600-Volt Secondary Bus Enclosure with Current Transformers Three-Phase – Pad-Mounted – Outdoor Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2016 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com Bulletin 340-067 Page 1 2016 Overlapping door and enclosure flanges - with other features - provide tamper resistance to meet national and regional standards Superlife finish includes phosphatizing, rust-inhibiting epoxy primer and Pad-Mount Green (Munsell 7GY 3.29/1.5) polyurethane top coat - over 5 mils dry Optional Color: Grey (Munsell 5BG 7.0/0.4) Coordinated padlock and hex-head or optional penta-head bolt (top and bottom) provides bolted door security with visual confirmation by supervisory personnel. Security bolt is made captive with a stainless steel washer compressed to an oval shape to severely discourage removal. Open bottom and bus arrangement allows access to all cables for easy installation and maintenance Neutral Bus without Current Transformer provisions Cross-kinked roof prevents standing moisture Accepts NEMA Standard 2-hole and 4-hole lugs back-to-back Nontracking self-scouring ELRIM cycloaliphatic epoxy insulators Removable lift provisions with blind holes for tamper resistance Door-holder rods are stainless steel and hold the door open 100 degrees or 140 degrees Corrosion proof nameplate is located to provide easy access for the operator Nonferrous hardware for long life Front and rear doors for easy access Ground lugs on each wall of the enclosure accept #6 - #2/0 ground cable Heavy duty 11-gauge steel enclosure is all-welded construction for long life Three Phase Aluminum bus standard Copper bus optional ENCLOSURE OPTIONS: 1) 0.125" #5052H32 Aluminum 2) 12-gauge #304L Stainless Steel Current Transformer provisions accept ABB SCL, ABB SCM & GE JAD-0C CTs Stainless steel hinges are welded to the door and the enclosure – 0.375" pins are standard
Transcript
Page 1: 600-Volt Secondary Bus Enclosure with Current Transformers ...elliott-industries.com/eipdf/b340-067.pdf · 600-Volt Secondary Bus Enclosure with Current ... Removable Primary Bus

600-Volt Secondary Bus Enclosurewith Current Transformers

Three-Phase – Pad-Mounted – Outdoor

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2016 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Bulletin

340-067Page 1 2016

Overlapping door andenclosure flanges - withother features - providetamper resistance tomeet national andregional standards

Superlife finish includesphosphatizing, rust-inhibitingepoxy primer and Pad-Mount Green (Munsell 7GY 3.29/1.5) polyurethane top coat -over 5 mils dryOptional Color: Grey(Munsell 5BG 7.0/0.4)

Coordinated padlock and hex-head or optional penta-head bolt (top and bottom) provides bolted door security with visual confirmation by supervisory personnel. Security bolt is made captive with a stainless steel washer compressed to an oval shape to severely discourage removal.

Open bottom and bus arrangement allows access to all cables for easy installation and maintenance

Neutral Bus without CurrentTransformer provisions

Cross-kinked roof prevents standing moisture Accepts NEMA Standard

2-hole and 4-hole lugs back-to-back

Nontracking self-scouring ELRIM cycloaliphatic epoxy insulators

Removable lift provisions with blind holes for tamper resistance

Door-holder rods are stainlesssteel and hold the door open100 degrees or 140 degrees

Corrosion proof nameplate is located to provide easy access for the operator

Nonferrous hardware for long life

Front and rear doors for easy access

Ground lugs on each wall of the enclosure accept #6 - #2/0 ground cable

Heavy duty 11-gauge steel enclosure is all-welded construction for long life

Three PhaseAluminum bus standardCopper bus optional

ENCLOSURE OPTIONS:1) 0.125" #5052H32 Aluminum2) 12-gauge #304L Stainless Steel

Current Transformer provisions acceptABB SCL, ABB SCM& GE JAD-0C CTs

Stainless steel hinges are welded to the door and the enclosure – 0.375" pins are standard

Page 2: 600-Volt Secondary Bus Enclosure with Current Transformers ...elliott-industries.com/eipdf/b340-067.pdf · 600-Volt Secondary Bus Enclosure with Current ... Removable Primary Bus

600-Volt Secondary Bus Enclosurewith Current Transformers

Three-Phase – Pad-Mounted – Outdoor

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2016 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Bulletin

340-067Page 2 2016

Ø 0.5625" Holes Typical

10.875"5.875"

2.125"

1.25"1.75"

0.625"

1.75"

Ø 0.5625" Holes Typical

1.75"

1.75"

or JAD-0C withPrimary Bar

SCL, SCM

or JAD-0C withPrimary Bar

SCL, SCM

10.875"5.875"

2.125"

0.75"1.75"1.75"

0.75"1.75"1.75"

Tapped Holes0.25"-20

Tapped Holes0.25"-20

0.625"

1.75"

Ø 0.5625" Holes Typical

1.75"

