power (along with active
power). As before, the higher primary voltage is converted into a higher secondary
voltage, while intensity is the same due to the regulation set point that has elevated the
electrodes to a higher position in order to get a longer arc with higher resistance to
obtain the same intensity with higher voltage. On opposition to the slag foaming
situation an increase of arc length results in less stable arcs with a higher reactance.
So although intensity is the same reactive power increases due to the higher operating
reactance. In the circle diagram, the operating point after the change in primary
voltage will move from a point in the constant-S, S1 curve to a point in the S2 curve
with higher Q and P. As both powers change more or less in the same way, the
translation from one point to the other is done along a line of constant power factor,
so the new point can be computed as the cross of the line that contains P1 and the
origin and the S2 curve. The equal power factor before and after the voltage increase
is also confirmed experimentally, as the average values of power factor P/S are equal
to 0.84 in both situations.
Slag foaming quality and active power similar effect to the previously
described appears also in a different context. A foamy slag quality assessment
technique is used at Bhugaon plant, Wardha. If the slag foaming process is correctly
done, a low noise index is obtained, measured both using acoustic noise and electric
THD (Total Harmonic Distortion). If for some reason a good foaming is not achieved
(for example due to problems in oxygen or graphite injection) then a high noise index
is obtained. Relating the slag foaming noise index with the electrical variables (active
power and secondary voltages) measured in the furnace during the process an
interesting result is observed. When the noise index is low, meaning that a very good
foaming has been reached a strong correlation between measured active power and
averaged secondary voltage is observed. But if noise index is high, this dependence is
not observed and both variables are uncorrelated.
In the case of having a low noise index, with good quality foam, the slag
covers the arcs completely, so the operating reactance will be the lowest possible
120
value (close or equal to the short-circuit reactance), regardless of arc length and
secondary voltage. As secondary intensity is the same in all the process (due to the
regulation and in the long time scale), arc length is directly proportional to voltage,
and so is arc resistance. This results in an active power proportional to secondary
voltage through P=3=S cos Ψ while reactive power remains constant. Voltage
fluctuations during slag foaming process results in directly related active power
fluctuations (for low noise index).This can be written as:
= S
( !"#)
$ ≈ constant (4.3)
On the contrary, if the foaming achieved is not good enough (for example as
result of oxygen or graphite injection malfunction or non standard slag composition)
the noise index will be high. In this situation the variation in arc length caused by a
variation in secondary voltage will result in a variation of both resistance and
reactance, so the voltage fluctuations don’t result in power factor fluctuations. It can
be said that, approximately, reactance and resistance both changes in the same way so
power factor is the same. In this situation must be changed to
= S
( !"#)
$ ≈ 0 (4.4)
This explains why the active power and the averaged secondary voltages are
not correlated when a high noise index is detected.
Discussion
In this work power data coming from an AC EAF has been analyzed using a
PQ diagram. It is observed that for a given operation set points (secondary voltage)
the distribution of active and reactive power points in the diagram lies on a curve of
constant apparent power (S) rather than in a constant voltage curve, as it is used for
theoretical determination of set points. This is explained considering the long time
scale of the measurements, where the constant intensity electrode regulation system
response dominates over other effects. Making use of the interpretation of the diagram
as a constant-S diagram, we have explained several phenomena observed in the EAF
under study. The increase of primary voltage resulted in a higher apparent power, but
for data collected during foamy slag this is not translated in higher reactive power,
121
that remained the same. This is not observed for data coming from main melting
stage, where apparent and reactive power both increase. Also, the different
relationship observed between active power and secondary voltage during slag
foaming when the noise index is high or low is also explained.
4.12.4 Effect of Phase Rotation
The phase rotation of the furnace is measured clockwise, which is normally
not recommended, because of higher risk of unscrewing of electrode joints. In
addition to this the direction of the slag moving due to electromagnetic forces is
opposite and thus is anticlockwise. This means the slag moves to the front from the
area where it is mainly created. Less efficient melting together with higher energy
consumption is possible.
4.13 Computational Analysis of EAF
Test system under study is considered here for analysis. When furnace 1 is tested for
the input. The results for Iarc,Varc, and Rarc are obtained as shown in the figure. The
V-I characteristics for the arc furnace is similar and close to the theoretical model 3 as
mentioned earlier.
