+ All Categories
Home > Documents > 8690739 Basis Stator Earth Fault Protection

8690739 Basis Stator Earth Fault Protection

Date post: 09-Apr-2018
Category:
Upload: azhan77
View: 235 times
Download: 2 times
Share this document with a friend

of 18

Transcript
  • 8/8/2019 8690739 Basis Stator Earth Fault Protection

    1/18

    Basis Stator Earth Fault Protection

  • 8/8/2019 8690739 Basis Stator Earth Fault Protection

    2/18

    Effects of Arc Burning on Stator Core Laminations

  • 8/8/2019 8690739 Basis Stator Earth Fault Protection

    3/18

    Methods of Neutral-Point Connection (1)

    Isolated or high ohmic earthedAdvantage: Small fault currents

    Disadvantage: High transient overvoltage forintermittent earth faults

    (2.5 3.5 ) Uph-E

    Compensated or reactive earthedAdvantage: Small fault currents at the fault

    locationDisadvantage: Transient overvoltage (

  • 8/8/2019 8690739 Basis Stator Earth Fault Protection

    4/18

    Methods of Neutral-Point Connection (2)

    Low ohmic earthedAdvantage: Lower transient overvoltage,

    95 to 98% protective range ofSEF protection

    Disadvantage: Great damages to generators

    at longer fault duration

    Solidly (effective) earthedAdvantage: Low transient voltage, better

    measuring conditions for theprotection

    Disadvantage: Great damages to generators,Leakage zero sequence currents

    Application in industrial plants

    Application at low voltage generators

    G

    < 200 - 400 A

  • 8/8/2019 8690739 Basis Stator Earth Fault Protection

    5/18

    Voltages in Case of an Earth Fault

    M

    Voltage without earth fault

    UL3,E UL3,E = UL31

    UE = -UL1,E

    UL1,E = 0

    UL2,E = UL21

    Voltages at the point of an earth fault at phase L1

    ULx,E ... phase-earth-voltage

    no displacement voltage (UE = 0)

    UL,E voltage decreases in the faulty

    phase (min 0)

    UL,E voltage in the both healthy phases

    are increase (max phase-to-phase)

    UE

    displacement-voltage(can be measured at star point to earth)

    MUL1,E

    UL2,E

    L1

    L2

    L3

  • 8/8/2019 8690739 Basis Stator Earth Fault Protection

    6/18

    Currents in the Case of an Earth FaultModel:

    Equivalent voltage UE at the point of fault

    IE =3.IE/3 = 3

    .UE/ZE

    IE/3 ... earth fault current in one phase

    ZE ... earth impedance at one phase

    Vector diagram: earth fault in phase L1

    UL3,E

    UL2,E

    IE =3U0

    1

    jCE

    = 3U0.jCE

    =3 UEZE

    IC,2

    IE

    IC,3

    L1

    L2

    L3

    IC 3

    3U0 =3UE

    UE

    IE/3

    IE

    ZE

    L1

    L2

    L3

    ~ ~ ~

  • 8/8/2019 8690739 Basis Stator Earth Fault Protection

    7/18

    Correlation from Earth fault Location

    Displacement voltage UE (U0) and earth current IE (3I0) as a function of the faultlocation of an earth fault in the machine winding.

    IE= 3UEZE

    UE

    UL2,EUL1,E

    UL1,E

    UL2,E

    UE ZE

    UE

    At faults close to the star-point the displacement voltage and the earthcurrents become small

  • 8/8/2019 8690739 Basis Stator Earth Fault Protection

    8/18

    Generators Connected via an Unit Transformer

    generator is galvanic isolated

    under the assumption of an ideal transformer, the displacementvoltage caused by an earth fault, can only be measured at the generator

    GGG

  • 8/8/2019 8690739 Basis Stator Earth Fault Protection

    9/18

    Elimination of the Disturbance High Voltage Earth Fault

    Earthingtransformer

    TR =

    CLCG CTr

    CK

    UEO U

    N3

    (Limb transformation ratio)

