Inspection Report Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum, Dan Phillips and David Herrell Property Address: 5555 Address Row Western MI, MI 49546 J.W. Inspection Services of Michigan John Wade 4001 Bedaki NE Lowell, MI 49331 616 889 0043
Transcript
Page 1: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

Inspection ReportTammy Wade & Bobbie Leach: Office Managers Home

Inspectors: John Wade, George McNeese James Underwood, Justin Slocum, Dan Phillips and David

Herrell

Property Address:5555 Address Row

Western MI, MI 49546

J.W. Inspection Services of Michigan

John Wade4001 Bedaki NELowell, MI 49331

616 889 0043

Page 2: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

Table of Contents

Cover Page.................................................................1

Table of Contents........................................................2

Intro Page ...................................................................3

1 ROOF SYSTEM, DRAINAGE AND ROOFPENETRATIONS........................................................4

2 EXTERIOR COMPONENTS..................................10

3 GARAGE................................................................15

4 STRUCTURAL COMPONENTS............................18

5 PLUMBING SYSTEM ............................................21

6 HEATING...............................................................23

7 ELECTRICAL SYSTEMS.......................................26

8 KITCHEN AND COMPONENTS............................30

9 BATHROOM AND LAUNDRY ...............................33

10 ROOMS ...............................................................37

11 ATTIC AND ROOF STRUCTURE .......................40

12 FIREPLACES.......................................................43

13 CENTRAL AIR CONDITIONING..........................45

14 BASIC PHOTOS OF THE HOME ........................47

Invoice.......................................................................58

Page 3: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

Date: 9/4/2015 Time: 09:00 AM Report ID: J1009 - 2015Property:5555 Address RowWestern MI, MI 49546

Customer:Tammy Wade & Bobbie Leach:Office ManagersHome Inspectors: John Wade,George McNeeseJames Underwood, Justin Slocum

Real Estate Professional:Real Estate Agent Professional

Comment Key or Definitions

The following definitions of comment descriptions represent this inspection report. All comments by the inspector should beconsidered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a secondopinion or further inspection by a qualified contractor and all costs associated with further inspection fees and repair orreplacement of item, component or unit should be considered before you purchase the property.

Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to befunctioning as intended allowing for normal wear and tear.

Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it wasfunctioning as intended and will state a reason for not inspecting.

Not Present (NP) = This item, component or unit is not in this home or building.

Maintenance Repair or Replace (MR) = The item, component or unit is not functioning as intended or needs repair ormaintenance by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may notneed replacement.

Tradesman Repair or Replace (TR) = The item, component or unit is not functioning as intended or needs furtherinspection by a qualified licensed contractor or qualified specialist. Items, components or units that can be repaired tosatisfactory condition may not need replacement.

Age Of Home:Over 10 Years

Style of Home:Apartment Bld

Home Faces:South

Client Is Present:Yes

Radon Test:Yes

Water Test:No

Weather:Clear

Temperature:Over 65

Rain in last 3 days:No

Page 4: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

1. ROOF SYSTEM, DRAINAGE AND ROOF PENETRATIONS

Styles & Materials

VIEWED ROOF COVERING FROM:LADDERBINOCULARS

ROOF-TYPE:GABLE

VENTILATION:RIDGE VENTSSOFFIT VENTS

SHINGLE LAYERS:1 LAYER

ROOF COVERING:SHINGLES

CHIMNEY:MASONRY

CHIMNEY FLU:TILE

FN R/R NP NI D/

S IP

1.0 ROOF COVERINGS •

1.1 FLASHINGS •

1.2 CHIMNEYS AND ROOF PENETRATIONS •

1.3 ROOF VENTILATION •

1.4 GUTTER DOWNSPOUTS AND DRAINAGE •

1.5 VALLEYS •

1.6 Sky Light •

1.7 Misc. •

FN R/R NP NI D/

S IP

FN= Functional, R/R= Repair or Replace, NP= Not Present, NI= Not Inspected, D/S= Defective - Repair or Replace/Safety Hazard, IP= Improvement

Page 5: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

Comments:

1.0 The photos you see are some of the many different problems we run into when inspection shingles on a home. Aroof is very important to inspect for a home inspector, JW Home Inspection will walk every roof possible, safety mustalways come first. If the home is not accessible then we either look at it from several different areas thru binoculars orwe place our ladder on the eves and look at the roof from several different directions.