1.75"

or JAD-0C withPrimary Bar

SCL, SCM

10.875"5.875"

2.125"

0.75"1.75"1.75"

Tapped Holes0.25"-20

0.625"

1.75"

Ø 0.5625" Holes Typical

1.75"

1.75"

or JAD-0C withPrimary Bar

SCL, SCM

10.875"5.875"

2.125"

0.75"1.75"1.75"

Tapped Holes0.25"-20

0.625"

1.75"

Ø 0.5625" Holes Typical

1.75"

1.75"

or JAD-0C withPrimary Bar

SCL, SCM

10.875"5.875"

2.125"

0.75"1.75"1.75"

Tapped Holes0.25"-20

Supplied in 42"W x 42"D Enclosure - See Pages 4 & 5

Standard Bus:Four Single 0.25" x 10" Aluminum Bus1,800/2,100 Amp at 30/45 degree C rise over 40 degree C Ambient

Alternate Bus:Four Single 0.25" x 10" Copper Bus2,400/2,800 Amp at 30/45 degree C rise over 40 degree C Ambient

Supplied in 48"W x 48"D Enclosure - See Pages 6 & 7

Alternate Bus:Four Single 0.25" x 12" Copper Bus2,800/3,400 Amp at 30/45 degree C rise over 40 degree C Ambient

Standard Bus:Four Single 0.25" x 12" Aluminum Bus2,100/2,500 Amp at 30/45 degree C rise over 40 degree C Ambient

Supplied in 60"W x 60"D Enclosure - See Pages 10 & 11

Alternate Bus:Four Sets: 2 - 0.25" x 12" Copper Bus4,250/5,300 Amp at 30/45 degree C rise over 40 degree C Ambient

Standard Bus:Four Sets: 2 - 0.25" x 12" Aluminum Bus3,200/4,000 Amp at 30/45 degree C rise over 40 degree C Ambient

Supplied in 54"W x 54"D Enclosure - See Pages 8 & 9

Alternate Bus:Four Sets: 1 - 0.25" x 12" and 1 - 0.25" x 8" Copper Bus3,600/4,500 Amp at 30/45 degree C rise over 40 degree C Ambient

Standard Bus:Four Sets: 1 - 0.25" x 12" and 1 - 0.25" x 8" Aluminum Bus2,700/3,400 Amp at 30/45 degree C rise over 40 degree C Ambient

Supplied in 66"W x 66"D Enclosure - See Pages 12 & 13

Alternate Bus:Four Sets: 2 - 0.25" x 12" and 1 - 0.25" x 10" Copper Bus5,000/6,200 Amp at 30/45 degree C rise over 40 degree C Ambient

Standard Bus:Four Sets: 2 - 0.25" x 12" and 1 - 0.25" x 10" Aluminum Bus3,750/4,650 Amp at 30/45 degree C rise over 40 degree C Ambient

Bus Selection Information

Page 3: 600-Volt Secondary Bus Enclosure with Current Transformers ...elliott-industries.com/eipdf/b340-067.pdf · 600-Volt Secondary Bus Enclosure with Current ... Removable Primary Bus

600-Volt Secondary Bus Enclosurewith Current Transformers

Three-Phase – Pad-Mounted – Outdoor

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2016 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Bulletin

340-067Page 3 2016

SCL

Nameplate

X2 X1

HI

8.5"

6.75"

4.25"

8.92"

6.75"8.5"

5.75 Dia.

2.125"

0.56 Dia. Hole4 Total

#10-32 Term. Stud2 Total

JAD-0C

Mounting Holes for 1/2" tubular spacers (4)

Primary polarity

H1

8.5"

6.75"

4.25"

9.875"

0.875"

0.87

5"

6.75"8.5"

5.75 Dia.

2.27"

Grip RingPrimary Bus Bar

Tap 0.25"-20

Current TransformerS.S. Lock washer

0.25"-20 S.S.Hex Nut Spacer

0.25"-20 x 2.75"S.S. Hex Head

Bolts

End Cap forPrimary Bus

Bar Assembly

End Cap forPrimary Bus

Bar Assembly

Tap 0.25"-20

#10-32S.S. Phillips Head

Screws

1.6875"3"

Removable Primary Bus Bar Assembly for SCL, SCM, and JAD-0C Current TransformersCan be ordered from GE with transformers - specify 10.875" Primary Bar

or to order end caps with hardware from Elliott - specify Elliott #PBA AssemblyGrip Ring

Primary Bus Bar

Tap 0.25"-20

Current TransformerS.S. Lock washer

0.25"-20 S.S.Hex Nut Spacer

0.25"-20 x 2.75"S.S. Hex Head

Bolts

End Cap forPrimary Bus

Bar Assembly

End Cap forPrimary Bus

Bar Assembly

Tap 0.25"-20

#10-32S.S. Phillips Head

Screws

1.6875"3"

