SUITE 17, 808 FOREST ROAD, PEAKHURST 2210 P. 02 9046 3800 [email protected] WWW.DAYDESIGN.COM.AU ABN 73 107 291 494 Acoustic Opinion Dincel 110 mm Wall Systems REPORT No 5880-1.1R Rev C DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759
Transcript
Page 1: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

SUITE 17, 808 FOREST ROAD, PEAKHURST 2210 P. 02 9046 3800 [email protected] WWW.DAYDESIGN.COM.AU ABN 73 107 291 494

Acoustic Opinion

Dincel 110 mm Wall Systems

REPORT No 5880-1.1R Rev C

DATE ISSUED 12 February 2018

Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759

Page 2: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 2 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

Revision History

Report Date Prepared Checked Comment

Final 07/04/2016 Stephen Gauld William Wang

Rev A 24/05/2016 Stephen Gauld William Wang

Rev B 30/05/2016 Stephen Gauld William Wang

Rev C draft 23/01/2018 Stephen Gauld William Wang

Rev C draft 2 02/02/2018 Stephen Gauld William Wang Edits made

Rev C 12/02/2018 Stephen Gauld William Wang Edits made

Document R\5880-1.1R REV C, 22 pages plus attachments

Disclaimer

The work presented in this document was carried out in accordance with the Day Design Pty Ltd Quality Management System. Day Design is certified to ISO9001.

Day Design Pty Ltd is a member company of the Association of Australian Acoustical Consultants, and the work herein reported has been performed in accordance with the terms of membership.

Day Design Pty Ltd reserves all copyright of intellectual property in any or all of Day Design’s documents. No permission, license or authority is granted by Day Design to any person or organisation to use any of Day Design’s documents for any purpose without written consent of Day Design.

This report has been prepared for the client identified in Section 1.0 only and cannot be relied or used by any third party. Any representation, statement, opinion or advice, expressed or implied in this report is made in good faith but on the basis that Day Design is not liable (whether by reason of negligence, lack of care or otherwise) to any person for any damage or loss whatsoever which has occurred or may occur in relation to that person taking or not taking (as the case may be) action in any respect of any representation, statement, or advice referred to above.

The information in this document should not be reproduced, presented or reviewed except in full. Prior to passing onto a third party, the Client is to fully inform the third party of the specific brief and limitations associated with the commission.

Page 3: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 3 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

TABLEOFCONTENTS

1.0 CONSULTINGBRIEF......................................................................................................................................................5

2.0 PREDICTIONOFRwANDCtr....................................................................................................................................5

3.0 MATERIALSUSEDFORSOUNDREDUCTION..................................................................................................6

3.1 DincelWallSystems..................................................................................................................................................6

3.2 Plasterboard.................................................................................................................................................................6

3.3 Insulation.......................................................................................................................................................................6

3.4 Studs................................................................................................................................................................................6

3.5 DirectFixingtoDincel..............................................................................................................................................7

4.0 BUILDINGCODEOFAUSTRALIA–ACOUSTICREQUIREMENTS..........................................................8

4.1 F5.5Soundinsulationratingofwalls–Class2and3..................................................................................8

4.2 F5.5Soundinsulationratingofwalls–Class9(c)........................................................................................9

4.3 F5.6Soundinsulationratingofservices...........................................................................................................9

5.0 DINCELWALLSYSTEMS–LABORATORYTESTED...................................................................................10

5.1 DCS110‐1....................................................................................................................................................................10

5.2 DCS110‐2....................................................................................................................................................................10

5.3 DCS110‐3....................................................................................................................................................................11

5.4 DCS110‐4....................................................................................................................................................................11

5.5 DCS110‐5....................................................................................................................................................................12

5.6 DCS110‐6....................................................................................................................................................................12

5.7 DCS110‐7....................................................................................................................................................................13

5.8 DCS110‐8....................................................................................................................................................................13

5.9 DCS110‐9....................................................................................................................................................................14

5.10 DCS110‐10..................................................................................................................................................................14