1.0 Item 1(Picture) 1.0 Item 2(Picture)

1.0 Item 3(Picture) 1.0 Item 4(Picture)

1.0 Item 5(Picture) 1.0 Item 6(Picture)

Page 6: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

1.1 Unfortunately when shingles are replaced, or when a second layer of shingles installed (we do not recommend asecond layer of shingles) the chimney flashing is not installed properly as you can see in these photos, when we seesomething like these photos we recommend to have a licensed contractor make all necessary repairs.

1.1 Item 1(Picture) 1.1 Item 2(Picture)

1.1 Item 3(Picture)

Page 7: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

1.2 Chimneys has evidence of flaking, spalling, chipping and loose mortar we recommend to have the chimney checkand repaired by a certified chimney sweep.

We recommend that all chimney cap that are cracked be caulked and sealed with a concrete caulk to help preventfuture chimney problems.

1.2 Item 1(Picture) 1.2 Item 2(Picture)

1.2 Item 3(Picture)

Page 8: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

1.3 Roof ventilation is very important is every home, and is checked very carefully with every inspection.

The 1st photo below shows a little bit older home that have been repainted and has mistakenly painted approximately50% if not more of the soffit vents closed, this can cause serious ventilation issues in your attic. Some of the differentproblems this can cause, ice back in the winter, shingles damage because to much heat in the attic, possible mold inyour attic and lack of ventilation can make it very difficult to cool your home in the summer months.

1.3 Item 1(Picture)

1.4 We recommend that gutters are clean twice a year, once in the early spring just after winter and once at the endof fall just before the winter months.

Recommend adding downspout diverters around the entire home, this will help eliminate the chance of water enteringthe basement of your home.

1.4 Item 1(Picture) 1.4 Item 2(Picture)

Page 9: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

1.5 Whenever a roof valley has been heavily caulked it is normally because the valley has been found to leak waterback into the home.

1.5 Item 1(Picture) 1.5 Item 2(Picture)

Page 10: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

2. EXTERIOR COMPONENTS

Styles & Materials

SIDING MATERIAL:VINYL

APPURTENANCE:DECK WITH STEPS

DRIVEWAY:CONCRETE

FN R/R NP NI D/

S IP

2.0 EXTERIOR SIDING& TRIM •

2.1 WINDOWS •

2.2 DOORS (Exterior) •

2.3DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES AND APPLICABLERAILINGS

2.4 DECK FLASHING •

2.5 EXTERIOR FOUNDATION WALLS AND MORTAR JOINTS •

2.6 LANDSCAPE DRAINAGE •

2.7RETAINING WALL(S) CONDITION (With respect to their effect on the condition of thebuilding)

2.8 WALKWAY AND DRIVEWAY •

2.9 TREES& SHRUBS •

2.10 EXTERIOR OUTLETS / GFCI OUTLET •

2.11 EXTERIOR FAUCETS •

2.12 ELECTRICAL SERVICE CABLE •

2.13 ELECTRICAL METER •

2.14 CRAWL SPACE VENTS •

2.15 GAS METER •

2.16 GROUND ROD •

2.17 MISC. •

FN R/R NP NI D/

S IP

FN= Functional, R/R= Repair or Replace, NP= Not Present, NI= Not Inspected, D/S= Defective - Repair or Replace/Safety Hazard, IP= Improvement

Page 11: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

Comments:

2.0 Melted siding found on the second level of the home, we are finding this more and more today, we believe this ishappening because the hot sun is hitting the windows and bouncing off and slightly melting the siding.

2.0 Item 1(Picture)

2.1 The supporting beam above this large window has dropped, the glass in window has been replaced withplexiglass, we recommend to have the entire window be remove and to have a new supporting beam along withabove the window installed.

2.1 Item 1(Picture)

Page 12: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

2.3 Deck are one of the biggest problems we find with homes today and need to be inspected very carefullyfor safety.

The deck boards are under sized, we recommend that the deck boards, are constructed with 2x10-16in on center forthe proper support. We recommend that all supporting beams have lag screws installed to give the proper strength tohold up the deck.

