    CommScope Z-IDC Interconnect System 201-205-001-19Instruction Sheet 400-Pair Connectorized Issue 6, February 2004

    Connecting Block Application, Installation Material ID 848 181 087and Frame Cabling on CommScope, Moreng

    (or similar) Network Bay Frames and CommScopeSingle-Side Low Profile Distr ibuting Frame (SSLPDF)

    2007 CommScope, Inc. Page 1

    Refer to Z-IDC Reference Manual, 201-205-001, for additi onal information.

    General

    This instruction sheet provides descriptions and instructions for:

    General overview and application using Z-IDC Connecting Blocks in an interconnectarrangement mounted in CommScope, Moreng, or similar network bay frames ....Pages 2 and 3.

    Detailed description of the Z-IDC Connecting Block and available accessories. ... Pages4 and 5.

    Instructions for mounting and cabling the Z-IDC Connecting Block into CommScope or similarnetwork bay frames using CommScope mounting adapter kits ......................Pages 6 through 15.

    Instructions for mounting and cabling the Z-IDC Connecting Block into Moreng framework usingMoreng mounting adapter kit ......................................................................... Pages 16 through 28.

    Description of the Z-IDC Connecting Block in a co-mounted application .......... Pages 29 and30.

    General overview and application using Z-IDC Connecting Blocks in an inter-connectarrangement mounted in an CommScope SSLPDF framework.................... Pages 31 through 33.

    Instructions for mounting and cabling the Z-IDC Connecting Blocks into an CommScopeSSLPDF framework using an CommScope mounting Adapter kit. ............... . Pages 33through 38.

    NOTE:

    While the instructions for mounting the Z-IDC Connecting Blocks onto CommScope andMoreng frames are similar, there are unique hardware differences in the mounting adapterkits, the mounting hole spacing, and where the kits mount to the frameworks. There are alsodifferences in the cabling arrangements. Be sure to use correct information for the specificapplication.

    NOTE:

    Nine digit Material ID ordering numbers do not contain spaces. They are included here forease of reading.

    How to Contact Us

    To find out more about Carrier Apparatusproducts, visit us on the web at:

    http://cw.commscope.com/ For technical assistance regarding Carrier Apparatus products: contact your local CommScope

    account representative or Commscope technical support at 1-800-344-0223.

    Report any missing or damaged parts to CommScope customer service in Omaha, Nebraska, at

    1-866-539-2795.

    Al l Rights Reserved 38 Pages

    Printed inU.S.A.

    http://cw.commscope.com/http://cw.commscope.com/http://cw.commscope.com/
  • 7/25/2019 848_181_087

    2/38

    Material ID 848 181 087Instruction Sheet

    Tools Required:

    Screwdriver, flat-bladed

    Cable ties and/or lacing cord

    Verify parts according to the Parts List shown below. Report any damaged or missing parts to your localCommScope representative.

    Parts List

    Item Description Quantity Material ID

    A ZIDC-A400-D01-AFE connecting block 1 108 406 679

    B Slotted pan-head thread cutting screw (TCS), typeT, 10-32 x 1/2 In.

    4 901 224 907

    C Instruction sheet 1 848 181 087

    Overview CommScope or Moreng Network Bay Frames

    The Z-IDC connecting blocks provide a frame mounted point-of-termination for Certified/CompetingLocal Exchange Carriers (CLECs) central office equipment to interconnect to the Incumbent Local

    Exchange Carriers (ILECs) subscriber outside plant cable network. Typically, these subscriber cablepairs are located on the vertical side of a Main Distributing Frame (MDF). The 100-pair tie cablesconnect the front of the connecting block to the horizontal side of the subscriber MDF. These circuits arecross connected on the MDF to subscriber cable pairs as required using single-pair, cross-connect wire.The 25-pair connectorized CLEC equipment cable (with male RJ-21 connectors) connect to female RJ-21connectors on the back of the connecting block. This cable is run to the CLEC equipment in the CLECequipment area (caged area). See Figure 1. These blocks are intended for high termination density inter-connect termination arrangements in CommScope AD-8C501-5 or AD-8C801-50 (Seismic) or MorengLT99519 (or similar) Network Bay Frames.

    CLEC Equipment Cage ILEC Subscriber MDF

    CLEC Equipment Cables

    Z-IDC Co-Location Frame

    CommScope or Moreng Network Bay Frame(or CommScope SSLPDF Frame)

    400-Pair -IDC Connecting BlocksZ3200-Pairs Total

    To ILEC OSP Subscriber Cable Nework

    1-Pair Cross-Connect Wire

    1

    2

    3

    4

    5

    6

    7

    8

    MDFProtectorBlocks

    Tie CableConnecting

    Block

    HMDF VMDF

    CLECEquipment

    ILEC - MDF Tie Cable

    Figure01CS.cdr

    Figure 1. Z-IDC 400-Pair Connecting Block Network Bay Frame Point ofTermination for Applications

    Page 2

    38 Pages

  • 7/25/2019 848_181_087

    3/38

    Material ID 848 181 087Issue 6, February 2004

    Cable Types

    The following cables are recommended for the MDF tie cables and can also be used as part of theconnectorized CLEC equipment cables.

    Cable Code Descript ion Appl ication Material ID

    806A 100 Pair26 AWG (0.4 mm) Plain old telephone service (POTS)under 400 feet

    105 412 472

    TIW-100 100 Pair24 AWG (0.5 mm) POTS over 400 feet 105 438 626

    Digital Subscriber Line (DSL) circuits may or may not require larger diameter shielded cables, which maylimit the number of DSL circuits per vertical.