GE End CapTwo (2) Required perCurrent Transformer

Elliott End CapTwo (2) Required perCurrent Transformer

NAMEPLATE

HI

8.5"

6.75"

4.25"

8.92"

6.75"8.5"

5.75 Dia.

1.06"

0.56 Dia. Hole4 Total

#10-32 Term. Stud2 Total

X2 X1

SCM

Removable Primary Bus Bars are supplied with all Bus Enclosures

See Page 15 for Ratios and Catalog Numbers

Current Transformer Information

Page 4: 600-Volt Secondary Bus Enclosure with Current Transformers ...elliott-industries.com/eipdf/b340-067.pdf · 600-Volt Secondary Bus Enclosure with Current ... Removable Primary Bus

600-Volt Secondary Bus Enclosurewith Current Transformers

Three-Phase – Pad-Mounted – Outdoor

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2016 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Bulletin

340-067Page 4 2016

Galv. Square

1.5"

BoltsAnchorØ.5"Enclosure Washer

2.25" X 2.25"

Bracket

1.5"

#6102-A81-7

Elliott Anchor

BoltsAnchorØ.5"Enclosure

Concrete Pad

Concrete Pad

Alternate #2

Alternate #1

Anchor Bolt Locations

"C" 2

2"C"

4" Min.

14"

14"

19.375" 19.375"3" Min.

3" Min.

CL

Ø 0.75" Typical

CL

Bottom Open

42"

"C"

20"

20"

42"

42"

20" 20"

Section BBand Typical Pad Dimensions

Typical Cable TrainingDim. "C" - Measure in the Field

Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.

Catalog Number Dim. "C"

ESBE-0.6-331-CT-42W42D-36H-D87231 Measure in the Field

ESBE-0.6-331-CT-42W42D-42H-D87231 Measure in the Field

ESBE-0.6-331-CT-42W42D-48H-D87231 Measure in the Field

ESBE-0.6-331-CT-42W42D-54H-D87231 Measure in the Field

Page 5: 600-Volt Secondary Bus Enclosure with Current Transformers ...elliott-industries.com/eipdf/b340-067.pdf · 600-Volt Secondary Bus Enclosure with Current ... Removable Primary Bus

600-Volt Secondary Bus Enclosurewith Current Transformers

Three-Phase – Pad-Mounted – Outdoor

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2016 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Bulletin

340-067Page 5 2016

H1

A

A

BB

4.5" 4.5"

ElliottApparatusInsulators

1,000 Amp CT has One Primary Bars2,000 Amp CT has Two Primary Bars

TwoGroundProvisionsEach Side

CL

Ø 0.75" Typical

CL

Bottom Open

42" 42"

"B"

"A" "A"

40"38"

40"38"

42"

42"

10.875"

2.125"

1.25"1.75"

0.75"1.75"1.75"

Split Bus Detail

5.875"

9" 9"

Ø 0.5625"Holes

Typical

Provision forPadlock andSecurity Bolt,Top andBottom

or JAD-0C withPrimary Bar

SCL, SCM

0.25"-20Tapped

Holes

Standard Bus:Four Single 0.25" x 10" Aluminum Bus1,800/2,100 Amp at 30/45 degree C rise over 40 degree C Ambient

Alternate Bus:Four Single 0.25" x 10" Copper Bus2,400/2,800 Amp at 30/45 degree C rise over 40 degree C Ambient

Front ViewRear View Opposite Hand

Door Removed

Section BB

Section AA

Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.

Catalog Number Dim. "A" Dim. "B"

ESBE-0.6-331-CT-42W42D-36H-D87231 36" 23.375"

ESBE-0.6-331-CT-42W42D-42H-D87231 42" 29.375"

ESBE-0.6-331-CT-42W42D-48H-D87231 48" 35.375"

ESBE-0.6-331-CT-42W42D-54H-D87231 54" 41.375"

Page 6: 600-Volt Secondary Bus Enclosure with Current Transformers ...elliott-industries.com/eipdf/b340-067.pdf · 600-Volt Secondary Bus Enclosure with Current ... Removable Primary Bus

600-Volt Secondary Bus Enclosurewith Current Transformers

Three-Phase – Pad-Mounted – Outdoor

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2016 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Bulletin

340-067Page 6 2016

Galv. Square

1.5"

BoltsAnchorØ.5"Enclosure Washer

2.25" X 2.25"

Bracket

1.5"

#6102-A81-7

Elliott Anchor

BoltsAnchorØ.5"Enclosure

Concrete Pad

Concrete Pad

Alternate #2

Alternate #1

Anchor Bolt Locations

"C" 2

2"C"

4" Min.

17"

17"

22.375" 22.375"3" Min.

3" Min.