Figure 4.11.1: Waveforms of Iarc,Varc,Rarcand V-I Characteristics of Arc Furnace
122
Vig
R1
VaR3
R2
i3 i2i1
Current(A)-1 -0.5 0 0.5 x 105 1
400
300
200
100
0
-100
-200
-300
-400
Figure 4.13.1: Theoretical Model
It is noticed that, there is little difference in the two models as illustrated,
which confirms the validity of the model. The nonlinearity exists due to the fact that
assumptions are made mostly non electric factors which contribute.
4.14 Comparison of Experimental Analysis and Statistical Analysis
It has been observed that statistical analysis shows the trend variations for impedance
and current distribution which is slightly different than values of parameters as
mentioned in experimental analysis. There is no information regarding change in
operating band of impedance or tap setting in experimental analysis, so statistical tool
of histograms prove to be useful.
4.15 Justification of Error For Arc Furnace Model
There is slight difference in both these analysis, the main reasons behind the variation
in non electric factors like DRI feeding pattern, use of non precise method of
electrode control. Manual method of regulation may contribute to the error of results.
There is a need of exact and precise mode of operation leading to new control strategy
which will make current distribution to be more uniform and problem of thermal
balancing will be sorted out.
123
4.16 SVC Light Analysis
SVC is a power quality conditioning device used for limiting flicker in arc furnaces,
rolling mills. This proves to be beneficial when it was used at different sites in steel
plants. This discussion will incorporate the uses of SVC at different locations in arc
plants.
4.17 Experimental and Computational Analysis for Flicker Mitigation
The electric arc furnace is deriving its power from MSETCL grid. Due to the
large power of the new steel industries associated with EAF, above existing the
furnaces, and relatively weak grid, concerns were raised. The EAF is a generator of
several kinds of disturbances. Furthermore, the EAF is an unsymmetrical load on the
three phase feeding grid, giving rise to current and voltage unbalance in the grid. The
EAF is a generator of harmonics, odd and even as well as inter harmonics.
Considering this scenario, the Jalna MIDC area having 90% of the power in
the area is consumed by steel industries and more plants are to in waiting for
installations. The analysis of fluctuations and reactive power flow were carried out.
Due to a modest short circuit level at the PCC, unless properly remedied, the EAFs
would become a formidable source of disturbances, which would spread through the
grid to other consumers of electric power. The EAF is also a heavy consumer of
reactive power.
To perform the computational analysis, a detailed model was used with the
power system as well as the EAF with the SVC Light. The complete SVC Light
system was represented in the EMTDC model. The model included all main circuit
components such as the IGBT converter with its DC capacitors, the phase reactors and
the harmonic filters. The model also included a complete representation of the control
system and the valve firing system. The EAF was represented as a current source,
124
reproducing the current waveform recorded on the old Kalika Stainless EAF. The data
used in the simulation had a length of 10 minutes, starting at the beginning of a
meltdown process, the most troublesome part of the melt from a flicker point of view.
To evaluate the flicker level, the voltage fluctuations were computed at the 33 kV bus.
The flicker level Pst was then estimated according to IEC [1].
A model of the flicker meter was included in the digital model. The voltage
measured at the PCC was passed through different filters to obtain the flicker level
according to the desired criteria. The output of the flicker meter was based on the
instantaneous flicker value of the IEC meter (output 3). Using the model and the input
data, the flicker level at the 33 kV bus was estimated both with and without the SVC
Light in operation.
126
Figure 4.17.1: Simulation at Pre Melting Stage
a) EAF active power
b) EAF and step-down transformer reactive power
c) Flicker
d) Bus voltage
e) EAF and step-down transformer negative sequence current.
In Fig.4.17.1, the corresponding flicker levels at the PCC are shown with the
SVC Light in service. Based on the figures, it can be noted that the active, useful,
power of the EAF increases when the SVC Light compensates the reactive power
consumed by the EAF. This is beneficial for the steel process with shorter melting
times, as well as for the power supplier with less reactive power flow. The design
studies indicated a flicker improvement ratio of approximately 13/3.1=4.2.
To assess the accuracy of the SVC model for MSETCL, actual field
measurements are done. For that two sites were chosen to see the impact of SVC
Light on flickers. The analysis presented in the next section is based on the data and
waveforms collected on practical sites.