5.11 DCS110‐11..................................................................................................................................................................15

5.12 DCS110‐12..................................................................................................................................................................15

6.0 110DINCELWALL–RECOMMENDEDWALLSYSTEMS........................................................................16

6.1 Rw+Ctr40‐ServicesWall.......................................................................................................................................16

6.2 Rw+Ctr40‐ServicesWall.......................................................................................................................................16

6.3 Rw45‐Class9(c)Wall............................................................................................................................................16

6.4 RW45–Class9(c)Wall...........................................................................................................................................17

6.5 RW45–Class9(c)Wall‐Discontinuous.........................................................................................................17

6.6 RW50–CorridorWall.............................................................................................................................................18

6.7 Rw50‐CorridorWall..............................................................................................................................................18

6.8 Rw50‐LiftShaftorPlantRoomWall(Discontinuous)............................................................................19

6.9 RW+Ctr‐50–IntertenancyWall........................................................................................................................19

6.10 RW+Ctr‐50–IntertenancyWall........................................................................................................................20

Page 4: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 4 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

6.11 RW+Ctr‐50–IntertenancyWall(Discontinuous)......................................................................................20

6.12 RW+Ctr‐50–IntertenancyWall(Discontinuous)......................................................................................21

6.13 RW+Ctr‐55.................................................................................................................................................................21

7.0 STATEMENTOFEFFECT...........................................................................................................................................22

Page 5: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 5 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

1.0 CONSULTINGBRIEF

DayDesignPtyLtdwasengagedbyDincelConstructionSystemtoprovideAcousticOpinionsontheRwandRw+CtrratingsforarangeofwallsconstructedusingtheirDCS110wallsystem.Theobjectiveistoprovideacousticaldatausefultobuildingdesignersforinclusionintechnicalpublications.

ScopeofWork:

Review the results of systems incorporating the DCS110 wall tested at CSIRO, HighettprovidedbyDincel.

Modelbasicwallsystemsusingacousticmodellingsoftware.

ComparetheRwandRw+Ctrpredictionswithtestresults.

ProvideAcousticOpinionsontheRwandRw+CtrratingsforarangeofDCS110systemstomeettheDeemed‐to‐SatisfyProvisionsintheBCA.

PrepareanAcousticalOpinionReport.

2.0 PREDICTIONOFRWANDCTR

Rw (weightedsoundreduction index)providesanacoustic ratingof thesound insulationofwallsandpartitionsduetoairbornesoundofthehumanvoice.Soundinsulationvarieswithfrequency and is dependent on the type of wall construction, however, the Rw provides aconvenientmethodofratingsoundinsulationusingasinglenumber.ThehighertheRwratingthebetterthesoundinsulationprovidedbythepartition.

Ctr is a correction factor to account for the sound insulation performance in the lowerfrequencies.TheCtrfactorisaddedtotheRwratingtogetanoverallRw+Ctrairbornerating.Formasonrywalls,theCtrfactoristypicallybetween–5and–3whileforplasterboardwallsthefactormayoftenbeaslowas–12,dependingontheconstructiontype.

TheAcousticOpinionsexpressedinthisreportarebasedfirstlyoncalculationsmadeusingtheMarshall Day Acoustics Acousti‐Max software and secondly by comparison with SoundTransmission Loss tests for similar plasterboard constructions. Acoustic opinions are thenprovided in the light of our general acoustic experience. Factors taken into account in ourcalculations include: the surface mass of the plasterboard, Young’s Modulus, the criticalfrequencyandspeedofsoundinplasterboard,theeffectofaircavitiesandacousticinsulationbetweenstuds.

WeareoftheopinionthatusingtheAcousti‐Maxsoftwareandmakingcorrectionsbasedoncomparisonwithtestresultsthatourpredictionaccuracyisintheorderof±2dB.

Becauseofthecomplexityofsuchcalculations,approvedlaboratorytestresults(inaccordancewithAustralianStandardAS1191:2002andAS/NZS1276.1:1999)arealwayspreferred.