CL

Ø 0.75" Typical

CL

Bottom Open

48"

"C"

23"

23"

48"

48"

23" 23"

Section BBand Typical Pad Dimensions

Typical Cable TrainingDim. "C" - Measure in the Field

Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.

Catalog Number Dim. "C"

ESBE-0.6-331-CT-48W48D-36H-D2001048 Measure in the Field

ESBE-0.6-331-CT-48W48D-42H-D2001048 Measure in the Field

ESBE-0.6-331-CT-48W48D-48H-D2001048 Measure in the Field

ESBE-0.6-331-CT-48W48D-54H-D2001048 Measure in the Field

Page 7: 600-Volt Secondary Bus Enclosure with Current Transformers ...elliott-industries.com/eipdf/b340-067.pdf · 600-Volt Secondary Bus Enclosure with Current ... Removable Primary Bus

600-Volt Secondary Bus Enclosurewith Current Transformers

Three-Phase – Pad-Mounted – Outdoor

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2016 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Bulletin

340-067Page 7 2016

H1

A

A

BB

4.5" 4.5"

ElliottApparatusInsulators

2,000 Amp CT has Two Primary Bars3,000 Amp CT has Three Primary Bars

TwoGroundProvisionsEach Side

CL

Ø 0.75" Typical

CL

Bottom Open

48" 48"

"B"

"A" "A"

46"44"

46"44"

48"

48"

9" 9"

Provision forPadlock andSecurity Bolt,Top andBottom

Split Bus Detail

0.625"

1.75"

Ø 0.5625" Holes Typical

1.75"

1.75"

or JAD-0C withPrimary Bar

SCL, SCM

10.875"5.875"

2.125"

0.75"1.75"1.75"

Tapped Holes0.25"-20

Standard Bus:Four Single 0.25" x 12" Aluminum Bus2,100/2,500 Amp at 30/45 degree C rise over 40 degree C Ambient

Alternate Bus:Four Single 0.25" x 12" Copper Bus2,800/3,400 Amp at 30/45 degree C rise over 40 degree C Ambient

Front ViewRear View Opposite Hand

Door Removed

Section BB

Section AA

Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.

Catalog Number Dim. "A" Dim. "B"

ESBE-0.6-331-CT-48W48D-36H-D2001048 36" 21.375"

ESBE-0.6-331-CT-48W48D-42H-D2001048 42" 27.375"

ESBE-0.6-331-CT-48W48D-48H-D2001048 48" 33.375"

ESBE-0.6-331-CT-48W48D-54H-D2001048 54" 39.375"

Page 8: 600-Volt Secondary Bus Enclosure with Current Transformers ...elliott-industries.com/eipdf/b340-067.pdf · 600-Volt Secondary Bus Enclosure with Current ... Removable Primary Bus

600-Volt Secondary Bus Enclosurewith Current Transformers

Three-Phase – Pad-Mounted – Outdoor

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2016 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Bulletin

340-067Page 8 2016

Galv. Square

1.5"

BoltsAnchorØ.5"Enclosure Washer

2.25" X 2.25"

Bracket

1.5"

#6102-A81-7

Elliott Anchor

BoltsAnchorØ.5"Enclosure

Concrete Pad

Concrete Pad

Alternate #2

Alternate #1

"C" 2

2"C"

4" Min.

20"

20"

25.375" 25.375"3" Min.

3" Min.

CL

Ø 0.75" Typical

CL

Bottom Open

54"

"C"

26"

26"

54"

54"

26" 26"

Anchor Bolt Locations

Section BBand Typical Pad Dimensions

Typical Cable TrainingDim. "C" - Measure in the Field

Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.

Catalog Number Dim. "C"

ESBE-0.6-331-CT-54W54D-36H-D2003218 Measure in the Field

ESBE-0.6-331-CT-54W54D-42H-D2003218 Measure in the Field

ESBE-0.6-331-CT-54W54D-48H-D2003218 Measure in the Field

ESBE-0.6-331-CT-54W54D-54H-D2003218 Measure in the Field

Page 9: 600-Volt Secondary Bus Enclosure with Current Transformers ...elliott-industries.com/eipdf/b340-067.pdf · 600-Volt Secondary Bus Enclosure with Current ... Removable Primary Bus

600-Volt Secondary Bus Enclosurewith Current Transformers

Three-Phase – Pad-Mounted – Outdoor

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2016 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Bulletin

340-067Page 9 2016

3,000 Amp CT has Three Primary Bars4,000 Amp CT has Four Primary Bars

H1

A

A

BB

5" 5"

Provision for Padlock andSecurity Bolt, Top and Bottom

ElliottApparatusInsulators

TwoGroundProvisionsEach Side

CL

Ø 0.75" Typical

CL

Bottom Open

54" 54"

"B"

"A" "A"

52"50"

52"50"

54"

54"

10" 10"

Split Bus Detail

0.625"

1.75"

Ø 0.5625" Holes Typical

1.75"

1.75"

or JAD-0C withPrimary Bar

SCL, SCM

10.875"5.875"

2.125"

0.75"1.75"1.75"

Tapped Holes0.25"-20

Standard Bus:Four Sets: 1 - 0.25" x 12" and 1 - 0.25" x 8" Aluminum Bus2,700/3,400 Amp at 30/45 degree C rise over 40 degree C Ambient

Alternate Bus:Four Sets: 1 - 0.25" x 12" and 1 - 0.25" x 8" Copper Bus3,600/4,500 Amp at 30/45 degree C rise over 40 degree C Ambient

Front ViewRear View Opposite Hand

Door Removed

Section BB

Section AA

Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.

