+ All Categories
Home > Documents > 5_Chiller Plant Control

5_Chiller Plant Control

Date post: 20-Oct-2015
Category:
Upload: gerardo-zamorano
View: 39 times
Download: 2 times
Share this document with a friend
Popular Tags:
55
1 Chiller Plant Control
Transcript
  • 1Chiller Plant Control

  • Introduction to Trane Control Systems2 2010 Trane

    What Do Customers Really Care About ?

    Operator safety Reliable chilled water flow Environmental awareness Operating cost (energy efficiency) Maintenance cost

  • Introduction to Trane Control Systems3 2010 Trane

    What We Will Cover

    Chiller plant control strategies Tracer control features Reliability and serviceability Chiller plant optimization Factory-integrated controls on chillers Additional discussion

  • Introduction to Trane Control Systems4 2010 Trane

    Tracer Chiller Plant Control Repeatability performance from plant to plant

    Maximize the use of pre-engineered features Minimize on-site customization

    Flexibility supports a variety of: Plant layouts Chiller types Control strategies

    Maximized energy savings Load matching Chiller tower optimization Distributed pump pressure optimization Thermal ice storage Minimize manual intervention

    Minimized operational costs Minimize manual intervention, but anticipate it Maintain chilled water flow and temperature Minimize service surprises

  • Introduction to Trane Control Systems5 2010 Trane

    LoadDetermination

    Chiller Plant Control

    ChillerSequencing

    Chiller Plant Control

    UserInterface

    SystemOptimization

  • Introduction to Trane Control Systems6 2010 Trane

    Chiller Plant Layout

    Variable Primary Flow Using Control System with

    adaptive control Chillers Chillers w/ feed-forward controls &

    flow compensation

    Decoupler System

    Air Handling Units

    Control Valves

    Variable-Speed

    Drive

    Pressure Differential Controller or Transmitter

    Production

    DistributionBypass Line

    SU PPL YD E

    MAN D

    UCP2UCP2

    UCP2UCP2

    Air Handling Units

    Control Valves

    Production

    DistributionBypass Line

    SUPPLY

    DEM

    AND

    Variable-Speed Drive

    Flow

    Meter

    UCP2UCP2

    UCP2UCP2

    Differential Pressure Sensor or

    Transmitter

  • Introduction to Trane Control Systems7 2010 Trane

    Pre-engineered Features

    Load determination Capacity matching Rotation Chiller setpoint control Failure recovery User interface

    Installation and operating reliability and efficiency

  • Introduction to Trane Control Systems8 2010 Trane

    Load Determination (when to add or subtract a chiller)

    What is the optimal sequencing for chillers? Should I run one chiller at 100% or two chillers at 50%?

    The givens whether you run one chiller or two

    The building load does not change The outside wet bulb temperature does not change

    When you run two chillers You may double the number of pumps You may double the number of tower cells

  • Introduction to Trane Control Systems9 2010 Trane

    0.40.50.60.70.80.9

    11.11.21.31.4

    0 20 40 60 80 100Percent Load

    k

    W

    /

    t

    o

    n

    One Chiller at 100%? orTwo Chillers at 50%?

    Constant Speed Centrifugal ChillerUnloading at constant condenser water temperature

  • Introduction to Trane Control Systems10 2010 Trane

    Capacity Matching(turn the right chiller on)

    Dependent on chiller plant design

    Normal - identical chillers Base - heat recovery/super efficient Peak - back up/alternate energy source/inefficient Swing - match the load! Custom - mix and match/nested CPC objects

    Reduce operating costs

  • Introduction to Trane Control Systems11 2010 Trane

    UCP2

    450 Ton Chiller (Swing) 900 Ton Chiller

    (Normal-1)

    900 Ton Chiller (Normal-2)

    UCP2UCP2

    0 2250450 18001350900

    UCP2

    Building Load (Tons)Reduce operating costs

  • Introduction to Trane Control Systems12 2010 Trane

    Flexible Rotation Which chiller is next?

    Schedule based Run-time Manual operator decision Customized

    Number of starts Other?