    General Cabling, Cable Racking, and Auxil iary Framing Recommendations

    a) It is recommended that the CLEC cabling be installed on one level of the cable rack (or two levelsif required) at the front of the frame and then run to the rear in a simple waterfall cablingarrangement to the vertical cabling path being installed.

    b) It is recommended that the ILEC MDF tie cables be installed on one level of the cable rack (or

    two levels if required) at the rear of the frame and then run to the front in a simple waterfallcabling arrangement to the vertical cabling path being installed.

    c) The above recommended cabling arrangements will avoid having to spiral cable off the racks andinto the frame and also provide rack segregation between the ILEC and CLEC cables.

    d) Recommended cable rack levels are 7 feet 6 inches (2.286 m) and 9 feet (2.7432 m) above thefloor level and as wide as practical. Cable pileup in the rack should not exceed 12 inches (304.8mm). See Figure 5 (CommScope frame) or Figure 14 (Moreng frame).

    e) Because of potentially heavy cable loads, the cross-aisle auxiliary framing should be spacedapproximately every 52 inches (1320.8 mm), or every other frame, and centered directly abovethe 2

    ndor 3

    rdvertical (9.25 or 14.63 inches [234.95 or 371.602 mm] in from the left side) of a

    frame. This will avoid interference with individual cabling at the top of the frame for paths on both

    the front and back of the frame. See Figure 7 (CommScope frame) or Figure 16 (Moreng frame).

    The cable racks should be horizontally offset from the vertical plane of cabling within the frame by aminimum of 10 times the diameter of the cable to allow for the minimum-bending radius of the cables.See Figure 5 (CommScope frame), Figure 14 (Moreng frame) or Figure 27 (SSLPDF) Frame.

    Page338Pages

  • 7/25/2019 848_181_087

    4/38

    Material ID 848 181 087Instruction Sheet

    Connecting Block Description

    The ZIDC-A400-D01-AFE Connecting Block (Material ID 108 406 679) is a 400-pair fixed bracket typeblock, which contains 40 ZIDC-A10-D01-A 10-pair disconnect-type connector modules (Material ID 107665 473) with internal normally closed dual contact sets. The cabling side of the connector modules arefactory wired within the connecting block bracket to Cinch female socket RJ-21 type, 25-pair connectors,which are mounted on the back surface of the connecting block bracket. These connectors (Part No. 97-22500-11) are equipped with InstaLatch

    *latches that engage and retain mating male RJ-21 connectors

    of interconnecting equipment cabling. This equipment cabling must beequipped with Cinch or equivalentmale plug RJ-21 type connectors arranged to accept these retaining latches, (male connectors havingsmall windows at each end). The recommended Cinch part numbers for male RJ-21 connectors are PartNo. 97-22500-11 or 97-22500-11A. Two and one-half 10-pair Z-IDC connector modules connect to one25-pair RJ-21 connector (each sequential set of ten adjacent Z-IDC connector modules are wired to setsof four adjacent RJ-21 connectors). These sets of four connectors are arranged diagonally with a total of16 RJ-21 connectors per block. See Figure 2.

    Figure 2. Z-IDC Connecting Block

    *InstaLatch is a trademark of Cinch Connector, a Division of Labinal Components and Systems Inc., 865 Parkview Blvd.,Lombard,

    Illinois

    Page 4

    38 Pages

  • 7/25/2019 848_181_087

    5/38

    Material ID 848 181 087Issue 6, February 2004

    Recommended Accessories

    The following accessories are available for use with the Z-IDC connecting block:

    Quantityper

    OrderedMaterial ID Ordering No. Descripti on Material ID

    1 ZIDC-FB10-A01 Label kit for fixed-type connecting blocks (8 pervertical) recommended for all connecting block.Each kit includes an extruded plastic label holderwith a premounted adhesive mounting strip andpreprinted labels indicating both module numbersand pair numbers for 100-pair increments. Spaceis provided for circuit designation, specific cablenumber/pair count, and frame type information

    107 629 032

    1 ZIDC-PB01-BK1-05 Bridging cord, 16-foot (5 meters) long with blackplugs on each end for bridged test access

    107 629 438

    1 ZIDC-PP01-WH1-05

    In/Out cord, 16-foot (5 meters) long with whiteplugs on each end for In/Out test access

    107 629 073

    10 pcs. ZIDC-DP10-WH1 Disconnect plugswhite (10 pair) 107 665 549

    100 pcs. ZIDC-DP01-WH1 Disconnect plugs

    white (1 pair) 107 629 081100 pcs. ZIDC-BP01-RD1 Blocking plugsred (1 pair) 107 665 515

    100 pcs. ZIDC-MC01-RD1 Marking capsred (1 pair) 107 665 457

    1 ZIDC-WT1 Wire-insertion tool 107 900 995

    Page538Pages

  • 7/25/2019 848_181_087

    6/38

    Material ID 848 181 087Instruction Sheet

    Installing CommScope Network Bay Frame and Mounting Adapter Ki t

    1. Install the frame per local practices using the ED-8C812-50, Group 21 (standard) or Group 22(seismic) floor mounting kit (one kit required per frame) and the junctioning plates (three required perframe and included with frame). The frame is arranged with (39) 2-inch (50.8 mm) high mountingplate positions, using constant 1-inch (25.4 mm) hole spacing. The mounting plate positions arenumbered 1 through 39 from bottom-to-top (numbering is not printed on frame).

    2. Install the ZIDC-84L23-MK01 Mounting Adapter Kit (Material ID 108 406 679) to the frame perinstruction sheet 201-205-001-21 (Material ID 848 508 636), which is included with the kit.

    Installing Connecting Blocks on CommScope Network Bay Frames

    Before installing the connecting blocks.

