+ All Categories
Home > Documents > 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

Date post: 05-Mar-2016
Category:
Upload: instengg
View: 7 times
Download: 0 times
Share this document with a friend
Description:
vegabar transmitter manual
20
7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 1/20 Quick setup guide Pressure transmitter with ceramic measuring cell VEGABAR 82 Slave sensor for electronic differential pres- sure Document ID: 46332
Transcript
Page 1: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 1/20

Quick setup guide

Pressure transmitter with ceramic

measuring cell

VEGABAR 82Slave sensor for electronic differential pres-

sure

Document ID: 46332

Page 2: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 2/20

2

Contents

VEGABAR 82 • Slave sensor for electronic dierential pressure

4   6   3   3  

2  -E N-1  4   0  2  2   8  

Contents

1 For your safety

1.1 Authorised personnel ....................................................................................................... 31.2 Appropriate use ................................................................................................................ 3

1.3 Warning about incorrect use ............................................................................................. 31.4 General safety instructions ............................................................................................... 31.5 CE conformity ................................................................................................................... 31.6 Permissible process pressure .......................................................................................... 31.7 Environmental instructions ............................................................................................... 4

2 Product description

2.1 Conguration .................................................................................................................... 5

3 Mounting

3.1 General instructions for use of the instrument .................................................................. 7

3.2 Ventilation and pressure compensation ............................................................................ 73.3 Combination Master - Slave ............................................................................................. 8

4 Connecting to power supply

4.1 Connecting ....................................................................................................................... 94.2 Single chamber housing ................................................................................................. 104.3 Connection example ...................................................................................................... 10

5 Set up with the display and adjustment module

5.1 Parameter adjustment - Quick setup .............................................................................. 125.2 Parameter adjustment - Extended adjustment................................................................ 15

6 Supplement6.1 Technical data ................................................................................................................ 18

Information:

This quick setup guide enables a quick setup of your instrument.

You can nd further information in the corresponding, comprehensive

operating instructions. This manual is available on the supplied DVD

or in the download area under "www.vega.com".Operating instructions VEGABAR 82 - Slave sensor for elec-tronic diferential pressure: Document-ID 45050

Editing status of the quick setup guide: 2014-02-11

Page 3: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 3/20

3

1 For your safety

VEGABAR 82 • Slave sensor for electronic dierential pressure

      4      6      3      3      2   -      E      N   -      1      4      0      2      2      8

1 For your safety

1.1 Authorised personnel

All operations described in this operating instructions manual must

be carried out only by trained specialist personnel authorised by theplant operator.

During work on and with the device the required personal protectiveequipment must always be worn.

1.2 Appropriate use

VEGABAR 82 is a slave sensor for electronic dierential pressuremeasurement.

You can nd detailed information about the area of application in

chapter "Product description".

Operational reliability is ensured only if the instrument is properlyused according to the specications in the operating instructionsmanual as well as possible supplementary instructions.

1.3 Warning about incorrect use

Inappropriate or incorrect use of the instrument can give rise toapplication-specic hazards, e.g. vessel overll or damage to system

components through incorrect mounting or adjustment.

1.4 General safety instructions

This is a high-tech instrument requiring the strict observance of stand-ard regulations and guidelines. The user must take note of the safetyinstructions in this operating instructions manual, the country-specicinstallation standards as well as all prevailing safety regulations and

accident prevention rules.

The instrument must only be operated in a technically awless andreliable condition. The operator is responsible for trouble-free opera-tion of the instrument.

During the entire duration of use, the user is obliged to determine the

compliance of the necessary occupational safety measures with the

current valid rules and regulations and also take note of new regula-tions.

1.5 CE conformity

The device fullls the legal requirements of the applicable EC guide-lines. By axing the CE marking, we conrm successful testing of theproduct.

You can nd the CE Certicate of Conformity in the download section

of our homepage.

1.6 Permissible process pressureThe permissible process pressure is specied on the type label with"Process pressure", see chapter "Conguration". For safety reasons,

Page 4: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 4/20

4

1 For your safety

VEGABAR 82 • Slave sensor for electronic dierential pressure

4   6   3   3  

2  -E N-1  4   0  2  2   8  

this range may not be exceeded. This applies even if a measuring cellwith a measuring range (order-related) higher than the permissiblepressure range of the process tting is installed.

1.7 Environmental instructions

Protection of the environment is one of our most important duties.That is why we have introduced an environment management systemwith the goal of continuously improving company environmental pro-tection. The environment management system is certied accordingto DIN EN ISO 14001.