    Reliable chilled water

  • Introduction to Trane Control Systems13 2010 Trane

    Unload Before StartKeep chillers online

    Ride out flow transients on startups Deals with less sophisticated chiller controllers

    Variable flow / multiple pump systems Low supply water temperatures

    Reliable chilled water

  • Introduction to Trane Control Systems14 2010 Trane

    Failure Recovery Keep chilled water flowing

    No manual intervention required Follow the standard sequence Multiple failure inputs

    Chiller level System level

    Reliable chilled water

  • Introduction to Trane Control Systems15 2010 Trane

    Intuitive User Interface

    Minimize training time Minimize undesirable manual control Maximize operator efficiency

    Reduced Operational Costs

  • Introduction to Trane Control Systems16 2010 Trane

    Reduced Operational Costs

    Chiller Plant Status Screen - Tracer Summit

    Easy to OperateEasy to Operate

  • Introduction to Trane Control Systems17 2010 Trane

    Alarm ManagementChiller Operating Parameters & Diagnostic Messages

    Direct high level link to chiller panel Workstation displays and logs all chillers

    Operating parameters Diagnostic messages

    Useful for chiller diagnosis and preventive maintenance

  • Introduction to Trane Control Systems18 2010 Trane

    Alarm ManagementChiller Operating Parameters & Diagnostic MessagesAlarm ManagementChiller Operating Parameters & Diagnostic Messages

  • Introduction to Trane Control Systems19 2010 Trane

    Diagnostics and Reports

    Standard status reports Diagnostic reporting and message routing

    Series R Rotary Liquid Chillers - Air Cooled Standard Report

    Current Value

    Chiller Name Chiller East Wing #1 Present Value Occupied Communication State Up Operating Mode Run: Normal

    Chilled Water Leaving Temp - deg F 47.30 Chilled Water Entering Temp - deg F 57.70 Chilled Water Setpoint - deg F 41.00

    Air Cooled Condenser Data Ckt 1 Sat Refrig Temp - deg F 74.00 Ckt 2 Sat Refrig Temp - deg F 74.30

    Current Draw - % RLA 47 Current Limit Setpoint - % RLA 0

    Compressor(s) Running? Yes

    Ice Making? No Outdoor Air Temperature - deg F 82.20

    RTA/RTW 70-125 Ton Unit: Compressor A Run Time - hrs 4271 Compressor A Starts 19 Compressor B Run Time - hrs 111 Compressor B Starts 18

    RTA 240 to 400 Ton Unit (Add'l): Compressor C Run Time - hrs 0 Compressor C Starts 0

    RTA 300 to 400 Ton Unit (Additional): Compressor D Run Time - hrs 0 Compressor D Starts 0

    Chiller Plant Control Standard Report

    Current Value

    Chiller Plant Name Building Plant #1

    System Mode Normal

    System Data: Supply Water Setpoint 38.00 Supply Water Temp 47.30 Return Water Temp 57.70

    Chilled Water Pump On Chilled Water Flow Flow Bypass Pipe Flow Not Used

    System Operation: Failure Exists No Number of Chillers Enabled 1 Active Operation Confirming Chiller Off

    Add Information: Next Chiller to Add 2 Add Delay Timer 6 Add Request Yes Add Temperature 39.50

    Subtract Information: Subtract Method Temperature Subtract Delay Timer 20 Chilled Water Delta Temp 10.40 Subtract Delta Temperature 9.50 Subtract Flow Threshold 0.00 Excess Flow Percentage 20.00

    Rotation Information: Rotation Type Day of Week Next Rotation Date & Time 03/21/04 00:01:00

    Chiller 1: Chiller Control On Chiller Status On Chilled Water Setpoint 40.00 Leaving Chilled Water Temp 47.30 Chilled Water Pump On Chilled Water Flow Flow Current Limit Setpoint 120.00 Chiller Failure None Sequence Number Base Chiller Available Yes