4.17.1 Experimental Analysis of SVC Light Commissioned at Bhilai Steel Plant
For analyzing the effect of SVC Light, practical measurement of flickers at the
EAF in the steel rolling plant of Bhilai Steel of Steel Authority of India Limited
(SAIL) situated in the Bhilai city of Chattisgarh, India was carried out. The Bhilai
Steel has commissioned 44 Mvar SVC Light for its electric arc furnace. The single
line diagram of the EAF and SVC Light is shown in (Figure 4.17.1). The EAF is rated
31.5 MVA with a 20% temporary overload capability, whereas the LF is rated 6 MVA
plus a 30% overload capability. Both furnaces are fed from a 132 kV grid via an
intermediate voltage of 11 kV (Fig.4.17.1). The feeding grid is relatively weak, with a
fault level at the P.C.C. of about 1000 MVA. It is obvious that this is quite insufficient
to enable operation of the two furnaces while up keeping reasonable power quality in
the grid. The SVC Light is rated at 0 - 44 Mvar of reactive power generation,
continuously variable. This dynamic range is attained by means of a VSC rated at 22
MVA in parallel with two harmonic filters, one rated at 14 Mvar existing in the plant
initially and one installed as part of the SVC Light undertaking, rated at 8 Mvar. Via
127
its phase reactors, the VSC is connected directly to the furnace bus voltage of 11 kV.
During the energisation of the VSC, the DC capacitors are charged via the charging
resistors. While the DC capacitors are charged, the by-pass switch is closed. The main
circuit diagram of the SVC Light is shown in the Figure 4.17.2.
Figure 4.17.2: Single-Line Diagram of EAF Feeding Network and Compensation
v
v
v
Figure 4.17.3: Main Circuit Diagram of Bhilai SVC Light
The possibility for the SVC Light to “follow” the stochastically varying
furnace current gives an enormous opportunity to reduce voltage flicker. However,
with its quick response, also other unpleasant disturbances can easily be reduced. The
recording below shows the initial operation of the SVC Light when paralleled to the
EAF in Bhilai steel Plant. Signals show the SVC Light ability to track the rapid
changing of the furnace current.
128
Figure 4.17.4: Tracking of Rapid Changes of EAF Current
With a switching frequency higher than 1 kHz, even fast transients can be
damped. In some installations switching transients from a furnace transformer could
for example lead to unexpected problems. With the SVC Light technology, the
furnace operation with all switching transients will be compensated.
Field measurements have been performed in order to evaluate the performance
of the SVC Light at Bhilai site. So far, the measurements have mostly been focusing
on flicker. The recordings and evaluation presented below show flicker mitigation of
3.4 times. The flicker mitigation is expected to increase to a factor around 4.5 to 5.0
times when new auxiliary transformers have been installed. The flicker measurements
have been performed according to the UIE/IEC method. The method is well known in
Europe, Canada, South America and South Africa and is also getting more common in
the United States.
Statistical evaluation
In order to evaluate flicker generation with and without SVC Light a statistical
evaluation has been performed. The figures below show histograms for the following
three cases:
Figure 4.17.5: Furnace in operation, without SVC Light. Pst(95%) = 3.90 p.u.
4.17.6: Furnace in operation, with SVC Light. Pst(95%) = 1.21 p.u.
4.17.7: Background flicker generation. Pst(95%) = 0.41 p.u
129
Figure 4.17.5: Flicker Generation without SVC Light
Figure 4.17.6: Flicker Generation with SVC Light in Operation.
Figure 4.17.7: Background Flicker Generation
130
According to the UIE (International Union For Electro heat), the recommend
practice to evaluate flicker severity from multiple sources is per the following
formula:
1/m
m
ST
i
PST = (P ) ∑ (4.5)
where m is the summation coefficient. The summation coefficient considers the risk
of coincident furnace operation. The factor is recommended to vary from 1 up to 4.
m=4 is used, when furnaces specifically run in order to avoid coincident melts. m=1 is
used when there is a very high occurrence of coincident voltage changes. The
background flicker is generated by many sources, and will therefore appear more or
less constant over the day. To deduct the background flicker, an “m” factor of 1
should be used. However to perform the evaluation in a very conservative way, a
factor of two is used.
In the case of flicker generated by the EAF only and without background
flicker, we get with no SVC Light in operation:
2 2 1/3 2 2 0.5
STA ST1 ST3P = [(P - P )] = [(3.90 - 0.41 )] = 3.88 (4.6)
p.u.
2 2 1/3 2 2 0.5
STB ST2 ST3P = [(P - P )] = [(1.21 -0.41 )] =1.14 (4.7)
p.u.