Catalog Number Dim. "A" Dim. "B"

ESBE-0.6-331-CT-54W54D-36H-D2003218 36" 21.375"

ESBE-0.6-331-CT-54W54D-42H-D2003218 42" 27.375"

ESBE-0.6-331-CT-54W54D-48H-D2003218 48" 33.375"

ESBE-0.6-331-CT-54W54D-54H-D2003218 54" 39.375"

Page 10: 600-Volt Secondary Bus Enclosure with Current Transformers ...elliott-industries.com/eipdf/b340-067.pdf · 600-Volt Secondary Bus Enclosure with Current ... Removable Primary Bus

600-Volt Secondary Bus Enclosurewith Current Transformers

Three-Phase – Pad-Mounted – Outdoor

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2016 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Bulletin

340-067Page 10 2016

Galv. Square

1.5"

BoltsAnchorØ.5"Enclosure Washer

2.25" X 2.25"

Bracket

1.5"

#6102-A81-7

Elliott Anchor

BoltsAnchorØ.5"Enclosure

Concrete Pad

Concrete Pad

Alternate #2

Alternate #1

Anchor Bolt Locations

28.375" 28.375"3" Min.

CL

Ø 0.75" Typical

CL

Bottom Open

60"

29"

29"

60"

29" 29"

23"

23"

3" Min.

60"

4" Min.

2"C"

"C" 2

"C"

Section BBand Typical Pad Dimensions

Typical Cable TrainingDim. "C" - Measure in the Field

Cable Training and Anchor Bolt Locations

Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.

Catalog Number Dim. "C"

ESBE-0.6-331-CT-60W60D-36H-D2010148 Measure in the Field

ESBE-0.6-331-CT-60W60D-42H-D2010148 Measure in the Field

ESBE-0.6-331-CT-60W60D-48H-D2010148 Measure in the Field

ESBE-0.6-331-CT-60W60D-54H-D2010148 Measure in the Field

Page 11: 600-Volt Secondary Bus Enclosure with Current Transformers ...elliott-industries.com/eipdf/b340-067.pdf · 600-Volt Secondary Bus Enclosure with Current ... Removable Primary Bus

600-Volt Secondary Bus Enclosurewith Current Transformers

Three-Phase – Pad-Mounted – Outdoor

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2016 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Bulletin

340-067Page 11 2016

H1

A

A

BB

6" 6"

Provision for Padlock andSecurity Bolt, Top and Bottom

ElliottApparatusInsulators

3,000 Amp CT has Three Primary Bars4,000 Amp CT has Four Primary Bars

TwoGroundProvisionsEach Side

CL

Ø 0.75" Typical

CL

Bottom Open

60" 60"

"B"

"A" "A"

58"56"

58"56"

60"

60"

12" 12"

0.625"

1.75"

Ø 0.5625" Holes Typical

1.75"

1.75"

or JAD-0C withPrimary Bar

SCL, SCM

10.875"5.875"

2.125"

0.75"1.75"1.75"

Tapped Holes0.25"-20

Split Bus Detail

Standard Bus:Four Sets: 2 - 0.25" x 12" Aluminum Bus3,200/4,000 Amp at 30/45 degree C rise over 40 degree C Ambient

Alternate Bus:Four Sets: 2 - 0.25" x 12" Copper Bus4,250/5,300 Amp at 30/45 degree C rise over 40 degree C Ambient

Front ViewRear View Opposite Hand

Door Removed

Section BB

Section AA

Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.

Catalog Number Dim. "A" Dim. "B"

ESBE-0.6-331-CT-60W60D-36H-D2010148 36" 21.375"

ESBE-0.6-331-CT-60W60D-42H-D2010148 42" 27.375"

ESBE-0.6-331-CT-60W60D-48H-D2010148 48" 33.375"

ESBE-0.6-331-CT-60W60D-54H-D2010148 54" 39.375"

Page 12: 600-Volt Secondary Bus Enclosure with Current Transformers ...elliott-industries.com/eipdf/b340-067.pdf · 600-Volt Secondary Bus Enclosure with Current ... Removable Primary Bus

600-Volt Secondary Bus Enclosurewith Current Transformers

Three-Phase – Pad-Mounted – Outdoor

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2016 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Bulletin

340-067Page 12 2016

Galv. Square

1.5"

BoltsAnchorØ.5"Enclosure Washer

2.25" X 2.25"

Bracket

1.5"

#6102-A81-7

Elliott Anchor

BoltsAnchorØ.5"Enclosure

Concrete Pad

Concrete Pad

Alternate #2

Alternate #1

CL

LC

Bottom Open

Ø 0.75" Typical

66"

3" Min.

