+ All Categories
Home > Documents > 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control...

6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control...

Date post: 22-Feb-2018
Category:
Upload: hoangtuyen
View: 221 times
Download: 3 times
Share this document with a friend
65
6.2.1.4 Edition 05.11 Technical Information · GB www.kromschroeder.com For directly ignited burners of unlimited capacity in intermittent operation or in continuous operation pursuant to EN 746-2 Plug-in function unit for mounting in 19" module subracks Flame control by UV, ionization or a further option of using the furnace chamber temperature Display of the program status, unit parameters and flame signal; Manual mode for burner adjustment and for diagnostic purposes Visualization and adaptation to the specific application via the PC programming and diagnostic software BCSoft to simplify logistics management Air valve control relieves the furnace control Connection to PROFIBUS-DP via field bus interface PFA Certified for systems up to SIL 3 and compliant with PL e Burner control unit PFU 760
Transcript
Page 1: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

6214 Edition 0511Technical Information middot GB

wwwkromschroedercom

bull For directly ignited burners of unlimited capacity in intermittent operation or in continuous operation pursuant to EN 746-2

bull Plug-in function unit for mounting in 19 module subracksbull Flame control by UV ionization or a further option of using the furnace

chamber temperaturebull Display of the program status unit parameters and flame signal

Manual mode for burner adjustment and for diagnostic purposesbull Visualization and adaptation to the specific application via the PC

programming and diagnostic software BCSoft to simplify logistics management

bull Air valve control relieves the furnace controlbull Connection to PROFIBUS-DP via field bus interface PFAbull Certified for systems up to SIL 3 and compliant with PL e

Burner control unit PFU 760

PFU 760 middot Edition 0511

2

t = To be continued

ContentsBurner control unit PFU 760 1Contents 21 Application 411 Examples of application 6

111 Staged OnOff burner control 6112 Staged HighLow burner control 7113 Two-stage-controlled burner 8114 Modulating-controlled burner 9116 PFU for PROFIBUS-DP with PFA 700 10115 PFU 760D High temperature equipment 10

2 Certification 113 Function 1231 Connection diagram 12311 PFU 760 12312 PFU 760K1 13313 PFU 760K2 14

32 PFU 760 program sequence 1533 Program status and fault messages 17

4 Parameters 1841 Scanning the parameters 1942 Flame control 20421 Burner flame signal 20422 Program status when the most recent fault occurred 20423 Switch-off threshold of the flame amplifier 20424 High temperature operation with PFUD 21425 UVS check 24

43 Behaviour in start-up positionstandby 25431 Flame simulation check in start-up positionstandby 25432 Minimum burner pause time tBP 26

44 Behaviour during start-up 27441 Safety time on start-up tSA 27442 Flame proving period tFS 27443 Minimum combustion time tB 27444 Burner start-up attempts 28

45 Behaviour during operation 29

451 Safety time during operation tSB for V1 and V2 29452 Fault lock-out or restart 29

46 Switchable gas valve V2 on PFUL 3147 Air valve control PFUL 32471 Purge 32472 Cooling in start-up positionstandby 32473 Burner start 32474 Air valve opens in the case of external activation (not during start-up) 33475 Air valve opens in the case of external activation (even during start-up) 34476 Air valve opens with valve V1 35477 Air valve opens with valve V2 36478 Low fire over run time tKN after a controlled shut-down 37479 Behaviour of the air valve in the event of a fault lock-out 38

48 Manual operation 39481 Manual mode limited to 5 minutes 39

49 Password 39410 Multi-flame control 40

5 Selection 4151 Safety time 41511 Calculating the safety time tSA 41

52 Selection table 4253 Type code 42

6 Project planning information 4361 Cable selection 43611 Ignition cable 43612 Ionization cable 43613 UV cable 43

62 Ignition electrode 43621 Electrode gap 43622 Star electrodes 43

63 Minimum combustion time 4464 Safety interlocks (Limits) 4465 Emergency stop 44

PFU 760 middot Edition 0511

3

t = To be continued

651 In the event of fire or electric shock 44652 Via the safety interlocks (limits) 44

66 Reset 45661 Parallel reset 45662 Permanent remote reset 45663 Automatic remote reset (PLC) 45664 Burner start 45665 Restart and start-up attempts 45

67 Fault signalling 4668 Protecting the burner from overload 4669 Installation 46610 Wiring 46

6101 UVS sensor wiring 46611 PFU switched off 46612 Furnace control 47613 Note on EC type-examination 47614 Mains switch 47615 Changing parameters 47

7 Flame control 4871 With ionization sensor 4872 With UV sensor 4873 Via the temperature in high temperature equipment 48

8 Accessories 4981 High-voltage cable 4982 BCSoft 4983 Stickers for labelling 4984 ldquoChanged parametersrdquo stickers 4985 Radio interference suppressed electrode adapters 5086 Socket connectors 5087 Module subracks 5088 Power supply PFP 700 5189 Relay module PFR 704 52810 Flame detector PFF 704 53811 Field bus interface PFA 700 54

812 Impulse system MPT 700 559 Technical data 5691 Safety-specific characteristic values 5892 Operating controls 59

10 Maintenance cycles 6011 Legend 6112 Glossary 62121 Waiting time tW 62122 Safety time on start-up tSA 62123 Ignition time tZ 62124 Flame simulationFlame simulation delay time tLV 62125 Safety time during operation tSB 62126 Flame signal 63127 Fault lock-out 63128 Safety interlocks (Limits) 63129 Pilot gas valve V1 631210 Main gas valve V2 631211 Continuous operation 631212 Air valve 631213 Diagnostic coverage DC 641214 Mode of operation 641215 Safe failure fraction SFF 641216 Probability of dangerous failure PFHD 641217 Mean time to dangerous failure MTTFd 64

Feedback 65Contact 65

PFU 760 middot Edition 0511

4

1 ApplicationThe burner control units PFU 760 control ignite and moni-tor gas burners for intermittent or continuous operation As a result of their fully electronic design they react quickly to various process requirements and are therefore also suitable for frequent cycling operationThe PFU 760 can be used for directly ignited industrial burners The burners may be modulating or stage-controlledOn industrial furnaces the PFU 760 reduces the load on the central furnace control by taking over tasks that only relate to the burner for example it ensures that the burner always ignites in a safe condition after it has been restartedThe burner control unit is used for burners with mechanical combustion air supply where the fan is controlled by a separate logic and for atmospheric burners

The air valve control on the burner control unit PFU 760L assists the furnace control for cooling purging and output control tasksThe program status the unit parameters and the level of the flame signal can be read directly from the unit The burner can be controlled manually for commissioning and diagnostic purposesIf the local requirements on the burner control unit change the PC software BCSoft can be adjusted to the unit parameters of the application by using the optical interfaceThe service personnel is supported by a convenient visualiza-tion system of the input and output signals and the error historyTo reduce the installation and wiring costs Elster Kromschroumlder offers the field bus interface PFA 700 to transfer the control signals and feedbacks via PROFIBUS-DP

Module subrack BGT for instance serves to accom-modate several function units It is provided with a backplane with screw terminals for simple reliable wiring

PFU 760 middot Edition 0511

5Application

Bogie hearth forging furnace in the metallurgical industry

Intermittent shuttle kiln in the ceramics industry

Walking beam furnace with overhead firing

PFU 760 middot Edition 0511

6

VRR

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

UV

ϑ1

microC

Application

1 1 Examples of application1 1 1 Staged OnOff burner controlThe burner can be started with reduced capacityA UV sensor monitors the flame signal from the burner UV sensor UVD 1 is used for continuous operation UV sensor UVS for intermittent operation

PFU 760 middot Edition 0511

7

VRR

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

GIKB

VASN

ϑ1

microC

Application gt Examples of application

1 1 2 Staged HighLow burner controlThe burner starts at low-fire rate When the operating state is reached the PFU 760L advises the control unit The PLC can now pulse the air valve in order to control the burner output

PFU 760 middot Edition 0511

8

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

Application gt Examples of application

1 1 3 Two-stage-controlled burnerControl ONOFF with ignition via bypassThe burner starts at low-fire rate When the operating state is reached the PFU 760L issues the Enable signal for the maximum burner output

PFU 760 middot Edition 0511

9

VAG

PFU 760

SPSPLCAPI

DI

L1 N PE

10e

2e 4e

2c 4c

26a

P

26e 10c

DI

BVA+IC 20

M

mA

TZI

16c

22a

BIO BIC

28c

ϑ1

microC

Application gt Examples of application

1 1 4 Modulating-controlled burnerControl continuousThe external control system moves the butterfly valve for air BVA to ignition position The burner starts at low-fire rate and a controller in the PLC controls the burner output via the butterfly valve for air BVA after the operating state has been signalled

PFU 760 middot Edition 0511

10

STW

L1

gt750 degC

microC

PFU 760D

18a

DI

22a

microC

PFU 760D

18a

DI

22a

SPSPLCAPI

DI

L1 N PE P

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

PROFIBUS-DP

1 1 5 PFU 760 D High temperature equipmentIndirect flame control using the tempera-ture During the start-up process as long as the wall temperature is below auto ignition temperature the flame must be controlled by conventional methods When the working temperature has exceeded 750degC the safety tempera-ture monitor (STW) takes over the indirect flame control

1 1 6 PFU for PROFIBUS-DP with PFA 700The bus system transfers the control sig-nals for starting resetting and for con-trolling the air valve from the control sys-tem (PLC) to the PFU 760 via the PFA 700 In the opposite direction it sends infor-mation on the operating status Control signals that are relevant for safety such as the safety interlocks and digital input are transferred independently of the bus communication by separate cables

Application gt Examples of application

PFU 760 middot Edition 0511

11

2 CertificationCertified pursuant to SIL

For systems up to SIL 3 pursuant to EN 61508Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

EC type-tested and certified

pursuant tondash Gas Appliances Directive (2009142EC) in conjunction

with EN 2982004-01

Meets the requirements of thendash Low Voltage Directive (200695EC)ndash EMC Directive (2004108EC)

PFU T is FM approved

Factory Mutual Research Class 1997Suitable for applications pursuant to NFPA 86 wwwfmglobalcom Products and Services Product Cer-tification Approval Guide

AGA approved

AGA

Australian Gas Association Approval No 5597 wwwagaasnauproduct_directory

PFU 760 middot Edition 0511

12

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)( 3 Function

3 1 Connection diagramFor cable selection and wiring see page 43 (Project planning information)

3 1 1 PFU 760For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

13

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

PFU 760K1 PFU 760LK1)(

F2

F1

Function gt Connection diagram

3 1 2 PFU 760 K1As a replacement unit for burner control unit PFSPFD 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

14

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760K2 PFU 760LK2)(

Function gt Connection diagram

3 1 3 PFU 760 K2As a replacement unit for burner control unit PFU 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

15

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

Function

3 2 PFU 760 program sequenceNormal start-upIf an ldquooldrdquo fault is still being signalled after switching on it will be necessary to reset this firstWhen the safety interlocks are closed the PFU reverts to start-up position and conducts a self-test If it does not deter-mine a malfunction of the internal elec-tronic circuitry or of the flame sensor the burner can be startedThe flame simulation check is conducted during start-up position or after applying the start-up signal (ϑ) depending on parameter 15After the min burner pause time tBP has elapsed the PFU opens valve V1 and ignites the burner The ignition time tZ is constantIf a flame is detected during the safety time tSA the flame proving period tFS starts after this safety time has elapsed Valve V2 opens and the operation signalling contact between terminals 2c and 4c closes This completes start-up An adjustable min combustion time tB ensures that the burner burns for a defined period even if the start-up signal (ϑ) is switched off beforehand

PFU 760Lwith air valve control features the following additional functions

In start-up position the air valve can be opened for cooling A

Using parameter 31 it can be determined whether the air valve can be activated externally during start-up

The air valve can be set to open together with V1 (display A2 ) via parameter 30

PFU 760 middot Edition 0511

16 Function gt PFU 760 program sequence

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

The air valve can also be set to open with V2 or to be activated externally (display A4 ) via parameter 30

The burner can also be started manually with the aid of the button on the PFU Voltage must be applied continuously to terminals 10e 26e and 30a in order for this to occurThe PFU can also be operated in Manual mode for start-up

Start-up without flame signal If no flame is detected during the safety time tSA either a fault lock-out occurs or up to three further start-up attempts occur The required functions and if applicable the number of start-up attempts must be specified when or-dering (Parameter 10 ldquoBurner start-up attemptsrdquo)

Behaviour in the event of flame failure during operationIf the flame fails during operation either an immediate fault lock-out occurs or a restart occurs This procedure can be set via the optical interface (parameter 12 ldquoBurner restartrdquo)

PFU 760 middot Edition 0511

17Function

Program status DISPLAY Fault message (blinking)Start-up positionstandby 00

Cooling A0

Waiting timePause time 1 Flame simulation pilot burnerBurner safety time on start-up 2 Burner start-up without flame signalBurner flame proving period 3 Flame failure during burner flame proving periodBurner operation 4 Flame failure during operation pilot burnerPurge P0 Air valve A

High temperature operation

10 Faulty remote reset

32 Supply voltage too low

33 Faulty parameterization

35 Short-circuit on a valve output

36 Short-circuit on ignition or valve output

51 Safety interlock failure

52 Permanent reset

53 Time between two start-ups is too short In Manual mode two dots will blink on the display in program status 01 ndash 04 Optionally available

3 3 Program status and fault messagesDuring operation the 7-segment display shows the program status In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault The burner control unit can be reset using the Reset button or the remote reset

PFU 760 middot Edition 0511

18

4 ParametersDescription Parameter Value range Factory default

setting Adjustable

Burner flame signal 01 0 ndash 30 μAProgram status when the most recent fault occurred 03 x0 ndash x8 Burner switch-off threshold 04 1 ndash 20 microA 1 microA

Burner start-up attempts 10 1 ndash 4 1

Burner restart 12 0 1 0

Safety time during operation for V1 and V2 tSB 14 1 2 s 1 s

Flame simulation check in start-up positionstandby 15 0 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 ndash 250 s 0 s

Burner safety time on start-up tSA 22 3 5 10 s

Burner flame proving period tFS 23 0 ndash 25 s 0 s

Switchable gas valve V2 (only on PFUL) 26 0 1 0

Air valve control 30 0 1 2 0

Air valve can be activated externally on start-up 31 0 1 0

Air valve closedcan be activated in the event of malfunction 32 0 1 1

High temperature operation 33 2 3

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 2: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

2

t = To be continued

ContentsBurner control unit PFU 760 1Contents 21 Application 411 Examples of application 6

111 Staged OnOff burner control 6112 Staged HighLow burner control 7113 Two-stage-controlled burner 8114 Modulating-controlled burner 9116 PFU for PROFIBUS-DP with PFA 700 10115 PFU 760D High temperature equipment 10

2 Certification 113 Function 1231 Connection diagram 12311 PFU 760 12312 PFU 760K1 13313 PFU 760K2 14

32 PFU 760 program sequence 1533 Program status and fault messages 17

4 Parameters 1841 Scanning the parameters 1942 Flame control 20421 Burner flame signal 20422 Program status when the most recent fault occurred 20423 Switch-off threshold of the flame amplifier 20424 High temperature operation with PFUD 21425 UVS check 24

43 Behaviour in start-up positionstandby 25431 Flame simulation check in start-up positionstandby 25432 Minimum burner pause time tBP 26

44 Behaviour during start-up 27441 Safety time on start-up tSA 27442 Flame proving period tFS 27443 Minimum combustion time tB 27444 Burner start-up attempts 28

45 Behaviour during operation 29

451 Safety time during operation tSB for V1 and V2 29452 Fault lock-out or restart 29

46 Switchable gas valve V2 on PFUL 3147 Air valve control PFUL 32471 Purge 32472 Cooling in start-up positionstandby 32473 Burner start 32474 Air valve opens in the case of external activation (not during start-up) 33475 Air valve opens in the case of external activation (even during start-up) 34476 Air valve opens with valve V1 35477 Air valve opens with valve V2 36478 Low fire over run time tKN after a controlled shut-down 37479 Behaviour of the air valve in the event of a fault lock-out 38

48 Manual operation 39481 Manual mode limited to 5 minutes 39

49 Password 39410 Multi-flame control 40

5 Selection 4151 Safety time 41511 Calculating the safety time tSA 41

52 Selection table 4253 Type code 42

6 Project planning information 4361 Cable selection 43611 Ignition cable 43612 Ionization cable 43613 UV cable 43

62 Ignition electrode 43621 Electrode gap 43622 Star electrodes 43

63 Minimum combustion time 4464 Safety interlocks (Limits) 4465 Emergency stop 44

PFU 760 middot Edition 0511

3

t = To be continued

651 In the event of fire or electric shock 44652 Via the safety interlocks (limits) 44

66 Reset 45661 Parallel reset 45662 Permanent remote reset 45663 Automatic remote reset (PLC) 45664 Burner start 45665 Restart and start-up attempts 45

67 Fault signalling 4668 Protecting the burner from overload 4669 Installation 46610 Wiring 46

6101 UVS sensor wiring 46611 PFU switched off 46612 Furnace control 47613 Note on EC type-examination 47614 Mains switch 47615 Changing parameters 47

7 Flame control 4871 With ionization sensor 4872 With UV sensor 4873 Via the temperature in high temperature equipment 48

8 Accessories 4981 High-voltage cable 4982 BCSoft 4983 Stickers for labelling 4984 ldquoChanged parametersrdquo stickers 4985 Radio interference suppressed electrode adapters 5086 Socket connectors 5087 Module subracks 5088 Power supply PFP 700 5189 Relay module PFR 704 52810 Flame detector PFF 704 53811 Field bus interface PFA 700 54

812 Impulse system MPT 700 559 Technical data 5691 Safety-specific characteristic values 5892 Operating controls 59

10 Maintenance cycles 6011 Legend 6112 Glossary 62121 Waiting time tW 62122 Safety time on start-up tSA 62123 Ignition time tZ 62124 Flame simulationFlame simulation delay time tLV 62125 Safety time during operation tSB 62126 Flame signal 63127 Fault lock-out 63128 Safety interlocks (Limits) 63129 Pilot gas valve V1 631210 Main gas valve V2 631211 Continuous operation 631212 Air valve 631213 Diagnostic coverage DC 641214 Mode of operation 641215 Safe failure fraction SFF 641216 Probability of dangerous failure PFHD 641217 Mean time to dangerous failure MTTFd 64

Feedback 65Contact 65

PFU 760 middot Edition 0511

4

1 ApplicationThe burner control units PFU 760 control ignite and moni-tor gas burners for intermittent or continuous operation As a result of their fully electronic design they react quickly to various process requirements and are therefore also suitable for frequent cycling operationThe PFU 760 can be used for directly ignited industrial burners The burners may be modulating or stage-controlledOn industrial furnaces the PFU 760 reduces the load on the central furnace control by taking over tasks that only relate to the burner for example it ensures that the burner always ignites in a safe condition after it has been restartedThe burner control unit is used for burners with mechanical combustion air supply where the fan is controlled by a separate logic and for atmospheric burners

The air valve control on the burner control unit PFU 760L assists the furnace control for cooling purging and output control tasksThe program status the unit parameters and the level of the flame signal can be read directly from the unit The burner can be controlled manually for commissioning and diagnostic purposesIf the local requirements on the burner control unit change the PC software BCSoft can be adjusted to the unit parameters of the application by using the optical interfaceThe service personnel is supported by a convenient visualiza-tion system of the input and output signals and the error historyTo reduce the installation and wiring costs Elster Kromschroumlder offers the field bus interface PFA 700 to transfer the control signals and feedbacks via PROFIBUS-DP

Module subrack BGT for instance serves to accom-modate several function units It is provided with a backplane with screw terminals for simple reliable wiring

PFU 760 middot Edition 0511

5Application

Bogie hearth forging furnace in the metallurgical industry

Intermittent shuttle kiln in the ceramics industry

Walking beam furnace with overhead firing

PFU 760 middot Edition 0511

6

VRR

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

UV

ϑ1

microC

Application

1 1 Examples of application1 1 1 Staged OnOff burner controlThe burner can be started with reduced capacityA UV sensor monitors the flame signal from the burner UV sensor UVD 1 is used for continuous operation UV sensor UVS for intermittent operation

PFU 760 middot Edition 0511

7

VRR

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

GIKB

VASN

ϑ1

microC

Application gt Examples of application

1 1 2 Staged HighLow burner controlThe burner starts at low-fire rate When the operating state is reached the PFU 760L advises the control unit The PLC can now pulse the air valve in order to control the burner output