The residual flicker value with the SVC Light and EAF in operation and
without background flicker is:
The flicker mitigation by the SVC Light is:
STASVCLight
STB
P 3.88R = = = 3.4 p.u.
P 1.14 (4.8)
Increased furnace power
An arc furnace requires a stable voltage supply for optimum performance. An
SVC Light can instantaneously compensate the random reactive power variations, and
hence the voltage variations, of an EAF.
131
Reactive power compensation by an SVC Light or an SVC helps to obtain the
following production benefits:
A higher and stabilized voltage level at the furnace bus bar, giving:
- Shorter melt down times
- Reduced energy losses
- Reduced electrode consumption.
4.18 Experimental Analysis and Computational Analysis of SVC Light
Commissioned at Steel Plant
*
*
*
*
**
220 kV
33 kV
220/34.5 kV
50th
0.8 Mvar
25th
2 Mvar
3rd
25 Mvar
4th
31.3 Mvar+ 32 MvarEAF
Figure 4.18.1.: Single Line Diagram of the EAF and the SVC Light
In Fig. 4.18.1, the EAF is shown to the left. Then two high-pass filters for
reduction of harmonics follow together with the VSC and its switchgear. A resistor is
temporarily inserted in series with the VSC during start-up. The resistor is used to
limit the inrush current during the start sequence. Finally two filters to provide bulk
power to bias capacitive reactive power are found. The harmonic filters are designed
to fulfill the specified voltage and current distortion at PCC. To fulfill these
requirements the tuning and damping of the harmonic filters have been selected. The
total filter rating is equal to the VSC rating providing an operation range from zero to
132
twice the VSC rating. Fig. 4.18.1 shows of the installation of the SVC Light at the
Lloyd Steel plant.
Field measurements have been performed to validate the flicker improvement
performance. The phase currents of arc furnace and compensator should be digitally
recorded simultaneously during a typical melting period. The fluctuating voltages and
corresponding instantaneous flicker levels should then be calculated using the
impedance of the grid. The grid model was tuned to give optimal correlation between
flicker caused by the measured 33 kV voltages and flicker caused by the calculated
voltages, which were based on the measured currents. Using only the arc furnace
currents the reference Pst0 is found. This corresponds to what could be expected
without any compensation. Then, the reduced flicker level Pst1 is calculated using the
total current of the arc furnace and the compensator. This corresponds to the real
operation case. The improvement ratio Pst0/Pst1 is finally calculated over the whole
melting period and then evaluated.
Measurements in a dynamic process with high sampling frequency require
special attention when selecting the equipment. A sophisticated measurement
computer with high bandwidth and synchronous sampling was found suitable for the
task. For the measurements, totally four three-phase signals are of interest:
1. The 33 kV bus voltages
2. The EAF currents
3. The VSC currents
4. The filter currents
The raw data were sampled with a frequency of 5200 Hz for off-line analysis.
For verification purposes, two different standard flicker meters were connected
simultaneously with the measurement computer. In the following plots, data from
these flicker meters are shown together with the results from the specified method. A
good correlation between the signals will verify the evaluation method and the
correctness of the used model.
133
First, the off-line flicker meter was verified against the standard flicker meter
output. In this process, tuning of the grid model is one part. The results are shown in
Figure 4.18.2.
Figure 4.18.2: Verification of the Off-Line Flicker Meter
The deviations between the Pst value calculated from measured bus voltage
and the Pst values obtained from the flicker meter are ignorable. The error is generally
about 2-4 % except during large Pstchanges. Note that the Pst- meters are not
synchronized, which explains the large errors at large Pst value changes. This test
validates the quality of the input data and the accuracy of the flicker meter
implemented in the digital model.
In Figure 4.18.2, subplot 1 shows the EAF active and reactive power, the two
top curves. The bottom curve shows the reactive power taken from the grid. Subplot 2
shows a comparison between actual measured 33 kV voltage and the corresponding
calculated voltage. The ignorable error is a verification of the grid impedance model.
Subplot 3 shows four different Pst curves calculated during sliding 10 minute
intervals. The top curve with the highest Pst levels shows the case with only EAF
current and no compensation. The three bottom curves only have small deviations and
show flicker curves based on the measured voltage, on the calculated voltage and on
data from the standard Pst meter. The flicker level from the simulation using EAF,
VSC and filter currents gives the same flicker level as the external flicker meter and
the flicker level using the measured voltage. Subplot 4, finally, shows the flicker
improvement ratio calculated as the ratio between Pst values with only EAF currents
and Pst values with the SVC Light in operation. The flicker improvement at the
134
beginning of the melt-down process is ignored because it contains the time window
when the EAF was not in operation and non-applicable flicker values.