    If the optional ZIDC-FB10-A01 Label Kits are used (four kits to a block), it is recommended that anymanually applied lettering be applied to the labels beforethey are installed into the plastic label holder. Itis also recommended that the label holder be attached to the block beforeattaching the block to theframe. Lay the block on a flat surface (such as a tabletop), and remove the protective cover from theadhesive mounting strips on the label holders. Position the label holders along the right side of the blockwith the back edge of the label holder aligned with the back edge of the block. Press firmly on the outside

    of the label holder in the area of the adhesive strip to insure that the holder is properly attached to theconnecting block bracket. Refer to instructions included with the label kit. See Figure 3.

    NOTE:Although frame lineups can grow left-to-right or right-to-left, the connecting blocks should beinstalled into each individual frame from left-to-right, with both blocks of the same verticalinstalled at the same time, and before cabling is secured to the frame. This will provide goodaccess to the connecting block mounting screw positions (not covered by previously installedILEC cable on the front of the vertical of previously installed blocks) and simplify thesequential installation of cable.

    1. Four 10-32 x 1/2-inch thread-cutting slotted pan-head screws are included with each connectingblock to mount it to the adapter brackets on the frame. The four screws can be installed into theadapter brackets with a few thread engagements first, and then the connecting block can be slid in

    from right-to-left under the screw heads. While the screws will support the weight of the connectingblocks while they are being tightened, the installer should maintain a hold on the block in themounting position.

    2. Mount the upper connecting block of each vertical to the uppermost (position 39) and center (position20) adapter brackets aligning the bottom of the block with the center of the center adapter bracket(position 20). In this upper connecting block position, the upper mounting screws will use the highestmounting slots on the upper mounting tabs and the lower mounting screws will use the lowestmounting slots on the lower mounting tabs of the block. See Figures 3 and 4.

    3. Mount the lower connecting block of each vertical to the center and lower adapter brackets (positions20 and 1) aligning the top of the block with the center of the center adapter bracket (position 20). Inthis lower connecting block position, the upper mounting screws will use the top mounting slots onthe upper mounting tabs and the lower mounting screws will use the bottom mounting slots on the

    lower mounting tabs of the block. See Figures 3 and 4.

    Page 6

    38 Pages

  • 7/25/2019 848_181_087

    7/38

    Material ID 848 181 087Issue 6, February 2004

    1

    3

    5

    7

    9

    11

    13

    15

    17

    19

    21

    23

    25

    27

    29

    31

    33

    35

    37

    39

    1 2 3 4

    ZIDC-A400-D01-AFECo-Location

    Connecting Block(108406679)

    (2) per Vertical

    (1) OptionalZIDC-FB10-A01Fixed Bracket

    Label Kits(107629032)

    (8) per Vertical(designates

    100-pair each )

    Mtg. PlatePosition No.

    848761-22CS.cdr

    Figure 3. Z-IDC Connecting Blocks Mounted on CommScope Network Bay Frame

    Page738Pages

  • 7/25/2019 848_181_087

    8/38

    Material ID 848 181 087Instruction Sheet

    13

    5

    7

    9

    11

    13

    15

    17

    19

    21

    23

    25

    27

    29

    31

    33

    35

    37

    39

    1 2 3 4

    U p

    pe

    rC o

    nn

    ec

    tin

    gBlockP

    ositions

    LowerC o

    nne

    ctin

    gB

    loc

    kP

    os

    ition

    s

    Upper Mounting Tab ofUpper Connecting Block

    Lower Mounting Tab ofUpper Connecting Block

    Upper Connecting Block

    Lower Connecting Block

    Lower Mounting Tab ofLower Connecting Block

    Upper Mounting Tab ofLower Connecting Block

    Uppermost AdapterBracket (Position 39)

    Middle AdapterBracket (Position 20)

    Lower AdapterBracket (Position 1)

    Mounting Screw in UppermostSlot of Mounting Tab

    Mounting Screw in UppermostSlot of Mounting Tab

    Mounting Screw in LowestSlot of Mounting Tab

    Mounting Screw in LowestSlot of Mounting Tab

    848761-24CS.cdr

    Figure 4. Z-IDC Connecting Block Installation on Mounting Adapter Brackets (CommScope ED-8C501-50, Group 1 or ED-8C801-50, Group 1)

    Page 8

    38 Pages

  • 7/25/2019 848_181_087

    9/38

    Material ID 848 181 087Issue 6, February 2004

    Cabling to the Network Bay Frame

    1. The CLEC cable is terminated (plugged into) the female RJ-21 connectors on the rear of the blockand should be run from the bay to the cage to eliminate any cable slack at the frame.

    2. CLEC cabling within the frame should be installed from top-to-bottom. Looking at the back of theblock, run cabling to the left of the blocks in the space between the blocks, four cables wide by eightcables deep. Secure this cable to the back surface of the cable support brackets (Material ID846800324) and the twelve section cable support bracket (Material ID 847147238) at the top of theframe. The twelve section cable bracket has 12 cabling compartments. When looking at the back ofthe frame, use the first, forth, seventh, and tenth compartments from left to right to support the cable.Note that this bracket provides the only cable support for cables terminating to the uppermost set offour connectors of the four upper connecting blocks. Refer to Figures 5, 6, 7, 8, and 10.

    3. The raw-ended ILEC MDF tie cables are terminated to the front insulation displacement contacts(IDCs) of the Z-IDC connector modules on the front of the connecting block. Looking at the front ofthe block, run cabling to the left of the blocks, in the space between the blocks, and secured to thefront surface of the CommScope mounting adapter brackets. They should also be banded togetherwith a cable tie just above every 100-pair breakout (see Figures 5, 7, 9, and 10). This cable istypically routed to the equipment or horizontal side of the ILECs subscriber MDF.