Please help us fulll this obligation by observing the environmentalinstructions in this manual:

•  Chapter "Packaging, transport and storage"

•  Chapter "Disposal "

Page 5: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 5/20

5

2 Product description

VEGABAR 82 • Slave sensor for electronic dierential pressure

      4      6      3      3      2   -      E      N   -      1      4      0      2      2      8

2 Product description

2.1 Conguration

The type label contains the most important data for identication and

use of the instrument:

2

1

14

15

16

17

13

11

12

5

3

6

4

7

8

9

10

Fig. 1: Layout of the type label (example)

1 Instrument type 2 Product code3 Field for approvals4 Power supply and signal output, electronics5 Protection rating6 Measuring range

7 Permissible process pressure8 Material, wetted parts9 Hardware and software version10 Order number 11 Serial number of the instrument 12 Data-Matrix-Code for Smartphone-App13 Symbol of the device protection class14 ID numbers, instrument documentation15 Reminder to observe the instrument documentation16 Notied authority for CE marking17 Approval directive

The type label contains the serial number of the instrument. With ityou can nd the following instrument data on our homepage:

•  Product code (HTML)

•  Delivery date (HTML)

•  Order-specic instrument features (HTML)

•  Operating instructions and quick setup guide at the time of ship-ment (PDF)

•  Order-specic sensor data for an electronics exchange (XML)

•  Test certicate (PDF) - optional

Go to www.vega.com, "VEGA Tools" and "Instrument search". Enter

the serial number.Alternatively, you can access the data via your smartphone:

Type label

Serial number - Instru-ment search

Page 6: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 6/20

6

2 Product description

VEGABAR 82 • Slave sensor for electronic dierential pressure

4   6   3   3  

2  -E N-1  4   0  2  2   8  

•  Download the smartphone app "VEGA Tools" from the " Apple App

Store" or the "Google Play Store"

•  Scan the Data Matrix code on the type label of the instrument or

•  Enter the serial number manually in the app

Page 7: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 7/20

7

3 Mounting

VEGABAR 82 • Slave sensor for electronic dierential pressure

      4      6      3      3      2   -      E      N   -      1      4      0      2      2      8

3 Mounting

3.1 General instructions for use of the instrument

Protect your instrument against moisture penetration through the fol-

lowing measures:•  Use the recommended cable (see chapter "Connecting to power

supply ")

•  Tighten the cable gland

•  Turn the housing in such a way that the cable gland points down-ward

•  Loop the connection cable downward in front of the cable gland

This applies particularly to:

•  Outdoor mounting

•  Installations in areas where high humidity is expected (e.g. through

cleaning processes)•  Installations on cooled or heated vessels

3.2 Ventilation and pressure compensation

The lter element is mounted into the electronics housing. It has thefollowing functions:

•  Ventilation of the electronics housing

•  Atmospheric pressure compensation (with relative pressure meas-uring ranges)

→ Turn the housing so that the lter element points downward afterthe instrument is installed. This provides better protection againstbuildup.

1 2 3

4 4 4

Fig. 2: Position of the lter element - non-Ex, Ex-ia version

1 Housing plastic, stainless steel precision casting 2 Housing aluminium3 Housing stainless steel, electropolished 4 Filter element 

With the following instruments a blind plug is installed instead of thelter element:

•  Instruments in protection IP 66/IP 68 (1 bar) - ventilation via capil-laries in non-detachable cable

•  Instruments with absolute pressure

Protection against mois-ture

Instruments in non-Exand Ex-ia version

Page 8: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 8/20

8

3 Mounting

VEGABAR 82 • Slave sensor for electronic dierential pressure

4   6   3   3  

2  -E N-1  4   0  2  2   8  

3.3 Combination Master - Slave

In principle, any sensor combination within the VEGABAR 80 series isallowed. The following requirements must be fullled:

•  Conguration, Master sensor suitable for electronic dierential

pressure•  Pressure type is identical for both sensors, i.e. relative pressure/ 

relative pressure or absolute pressure/absolute pressure

•  Master sensor measures the higher pressure

•  Measurement setup as shown in the following chapters

The measuring range of each sensor is selected to t the measuringpoint. Hence the measuring ranges of master and slave do not haveto coincide exactly.

Depending on the application, individual combinations can result, seefollowing table with examples:

Examples Vessel withheight 12 m, me-

dium water

Superimposed

pressure 1 bar

Vessel with level250 mm, medi-

um water

Superim-

posed pressure

350 mbar

Pipeline, staticpressure 0.8 bar,

medium gas

Diferential

pressure at the

orice: 50 mbar

Nominal meas-

uring range,

Master

2.5 bar 0.4 bar 1 bar

Nominal meas-

uring range,

Slave

1 bar 0.4 bar 1 bar

Adjustment

range

-1 … +3 bar -0.48 … +0.48 bar -1.2 … +1.2 bar

Turn Down (TD) 1.15 : 1 14 : 1 20 : 1

The adjustment range corresponds to that of the Master. Note the

max. recommended Turn Down. See chapter "Technical data".

