+ All Categories
Home > Documents > 8000S in A4 Catalogue

8000S in A4 Catalogue

Date post: 10-Apr-2018
Category:
Upload: matiasc
View: 227 times
Download: 0 times
Share this document with a friend

of 6

Transcript
  • 8/8/2019 8000S in A4 Catalogue

    1/6

  • 8/8/2019 8000S in A4 Catalogue

    2/6

    KEY FEATURES

    ?

    ?

    ?

    ?

    ?

    ?

    ?

    ?

    STANDARDS COMPLIANCE

    Smaller & lighter than conventional methods, yettough and durableImmune to system noise - Selectable testing

    frequency and precise filters eliminate noise and interference concerns.

    Live testing - Test can be made with the substation inservice.

    Easier testing - No network reconfiguration or protection equipment alterations required.

    Safer testing - Lower current values increases testssafety.

    Faster testing - Reduce testing times and testing costs toabout 50% of high current methods.

    Inbuilt memory - Frequency selective multimeters storeup to 7000 records which can be later downloaded by USBto a computer.

    High accuracy - Measure complex impedancesaccurately and repetitively .

    Red Phase Instruments 8000S system, can be used toperform measurements included in internationalstandards such as: IEEE 80-2000; IEEE 81-1983; DIN VDE0101; CENELEC HD637S1.

    8000S HIGH POWER

    EARTH TESTING SYSTEM

    TEST CAPABILITIES

    High power earth systems (Substations, Transmissionowers, etc) have to be periodically monitored to checkf they comply with safety levels established in standards

    and regulations. This testing is critical, as the safety of he employees and neighbors depend on it.

    n order to reduce the effects of noise (caused bynduction and unbalanced loads) in these systems,

    conventional testing require high values of currentnjected into the system. This not only compromisesafety, but also means bulky, heavy and expensive

    equipment that is difficult to carry and set up for fieldesting.

    Red Phase Instruments 8000S High power earth testingystem was designed to solve all the problems present in

    conventional testing methods.

    By generating a stable off-frequency current, that isvery near but different to the grids frequency, and usingprecise filters to pick up the signal, we can test with noconcern of the systems noise (fundamental andharmonics wont affect the measurement).

    Earth Impedance.

    Earth grid voltage rise.Step and touch voltages.Surface potential distribution.Soil resistivity.Earth continuity.

  • 8/8/2019 8000S in A4 Catalogue

    3/6

    Earth impedance directly refers to voltage rises inelectrical systems under fault. These voltage rises can beextremely dangerous to utility and other personnel if hey are over accepted safety levels.

    Off frequency current is injected into the earth eitherby an independent cable and stake or, where possibleusing an out of service overhead line.

    There are different accepted methods to set up thecurrent injection point and loop. The simplest method ishe linear method, where the current stake is located at a

    distance C=5D (5 times the Earthing grid longestmeasure, diagonal D). The reference (remote) potentialpoint P, is located between P=0.6C and P=0.65C (60% to65% of the Cs length).

    Once the current loop and remote voltage are set up,njecting current at the chosen frequency into theystem, and using the frequency selective multimeter,he impedance is automatically calculated.

    For more accurate results, the current loop and voltageeference can be configured in different ways, and thempedance at the lines frequency can be calculated bynterpolation of impedances at off-key frequencies.

    The same injection circuit used to calculate groundmpedance can be used.

    The frequency selective multimeter should be set up forouch and step voltages by selecting the 1k resistancehat simulates a persons internal resistance.

    Circular metal discs of 8 cm radius are used to simulatehe feet and hands and used to measure the voltage at

    different points of the area searching for high risk areas.

    V0

    VtouchVstep

    STEP AND TOUCH VOLTAGES

    EARTH IMPEDANCE

    Under fault conditions, currents flowing through theearth grid cause voltage gradients.

    Touch voltages refer to voltages that appear betweenhand accessible points and the feet.

    Step voltages refer to voltages that appear between thefeet while walking through the site.

    Both step and touch voltages should be monitored inorder to prevent possible electrocution.

    EarthingGrid

    D

    C

    1mm

    1mm

    STEP & TOUCH VOLTAGE

    ARRAY

    EARTH IMPEDANCE ARRAY

    C

    D

    P

    EarthingGrid

    RemotePotential

    CurrentStake

  • 8/8/2019 8000S in A4 Catalogue

    4/6

    Surface Potential distribution is a key factor thatconveniently shows the state of the grounding system.After measuring the voltages generated at equidistantpoints over the grid, graphs can be easily generatedshowing equipotential sections and further investigationcan be done in high risk areas.

    The same injection circuit used to calculate groundmpedance can used.