PFU 760 middot Edition 0511

8

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

Application gt Examples of application

1 1 3 Two-stage-controlled burnerControl ONOFF with ignition via bypassThe burner starts at low-fire rate When the operating state is reached the PFU 760L issues the Enable signal for the maximum burner output

PFU 760 middot Edition 0511

9

VAG

PFU 760

SPSPLCAPI

DI

L1 N PE

10e

2e 4e

2c 4c

26a

P

26e 10c

DI

BVA+IC 20

M

mA

TZI

16c

22a

BIO BIC

28c

ϑ1

microC

Application gt Examples of application

1 1 4 Modulating-controlled burnerControl continuousThe external control system moves the butterfly valve for air BVA to ignition position The burner starts at low-fire rate and a controller in the PLC controls the burner output via the butterfly valve for air BVA after the operating state has been signalled

PFU 760 middot Edition 0511

10

STW

L1

gt750 degC

microC

PFU 760D

18a

DI

22a

microC

PFU 760D

18a

DI

22a

SPSPLCAPI

DI

L1 N PE P

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

PROFIBUS-DP

1 1 5 PFU 760 D High temperature equipmentIndirect flame control using the tempera-ture During the start-up process as long as the wall temperature is below auto ignition temperature the flame must be controlled by conventional methods When the working temperature has exceeded 750degC the safety tempera-ture monitor (STW) takes over the indirect flame control

1 1 6 PFU for PROFIBUS-DP with PFA 700The bus system transfers the control sig-nals for starting resetting and for con-trolling the air valve from the control sys-tem (PLC) to the PFU 760 via the PFA 700 In the opposite direction it sends infor-mation on the operating status Control signals that are relevant for safety such as the safety interlocks and digital input are transferred independently of the bus communication by separate cables

Application gt Examples of application

PFU 760 middot Edition 0511

11

2 CertificationCertified pursuant to SIL

For systems up to SIL 3 pursuant to EN 61508Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

EC type-tested and certified

pursuant tondash Gas Appliances Directive (2009142EC) in conjunction

with EN 2982004-01

Meets the requirements of thendash Low Voltage Directive (200695EC)ndash EMC Directive (2004108EC)

PFU T is FM approved

Factory Mutual Research Class 1997Suitable for applications pursuant to NFPA 86 wwwfmglobalcom Products and Services Product Cer-tification Approval Guide

AGA approved

AGA

Australian Gas Association Approval No 5597 wwwagaasnauproduct_directory

PFU 760 middot Edition 0511

12

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)( 3 Function

3 1 Connection diagramFor cable selection and wiring see page 43 (Project planning information)

3 1 1 PFU 760For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

13

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

PFU 760K1 PFU 760LK1)(

F2

F1

Function gt Connection diagram

3 1 2 PFU 760 K1As a replacement unit for burner control unit PFSPFD 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

14

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760K2 PFU 760LK2)(

Function gt Connection diagram

3 1 3 PFU 760 K2As a replacement unit for burner control unit PFU 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

15

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

Function

3 2 PFU 760 program sequenceNormal start-upIf an ldquooldrdquo fault is still being signalled after switching on it will be necessary to reset this firstWhen the safety interlocks are closed the PFU reverts to start-up position and conducts a self-test If it does not deter-mine a malfunction of the internal elec-tronic circuitry or of the flame sensor the burner can be startedThe flame simulation check is conducted during start-up position or after applying the start-up signal (ϑ) depending on parameter 15After the min burner pause time tBP has elapsed the PFU opens valve V1 and ignites the burner The ignition time tZ is constantIf a flame is detected during the safety time tSA the flame proving period tFS starts after this safety time has elapsed Valve V2 opens and the operation signalling contact between terminals 2c and 4c closes This completes start-up An adjustable min combustion time tB ensures that the burner burns for a defined period even if the start-up signal (ϑ) is switched off beforehand

PFU 760Lwith air valve control features the following additional functions

In start-up position the air valve can be opened for cooling A

Using parameter 31 it can be determined whether the air valve can be activated externally during start-up

The air valve can be set to open together with V1 (display A2 ) via parameter 30

PFU 760 middot Edition 0511

16 Function gt PFU 760 program sequence

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

The air valve can also be set to open with V2 or to be activated externally (display A4 ) via parameter 30

The burner can also be started manually with the aid of the button on the PFU Voltage must be applied continuously to terminals 10e 26e and 30a in order for this to occurThe PFU can also be operated in Manual mode for start-up

Start-up without flame signal If no flame is detected during the safety time tSA either a fault lock-out occurs or up to three further start-up attempts occur The required functions and if applicable the number of start-up attempts must be specified when or-dering (Parameter 10 ldquoBurner start-up attemptsrdquo)

Behaviour in the event of flame failure during operationIf the flame fails during operation either an immediate fault lock-out occurs or a restart occurs This procedure can be set via the optical interface (parameter 12 ldquoBurner restartrdquo)

PFU 760 middot Edition 0511

17Function

Program status DISPLAY Fault message (blinking)Start-up positionstandby 00

Cooling A0

Waiting timePause time 1 Flame simulation pilot burnerBurner safety time on start-up 2 Burner start-up without flame signalBurner flame proving period 3 Flame failure during burner flame proving periodBurner operation 4 Flame failure during operation pilot burnerPurge P0 Air valve A

High temperature operation

10 Faulty remote reset

32 Supply voltage too low

33 Faulty parameterization

35 Short-circuit on a valve output

36 Short-circuit on ignition or valve output

51 Safety interlock failure

52 Permanent reset

53 Time between two start-ups is too short In Manual mode two dots will blink on the display in program status 01 ndash 04 Optionally available

3 3 Program status and fault messagesDuring operation the 7-segment display shows the program status In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault The burner control unit can be reset using the Reset button or the remote reset

PFU 760 middot Edition 0511

18

4 ParametersDescription Parameter Value range Factory default

setting Adjustable

Burner flame signal 01 0 ndash 30 μAProgram status when the most recent fault occurred 03 x0 ndash x8 Burner switch-off threshold 04 1 ndash 20 microA 1 microA

Burner start-up attempts 10 1 ndash 4 1

Burner restart 12 0 1 0

Safety time during operation for V1 and V2 tSB 14 1 2 s 1 s

Flame simulation check in start-up positionstandby 15 0 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 ndash 250 s 0 s

Burner safety time on start-up tSA 22 3 5 10 s

Burner flame proving period tFS 23 0 ndash 25 s 0 s

Switchable gas valve V2 (only on PFUL) 26 0 1 0

Air valve control 30 0 1 2 0

Air valve can be activated externally on start-up 31 0 1 0

Air valve closedcan be activated in the event of malfunction 32 0 1 1

High temperature operation 33 2 3

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 3: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

3

t = To be continued

651 In the event of fire or electric shock 44652 Via the safety interlocks (limits) 44

66 Reset 45661 Parallel reset 45662 Permanent remote reset 45663 Automatic remote reset (PLC) 45664 Burner start 45665 Restart and start-up attempts 45

67 Fault signalling 4668 Protecting the burner from overload 4669 Installation 46610 Wiring 46

6101 UVS sensor wiring 46611 PFU switched off 46612 Furnace control 47613 Note on EC type-examination 47614 Mains switch 47615 Changing parameters 47

7 Flame control 4871 With ionization sensor 4872 With UV sensor 4873 Via the temperature in high temperature equipment 48

8 Accessories 4981 High-voltage cable 4982 BCSoft 4983 Stickers for labelling 4984 ldquoChanged parametersrdquo stickers 4985 Radio interference suppressed electrode adapters 5086 Socket connectors 5087 Module subracks 5088 Power supply PFP 700 5189 Relay module PFR 704 52810 Flame detector PFF 704 53811 Field bus interface PFA 700 54

812 Impulse system MPT 700 559 Technical data 5691 Safety-specific characteristic values 5892 Operating controls 59

10 Maintenance cycles 6011 Legend 6112 Glossary 62121 Waiting time tW 62122 Safety time on start-up tSA 62123 Ignition time tZ 62124 Flame simulationFlame simulation delay time tLV 62125 Safety time during operation tSB 62126 Flame signal 63127 Fault lock-out 63128 Safety interlocks (Limits) 63129 Pilot gas valve V1 631210 Main gas valve V2 631211 Continuous operation 631212 Air valve 631213 Diagnostic coverage DC 641214 Mode of operation 641215 Safe failure fraction SFF 641216 Probability of dangerous failure PFHD 641217 Mean time to dangerous failure MTTFd 64

Feedback 65Contact 65

PFU 760 middot Edition 0511

4

1 ApplicationThe burner control units PFU 760 control ignite and moni-tor gas burners for intermittent or continuous operation As a result of their fully electronic design they react quickly to various process requirements and are therefore also suitable for frequent cycling operationThe PFU 760 can be used for directly ignited industrial burners The burners may be modulating or stage-controlledOn industrial furnaces the PFU 760 reduces the load on the central furnace control by taking over tasks that only relate to the burner for example it ensures that the burner always ignites in a safe condition after it has been restartedThe burner control unit is used for burners with mechanical combustion air supply where the fan is controlled by a separate logic and for atmospheric burners

The air valve control on the burner control unit PFU 760L assists the furnace control for cooling purging and output control tasksThe program status the unit parameters and the level of the flame signal can be read directly from the unit The burner can be controlled manually for commissioning and diagnostic purposesIf the local requirements on the burner control unit change the PC software BCSoft can be adjusted to the unit parameters of the application by using the optical interfaceThe service personnel is supported by a convenient visualiza-tion system of the input and output signals and the error historyTo reduce the installation and wiring costs Elster Kromschroumlder offers the field bus interface PFA 700 to transfer the control signals and feedbacks via PROFIBUS-DP

Module subrack BGT for instance serves to accom-modate several function units It is provided with a backplane with screw terminals for simple reliable wiring

PFU 760 middot Edition 0511

5Application

Bogie hearth forging furnace in the metallurgical industry

Intermittent shuttle kiln in the ceramics industry

Walking beam furnace with overhead firing

PFU 760 middot Edition 0511

6

VRR

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

UV

ϑ1

microC

Application

1 1 Examples of application1 1 1 Staged OnOff burner controlThe burner can be started with reduced capacityA UV sensor monitors the flame signal from the burner UV sensor UVD 1 is used for continuous operation UV sensor UVS for intermittent operation

PFU 760 middot Edition 0511

7

VRR

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

GIKB

VASN

ϑ1

microC

Application gt Examples of application

1 1 2 Staged HighLow burner controlThe burner starts at low-fire rate When the operating state is reached the PFU 760L advises the control unit The PLC can now pulse the air valve in order to control the burner output

PFU 760 middot Edition 0511

8

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

Application gt Examples of application

1 1 3 Two-stage-controlled burnerControl ONOFF with ignition via bypassThe burner starts at low-fire rate When the operating state is reached the PFU 760L issues the Enable signal for the maximum burner output

PFU 760 middot Edition 0511

9

VAG

PFU 760

SPSPLCAPI

DI

L1 N PE

10e

2e 4e

2c 4c

26a

P

26e 10c

DI

BVA+IC 20

M

mA

TZI

16c

22a

BIO BIC

28c

ϑ1

microC

Application gt Examples of application

1 1 4 Modulating-controlled burnerControl continuousThe external control system moves the butterfly valve for air BVA to ignition position The burner starts at low-fire rate and a controller in the PLC controls the burner output via the butterfly valve for air BVA after the operating state has been signalled

PFU 760 middot Edition 0511

10

STW

L1

gt750 degC

microC

PFU 760D

18a

DI

22a

microC

PFU 760D

18a

DI

22a

SPSPLCAPI

DI

L1 N PE P

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

PROFIBUS-DP

1 1 5 PFU 760 D High temperature equipmentIndirect flame control using the tempera-ture During the start-up process as long as the wall temperature is below auto ignition temperature the flame must be controlled by conventional methods When the working temperature has exceeded 750degC the safety tempera-ture monitor (STW) takes over the indirect flame control

1 1 6 PFU for PROFIBUS-DP with PFA 700The bus system transfers the control sig-nals for starting resetting and for con-trolling the air valve from the control sys-tem (PLC) to the PFU 760 via the PFA 700 In the opposite direction it sends infor-mation on the operating status Control signals that are relevant for safety such as the safety interlocks and digital input are transferred independently of the bus communication by separate cables

Application gt Examples of application

PFU 760 middot Edition 0511

11

2 CertificationCertified pursuant to SIL

For systems up to SIL 3 pursuant to EN 61508Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

EC type-tested and certified

pursuant tondash Gas Appliances Directive (2009142EC) in conjunction

with EN 2982004-01

Meets the requirements of thendash Low Voltage Directive (200695EC)ndash EMC Directive (2004108EC)

PFU T is FM approved

Factory Mutual Research Class 1997Suitable for applications pursuant to NFPA 86 wwwfmglobalcom Products and Services Product Cer-tification Approval Guide

AGA approved

AGA

Australian Gas Association Approval No 5597 wwwagaasnauproduct_directory

PFU 760 middot Edition 0511

12

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)( 3 Function

3 1 Connection diagramFor cable selection and wiring see page 43 (Project planning information)

3 1 1 PFU 760For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

13

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

PFU 760K1 PFU 760LK1)(

F2

F1

Function gt Connection diagram

3 1 2 PFU 760 K1As a replacement unit for burner control unit PFSPFD 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

14

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760K2 PFU 760LK2)(

Function gt Connection diagram

3 1 3 PFU 760 K2As a replacement unit for burner control unit PFU 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

15

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

Function

3 2 PFU 760 program sequenceNormal start-upIf an ldquooldrdquo fault is still being signalled after switching on it will be necessary to reset this firstWhen the safety interlocks are closed the PFU reverts to start-up position and conducts a self-test If it does not deter-mine a malfunction of the internal elec-tronic circuitry or of the flame sensor the burner can be startedThe flame simulation check is conducted during start-up position or after applying the start-up signal (ϑ) depending on parameter 15After the min burner pause time tBP has elapsed the PFU opens valve V1 and ignites the burner The ignition time tZ is constantIf a flame is detected during the safety time tSA the flame proving period tFS starts after this safety time has elapsed Valve V2 opens and the operation signalling contact between terminals 2c and 4c closes This completes start-up An adjustable min combustion time tB ensures that the burner burns for a defined period even if the start-up signal (ϑ) is switched off beforehand

PFU 760Lwith air valve control features the following additional functions

In start-up position the air valve can be opened for cooling A

Using parameter 31 it can be determined whether the air valve can be activated externally during start-up

The air valve can be set to open together with V1 (display A2 ) via parameter 30

PFU 760 middot Edition 0511

16 Function gt PFU 760 program sequence

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

The air valve can also be set to open with V2 or to be activated externally (display A4 ) via parameter 30

The burner can also be started manually with the aid of the button on the PFU Voltage must be applied continuously to terminals 10e 26e and 30a in order for this to occurThe PFU can also be operated in Manual mode for start-up

Start-up without flame signal If no flame is detected during the safety time tSA either a fault lock-out occurs or up to three further start-up attempts occur The required functions and if applicable the number of start-up attempts must be specified when or-dering (Parameter 10 ldquoBurner start-up attemptsrdquo)

Behaviour in the event of flame failure during operationIf the flame fails during operation either an immediate fault lock-out occurs or a restart occurs This procedure can be set via the optical interface (parameter 12 ldquoBurner restartrdquo)

PFU 760 middot Edition 0511

17Function

Program status DISPLAY Fault message (blinking)Start-up positionstandby 00

Cooling A0

Waiting timePause time 1 Flame simulation pilot burnerBurner safety time on start-up 2 Burner start-up without flame signalBurner flame proving period 3 Flame failure during burner flame proving periodBurner operation 4 Flame failure during operation pilot burnerPurge P0 Air valve A

High temperature operation

10 Faulty remote reset

32 Supply voltage too low

33 Faulty parameterization

35 Short-circuit on a valve output

36 Short-circuit on ignition or valve output

51 Safety interlock failure

52 Permanent reset

53 Time between two start-ups is too short In Manual mode two dots will blink on the display in program status 01 ndash 04 Optionally available

3 3 Program status and fault messagesDuring operation the 7-segment display shows the program status In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault The burner control unit can be reset using the Reset button or the remote reset

PFU 760 middot Edition 0511

18

4 ParametersDescription Parameter Value range Factory default

setting Adjustable

Burner flame signal 01 0 ndash 30 μAProgram status when the most recent fault occurred 03 x0 ndash x8 Burner switch-off threshold 04 1 ndash 20 microA 1 microA

Burner start-up attempts 10 1 ndash 4 1

Burner restart 12 0 1 0

Safety time during operation for V1 and V2 tSB 14 1 2 s 1 s

Flame simulation check in start-up positionstandby 15 0 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 ndash 250 s 0 s

Burner safety time on start-up tSA 22 3 5 10 s

Burner flame proving period tFS 23 0 ndash 25 s 0 s

Switchable gas valve V2 (only on PFUL) 26 0 1 0

Air valve control 30 0 1 2 0

Air valve can be activated externally on start-up 31 0 1 0

Air valve closedcan be activated in the event of malfunction 32 0 1 1

High temperature operation 33 2 3

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 4: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

4

1 ApplicationThe burner control units PFU 760 control ignite and moni-tor gas burners for intermittent or continuous operation As a result of their fully electronic design they react quickly to various process requirements and are therefore also suitable for frequent cycling operationThe PFU 760 can be used for directly ignited industrial burners The burners may be modulating or stage-controlledOn industrial furnaces the PFU 760 reduces the load on the central furnace control by taking over tasks that only relate to the burner for example it ensures that the burner always ignites in a safe condition after it has been restartedThe burner control unit is used for burners with mechanical combustion air supply where the fan is controlled by a separate logic and for atmospheric burners

The air valve control on the burner control unit PFU 760L assists the furnace control for cooling purging and output control tasksThe program status the unit parameters and the level of the flame signal can be read directly from the unit The burner can be controlled manually for commissioning and diagnostic purposesIf the local requirements on the burner control unit change the PC software BCSoft can be adjusted to the unit parameters of the application by using the optical interfaceThe service personnel is supported by a convenient visualiza-tion system of the input and output signals and the error historyTo reduce the installation and wiring costs Elster Kromschroumlder offers the field bus interface PFA 700 to transfer the control signals and feedbacks via PROFIBUS-DP

Module subrack BGT for instance serves to accom-modate several function units It is provided with a backplane with screw terminals for simple reliable wiring

PFU 760 middot Edition 0511

5Application

Bogie hearth forging furnace in the metallurgical industry

Intermittent shuttle kiln in the ceramics industry

Walking beam furnace with overhead firing

PFU 760 middot Edition 0511

6

VRR

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

UV

ϑ1

microC

Application

1 1 Examples of application1 1 1 Staged OnOff burner controlThe burner can be started with reduced capacityA UV sensor monitors the flame signal from the burner UV sensor UVD 1 is used for continuous operation UV sensor UVS for intermittent operation

PFU 760 middot Edition 0511

7

VRR

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

GIKB

VASN

ϑ1

microC

Application gt Examples of application

1 1 2 Staged HighLow burner controlThe burner starts at low-fire rate When the operating state is reached the PFU 760L advises the control unit The PLC can now pulse the air valve in order to control the burner output

PFU 760 middot Edition 0511

8

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

Application gt Examples of application

1 1 3 Two-stage-controlled burnerControl ONOFF with ignition via bypassThe burner starts at low-fire rate When the operating state is reached the PFU 760L issues the Enable signal for the maximum burner output

PFU 760 middot Edition 0511

9

VAG

PFU 760

SPSPLCAPI

DI

L1 N PE

10e

2e 4e

2c 4c

26a

P

26e 10c

DI

BVA+IC 20

M

mA

TZI

16c

22a

BIO BIC

28c

ϑ1

microC

Application gt Examples of application

1 1 4 Modulating-controlled burnerControl continuousThe external control system moves the butterfly valve for air BVA to ignition position The burner starts at low-fire rate and a controller in the PLC controls the burner output via the butterfly valve for air BVA after the operating state has been signalled

PFU 760 middot Edition 0511

10

STW

L1

gt750 degC

microC

PFU 760D

18a

DI

22a

microC

PFU 760D

18a

DI

22a

SPSPLCAPI

DI

L1 N PE P

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

PROFIBUS-DP

1 1 5 PFU 760 D High temperature equipmentIndirect flame control using the tempera-ture During the start-up process as long as the wall temperature is below auto ignition temperature the flame must be controlled by conventional methods When the working temperature has exceeded 750degC the safety tempera-ture monitor (STW) takes over the indirect flame control