Measuring result = Measured value Master minus measuredvalue Slave

Page 9: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 9/20

9

4 Connecting to power supply

VEGABAR 82 • Slave sensor for electronic dierential pressure

      4      6      3      3      2   -      E      N   -      1      4      0      2      2      8

4 Connecting to power supply

4.1 Connecting

The connection to the Master sensor is carried out via spring-loaded

terminals in the housing.Information:

The terminal block is pluggable and can be removed from theelectronics. To do this, lift the terminal block with a small screwdriverand pull it out. When reinserting the terminal block, you should hear itsnap in.

Proceed as follows:

1. Unscrew the housing cover

2. Loosen compression nut of the cable entry gland

3. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.1 cm (0.4 in) insulation from the individual wires or use suppliedconnection cable

4. Insert the cable into the sensor through the cable entry

Fig. 3: Connection steps 5 and 6 

5. Insert the wire ends into the terminals according to the wiring plan

Information:Solid cores as well as exible cores with cable end sleeves areinserted directly into the terminal openings.

In case of exible cores without end sleeves, press the terminal fromabove with a small screwdriver, the terminal opening is then free.When the screwdriver is released, the terminal closes again.

You can nd further information on the max. wire cross-section under

"Technical data/Electromechanical data"6. Check the hold of the wires in the terminals by lightly pulling on

them

Connection technology

Connection procedure

Page 10: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 10/20

10

4 Connecting to power supply

VEGABAR 82 • Slave sensor for electronic dierential pressure

4   6   3   3  

2  -E N-1  4   0  2  2   8  

7. Connect the screen to the internal ground terminal, connect theouter ground terminal to potential equalisation

8. Tighten the compression nut of the cable entry gland. The seal

ring must completely encircle the cable

9. Unscrew the bling plug on the Master, screw in the supplied cable

gland

10. Conenct cable to Master

11. Screw the housing cover back on

The electrical connection is nished.

4.2 Single chamber housing

The following illustration applies to the non-Ex, Ex-ia and Ex-d ver-sion.

5 6 7 84

2

1

Master

Fig. 4: Wiring plan VEGABAR 82 Slave sensor 

1 To the Master sensor  2 Ground terminal for connection of the cable screen1)

4.3 Connection example

5 6 7 8

4

2

3

1

4

51   2+( ) (-)   6 7 8

4...20mA

Fig. 5: Connection example VEGABAR 82 slave sensor 

1 Master sensor  2 VEGABAR 82 slave sensor 

3 Connection cable4 Supply and signal circuit, Master sensor 

Electronics and terminal

compartment

Connection example,slave sensor

1)  Connect screen here. Connect ground terminal on the outside of the housingto ground as prescribed. The two terminals are galvanically connected.

Page 11: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 11/20

11

4 Connecting to power supply

VEGABAR 82 • Slave sensor for electronic dierential pressure

      4      6      3      3      2   -      E      N   -      1      4      0      2      2      8

The connection between VEGABAR 82 and the VEGABAR 82 slavesensor is made with a standard cable according to the chart:

Master sensor Slave sensor

Terminal 5 Terminal 5

Terminal 6 Terminal 6

Terminal 7 Terminal 7

Terminal 8 Terminal 8

Page 12: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 12/20

12

5 Set up with the display and adjustment module

VEGABAR 82 • Slave sensor for electronic dierential pressure

4   6   3   3  

2  -E N-1  4   0  2  2   8  

5 Set up with the display and adjustment

module

5.1 Parameter adjustment - Quick setup

To quickly and easily adapt the sensor to the application, selectthe menu item "Quick setup" in the start graphic on the display andadjustment module.

Carry out the following steps in the sequence specied below. Thepresettings apply to all applications.

You can nd "Extended adjustment " in the next sub-chapter.

1. Measurement loop name

In the rst menu item you assign a suitable measurement loop name.Permitted are names with max. 19 characters.

2. ApplicationIn this menu item you activate/deactivate the slave sensor for elec-tronic dierential pressure and select the application.

Note:It is absolutely necessary to activate the slave sensor in advance tohave the applications displayed in the electronic dierential pressure

measurement menus.