32"

32"

32"32"

31.375"31.375"

26"

26"

66"

66"

4" Min.

2"C"

"C" 2

"C"

Anchor Bolt Locations

3" Min.

Section BBand Typical Pad Dimensions

Typical Cable TrainingDim. "C" - Measure in the Field

Cable Training and Anchor Bolt Locations

Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.

Catalog Number Dim. "C"

ESBE-0.6-331-CT-66W66D-36H-D2011103 Measure in the Field

ESBE-0.6-331-CT-66W66D-42H-D2011103 Measure in the Field

ESBE-0.6-331-CT-66W66D-48H-D2011103 Measure in the Field

ESBE-0.6-331-CT-66W66D-54H-D2011103 Measure in the Field

ESBE-0.6-331-CT-66W66D-60H-D2011103 Measure in the Field

Page 13: 600-Volt Secondary Bus Enclosure with Current Transformers ...elliott-industries.com/eipdf/b340-067.pdf · 600-Volt Secondary Bus Enclosure with Current ... Removable Primary Bus

600-Volt Secondary Bus Enclosurewith Current Transformers

Three-Phase – Pad-Mounted – Outdoor

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2016 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Bulletin

340-067Page 13 2016

4,000 Amp CT has Four Primary Bars5,000 Amp CT has Five Primary Bars

CL

A

A

BB

LC

GroundProvisionEach Side

Ø 0.75" Typical

Bottom Open

Provision for Padlock andSecurity Bolt, Top and Bottom

66"

13" 13"6.5" "A"6.5"

66"

"B"

66"

64"62"

64"62"

66"

H1

Split Bus Detail

0.625"

1.75"

Ø 0.5625" Holes Typical

1.75"

1.75"

or JAD-0C withPrimary Bar

SCL, SCM

10.875"5.875"

2.125"

0.75"1.75"1.75"

Tapped Holes0.25"-20

Front ViewRear View Opposite Hand

Door Removed

Section BB

Section AA

Standard Bus:Four Sets: 2 - 0.25" x 12" and 1 - 0.25" x 10" Aluminum Bus3,750/4,650 Amp at 30/45 degree C rise over 40 degree C Ambient

Alternate Bus:Four Sets: 2 - 0.25" x 12" and 1 - 0.25" x 10" Copper Bus5,000/6,200 Amp at 30/45 degree C rise over 40 degree C Ambient

Secondary Bus Enclosures are available in other size enclosures, bus ratings and current transformer provisions. If you do not find a model to fit your need, please contact our representative or the factory.

Catalog Number Dim. "A" Dim. "B"

ESBE-0.6-331-CT-66W66D-36H-D2011103 36" 21.375"

ESBE-0.6-331-CT-66W66D-42H-D2011103 42" 27.375"

ESBE-0.6-331-CT-66W66D-48H-D2011103 48" 33.375"

ESBE-0.6-331-CT-66W66D-54H-D2011103 54" 39.375"

ESBE-0.6-331-CT-66W66D-60H-D2011103 60" 45.375"

Page 14: 600-Volt Secondary Bus Enclosure with Current Transformers ...elliott-industries.com/eipdf/b340-067.pdf · 600-Volt Secondary Bus Enclosure with Current ... Removable Primary Bus

600-Volt Secondary Bus Enclosurewith Current Transformers

Three-Phase – Pad-Mounted – Outdoor

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2016 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Bulletin

340-067Page 14 2016

Typical Specification - Page 1 of 2

GeneralThe secondary bus enclosure with current transformers

shall be 600 volt class, suitable for use on systems that do not exceed 600 volts to ground (nor 1000 volts phase-to-phase). Each phase bus shall be designed for and include (or accept) a 600 volt class current transformer (ABB SCL, ABB SCM, GE JAD-0C or equal). The phase bus(es) and the full-size neutral bus shall be constructed for connection to the electrical system with two-hole and/or four-hole NEMA standard bolt-on cable-terminal lugs (terminal lugs shall be supplied by the user). Tamper resistance shall meet the Enclosure Security requirements of IEEE Standard C57.12.28 (Pad-Mounted Equipment—Enclosure Integrity) to resist unauthorized entry, protect authorized and unauthorized persons, and provide positive safety features when installed in areas accessible to the general public. The enclosure shall be constructed for outdoor installation in areas subject to heavy precipitation and in areas of windblown contamination. The equipment shall be completely assembled prior to shipment.