We recommend that the deck railing be properly installed for safety by a licensed contractor.

The deck stairs are very much under built, the blue lines represent where additional support should be added for theproper strength and safety. We recommend that all work is completed by a licensed contractor.

2.3 Item 1(Picture) 2.3 Item 2(Picture)

2.3 Item 3(Picture) 2.3 Item 4(Picture)

Page 13: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

2.6 The grading is flat or sloped back toward the property. We recommend a 10 degree slope away from thefoundation walls, this will help prevent water from entering the basement or crawlspace.

2.6 Item 1(Picture) 2.6 Item 2(Picture)

2.9 We recommend to keep all the trees cut away from the roof and the siding.

2.9 Item 1(Picture)

Page 14: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

The exterior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas ofconcern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this reportshould be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates tothe comments in this inspection report.

2.10 We recommend all exterior outlets are GFCI protected for safety.

2.10 Item 1(Picture)

Page 15: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

3. GARAGE

Styles & Materials

GARAGE DOOR MATERIAL:METAL

GARAGE DOOR TYPE:TWO AUTOMATIC

FN R/R NP NI D/

S IP

3.0GARAGE DOOR OPERATORS (Report whether or not doors will reverse when met withresistance)

3.1 GARAGE DOOR OPENER •

3.2 DOORS (Exterior) •

3.3 CEILINGS •

3.4 WALLS •

3.5 FLOORS •

3.6 WINDOWS (REPRESENTATIVE NUMBER) •

3.7 OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS) •

3.8 FIRE WALL, DOOR, ATTIC ENTRANCE •

3.9 ROOF •

3.10 EXTERIOR •

3.11 HEATING •

3.12 ELECTRICAL •

3.13 MISC. •

FN R/R NP NI D/

S IP

FN= Functional, R/R= Repair or Replace, NP= Not Present, NI= Not Inspected, D/S= Defective - Repair or Replace/Safety Hazard, IP= Improvement

Page 16: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

Comments:

3.0 We recommend that the electronic garage door eyes are properly installed 6" off the ground for safety. Theseelectronic eyes were installed over the top of the garage door opener.

3.0 Item 1(Picture)

3.7 Based on today's standards we recommend to install GFCI outlets in the garage.

3.7 Item 1(Picture)

Page 17: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

3.8 We recommend to install a one hour fire door. ( possible fire hazard )

3.8 Item 1(Picture)

Page 18: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

4. STRUCTURAL COMPONENTS

Styles & Materials

FOUNDATION:POURED CONCRETE

METHOD USED TO OBSERVECRAWLSPACE:NO CRAWLSPACE

FLOOR STRUCTURE:ENGINERED FLOOR TRUSS

COLUMNS OR PIERS:SUPPORTING WALLS

FN R/R NP NI D/

S IP

4.0 FOUNDATION / WALLS AND MORTAR JOINTS •

4.1 COLUMNS OR PIERS •

4.2 FLOORS (Structural) •

4.3 VAPOR BARRIER ON DIRT FLOOR OF CRAWLSPACE •

4.4 INSULATION /RIM BOX •

4.5 BASEMENT WINDOWS •

4.6 REPORT ANY WATER INTRUSION SIGNS OR UNUSUALLY DAMP AREAS •

4.7 SUMP PUMP •

4.8 DESCRIBE ANY INACCESSIBLE AREAS IN CRAWLSPACE OR BASEMENT •

4.9 RAILINGS •

4.10 BASEMENT STAIRS •

4.11 MISC. •

4.12 Misc. •

FN R/R NP NI D/

S IP

FN= Functional, R/R= Repair or Replace, NP= Not Present, NI= Not Inspected, D/S= Defective - Repair or Replace/Safety Hazard, IP= Improvement

Page 19: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

Comments:

4.0 The basement foundation is cracked and has been repaired by a eppoxy injection.

The second photo below indicates where the foundation has bowed outward and steel I beams were installed to stopthe wall from moving further inward.