Page 6: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 6 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

3.0 MATERIALSUSEDFORSOUNDREDUCTION

3.1 DincelWallSystems

TheDincelwallsystemsinthisreporthavespecificationsasdetailedinTable1below:

Table1 DincelWall

ProductName Thickness(mm) FinishedBulkDensity(kg/m3)

DCS110 110mm 2,350

3.2 Plasterboard

IncompilingthisscheduleofacousticratingsforvariousplasterboardconstructionsDincelhasworkedcloselywithKnaufPlasterboard.ThedensityoftheplasterboardprovidedbyKnaufandusedinthisreportisshowninTable2below.

Table2 KnaufPlasterboardDensities

ProductName Thickness(mm) BulkDensity(kg/m3)

MastaShield*10 640

13 623

FireShield* 16 766*Similarorhigherdensityplasterboardmayalsobeused.

3.3 Insulation

Acousticinsulationspecifiedhavebulkdensitiesasfollows:

Table3 Knauf’sInsulationDensities

ProductName Thickness(mm)ApproxBulkDensity

(kg/m3)

Glasswool 25 24

Earthwool 50 11

Thickerorhigherdensityofthesamebulkinsulationmaybesubstitutedforwallsystemsinthisreport.

3.4 Studs

Allsystemswithaseparatesteelstudleafincludeanoptionfor51mmor64mmsteelstuds.

Page 7: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 7 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

3.5 DirectFixingtoDincel

PlasterboardcanbedirectfixedtoDinceleitherbyscrewingoracombinationofgluingandscrewing.ThefollowingdiagramindicateshowconventionalscrewingcanbeusedwithDincelwall.

Page 8: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 8 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

4.0 BUILDINGCODEOFAUSTRALIA–ACOUSTICREQUIREMENTS

TheinformationinthissectionisextractedfromtheBuildingCodeofAustralia(BCA),whichisnow part of the National Construction Code (NCC), Part F5 “Sound Transmission andInsulation”.TheacousticrequirementsandthebuildingsolutionsinthisreportarebasedontheDeemed‐to‐SatisfyProvisionsoftheBCA.

TheObjectiveofthisPartistosafeguardoccupantsfromillnessorlossofamenityasaresultofunduesoundbeingtransmitted‐

(a) betweenadjoiningsole‐occupancyunits;and

(b) fromcommonspacestosole‐occupancyunits;and

(c) frompartsofdifferentclassificationstosole‐occupancyunits.

TheObjectiveonlyappliestoaClass2or3buildingoraClass9cagedcarebuilding.

4.1 F5.5 Soundinsulationratingofwalls–Class2and3

AwallinaClass2or3buildingmust‐

(i) haveanRw+Ctr(airborne)notlessthan50,ifitseparatessole‐occupancyunits;and

(ii) haveanRw(airborne)not less than50, if itseparatessole‐occupancyunit fromaplantroom,liftshaft,stairway,publiccorridor,publiclobbyorthelike,orpartsofadifferentclassification;and

(iii) beofdiscontinuousconstructionifitseparates‐

(A) abathroom,sanitarycompartment, laundryorkitcheninonesole‐occupancyunitfromahabitableroom(otherthanakitchen)inanadjoiningunit;or

(B) asole‐occupancyunitfromaplantroomorliftshaft.

Discontinuousconstructionmeansawallhavingaminimum20mmcavitybetween2separateleaves,and

(i) formasonry, where wall ties are required to connect leaves, the ties are of theresilienttype;and

(ii) forotherthanmasonry,thereisnomechanicallinkagebetweenleavesexceptattheperiphery.

AdoormaybeincorporatedinawallinaClass2buildingthatseparatesasole‐occupancyunitfromastairway,publiccorridor,publiclobbyorthelike,providedthedoorassemblyhasanRwnotless30.

Page 9: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 9 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

Whereawallrequiredtohavesoundinsulationhasafloorabove,thewallmustcontinueto‐

(i) theundersideofthefloorabove;or

(ii) aceilingthatprovidesthesoundinsulationrequiredforthewall.