Operation of the EAF with full power requires stable voltage and an efficient
compensator. Operating the EAF without compensation is also possible, however, at a
reduced power. During the measurement campaign measurements at reduced EAF
power were performed both without and with the SVC Light in operation. Fig. 4.18.3
shows the results of the data processing.
135
EAF MW&Mvar, Network Mvar
33 kV bus voltage
P 10 minutesst
P 10 Improvementst
P 1
0 I
mp
rov
eme
nt
stP
st
p.u
.M
W M
var
Figure 4.18.3: Flicker with Full EAF Power and with SVC Light in Operation
• Subplot 1: EAF power and grid reactive power.
136
• Subplot 2: Voltage profile; measured (black) and simulated (red).
• Subplot 3: Sliding Pst 10-minute values from measured voltage (black), from
simulation with EAF current only (red), simulated with EAF+VSC+Filter
currents (blue) and from external flicker meter (green).
• Subplot 4: Simulated flicker improvement ratio.
Two melts with the same EAF transformer tap changer patterns are shown. At
approximately 14:40, the SVC Light was put on line. Subplot 2 showing the 33 kV
bus RMS voltages clearly indicates the difference. The large voltage peaks during the
melting without the SVC Light are due to load rejection. The voltage is then
controlled with the 132/33 kV transformer tap changer and finally reaches the set
point. The voltage set point was chosen below unity to reduce the voltage amplitudes
after load rejection.
The flicker improvement ratio is calculated during a time window were the EAF is in
operation. When the EAF is out of operation the flicker improvement will be unity in
case of no background flicker and below unity to zero if there is disturbing
background flicker existing. The flicker improvement ratio was calculated using a
time window beginning 10 minute after EAF melting start and ending at the end of
the same heat. The 10 minute delay corresponds to the 10-minute time window used
by the flicker meter to exclude the period the EAF was not in operation. The method
was applied to the data with full EAF power. This time window includes two EAF
transformer energizations and includes the time window with the highest flicker level
recorded during the measurements. The result was a flicker improvement ratio of 4.6
times for full EAF power. On the other hand, the flicker improvement ratio with
lower power in the EAF is between 5 and 6 times. If higher flicker improvement is
desired, it is hence essential to choose an adequate rating of the SVC Light.
137
Network MW & Mvar
P 10 minutesst
P i
mp
rov
emen
tst
Pst
p.u
.M
W M
var
P improvementst
33 kV bas voltage
Figure 4.18.4: Flicker Without and with the SVC Light, Reduced EAF Power
138
Apart from the flicker mitigation performance of the SVC Light, it also
contributes to the reduction of negative phase sequence currents in the grid. Fig. 4.32
shows the positive and negative phase sequences of the grid current without (top) and
with (bottom) the SVC Light in operation.
Net
work -Seq
.N
etw
ork +
Seq
.Network kA Currents
Figure 4.18.5: Positive & Negative Phase Sequence Currents without &with SVC Light
Comparison of field results with the simulated results shows consistency in the
operation of SVC Light. It clearly observed that SVC will be proved to be an efficient
flicker mitigate instrument to MSETCL network to the rolling mills in Jalna,
Maharashtra. Hence following benefits are assessed to MSETCL Network on basis of
analysis done above.
The installation of the SVC Light has brought benefits not only to the steel plant, but
also to the grid owner:
• Acceptably low flicker level at the Point of Common Coupling.
• Acceptably low amounts of harmonic distortion.
• Adequate load balancing between phases of the 132 kVgrid.
• A high and constant power factor at the feeding point of the plant, with low and
constant reactive power consumption from the grid.
139
• Keeping grid reinforcements at a minimum. Hence, this is a win-win situation where
the steel works as well as the utility can gain from the SVC Light installation.
4.19 Comparison
Comparison of Experimental analysis and Computational analysis shows the SVC
light is useful in mitigating flicker. The software used for analysis is EMTDC which
requires correctness of data to be fed.
4.20 Justification for Error:
There is difference in experimental results and computational analysis, the resons are
tuning of SVC to random variations in arc power.