3. UnitsIn this menu item you determine the adjustment and temperatureunits of the instrument. Depending on the selected application in themenu item " Application", dierent adjustment units are available.

4. Unit, static pressureIn this menu item, you determine the unit of the static, i.e. superim-posed pressure.

5. Position correctionIn this menu item you compensate the inuence of the installationposition of the instrument (oset) on the measured value.

6. Min. adjustmentIn this menu item you carry out the min. adjustment for level.

Enter the percentage value and the corresponding pressure value for

the min. level.

7. Max. adjustmentIn this menu item you carry out the max. adjustment for level.

Presettings

Quick setup - Level meas-urement

Page 13: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 13/20

13

5 Set up with the display and adjustment module

VEGABAR 82 • Slave sensor for electronic dierential pressure

      4      6      3      3      2   -      E      N   -      1      4      0      2      2      8

Enter the percentage value and the corresponding pressure value forthe max. level.

The quick setup for level measurement is nished.

4. Position correctionIn this menu item you compensate the inuence of the installationposition of the instrument (oset) on the measured value.

5. Min. adjustmentIn this menu item you carry out the min. adjustment for ow.

Enter the percentage value and the corresponding pressure value forthe min. ow.

6. Max. adjustmentIn this menu item you carry out the max. adjustment for ow.

Enter the percentage value and the corresponding pressure value forthe max. ow.

7. LinearizationIn this menu item, you select the characterics of the output signal.

The quick setup for ow measurement is nished.

4. Unit, static pressureIn this menu item, you determine the unit of the static, i.e. superim-posed pressure.

5. Position correctionIn this menu item you compensate the inuence of the installationposition of the instrument (oset) on the measured value.

6. Zero adjustmentIn this menu item you carry out the zero adjustment for the dierentialpressure.

Enter the respective pressure value for 0 %.

7. Span adjustmentIn this menu item you carry out the span adjustment for the dierentialpressure

Enter the respective pressure value for 100 %.

Quick setup - Flow meas-urement

Quick setup - Diferentialpressure measurement

Page 14: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 14/20

14

5 Set up with the display and adjustment module

VEGABAR 82 • Slave sensor for electronic dierential pressure

4   6   3   3  

2  -E N-1  4   0  2  2   8  

The quick setup for dierential pressure measurement is nished.

4. Unit, static pressureIn this menu item, you determine the unit of the static, i.e. superim-posed pressure.

5. Position correctionIn this menu item you compensate the inuence of the installationposition of the instrument (oset) on the measured value.

6. DistanceIn this menu item, you enter the installation distance between masterand slave sensor.

7. Min. adjustmentIn this menu item you carry out the min. adjustment for density.

Enter the percentage value and the corresponding density value for

the min. density.

8. Max. adjustmentIn this menu item you carry out the max. adjustment for density.

Enter the percentage value and the corresponding density value forthe max. density.

The quick setup for density measurement is nished.

4. Unit, static pressureIn this menu item, you determine the unit of the static, i.e. superim-posed pressure.

5. Position correctionIn this menu item you compensate the inuence of the installationposition of the instrument (oset) on the measured value.

6. DistanceIn this menu item, you enter the installation distance between master

and slave sensor.

7. Min. adjustment

In this menu item, you carry out the adjustment for the min. height ofthe interface.

Enter the percentage value and the corresponding height of the

interface.

8. Max. adjustmentIn this menu item, you carry out the adjustment for the max. height ofthe interface.

Enter the percentage value and the corresponding height of theinterface.

Quick setup - Densitymeasurement

Quick setup - Interfacemeasurement

Page 15: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 15/20

15

5 Set up with the display and adjustment module

VEGABAR 82 • Slave sensor for electronic dierential pressure

      4      6      3      3      2   -      E      N   -      1      4      0      2      2      8

The quick setup for interface measurement is nished.

5.2 Parameter adjustment - Extended adjustment

For technically demanding measuring points, you can carry outextended settings in "Extended adjustment ".

The main menu is divided into ve sections with the following func-tions:

Setup: Settings, e.g., for measurement loop name, application, units,position correction, adjustment, signal output

Display: Settings, e.g., for language, measured value display, lighting

Diagnosis: Information, e.g. on instrument status, pointer, measure-

ment reliability, simulationAdditional adjustments: PIN, date/time, reset, copy function

Info: Instrument name, hardware and software version, date of manu-facture, sensor features

In the main menu item "Setup", the individual submenu items shouldbe selected one after the other and provided with the correct param-eter values.

The following submenu points are available:

In the following section, the menu items from the menu "Setup" forelectronic dierential pressure measurement are described in detail.Depending on the selected application, dierent sections are relevant.