Whereawallrequiredtohavesoundinsulationhasaroofabove,thewallmustcontinueto‐

(i) theundersideoftheroofabove;or

(ii) aceilingthatprovidesthesoundinsulationrequiredforthewall.

4.2 F5.5 Soundinsulationratingofwalls–Class9(c)

(c) AwallinaClass9cagedcarebuildingmusthaveanRwnotlessthan45ifitseparates‐

(i) sole‐occupancyunits;or

(ii) Asole‐occupancyunitfromakitchen,bathroom,sanitarycompartment(notbeinganassociatedensuite),laundry,plantroomorutilitiesroom.

(d) Inadditionto(c),awallseparatingasole‐occupancyunitinaClass9cagedcarebuildingfromakitchenorlaundry,plantmustcomplywithF5.3(b).

(e) Whereawallrequiredtohavesoundinsulationhasafloorabove,thewallmustcontinueto‐

(i) theundersideofthefloorabove;or

(ii) aceilingthatprovidesthesoundinsulationrequiredforthewall.

(f) Whereawallrequiredtohavesoundinsulationhasaroofabove,thewallmustcontinueto‐

(i) theundersideoftheroofabove;or

(ii) aceilingthatprovidesthesoundinsulationrequiredforthewall.

4.3 F5.6 Soundinsulationratingofservices

(a) Ifaduct,soil,wasteorwatersupplypipe,includingaductorpipethatislocatedinawallor floorcavity,servesorpassesthroughmorethanonesole‐occupancyunit, theductorpipemustbeseparatedfromtheroomsofanysole‐occupancyunitbyconstructionwithanRw+Ctr(airborne)notlessthan‐

(i) 40iftheadjacentroomisahabitableroom(otherthanakitchen);or

(ii) 25iftheadjacentroomisakitchenornon‐habitableroom.

(b) If a storm water pipe passes through a sole‐occupancy unit it must be separated inaccordancewith(a)(i)and(ii).

Page 10: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 10 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

5.0 DINCELWALLSYSTEMS–LABORATORYTESTED

SeveralsystemsincorporatingtheDincelConstructionSystem110mmwallhavebeentestedattheCSIROacousticlaboratoryinHighett,VIC.

5.1 DCS110‐1

LaboratoryTestedSystem110mmDincelWall

WallWidth(mm) LaboratoryTestedRw(Rw+Ctr)

110 48(43)

5.2 DCS110‐2

LaboratoryTestedSystem10mmKnaufMastaShieldplasterboard,screwfixed110mmDincelWall28mmfurringchannel@600mmcentres,41mmcavity50mmKnaufEarthwoolinsulationinthecavity16mmKnaufFireShieldplasterboard,screwfixedtofurringchannel

WallWidth(mm) LaboratoryTestedRw(Rw+Ctr)

177 54(48)

Page 11: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 11 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

5.3 DCS110‐3

LaboratoryTestedSystem10mmKnaufMastaShieldplasterboard,screwfixed110mmDincelWall28mmfurringchannel@600mmcentres,58mmcavity50mmKnaufEarthwoolinsulationinthecavity16mmKnaufFireShieldplasterboard,screwfixedtofurringchannel

WallWidth(mm) LaboratoryTestedRw(Rw+Ctr)

194 57(51)

5.4 DCS110‐4

LaboratoryTestedSystem10mmKnaufMastaShieldplasterboard,screwandgluefixed110mmDincelWall28mmfurringchannel@600mmcentres,58mmcavity50mmKnaufEarthwoolinsulationinthecavity16mmKnaufFireShieldplasterboard,screwfixedtofurringchannel

WallWidth(mm)LaboratoryTested

Rw(Rw+Ctr)

196 57(51)

Page 12: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 12 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