1 1 6 PFU for PROFIBUS-DP with PFA 700The bus system transfers the control sig-nals for starting resetting and for con-trolling the air valve from the control sys-tem (PLC) to the PFU 760 via the PFA 700 In the opposite direction it sends infor-mation on the operating status Control signals that are relevant for safety such as the safety interlocks and digital input are transferred independently of the bus communication by separate cables

Application gt Examples of application

PFU 760 middot Edition 0511

11

2 CertificationCertified pursuant to SIL

For systems up to SIL 3 pursuant to EN 61508Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

EC type-tested and certified

pursuant tondash Gas Appliances Directive (2009142EC) in conjunction

with EN 2982004-01

Meets the requirements of thendash Low Voltage Directive (200695EC)ndash EMC Directive (2004108EC)

PFU T is FM approved

Factory Mutual Research Class 1997Suitable for applications pursuant to NFPA 86 wwwfmglobalcom Products and Services Product Cer-tification Approval Guide

AGA approved

AGA

Australian Gas Association Approval No 5597 wwwagaasnauproduct_directory

PFU 760 middot Edition 0511

12

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)( 3 Function

3 1 Connection diagramFor cable selection and wiring see page 43 (Project planning information)

3 1 1 PFU 760For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

13

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

PFU 760K1 PFU 760LK1)(

F2

F1

Function gt Connection diagram

3 1 2 PFU 760 K1As a replacement unit for burner control unit PFSPFD 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

14

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760K2 PFU 760LK2)(

Function gt Connection diagram

3 1 3 PFU 760 K2As a replacement unit for burner control unit PFU 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

15

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

Function

3 2 PFU 760 program sequenceNormal start-upIf an ldquooldrdquo fault is still being signalled after switching on it will be necessary to reset this firstWhen the safety interlocks are closed the PFU reverts to start-up position and conducts a self-test If it does not deter-mine a malfunction of the internal elec-tronic circuitry or of the flame sensor the burner can be startedThe flame simulation check is conducted during start-up position or after applying the start-up signal (ϑ) depending on parameter 15After the min burner pause time tBP has elapsed the PFU opens valve V1 and ignites the burner The ignition time tZ is constantIf a flame is detected during the safety time tSA the flame proving period tFS starts after this safety time has elapsed Valve V2 opens and the operation signalling contact between terminals 2c and 4c closes This completes start-up An adjustable min combustion time tB ensures that the burner burns for a defined period even if the start-up signal (ϑ) is switched off beforehand

PFU 760Lwith air valve control features the following additional functions

In start-up position the air valve can be opened for cooling A

Using parameter 31 it can be determined whether the air valve can be activated externally during start-up

The air valve can be set to open together with V1 (display A2 ) via parameter 30

PFU 760 middot Edition 0511

16 Function gt PFU 760 program sequence

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

The air valve can also be set to open with V2 or to be activated externally (display A4 ) via parameter 30

The burner can also be started manually with the aid of the button on the PFU Voltage must be applied continuously to terminals 10e 26e and 30a in order for this to occurThe PFU can also be operated in Manual mode for start-up

Start-up without flame signal If no flame is detected during the safety time tSA either a fault lock-out occurs or up to three further start-up attempts occur The required functions and if applicable the number of start-up attempts must be specified when or-dering (Parameter 10 ldquoBurner start-up attemptsrdquo)

Behaviour in the event of flame failure during operationIf the flame fails during operation either an immediate fault lock-out occurs or a restart occurs This procedure can be set via the optical interface (parameter 12 ldquoBurner restartrdquo)

PFU 760 middot Edition 0511

17Function

Program status DISPLAY Fault message (blinking)Start-up positionstandby 00

Cooling A0

Waiting timePause time 1 Flame simulation pilot burnerBurner safety time on start-up 2 Burner start-up without flame signalBurner flame proving period 3 Flame failure during burner flame proving periodBurner operation 4 Flame failure during operation pilot burnerPurge P0 Air valve A

High temperature operation

10 Faulty remote reset

32 Supply voltage too low

33 Faulty parameterization

35 Short-circuit on a valve output

36 Short-circuit on ignition or valve output

51 Safety interlock failure

52 Permanent reset

53 Time between two start-ups is too short In Manual mode two dots will blink on the display in program status 01 ndash 04 Optionally available

3 3 Program status and fault messagesDuring operation the 7-segment display shows the program status In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault The burner control unit can be reset using the Reset button or the remote reset

PFU 760 middot Edition 0511

18

4 ParametersDescription Parameter Value range Factory default

setting Adjustable

Burner flame signal 01 0 ndash 30 μAProgram status when the most recent fault occurred 03 x0 ndash x8 Burner switch-off threshold 04 1 ndash 20 microA 1 microA

Burner start-up attempts 10 1 ndash 4 1

Burner restart 12 0 1 0

Safety time during operation for V1 and V2 tSB 14 1 2 s 1 s

Flame simulation check in start-up positionstandby 15 0 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 ndash 250 s 0 s

Burner safety time on start-up tSA 22 3 5 10 s

Burner flame proving period tFS 23 0 ndash 25 s 0 s

Switchable gas valve V2 (only on PFUL) 26 0 1 0

Air valve control 30 0 1 2 0

Air valve can be activated externally on start-up 31 0 1 0

Air valve closedcan be activated in the event of malfunction 32 0 1 1

High temperature operation 33 2 3

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 5: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

5Application

Bogie hearth forging furnace in the metallurgical industry

Intermittent shuttle kiln in the ceramics industry

Walking beam furnace with overhead firing

PFU 760 middot Edition 0511

6

VRR

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

UV

ϑ1

microC

Application

1 1 Examples of application1 1 1 Staged OnOff burner controlThe burner can be started with reduced capacityA UV sensor monitors the flame signal from the burner UV sensor UVD 1 is used for continuous operation UV sensor UVS for intermittent operation

PFU 760 middot Edition 0511

7

VRR

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

GIKB

VASN

ϑ1

microC

Application gt Examples of application

1 1 2 Staged HighLow burner controlThe burner starts at low-fire rate When the operating state is reached the PFU 760L advises the control unit The PLC can now pulse the air valve in order to control the burner output

PFU 760 middot Edition 0511

8

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

Application gt Examples of application

1 1 3 Two-stage-controlled burnerControl ONOFF with ignition via bypassThe burner starts at low-fire rate When the operating state is reached the PFU 760L issues the Enable signal for the maximum burner output

PFU 760 middot Edition 0511

9

VAG

PFU 760

SPSPLCAPI

DI

L1 N PE

10e

2e 4e

2c 4c

26a

P

26e 10c

DI

BVA+IC 20

M

mA

TZI

16c

22a

BIO BIC

28c

ϑ1

microC

Application gt Examples of application

1 1 4 Modulating-controlled burnerControl continuousThe external control system moves the butterfly valve for air BVA to ignition position The burner starts at low-fire rate and a controller in the PLC controls the burner output via the butterfly valve for air BVA after the operating state has been signalled

PFU 760 middot Edition 0511

10

STW

L1

gt750 degC

microC

PFU 760D

18a

DI

22a

microC

PFU 760D

18a

DI

22a

SPSPLCAPI

DI

L1 N PE P

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

PROFIBUS-DP

1 1 5 PFU 760 D High temperature equipmentIndirect flame control using the tempera-ture During the start-up process as long as the wall temperature is below auto ignition temperature the flame must be controlled by conventional methods When the working temperature has exceeded 750degC the safety tempera-ture monitor (STW) takes over the indirect flame control

1 1 6 PFU for PROFIBUS-DP with PFA 700The bus system transfers the control sig-nals for starting resetting and for con-trolling the air valve from the control sys-tem (PLC) to the PFU 760 via the PFA 700 In the opposite direction it sends infor-mation on the operating status Control signals that are relevant for safety such as the safety interlocks and digital input are transferred independently of the bus communication by separate cables

Application gt Examples of application

PFU 760 middot Edition 0511

11

2 CertificationCertified pursuant to SIL

For systems up to SIL 3 pursuant to EN 61508Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

EC type-tested and certified

pursuant tondash Gas Appliances Directive (2009142EC) in conjunction

with EN 2982004-01

Meets the requirements of thendash Low Voltage Directive (200695EC)ndash EMC Directive (2004108EC)

PFU T is FM approved

Factory Mutual Research Class 1997Suitable for applications pursuant to NFPA 86 wwwfmglobalcom Products and Services Product Cer-tification Approval Guide

AGA approved

AGA

Australian Gas Association Approval No 5597 wwwagaasnauproduct_directory

PFU 760 middot Edition 0511

12

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)( 3 Function

3 1 Connection diagramFor cable selection and wiring see page 43 (Project planning information)

3 1 1 PFU 760For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

13

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

PFU 760K1 PFU 760LK1)(

F2

F1

Function gt Connection diagram

3 1 2 PFU 760 K1As a replacement unit for burner control unit PFSPFD 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

14

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760K2 PFU 760LK2)(

Function gt Connection diagram

3 1 3 PFU 760 K2As a replacement unit for burner control unit PFU 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

15

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

Function

3 2 PFU 760 program sequenceNormal start-upIf an ldquooldrdquo fault is still being signalled after switching on it will be necessary to reset this firstWhen the safety interlocks are closed the PFU reverts to start-up position and conducts a self-test If it does not deter-mine a malfunction of the internal elec-tronic circuitry or of the flame sensor the burner can be startedThe flame simulation check is conducted during start-up position or after applying the start-up signal (ϑ) depending on parameter 15After the min burner pause time tBP has elapsed the PFU opens valve V1 and ignites the burner The ignition time tZ is constantIf a flame is detected during the safety time tSA the flame proving period tFS starts after this safety time has elapsed Valve V2 opens and the operation signalling contact between terminals 2c and 4c closes This completes start-up An adjustable min combustion time tB ensures that the burner burns for a defined period even if the start-up signal (ϑ) is switched off beforehand

PFU 760Lwith air valve control features the following additional functions

In start-up position the air valve can be opened for cooling A

Using parameter 31 it can be determined whether the air valve can be activated externally during start-up

The air valve can be set to open together with V1 (display A2 ) via parameter 30

PFU 760 middot Edition 0511

16 Function gt PFU 760 program sequence

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

The air valve can also be set to open with V2 or to be activated externally (display A4 ) via parameter 30

The burner can also be started manually with the aid of the button on the PFU Voltage must be applied continuously to terminals 10e 26e and 30a in order for this to occurThe PFU can also be operated in Manual mode for start-up

Start-up without flame signal If no flame is detected during the safety time tSA either a fault lock-out occurs or up to three further start-up attempts occur The required functions and if applicable the number of start-up attempts must be specified when or-dering (Parameter 10 ldquoBurner start-up attemptsrdquo)

Behaviour in the event of flame failure during operationIf the flame fails during operation either an immediate fault lock-out occurs or a restart occurs This procedure can be set via the optical interface (parameter 12 ldquoBurner restartrdquo)

PFU 760 middot Edition 0511

17Function

Program status DISPLAY Fault message (blinking)Start-up positionstandby 00

Cooling A0

Waiting timePause time 1 Flame simulation pilot burnerBurner safety time on start-up 2 Burner start-up without flame signalBurner flame proving period 3 Flame failure during burner flame proving periodBurner operation 4 Flame failure during operation pilot burnerPurge P0 Air valve A

High temperature operation

10 Faulty remote reset

32 Supply voltage too low

33 Faulty parameterization

35 Short-circuit on a valve output

36 Short-circuit on ignition or valve output

51 Safety interlock failure

52 Permanent reset

53 Time between two start-ups is too short In Manual mode two dots will blink on the display in program status 01 ndash 04 Optionally available

3 3 Program status and fault messagesDuring operation the 7-segment display shows the program status In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault The burner control unit can be reset using the Reset button or the remote reset

PFU 760 middot Edition 0511

18

4 ParametersDescription Parameter Value range Factory default

setting Adjustable

Burner flame signal 01 0 ndash 30 μAProgram status when the most recent fault occurred 03 x0 ndash x8 Burner switch-off threshold 04 1 ndash 20 microA 1 microA

Burner start-up attempts 10 1 ndash 4 1

Burner restart 12 0 1 0

Safety time during operation for V1 and V2 tSB 14 1 2 s 1 s

Flame simulation check in start-up positionstandby 15 0 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 ndash 250 s 0 s

Burner safety time on start-up tSA 22 3 5 10 s

Burner flame proving period tFS 23 0 ndash 25 s 0 s

Switchable gas valve V2 (only on PFUL) 26 0 1 0

Air valve control 30 0 1 2 0

Air valve can be activated externally on start-up 31 0 1 0

Air valve closedcan be activated in the event of malfunction 32 0 1 1

High temperature operation 33 2 3

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 6: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

6

VRR

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

UV

ϑ1

microC

Application

1 1 Examples of application1 1 1 Staged OnOff burner controlThe burner can be started with reduced capacityA UV sensor monitors the flame signal from the burner UV sensor UVD 1 is used for continuous operation UV sensor UVS for intermittent operation

PFU 760 middot Edition 0511

7

VRR

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

GIKB

VASN

ϑ1

microC

Application gt Examples of application

1 1 2 Staged HighLow burner controlThe burner starts at low-fire rate When the operating state is reached the PFU 760L advises the control unit The PLC can now pulse the air valve in order to control the burner output

PFU 760 middot Edition 0511

8

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

Application gt Examples of application

1 1 3 Two-stage-controlled burnerControl ONOFF with ignition via bypassThe burner starts at low-fire rate When the operating state is reached the PFU 760L issues the Enable signal for the maximum burner output

PFU 760 middot Edition 0511

9

VAG

PFU 760

SPSPLCAPI

DI

L1 N PE

10e

2e 4e

2c 4c

26a

P

26e 10c

DI

BVA+IC 20

M

mA

TZI

16c

22a

BIO BIC

28c

ϑ1

microC

Application gt Examples of application

1 1 4 Modulating-controlled burnerControl continuousThe external control system moves the butterfly valve for air BVA to ignition position The burner starts at low-fire rate and a controller in the PLC controls the burner output via the butterfly valve for air BVA after the operating state has been signalled

PFU 760 middot Edition 0511

10

STW

L1

gt750 degC

microC

PFU 760D

18a

DI

22a

microC

PFU 760D

18a

DI

22a

SPSPLCAPI

DI

L1 N PE P

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

PROFIBUS-DP

1 1 5 PFU 760 D High temperature equipmentIndirect flame control using the tempera-ture During the start-up process as long as the wall temperature is below auto ignition temperature the flame must be controlled by conventional methods When the working temperature has exceeded 750degC the safety tempera-ture monitor (STW) takes over the indirect flame control

1 1 6 PFU for PROFIBUS-DP with PFA 700The bus system transfers the control sig-nals for starting resetting and for con-trolling the air valve from the control sys-tem (PLC) to the PFU 760 via the PFA 700 In the opposite direction it sends infor-mation on the operating status Control signals that are relevant for safety such as the safety interlocks and digital input are transferred independently of the bus communication by separate cables

Application gt Examples of application

PFU 760 middot Edition 0511

11

2 CertificationCertified pursuant to SIL

For systems up to SIL 3 pursuant to EN 61508Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

EC type-tested and certified

pursuant tondash Gas Appliances Directive (2009142EC) in conjunction

with EN 2982004-01

Meets the requirements of thendash Low Voltage Directive (200695EC)ndash EMC Directive (2004108EC)

PFU T is FM approved

Factory Mutual Research Class 1997Suitable for applications pursuant to NFPA 86 wwwfmglobalcom Products and Services Product Cer-tification Approval Guide

AGA approved

AGA

Australian Gas Association Approval No 5597 wwwagaasnauproduct_directory

PFU 760 middot Edition 0511

12

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)( 3 Function

3 1 Connection diagramFor cable selection and wiring see page 43 (Project planning information)

3 1 1 PFU 760For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

13

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

PFU 760K1 PFU 760LK1)(

F2

F1

Function gt Connection diagram

3 1 2 PFU 760 K1As a replacement unit for burner control unit PFSPFD 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

14

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760K2 PFU 760LK2)(

Function gt Connection diagram

3 1 3 PFU 760 K2As a replacement unit for burner control unit PFU 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

15

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

Function

3 2 PFU 760 program sequenceNormal start-upIf an ldquooldrdquo fault is still being signalled after switching on it will be necessary to reset this firstWhen the safety interlocks are closed the PFU reverts to start-up position and conducts a self-test If it does not deter-mine a malfunction of the internal elec-tronic circuitry or of the flame sensor the burner can be startedThe flame simulation check is conducted during start-up position or after applying the start-up signal (ϑ) depending on parameter 15After the min burner pause time tBP has elapsed the PFU opens valve V1 and ignites the burner The ignition time tZ is constantIf a flame is detected during the safety time tSA the flame proving period tFS starts after this safety time has elapsed Valve V2 opens and the operation signalling contact between terminals 2c and 4c closes This completes start-up An adjustable min combustion time tB ensures that the burner burns for a defined period even if the start-up signal (ϑ) is switched off beforehand

PFU 760Lwith air valve control features the following additional functions

In start-up position the air valve can be opened for cooling A

Using parameter 31 it can be determined whether the air valve can be activated externally during start-up

The air valve can be set to open together with V1 (display A2 ) via parameter 30

PFU 760 middot Edition 0511

16 Function gt PFU 760 program sequence

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

The air valve can also be set to open with V2 or to be activated externally (display A4 ) via parameter 30

The burner can also be started manually with the aid of the button on the PFU Voltage must be applied continuously to terminals 10e 26e and 30a in order for this to occurThe PFU can also be operated in Manual mode for start-up

Start-up without flame signal If no flame is detected during the safety time tSA either a fault lock-out occurs or up to three further start-up attempts occur The required functions and if applicable the number of start-up attempts must be specified when or-dering (Parameter 10 ldquoBurner start-up attemptsrdquo)

Behaviour in the event of flame failure during operationIf the flame fails during operation either an immediate fault lock-out occurs or a restart occurs This procedure can be set via the optical interface (parameter 12 ldquoBurner restartrdquo)

PFU 760 middot Edition 0511

17Function

Program status DISPLAY Fault message (blinking)Start-up positionstandby 00

Cooling A0

Waiting timePause time 1 Flame simulation pilot burnerBurner safety time on start-up 2 Burner start-up without flame signalBurner flame proving period 3 Flame failure during burner flame proving periodBurner operation 4 Flame failure during operation pilot burnerPurge P0 Air valve A

High temperature operation

10 Faulty remote reset

32 Supply voltage too low

33 Faulty parameterization

35 Short-circuit on a valve output

36 Short-circuit on ignition or valve output

51 Safety interlock failure

52 Permanent reset

53 Time between two start-ups is too short In Manual mode two dots will blink on the display in program status 01 ndash 04 Optionally available

3 3 Program status and fault messagesDuring operation the 7-segment display shows the program status In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault The burner control unit can be reset using the Reset button or the remote reset

PFU 760 middot Edition 0511

18

4 ParametersDescription Parameter Value range Factory default

setting Adjustable

Burner flame signal 01 0 ndash 30 μAProgram status when the most recent fault occurred 03 x0 ndash x8 Burner switch-off threshold 04 1 ndash 20 microA 1 microA

Burner start-up attempts 10 1 ndash 4 1

Burner restart 12 0 1 0

Safety time during operation for V1 and V2 tSB 14 1 2 s 1 s

Flame simulation check in start-up positionstandby 15 0 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 ndash 250 s 0 s

Burner safety time on start-up tSA 22 3 5 10 s

Burner flame proving period tFS 23 0 ndash 25 s 0 s

Switchable gas valve V2 (only on PFUL) 26 0 1 0

Air valve control 30 0 1 2 0

Air valve can be activated externally on start-up 31 0 1 0

Air valve closedcan be activated in the event of malfunction 32 0 1 1

High temperature operation 33 2 3

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 7: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

7

VRR

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

GIKB

VASN

ϑ1

microC

Application gt Examples of application

1 1 2 Staged HighLow burner controlThe burner starts at low-fire rate When the operating state is reached the PFU 760L advises the control unit The PLC can now pulse the air valve in order to control the burner output

PFU 760 middot Edition 0511

8

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

Application gt Examples of application

1 1 3 Two-stage-controlled burnerControl ONOFF with ignition via bypassThe burner starts at low-fire rate When the operating state is reached the PFU 760L issues the Enable signal for the maximum burner output