4.0 Item 1(Picture) 4.0 Item 2(Picture)

4.1 This is the main supporting wall in the center of the basement and has been cut open but has never had theproper supports added to allow such a opening, we recommend to hire a licensed contractor to make all necessaryrepairs.

4.1 Item 1(Picture)

Page 20: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

4.2 We recommend to install floor joist hangers under the basement staircase landing.

4.2 Item 1(Picture)

4.7 We recommend that this sump pump was installed using PVC pipe along with a back flow preventer.

4.7 Item 1(Picture)

Page 21: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

5. PLUMBING SYSTEM

Styles & Materials

WATER SOURCE:PUBLIC

WATER FILTERS:NONE

PLUMBING SUPPLY:COPPER

PLUMBING WATER LINES:COPPER

PLUMBING WASTE:PVC

WATER HEATER POWER SOURCE:GAS

CAPACITY:48 GAL

MANUFACTURER:BRADFORD-WHITE

AGE:9

FN R/R NP NI D/

S IP

5.0 INTERIOR DRAIN, WASTE AND VENT SYSTEMS •

5.1 HOT WATER HEATER •

5.2 WATER HEATER T&P VALVE SHOULD BE PIPED WITHIN 6 INCHES OF THE FLOOR •

5.3 FLU TO WATER HEATER •

5.4 WATER PRESSURE •

5.5 WATER LINES •

5.6 MAIN WATER SUPPLY •

5.7 MISC. •

FN R/R NP NI D/

S IP

FN= Functional, R/R= Repair or Replace, NP= Not Present, NI= Not Inspected, D/S= Defective - Repair or Replace/Safety Hazard, IP= Improvement

Comments:

5.1 Based on today's standards we recommend that all copper gas lines are replaced with black pipe of the new flexline for safety.

5.1 Item 1(Picture)

Page 22: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

5.2 We recommend to install a drip pipe within 6" of the floor, this drip should be made of either black pipe, copper orsafety designed plastic pipe.

5.2 Item 1(Picture) 5.2 Item 2(Picture)

5.3 The water heater flu is disconnected and is allowing carbon monoxide to enter the basement / home. Werecommend that this be repaired by a licensed contractor.

5.3 Item 1(Picture)

Page 23: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

6. HEATING

Styles & Materials

HEAT TYPE:FORCED AIR

ENERGY SOURCE:GAS

NUMBER OF HEAT SYSTEMS(excluding wood):ONE

HEATING BRAND:GOODMAN

DUCTWORK:NON-INSULATED

FILTER TYPE:DISPOSABLE

AGE:10 YR

FN R/R NP NI D/

S IP

6.0 HEATING EQUIPMENT •

6.1 THERMOSTAT •

6.2 ELECTRIC WIRING FEEDING THE FURNACE •

6.3 CHIMNEYS, FLUES AND VENTS (FOR FURNACE) •

6.4 PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM •

6.5 HUMIDIFIER •

6.6 RETURN AIR •

6.7 FILTER •

6.8 MISC. •

FN R/R NP NI D/

S IP

FN= Functional, R/R= Repair or Replace, NP= Not Present, NI= Not Inspected, D/S= Defective - Repair or Replace/Safety Hazard, IP= Improvement

Page 24: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

Comments:

6.0 This line is called a fresh air or make up air line, we do not recommend that these lines are plugged withinsulation, these lines are installed for the furnace to operate properly.

6.0 Item 1(Picture)

6.3 We recommend that all furnace flu's are properly installed with no holes in them allowing carbon monoxide toenter back into the home.

6.3 Item 1(Picture) 6.3 Item 2(Picture)

Page 25: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

6.5 We recommend that all humidifier filters are replaced once a year.

6.5 Item 1(Picture)

6.7 Depending on the type of filter you have in your furnace we recommend that it be changed on a regular basic, if itis a one month filter we recommend that it be changed every month, it you use a three month filter that you shouldchange every three months and the same thing goes for a 6 month and a one year filter. The life of these filters canbe extended depending on how much your heating and cooling is being used and how dirty or clean your air ductsystem may be in your home.