    Reduced Maintenance Cost

  • Introduction to Trane Control Systems20 2010 Trane

    Chiller Plant Dashboard Details

    Daily Average MetricsPump Pressure

    Pump StatusSystem and

    Chiller Status

    Chilled Water Temps

    Tower Water TempsSystem

    Load

    System Efficiency

    Pump Flow

  • Introduction to Trane Control Systems21 2010 Trane

    Chiller - Tower Optimization Tower Setpoint Optimization

    Load Condenser water

    temperature Wet bulb Tower design

    Load Condenser water

    temperature Chiller design

  • Introduction to Trane Control Systems22 2010 Trane

    Chiller - Tower Optimization ChillerTower Interaction

    Condenser Water Temperature, C

    400

    25

    E

    n

    e

    r

    g

    y

    C

    o

    n

    s

    u

    m

    p

    t

    i

    o

    n

    ,

    k

    W

    26 27 28 2924

    300

    200

    100

    030

    Tower

    Optimalcontrol point

    Chiller

    Total

  • Introduction to Trane Control Systems23 2010 Trane

    Cooling Tower OptimizationResults

    Minimumtemperature

    Design CW WB + 5degrees

    Optimized$47,500.00

    $48,000.00

    $48,500.00

    $49,000.00

    $49,500.00

    $50,000.00

    $50,500.00

    $51,000.00

    Minimumtemperature

    Design CW WB + 5degrees

    Optimized

    Chiller+Tower Yearly Estimated Operating Cost

    EarthWise

  • Introduction to Trane Control Systems24 2010 Trane

    Plant Layout FlexibilityVariable Primary Flow

    Air Handling Units

    Control Valves

    Production

    DistributionBypass Line

    SUPPLY

    DEMAN D

    Variable-Speed Drive

    Flow Meter

    UCP2UCP2

    UCP2UCP2

    Differential Pressure Sensor or

    Transmitter

  • Introduction to Trane Control Systems25 2010 Trane

    Energy OptimisationVariable Primary Chilled Water Flow Control

    UCP2UCP2

    UCP2UCP2

    F

    AHU

    P

    UCP2UCP2

    VSD

    VSD

    VSD

    Advanced

    Variable

    Primary Chilled Water

    Flow Control

  • Introduction to Trane Control Systems26 2010 Trane

    Trane AdaptiView Control System4th Generation Microprocessor Chiller Control

    Adaptive control Reliable operation through difficult

    operation conditions Feed-forward control

    Accurate and stable control under the most dynamic system transients

    Flow Compensation Sophisticated diagnostics Fast restarts Operator tested informative display Multiple open protocol communication options

  • Introduction to Trane Control Systems27 2010 Trane

    Feed-forward control is an open loop predictive control strategy which enables the chiller to respond faster to load changes

    Feed-forward control uses flow change and entering water temperature as an indication of load change

    It proactively compensates for load changes

    PID Feedback

    7?

    UC800 Feedback

    712

    Feedforward

    DP40 l/s

    Typical Controller

    AdaptiView Controller

    Trane AdaptiView Control SystemFeed-forward Control

  • Introduction to Trane Control Systems28 2010 Trane

    Figure 1: Temperature Control w ith out Feedforward

    30

    40

    50

    60

    70

    80

    90

    100

    0:00:00 0:30:00 1:00:00 1:30:00 2:00:00 2:30:00 3:00:00 3:30:00 4:00:00 4:30:00Tim e (hour:min:sec)

    T

    e

    m

    p

    [

    d

    e

    g

    F

    ]

    Condenser Entering W ater Temperature

    Evaporator Entering W ater Temperature

    Evaporator Leaving W ater Temperature Chiller CycledOff, Low W aterTem perature

    Temperature Control

  • Introduction to Trane Control Systems29 2010 Trane

    Feedforward ControlFigure 2: Temperature Control w ith Feedforward

    30

    40

    50

    60

    70

    80

    90

    100

    0:00:00 0:30:00 1:00:00 1:30:00 2:00:00 2:30:00 3:00:00 3:30:00 4:00:00 4:30:00Time (hour:min:sec)

    T

    e

    m

    p

    [

    d

    e

    g

    F

    ]

    Condenser Entering W ater Temperature

    Evaporator Entering W ater Temperature

    Evaporator Leaving W ater Temperature

  • Introduction to Trane Control Systems30 2010 Trane

    Directly measures chilled water flow Enhances leaving water temperature control during

    rapid flow rate changes of up to 50%/min. >30 % /min commercial control 10% /min precision process control

    Auto-tunes control gains to maintain stability and accuracy over chillers full range of flow rates.

    Trane AdaptiView Control SystemVariable Flow Compensation

  • Introduction to Trane Control Systems31 2010 Trane

    Capacity Controlw/o Water Flow Compensation

    30

    40

    50

    60

    70

    80

    90

    100

    110

    120

    130

    0:00:00 0:10:00 0:20:00 0:30:00 0:40:00 0:50:00Time (hour:min:sec)

    W

    a

    t

    e

    r

    T

    e

    m

    p

    [

    d

    e

    g

    F

    ]

    -500.00

    -300.00

    -100.00

    100.00

    300.00

    500.00

    700.00

    900.00

    1,100.00

    1,300.00

    1,500.00

    W

    a

    t

    e

    r

    F

    l

    o

    w

    [

    g

    p

    m

    ]

    Evaporator W ater Flow

    Evap Entering W ater Temp

    Evap Leaving W ater TempChiller off Chiller

    off

    Chiller on

    50% Flow Reduction

  • Introduction to Trane Control Systems32 2010 Trane

    With CompensationCapacity Control

    with Water Flow Compensation

    30

    40

    50

    60

    70

    80

    90

    100

    110

    120

    130

    0:00:00 0:10:00 0:20:00 0:30:00 0:40:00 0:50:00Time (hour:min:sec)

    W

    a

    t

    e

    r

    T

    e

    m

    p

    [

    d

    e

    g

    F

    ]

    -500.00

    -300.00

    -100.00

    100.00

    300.00

    500.00

    700.00

    900.00

    1,100.00

    1,300.00

    1,500.00

    W

    a

    t

    e

    r

    F

    l

    o

    w

    [

    g

    p

    m

    ]