    Page938Pages

  • 7/25/2019 848_181_087

    10/38

    Material ID 848 181 087Instruction Sheet

    100-Pair ILEC-HMDFTie Cables

    (8) per Vertical

    1 2 3 4

    Front View

    2nd Level Cable Rack If Required10 in. wide (254mm) cable rack shown

    1st Level Cable Racking10in. wide (254mm) cable rack shown

    Left Side View

    AuxilliaryFraming

    9 Bays or (1152) 824A25-Pair 26awg CLEC Cable0.30 in.Dia. (7.6mm) - Sewn in Rack

    7Bays or (896) TIW25/2425-Pair 24awg CLEC Cable

    0.33 in. Dia. (8.4mm)- Sewn in Rack

    7 Bays or 224TIW100/24

    100-Pair 24awgILEC Cable[0.63 in. Dia.

    (16mm) Sewn in Rack]

    11 Bays or (352)806A 100-Pair

    26awgILEC Cable[0.54 in. Dia.

    (14mm)- Sewn in Rack]

    Cable SupportBracket

    (846800324)(8

    CLECEquipment

    Cable

    ) Places

    Mounting

    AdapterBracket(848502811)(3) Places

    12-Section CableSupport Bracket

    (847147238)(1) Place

    1

    10

    20

    30

    401

    10

    20

    30

    40

    1

    10

    20

    30

    40

    1

    10

    20

    30

    401

    10

    20

    30

    40

    848761-25CS.cdr

    Figure 5. CLEC and ILEC MDF Cabling to Bay

    Page 10

    38 Pages

  • 7/25/2019 848_181_087

    11/38

    Material ID 848 181 087Issue 6, February 2004

    Figure 6. Equipment Cabling Within Bay

    Page1138Pages

  • 7/25/2019 848_181_087

    12/38

    Material ID 848 181 087Instruction Sheet

    Figure 7. Z-IDC Bay Cabling Plan (CommScope Framework)Showing Cross-Aisle Auxiliary Framing (Top View)

    Page 12

    38 Pages

  • 7/25/2019 848_181_087

    13/38

    Material ID 848 181 087Issue 6, February 2004

    Top of FrameUpper

    ConnectingBlocks

    Midpoint of FrameLower

    ConnectingBlocks

    Bottomof Frame

    1st set of4 Connectors

    5th set of4 Connectors

    1-2-3-4 17-18-19-20

    5-6-7-8

    3rd setof4Connectors

    4th setof4Connectors

    7th set of4 Connectors

    8th set of4 Connectors

    9-10-11-12

    13-14-15-16

    25-26-27-28

    29-30-31-32

    Cable SupportBracket Typical

    848761-28

    Figure 8. Z-IDC Bay Cabling Sequence on CommScope FrameworkTop View of (32) 25-PairConnectorized CLEC Cables at Each Vertical

    Page1338Pages

  • 7/25/2019 848_181_087

    14/38

    Material ID 848 181 087Instruction Sheet

    Top of FrameMidpoint of Frame

    Bottom of Frame

    Butt 1st 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    1st Connector Module

    Butt 2nd 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    10th Connector Module

    Butt 3rd 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    20th Connector Module

    Butt 4th 100-Pair Cable

    and SecureEntire Cable Bundleto Wire Clip of

    30th Connector Module

    Butt 5th 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    40th Connector Module

    Butt 6th 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    50th Connector Module

    Butt 7th 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    60th Connector Module

    Butt 8th 100-Pair Cable

    and SecureEntire Cable Bundleto Wire Clip of

    70th Connector Module

    Figure9 848765-02CS.cdr

    Figure 9. Z-IDC Bay Cabling Sequence on CommScope Framework

    TopView of 100-Pair ILEC MDF Tie Cables at Each Vertical

    Page 14

    38 Pages

  • 7/25/2019 848_181_087

    15/38

    Material ID 848 181 087Issue 6, February 2004

    Figure 10. Lineup Cable Rack and Cabling Plan

    Page1538Pages

  • 7/25/2019 848_181_087

    16/38

    Material ID 848 181 087Instruction Sheet

    Installing Moreng Framework LT99519

    Note: The Moreng LT99519 framework is arranged specifically to mount up to eight ZIDC-A400-D01-AFE Connecting Blocks. This provides up to 3200 pairs in an interconnect arrangement.

    1. Install the frame per local practices using the Moreng floor mounting kit No. R8M084-FGH or the ED-8C812-50, Group 21 kits (one kit required per frame) and the Moreng frame junctioning plate No. R8-

    306 (three required per frame and included with frame). The Moreng frame is arranged with (44) 1-3/4 inch (44.45 mm) mounting plate positions, using a staggered 1-1/4 inch (31.75 mm) and 1/2-inch (12.7 mm) hole spacing (EIA type hole pattern). The mounting plate positions are numbered 1through 44 from bottom-to-top (numbering is not printed on frame). Refer to Figure 11.

    2. Install the four connecting block mounting adapter brackets (Moreng part No. LT-990401) in mountingplate positions 1, 22, 23, and 44 using four 12-24 x 1/2-inch (12.7 mm) long slotted hex-washer headmachine screws (Material ID 840 026 827) furnished with each of the brackets. Install position 22before 23.

    Note:That the hole pattern for mounting the connecting blocks is shifted to the left and therefore thebrackets are not reversible.

    3. The screws may be installed into the frame with a few thread engagements first, and then the adapter

    bracket can be slid under the screwheads. This will support the adapter brackets until the screws aretightened.

    4. Install the cable support brackets (Moreng part No. R2-23-120). Eight are required per bay. Thecable support brackets are to be mounted just above each of the four sets of RJ-21 connectors. Thisallows cable to be secured to the brackets immediately above their terminating connector positionsand at each additional bracket on their path to the top of the bay. These brackets are made from wirerod with an eyelet loop at each end and come with two 12-24 x 5/16-inch slotted pan-head machinescrews for mounting. See Figure 11.

    Note: Flipping the eyelet from top-to-bottom or vice-versa allows a small adjustment in height fromthe floor to optimize the location of the bracket in relation to the connector sets.