PFU 760 middot Edition 0511

9

VAG

PFU 760

SPSPLCAPI

DI

L1 N PE

10e

2e 4e

2c 4c

26a

P

26e 10c

DI

BVA+IC 20

M

mA

TZI

16c

22a

BIO BIC

28c

ϑ1

microC

Application gt Examples of application

1 1 4 Modulating-controlled burnerControl continuousThe external control system moves the butterfly valve for air BVA to ignition position The burner starts at low-fire rate and a controller in the PLC controls the burner output via the butterfly valve for air BVA after the operating state has been signalled

PFU 760 middot Edition 0511

10

STW

L1

gt750 degC

microC

PFU 760D

18a

DI

22a

microC

PFU 760D

18a

DI

22a

SPSPLCAPI

DI

L1 N PE P

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

PROFIBUS-DP

1 1 5 PFU 760 D High temperature equipmentIndirect flame control using the tempera-ture During the start-up process as long as the wall temperature is below auto ignition temperature the flame must be controlled by conventional methods When the working temperature has exceeded 750degC the safety tempera-ture monitor (STW) takes over the indirect flame control

1 1 6 PFU for PROFIBUS-DP with PFA 700The bus system transfers the control sig-nals for starting resetting and for con-trolling the air valve from the control sys-tem (PLC) to the PFU 760 via the PFA 700 In the opposite direction it sends infor-mation on the operating status Control signals that are relevant for safety such as the safety interlocks and digital input are transferred independently of the bus communication by separate cables

Application gt Examples of application

PFU 760 middot Edition 0511

11

2 CertificationCertified pursuant to SIL

For systems up to SIL 3 pursuant to EN 61508Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

EC type-tested and certified

pursuant tondash Gas Appliances Directive (2009142EC) in conjunction

with EN 2982004-01

Meets the requirements of thendash Low Voltage Directive (200695EC)ndash EMC Directive (2004108EC)

PFU T is FM approved

Factory Mutual Research Class 1997Suitable for applications pursuant to NFPA 86 wwwfmglobalcom Products and Services Product Cer-tification Approval Guide

AGA approved

AGA

Australian Gas Association Approval No 5597 wwwagaasnauproduct_directory

PFU 760 middot Edition 0511

12

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)( 3 Function

3 1 Connection diagramFor cable selection and wiring see page 43 (Project planning information)

3 1 1 PFU 760For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

13

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

PFU 760K1 PFU 760LK1)(

F2

F1

Function gt Connection diagram

3 1 2 PFU 760 K1As a replacement unit for burner control unit PFSPFD 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

14

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760K2 PFU 760LK2)(

Function gt Connection diagram

3 1 3 PFU 760 K2As a replacement unit for burner control unit PFU 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

15

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

Function

3 2 PFU 760 program sequenceNormal start-upIf an ldquooldrdquo fault is still being signalled after switching on it will be necessary to reset this firstWhen the safety interlocks are closed the PFU reverts to start-up position and conducts a self-test If it does not deter-mine a malfunction of the internal elec-tronic circuitry or of the flame sensor the burner can be startedThe flame simulation check is conducted during start-up position or after applying the start-up signal (ϑ) depending on parameter 15After the min burner pause time tBP has elapsed the PFU opens valve V1 and ignites the burner The ignition time tZ is constantIf a flame is detected during the safety time tSA the flame proving period tFS starts after this safety time has elapsed Valve V2 opens and the operation signalling contact between terminals 2c and 4c closes This completes start-up An adjustable min combustion time tB ensures that the burner burns for a defined period even if the start-up signal (ϑ) is switched off beforehand

PFU 760Lwith air valve control features the following additional functions

In start-up position the air valve can be opened for cooling A

Using parameter 31 it can be determined whether the air valve can be activated externally during start-up

The air valve can be set to open together with V1 (display A2 ) via parameter 30

PFU 760 middot Edition 0511

16 Function gt PFU 760 program sequence

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

The air valve can also be set to open with V2 or to be activated externally (display A4 ) via parameter 30

The burner can also be started manually with the aid of the button on the PFU Voltage must be applied continuously to terminals 10e 26e and 30a in order for this to occurThe PFU can also be operated in Manual mode for start-up

Start-up without flame signal If no flame is detected during the safety time tSA either a fault lock-out occurs or up to three further start-up attempts occur The required functions and if applicable the number of start-up attempts must be specified when or-dering (Parameter 10 ldquoBurner start-up attemptsrdquo)

Behaviour in the event of flame failure during operationIf the flame fails during operation either an immediate fault lock-out occurs or a restart occurs This procedure can be set via the optical interface (parameter 12 ldquoBurner restartrdquo)

PFU 760 middot Edition 0511

17Function

Program status DISPLAY Fault message (blinking)Start-up positionstandby 00

Cooling A0

Waiting timePause time 1 Flame simulation pilot burnerBurner safety time on start-up 2 Burner start-up without flame signalBurner flame proving period 3 Flame failure during burner flame proving periodBurner operation 4 Flame failure during operation pilot burnerPurge P0 Air valve A

High temperature operation

10 Faulty remote reset

32 Supply voltage too low

33 Faulty parameterization

35 Short-circuit on a valve output

36 Short-circuit on ignition or valve output

51 Safety interlock failure

52 Permanent reset

53 Time between two start-ups is too short In Manual mode two dots will blink on the display in program status 01 ndash 04 Optionally available

3 3 Program status and fault messagesDuring operation the 7-segment display shows the program status In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault The burner control unit can be reset using the Reset button or the remote reset

PFU 760 middot Edition 0511

18

4 ParametersDescription Parameter Value range Factory default

setting Adjustable

Burner flame signal 01 0 ndash 30 μAProgram status when the most recent fault occurred 03 x0 ndash x8 Burner switch-off threshold 04 1 ndash 20 microA 1 microA

Burner start-up attempts 10 1 ndash 4 1

Burner restart 12 0 1 0

Safety time during operation for V1 and V2 tSB 14 1 2 s 1 s

Flame simulation check in start-up positionstandby 15 0 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 ndash 250 s 0 s

Burner safety time on start-up tSA 22 3 5 10 s

Burner flame proving period tFS 23 0 ndash 25 s 0 s

Switchable gas valve V2 (only on PFUL) 26 0 1 0

Air valve control 30 0 1 2 0

Air valve can be activated externally on start-up 31 0 1 0

Air valve closedcan be activated in the event of malfunction 32 0 1 1

High temperature operation 33 2 3

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 8: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

8

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

Application gt Examples of application

1 1 3 Two-stage-controlled burnerControl ONOFF with ignition via bypassThe burner starts at low-fire rate When the operating state is reached the PFU 760L issues the Enable signal for the maximum burner output

PFU 760 middot Edition 0511

9

VAG

PFU 760

SPSPLCAPI

DI

L1 N PE

10e

2e 4e

2c 4c

26a

P

26e 10c

DI

BVA+IC 20

M

mA

TZI

16c

22a

BIO BIC

28c

ϑ1

microC

Application gt Examples of application

1 1 4 Modulating-controlled burnerControl continuousThe external control system moves the butterfly valve for air BVA to ignition position The burner starts at low-fire rate and a controller in the PLC controls the burner output via the butterfly valve for air BVA after the operating state has been signalled

PFU 760 middot Edition 0511

10

STW

L1

gt750 degC

microC

PFU 760D

18a

DI

22a

microC

PFU 760D

18a

DI

22a

SPSPLCAPI

DI

L1 N PE P

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

PROFIBUS-DP

1 1 5 PFU 760 D High temperature equipmentIndirect flame control using the tempera-ture During the start-up process as long as the wall temperature is below auto ignition temperature the flame must be controlled by conventional methods When the working temperature has exceeded 750degC the safety tempera-ture monitor (STW) takes over the indirect flame control

1 1 6 PFU for PROFIBUS-DP with PFA 700The bus system transfers the control sig-nals for starting resetting and for con-trolling the air valve from the control sys-tem (PLC) to the PFU 760 via the PFA 700 In the opposite direction it sends infor-mation on the operating status Control signals that are relevant for safety such as the safety interlocks and digital input are transferred independently of the bus communication by separate cables

Application gt Examples of application

PFU 760 middot Edition 0511

11

2 CertificationCertified pursuant to SIL

For systems up to SIL 3 pursuant to EN 61508Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

EC type-tested and certified

pursuant tondash Gas Appliances Directive (2009142EC) in conjunction

with EN 2982004-01

Meets the requirements of thendash Low Voltage Directive (200695EC)ndash EMC Directive (2004108EC)

PFU T is FM approved

Factory Mutual Research Class 1997Suitable for applications pursuant to NFPA 86 wwwfmglobalcom Products and Services Product Cer-tification Approval Guide

AGA approved

AGA

Australian Gas Association Approval No 5597 wwwagaasnauproduct_directory

PFU 760 middot Edition 0511

12

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)( 3 Function

3 1 Connection diagramFor cable selection and wiring see page 43 (Project planning information)

3 1 1 PFU 760For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

13

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

PFU 760K1 PFU 760LK1)(

F2

F1

Function gt Connection diagram

3 1 2 PFU 760 K1As a replacement unit for burner control unit PFSPFD 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

14

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760K2 PFU 760LK2)(

Function gt Connection diagram

3 1 3 PFU 760 K2As a replacement unit for burner control unit PFU 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

15

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

Function

3 2 PFU 760 program sequenceNormal start-upIf an ldquooldrdquo fault is still being signalled after switching on it will be necessary to reset this firstWhen the safety interlocks are closed the PFU reverts to start-up position and conducts a self-test If it does not deter-mine a malfunction of the internal elec-tronic circuitry or of the flame sensor the burner can be startedThe flame simulation check is conducted during start-up position or after applying the start-up signal (ϑ) depending on parameter 15After the min burner pause time tBP has elapsed the PFU opens valve V1 and ignites the burner The ignition time tZ is constantIf a flame is detected during the safety time tSA the flame proving period tFS starts after this safety time has elapsed Valve V2 opens and the operation signalling contact between terminals 2c and 4c closes This completes start-up An adjustable min combustion time tB ensures that the burner burns for a defined period even if the start-up signal (ϑ) is switched off beforehand

PFU 760Lwith air valve control features the following additional functions

In start-up position the air valve can be opened for cooling A

Using parameter 31 it can be determined whether the air valve can be activated externally during start-up

The air valve can be set to open together with V1 (display A2 ) via parameter 30

PFU 760 middot Edition 0511

16 Function gt PFU 760 program sequence

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

The air valve can also be set to open with V2 or to be activated externally (display A4 ) via parameter 30

The burner can also be started manually with the aid of the button on the PFU Voltage must be applied continuously to terminals 10e 26e and 30a in order for this to occurThe PFU can also be operated in Manual mode for start-up

Start-up without flame signal If no flame is detected during the safety time tSA either a fault lock-out occurs or up to three further start-up attempts occur The required functions and if applicable the number of start-up attempts must be specified when or-dering (Parameter 10 ldquoBurner start-up attemptsrdquo)

Behaviour in the event of flame failure during operationIf the flame fails during operation either an immediate fault lock-out occurs or a restart occurs This procedure can be set via the optical interface (parameter 12 ldquoBurner restartrdquo)

PFU 760 middot Edition 0511

17Function

Program status DISPLAY Fault message (blinking)Start-up positionstandby 00

Cooling A0

Waiting timePause time 1 Flame simulation pilot burnerBurner safety time on start-up 2 Burner start-up without flame signalBurner flame proving period 3 Flame failure during burner flame proving periodBurner operation 4 Flame failure during operation pilot burnerPurge P0 Air valve A

High temperature operation

10 Faulty remote reset

32 Supply voltage too low

33 Faulty parameterization

35 Short-circuit on a valve output

36 Short-circuit on ignition or valve output

51 Safety interlock failure

52 Permanent reset

53 Time between two start-ups is too short In Manual mode two dots will blink on the display in program status 01 ndash 04 Optionally available

3 3 Program status and fault messagesDuring operation the 7-segment display shows the program status In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault The burner control unit can be reset using the Reset button or the remote reset

PFU 760 middot Edition 0511

18

4 ParametersDescription Parameter Value range Factory default

setting Adjustable

Burner flame signal 01 0 ndash 30 μAProgram status when the most recent fault occurred 03 x0 ndash x8 Burner switch-off threshold 04 1 ndash 20 microA 1 microA

Burner start-up attempts 10 1 ndash 4 1

Burner restart 12 0 1 0

Safety time during operation for V1 and V2 tSB 14 1 2 s 1 s

Flame simulation check in start-up positionstandby 15 0 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 ndash 250 s 0 s

Burner safety time on start-up tSA 22 3 5 10 s

Burner flame proving period tFS 23 0 ndash 25 s 0 s

Switchable gas valve V2 (only on PFUL) 26 0 1 0

Air valve control 30 0 1 2 0

Air valve can be activated externally on start-up 31 0 1 0

Air valve closedcan be activated in the event of malfunction 32 0 1 1

High temperature operation 33 2 3

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 9: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

9

VAG

PFU 760

SPSPLCAPI

DI

L1 N PE

10e

2e 4e

2c 4c

26a

P

26e 10c

DI

BVA+IC 20

M

mA

TZI

16c

22a

BIO BIC

28c

ϑ1

microC

Application gt Examples of application

1 1 4 Modulating-controlled burnerControl continuousThe external control system moves the butterfly valve for air BVA to ignition position The burner starts at low-fire rate and a controller in the PLC controls the burner output via the butterfly valve for air BVA after the operating state has been signalled

PFU 760 middot Edition 0511

10

STW

L1

gt750 degC

microC

PFU 760D

18a

DI

22a

microC

PFU 760D

18a

DI

22a

SPSPLCAPI

DI

L1 N PE P

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

PROFIBUS-DP

1 1 5 PFU 760 D High temperature equipmentIndirect flame control using the tempera-ture During the start-up process as long as the wall temperature is below auto ignition temperature the flame must be controlled by conventional methods When the working temperature has exceeded 750degC the safety tempera-ture monitor (STW) takes over the indirect flame control

1 1 6 PFU for PROFIBUS-DP with PFA 700The bus system transfers the control sig-nals for starting resetting and for con-trolling the air valve from the control sys-tem (PLC) to the PFU 760 via the PFA 700 In the opposite direction it sends infor-mation on the operating status Control signals that are relevant for safety such as the safety interlocks and digital input are transferred independently of the bus communication by separate cables

Application gt Examples of application

PFU 760 middot Edition 0511

11

2 CertificationCertified pursuant to SIL

For systems up to SIL 3 pursuant to EN 61508Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

EC type-tested and certified

pursuant tondash Gas Appliances Directive (2009142EC) in conjunction

with EN 2982004-01

Meets the requirements of thendash Low Voltage Directive (200695EC)ndash EMC Directive (2004108EC)

PFU T is FM approved

Factory Mutual Research Class 1997Suitable for applications pursuant to NFPA 86 wwwfmglobalcom Products and Services Product Cer-tification Approval Guide

AGA approved

AGA

Australian Gas Association Approval No 5597 wwwagaasnauproduct_directory

PFU 760 middot Edition 0511

12

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)( 3 Function

3 1 Connection diagramFor cable selection and wiring see page 43 (Project planning information)

3 1 1 PFU 760For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

13

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

PFU 760K1 PFU 760LK1)(

F2

F1

Function gt Connection diagram

3 1 2 PFU 760 K1As a replacement unit for burner control unit PFSPFD 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

14

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760K2 PFU 760LK2)(

Function gt Connection diagram

3 1 3 PFU 760 K2As a replacement unit for burner control unit PFU 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

15

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

Function

3 2 PFU 760 program sequenceNormal start-upIf an ldquooldrdquo fault is still being signalled after switching on it will be necessary to reset this firstWhen the safety interlocks are closed the PFU reverts to start-up position and conducts a self-test If it does not deter-mine a malfunction of the internal elec-tronic circuitry or of the flame sensor the burner can be startedThe flame simulation check is conducted during start-up position or after applying the start-up signal (ϑ) depending on parameter 15After the min burner pause time tBP has elapsed the PFU opens valve V1 and ignites the burner The ignition time tZ is constantIf a flame is detected during the safety time tSA the flame proving period tFS starts after this safety time has elapsed Valve V2 opens and the operation signalling contact between terminals 2c and 4c closes This completes start-up An adjustable min combustion time tB ensures that the burner burns for a defined period even if the start-up signal (ϑ) is switched off beforehand

PFU 760Lwith air valve control features the following additional functions

In start-up position the air valve can be opened for cooling A

Using parameter 31 it can be determined whether the air valve can be activated externally during start-up

The air valve can be set to open together with V1 (display A2 ) via parameter 30

PFU 760 middot Edition 0511

16 Function gt PFU 760 program sequence

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

The air valve can also be set to open with V2 or to be activated externally (display A4 ) via parameter 30

The burner can also be started manually with the aid of the button on the PFU Voltage must be applied continuously to terminals 10e 26e and 30a in order for this to occurThe PFU can also be operated in Manual mode for start-up

Start-up without flame signal If no flame is detected during the safety time tSA either a fault lock-out occurs or up to three further start-up attempts occur The required functions and if applicable the number of start-up attempts must be specified when or-dering (Parameter 10 ldquoBurner start-up attemptsrdquo)

Behaviour in the event of flame failure during operationIf the flame fails during operation either an immediate fault lock-out occurs or a restart occurs This procedure can be set via the optical interface (parameter 12 ldquoBurner restartrdquo)

PFU 760 middot Edition 0511

17Function

Program status DISPLAY Fault message (blinking)Start-up positionstandby 00

Cooling A0

Waiting timePause time 1 Flame simulation pilot burnerBurner safety time on start-up 2 Burner start-up without flame signalBurner flame proving period 3 Flame failure during burner flame proving periodBurner operation 4 Flame failure during operation pilot burnerPurge P0 Air valve A

High temperature operation

10 Faulty remote reset

32 Supply voltage too low

33 Faulty parameterization

35 Short-circuit on a valve output

36 Short-circuit on ignition or valve output

51 Safety interlock failure

52 Permanent reset

53 Time between two start-ups is too short In Manual mode two dots will blink on the display in program status 01 ndash 04 Optionally available

3 3 Program status and fault messagesDuring operation the 7-segment display shows the program status In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault The burner control unit can be reset using the Reset button or the remote reset

PFU 760 middot Edition 0511

18

4 ParametersDescription Parameter Value range Factory default

setting Adjustable

Burner flame signal 01 0 ndash 30 μAProgram status when the most recent fault occurred 03 x0 ndash x8 Burner switch-off threshold 04 1 ndash 20 microA 1 microA

Burner start-up attempts 10 1 ndash 4 1

Burner restart 12 0 1 0

Safety time during operation for V1 and V2 tSB 14 1 2 s 1 s

Flame simulation check in start-up positionstandby 15 0 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 ndash 250 s 0 s

Burner safety time on start-up tSA 22 3 5 10 s

Burner flame proving period tFS 23 0 ndash 25 s 0 s

Switchable gas valve V2 (only on PFUL) 26 0 1 0

Air valve control 30 0 1 2 0

Air valve can be activated externally on start-up 31 0 1 0

Air valve closedcan be activated in the event of malfunction 32 0 1 1

High temperature operation 33 2 3

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 10: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

10

STW

L1

gt750 degC

microC

PFU 760D

18a

DI

22a

microC

PFU 760D

18a

DI

22a

SPSPLCAPI

DI

L1 N PE P

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

hellip

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFU

760

PFA

PFP

BUS

PROFIBUS-DP

1 1 5 PFU 760 D High temperature equipmentIndirect flame control using the tempera-ture During the start-up process as long as the wall temperature is below auto ignition temperature the flame must be controlled by conventional methods When the working temperature has exceeded 750degC the safety tempera-ture monitor (STW) takes over the indirect flame control

1 1 6 PFU for PROFIBUS-DP with PFA 700The bus system transfers the control sig-nals for starting resetting and for con-trolling the air valve from the control sys-tem (PLC) to the PFU 760 via the PFA 700 In the opposite direction it sends infor-mation on the operating status Control signals that are relevant for safety such as the safety interlocks and digital input are transferred independently of the bus communication by separate cables

Application gt Examples of application

PFU 760 middot Edition 0511

11

2 CertificationCertified pursuant to SIL

For systems up to SIL 3 pursuant to EN 61508Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

EC type-tested and certified

pursuant tondash Gas Appliances Directive (2009142EC) in conjunction

with EN 2982004-01

Meets the requirements of thendash Low Voltage Directive (200695EC)ndash EMC Directive (2004108EC)

PFU T is FM approved

Factory Mutual Research Class 1997Suitable for applications pursuant to NFPA 86 wwwfmglobalcom Products and Services Product Cer-tification Approval Guide