    UGen

    3

    100

    3

    500

    3VV

    ( )R

    RPrim

    3

    2TR

    =UR

    Problem:grid earth faults cause disturbancesdue to the coupling capacitancebetween the two transformer windings

    Solution:attenuation by means ofa load resistor

    Note:At solidly earthed

    transformer the UE0 is

    appr. 80% of UN/3

    (Safety margin, if solidlyearthing is open)

  • 8/8/2019 8690739 Basis Stator Earth Fault Protection

    10/18

    Unit Connection - Influence on the Coupling Capacitance

    UR,prim Rprim

    CK

    UC

    UEO

    UR,prim R

    prim UEO1Rprim +j CK

    Example: CK = 10 nF UEO =220 kV

    3

    UR,prim

    =293V

    ==

    735

    3RR

    2

    TRPrim

    UN,G = 10.5 kV R = 5

    Tr = 36.4

    UR,sek 24V

    24V500V

    4.83% disturbanceinfluence

    CE.

    equivalent circuit disturbance voltage

    CG+CL+CTr neglected

    UEO displacement voltage on the high voltage side

    CK three phase coupling capacitance

    Rprim primary load resistor

    Tr earthing transformer ratio

  • 8/8/2019 8690739 Basis Stator Earth Fault Protection

    11/18

    Unit Connection with Neutral Transformer

    This design is very often used outside Germany, mostly on small generators

    GeneratorUnit transformer

    Rsek=Rprim

    2TRDesign of Rprim so that the fault current is < 10A

    R

    UR

    TR =

    UGen

    3 UR

    A high secondary nominal voltage UR (250V - 500V) is selected inorder to avoid very small load resistors.

  • 8/8/2019 8690739 Basis Stator Earth Fault Protection

    12/18

    Generator Connected Directly to the Grid

    machines are galvanic connected

    displacement voltage caused by an earth faultcan be measured in all locations

    G G G M

  • 8/8/2019 8690739 Basis Stator Earth Fault Protection

    13/18

    Directional Stator Earth Fault Protection

    CE

    L1 L2 L3

    L1

    L2

    L3

    IC + IR

    Ohmic currentboost

    IC

    IR

    ICL2

    ICL1

    3I0

    3U0

    UL1 UL2

    Network

    3i0 3u0

    DFT 3U0>, 3I0>

    Direction

    (3U

    0, 3I0)

    Earthingtransformer

  • 8/8/2019 8690739 Basis Stator Earth Fault Protection

    14/18

    Fault Currents - Direct Connection

    G1

    G2

    IMess

    IMess

  • 8/8/2019 8690739 Basis Stator Earth Fault Protection

    15/18

    Fault Currents - Direct Connection with Earthing Transformer

    G1

    G2

    IMeas

    IMeas

    Earthing transformer

    Ohmic current

    RB

  • 8/8/2019 8690739 Basis Stator Earth Fault Protection

    16/18

    Earth Current Detection - Toroidal and Holmgreen Connection

    Toroidal Current Transformer

    IE3

    per phase

    I E

    L1 L3L2

    IE

    I3 ~

    Holmgreen connection

    (separate cores)

    Holmgreenconnection

    (commonneutral returnconnector

    Sensitivity is

    limitedProblem:

    Large CT ratioleads to smallcurrents on thesecondary side

    IE3

    per phase

    L1

    L3L2

    I E

    (IE = 3

    I0)

    magnetic additionof earth currents,

    principle is sensitive

  • 8/8/2019 8690739 Basis Stator Earth Fault Protection

    17/18

    Directional Stator Earth Fault Protection - Characteristic

  • 8/8/2019 8690739 Basis Stator Earth Fault Protection

    18/18

    Directional Stator Earth Fault Protection - Logic


Recommended