6.7 Item 1(Picture)

Page 26: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

7. ELECTRICAL SYSTEMS

Styles & Materials

ELECTRICAL SERVICE CONDUCTORS:BELOW GROUND

PANEL CAPACITY:200 AMP

PANEL TYPE:CIRCUIT BREAKERS

BRANCH WIRE 15 and 20 AMP:COPPER

WIRING METHODS:ROMEX

GROUNDED TO A WATER PIPE:YES

MAIN SHUTOFF LOCATION:ON THE ELECTRICAL PANEL

FN R/R NP NI D/

S IP

7.0 MAIN ELECTRICAL SERVICE PANEL •

7.1 LIGHT FIXTURES •

7.2 REVERSE POLARITY •

7.3 SMOKE DETECTORS •

7.4 THREE PRONG UN-GROUNDED OUTLETS •

7.5 MISSING FACE PLATES - JUNCTION BOX COVERS •

7.6 LOOSE SPLICED WIRES •

7.7 EXPOSED ROMEX •

7.8 LAUNDRY •

7.9 OUTLETS / SWITCHES •

7.10 MAIN PANEL GROUNDED •

7.11 MISC. •

7.12 Misc. •

FN R/R NP NI D/

S IP

FN= Functional, R/R= Repair or Replace, NP= Not Present, NI= Not Inspected, D/S= Defective - Repair or Replace/Safety Hazard, IP= Improvement

Page 27: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

Comments:

7.0 In this electrical panel it appears that the home owner has had the heating contractor double tap off the mainelectrical supply to feed the new AC unit, this is incorrect and we recommend to have a licensed electrician make allnecessary repairs or possibly replace the main electrical panel.

7.0 Item 1(Picture)

7.3 We recommend that all smoke detectors are replaced every 10 years.

7.3 Item 1(Picture)

Page 28: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

7.4 We recommend that all non grounded two prong outlets have only two prong outlets installed, three pronggrounded outlets should not be installed.

7.4 Item 1(Picture)

7.6 We recommend all loose spliced wires be placed into junction boxes.

7.6 Item 1(Picture)

Page 29: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

7.8 We recommend that all electrical outlets near water should be run in a GFCI outlet (Ground fault circuitinterrupter) for safety. The wire feeding the outlet should also be run in a armored protective cable down the all.

We recommend that all laundry outlets in older homes have a new grounded wire installed to operate the washer anddryer.

7.8 Item 1(Picture) 7.8 Item 2(Picture)

Page 30: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

8. KITCHEN AND COMPONENTS

Styles & Materials

Kitchen Stove Gas or Electric:GAS

FN R/R NP NI D/

S IP

8.0 CEILINGS •

8.1 WALLS •

8.2 FLOORS •

8.3 OUTLETS AND WALL SWITCHES •

8.4 GFCI OUTLETS •

8.5 THE CONDITION OF PLUMBING UNDER THE SINK •

8.6 FAUCET AND SPRAY NOZZLE CONDITION •

8.7 GARBAGE DISPOSAL •

8.8 SHUT OFF VALVE UNDER KITCHEN SINK •

8.9 Misc. •

FN R/R NP NI D/

S IP

FN= Functional, R/R= Repair or Replace, NP= Not Present, NI= Not Inspected, D/S= Defective - Repair or Replace/Safety Hazard, IP= Improvement

Comments:

8.4 Based on today's standards we recommend that all kitchen outlets within 6ft of water have GFCI outlets installedfor safety.

8.4 Item 1(Picture)

Page 31: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

8.6 The kitchen faucet is leaking at the base of the faucet and should be repaired.

8.6 Item 1(Picture)

8.7 We recommend that all exposed electrical wires running from the garbage disposal be run in a armoredprotective cable for safety.