5.5 DCS110‐5

LaboratoryTestedSystem16mmKnaufFireShieldplasterboard,screwfixedtofurringchannel28mmfurringchannel@600mmcentres,overall51mmcavity50mmKnaufEarthwoolinsulationinthecavity110mmDincelWall28mmfurringchannel@600mmcentres,overall58mmcavity50mmKnaufEarthwoolinsulationinthecavity16mmKnaufFireShieldplasterboard,screwfixedtofurringchannel

WallWidth(mm) LaboratoryTestedRw(Rw+Ctr)

251 64(52)

5.6 DCS110‐6

LaboratoryTestedSystem16mmKnaufFireShieldplasterboard,screwfixedtofurringchannel28mmfurringchannel@600mmcentres,51mmcavity50mmKnaufEarthwoolinsulationinthecavity110mmDincelWall20mmairgap51mmbacktobacksteelstuds@600mmcentres,overall71mmcavity50mmKnaufEarthwoolinsulationinthecavity16mmKnaufFireShieldplasterboard,screwfixedtostuds

WallWidth(mm) LaboratoryTestedRw(Rw+Ctr)

264 65(54)

Page 13: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 13 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

5.7 DCS110‐7

LaboratoryTestedSystem10mmKnaufMastaShieldplasterboard,screwfixedtofurringchannel28mmfurringchannel@600mmcentres,30mmcavity25mmglasswoolinsulationinthecavity110mmDincelWall20mmairgap51mmbacktobacksteelstuds@600mmcentres,overall71mmcavity50mmKnaufEarthwoolinsulationinthecavity16mmKnaufFireShieldplasterboard,screwfixedtostuds

WallWidth(mm) LaboratoryTestedRw(Rw+Ctr)

237 64(53)

5.8 DCS110‐8

LaboratoryTestedSystem10mmKnaufMastaShieldplasterboard,glueandscrewfixed110mmDincelWall20mmairgap51mmbacktobacksteelstuds@600mmcentres,overall71mmcavity50mmKnaufEarthwoolinsulationinthecavity16mmKnaufFireShieldplasterboard,screwfixedtostuds

WallWidth(mm) LaboratoryTestedRw(Rw+Ctr)

209 56(51)

Page 14: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 14 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

5.9 DCS110‐9

LaboratoryTestedSystem110mmDincelWall20mmairgap51mmbacktobacksteelstuds@600mmcentres,overall71mmcavity10mmKnaufMastaShieldplasterboard,screwfixedtostuds

WallWidth(mm) LaboratoryTestedRw(Rw+Ctr)

191 51(43)

5.10 DCS110‐10

LaboratoryTestedSystem110mmDincelWall28mmfurringchannel@600mmcentres,30mmcavity25mmglasswoolinsulationinthecavity10mmKnaufMastaShieldplasterboard,screwfixedtofurringchannel

WallWidth(mm) LaboratoryTestedRw(Rw+Ctr)

150 55(44)

Page 15: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 15 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

5.11 DCS110‐11

LaboratoryTestedSystem110mmDincelWall28mmfurringchannel@600mmcentres,30mmcavityNoinsulation10mmKnaufMastaShieldplasterboard,screwfixedtofurringchannel

WallWidth(mm) LaboratoryTestedRw(Rw+Ctr)

150 48(41)

5.12 DCS110‐12

LaboratoryTestedSystem10mmKnaufMastaShieldplasterboard,directfixed110mmDincelWall28mmfurringchannel@600mmcentres,30mmcavityNoinsulation16mmKnaufFireShieldplasterboard,screwfixedtofurringchannel

WallWidth(mm)LaboratoryTested

Rw(Rw+Ctr)

166 46(41)

Page 16: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 16 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

6.0 110DINCELWALL–RECOMMENDEDWALLSYSTEMS

The acoustic opinions below are based on the comparable tests, Marshall Day AcousticsAcousti‐Maxsoftwareaswellasourownexperience.

Aonepagesummarysheethasbeenattachedtothisreport.