AGA approved

AGA

Australian Gas Association Approval No 5597 wwwagaasnauproduct_directory

PFU 760 middot Edition 0511

12

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)( 3 Function

3 1 Connection diagramFor cable selection and wiring see page 43 (Project planning information)

3 1 1 PFU 760For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

13

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

PFU 760K1 PFU 760LK1)(

F2

F1

Function gt Connection diagram

3 1 2 PFU 760 K1As a replacement unit for burner control unit PFSPFD 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

14

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760K2 PFU 760LK2)(

Function gt Connection diagram

3 1 3 PFU 760 K2As a replacement unit for burner control unit PFU 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

15

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

Function

3 2 PFU 760 program sequenceNormal start-upIf an ldquooldrdquo fault is still being signalled after switching on it will be necessary to reset this firstWhen the safety interlocks are closed the PFU reverts to start-up position and conducts a self-test If it does not deter-mine a malfunction of the internal elec-tronic circuitry or of the flame sensor the burner can be startedThe flame simulation check is conducted during start-up position or after applying the start-up signal (ϑ) depending on parameter 15After the min burner pause time tBP has elapsed the PFU opens valve V1 and ignites the burner The ignition time tZ is constantIf a flame is detected during the safety time tSA the flame proving period tFS starts after this safety time has elapsed Valve V2 opens and the operation signalling contact between terminals 2c and 4c closes This completes start-up An adjustable min combustion time tB ensures that the burner burns for a defined period even if the start-up signal (ϑ) is switched off beforehand

PFU 760Lwith air valve control features the following additional functions

In start-up position the air valve can be opened for cooling A

Using parameter 31 it can be determined whether the air valve can be activated externally during start-up

The air valve can be set to open together with V1 (display A2 ) via parameter 30

PFU 760 middot Edition 0511

16 Function gt PFU 760 program sequence

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

The air valve can also be set to open with V2 or to be activated externally (display A4 ) via parameter 30

The burner can also be started manually with the aid of the button on the PFU Voltage must be applied continuously to terminals 10e 26e and 30a in order for this to occurThe PFU can also be operated in Manual mode for start-up

Start-up without flame signal If no flame is detected during the safety time tSA either a fault lock-out occurs or up to three further start-up attempts occur The required functions and if applicable the number of start-up attempts must be specified when or-dering (Parameter 10 ldquoBurner start-up attemptsrdquo)

Behaviour in the event of flame failure during operationIf the flame fails during operation either an immediate fault lock-out occurs or a restart occurs This procedure can be set via the optical interface (parameter 12 ldquoBurner restartrdquo)

PFU 760 middot Edition 0511

17Function

Program status DISPLAY Fault message (blinking)Start-up positionstandby 00

Cooling A0

Waiting timePause time 1 Flame simulation pilot burnerBurner safety time on start-up 2 Burner start-up without flame signalBurner flame proving period 3 Flame failure during burner flame proving periodBurner operation 4 Flame failure during operation pilot burnerPurge P0 Air valve A

High temperature operation

10 Faulty remote reset

32 Supply voltage too low

33 Faulty parameterization

35 Short-circuit on a valve output

36 Short-circuit on ignition or valve output

51 Safety interlock failure

52 Permanent reset

53 Time between two start-ups is too short In Manual mode two dots will blink on the display in program status 01 ndash 04 Optionally available

3 3 Program status and fault messagesDuring operation the 7-segment display shows the program status In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault The burner control unit can be reset using the Reset button or the remote reset

PFU 760 middot Edition 0511

18

4 ParametersDescription Parameter Value range Factory default

setting Adjustable

Burner flame signal 01 0 ndash 30 μAProgram status when the most recent fault occurred 03 x0 ndash x8 Burner switch-off threshold 04 1 ndash 20 microA 1 microA

Burner start-up attempts 10 1 ndash 4 1

Burner restart 12 0 1 0

Safety time during operation for V1 and V2 tSB 14 1 2 s 1 s

Flame simulation check in start-up positionstandby 15 0 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 ndash 250 s 0 s

Burner safety time on start-up tSA 22 3 5 10 s

Burner flame proving period tFS 23 0 ndash 25 s 0 s

Switchable gas valve V2 (only on PFUL) 26 0 1 0

Air valve control 30 0 1 2 0

Air valve can be activated externally on start-up 31 0 1 0

Air valve closedcan be activated in the event of malfunction 32 0 1 1

High temperature operation 33 2 3

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 11: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

11

2 CertificationCertified pursuant to SIL

For systems up to SIL 3 pursuant to EN 61508Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

EC type-tested and certified

pursuant tondash Gas Appliances Directive (2009142EC) in conjunction

with EN 2982004-01

Meets the requirements of thendash Low Voltage Directive (200695EC)ndash EMC Directive (2004108EC)

PFU T is FM approved

Factory Mutual Research Class 1997Suitable for applications pursuant to NFPA 86 wwwfmglobalcom Products and Services Product Cer-tification Approval Guide

AGA approved

AGA

Australian Gas Association Approval No 5597 wwwagaasnauproduct_directory

PFU 760 middot Edition 0511

12

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)( 3 Function

3 1 Connection diagramFor cable selection and wiring see page 43 (Project planning information)

3 1 1 PFU 760For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

13

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

PFU 760K1 PFU 760LK1)(

F2

F1

Function gt Connection diagram

3 1 2 PFU 760 K1As a replacement unit for burner control unit PFSPFD 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

14

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760K2 PFU 760LK2)(

Function gt Connection diagram

3 1 3 PFU 760 K2As a replacement unit for burner control unit PFU 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

15

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

Function

3 2 PFU 760 program sequenceNormal start-upIf an ldquooldrdquo fault is still being signalled after switching on it will be necessary to reset this firstWhen the safety interlocks are closed the PFU reverts to start-up position and conducts a self-test If it does not deter-mine a malfunction of the internal elec-tronic circuitry or of the flame sensor the burner can be startedThe flame simulation check is conducted during start-up position or after applying the start-up signal (ϑ) depending on parameter 15After the min burner pause time tBP has elapsed the PFU opens valve V1 and ignites the burner The ignition time tZ is constantIf a flame is detected during the safety time tSA the flame proving period tFS starts after this safety time has elapsed Valve V2 opens and the operation signalling contact between terminals 2c and 4c closes This completes start-up An adjustable min combustion time tB ensures that the burner burns for a defined period even if the start-up signal (ϑ) is switched off beforehand

PFU 760Lwith air valve control features the following additional functions

In start-up position the air valve can be opened for cooling A

Using parameter 31 it can be determined whether the air valve can be activated externally during start-up

The air valve can be set to open together with V1 (display A2 ) via parameter 30

PFU 760 middot Edition 0511

16 Function gt PFU 760 program sequence

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

The air valve can also be set to open with V2 or to be activated externally (display A4 ) via parameter 30

The burner can also be started manually with the aid of the button on the PFU Voltage must be applied continuously to terminals 10e 26e and 30a in order for this to occurThe PFU can also be operated in Manual mode for start-up

Start-up without flame signal If no flame is detected during the safety time tSA either a fault lock-out occurs or up to three further start-up attempts occur The required functions and if applicable the number of start-up attempts must be specified when or-dering (Parameter 10 ldquoBurner start-up attemptsrdquo)

Behaviour in the event of flame failure during operationIf the flame fails during operation either an immediate fault lock-out occurs or a restart occurs This procedure can be set via the optical interface (parameter 12 ldquoBurner restartrdquo)

PFU 760 middot Edition 0511

17Function

Program status DISPLAY Fault message (blinking)Start-up positionstandby 00

Cooling A0

Waiting timePause time 1 Flame simulation pilot burnerBurner safety time on start-up 2 Burner start-up without flame signalBurner flame proving period 3 Flame failure during burner flame proving periodBurner operation 4 Flame failure during operation pilot burnerPurge P0 Air valve A

High temperature operation

10 Faulty remote reset

32 Supply voltage too low

33 Faulty parameterization

35 Short-circuit on a valve output

36 Short-circuit on ignition or valve output

51 Safety interlock failure

52 Permanent reset

53 Time between two start-ups is too short In Manual mode two dots will blink on the display in program status 01 ndash 04 Optionally available

3 3 Program status and fault messagesDuring operation the 7-segment display shows the program status In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault The burner control unit can be reset using the Reset button or the remote reset

PFU 760 middot Edition 0511

18

4 ParametersDescription Parameter Value range Factory default

setting Adjustable

Burner flame signal 01 0 ndash 30 μAProgram status when the most recent fault occurred 03 x0 ndash x8 Burner switch-off threshold 04 1 ndash 20 microA 1 microA

Burner start-up attempts 10 1 ndash 4 1

Burner restart 12 0 1 0

Safety time during operation for V1 and V2 tSB 14 1 2 s 1 s

Flame simulation check in start-up positionstandby 15 0 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 ndash 250 s 0 s

Burner safety time on start-up tSA 22 3 5 10 s

Burner flame proving period tFS 23 0 ndash 25 s 0 s

Switchable gas valve V2 (only on PFUL) 26 0 1 0

Air valve control 30 0 1 2 0

Air valve can be activated externally on start-up 31 0 1 0

Air valve closedcan be activated in the event of malfunction 32 0 1 1

High temperature operation 33 2 3

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 12: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

12

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)( 3 Function

3 1 Connection diagramFor cable selection and wiring see page 43 (Project planning information)

3 1 1 PFU 760For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

13

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

PFU 760K1 PFU 760LK1)(

F2

F1

Function gt Connection diagram

3 1 2 PFU 760 K1As a replacement unit for burner control unit PFSPFD 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

14

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760K2 PFU 760LK2)(

Function gt Connection diagram

3 1 3 PFU 760 K2As a replacement unit for burner control unit PFU 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

15

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

Function

3 2 PFU 760 program sequenceNormal start-upIf an ldquooldrdquo fault is still being signalled after switching on it will be necessary to reset this firstWhen the safety interlocks are closed the PFU reverts to start-up position and conducts a self-test If it does not deter-mine a malfunction of the internal elec-tronic circuitry or of the flame sensor the burner can be startedThe flame simulation check is conducted during start-up position or after applying the start-up signal (ϑ) depending on parameter 15After the min burner pause time tBP has elapsed the PFU opens valve V1 and ignites the burner The ignition time tZ is constantIf a flame is detected during the safety time tSA the flame proving period tFS starts after this safety time has elapsed Valve V2 opens and the operation signalling contact between terminals 2c and 4c closes This completes start-up An adjustable min combustion time tB ensures that the burner burns for a defined period even if the start-up signal (ϑ) is switched off beforehand

PFU 760Lwith air valve control features the following additional functions

In start-up position the air valve can be opened for cooling A

Using parameter 31 it can be determined whether the air valve can be activated externally during start-up

The air valve can be set to open together with V1 (display A2 ) via parameter 30

PFU 760 middot Edition 0511

16 Function gt PFU 760 program sequence

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

The air valve can also be set to open with V2 or to be activated externally (display A4 ) via parameter 30

The burner can also be started manually with the aid of the button on the PFU Voltage must be applied continuously to terminals 10e 26e and 30a in order for this to occurThe PFU can also be operated in Manual mode for start-up

Start-up without flame signal If no flame is detected during the safety time tSA either a fault lock-out occurs or up to three further start-up attempts occur The required functions and if applicable the number of start-up attempts must be specified when or-dering (Parameter 10 ldquoBurner start-up attemptsrdquo)

Behaviour in the event of flame failure during operationIf the flame fails during operation either an immediate fault lock-out occurs or a restart occurs This procedure can be set via the optical interface (parameter 12 ldquoBurner restartrdquo)

PFU 760 middot Edition 0511

17Function

Program status DISPLAY Fault message (blinking)Start-up positionstandby 00

Cooling A0

Waiting timePause time 1 Flame simulation pilot burnerBurner safety time on start-up 2 Burner start-up without flame signalBurner flame proving period 3 Flame failure during burner flame proving periodBurner operation 4 Flame failure during operation pilot burnerPurge P0 Air valve A

High temperature operation

10 Faulty remote reset

32 Supply voltage too low

33 Faulty parameterization

35 Short-circuit on a valve output

36 Short-circuit on ignition or valve output

51 Safety interlock failure

52 Permanent reset

53 Time between two start-ups is too short In Manual mode two dots will blink on the display in program status 01 ndash 04 Optionally available

3 3 Program status and fault messagesDuring operation the 7-segment display shows the program status In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault The burner control unit can be reset using the Reset button or the remote reset

PFU 760 middot Edition 0511

18

4 ParametersDescription Parameter Value range Factory default

setting Adjustable

Burner flame signal 01 0 ndash 30 μAProgram status when the most recent fault occurred 03 x0 ndash x8 Burner switch-off threshold 04 1 ndash 20 microA 1 microA

Burner start-up attempts 10 1 ndash 4 1

Burner restart 12 0 1 0

Safety time during operation for V1 and V2 tSB 14 1 2 s 1 s

Flame simulation check in start-up positionstandby 15 0 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 ndash 250 s 0 s

Burner safety time on start-up tSA 22 3 5 10 s

Burner flame proving period tFS 23 0 ndash 25 s 0 s

Switchable gas valve V2 (only on PFUL) 26 0 1 0

Air valve control 30 0 1 2 0

Air valve can be activated externally on start-up 31 0 1 0

Air valve closedcan be activated in the event of malfunction 32 0 1 1

High temperature operation 33 2 3

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 13: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

13

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

PFU 760K1 PFU 760LK1)(

F2

F1

Function gt Connection diagram

3 1 2 PFU 760 K1As a replacement unit for burner control unit PFSPFD 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

14

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760K2 PFU 760LK2)(

Function gt Connection diagram

3 1 3 PFU 760 K2As a replacement unit for burner control unit PFU 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

15

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

Function

3 2 PFU 760 program sequenceNormal start-upIf an ldquooldrdquo fault is still being signalled after switching on it will be necessary to reset this firstWhen the safety interlocks are closed the PFU reverts to start-up position and conducts a self-test If it does not deter-mine a malfunction of the internal elec-tronic circuitry or of the flame sensor the burner can be startedThe flame simulation check is conducted during start-up position or after applying the start-up signal (ϑ) depending on parameter 15After the min burner pause time tBP has elapsed the PFU opens valve V1 and ignites the burner The ignition time tZ is constantIf a flame is detected during the safety time tSA the flame proving period tFS starts after this safety time has elapsed Valve V2 opens and the operation signalling contact between terminals 2c and 4c closes This completes start-up An adjustable min combustion time tB ensures that the burner burns for a defined period even if the start-up signal (ϑ) is switched off beforehand

PFU 760Lwith air valve control features the following additional functions

In start-up position the air valve can be opened for cooling A

Using parameter 31 it can be determined whether the air valve can be activated externally during start-up

The air valve can be set to open together with V1 (display A2 ) via parameter 30

PFU 760 middot Edition 0511

16 Function gt PFU 760 program sequence

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

The air valve can also be set to open with V2 or to be activated externally (display A4 ) via parameter 30

The burner can also be started manually with the aid of the button on the PFU Voltage must be applied continuously to terminals 10e 26e and 30a in order for this to occurThe PFU can also be operated in Manual mode for start-up

Start-up without flame signal If no flame is detected during the safety time tSA either a fault lock-out occurs or up to three further start-up attempts occur The required functions and if applicable the number of start-up attempts must be specified when or-dering (Parameter 10 ldquoBurner start-up attemptsrdquo)

Behaviour in the event of flame failure during operationIf the flame fails during operation either an immediate fault lock-out occurs or a restart occurs This procedure can be set via the optical interface (parameter 12 ldquoBurner restartrdquo)

PFU 760 middot Edition 0511

17Function

Program status DISPLAY Fault message (blinking)Start-up positionstandby 00

Cooling A0

Waiting timePause time 1 Flame simulation pilot burnerBurner safety time on start-up 2 Burner start-up without flame signalBurner flame proving period 3 Flame failure during burner flame proving periodBurner operation 4 Flame failure during operation pilot burnerPurge P0 Air valve A

High temperature operation

10 Faulty remote reset

32 Supply voltage too low

33 Faulty parameterization

35 Short-circuit on a valve output

36 Short-circuit on ignition or valve output

51 Safety interlock failure

52 Permanent reset

53 Time between two start-ups is too short In Manual mode two dots will blink on the display in program status 01 ndash 04 Optionally available

3 3 Program status and fault messagesDuring operation the 7-segment display shows the program status In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault The burner control unit can be reset using the Reset button or the remote reset

PFU 760 middot Edition 0511

18

4 ParametersDescription Parameter Value range Factory default

setting Adjustable

Burner flame signal 01 0 ndash 30 μAProgram status when the most recent fault occurred 03 x0 ndash x8 Burner switch-off threshold 04 1 ndash 20 microA 1 microA

Burner start-up attempts 10 1 ndash 4 1

Burner restart 12 0 1 0

Safety time during operation for V1 and V2 tSB 14 1 2 s 1 s

Flame simulation check in start-up positionstandby 15 0 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 ndash 250 s 0 s

Burner safety time on start-up tSA 22 3 5 10 s

Burner flame proving period tFS 23 0 ndash 25 s 0 s

Switchable gas valve V2 (only on PFUL) 26 0 1 0

Air valve control 30 0 1 2 0

Air valve can be activated externally on start-up 31 0 1 0

Air valve closedcan be activated in the event of malfunction 32 0 1 1

High temperature operation 33 2 3

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 14: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

14

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760K2 PFU 760LK2)(

Function gt Connection diagram

3 1 3 PFU 760 K2As a replacement unit for burner control unit PFU 778For the explanation of symbols see page 61 (Legend)

PFU 760 middot Edition 0511

15

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

Function

3 2 PFU 760 program sequenceNormal start-upIf an ldquooldrdquo fault is still being signalled after switching on it will be necessary to reset this firstWhen the safety interlocks are closed the PFU reverts to start-up position and conducts a self-test If it does not deter-mine a malfunction of the internal elec-tronic circuitry or of the flame sensor the burner can be startedThe flame simulation check is conducted during start-up position or after applying the start-up signal (ϑ) depending on parameter 15After the min burner pause time tBP has elapsed the PFU opens valve V1 and ignites the burner The ignition time tZ is constantIf a flame is detected during the safety time tSA the flame proving period tFS starts after this safety time has elapsed Valve V2 opens and the operation signalling contact between terminals 2c and 4c closes This completes start-up An adjustable min combustion time tB ensures that the burner burns for a defined period even if the start-up signal (ϑ) is switched off beforehand

PFU 760Lwith air valve control features the following additional functions

In start-up position the air valve can be opened for cooling A

Using parameter 31 it can be determined whether the air valve can be activated externally during start-up

The air valve can be set to open together with V1 (display A2 ) via parameter 30

PFU 760 middot Edition 0511

16 Function gt PFU 760 program sequence

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

The air valve can also be set to open with V2 or to be activated externally (display A4 ) via parameter 30

The burner can also be started manually with the aid of the button on the PFU Voltage must be applied continuously to terminals 10e 26e and 30a in order for this to occurThe PFU can also be operated in Manual mode for start-up

Start-up without flame signal If no flame is detected during the safety time tSA either a fault lock-out occurs or up to three further start-up attempts occur The required functions and if applicable the number of start-up attempts must be specified when or-dering (Parameter 10 ldquoBurner start-up attemptsrdquo)

Behaviour in the event of flame failure during operationIf the flame fails during operation either an immediate fault lock-out occurs or a restart occurs This procedure can be set via the optical interface (parameter 12 ldquoBurner restartrdquo)

PFU 760 middot Edition 0511

17Function

Program status DISPLAY Fault message (blinking)Start-up positionstandby 00

Cooling A0

Waiting timePause time 1 Flame simulation pilot burnerBurner safety time on start-up 2 Burner start-up without flame signalBurner flame proving period 3 Flame failure during burner flame proving periodBurner operation 4 Flame failure during operation pilot burnerPurge P0 Air valve A

High temperature operation

10 Faulty remote reset

32 Supply voltage too low

33 Faulty parameterization

35 Short-circuit on a valve output

36 Short-circuit on ignition or valve output

51 Safety interlock failure

52 Permanent reset

53 Time between two start-ups is too short In Manual mode two dots will blink on the display in program status 01 ndash 04 Optionally available

3 3 Program status and fault messagesDuring operation the 7-segment display shows the program status In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault The burner control unit can be reset using the Reset button or the remote reset

PFU 760 middot Edition 0511

18

4 ParametersDescription Parameter Value range Factory default

setting Adjustable

Burner flame signal 01 0 ndash 30 μAProgram status when the most recent fault occurred 03 x0 ndash x8 Burner switch-off threshold 04 1 ndash 20 microA 1 microA