8.7 Item 1(Picture)

Page 32: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

8.8 Based on today's standards we recommend to install shutoff valves under the kitchen sink.

8.8 Item 1(Picture)

Page 33: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

9. BATHROOM AND LAUNDRY

Styles & Materials

DRYER - GAS OR ELECTRIC:GAS

BATHROOM FANS:FAN W/LIGHT

FN R/R NP NI D/

S IP

9.0 CEILINGS •

9.1 WALLS •

9.2 FLOORS •

9.3 DOORS (REPRESENTATIVE NUMBER) •

9.4 GFCI OUTLET IN BATHROOM •

9.5 SINK / PLUMBING UNDER SINK •

9.6 CUT-OFF VALVES UNDER THE SINK AND TOILET •

9.7 SINK FAUCETS, STOP VALVE AND DRAIN •

9.8 TOILET SHOULD BE SECURE AND OPERATIONAL •

9.9 SHOWER/BATH SHOULD DRAIN PROPERLY •

9.10 SHOWER HEAD, TUB FAUCETS AND STOP VALVE •

9.11 EXHAUST FAN •

9.12 SHOWER SURROUND •

9.13 BATHROOM TUB / WHIRLPOOL TUB •

9.14 LAUNDRY TUB& FAUCET •

9.15 DRYER VENTS •

9.16 DRYER GAS LINE OR ELECTRICAL LINE •

9.17 WET BAR / GFCI OUTLETS •

9.18 MISC. •

FN R/R NP NI D/

S IP

FN= Functional, R/R= Repair or Replace, NP= Not Present, NI= Not Inspected, D/S= Defective - Repair or Replace/Safety Hazard, IP= Improvement

Page 34: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

Comments:

9.2 We always recommend to caulk where the floor and shower or tub come together, this is a very common area forwater to get into the wood and begin rotting the floor.

Wood rot found behind the toilet, the toilet is currently leaking water. we recommend to have the floor around thetoilet replaced, this generally happened because the wax ring under the toilet should have been replaced.

9.2 Item 1(Picture) 9.2 Item 2(Picture)

9.4 Based on today's standards we recommend that all bathroom outlets within 6ft of water are protected by a GFCIoutlet (ground fault circuit interrupter).

This GFCI outlet was installed in the bathroom but is not operating, we recommend to have it replaced or repaired bya licensed electrician.

9.4 Item 1(Picture) 9.4 Item 2(Picture)

Page 35: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

9.6 We recommend that all bathroom toilets and sinks have shut off valves installed under them.

9.6 Item 1(Picture) 9.6 Item 2(Picture)

9.9 When trying to drain this tub the toilet was flushed and the tub began backing up, we recommend to call aprofessional plumber to make all necessary repairs.

9.9 Item 1(Picture)

Page 36: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

9.10 The shower head diverter valve is not operating, we recommend to have this valve either cleaned or replaced.

9.10 Item 1(Picture)

9.12 We recommend to re caulk where the floor and the walls come together in the master bathroom shower.

9.12 Item 1(Picture)

Page 37: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

10. ROOMS

Styles & Materials

INTERIOR DOORS:SOLID DOORS

WINDOWS:THERMAL/INSULATED

FN R/R NP NI D/

S IP

10.0 CEILINGS •

10.1 WALLS •

10.2 FLOORS •

10.3 STEPS, STAIRWAYS, BALCONIES AND RAILINGS •

10.4 DOORS (REPRESENTATIVE NUMBER) •

10.5 WINDOWS (REPRESENTATIVE NUMBER) •

10.6 SKYLIGHTS •

10.7 ATTIC FAN •

10.8 MISC. •

FN R/R NP NI D/

S IP

FN= Functional, R/R= Repair or Replace, NP= Not Present, NI= Not Inspected, D/S= Defective - Repair or Replace/Safety Hazard, IP= Improvement

Comments:

10.0 Drywall repairs found around the fireplace chimney area, this is a common area to find water stains in a home.

10.0 Item 1(Picture)

Page 38: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

10.1 Water stains found in the lower level bedroom directly in the corner of the room.

Bubbling paint was found on the wall of the main floor family room, this leak appears to have been caused by iceback in the winter months.

10.1 Item 1(Picture) 10.1 Item 2(Picture)

10.3 Recommend to install railing leading to the second floor of the home.

Recommend to check all the different railings in the home to see if they are secure.

10.3 Item 1(Picture) 10.3 Item 2(Picture)

Page 39: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas ofconcern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructedfrom view. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered beforepurchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.

10.5 All the windows in the home are checked carefully for broken thermal seals, broken thermal seals are verycommon, depending on how badly the seals are broken these can be very difficult at times to determine.