6.1 Rw+Ctr40‐ServicesWall

LaboratoryTestedSystem110mmDincelWall

WallWidth(mm) LaboratoryTestedRw(Rw+Ctr)

110 48(43)

6.2 Rw+Ctr40‐ServicesWall

NoservicesonthewallAcousticOpinion10mmKnaufMastaShieldplasterboard,directfix110mmDincelWall

WallWidth(mm) Rw(Rw+Ctr)

120 45(41)

6.3 Rw45‐Class9(c)Wall

NoservicesonthewallAcousticOpinion10mmKnaufMastaShieldplasterboard,directfix110mmDincelWall10mmKnaufMastaShieldplasterboard,directfix

WallWidth(mm) Rw(Rw+Ctr)

130 45(41)

Page 17: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 17 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

6.4 RW45–Class9(c)Wall

ElectricalservicesononesideAcousticOpinion13mmKnaufMastaShieldplasterboard,directfix110mmDincelWall28mmfurringchannel@600mmcentres,30mmcavityNoinsulation13mmKnaufMastaShieldplasterboard,screwfixedtofurringchannel

WallWidth(mm) Rw(Rw+Ctr)

166 45(42)

6.5 RW45–Class9(c)Wall‐Discontinuous

ServicesonbothsidesAcousticOpinion10mmKnaufMastaShieldplasterboard,screwfixed28mmfurringchannel@600mmcentres,30mmcavityNoinsulation110mmDincelWall20mmairgap51/64mmsteelstuds@600mmcentres,overall71/84mmcavityNoinsulation10mmKnaufMastaShieldplasterboard,screwfixedtostuds

WallWidth(mm) Rw(Rw+Ctr)

231with51mmsteelstuds 47(41)

244with64mmsteelstuds 49(42)

Page 18: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 18 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

6.6 RW50–CorridorWall

ElectricalservicesononesideAcousticOpinion10mmKnaufMastaShieldplasterboard,directfix110mmDincelWall28mmfurringchannel@600mmcentres,30mmcavity25mmglasswoolinsulationincavity10mmKnaufMastaShieldplasterboard,screwfixedtofurringchannel

WallWidth(mm) Rw(Rw+Ctr)

160 53(46)

6.7 Rw50‐CorridorWall

ElectricalservicesonbothsidesAcousticOpinion10mmKnaufMastaShieldplasterboardscrewfixedtofurringchannel25mmglasswoolinsulationincavity28mmfurringchannel@600mmcentres,30mmcavity110mmDincelwall28mmfurringchannel@600mmcentres,30mmcavity25mmglasswoolinsulationincavity10mmKnaufMastaShieldplasterboardscrewfixedtofurringchannel

WallWidth(mm) Rw(Rw+Ctr)

190 54(39)

Page 19: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 19 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

6.8 Rw50‐LiftShaftorPlantRoomWall(Discontinuous)

DiscontinuouswallServicesononesideAcousticOpinion110mmDincelWall20mmairgap51/64mmsteelstuds@600mmcentres,overall71/84mmcavity10mmKnaufMastaShieldplasterboardfixedtostuds

WallWidth(mm) Rw(Rw+Ctr)

191with51mmsteelstuds 51(43)

204with64mmsteelstuds 52(44)

6.9 RW+Ctr‐50–IntertenancyWall

ElectricalservicesononesideAcousticOpinion13mmKnaufMastaShieldplasterboard,directfix110mmDincelWall28mmfurringchannel@600mmcentres,50mmcavity50mmKnaufEarthwoolinsulationincavity16mmKnaufFireShieldplasterboard,screwfixedtofurringchannel

WallWidth(mm) Rw(Rw+Ctr)

189 55(50)

Page 20: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 20 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

6.10 RW+Ctr‐50–IntertenancyWall

ElectricalservicesonbothsidesAcousticOpinion16mmKnaufFireShieldplasterboardscrewfixedtofurringchannel25mmglasswoolinsulationincavity28mmfurringchannel@600mmcentres,45mmcavity110mmDincelwall28mmfurringchannel@600mmcentres,45mmcavity25mmglasswoolinsulationincavity16mmKnaufFireShieldplasterboardscrewfixedtofurringchannel