Burner start-up attempts 10 1 ndash 4 1

Burner restart 12 0 1 0

Safety time during operation for V1 and V2 tSB 14 1 2 s 1 s

Flame simulation check in start-up positionstandby 15 0 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 ndash 250 s 0 s

Burner safety time on start-up tSA 22 3 5 10 s

Burner flame proving period tFS 23 0 ndash 25 s 0 s

Switchable gas valve V2 (only on PFUL) 26 0 1 0

Air valve control 30 0 1 2 0

Air valve can be activated externally on start-up 31 0 1 0

Air valve closedcan be activated in the event of malfunction 32 0 1 1

High temperature operation 33 2 3

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 15: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

15

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

Function

3 2 PFU 760 program sequenceNormal start-upIf an ldquooldrdquo fault is still being signalled after switching on it will be necessary to reset this firstWhen the safety interlocks are closed the PFU reverts to start-up position and conducts a self-test If it does not deter-mine a malfunction of the internal elec-tronic circuitry or of the flame sensor the burner can be startedThe flame simulation check is conducted during start-up position or after applying the start-up signal (ϑ) depending on parameter 15After the min burner pause time tBP has elapsed the PFU opens valve V1 and ignites the burner The ignition time tZ is constantIf a flame is detected during the safety time tSA the flame proving period tFS starts after this safety time has elapsed Valve V2 opens and the operation signalling contact between terminals 2c and 4c closes This completes start-up An adjustable min combustion time tB ensures that the burner burns for a defined period even if the start-up signal (ϑ) is switched off beforehand

PFU 760Lwith air valve control features the following additional functions

In start-up position the air valve can be opened for cooling A

Using parameter 31 it can be determined whether the air valve can be activated externally during start-up

The air valve can be set to open together with V1 (display A2 ) via parameter 30

PFU 760 middot Edition 0511

16 Function gt PFU 760 program sequence

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

The air valve can also be set to open with V2 or to be activated externally (display A4 ) via parameter 30

The burner can also be started manually with the aid of the button on the PFU Voltage must be applied continuously to terminals 10e 26e and 30a in order for this to occurThe PFU can also be operated in Manual mode for start-up

Start-up without flame signal If no flame is detected during the safety time tSA either a fault lock-out occurs or up to three further start-up attempts occur The required functions and if applicable the number of start-up attempts must be specified when or-dering (Parameter 10 ldquoBurner start-up attemptsrdquo)

Behaviour in the event of flame failure during operationIf the flame fails during operation either an immediate fault lock-out occurs or a restart occurs This procedure can be set via the optical interface (parameter 12 ldquoBurner restartrdquo)

PFU 760 middot Edition 0511

17Function

Program status DISPLAY Fault message (blinking)Start-up positionstandby 00

Cooling A0

Waiting timePause time 1 Flame simulation pilot burnerBurner safety time on start-up 2 Burner start-up without flame signalBurner flame proving period 3 Flame failure during burner flame proving periodBurner operation 4 Flame failure during operation pilot burnerPurge P0 Air valve A

High temperature operation

10 Faulty remote reset

32 Supply voltage too low

33 Faulty parameterization

35 Short-circuit on a valve output

36 Short-circuit on ignition or valve output

51 Safety interlock failure

52 Permanent reset

53 Time between two start-ups is too short In Manual mode two dots will blink on the display in program status 01 ndash 04 Optionally available

3 3 Program status and fault messagesDuring operation the 7-segment display shows the program status In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault The burner control unit can be reset using the Reset button or the remote reset

PFU 760 middot Edition 0511

18

4 ParametersDescription Parameter Value range Factory default

setting Adjustable

Burner flame signal 01 0 ndash 30 μAProgram status when the most recent fault occurred 03 x0 ndash x8 Burner switch-off threshold 04 1 ndash 20 microA 1 microA

Burner start-up attempts 10 1 ndash 4 1

Burner restart 12 0 1 0

Safety time during operation for V1 and V2 tSB 14 1 2 s 1 s

Flame simulation check in start-up positionstandby 15 0 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 ndash 250 s 0 s

Burner safety time on start-up tSA 22 3 5 10 s

Burner flame proving period tFS 23 0 ndash 25 s 0 s

Switchable gas valve V2 (only on PFUL) 26 0 1 0

Air valve control 30 0 1 2 0

Air valve can be activated externally on start-up 31 0 1 0

Air valve closedcan be activated in the event of malfunction 32 0 1 1

High temperature operation 33 2 3

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 16: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

16 Function gt PFU 760 program sequence

01

02

03

04

04

00

00

Switch on PFU 760

Start-up with ϑ signal

Safety interlocks (Limits)

In the event of fault signalReset

If parameter P15 = 1Flame simulation check

Wait until min burner pause time tBP

has elapsed (P21)

If parameter P15 = 0Flame simulation check

If no flame detectednext start-up attempt (P10)

or fault lock-out

In the event of flame failure restart or

fault lock-out

Start-up positionstandby

Controlled shut-down via ϑ signal

Operation signalling contact closes and V2 opens

Flame proving period tFS running (P23)

In the event of flame failure fault lock-out

Safety time tSA running (P22)

ignition in process V1 opens and

min combustion time tB starts to elapse (P20)

If min combustion time tB has elapsed

Operation signalling contact opens

V1 and V2 closemin burner pause time tBP

starts to elapse (P21)

The air valve can also be set to open with V2 or to be activated externally (display A4 ) via parameter 30

The burner can also be started manually with the aid of the button on the PFU Voltage must be applied continuously to terminals 10e 26e and 30a in order for this to occurThe PFU can also be operated in Manual mode for start-up

Start-up without flame signal If no flame is detected during the safety time tSA either a fault lock-out occurs or up to three further start-up attempts occur The required functions and if applicable the number of start-up attempts must be specified when or-dering (Parameter 10 ldquoBurner start-up attemptsrdquo)

Behaviour in the event of flame failure during operationIf the flame fails during operation either an immediate fault lock-out occurs or a restart occurs This procedure can be set via the optical interface (parameter 12 ldquoBurner restartrdquo)

PFU 760 middot Edition 0511

17Function

Program status DISPLAY Fault message (blinking)Start-up positionstandby 00

Cooling A0

Waiting timePause time 1 Flame simulation pilot burnerBurner safety time on start-up 2 Burner start-up without flame signalBurner flame proving period 3 Flame failure during burner flame proving periodBurner operation 4 Flame failure during operation pilot burnerPurge P0 Air valve A

High temperature operation

10 Faulty remote reset

32 Supply voltage too low

33 Faulty parameterization

35 Short-circuit on a valve output

36 Short-circuit on ignition or valve output

51 Safety interlock failure

52 Permanent reset

53 Time between two start-ups is too short In Manual mode two dots will blink on the display in program status 01 ndash 04 Optionally available

3 3 Program status and fault messagesDuring operation the 7-segment display shows the program status In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault The burner control unit can be reset using the Reset button or the remote reset

PFU 760 middot Edition 0511

18

4 ParametersDescription Parameter Value range Factory default

setting Adjustable

Burner flame signal 01 0 ndash 30 μAProgram status when the most recent fault occurred 03 x0 ndash x8 Burner switch-off threshold 04 1 ndash 20 microA 1 microA

Burner start-up attempts 10 1 ndash 4 1

Burner restart 12 0 1 0

Safety time during operation for V1 and V2 tSB 14 1 2 s 1 s

Flame simulation check in start-up positionstandby 15 0 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 ndash 250 s 0 s

Burner safety time on start-up tSA 22 3 5 10 s

Burner flame proving period tFS 23 0 ndash 25 s 0 s

Switchable gas valve V2 (only on PFUL) 26 0 1 0

Air valve control 30 0 1 2 0

Air valve can be activated externally on start-up 31 0 1 0

Air valve closedcan be activated in the event of malfunction 32 0 1 1

High temperature operation 33 2 3

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 17: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

17Function

Program status DISPLAY Fault message (blinking)Start-up positionstandby 00

Cooling A0

Waiting timePause time 1 Flame simulation pilot burnerBurner safety time on start-up 2 Burner start-up without flame signalBurner flame proving period 3 Flame failure during burner flame proving periodBurner operation 4 Flame failure during operation pilot burnerPurge P0 Air valve A

High temperature operation

10 Faulty remote reset

32 Supply voltage too low

33 Faulty parameterization

35 Short-circuit on a valve output

36 Short-circuit on ignition or valve output

51 Safety interlock failure

52 Permanent reset

53 Time between two start-ups is too short In Manual mode two dots will blink on the display in program status 01 ndash 04 Optionally available

3 3 Program status and fault messagesDuring operation the 7-segment display shows the program status In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault The burner control unit can be reset using the Reset button or the remote reset

PFU 760 middot Edition 0511

18

4 ParametersDescription Parameter Value range Factory default

setting Adjustable

Burner flame signal 01 0 ndash 30 μAProgram status when the most recent fault occurred 03 x0 ndash x8 Burner switch-off threshold 04 1 ndash 20 microA 1 microA

Burner start-up attempts 10 1 ndash 4 1

Burner restart 12 0 1 0

Safety time during operation for V1 and V2 tSB 14 1 2 s 1 s

Flame simulation check in start-up positionstandby 15 0 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 ndash 250 s 0 s

Burner safety time on start-up tSA 22 3 5 10 s

Burner flame proving period tFS 23 0 ndash 25 s 0 s

Switchable gas valve V2 (only on PFUL) 26 0 1 0

Air valve control 30 0 1 2 0

Air valve can be activated externally on start-up 31 0 1 0

Air valve closedcan be activated in the event of malfunction 32 0 1 1

High temperature operation 33 2 3

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 18: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

18

4 ParametersDescription Parameter Value range Factory default

setting Adjustable

Burner flame signal 01 0 ndash 30 μAProgram status when the most recent fault occurred 03 x0 ndash x8 Burner switch-off threshold 04 1 ndash 20 microA 1 microA

Burner start-up attempts 10 1 ndash 4 1

Burner restart 12 0 1 0

Safety time during operation for V1 and V2 tSB 14 1 2 s 1 s

Flame simulation check in start-up positionstandby 15 0 1 1

Minimum combustion time tB 20 25 s tSA

Minimum burner pause time tBP 21 0 ndash 250 s 0 s

Burner safety time on start-up tSA 22 3 5 10 s

Burner flame proving period tFS 23 0 ndash 25 s 0 s

Switchable gas valve V2 (only on PFUL) 26 0 1 0

Air valve control 30 0 1 2 0

Air valve can be activated externally on start-up 31 0 1 0

Air valve closedcan be activated in the event of malfunction 32 0 1 1

High temperature operation 33 2 3

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 19: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

19

Description Parameter Value range Factory default setting Adjustable

Manual mode limited to 5 minutes 34 0 1 1

UVS check (1 x in 24 hours) 35 0 1 0

Low fire over run time 36 0 3 5 10 15 25 60 s 0 s

Purge 42 0 1 1

Multi-flame control 45 0 1 0

Password 50 0000 ndash 9999 1234

Adjustable using BCSoft software and a PC opto-adapter Please quote in your order0 = Function inactive1 = Function active

On parameterization ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

4 1 Scanning the parametersDuring operation the 7-segment display shows the program statusThe flame signal and all following parameters of the PFU can be scanned one after the other by repeatedly pressing the ResetInformation button (for 2 s)In the event of a fault the PFU halts the program run the display blinks and it then displays the cause of the fault in coded form

Parameters

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 20: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

20

4 2 Flame control4 2 1 Burner flame signalParameter 01Flame signal of the burner display in microA measuring range 0 ndash 30 microA

4 2 2 Program status when the most recent fault occurredParameter 03This indicates the program status in which the last burner fault occurred (eg the unit indicates that a flame simulation has been detected with a blinking 01 In parameter 03 it is now shown which program position the unit was in when the fault was detected (waiting time 01 or standby 00 )Result A flame simulation was detected during the waiting time or standby

4 2 3 Switch-off threshold of the flame amplifierParameter 04 burner switch-off thresholdThe sensitivity at which the burner control unit still detects a flame can be set between 1 and 20 microAExample In the case of UV control with the UV sensor UVS the signal of the burner to be monitored is influenced by other burnersThe set value can be incremented in parameter 04 so that only the flame of the systemrsquos ldquoownrdquo burner is detectedThe measured flame signal of the systemrsquos ldquoownrdquo burner should be at least 3 microA (empirical value) higher than the set switch-off threshold

Parameters

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 21: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

21

4 2 4 High temperature operation with PFU D Parameter 33Operation of firing systems at temperatures above 750degC The PFU features a safety-relevant DI input (Digital Input) This input supports the ldquoHigh temperature operationrdquo function If firing systems are operated above 750degC the system is considered to be a high temperature equipment (see EN 746-2) Flame control must be in operation until the furnace wall temperature has exceeded 750degC Note the requirements of the StandardsFlame control can be dispensed with during high temperature operation to improve the system availability This means that no incorrect flame signals eg signals from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation may lead to faultsWhen the DI input is activated the burner control unit reverts to High temperature mode This means the PFU operates without evaluation of the flame signal The safety function of the device-internal flame control system is placed out of operationIn High temperature mode the gas valves are opened without flame controlThe precondition for high temperature operation is that an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the temperature For this purpose we recommend a safety temperature monitor with twin thermocouple (DIN 3440) Sensor discontinuity sensor short-circuit failure of a component or mains failure must set the installation to a safe state

The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only when the temperature at the furnace wall has exceeded 750degC The PFU starts the burner as usual without monitoring the presence of the flame

00

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 03

tFS

If the temperature in the furnace chamber drops below 750degC the DI input must be disconnected from the electrical power supply and the furnace must be operated with the internal flame control system

Parameters gt Flame control

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 22: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

22

The PFU then responds depending on setting Parameter 33 = 1 (PFU 760K2 only)

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

FA

If the flame fails during high temperature operation the ready contact opens for the duration of the flame failure (FA)When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)

Parameter 33 = 2

04

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

tSA

tZ

0402 0301

tFS

tW

2andash4a

When High temperature mode is ended the PFU switches off the burner and restarts with flame simulation check (recom-mended in the case of UV control with UVS)On programming parameter 33 ensure that the program sequence matches the application Select the parameters so that the burner can be operated as intended in all operating phases

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 23: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

23

Parameter 33 = 3

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

When High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)If no flame signal is present when High temperature mode is ended the burner control unit performs a fault lock-out regardless of parameter 33

t

04 04

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

Parameter 33 = 4 (PFU 760K2 only)

0404

t

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

22aV1

V2

ϑ

DI

2andash4a

FA

If the flame fails during high temperature operation the ready contact is opened for the duration of the flame failureWhen High temperature mode is ended the burner remains in operation and the PFU performs flame control again (recommended in the case of ionization control or UV control with UVD)

Parameters gt Flame control gt High temperature operation with PFU D

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 24: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

24

4 2 5 UVS checkParameter 35 An automatic restart of the burner control unit can be activated every 24 hours via this parameter The time starts each time the start-up signal (ϑ) is appliedParameter 35 = 0 Unlimited burner operationParameter 35 = 1 An automatic restart is activated once every 24 hoursIt must be ensured in this case that the program sequence started matches the application This parameter may be set in this way only if the burner can restart as intended in all operating phases

Parameters gt Flame control

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 25: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

25

4 3 Behaviour in start-up positionstandby4 3 1 Flame simulation check in start-up positionstandbyParameter 15This defines the instant for the flame simulation check

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 0 The flame simulation check is conducted after applying the start-up signal (ϑ) during the waiting time tW

t

88 02 00

t

88 00 02 01

t W

V1

V1

Parameter 15 = 1 The flame simulation check is conducted provided no start-up signal (ϑ) is applied (during the so-called start-up positionstandby) This allows fast start-up of the burner since there is no waiting time tWThe burner must have been switched off for at least 4 s be-fore start-up in order for the flame simulation check to be conducted correctly

What is an extraneous signal

tLV

00

t

01

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

An extraneous signal is an incorrect signal which is detected as a flame signal out of sequence If the PFU 760 notices such an extraneous signal during the flame simulation check it starts the flame simulation delay time tLV If the extraneous signal is discontinued during this period the burner can start up Otherwise a fault lock-out occurs 01 blinks on the displayThe flame simulation check of the burner is active until valve V1 is enabled

Parameters

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 26: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

26

4 3 2 Minimum burner pause time tBP Parameter 21 Programmable time between 0 and 250 s

tSA

tZ

04 02 03 04

t tBP tFS

01 00 88

451

79

18-19

12 V114 V216-17

ϑ

An immediate restart of the main burner after a controlled shut-down a start-up attempt restart cooling or purging is prevented by the pause time The pause time starts when the air valve is switched off If a start-up signal (ϑ) is applied before expiry of this time the start-up is delayed until the end of the pause timeAfter the pause time the burner is started if the start-up signal (ϑ) is appliedThe minimum burner pause time tBP serves to adapt the pro-gram sequence to the requirements of the applicationThe time should be set such that the system can be moved to ignition position ie butterfly valves can be closed and pos-sibly gas can be flared off before a restart occursSee examples of application Staged OnOff burner control Staged HighLow burner control oder Two-stage-controlled burner

Parameters gt Behaviour in start-up positionstandby

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 27: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

27

4 4 Behaviour during start-up4 4 1 Safety time on start-up tSA Parameter 22

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Safety time on start-up tSA for the burner

4 4 2 Flame proving period tFS Parameter 23

tSA

tZ

04 02 03 00

t tFS

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

Programmable time between 0 and 25 sThis time elapses before the PFU starts the next program step so as to give the flame time to stabilize

4 4 3 Minimum combustion time tB Parameter 20 Programmable time in the range from minimum safety time start-up tSA to maximum 25 s during which the burner remains in operationIn the case of brief activation of the start-up signal input (ϑ) (eg with a pulse) the combustion time tB is started and the burner remains in operation for at least this period

Parameters

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 28: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

28

4 4 4 Burner start-up attemptsParameter 10This indicates the number of possible start-up attempts of the burnerIn accordance with EN 746-2 three start-ups are permitted in specific cases in the event of flame failure during start-up if the safety of the installation is not impaired Note the require-ments of the StandardsIf no flame is detected during start-up either a fault lock-out is performed or further start-up attempts in accordance with EN 746-2 occurPursuant to NFPA 86 only one start-up attempt is permitted in the event of flame failure during start-up For units approved by FM Approval (see type label) it is only possible to select one start-up attempt

1 start-up attemptParameter 10 = 1

t SA

t Z

02 00

t

02

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ1

If no flame forms during start-up a fault lock-out is performed after expiry of time tSA The display blinks and shows the cause of the fault

2 or 3 start-up attemptsParameter 10 = 2 3

tSA

tZ

02 00

t

tSA

tZ

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

If several start-up attempts are set and if the PFU detects a flame failure during start-up it closes valve V1 after the safety time tSA has expired and attempts to start up again After the last programmed start-up attempt has been completed the burner control unit conducts a fault lock-out The display blinks and shows the cause of the fault

Parameters gt Behaviour during start-up

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 29: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

29

4 5 Behaviour during operation4 5 1 Safety time during operation tSB for V1 and V2Parameter 14This indicates the safety time during operation tSB for valves V1 and V2 The default in accordance with EN 298 is 1 s The PFU has also the available option of a safety time during operation tSB of 2 s Prolonging the time increases the installation avail-ability in the case of brief-duration signal fades (eg fades of the flame signal) In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards)

4 5 2 Fault lock-out or restartParameter 12 This parameter determines whether the PFU starts a one-off restart or performs an immediate fault lock-out for the burner after a flame failure (see also Project planning information)

Immediate fault lock-out following flame failureParameter 12 = 0

04

t tSB

04

26a16c18e2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

After a fault lock-out the burner control unit can be reset either with the button on the front panel or using an external button Several burner control units can be reset in parallel using the external buttonThe PFU cannot be reset by mains failure The fault signalling contact does however open as soon as the mains voltage failsSee also parameter 32 Behaviour of the air valve in the event of a fault lock-out

Parameters

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 30: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

30

Restart following flame failureParameter 12 = 1 Restart following flame failure

tSA

tZ

04 04 03 01

t tFS

tW

tSB

1x

gt2 s

26a16c2cndash4c

88

10e26e30a

28c

2endash4e

V1

ϑ

If the PFU detects a flame failure after a minimum operating time of 2 s the valves are closed and the operation signalling contact is opened within time tSBThe burner control unit now attempts to restart the burner once If the burner does not function a fault lock-out occurs The display blinks and shows the cause of the faultIn accordance with EN 746-2 a restart may be conducted only if the safety of the installation is not impaired Restart is recommended for burners which occasionally display unstable behaviour during operationThe precondition for a restart is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the application