Wood rot found at the base of the basement window. We check every window in every home to determine if thewindows are operating or if they have any wood rot.

10.5 Item 1(Picture) 10.5 Item 2(Picture)

10.5 Item 3(Picture) 10.5 Item 4(Picture)

Page 40: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

11. ATTIC AND ROOF STRUCTURE

Styles & Materials

ATTIC INSULATION:BLOWNCELLULOSE

ROOF STRUCTURE:ENGINERED WOOD TRUSS24" ON CENTER

METHOD USED TO OBSERVE ATTIC:FROM ENTRY

ATTIC INFO:SCUTTLE HOLE

INCHES OF INSULATION:8-10

FN R/R NP NI D/

S IP

11.0 ATTIC ACCESS •

11.1 INSULATION •

11.2 ROOF STRUCTURE •

11.3 VENTILATION •

11.4 SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS ( ATTIC VIEW) •

11.5 VISIBLE ELECTRIC WIRING IN ATTIC •

11.6 SHEATHING •

11.7 RIDGE VENT •

11.8 ROOF VENT •

11.9 GABLE VENT •

11.10 SOFFIT VENT •

11.11 MISC. •

FN R/R NP NI D/

S IP

FN= Functional, R/R= Repair or Replace, NP= Not Present, NI= Not Inspected, D/S= Defective - Repair or Replace/Safety Hazard, IP= Improvement

Page 41: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

Comments:

11.1 Based on today's standards we recommend approximately 14" to 16" of insulation.

11.1 Item 1(Picture)

11.6 When the roof sheathing was installed no roof clips were installed which is allowing the dips in the roof.

11.6 Item 1(Picture)

Page 42: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

11.7 The ridge vent should be cut open approximately 3" to 4" wide to allow the proper ventilation, this ridge vent wasnever cut open.

This ridge vent is plugged with insulation,we recommend to either have the ridge vent cleaned or replaced.

If the ridge vents are not cut open properly or they are not kept clean several different problems can happen in thehome.

11.7 Item 1(Picture) 11.7 Item 2(Picture)

11.11 We recommend that all bathroom fan vents are run to the exterior of the home, in newer homes it is verycommon that all these bathroom vents are run to the exterior, but in older homes it is common to see them just run upinto the attic.

11.11 Item 1(Picture)

Page 43: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

12. FIREPLACES

Styles & Materials

TYPES OF FIREPLACES:CONVENTIONAL / WOOD BURNINGFIREPLACEVENTED GAS LOGS

OPERABLE FIREPLACES:TWO

NUMBER OF WOODSTOVES:NONE

FN R/R NP NI D/

S IP

12.0 DAMPER CONDITION AND FUNCTION •

12.1 FIRE-BRICK WALLS •

12.2 CONDITION OF HEARTH, MANTLE •

12.3 FIREPLACE LINER •

12.4 GAS FIREPLACE •

12.5 MISC. •

FN R/R NP NI D/

S IP

FN= Functional, R/R= Repair or Replace, NP= Not Present, NI= Not Inspected, D/S= Defective - Repair or Replace/Safety Hazard, IP= Improvement

Comments:

12.0 The fireplace damper is no operating we recommend it be repaired or replaced by a certified chimney sweep.

12.0 Item 1(Picture)

Page 44: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

12.3 The fireplace liner is very dirty, we recommend to have a licensed chimney sweep clean the liner and determineif their were any problems with the chimney and liner.

12.3 Item 1(Picture)

12.4 The gas fireplace is putting out a black soot on the back side of the home, we recommend to have a licensedchimney sweep come out and adjust the gas fireplace exhaust.