WallWidth(mm) Rw(Rw+Ctr)

232 63(50)

6.11 RW+Ctr‐50–IntertenancyWall(Discontinuous)

DiscontinuouswallServicesononesideAcousticOpinion10mmKnaufMastaShieldplasterboard,directfix110mmDincelWall20mmairgap51/64mmsteelstuds@600mmcentres,overall71/84mmcavity50mmKnaufEarthwoolinsulationincavity13mmKnaufFireShieldplasterboard,screwfixedtostuds

WallWidth(mm) Rw(Rw+Ctr)

204with51mmsteelstuds 57(50)

217with64mmsteelstuds 57(51)

Page 21: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 21 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

6.12 RW+Ctr‐50–IntertenancyWall(Discontinuous)

DiscontinuouswallServicesonbothsidesAcousticOpinion13mmKnaufFireShieldplasterboard,screwfixedtofurringchannel28mmfurringchannel@600mmcentres,30mmcavity25mmglasswoolinsulationinthecavity110mmDincelWall20mmairgap51/64mmsteelstuds@600mmcentres,overall71/84mmcavity50mmKnaufEarthwoolinsulationinthecavity13mmKnaufFireShieldplasterboard,screwfixedtostuds

WallWidth(mm) Rw(Rw+Ctr)

237with51mmsteelstuds 62(50)

250with64mmsteelstuds 63(52)

6.13 RW+Ctr‐55

SuperioracousticperformanceDiscontinuouswallServicesonbothsidesAcousticOpinion16mmKnaufFireShieldplasterboard,screwfixedtofurringchannel28mmfurringchannel@600mmcentres,30mmcavity25mmglasswoolinsulationinthecavity110mmDincelWall20mmairgap51/64mmsteelstuds@600mmcentres,overall71/84mmcavity50mmKnaufEarthwoolinsulationincavity2layers16mmKnaufFireShieldscrewfixedtostud

WallWidth(mm) Rw(Rw+Ctr)

259with51mmsteelstuds 66(55)

272with64mmsteelstuds 67(57)

Page 22: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Dincel Construction Systems Page 22 of 22

Acoustic Opinion

Ref: 5880-1.1R REV C 12-Feb-18

7.0 STATEMENTOFEFFECT

Weareconfidentthatprovidedthewallsarebuiltofthematerialsspecifiedinaworkmanlikemannerinaccordancewiththemanufacturer’sinstructions(takingduecaretosealalljointsanduseconstructionsthatwillavoidflankingtransmissionproblems),theywillprovidethesoundinsulationratingslistedintheAcousticOpinionssectionofthisreport.

StephenGauld,BE(Mech),MEngSc(NoiseandVibration),MIEAust,MAAS

PrincipalAcousticalEngineer

forandonbehalfofDayDesignPtyLtd

Attachments:

SummaryofDCS110DincelWallSystems

TheundersignedherebycertifiesthatthisReporthasbeencheckedand

approvedinaccordancewithourQualityManagementSystem.

Date:12/2/18

Page 23: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Acoustic System Summary – 110mm Dincel Wall

REPORT REF: 5880-1 REV C

DAY DESIGN PTY LTD 2-FEB-18

System Nᴼ

Rw/Rw+Ctr

WALL LINING SIDE 1

110mm DINCEL WALL CONCRETE DENSITY

2,350 kg/m3

WALL LINING SIDE 2

110-6.1

48 / 43 Nil, painted or rendered

Wall width: 110mm

Nil, painted or rendered

110-6.2

45 / 41

10mm Knauf MastaShield plasterboard, direct fix

Wall width: 120mm

Nil, painted or rendered

110-6.3

45 / 41

10mm Knauf MastaShield plasterboard, direct fix

Wall width: 130mm

10mm Knauf MastaShield plasterboard, direct fix

110-6.4

45 / 42

13mm Knauf MastaShield plasterboard, direct fix

Wall width: 166mm

13mm Knauf MastaShield plasterboard,

screw fixed to 28mm furring channel (30mm cavity)