    The following chart indicates the recommended hole and eyelet positions for each bracket location from

    bottom-to-top.

    Cable Suppor tBracket No.

    Mounting PlatePosition Number

    Mounting Plate HolesUsed Cable Eyelet Position

    1 - bottom 7 Lower Down

    2 12 Lower Up

    3 17 Lower Up

    4 22 Lower * Up

    5 29 Lower Down

    6 34 Lower Down

    7 39 Lower Up

    8 - top 44 Lower * Up

    * Mounts within the same mounting plate position as the adapter bracket, using the longer adapterbracket mounting screws.

    Page 16

    38 Pages

  • 7/25/2019 848_181_087

    17/38

    Material ID 848 181 087Issue 6, February 2004

    Note: The Moreng Framework LT99519 (ordered separately) includes a Mounting Adapter Kit LT99421which includes the following individual parts.

    Item Descript ion Qty. Moreng Part Number

    A Mounting adapter 4 LT990401

    B 12-24 x 1/2 SL, hex-washer head screw 16 Material ID 840 026 827

    C Cable support bracket 8 R2-23-120

    D 12-24 x 5/16 SL pan head machine screw 16 MPC01224031Y

    Page1738Pages

  • 7/25/2019 848_181_087

    18/38

    Material ID 848 181 087Instruction Sheet

    Figure 11. Connecting Block Mounting Adapter Brackets and Cable Support Brackets KitInstallation of Moreng Part Number LT-99421

    The Z-IDC connecting blocks mount vertically (modules horizontal with the module wire retainer clip tothe left) into a Moreng Telecom Products, LLC. relay rack (LT99519). A Moreng mounting adapter kitLT99421 (included with Moreng frame) is used to mount the blocks to the frame and to provide cablingsupport. Included in the kit are four connecting block mounting adapter brackets (LT990401), eightMoreng cable support brackets (R2-23-120), and associated mounting hardware. The mounting adapterkit may also be ordered separately from Moreng. The block adapter brackets are mounted

    Page 18

    38 Pages

  • 7/25/2019 848_181_087

    19/38

    Material ID 848 181 087Issue 6, February 2004

    horizontally to the frame using a total of 16 slotted hex-washer head thread forming screws. Thesescrews provide a ground connection between the mounting adapter brackets and framework. The cablesupport brackets are mounted to the frame with a total of 16 slotted pan-head machine screws.

    Installing Connecting Blocks on Moreng Framework

    Before installing the connecting blocks.

    If the optional ZIDC-FB10-A01 label kits are used (four kits to a block), it is recommended that anymanually applied lettering be applied to the labels before they are installed into the plastic label holder. Itis also recommended that the label holder be attached to the block before attaching the block to theframe. Lay the block on a flat surface (such as a tabletop), and remove the protective cover from theadhesive mounting strips on the label holders. Position the label holders along the right side of the blockwith the back edge of the label holder aligned with the back edge of the block. Press firmly on the outsideof the label holder in the area of the adhesive strip to insure that the holder is properly attached to theconnecting block bracket. Refer to instructions included with the label kit.

    Note: Although frame lineups can grow left-to-right or right-to-left, the connecting blocks should beinstalled into each individual frame from left-to-right, with both blocks of the same vertical installed atthe same time, and before cabling is secured to the frame. This will provide good access to theconnecting block mounting screw positions (not covered by previously installed ILEC cable on the

    front of the vertical of previously installed blocks) and simplify the sequential installation of cable.

    1. Four 10-32 x 1/2-inch thread-cutting slotted pan-head screws are included with each connectingblock to mount it to the adapter brackets on the frame. The four screws can be installed into theadapter bracket with a few thread engagements first, and then the connecting block can be slid infrom right-to-left under the screwheads. While the screws will support the weight of the connectingblocks while they are being tightened, the installer should maintain a hold on the block in themounting position.

    2. Mount the upperconnecting block of each vertical to the two uppermost adapter brackets (positions44 and 23) aligning the bottom of the block with the bottom edge of the lower adapter bracket(position 23). In this upper connecting block position, the upper mounting screws will use the lowestmounting slots on the upper mounting tabs and the lower mounting screws will use the middlemounting slots on the lower mounting tabs of the block. See Figure 12 and 13.

    3. Mount the lower connecting block of each vertical to the two lowest adapter brackets (positions 22and 1) aligning the top of the block with the top edge of the upper adapter bracket (position 22). Inthis lower connecting block position, the upper mounting screws will use the middle mounting slots onthe upper mounting tabs and the lower mounting screws will use the uppermost mounting slots on thelower mounting tabs of the block. See Figure 12 and 13.

    Page1938Pages

  • 7/25/2019 848_181_087

    20/38

    Material ID 848 181 087Instruction Sheet

    12

    4

    6

    8

    10

    12

    14

    16

    18

    20

    24

    26

    28

    30

    32

    34

    36

    38

    40

    42

    44

    22

    1 2 3 4

    Mtg. PlatePosition No.

    ZIDC-A400-D01-AFECo-Location

    Connecting Block(108406679)

    (2) per Vertical

    (1) OptionalZIDC-FB10-A01Fixed Bracket

    Label Kits(107629032)

    (8) per Vertical(each 100-pair)

    23

    Figure 12. Z-IDC Connecting Blocks Mounted on Moreng Relay Rack Framework LT99519

    Page 20

    38 Pages

  • 7/25/2019 848_181_087

    21/38

    Material ID 848 181 087Issue 6, February 2004

    Figure 13. Z-IDC Connecting Block Installation on Mounting Adapter

    Brackets on Moreng Frame LT99519

    Page2138Pages

  • 7/25/2019 848_181_087

    22/38

    Material ID 848 181 087Instruction Sheet

    Cabling for Moreng Frames

    1. The CLEC cable is terminated (plugged) into the female RJ-21 connectors on the rear of the blockand should be run from the bay to the cage to eliminate any cable slack at the frame.