12.4 Item 1(Picture)

Page 45: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

13. CENTRAL AIR CONDITIONING

Styles & Materials

COOLING EQUIPMENT TYPE:AIR CONDITIONER UNIT

COOLING EQUIPMENT ENERGYSOURCE:ELECTRICITY

NUMBER OF A/C UNITS:ONE

FN R/R NP NI D/

S IP

13.0 AC THERMOSTAT •

13.1 PRESENCE OF INSTALLED COOLING SOURCE IN EACH ROOM •

13.2 CONDENSER •

13.3 MISC. •

FN R/R NP NI D/

S IP

FN= Functional, R/R= Repair or Replace, NP= Not Present, NI= Not Inspected, D/S= Defective - Repair or Replace/Safety Hazard, IP= Improvement

Comments:

13.2 The AC condenser unit on the exterior of the home is very dirty and should be cleaned.

13.2 Item 1(Picture)

Page 46: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

13.3 The AC built around it, and the AC was not operating properly at the time of the inspection, we recommend tohave a licensed heating cooling contractor make all necessary repairs.

13.3 Item 1(Picture)

Page 47: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

14. BASIC PHOTOS OF THE HOME

FN R/R NP NI D/

S IP

14.0 Basic Photos Of The Home •

FN R/R NP NI D/

S IP

FN= Functional, R/R= Repair or Replace, NP= Not Present, NI= Not Inspected, D/S= Defective - Repair or Replace/Safety Hazard, IP= Improvement

Page 48: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

Comments:

Page 49: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

14.0 The photos in this section do not involve problem areas, but are only for the viewing purpose of the newbuyer.

JW Inspection Services of MI has this section for new home buyers to view some of the many different areasof the home after the home inspection and for us to show our customers some of the many different areasthat we have inspected. In every Home Inspection we provide approximately 50 different photos dependingon how large the home is.

14.0 Item 1(Picture) 14.0 Item 2(Picture)

14.0 Item 3(Picture) 14.0 Item 4(Picture)

Page 50: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

14.0 Item 5(Picture) 14.0 Item 6(Picture)

14.0 Item 7(Picture) 14.0 Item 8(Picture)

14.0 Item 9(Picture) 14.0 Item 10(Picture)

Page 51: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

14.0 Item 11(Picture) 14.0 Item 12(Picture)

14.0 Item 13(Picture) 14.0 Item 14(Picture)

14.0 Item 15(Picture) 14.0 Item 16(Picture)

Page 52: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

14.0 Item 17(Picture) 14.0 Item 18(Picture)

14.0 Item 19(Picture) 14.0 Item 20(Picture)

14.0 Item 21(Picture) 14.0 Item 22(Picture)

Page 53: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

14.0 Item 23(Picture) 14.0 Item 24(Picture)

14.0 Item 25(Picture) 14.0 Item 26(Picture)

14.0 Item 27(Picture) 14.0 Item 28(Picture)

Page 54: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

14.0 Item 29(Picture) 14.0 Item 30(Picture)

14.0 Item 31(Picture) 14.0 Item 32(Picture)

14.0 Item 33(Picture) 14.0 Item 34(Picture)

Page 55: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

14.0 Item 35(Picture) 14.0 Item 36(Picture)

14.0 Item 37(Picture) 14.0 Item 38(Picture)

14.0 Item 39(Picture) 14.0 Item 40(Picture)

Page 56: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

14.0 Item 41(Picture) 14.0 Item 42(Picture)

14.0 Item 43(Picture) 14.0 Item 44(Picture)

Page 57: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

14.0 Item 45(Picture) 14.0 Item 46(Picture)

14.0 Item 47(Picture) 14.0 Item 48(Picture)

Page 58: 5555 Address Row / J.W. Inspection Services of Michigan ... · Tammy Wade & Bobbie Leach: Office Managers Home Inspectors: John Wade, George McNeese James Underwood, Justin Slocum,

INVOICE

J.W. Inspection Services of Michigan4001 Bedaki NELowell, MI 49331616 889 0043Inspected By: John Wade

Inspection Date: 9/4/2015Report ID: J1009 - 2015

Customer Info: Inspection Property:

Tammy Wade & Bobbie Leach: Office ManagersHome Inspectors: John Wade, George McNeeseJames Underwood, Justin Slocum

Customer's Real Estate Professional:Real Estate Agent Professional

5555 Address RowWestern MI, MI 49546

Inspection Fee:Service Price Amount Sub-TotalHeated Sq Feet up to 2000sq 285.00 1 285.00Radon Monitor 48 Hr. Test 140.00 1 140.00Termite Inspection 75.00 1 75.00

Tax $0.00Total Price $500.00