110-6.5

47 / 41 1

49 / 42 2

10mm Knauf MastaShield plasterboard,

screw fixed to 28mm furring channel (30mm cavity)

Wall width: 231mm 1 244mm 2

10mm Knauf MastaShield plasterboard,

screw fixed to studs at 600mm cts

20mm air gap (711/842mm cavity)

110-6.6

53 / 46

10mm Knauf MastaShield plasterboard,

direct fix

Wall width: 160mm

10mm Knauf MastaShield plasterboard,

screw fixed to 28mm furring channel (30mm cavity)

25mm glasswool insulation in cavity

110-6.7

54 / 39

10mm Knauf MastaShield plasterboard,

screw fixed to 28mm furring channel at 600mm cts

(30mm cavity) 25mm glasswool in cavity

Wall width: 190mm

10mm Knauf MastaShield plasterboard,

screw fixed to 28mm furring channel at 600mm cts

(30mm cavity) 25mm glasswool in cavity

110-6.8

51 / 43 1 52 / 44 2

Nil, painted or rendered

Wall width: 191mm 1 204mm 2

10mm Knauf MastaShield plasterboard,

fixed to studs at 600mm cts 20mm air gap

(711/842mm cavity)

110-6.9

55 / 50

13mm Knauf MastaShield plasterboard, direct fix

Wall width: 189mm

16mm Knauf FireShield plasterboard,

screw fixed to 28mm furring channel (50mm cavity)

50mm Knauf Earthwool in cavity

110-6.10

63 / 50

16mm Knauf FireShield plasterboard,

screw fixed to 28mm furring channel at 600mm cts

(45mm cavity) 25mm glasswool in cavity

Wall width: 232mm

16mm Knauf FireShield plasterboard,

screw fixed to 28mm furring channel at 600mm cts

(45mm cavity) 25mm glasswool in cavity

Page 24: 5880-1.1R Rev C€¦ · DATE ISSUED 12 February 2018 Prepared For: Dincel Construction Systems 101 Quarry Road Erskine Park NSW 2759 . Dincel Construction Systems Page 2 of 22 Acoustic

Acoustic System Summary – 110mm Dincel Wall

REPORT REF: 5880-1 REV C

DAY DESIGN PTY LTD 2-FEB-18

System Nᴼ

Rw/Rw+Ctr

WALL LINING SIDE 1

110mm DINCEL WALL CONCRETE DENSITY

2,350 kg/m3

WALL LINING SIDE 2

110-6.11

57 / 50 1 57 / 51 2

10mm Knauf MastaShield plasterboard, direct fix

Wall width: 204mm 1 217mm 2

13mm Knauf FireShield plasterboard,

screw fixed to studs at 600mm cts

20mm air gap (711/842mm cavity)

50mm Knauf Earthwool in cavity

10-6.12

62 / 50 1 63 / 52 2

13mm Knauf FireShield plasterboard,

screw fixed to 28mm furring channel (30mm cavity)

25mm glasswool insulation in cavity

Wall width: 237mm 1 250mm 2

13mm Knauf FireShield plasterboard,

screw fixed to studs at 600mm cts

20mm air gap (711/842mm cavity)

50mm Knauf Earthwool in cavity

10-6.13

66 / 55 1 67 / 57 2

16mm Knauf FireShield plasterboard,

screw fixed to furring channel 28mm furring channel at 600mm

cts (30mm cavity) 25mm glasswool insulation in

cavity

Wall width: 259mm 1 272mm 2

2 layers 16mm Knauf FireShield plasterboard,

screw fixed to studs at 600mm cts

20mm air gap (711/842mm cavity)

50mm Knauf Earthwool in cavity 1 51 mm steel studs 2 64 steel studs

The acoustic ratings provided are opinions based on test data of comparable laboratory tests and

acoustic modelling carried out by Day Design Pty Ltd.


Recommended