    2. CLEC cabling within the frame should be installed from top-to-bottom. Looking at the back of theblock, run cabling to the left of the blocks in the space between the blocks, four cables wide by eight

    cables deep. Secure this cable to the back surface of the Moreng cable support brackets (seeFigures 14, 15, 16, 17, 18, and 19).

    3. The raw-ended ILEC MDF tie cables are terminated to the front insulation displacement contacts(IDCs) of the Z-IDC connector modules on the front of the connecting block. ILEC cabling within theframe should be installed from bottom-to-top. Looking at the front of the block, run cabling to the leftof the blocks, in the space between the blocks, and secured to the front surface of the Morengmounting adapter brackets. They should also be banded together with a cable tie just above every100-pair breakout. This cable is typically routed to the equipment or horizontal side of the ILECssubscriber MDF.

    Page 22

    38 Pages

  • 7/25/2019 848_181_087

    23/38

    Material ID 848 181 087Issue 6, February 2004

    Figure 14. CLEC and ILEC MDF Cabling to Bay (Front/Side View)Moreng Framework LT99519

    Page2338Pages

  • 7/25/2019 848_181_087

    24/38

    Material ID 848 181 087Instruction Sheet

    Figure 15. Equipment Cabling Within Bay (Rear View) Moreng Framework LT99519

    Page 24

    38 Pages

  • 7/25/2019 848_181_087

    25/38

    Material ID 848 181 087Issue 6, February 2004

    Figure 16. Z-IDC Bay Cabling Plan Showing Cross-Ais le AuxiliaryFraming (Top View) Moreng Framework LT99519

    Page2538Pages

  • 7/25/2019 848_181_087

    26/38

    Material ID 848 181 087Instruction Sheet

    Figure 17. Z-IDC Cabling Sequence for (32) 25-Pair Connectorized CLEC Cables at Each Vertical(Top View) Moreng Framework LT99519

    Page 26

    38 Pages

  • 7/25/2019 848_181_087

    27/38

    Material ID 848 181 087Issue 6, February 2004

    Top of FrameMidpoint of Frame

    Bottom of Frame

    Butt 1st 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    1st Connector Module

    Butt 2nd 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    10th Connector Module

    Butt 3rd 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    20th Connector Module

    Butt 4th 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    30th Connector Module

    Butt 5th 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    40th Connector Module

    Butt 6th 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    50th Connector Module

    Butt 7th 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    60th Connector Module

    Butt 8th 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    70th Connector Module

    Figure9 848765-02Rev2CS.cdr

    Figure 18. Top View Z-IDC Bay Cabling Sequence for 100-PairILEC MDF Tie Cables at Each Vertical Moreng Framework LT99519

    Page2738Pages

  • 7/25/2019 848_181_087

    28/38

    Material ID 848 181 087Instruction Sheet

    Cross-AisleAuxilliary Framing

    136

    24578

    Ladder Type Cable Rack1st Level 7 Ft. - 6 in. (2.29 M)Above Floor Level or Higher

    Alternate FramingLocations

    136

    24578

    Cabling PatternRepeats Every Frame26 Inches ( 660mm )

    Figure 19. Z-IDC Bay Cabling Plan (Top View) Moreng Framework LT99519

    Page 28

    38 Pages

  • 7/25/2019 848_181_087

    29/38

    Material ID 848 181 087Issue 6, February 2004

    Z-IDC Connecting Block in a Co-Mounted Application

    The ZIDC-A400-D01-AFE Connecting Block can also be used co-mounted with related equipment, suchas the Stinger multiplexer, within the same CommScope network bay frame. The DSLAM-ZIDC-A400-DO1-2 (Material ID 700018872) Connecting Block Mounting Kit provides mounting adapter brackets andcable support hardware. This kit is typically used in conjunction with the DSLAM-DDF-DM6-SC8 (MaterialID 700018633) used for interconnecting fiber or coax cables to the high frequency side of the Stingermultiplexer. Refer to Figures 20 and 21.

    For the Stinger application, two of the 400-pair connecting blocks are utilized to Interconnect up to eight100-pair tie cables coming from the ILEC MDF and up to the 672 Stinger equipment pairs. It isrecommended that the upper half of the frame be used to mount the ZIDC blocks because the ILEC tiecables will typically be coming to the frame from an overhead cable rack.

    1

    3

    5

    7

    9

    11

    13

    15

    17

    19

    21

    23

    25

    27

    29

    31

    33

    35

    37

    39

    DS3 CoaxOr

    OC3 Fiber

    1212 Compartment BracketPart of Block Mounting Kit

    (Rear Mounted)

    MountingAdapter BracketPart of

    Block Mounting Kit(Front Mounted)

    MountingAdapter BracketPart of

    Block Mounting Kit(Front Mounted)

    (Rear Mounted)

    Cable Bracket( 4 places)

    Part of BlockMounting Kit

    Cable Bracket( 4 places)

    Part of BlockMounting Kit

    (Front Mounted)

    Rear ViewStinger /ZIDCCo-MountedCo-LocationArrangement

    In CommScopeNetwork Bay Frame

    Fiber or Coax TerminationPanel Kit

    Fig20 848765-06bCS.cdr

    Figure 20. Z-IDC Connecting Block Mount ing Kit (DSLAM-ZIDC-A400-D01-2Material ID 700018872) and Fiber or Coax Termination Panel Mount ingKit (DSLAM-DDF-DM6-SC8 Material ID 700018633) Co-Mounted Wi th

    Stinger Mult iplexer in a CommScope Network Bay Frame (Rear View)

    Page2938Pages

  • 7/25/2019 848_181_087

    30/38

    Material ID 848 181 087Instruction Sheet

    Lucent Technologies

    23 in.FrameMtg.