    Evaporator W ater Flow

    Evap Entering W ater Temp

    Evap Leaving W ater Temp

  • Introduction to Trane Control Systems33 2010 Trane33

    Trane Chiller Plant Control & Optimization

    F

    P

    VSD

    VSD

    VSD

    UCP2UCP2

    UCP2UCP2

    UCP2UCP2

    VSD VSD VSD

    WB T

    SMS

    Energy Optimization

    Flexible & Reliable Op

    Better Plant Mgmt

  • Introduction to Trane Control Systems34 2010 Trane

    Landmark East

    Four Seasons Hotel

    Tai Tung Building

    Oriental Press

    AIA Building

    DHL Asia Hub

    Major Job Reference

  • Introduction to Trane Control Systems35 2010 Trane

    Landmark East

    Project Developer USI Property Management Ltd.

    E & M Consultant TAP

    Project Category HVAC Control System

    BACnet Interface with BMS

  • Introduction to Trane Control Systems36 2010 Trane

    Project Scenario

    30,000 Points

    6 chiller plants (18 nos. Trane Chillers)

    3,000 nos. VAV/CAV boxes (Trane)

  • Introduction to Trane Control Systems37 2010 Trane

    Four Season Hotel

    Project Developer SHK / Four Seasons

    Group E & M Consultant

    JRP/SHK Project Category

    HVAC Control System

    Four Season Hotel

    Project Developer SHK / Four Seasons

    Group E & M Consultant

    JRP/SHK Project Category

    HVAC Control System

  • Introduction to Trane Control Systems38 2010 Trane

    Project Scenario

    10,000 Points

    1 chiller plants (5 nos. Trane Chillers)

    800 nos. VAV/CAV boxes (Trane Controller)

    3,500 nos. FCUs (Trane)

    104 AHU/PAUs (Trane)

    10,000 Points

    1 chiller plants (5 nos. Trane Chillers)

    800 nos. VAV/CAV boxes (Trane Controller)

    3,500 nos. FCUs (Trane)

    104 AHU/PAUs (Trane)

    Project Scenario

    10,000 Points

    1 chiller plants (5 nos. Trane Chillers)

    800 nos. VAV/CAV boxes (Trane Controller)

    3,500 nos. FCUs (Trane)

    104 AHU/PAUs (Trane)

  • Introduction to Trane Control Systems39 2010 Trane

    Project Developer Tak Shing Property

    E & M Consultant Rankin & Hill

    Project Category BMS Supplier

    BMS System Integration

    Tai Tung Building

  • Introduction to Trane Control Systems40 2010 Trane

    Project Scenario

    8,000 Points 4 nos. Trane Chillers 500 nos. Trane VAV boxes 30 AHU/PAUs (Trane)

  • Introduction to Trane Control Systems41 2010 Trane

    Oriental Press

    Project Developer Oriental Press

    E & M Consultant Hang Foong

    Project Category BMS Supplier

    BMS System Integration

  • Introduction to Trane Control Systems42 2010 Trane

    Project Scenario

    4,000 Points 7 nos. Trane Chillers Tube Cleaning System 600 nos. FCUs (Trane) 18 AHU (Trane)

  • Introduction to Trane Control Systems43 2010 Trane

    200 Points4 Chillers20 AHUsBMS System

    Integration

    AIA Building

  • Introduction to Trane Control Systems44 2010 Trane

    1,000 Points2 Chillers10 AHUs70 VAVsBMS System

    Integration

    DHL Asia Hub

  • Introduction to Trane Control Systems45 2010 Trane

    Tracer Summit GraphicTracer Summit Graphic

  • Introduction to Trane Control Systems46 2010 Trane

    Tracer Summit GraphicTracer Summit Graphic

  • Introduction to Trane Control Systems47 2010 Trane

    Tracer Summit GraphicTracer Summit Graphic

  • Introduction to Trane Control Systems48 2010 Trane

    Tracer Summit GraphicTracer Summit Graphic

  • Introduction to Trane Control Systems49 2010 Trane

    Tracer Summit GraphicTracer Summit Graphic

  • Introduction to Trane Control Systems50 2010 Trane

    Tracer Summit GraphicTracer Summit Graphic

  • Introduction to Trane Control Systems51 2010 Trane

    Tracer Summit GraphicTracer Summit Graphic

  • Introduction to Trane Control Systems52 2010 Trane

    Tracer Summit GraphicTracer Summit Graphic

  • Introduction to Trane Control Systems53 2010 Trane

    Tracer Summit GraphicTracer Summit Graphic

  • Introduction to Trane Control Systems54 2010 Trane

    Tracer Summit GraphicTracer Summit Graphic

  • 55

    Thank you!


Recommended