Enclosure ConstructionThe enclosure shall be tamper-resistant, all-welded

construction utilizing 11-gauge minimum sheet steel. Corner plates and braces shall be used as necessary to assure rigidity. The enclosure top shall be cross-kinked to provide watershed and rigidity. The enclosure shall be open bottom with a 1-inch flange inside, all around. The door(s) shall be furnished with a stainless steel door holder that will latch the door open 100 degrees and 140 degrees and resist accidental closing. Door(s) shall be provided with provisions for padlocking and a recessed hex-head (or penta-head) security bolt to prevent unauthorized entry (coordinated to prevent installation of the padlock until the security bolt is tightened when closing the door(s) and to prevent a wrench from operating the security bolt until the padlock is removed when opening the door(s)). The security bolt shall be made captive with a stainless steel washer compressed to an oval shape to severely discourage removal. Hinges shall be stainless steel (with stainless steel pins not less than 0.3125-inch diameter) and shall be welded to both the enclosure and the door(s) to maintain door alignment for the life of the equipment. The enclosure shall be nonventilated to minimize the entrance of airborne contamination, insects, rodents or reptiles. The protective finish shall include necessary grinding, cleaning and phosphatizing, two-component rust-inhibiting epoxy primer and a Pad-Mount Green two-component polyurethane top coat finish (Munsell color 7GY 3.29/1.5). The primer and top coat shall be electronically monitored during application to insure proper ratio and mixing of each component. Total average thickness of paint (after curing) shall be not less than 5 mils. The protective coating shall meet the Enclosure Coating System requirements of IEEE Standard C57.12.28 (Pad-Mounted Equipment—Enclosure Integrity). Removable lift provisions, adequate to withstand handling with normal utility equipment, shall be provided on the outside of

the enclosure. Threaded openings for lift provision bolts shall be blind holes to prevent the entrance of wire or other foreign objects into the enclosure when lift provisions are removed.

Bus and Bus MountingsBus shall be aluminum (Alternate #1—bare copper,

Alternate #2—tin-plated copper) with all burrs and sharp corners removed prior to installation. It shall be punched with 0.5625-inch diameter holes on 1.75-inch centers to accommodate both two-hole and four-hole NEMA standard cable-terminal lugs. The bus shall be constructed to allow installation and provide support for 600 volt class current transformers (ABB SCL, ABB SCM, GE JAD-0C or equal) utilizing the correct number of 0.25-inch by 4-inch primary bars with 10.875-inch outboard centerline mounting holes. The current transformers shall be mounted in a manner that will allow installation or field replacement without the removal of cables that may be bolted to the bus. A minimum of two insulators shall be provided for each bus assembly. The insulators shall be cycloaliphatic epoxy and shall be mounted in a manner that will allow field replacement with standard tools without removal of cables that may be bolted to the bus. Insulators and bus bars shall be installed with stainless steel mounting hardware to provide long life and reduced maintenance. All components shall be arranged to allow visual inspection without de-energizing or removing the equipment from service.

Current TransformersAlternate 1: Current Transformers shall be supplied and

installed by the user.Alternate 2: Current Transformers specified by the user

shall be supplied and installed by the manufacturer.

Voltage TransformersAlternate 1: Voltage Transformers are not required.Alternate 2: When specified, a mounting plate shall be

provided for Voltage Tranformers supplied and installed by the user.

Alternate 3: When specified, a mounting plate shall be provided for Voltage Transformers supplied and installed by the manufacturer.

Secondary WiringAlternate 1: Secondary wiring shall be supplied and

installed by the user.Alternate 2: Secondary wiring shall be #10 THW/XHHW

stranded-copper wire connecting the instrument transformer secondary to the 10-Terminal Test Switch and 13-Terminal Meter Socket installed on the right-hand exterior wall of the Secondary Bus Enclosure (when facing the front door). The secondary wiring shall be color-coded as specified by the user (or the factory color code when the user does not specify a color code).

Page 15: 600-Volt Secondary Bus Enclosure with Current Transformers ...elliott-industries.com/eipdf/b340-067.pdf · 600-Volt Secondary Bus Enclosure with Current ... Removable Primary Bus

600-Volt Secondary Bus Enclosurewith Current Transformers

Three-Phase – Pad-Mounted – Outdoor

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2016 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Bulletin

340-067Page 15 2016

Barrier OptionWhen Option B11 is specified, a clear polycarbonate

barrier not less than 0.25-inch nominal thickness shall be provided (and installed) that divides the utility access compartment from the consumer access compartment. The clearance from the barrier to each wall shall not exceed two inches. The clearance from the barrier to the bottom of the enclosure shall not exceed twelve inches. Openings to accommodate bus bars extending through the barrier shall provide not less than 0.5-inch clearance nor more than 2-inch clearance from the bus bar in every direction.