    Adapters

    1

    3

    5

    7

    9

    11

    13

    15

    17

    19

    21

    23

    25

    27

    29

    31

    33

    35

    37

    39

    12 Compartment BracketPart of Block Mounting Kit

    (4) 806A Cablesto MDF

    per Block

    Cable Bracket(4 places)

    Part of BlockMounting Kit

    (Slack Loop)

    MountingAdapter Bracket(Front Mounted)

    Part of BlockMounting Kit

    ZIDCConnecting

    Blocks

    (457 mm)

    (533.4 mm)

    (419 mm)

    Fiber or Coax TerminationPanel Kit

    Fig21 848765-07

    Up to (28)Double-EdgedConnectorizedStinger Cables

    Figure 21. Z-IDC Connecting Block Mount ing Kit (DSLAM-ZIDC-A400-D01-2Material ID 700018872) and Fiber or Coax Termination Panel Mount ing

    Kit (DSLAM-DDF-DM6-SC8 Material ID 700018633) Co-Mounted With StingerMultiplexer in a CommScope Network Bay Frame (Front/Side View)

    Page 30

    38 Pages

  • 7/25/2019 848_181_087

    31/38

    Material ID 848 181 087Issue 6, February 2004

    Overview

    The Z-IDC connecting blocks provide a frame mounted point-of-termination for Certified/CompetingLocal Exchange Carriers (CLECs) central office equipment to interconnect to the Incumbent LocalExchange Carriers (ILECs) subscriber outside plant cable network. Typically, these subscriber cablepairs are located on the vertical side of a Main Distributing Frame (MDF). The 100-pair tie cablesconnect the front of the connecting block to the horizontal side of the subscriber MDF. These circuits arecross-connected on the MDF to subscriber cable pairs as required using single-pair, cross-connect wire.The 25-pair connectorized CLEC equipment cable with male RJ-21 connectors connect to female RJ-21connectors on the back of the connecting block. This cable is run to the CLEC equipment in the CLECequipment area (caged area). See Figure 22. These blocks are intended for high termination densityinter-connect arrangements on the CommScope Single-Sided Low Profile Distributing Frame (SSLPDP).Refer to Figure 22.

    CLECEquipment

    Cables

    CLEC EquipmentCage

    ILECMDFTie Cables

    ZIDC Co-LocationSSLPDF

    (4) 400-Pair ZIDC Connecting Blocks1600-Pairs Total per 16 in. Wide Frame

    To ILECOSP Subscriber CableNework

    Single-Pair Cross-ConnectWire

    MDFProtector

    Blocks

    MDFTie Cable

    ConnectingBlock

    HMDF VMDF

    CLECEquipment ED-6C331-70,

    Group 83MountingAdapter

    Kit

    ConnectorizedCabling at

    Rear of Block

    1 2

    1 2

    Fig22 848765-05

    ILEC Subscriber MDF

    16.0 inches(406.4 mm)

    90.0

    inches(2286mm)

    84.0

    inches(2133.6mm)

    Figure 22. Z-IDC 400-Pair Connecting Blocks SSLPDF Pointof Termination for Appli cations

    Page3138Pages

  • 7/25/2019 848_181_087

    32/38

    Material ID 848 181 087Instruction Sheet

    Installing Mounting Adapter Kit and 400-Pair Connecting Blocks to the SSLPDFFramework

    1. Install the ED-6C331-70, Group 83 Mounting Adapter Kit to the SSLPDF Framework (one kit pervertical) per Instruction Sheet 201-205-001-22, which comes with the adapter kit. Refer also toFigure 23 or 24.

    2. Install two ZIDC-A400-D01-AFE per vertical to the Mounting Adapter Kit per Instruction Sheet

    201-205-001-22.

    1 2

    ED-6C331-70, Group 83

    Mounting Adapter Kit

    consists of threeMounting Adapter Brackets

    andHex Washer Head

    Mounting Screws (12-24 X 3/8)

    Bottom

    Kick Plate

    Must Be Removed

    7-0 Frame

    ZIDC-A400-D01-AFE (108406679)

    400-Pair Co-Location Connecting Block

    2 per vertical

    22-848671-59a

    Mounting Tabs ofConnecting BlocksDepicts mounting

    screw location

    Mounting Tabs ofConnecting BlocksDepicts mounting

    screw location

    Designation Panel

    (965.2mm)

    (965.2mm)

    (2133.6mm)

    (1981.2mm)

    (1) OptionalZIDC-FB10-A01 FixedBracket Label Kits(107629032)(8) per Vertical(designates 100-pair each)

    Figure 23. 7 feet 0 inchSSLPDFZ-IDC Connecting Block Point ofTermination for Applications

    Page 32

    38 Pages

  • 7/25/2019 848_181_087

    33/38

    Material ID 848 181 087Issue 6, February 2004

    1 2

    Bottom

    Kick Plate

    Remains

    7-6 Frame or

    Higher

    Designation Panel

    Mounting Tabs ofConnecting BlocksDepicts mounting

    screw location

    ZID -A400-D01-AFE 108406679

    2 per vertical

    848671-58

    ED-6C331-70, Group 83

    Mounting Adapter Kit

    consists of three

    Mounting Adapter Brackets

    Hex Washer Head

    Screws (12-24 X 3/8)

    (1981.2m

    m)

    (965.2mm)

    (965.2mm)

    (2286mm)

    1 2

    Bottom

    Kick Plate

    Remains

    7-6 Frame or

    Higher

    Designation Panel

    Mounting Tabs ofConnecting BlocksDepicts mounting

    screw location

    Mounting Tabs ofConnecting BlocksDepicts mounting

    screw location

    ZID -A400-D01-AFE 108406679

    2 per vertical

    848671-58

    ED-6C331-70, Group 83

    Mounting Adapter Kit

    consists of three

    Mounting Adapter Brackets

    Hex Washer Head

    Screws (12-24 X 3/8)