Parameters gt Behaviour during operation gt Fault lock-out or restart

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 31: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

31

4 6 Switchable gas valve V2 on PFU LParameter 26Parameter 26 = 0 Gas valve V2 opens with the operating signalParameter 26 = 1 Gas valve V2 opens with the air valve during operation

VAG

SPSPLCAPI

DI

L1 N PE

P A

P

DI

PFU 760L 10e

2c 4c

26e 10c

22e

22a

28c 16c

2e 4e

30e 10a

TZI

26a

BVA + IC 40

4

7

18e

VBY

ϑ1

microC

M

A switchable gas solenoid valve V2 can be activated with the PFUL If Parameter 26 is set to 1 gas valve V2 can be activated synchronously with the air valve during operation via the input for the external activation of the air valve (terminals 10a12a)

Parameters

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 32: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

32

4 7 Air valve control PFU LParameter 30 Behaviour of the air valve during operationParameter 31 Behaviour of the air valve during start-upParameter 32 Behaviour of the air valve in the event of a fault lock-outThe PFUL features an adjustable air valve control The display shows that purging is currently being carried out with P0 A indicates that the air valve is being activated for cooling or heatingThe PFUL supports the following functionsndash Purgendash Cooling in start-up positionstandbyndash Switching of the burner between low and high burner

output during operation via the air valvendash To start up the burner as intended external activation of

the air valve can be blocked during start-up (prevents synchronization problems between the PFU and the central control system)

ndash Controlling the air valve so that it ndash opens with valve V1 ndash opens with valve V2ndash Low fire over run time tKN after a controlled shut-down

4 7 1 PurgeParameter 42 = 0 The air valve is closed when voltage is applied to terminal 30eParameter 42 = 1 The air valve is opened when voltage is applied to terminal 30eIn the case of multiple burner applications burners with mechanical combustion air supply are used The air for com-bustion and pre-purge is supplied by a central fan controlled by a separate logic This logic determines the purging timeThe PFUL supports centrally-controlled pre-purge or post-purge The PFUL is informed that purging is currently being performed by input 30e It then opens the air valve regard-less of the status of the other inputs (purging has priority) The display indicates P0

4 7 2 Cooling in start-up positionstandbyThe air valve can be activated externally via input 10a for cool-ing in the start-up position During activation of the air valve the display shows A0 indicating that cooling is currently being carried out

4 7 3 Burner startParameters 30 and 31 determine the behaviour of the air valve during burner start

Parameters

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 33: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

33

4 7 4 Air valve opens in the case of external activation (not during start-up)

tSA

tZ

A4 02 03 00 A0

t tFS

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

VRR

TZI

GIKB

VASN

Parameter 30 = 0 The air valve opens if it is activated exter-nally by input 10aParameter 31 = 0 The air valve remains closed during start-up even if it is activated externallyThese settings are required on burners on which the gasair ratio is controlled by a pneumatic ratio control system and which also need to be started at low fire eg on two-stage-controlled burners In this case activation of the air valve during burner start via input 10a must be preventedExternal control allows switchover between low fire and high fire during operationThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 34: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

34

4 7 5 Air valve opens in the case of external activation (even during start-up)

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 0 The air valve opens if it is activated exter-nally via input 10aParameter 31 = 1 The air valve can be activated even during start-upThese settings may be selected only if the burner can start with full air capacityThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 35: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

35Parameters gt Air valve control PFU L

4 7 6 Air valve opens with valve V1

tSA

tZ

A4 A2 A3 00 A0 00

t tFS

A0

A10a22e

26a

18e

2cndash4c

88

10e26e30a

28c

2endash4e

16c V1V2

ϑ1

VRR BICR

VGL

LEH EKO

GEH

EKO

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

TZI

Parameter 30 = 1The air valve opens simultaneously with valve V1Application Single-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 36: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

36

4 7 7 Air valve opens with valve V2

tSA

tZ

A4 02 03 00

t tFS

00 A0

A10a22e

26a16c18e

2cndash4c

88

10e26e30a

28c

2endash4e

V1V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 30 = 2The air valve opens simultaneously with valve V2Application Two-stage-controlled burner is switched ONOFF via the ϑ inputThe air valve can be activated externally via input 10a for cool-ing the burner in the start-up positionstandby

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 37: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

37

4 7 8 Low fire over run time tKN after a controlled shut-down

00A4

ttKN

22e

26a16c

18e2cndash4c

88

10e26e30a

28c

2endash4e

V1

V2

ϑ

VRR

VAG

TZI

UV

PFU 760L

A

P

L1

SPSPLCAPI

ϑ

Parameter 36Settings 0 3 5 10 15 25 or 60 (low fire over run time in seconds)This parameter is applicable to systems with a pneumatic ratio control system and OnOff controlParameter 36 = 0 (low fire over run time tKN = 0 s) Without low fire over run the gas side is closed immediately owing to the quick-closing gas valve in the case of OnOff control The air side closes more slowly The air flowing in during the closing time increases the O2 content in the combustion chamberParameter 36 = 3 5 10 15 25 or 60 (low fire over run time tKN = 3 5 10 15 25 or 60 s) The air valve closes slowly after the activation signal has been switched off The gas valve remains open for tKN This means that the burner after deactivation of the start-up signal (ϑ) is initially adjusted down to low fire and then switched off completelyUsing the low fire over run function reduces the O2 content in the furnace atmosphereFlame control is still operational Can be used only in the case of a pneumatic airgas ratio control system and OnOff control Its must be ensured that no excess gas occurs

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 38: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

38

4 7 9 Behaviour of the air valve in the event of a fault lock-outParameter 32This determines whether the air valve can be activated in the case of a fault lock-outParameter 32 = 0The air valve is closed in the event of a fault It cannot be activated externally via terminal 10aParameter 32 = 1The air valve can be activated externally via input 10a even during a fault eg for cooling

Parameters gt Air valve control PFU L

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 39: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

39

4 8 Manual operationFor convenient setting of the burner or analyzing faultsThe parameter display is not available in Manual mode Manual mode can be accessed only if the unit was not in Fault state before switching off The following timesfunctions are not active in Manual mode start-up attempts restart minimum combustion time and cycle lockIf the ResetInformation button is pressed for 2 s during switch-on the PFU reverts to Manual mode Two dots blink on the displayIn this operating mode the burner control unit operates inde-pendently of the status of the inputs (apart from the pre-purge input and the safety interlocks These are of higher priority and will be processed first)Each time after the button is pressed again the PFU moves to the next section of the program sequence and stops there After approx 3 s the flame signal will be displayed instead of the program parameter Briefly pressing the ResetInforma-tion button (lt 1 s) displays the relevant Manual mode step If there is flame simulation during the start-up the flame signal is displayed immediatelyOn units with air valve control the air valve can be opened and closed repeatedly by pressing the button during operationManual mode can be terminated by switching off the PFU (OnOff button)

4 8 1 Manual mode limited to 5 minutesParameter 34Parameter 34 determines when Manual mode is terminatedParameter 34 = 0 Manual mode is not limited in time If this function has been selected operation of the furnace may be continued manually in the event of failure of the central control systemParameter 34 = 1 Manual mode ends automatically five minutes after the last time the button was pressed The PFU then moves abruptly back to start-up positionstandby

4 9 PasswordParameter 50(Four-digit) password saved to protect parameter settings To prevent unauthorized changes to parameter settings a password is stored in parameter 50 Changes to parameter settings can only be made once this number has been entered The password can be changed using BCSoftNote the effect of parameter settings on the safe functioning of your systemThe password set at the factory can be found in the delivery note supplied

Parameters

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 40: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

40

4 10 Multi-flame controlParameter 45

24 V

30a

32c

30e

2a230V

6e

4c

N

4e

PFF 704

6a

L1

8a

8e

230V

12e

10c

10e

12a

18a

18e

230V

22e

20c

20e

22a

24a

24e

230V

28e

26c

26e

28a

2e

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e

NIZ

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

0 V

Parameter 45 = 0 Multi-flame control is switched offParameter 45 = 1 Multi-flame control is switched on The parameter must be set to 1 to ensure that the flames are monitored

Parameters

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 41: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

41

5 Selection5 1 Safety timePlease quote the safety time tSA when ordering

PN

PZ 033 x PN P Zmax = 350 kW

tSA

le 70 kW

gt 70 kW

5 s

3 s

le 350 kW

gt 350 kW

10 s

10 s

5 s

EN 746-2

0 infin

PZ 01 x PN P Zmax = 350 kW

tSA = 3 s 5 s or 10 sPN = Rated heat outputPZ = Ignition capacityThe safety time of the burner control unit depends on the burner type the burner output and the respective application

Burner with mechanical combustion air supply

Burner output

5 1 1 Calculating the safety time tSA

Natural draught burner with direct ignitionNatural draught burner with pilot burner

kWSafety time

on start-up tSA

s

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 42: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

42 Selection

5 2 Selection tableType L T N D U K1 K2PFU 760

If ldquononerdquo this specifi cation is omitted = standard = available

Order examplePFU 760LT

5 3 Type codeCode DescriptionL Air valve control

Mains voltageT 220 ndash 240 V AC -15+10 5060 HzN 110 ndash 120 V AC -15+10 5060 HzD Digital input to interrupt fl ame controlU Preparation for UV sensor for continuous operation UVD 1K1 Compatible with PFSPFDK2 PFU 778

If ldquononerdquo this specifi cation is omitted

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 43: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

43

6 Project planning information6 1 Cable selectionUse mains cable suitable for the type of operation and com-plying with local regulations Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields

6 1 1 Ignition cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 5 m recommended lt 1 m Screw the igni-tion cable securely into the ignition transformer and run to the burner by the shortest possible route The longer the ignition cable the lower the ignition capacity Only use radio interference suppressed electrode adapters (with 1 kΩ resistor) for ignition electrodes see page 49 (Acces-sories) Do not lay UVionization cable and ignition cables together and lay them as far apart as possible

6 1 2 Ionization cableUse unscreened high-voltage cable see page 49 (Accessories) Cable length max 100 m Avoid external electrical interfer-ence Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several ionization cables can be routed together

6 1 3 UV cableCable length max 100 m Avoid external electrical interference Install as far as possible from mains and ignition cables and interference from electro-magnetic sources If possible do not lay in a metal conduit Several UV cables can be routed together

6 2 Ignition electrode6 2 1 Electrode gapGap between electrode and burner ground 2 mm plusmn 05 mm

6 2 2 Star electrodesWe recommend using 75 kV ignition transformers on burners with star electrodes

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 44: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

44 Project planning information

6 3 Minimum combustion timeEven if the start-up signal (ϑ) is applied only briefly the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a faultThe minimum combustion time tB can be extended beyond the safety time tSA to max 25 s

6 4 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimum and maximum gas pressure tightness control) must isolate ter-minal 26e from the voltage supply If the safety interlock is interrupted this is indicated by a blinking 51 on the displayIf the safety interlocks fail an immediate program abort with switch-off of all outputs occurs (even during the safety time) If the safety interlocks are operational again or the unit is switched back on the program run is restarted in standby

6 5 Emergency stop6 5 1 In the event of fire or electric shockIf there is a risk of fire electric shock or similar inputs L1 N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply ndash this should be reflected in the wiring on site

6 5 2 Via the safety interlocks (limits)The safety interlock turns off the power to input 26e such as in the event of air deficiency or similar

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 45: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

45 Project planning information

6 6 Reset6 6 1 Parallel resetSeveral burner control units can be reset in parallel using the external button The PFU cannot be reset by mains failure

6 6 2 Permanent remote resetPermanent remote reset gives rise to a malfunction If a remote reset signal is permanently applied to terminals 10c12c 52 flashes on the display to indicate a faultReset with a pulse lt 1 s

6 6 3 Automatic remote reset (PLC)In the case of automatic remote reset (PLC) the reset pulse duration should not exceed 1 second Check compliance with standardsIf a fault is acknowledged by remote reset too often error 10 (Too many remote resets) is displayed The error can only be acknowledged with the ResetInformation button on the unitThe burner malfunction must be remedied The malfunction can not be remedied by changing the method of activation

6 6 4 Burner startA furnace start may only be initiated if it has been ensured using an appropriate procedure that there is no combustible mixture in the combustionprocessing chamber in the con-nected areas or in the exhaust gas system (heat exchanger dust collector) This can be achieved by pre-purge which occurs immediately before ignition or within the period speci-fied in the operating instructionsIn the case of multiple burner applications pre-purge is not necessary after a controlled burner shut-downNote the requirements of the Standards For exceptions see Standards

6 6 5 Restart and start-up attemptsThe precondition for a restartstart-up attempt is that activation of the restart allows the burner to restart as intended (in all operating phases) In this case it must be ensured that the program sequence started by the PFU matches the applicationNote the requirements of the Standards For exceptions see Standards

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 46: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

46

6 7 Fault signallingThe fault signalling contact opens as soon as the mains volt-age fails

6 8 Protecting the burner from overloadTo protect the unit against overload by frequent cycling the maximum number of start-ups per minute is limited for the PFU Excessive cycling triggers a fault message (blinking 53 ) The max number of start-ups per minute depends on the safety time tSA

tSA [s] Ignition transformer TZI Max start-upsmin3 5-15100 65 5-15100 510 5-15100 4

6 9 InstallationInstallation position anyInstallation in 19 module subracks only see page 50 (Module subracks)Install in clean environment ensuring enclosure IP 54 or higher whereby no condensation is permittedCable length between PFU and burner max 100 m

6 10 WiringThe PFU is suitable for hard wiring only Do not reverse phase and neutral conductor Different phases of a three-phase current system must not be installed at the PFU No voltage may be connected to the valve and ignition outputs

6 10 1 UVS sensor wiringConnect the UVS sensor directly to the PFU Operating the sensor with incorrect polarity or voltage can lead to destruc-tion of the sensor

6 11 PFU switched offThe PFU cannot be activated when no mains voltage is applied or when it is switched off The fault signalling contact is only closed when the unit is supplied with voltage and switched onIf the unit is switched off an immediate program abort with switch-off of all outputs occurs (even during the safety time) When the unit is switched on the program run is restarted in standby

Project planning information

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 47: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

47Project planning information

6 12 Furnace controlSwitch on the system to start up the furnace then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended To shut down the furnace first disconnect the burner control unit from the temperature control (burner ON signal) then disconnect the safety interlocks and finally switch off the system

6 13 Note on EC type-examinationSince EN 298 (1993) does not describe all functions of the PFU the operator is responsible for ensuring that all parameters and functions are matched to the respective application

6 14 Mains switchThe mains switch in the unit isolates the PFU on two poles from the mains It does not meet the requirements of EN 50156-12004 (522 Switch disconnectors) set out in chapter 5 for a device to disconnect the power supply Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156 it does allow the burner to be isolated functionally from the central control system This function is required for manual operation and in the case of PROFIBUS units to switch off the unit without causing BUS errors Disconnection for electrical maintenance work is to be implemented by removing the unit or with an external switch per unit or group only in accordance with Standard EN 50156

6 15 Changing parametersIn certain cases it may be necessary to change the default settings Using a separate software package and a PC opto-adapter it is possible to modify certain parameters on the PFU such as the switch-off threshold of the flame amplifier or the behaviour in the event of a flame failureThe software package with PC opto-adapter as well as ldquoChanged parametersrdquo stickers are available as accesso-ries ndash see section entitled ldquoAccessoriesrdquoThe unit parameters set at the factory are specified in the delivery noteDocument changed parameters in BCSoft using the protocol function and enclose the protocol with the plant documentationIf a replacement is ordered for a PFU with changed parameters refer to the protocol for details

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 48: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

48

7 Flame control7 1 With ionization sensorThe PFU generates an alternating voltage (230 V AC) between the sensing electrode and burner ground The flame rectifies this voltage Only the DC signal (depending on the switch-off threshold) is recognized by the burner control unit as a flame signalA flame cannot be simulated Ignition and monitoring with a single electrode is possible

7 2 With UV sensorA UV tube inside the UV sensor detects the ultraviolet light of a flame It does not respond to sunlight incandescent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace wallsIn the event of incident UV radiation the UV sensor rectifies the supplied alternating voltage As with ionization control the burner control unit only detects this DC signalWhen using UV sensors of Type UVS the burner control unit may be used for intermittent operation only This means that operation must be interrupted at least once every 24 hours This can be programmed using parameter 35For further information see brochure UVSThe burner control unit PFUU is prepared for UV sensor UVD 1 This enables continuous operation For further information see Technical Information Bulletin UVD

7 3 Via the temperature in high temperature equipmentHigh temperature equipment is defined as a thermoprocessing installation in which the wall temperature of the combustion chamber andor the processing chamber exceeds 750degC Burner control unit PFUD features a special ldquoHigh temperature operationrdquo function During heating up standard monitoring methods (ionization or UV) must be used for flame control When the working temperature has exceeded 750degC indirect flame control can be taken over by a central monitoring device When the DI input (terminal 22a) is activated the burner control unit reverts to this operating modeImportant In ldquoHigh temperature operationrdquo ie with the DI input being activated burner control unit PFUD does not evaluate the flame signal The safety function of the burner control unitrsquos flame control is deactivated during this operat-ing phase

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 49: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

49

8 Accessories8 1 High-voltage cableFZLSi 17 up to 180degC Order No 04250410FZLK 17 up to 80degC Order No 04250409

8 2 BCSoft

Opto-adapter including BCSoft CD-ROM Order No 74960437The current software can be downloaded from our Internet site at wwwdocuthekcom To do so you need to register in the DOCUTHEK

8 3 Stickers for labelling

Brenner 1

Zone 3

For printing with laser print-ers plotters or engraving machines 27 times 18 mm or 28 times 175 mmColour silver

8 4 ldquoChanged parametersrdquo stickers

D-49018 Osnabruumlck Germany

Achtung geaumlnderte ParameterDie Angaben auf dem Typenschild gelten nicht mehr in vollem UmfangAktuelle Parameter direkt auslesen

Important changed parametersThe details on the type label are no longer completely accurate Read the current parameters direct from the unit

Attention paramegravetres modifieacutes Les informations figurant sur la plaque signaleacutetique ne sont plus valables dans leur inteacutegraliteacute Veuillez vous reacutefeacuterer directement aux paramegravetres actualiseacutes

Affix on the connection diagram of the PFU following changes to unit parameters set at the factory100 pcs Order No 74921492

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 50: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

50 Accessories

8 5 Radio interference suppressed electrode adapters Plug cap 4 mm interference-suppressed Order No 04115308Straight adapter 6 mm interference-suppressed Order No 04115306

8 6 Socket connectorsType Order NoSocket connector E 48-pin solder tag connection 04120148Socket connector E 48-pin wire-wrap connection 04120158

8 7 Module subracks

Module subracks BGT S-9U1 for PFP 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rearSlots 1ndash9 for PFU 760 slot 10 for PFP 700Order No 84402281

Module subrack BGT SM-811 for MPT 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear single-zone operation for MPT 700 operating modes 1-4 two-zone operation for MPT 700 operating modes 1-4 but max 4 burners per zoneSlot 1 for MPT 700 slots 2ndash9 for PFU 760 slot 10 for PFP 700Order No 84402282 (no illustration provided)

Module subrack BGT SA-9U1DP for PFA 700 PFU 760comprising module subrack printed-circuit board with rear terminal strip function-tested standard documentation guide rails without partial front plates screw terminals at the rear relays and screw terminals for four free inputs and four free outputsSlot 1 for PFA 700 slots 2ndash10 for PFU 778 without digital input connection to PROFIBUS-DP with D-Sub socketOrder No 84402283 (no illustration provided)

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 51: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

51

8ace30a

32c

F1

12aceN

L1

PFP 700

U I

24 V=600 mA

0 V

O

I

S0

230 V

115 V

S1

8 8 Power supply PFP 700For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704 Operating status display on the front plate PFP switches off in the event of an output overloadOutput voltage 24 V output rating 14 VA

Accessories

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 52: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

52

2e2a2c

4e 6c

8e1

115 V~

8c

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFR 704

8a

6e6a230 V~

24 V=~

0 V

10e10a10c

12e 16c

14e214c

14a

16e16a

0 V

18e18a18c

20e 24c

22e322c

22a

24e24a

0 V

26e26a26c

28e 32c

30e430c

30a

32e32a

0 V

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

115 V~230 V~

24 V=~

8 9 Relay module PFR 704For contact multiplication eg if several air valves are activated via one control signal for pre-purge or for heatingcooling switchover when using an MPT Switching status display on the front plateInput voltage 110120 V AC -15+10 5060 Hz 220240 V AC -15+10 5060 Hz 24 V ACDC plusmn 10Current per relay 25 mAContact rating of floating outputs max 2 A 264 V (not fused internally)

