Date post: | 05-Nov-2015 |
Category: |
Documents |
Upload: | jonathan-lewis |
View: | 5 times |
Download: | 0 times |
Introduction to Distance Protection
J. Gosalia
Protection Types
Differential protection
Tfr., Bus, Gen. & line diff. protection
Pilot protection
Transfer trip schemes
Under/over reaching pilot protection
Unit Protection
Over Current protection
Time over current or inst. protection
3 Zones of distance protection
Non-Unit protection
Unit Protection
Protection
In Zone fault protection
No protection for fault outside the zones
Non-Unit Protection
A B DC
Distance
Tim
e
Zone 1 Protection : line AB
Zone 2 & 3 : Back up protection for line BC and CD
Zone 2
Zone 3
Zone 1
Presentation Topics
Distance Protection
Application
Basic Principle
Theory of operation
Design
5
Distance Protection
Impedance of the line
Impedance istance
Voltage & Current transformer inputs
Current an operating force & Volt. a restraining force
Distance Protection: Principle
Current Voltage
Fault condition
Normal condition 69 Volts and 1 A load current
Fault condition 20 Volts & 10 A fault current
A B DC
Fault condition
Quick isolation of the faulted section
Damage reduction
Stress reduction
Continuity of energy
Fast operation of the distance protection
A B DC
Distance Protection: Basics
Resistance : R
Reactance : X Z
RF
A B DC
R-X Diagram
11
Basics of R-X Diagram
Reach Representation
Fault Resistance
Voltage Diagram
R-X Diagram : Basics
12
R
XZ
R-X Diagram : Relay Reach
13
R
XZR
R-X Diagram : Fault Resistance
14
R
XZR
Rf
R-X Diagram : Voltage Diagram
15
I*R
I*XI*ZR
I*Rf
I Ref
Vf
ZR
Rf
R
X
Distance Protection
IR
IX IZ
V
V-IZ
Angle = 900
IX IZ
ZI
V
IZ
+ OutputAngleComparator
>= 900
Distance Protection
IR
IX IZ
V
V-IZ
ZI
V
IZ
+ OutputAngleComparator
>= 900
Principle
Angle between the two cords drawn from the diameter
Of a circle is always 90 degrees.
Internal Fault
IR
IX IZ
V
V-IZ
Internal fault
Angle >=900
ZI
V
IZ
+ OutputAngleComparator
>= 900
External Fault
IR
IX IZ
V
V-IZ
External fault
Angle < 900
ZI
V
IZ
+ OutputAngleComparator
>= 900
Distance Protection : Design
Set line impedance Replica : Relay Reach
Convert current I in to vector IZR
Derive voltage of the system : V = Vpol
Create Vpol IZR : Measure angle with Vpol
Output if the angle = 900 or > : MHO Char.
21
Distance Protection : Ph-G Fault
For A-G fault
IZR is IA*ZR Vpol is VA Vpol IZR is VA IAZR
Polarizing voltage = Fault voltage
Self polarized Relay
B-G fault
Polarized voltage = Fault voltage = VB
Earlier designs self polarized
Self Polarized Protection
Problem
Breaker terminal Fault Fault voltage = 0
Polarized voltage Vpol = 0
No Vpol to compare with V-IZ
No operation
Solution
Memory Voltage
Memory Polarized Protection
ZI
V
IZ
+Output
Angle
Comparator
>= 900
Memory
ZI
V
IZ
+Output
Angle
Comparator
>= 900
Memory
Memory Polarized Protection
Memory Voltage Effect on MHO characteristic?
Memory Polarization
A B
G LZs
E21
E
Load Current
Pre-Fault voltage = E
Memory Polarization
A B
G LZs
E21
VF
Fault Current : IF
Pre-Fault voltage = E
Fault Voltage E = IFZs + VF
Memory Polarization
IR
IX IZR
VF
V-IZ
Angle > 900
IFZs
Vpol = V pre fault= E
E = VF + IFZs
Mho Ch. : Memory Polarization
IR
IX IZR
VF
V-IZ
IZs
Vpol = V pre fault
Memory Polarization Effect
IR
IX
IZR
VF
V-IZ
IZsVpol = V pre fault More fault resistance
Coverage due to
memory Polarization
Memory Polarization Effect
Memory Polarization: Summary
Reference voltage (Vpol) under all faults
Char. expands : More Fault coverage
Memory, Self & Cross polarizations
Cross Polarization
Healthy phase voltage Polarizing volts for a zero voltage Fault
For A-G fault: Polarizing Voltage is -(VB+VC) Cross polarizing
Memory Polarization effect
VA
VC
VB
-(VB+VC)
Distance Protection: Architecture
ZRI
V
IZ
+Output
Timer = 0.25
Cycles
Memory
Distance Protection: Architecture
ZRI
V
IZ
+Output
Memory
Phase
Shift
- 900
Phase
Detector
V-IZ in phase
Or lag
Vpol
Distance Protection: Architecture
ZR
V-IZ
Zs
Vpol
ZRI
V
IZ
+Output
Memory
Phase
Shift
- 900
Phase
Detector
V-IZ in phase
Or lag
Vpol
Distance Protection: Architecture
ZR
V-IZ
Zs
Vpol
ZR
V-IZ
Zs
Vpol
ZRI
V
IZ
+Output
Memory
Phase
Shift
- 900
Phase
Detector
V-IZ in phase
Or lag
Vpol
Memory Polarization : Questions
How protection works for
3 phase zero voltage faults?
permanent 3 phase zero voltage faults during
reclosing?