    (1981.2m

    m)

    (965.2mm)

    (965.2mm)

    (2286mm)

    1 2

    Bottom

    Kick Plate

    Remains

    7-6 Frame or

    Higher

    Designation Panel

    Mounting Tabs ofConnecting BlocksDepicts mounting

    screw location

    ZID -A400-D01-AFE 108406679

    2 per vertical

    848671-58

    ED-6C331-70, Group 83

    Mounting Adapter Kit

    consists of three

    Mounting Adapter Brackets

    Hex Washer Head

    Screws (12-24 X 3/8)

    (1981.2m

    m)

    (965.2mm)

    (965.2mm)

    (2286mm)

    (1) OptionalZIDC-FB10-A01 FixedBracket Label Kits(107629032)(8) per Vertical(designates 100-pair each)

    Figure 24. 7 feet 6 inch (or higher) SSLPDFZ-IDC Connect ing Block DS-0 Pointof Termination for Appl ications

    Page3338Pages

  • 7/25/2019 848_181_087

    34/38

    Material ID 848 181 087Instruction Sheet

    Cabling the Connecting Blocks mounted to the SSLPDF Framework

    1. Typically, the CLEC cable is terminated (plugged into) the female RJ-21 connectors on the rearof the block and should be run from the Frame to the Cage to eliminate any cable slack withinthe frame.

    2. Cabling to the rear of the block within the frame should be run and terminated starting from topand sequentially to the bottom. These cables should be run down on the right side of the verticaland secured to the horizontal straps behind the vertical mounting bar. Refer to Figures 25 or 26,and 27 and 28. If access to the back of the frame is not available, plugging the cables in to theirmating connectors will have to be done blind. The connectors at the end of the cables can onlyplug into the mating connectors on the block one way. Align the mating connectors and push theconnector on the end of the cable onto the mating connector on the back of the block. Theconnector on the block has latches, which will engage on the mating connector on the cable andlock the mating connector halves together. The mated connectors can be unlocked bydepressing one of the two latches at either end (within the small square window on the maleconnector) using a small Phillips screw driver (or similar tool) and rotating the connector halvesapart.

    3. Typically, the ILEC 100-Pair MDF tie cable is raw ended and terminates on the front of the blockto the ZIDC Connector Modules using the ZIDC Wire Insertion Tool. Run the cables in sequencefrom top to bottom on the left side of the connecting blocks.

    4. Bring the first cable to the top left side of the upper connecting block and butt the first cable just

    above the uppermost ZIDC module. Fan the leads in 10-Pair groups to each of the first ten 10 -Pair ZIDC modules according to the color code sequence of the cable.

    5. Repeat this process for each subsequent cable. At each point where a cable is butted, securethe entire cable bundle to the wire clip of the adjacent connector module. Refer to Figure 28.

    Page 34

    38 Pages

  • 7/25/2019 848_181_087

    35/38

    Material ID 848 181 087Issue 6, February 2004

    1 2

    R a w En d ed

    C a b l e

    T e r m i n a te d

    o n F ro n to f B l o c Ks

    C o n n e c t o r i z e d

    C a b l e

    T e r m i n a te d

    o n R ea r

    o f B l o c k s

    Fig25 19-848671-56

    Figure 25. Front View Inter-Connect Cabling Arrangement for

    7 feet 0 inchSSLPDF Framework

    Page3538Pages

  • 7/25/2019 848_181_087

    36/38

    Material ID 848 181 087Instruction Sheet

    1 2

    R a w E n d ed

    C ab le

    T e r m i n a te d

    o n F r o n t

    o f B l o c k s

    o n n e c t o r i z e d

    C ab le

    T e r m i n a te d

    o n R ea r

    o f B l o ck s

    Fig26 19-848671-57

    Figure 26. Front View Inter-Connect Cabling Arrangement for 7 feet 6 inch(or higher) SSLPDF Framework

    Page 36

    38 Pages

  • 7/25/2019 848_181_087

    37/38

    Material ID 848 181 087Issue 6, February 2004

    Option 2(32) 25-Pair

    824A25-Pair103 934 667

    formed end with(1) 25-pair connector

    Option 1(8) 100-Pair Tie Cables

    806A 100-Pair105 412 472

    formed end with(4) 25-pair connectors

    raw ended cablessecure with cable tie to1st, 10th, 20th and 30th

    connector module wire clipfor each block

    Frame Verticals

    SSLPDFFootprint

    MountingAdapter Bracket

    ZIDC400-PairCo-LoBlock

    25-PairRJ-21

    ConnectorsMF

    MF

    (406.4 mm)

    (203.2 mm)

    (99.1 mm)

    Fig27 848765-04

    Figure 27. Top View SSLPDF with 400-Pair Z-IDC Connecting Blocks Cabling Location w ithin theFrame for Inter-Connect Arrangement

    Page3738Pages

  • 7/25/2019 848_181_087

    38/38

    Material ID 848 181 087Instruction Sheet

    Top of FrameMidpoint of Frame

    Bottom of Frame

    Butt 1st 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    1st Connector Module

    Butt 2nd 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    10th Connector Module

    Butt 3rd 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    20th Connector Module

    Butt 4th 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    30th Connector Module

    Butt 5th 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    40th Connector Module

    Butt 6th 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    50th Connector Module

    Butt 7th 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    60th Connector Module

    Butt 8th 100-Pair Cableand Secure

    Entire Cable Bundleto Wire Clip of

    70th Connector Module

    Figure9 848765-02CS.cdr

    Figure 28. Top View Z-IDC Bay Cabling Sequence for 100-Pair ILECMDF Tie Cables at Each Vertical Moreng Framework LT99519