Information:

Further menu items of the menu "Setup" as well as the completemenus "Display ", "Diagnosis", " Additional adjustments" and "Info"are described in the operating instructions of the respective master

sensor.

Main menu

Page 16: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 16/20

16

5 Set up with the display and adjustment module

VEGABAR 82 • Slave sensor for electronic dierential pressure

4   6   3   3  

2  -E N-1  4   0  2  2   8  

Setup

Menu item

Measurement loop name

Application Slave for electronic dierential pres-

sure

Application

Units Unit of measurement

Static pressure

Position correction

Adjustment Distance (with density and interface)

Min. adjustment

Max. adjustment

Damping Integration time

Linearization Linearization type

Current output Current output - Mode

Current output - Min./Max.

Block adjustment

Display

Menu item

LanguageDisplayed value 1

Displayed value 2

Backlight

Diagnostics

Menu item

Sensor status

Peak value indicator Pressure

Temperature

Simulation

Additional adjustments

Menu item

PIN

Date/Time

Copy instrument settings

Special parameters

Scaling Scaling size

Scaling format

Page 17: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 17/20

17

5 Set up with the display and adjustment module

VEGABAR 82 • Slave sensor for electronic dierential pressure

      4      6      3      3      2   -      E      N   -      1      4      0      2      2      8

Menu item

Current output Current output - Size

Current output - adjustment

HART mode

DP ow element Unit

Adjustment

Page 18: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 18/20

18

6 Supplement

VEGABAR 82 • Slave sensor for electronic dierential pressure

4   6   3   3  

2  -E N-1  4   0  2  2   8  

6 Supplement

6.1 Technical data

Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar

Options of the cable entry

 Ʋ Cable gland M20 x 1.5

 Ʋ Cable diameter (options) 5 … 9 mm (0.20 … 0.35 in)

6 … 12 mm (0.24 … 0.47 in)

10 … 14 mm (0.39 … 0.55 in)

 Ʋ Cable entry ½ NPT

 Ʋ Blind plug M20 x 1.5; ½ NPT

 Ʋ Closing cap M20 x 1.5; ½ NPT

Wire cross-section (spring-loaded terminals)

 Ʋ Massive wire, cord 0.2 … 2.5 mm² (AWG 24 … 14)

 Ʋ Stranded wire with end sleeve 0.2 … 1.5 mm² (AWG 24 … 16)

Interface to the Master sensor

Data transmission digital (I²C-Bus)

Conguration, connection cable 4-wire, screened

Cable length max. 25 m

Voltage supply for the complete system through Master

Operating voltage UB

 Ʋ Non-Ex instrument 12 … 35 V DC

 Ʋ Ex-d instrument 12 … 35 V DC

 Ʋ Ex-ia instrument 12 … 30 V DC

 Ʋ Ex-d-ia instrument with ship approval 15 … 35 V DC

Interpolation protection Integrated

Permissible residual ripple - Non-Ex, Ex-ia instrument

 Ʋ for UN 12 V DC (9.6 V< U

B < 14 V) ≤ 0.7 V

e (16 … 400 Hz)

 Ʋ for UN 24 V DC (18 V< U

B < 35 V)

≤ 1.0 Ve (16 … 400 Hz)Permissible residual ripple - Ex-d-ia instrument

 Ʋ for UN 24 V DC (18 V< U

B < 35 V) ≤ 1 V

e (16 … 400 Hz)

Load resistor

 Ʋ Calculation (UB - U

min)/0.022 A

 Ʋ Example - Non-Ex instrument withU

B= 24 V DC

(24 V - 12 V)/0.022 A = 545 Ω

Page 19: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 19/20

19

Notes

VEGABAR 82 • Slave sensor for electronic dierential pressure

      4      6      3      3      2   -      E      N   -      1      4      0      2      2      8

Page 20: 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

7/21/2019 46332 en VEGABAR 82 Slave Sensor for Electronic Differential Pressure

http://slidepdf.com/reader/full/46332-en-vegabar-82-slave-sensor-for-electronic-differential-pressure 20/20

Printing date:

VEGA Grieshaber KG

 Am Hohenstein 113

77761 Schiltach

G

      4      6      3      3      2   -      E      N   -      1      4      0      2      2      8

 All statements concerning scope of delivery, application, practical use and operat-

ing conditions of the sensors and processing systems correspond to the information

available at the time of printing.

Subject to change without prior notice

© VEGA Grieshaber KG, Schiltach/Germany 2014

Phone +49 7836 50-0

Fax +49 7836 50-201

E-mail: [email protected]


Recommended