    An imaginary grid is laid over the substation or area and

    he frequency selective multimeter is connected tomeasure the voltage difference between the injectionpoint and equidistant points over the grid.

    As the impedance of an earth grid is influenced by theesistivity of the soil where it lays, soil resistivity

    measurements are an important parameter whendesigning earthing systems.

    There are several possible connections. The Wennerarray (shown in the drawing) is the simplest one. Currents injected over the Current stakes and the frequency

    selective multimeter calculates the resistance (R)according to the appearing voltage between thepotential stakes

    Resistivity is then easily calculated using the formula thatsuits the Wenner array:

    SOIL RESISTIVITY

    SOIL RESISTIVITY ARRAY

    a a a

    a/20

    C1 P 1 P 2 C2

    SURFACE POTENTIAL DISTRIBUTION

    d d d d d d d d d d d d d

    SURFACE POTENTIAL DISTRIBUTIONARRAY

    Once all these points are surveyed, resultscan be graphed and analyzed.

    A good performance grounding surfacedistribution curve should be relatively flat,usually with only a slight elevation at bothends.

    Curve 1 is an example of an even potentialdistribution.

    Curve 2 fluctuates and is an indication of apoor grounding system curve.

    X

    Y

    d d d d

    d

    d

    d

    d

    d

    d

    dd d d d

    d X

    v

    ( m V )

    (m)

    curve 2curve 1

    curve 3

    Even though most of Curve 3 has lower voltage difference values than Curve 1, it shows a severe voltage peak,ndicating a localized problem in the grounding grid.

    Grounding systems with curves like 2 or 3 need further analysis to correct their problems and be made safe.

  • 8/8/2019 8000S in A4 Catalogue

    5/6

    .SYSTEM COMPOSITION

    OPTIONAL ACCESSORIES

    .

    Switch mode voltage source generates stable signals at selectedrequencies.

    Currents at frequencies within the 45 to 65 Hz range can begenerated, which will suit 50 or 60 Hz networks.

    This unit is connected to model 4023 (Coupling transformer) toncrease the current signal by matching impedance.

    Frequency selective ammeter and voltmeter, measures themagnitude and phase angles of signals in the selected frequencyrange 40 to 69 Hz)

    High quality filters allow use at frequencies up to a limit of 1 Hzdifference from the line frequency and still be immune tonterference.

    nternal rechargeable battery allows for flexible field testing.

    Current inputs for Rogowski type 545 worm coil, LEM-flex Rr3020 ACor Fluke i300S flex current probe.

    Two 4025D are included in the standard 8000S bundle to allow moreefficient testing.

    MODEL 4024 INJECTION UNIT

    MODEL 4025D FREQUENCY

    SELECTIVE MULTIMETER

    .

    Coupling transformer designed to produce maximum power outputinto a 1500VA load.

    This transformer is driven by Model 4024 (injection unit) at 180Vwhich is connected to the primary. The secondary is then connectedto the current loop to inject the current into the grounding grid.

    A selector switch is used for different secondary taps to matchcurrent loop impedance.

    Easily checks the continuity of connections within an earthingsystem.

    Composed by a base unit which contains the DC power supply andcurrent source, and a remote unit which contains the handheldmeter and measurement probe.

    Remote unit has a fixed 5m lead that connects to the base unit and a0.8 m lead to the probe handle. A 100m extension reel allows speedytesting over a 100m radius from the base unit.

    MODEL 4023 COUPLING

    TRANSFORMER

    MODEL 4022B EARTH

    CONTINUITY TESTER

    Rogowski coil Fluke i3000S Flex 24 100 m extension cable on a reelType 545 worm current input current probe for remote unit of 4022B earth3 m long with interface unit.

    continuity tester.

  • 8/8/2019 8000S in A4 Catalogue

    6/6

    TECHNICAL DATASHEET

    RED PHASE INSTRUMENTS has been providing instrument andesting solutions for the worldwide electric power industry for more than 35 years.

    From our headquarters in Melbourne, Australia, we design and manufacture state of theart equipment that often no other company makes. We also manufacture and serviceolder an more mature products that are still in demand.

    Our customers vary from the very largest national utilities to small pacific islandcooperatives with only 10MW capacity.

    No matter who our customers are, we plan to give them excellent service and productshelping them to achieve the maximum result at a reasonable price.

    Red Phase Instruments Pty Ltd.10 Ceylon St,Nunawading (3131),Melbourne,VIC, [email protected]

    Distributed By:

    S u b j e c t

    t o c h a n g e w

    i t h o u

    t n o

    t i c e

    40 TO 69 IN 0.1 Hz steps


Recommended