Accessories

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 53: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

53

30a32c30e

2a

2e

230V

F2 6e

4c

P11

+-

N

F1 4e

max

2 A

264

Vm

ax 2

A 2

64 V

max

2 A

264

Vm

ax 2

A 2

64 V

PFF 7x4

4a

6c6a

L1

8a

8e230V

F4 12e

10c

P22

+-

F3 10e

10a

12c12a

18a

18e230V

F6 22e

20c

P33

+-

F5 20e

20a

22c22a

24a

24e230V

F8 28eP1ndashP4 PFF 704

26c

P44

+-

F7 26e

26a

28c28a

OI

S0

230 V115 V

S1

IZN

L1L1N

2a2e

30eUVS

123

Z

IZN

L1

IZN

L1

IZN

L1

L1N

8a8e

30eUVS

123

Z

L1N

18a18e

30eUVS

123

Z

L1N

24a24e

30eUVS

123

Z

8 10 Flame detector PFF 704For flame detection or multi-flame control in conjunction with PFU with 4 independent flame detectors For intermittent op-eration with ionization or UV controlPower consumption 10 VAIonization voltage 230 V ACMax flame signal cable length 100 mCut-off sensitivity of the flame amplifiers adjustable between 1 microA and 10 microA (factory default setting 1 microA)Contact rating max 2 AMains voltage 110 ndash 240 V AC 1510 5060 HzFurther information can be found in brochure PF 19rdquo

Accessories

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 54: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

54

32b30aN

L1

8b11b12b

PFA 700

microC

15b16b

1c

9c

VP

1 PFU

9 PFU

RxDTxD-P

RxDTxD-N

DGND

0 V

24 V=

hellip

hellip

ϑ

10c 1 PFU

9 PFU

hellip2

1

1a

9a

1 PFU

9 PFU

hellip

10a

18a

1 PFU

9 PFU

hellip

19a

23a

1 PFU

5 PFU

hellip

20c

23c

6 PFU

9 PFU

30c

hellip

24 V

0 V24 V hellip

1

4

14b

18b

21b22b

hellip hellip

1

4

23b

26b

24 V

24 V

IO

18c

PFU19c

17b

30e

26ePFU

24 V

L1

PR

OFI

BU

S D

P

8 11 Field bus interface PFA 700For connection of up to nine automatic burner control units PFU 760 to industrial communication networks using PROFIBUS-DP in order to transfer measuring control and regulation signals as a bundle4 digital inputs 24 V DC plusmn 10 lt 10 mA 4 digital outputs relay contact max 1 A 264 V (not fused internally)Mains voltage 110 ndash 240 V AC -15+10 5060 HzFurther information can be found in brochure PFA

Accessories

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 55: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

55

F1 2b4b

MPT 700

12ndash24 V

0 V

12ndash24 V

0 ndash 100

GND

16b

14zE1

14dE2

16zE3

14b

10b12b

0 V

2z A1

6b8b

COM

L130b30z

30d

N28b28z

28d

PE32b32z

32d

20b20zmA 1

20dmA 2

GND100 ndash 0

18b18z

18d

2d A2

4z A3

4d A4

6z A5

6d A6

8z A7

8d A8

10z 1

12z

10d

microC

2

8888

88

8 12 Impulse system MPT 700With 11 outputs for activation of burner control units PFU 780 The furnace atmosphere is circulated thanks to intermittent operation and thereby constant temperature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensuredMains voltage 95 ndash 240 V AC plusmn 10 5060 HzPower consumption 10 VAAdditional auxiliary voltage 12 ndash 24 V DC plusmn 10 max 11 AController inputs 2 x 0(4) ndash 20 mA with common ground float-ing load impedance approx 225 ΩThree-point step input floating 12 ndash 24 V DC load impedance approx 27 kΩDigital inputs E1 ndash E3 with common ground floating 12 ndash 24 V DC load impedance approx 27 kΩFurther information can be found in brochure MPT

Accessories

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 56: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

56

9 Technical dataMains voltage 220240 V AC -15+10 5060 Hz or 110120 V AC -15+10 5060 Hz for grounded and ungrounded mainsPower consumption lt 8 VAControl inputs Input voltagecurrent Burner air valve multi-flame control and remote reset 24 V DC plusmn 10 lt 7 mA per inputInput voltage for safety interlocks digital input DI and purge = mains voltageInput voltage of signal inputs Rated value 110120 V AC 220240 V ACSignal ldquo1rdquo 80 ndash 132 V 160 ndash 264 VSignal ldquo0rdquo 0 ndash 20 V 0 ndash 40 VFrequency 5060 Hz 5060 Hz

Rated value 24 V DCSignal ldquo1rdquo 24 V plusmn10Signal ldquo0rdquo lt 1 V

Inherent currentSignal ldquo1rdquo typ 5 mA

Output voltage for voltage-related outputs = mains voltage

Contact ratingGas valve V1 V2 Max 1 A resistive Max 1 A cos ϕ 03Air valve Max 1 A resistive Max 1 A cos ϕ 03Ignition Max 1 A resistive Max 1 A cos ϕ 03Number of oper-ating cycles

Max 1000000 typically 400000

Max 250000 typically 100000

Output current max 2 A per output but total current for valves and ignition transformer max 25 ANumber of operating cycles Mains switch 1000 ResetInformation button 1000

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 57: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

57

Signalling contacts max 24 V 1 AFlame control Sensor voltage approx 230 V AC Sensor current gt 1 μA Length of sensor cable max 100 mFuse in unit F1 315 A slow-acting H pursuant to IEC 127-25 F2 315 A slow-acting H pursuant to IEC 127-25Ambient temperature -20 to +60degC (-4 to +140degF) Climate no condensation permittedEnclosure IP 00 pursuant to IEC 529 after installing in a 19 module subrack according to the in-structions eg type BGT the front corresponds to IP 20InputOutput safety circuit All the inputs and outputs marked ldquo rdquo (see connection dia-grams) may be used for safety tasksWeight approx 650 g (23 oz)

Technical data

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 58: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

58 Technical data

9 1 Safety-specific characteristic valuesIn the case of ionization control suitable for Safety Integrity Level

SIL 3

Diagnostic coverage DC 979

Type of subsystem Type B to EN 61508-2 74314

Mode of operation High demand mode pursu-ant to EN 61508-4 3512

Mean probability of dan-gerous failure PFHD

134 x 10-8 lh

Mean time to dangerous failure MTTFdSafe failure fraction SFF 992

The specified values apply for the combination with ionization electrode (sensor) and PFU 760 (logic)

Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)

PL SILa ndashb 1c 1d 2e 3

Pursuant to EN ISO 13849-12006 Table 4 the PFU can be used up to PL e

Max service life under operating conditions20 years after date of production plus max 12 year in stor-age prior to first useFor a glossary of terms see page 62 (Glossary)

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 59: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

59

F1 F2

00AB

C

D

E

9 2 Operating controlsA 2-digit 7-segment displayB ResetInformation button to reset the system after a fault

or to scan parameters on the displayC Mains switchD Optical interfaceE Type label

Technical data

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 60: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

60

10 Maintenance cyclesBurner control unit PFU requires little servicing

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 61: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

61

11 Legend88 Display

88 Blinking display

ReadySafety interlocks (Limits)Burner start-up signal

DI Digital inputIgnition transformer

Gas valve

Air valveP PurgeA Ext air valve control

Flame signal1 Burner operating signal

Fault signalResetInput signalOutput signalFlame simulation check

tW Waiting time ge 2 stSA Safety time on start-up 3 s 5 s or 10 stSB Safety time during operation lt 1 s or lt 2 stZ Ignition time 2 s 3 s or 6 s

tLV Flame simulation delay time 25 stFS Flame proving period 0 ndash 25 stB Minimum combustion time tSA up to max 25 s

tBP Minimum burner pause time 0 ndash 250 s

tKN Low fire over run time 0 s 5 s 15 s or 25 sInputOutput safety circuit

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 62: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

62

12 Glossary12 1 Waiting time tW

tW t tZ

tSA

02 02 01 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

Once the start-up signal ϑ has been applied the waiting time tW starts to elapse During this time a self-test is conducted to detect errors in internal and external circuit components If no malfunction is detected the burner will start up

12 2 Safety time on start-up tSA This refers to the period of time between switching on and switching off of the gas valve when no flame signal is detected The safety time on start-up tSA (3 5 or 10 s) is the minimum operating time of the burner and burner control unit

12 3 Ignition time tZ If no malfunction is detected during the waiting time tW the ignition time tZ then starts to elapse Voltage is supplied to the pilot gas valve V1 and the ignition transformer and the burner is ignited The duration of the ignition time is either 2 3 or 7 seconds (depending on safety time tSA selected)

12 4 Flame simulationFlame simulation delay time tLV

t

30e10e28c16c

26a18e

L1

V1

V2

01 01 88

tW tLV

2endash4e2cndash4c

ϑ

An extraneous signal (flame simulation) is a flame signal that is detected although there should be no flame according to the program sequence If such an extraneous signal is detected the flame simulation delay time tLV starts to elapse If the flame simulation is discontinued during the flame simu-lation delay time tLV start-up can be initiated or operation continued Otherwise a fault lock-out occurs

12 5 Safety time during operation tSB

tSB t

04 04 30e10e28c16c

26a18e

L1

V1

V2

88

2endash4e2cndash4c

ϑ

If the flame fails during operation the valve outputs are dis-connected within the safety time tSB

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 63: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

63

The default safety time during operation tSB in accordance with EN 298 is 1 second In accordance with EN 746-2 the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (see ldquoProject plan-ning informationrdquo) Note the requirements of the Standards

12 6 Flame signalIf a flame is detected the flame detector will supply a flame signal

12 7 Fault lock-outIn the event of a fault lock-out all valves and the ignition trans-former are disconnected from the electrical power supply and a fault is signalled Resetting must take place manually following a fault lock-out

12 8 Safety interlocks (Limits)The limiters in the safety interlock (linking of all the relevant safety control and switching equipment for the use of the application eg safety temperature limiter minimummaxi-mum gas pressure) must isolate input from the voltage supply

12 9 Pilot gas valve V1The start fuel flow rate for the burner is released by pilot gas valve V1 It opens when the safety time on start-up tSA starts to elapse It remains open until the burner is switched off again by a normal shut-down or fault lock-out

12 10 Main gas valve V2Once the safety time on start-up tSA has elapsed the main gas valve V2 is opened It remains open until the burner is switched off or a fault is signalled

N (L2)

22e

16c

N

26e

30a

32c

230 V

18e

2a4aa

2e4es

2c4cm

sk1

V2

V1

L1 (L1)

max

1 A

24

V

24 V

0 V

10c

12c

10a

12a

30e

22a

P

DI

A

28c

26a

ϑ1 10e

12e

24c20c

8a8c8e0 V

8a8c

8e

24 V

PFF 704

NIZ

26a

28cN

28cN

20c26a

24cUVS

123

microC

SK

A

S

F1

PFU 760 PFU 760L)(

12 11 Continuous operationThe gas burner runs continuously for more than 24 hours

12 12 Air valveThe air valve can be usedndash for coolingndash for purgingndash to control the burner output in ONOFF mode and in High

Low mode when using a pneumatic airgas ratio control system

Glossary

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 64: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

64

12 13 Diagnostic coverage DCMeasure of the effectiveness of diagnostics which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failuresNOTE Diagnostic coverage can exist for the whole or parts of a safety-related system For example diagnostic cover-age could exist for sensors andor logic system andor final elements Unit from EN ISO 13849-12008

12 14 Mode of operationHigh demand mode or continuous modeOperating mode where the frequency of demands for opera-tion made on a safety-related system is greater than one per year or greater than twice the proof-test frequencyfrom EN 61508-42001

12 15 Safe failure fraction SFFFraction of safe failures related to all failures which are as-sumed to appearfrom EN 13611A22011

12 16 Probability of dangerous failure PFHD Value describing the likelihood of dangerous failure per hour of a component for high demand mode or continuous mode Unit 1hfrom EN 13611A22011

12 17 Mean time to dangerous failure MTTFd Expectation of the mean time to dangerous failurefrom EN ISO 13849-12008

Glossary

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden
Page 65: 6.2.1.4 Edition 05 - Lesman … · PFU 760 · Edition 05.11 4 1 Application The burner control units PFU 760 control, ignite and moni-tor gas burners for intermittent or continuous

PFU 760 middot Edition 0511

65

FeedbackFinally we are offering you the opportunity to assess this ldquoTechnical Information (TI)rdquo and to give us your opinion so that we can improve our documents further and suit them to your needs

ClarityFound information quicklySearched for a long timeDidnrsquot find informationWhat is missing

ComprehensionCoherentToo complicatedNo answer

ScopeToo littleSufficientToo wideNo answer

No answer

NavigationI can find my way aroundI got ldquolostrdquoNo answer

UseTo get to know the productTo choose a productPlanningTo look for information

My scope of functionsTechnical departmentSalesNo answer

Remarks

(Adobe Reader 7 or higher required) wwwadobecom

Elster GmbH Postfach 2809 middot 49018 Osnabruumlck Strotheweg 1 middot 49504 Lotte (Buumlren) GermanyT +49 541 1214-0 F +49 541 1214-370 infokromschroedercomwwwkromschroedercom wwwelstercom

The current addresses of our international agents are available on the Internetwwwkromschroederdeindexphpid=718ampL=1

We reserve the right to make technical modifications in the interests of progressCopyright copy 2007 ndash 2011 Elster Group All rights reserved

Contact

0325

0721

Feedback

  • Burner control unit PFU 760
  • Contents
  • 1 Application
    • 11 Examples of application
      • 111 Staged OnOff burner control
      • 112 Staged HighLow burner control
      • 113 Two-stage-controlled burner
      • 114 Modulating-controlled burner
      • 116 PFU for PROFIBUS-DP with PFA 700
      • 115 PFU 760D High temperature equipment
          • 2 Certification
          • 3 Function
            • 31 Connection diagram
              • 311 PFU 760
              • 312 PFU 760K1
              • 313 PFU 760K2
                • 32 PFU 760 program sequence
                • 33 Program status and fault messages
                  • 4 Parameters
                    • 41 Scanning the parameters
                    • 42 Flame control
                      • 421 Burner flame signal
                      • 422 Program status when the most recent fault occurred
                      • 423 Switch-off threshold of the flame amplifier
                      • 424 High temperature operation with PFUD
                      • 425 UVS check
                        • 43 Behaviour in start-up positionstandby
                          • 431 Flame simulation check in start-up positionstandby
                          • 432 Minimum burner pause time tBP
                            • 44 Behaviour during start-up
                              • 441 Safety time on start-up tSA
                              • 442 Flame proving period tFS
                              • 443 Minimum combustion time tB
                              • 444 Burner start-up attempts
                                • 45 Behaviour during operation
                                  • 451 Safety time during operation tSB for V1 and V2
                                  • 452 Fault lock-out or restart
                                    • 46 Switchable gas valve V2 on PFUL
                                    • 47 Air valve control PFUL
                                      • 471 Purge
                                      • 472 Cooling in start-up positionstandby
                                      • 473 Burner start
                                      • 474 Air valve opens in the case of external activation (not during start-up)
                                      • 475 Air valve opens in the case of external activation (even during start-up)
                                      • 476 Air valve opens with valve V1
                                      • 477 Air valve opens with valve V2
                                      • 478 Low fire over run time tKN after a controlled shut-down
                                      • 479 Behaviour of the air valve in the event of a fault lock-out
                                        • 48 Manual operation
                                          • 481 Manual mode limited to 5 minutes
                                            • 49 Password
                                            • 410 Multi-flame control
                                              • 5 Selection
                                                • 51 Safety time
                                                  • 511 Calculating the safety time tSA
                                                    • 52 Selection table
                                                    • 53 Type code
                                                      • 6 Project planning information
                                                        • 61 Cable selection
                                                          • 611 Ignition cable
                                                          • 612 Ionization cable
                                                          • 613 UV cable
                                                            • 62 Ignition electrode
                                                              • 621 Electrode gap
                                                              • 622 Star electrodes
                                                                • 63 Minimum combustion time
                                                                • 64 Safety interlocks (Limits)
                                                                • 65 Emergency stop
                                                                  • 651 In the event of fire or electric shock
                                                                  • 652 Via the safety interlocks (limits)
                                                                    • 66 Reset
                                                                      • 661 Parallel reset
                                                                      • 662 Permanent remote reset
                                                                      • 663 Automatic remote reset (PLC)
                                                                      • 664 Burner start
                                                                      • 665 Restart and start-up attempts
                                                                        • 67 Fault signalling
                                                                        • 68 Protecting the burner from overload
                                                                        • 69 Installation
                                                                        • 610 Wiring
                                                                          • 6101 UVS sensor wiring
                                                                            • 611 PFU switched off
                                                                            • 612 Furnace control
                                                                            • 613 Note on EC type-examination
                                                                            • 614 Mains switch
                                                                            • 615 Changing parameters
                                                                              • 7 Flame control
                                                                                • 71 With ionization sensor
                                                                                • 72 With UV sensor
                                                                                • 73 Via the temperature in high temperature equipment
                                                                                  • 8 Accessories
                                                                                    • 81 High-voltage cable
                                                                                    • 82 BCSoft
                                                                                    • 83 Stickers for labelling
                                                                                    • 84 ldquoChanged parametersrdquo stickers
                                                                                    • 85 Radio interference suppressed electrode adapters
                                                                                    • 86 Socket connectors
                                                                                    • 87 Module subracks
                                                                                    • 88 Power supply PFP 700
                                                                                    • 89 Relay module PFR 704
                                                                                    • 810 Flame detector PFF 704
                                                                                    • 811 Field bus interface PFA 700
                                                                                    • 812 Impulse system MPT 700
                                                                                      • 9 Technical data
                                                                                        • 91 Safety-specific characteristic values
                                                                                        • 92 Operating controls
                                                                                          • 10 Maintenance cycles
                                                                                          • 11 Legend
                                                                                          • 12 Glossary
                                                                                            • 121 Waiting time tW
                                                                                            • 122 Safety time on start-up tSA
                                                                                            • 123 Ignition time tZ
                                                                                            • 124 Flame simulationFlame simulation delay time tLV
                                                                                            • 125 Safety time during operation tSB
                                                                                            • 126 Flame signal
                                                                                            • 127 Fault lock-out
                                                                                            • 128 Safety interlocks (Limits)
                                                                                            • 129 Pilot gas valve V1
                                                                                            • 1210 Main gas valve V2
                                                                                            • 1211 Continuous operation
                                                                                            • 1212 Air valve
                                                                                            • 1213 Diagnostic coverage DC
                                                                                            • 1214 Mode of operation
                                                                                            • 1215 Safe failure fraction SFF
                                                                                            • 1216 Probability of dangerous failure PFHD
                                                                                            • 1217 Mean time to dangerous failure MTTFd
                                                                                              • Feedback
                                                                                              • Contact
                                                                                                  1. naechste_Seite 32
                                                                                                  2. naechste_Seite 37
                                                                                                  3. naechste_Seite 33
                                                                                                  4. naechste_Seite 34
                                                                                                  5. naechste_Seite_39
                                                                                                  6. naechste_Seite 43
                                                                                                  7. naechste_Seite 35
                                                                                                  8. ftBrennerart Geblaese
                                                                                                  9. fzLeistung 1
                                                                                                  10. fz_tSA 3
                                                                                                  11. ftMeldung Ignition burner input rating at a level of 10 of nominal heat input with a maximum of 350 kW
                                                                                                  12. ftUebersicht Info nicht gefunden
                                                                                                  13. ftVerstaendlichkeit Off
                                                                                                  14. ftFehlende_Info dsavsdvsdv
                                                                                                  15. ftUmfang Off
                                                                                                  16. ftVerwendung_1 Off
                                                                                                  17. ftVerwendung_2 Produktauswahl
                                                                                                  18. ftVerwendung_3 Projektierung
                                                                                                  19. ftVerwendung_4 Off
                                                                                                  20. ftNavigation Off
                                                                                                  21. ftTaetigkeitsbereich Off
                                                                                                  22. ftBemerkung sdvsdvsdv
                                                                                                  23. Michael Rehkamp Elster Kromschroumlder>btnSenden

Recommended