Grounding ProvisionsFour high-conductivity bronze eyebolt-type ground lugs,

which accept #6 through #2/0 copper conductor, shall be installed on the inside walls of the enclosure (located on each side of each door opening in an accessible position as shown on the drawings).

Accessory EquipmentA corrosion proof nameplate with permanent thermal

transfer printing shall be installed inside one door on the cable compartment. It shall be located at the top corner farthest from the cables when the door is open. The nameplate will provide Type of Equipment, Model Number, Amps Continuous, kV Maximum, BIL, Serial Number, Job Number, Date Manufactured and Weight of Equipment.

When specified, one “Warning - Keep Out! - Hazardous Voltage” sign, Elliott #7201-W2003-316, shall be provided on the outside of each door.

When specified, four anchor-bolt brackets, Elliott #6102-A81-7 or approved equal, shall be supplied with each secondary bus enclosure to provide a means of clamping the equipment to the concrete pad.

PackagingEach secondary bus enclosure shall be bolted to a

solid-top wood pallet (to prevent the forks of a forklift truck from entering the open bottom of the equipment) to prevent hidden damage. The equipment shall be wrapped with 0.125-inch thick polyethylene foam or other suitable material to minimize damage to the finish during shipment.

DrawingsWhen specified, drawings shall be furnished for each

secondary bus enclosure that include:1) enclosure dimensions and location of components.2) proposed cable-training layout and dimensions.3) proposed pad dimensions and location of anchor

bolts.

Typical Specification - Page 2 of 2

Primary Amps

StyleNumber

Rating Factor30°C 55°C

200 7526A81G01 2.0 1.5300 7526A81G02 2.0 1.5400 7526A81G03 2.0 1.5600 7526A81G04 2.0 1.5800 7526A81G05 2.0 1.5

1000 7526A81G06 1.5 1.01200 7526A81G07 1.5 1.01500 7526A81G08 1.33 1.02000 7526A81G09 1.33 1.02500 7526A81G10 1.33 1.03000 7526A81G11 1.33 1.04000 7526A81G12 1.33 1.0

SCL

Primary Amps

StyleNumber

Rating Factor30°C 55°C

200 7525A36G01 1.33 1.0300 7525A36G02 1.33 1.0400 7525A36G03 1.33 1.0500 7525A36G04 1.33 1.0600 7525A36G05 1.33 1.0800 7525A36G06 1.33 1.0

1000 7525A36G07 1.33 1.01200 7525A36G08 1.33 1.01500 7525A36G09 1.33 1.01600 7525A36G10 1.33 1.02000 7525A36G11 1.33 1.02500 7525A36G12 1.33 1.03000 7525A36G13 1.33 1.04000 7525A36G14 1.0 0.5

SCM

JAD-0CCurrent Ratio in

AmperesPri : Sec

Catalog Number(with Round Window;

withoutMounting Base)

Continuous-thermal-current Rating Factor 30°C Ambient

200:5 750X120240 4.0300:5 750X120241 4.0400:5 750X120242 4.0500:5 750X120243 4.0600:5 750X120244 3.0800:5 750X120001 3.0

1000:5 750X120002 2.01200:5 750X120003 2.01500:5 750X120180 3.02000:5 750X120005 2.02500:5 750X120006 1.53000:5 750X120007 1.54000:5 750X120008 1.5

Page 16: 600-Volt Secondary Bus Enclosure with Current Transformers ...elliott-industries.com/eipdf/b340-067.pdf · 600-Volt Secondary Bus Enclosure with Current ... Removable Primary Bus

600-Volt Secondary Bus Enclosurewith Current Transformers

Three-Phase – Pad-Mounted – Outdoor

Elliott Industries, Inc. 1509 Hamilton Road Bossier City, LoUiSiAna 71111 [email protected] © Copyright 2016 Phone 318-746-3296 Fax 318-741-1127 www.elliott-industries.com

Bulletin

340-067Page 16 2016

Information needed to provide a Quotation for aSecondary Bus Enclosure with Current Transformers

Catalog Number:

Enclosure: Standard 11-gauge Steel □ 0.125” Aluminum □ 12-gauge Stainless Steel □Hex Head Security Bolts □ Penta Head Security Bolts □Actual Secondary Voltage (Optional):

Without CTs: □ With CTs: □ CT Ratio :5 Without VTs: □ With VTs: □ VT Ratio :1

Preferred Brand of Transformers: ABB □ GE □ Either □ Other

CT Style/Catalog Number: VT Style/Catalog Number:

Your Name, Company Name, Complete Postal Address and E-mail Address:

Name and Complete Shipping Address: Project Name:

NOTE: Single phase and two phase Secondary Bus Enclosures are available. Contact our representative or the factory.

If you do not find the design

you need

PLEASE CONTACT

our REPRESENTATIVE or the FACTORY


Recommended