Looks like that protection can trip for a reverse faults
True?
IR
IX IZR
IZs
3 phase zero voltage Fault
ZR
V-IZ
Zs
Vpol
Protection memory of 16-20
Cycles of pre Fault Voltage
Permanent 3 ph. zero voltage
Faults during breaker reclosing
Breaker is closed with grounding chains on the breaker
Protection has no voltage in the memory
Fault voltage = 0
Protection sees only fault current.
Switch On To Fault - SOTF feature trips the breaker
Protection sees the current but no voltage following breaker close
A B
G Zs
21
Review Question - 3
Looks like that protection can trip for a reverse faults. True?
Characteristic is true only for forward faults for reverse fault protection will not operate
Zs
ZR
V-IZ
Vpol
Memory Polarization : FactsA B
G
21
ZsZL
Char. diameter : Zs - ZR Reverse Fault : ZS = Zs + ZR Substitute the value for Zs Char. diameter : Zs
ZR
V-IZ
Zs
Vpol
Memory Polarization : FactsA B
G
21
ZsZL
ZR
Zs
Char. diameter : Zs - ZR Reverse Fault : ZS = Zs + ZR Substitute the value for Zs Char. diameter : Zs
Memory Polarization : ConclusionA B
G
21
ZsZL
Memory polarized MHO :
Very secure & no operation
for reverse faults
ZR
Zs
Fault Res.: Memory Vs. Self Polarized
A B
G
21
ZsZLZs
RF
ZR
Zs
ZR
Zs
Fault Res.: Strong Vs. Weak Source
A B
G
21
ZsZLZs
RF
ZR
Zs
ZR
ZsStrong SourceWeak Source
Fault Res.: Short Vs. Long Line
G
21
ZsZLZs
RF
ZR
Zs
ZR
ZsStrong Source/Short line Weak Source/long line
Fault Resistance Coverage
Strong source & short line reduced fault resistance coverage
Quadrilateral char. Improves fault resistance coverage
Weak Source & long line increases fault resistance coverage
Memory polarization : more secure all fault conditions
Self polarization : limited fault resistance coverage
Memory polarization increases fault resistance coverage
Cross polarization : same effect as memory polarization
Quadrilateral Characteristics
Four comparators used for detection of fault conditions
If all four comparators produces output: protection trips
Quad characteristic :good fault resistance coverage
ZR
ZL
R
X
Dir
Reach
Load Blinder
KR
How Directional line works?
ZR
ZL
R
X
Dir
Reach
Load Blinder
KR
Directional line : Forward Fault
IR
IZ = Signal B
VF
VF
Directional line : Reverse Fault
IR
IZ = Signal B
VF
VF
Reach line : Ext. Fault
IR
IZ
VF
I*Kr = Signal B
IX
If A lags B
By 00 1800
VF - IZ = Signal A
Reach line : Int. Fault
IR
IZ
VF
I*Kr = Signal B
IX
If A lags B
By 00 1800
VF - IZ = Signal A
Reach line
IR
IZ
VF
I*Kr = Signal B
IX
If A lags B
By 00 1800
VF - IZ = Signal A
Quadrilateral Char. : Facts
Quad char. better : short line and/or strong source
Good for Ph-G fault : Fault Res. Coverage
Reactance & Resistance Reach set independently
Quad Char. : Reactance Line
Reactance line : not a straight line parallel to R axis.
Top line has a tilt of approx 30
The tilt for security against external fault
Without tilt : protection can operate for an external fault due to load on the line
How?
Effect of Load : Quad Ch.
G G
21
ZsZLZs
Vx
Impedance Seen at Protection X
(Ix+Iy)*R
(Ix)*ZL
Tilt of the reactance line
Prevents tripping for the
External faults
Ix
IyIx + Iy
G G
21
ZsZLZs
Vx
Effect of Load : Quad Ch.
G G
21
ZsZLZs
Vx
Impedance Seen at Protection X
G G
21
ZsZLZs
Vx
Quad Characteristics : Ext. Fault
Quad Characteristics : Int. Fault
Quad Characteristics : Int. Fault
By polarizing the top line with Ve or Zero sequence current, it will adapt to load Condition
MHO Characteristics : Zone 3
Zone 3 provides the back up protection
Zone 3 is typically time delayed zone
Used in blocking scheme to determine fault direction
Zone 3 is mostly offset characteristic
It can trip for a reverse fault
Lens shape used to avoid load encroachment
Zones of Protection
Load profile
Zone 3 : Offset MHO
OFFSET MHOIZ
-IZ
V-IZ
V-IZ
Z = Forward Reach
Z = Reverse Reach
OFFSET MHOIZ
-IZ
Load profile
Two Comparators are phase shifted by
same angle in opposite direction
OFFSET MHOIZ
-IZ
Load profile
Major axis to minor axis ratio is equal to tan (180 - )/2Each comparator is shifted by an angle
MHO or Quad : Pros and Cons
Simple and directional
Less sensitive to power swings Reach does not extend
as far along R-Axis
Limited fault resistance coverage for short lines
Good fault resistance coverage as char. can be set along R- Axis Good for short line and
strong source
Sensitive to power swing Characteristic extends on
R-Axis